Informationstag "Der Eisspeicher als Energiemanager"
16. März 2016
Vortrag: Ralf Mnich, PBS & Partner | Zentrale Eis-Energiespeicher in Verbindung mit kalten Nahwärmenetzen
Informationstag "Der Eisspeicher als Energiemanager"
16. März 2016
Vortrag: Ralf Mnich, PBS & Partner | Zentrale Eis-Energiespeicher in Verbindung mit kalten Nahwärmenetzen
This is a training module developed in the European project SESEC. More information and the full training can be found here: www.sesec-training.eu
The SESEC project is designed to address the energy efficiency needs of the EU clothing industry. The Consortium relies on outstanding competences of the partners, spread over 6 countries (Bulgaria, Romania, Portugal, Italy, Germany, Belgium) to provide the missing energy efficiency benchmarks and ready-to-use solutions for the large number of SMEs as well as larger companies. The SESEC project has 4 major objectives:
• To develop, test and offer an Energy Efficiency tool for clothing production, made up of guidelines and web-based applications, suitable for SMEs and large companies
• To transfer the project results to the sector, EURATEX members and interested companies
• To offer training and support to companies to implement energy-saving measures considering cost-effectiveness
• To improve opportunities for energy-efficiency for the whole European clothing industry
The Dominican Republic is interested to promote the utilization of Renewable Energy, on the other hand they are planning to invest into two new coal fired power plants, a clear contradiction. The rest of the world is on its way to decarbonization. The presentation shows technologies which are helping to reach 100%.
Die neue LUNOS Lüftergeneration e², jetzt mit Wärmerückgewinnung. Energieeffiziente Wohnungslüftung einfach in der Montage, leise und sparsam im Betrieb. Präsentation mit ausführlicher Beschreibung der Wohnungslüftung mit dem neuen Lüftungsgeräten e² - lieferbar ab März 2011.
This is a training module developed in the European project SESEC. More information and the full training can be found here: www.sesec-training.eu
The SESEC project is designed to address the energy efficiency needs of the EU clothing industry. The Consortium relies on outstanding competences of the partners, spread over 6 countries (Bulgaria, Romania, Portugal, Italy, Germany, Belgium) to provide the missing energy efficiency benchmarks and ready-to-use solutions for the large number of SMEs as well as larger companies. The SESEC project has 4 major objectives:
• To develop, test and offer an Energy Efficiency tool for clothing production, made up of guidelines and web-based applications, suitable for SMEs and large companies
• To transfer the project results to the sector, EURATEX members and interested companies
• To offer training and support to companies to implement energy-saving measures considering cost-effectiveness
• To improve opportunities for energy-efficiency for the whole European clothing industry
This is a training module developed in the European project SESEC. More information and the full training can be found here: www.sesec-training.eu
The SESEC project is designed to address the energy efficiency needs of the EU clothing industry. The Consortium relies on outstanding competences of the partners, spread over 6 countries (Bulgaria, Romania, Portugal, Italy, Germany, Belgium) to provide the missing energy efficiency benchmarks and ready-to-use solutions for the large number of SMEs as well as larger companies. The SESEC project has 4 major objectives:
• To develop, test and offer an Energy Efficiency tool for clothing production, made up of guidelines and web-based applications, suitable for SMEs and large companies
• To transfer the project results to the sector, EURATEX members and interested companies
• To offer training and support to companies to implement energy-saving measures considering cost-effectiveness
• To improve opportunities for energy-efficiency for the whole European clothing industry
Eigenverbrauchs-Energielösungen - ein Business Case für Investoren & die Umweltengineeringzhaw
In der Diskussion um den Klimawandel und erneuerbare Energien wird das Thema Eigenverbrauch immer wichtiger.
Eigenverbrauchsgemeinschaften sind Zusammenschlüsse von Stromerzeugern und -verbrauchern.
Veränderte gesetzliche Rahmenbedingungen sowie die erreichte Kostenreduktion bei Photovoltaikanlagen führen dazu, dass Eigenverbrauchsgemeinschaften wirtschaftlicher immer interessanter werden.
Beim Energie- und Umweltforum greifen wir dieses aktuelle Thema auf und informieren über Rahmenbedingungen, technische Lösungen und realisierte Projekte.
Präsentation von Rainer Stock (VKU) auf dem BID.workshop Energiepolitik für Parlamentsmitarbeiter am 22.01.2014 - weitere Infos unter: http://workshop-energiepolitik.bid.ag
The document discusses Samsung's memory technology and its advantages. Samsung's memory products combine the highest performance with the lowest power consumption, helping to save on infrastructure and maintenance costs compared to competitors' technologies. Their latest green memory solutions can reduce server power consumption by up to 29% and lower cooling costs through improved thermal efficiency.
Green IT BB Award 2012 - Deutsche Bank - 8 Punkte-Programm für eine umweltfre...Netzwerk GreenIT-BB
The document outlines an 8-point program for an environmentally friendly IT infrastructure at a bank. It discusses making the bank's IT climate neutral, an eco-supplier program and recycling. It also discusses commitments to server and desktop efficiency, printer efficiency, and electronics recycling. Key aspects include governance, efficiency requirements, standards, TCO modeling, and a global recycling metric. Success requires strong cross-divisional partnerships. Charts show data center energy efficiency improvements over time from facilities, infrastructure, servers, and overall improvements relative to goals.
GreenIT Best Practice Award 2011: Nominiert in der Kategorie III (Visionäre Gesamtkonzepte) - DURABILIT BV
Greener Network Calculator - Wie „GRÜN“ ist Ihre Lieferkette?
GreenIT Best Practice Award 2011: Nominiert in der Kategorie I (Energieeffiziente Systeme) - mib solutions Zeller Berlin GmbH & Co.KG
Intelligentes PC-Management „IQ-Energy®“
das Green-IT Werkzeug im Anwenderbereich
GreenIT Best Practice Award 2011: Nominiert in der Kategorie III (Visionäre Gesamtkonzepte) - Solardynamik GmbH
Feste und nachführbare Trägersysteme für Photovoltaikmodule und –folien, dynamische Ausrichtung nach der Sonnenposition über Sensoren, basiert auf gesteuerten, aufblasbaren Luftkammern aus polymerer Membrantechnologie
GreenIT Best Practice Award 2011: Nominiert in der Kategorie III (Visionäre Gesamtkonzepte) - AUDI AG
Energie sparende und innovative Kundenbegeisterung
mit dem Audi Multimedia System (AMMS)
1. GreenIT Best Practice Award 2012:
Nominierung in der Kategorie 1, Energieeffiziente Systeme
Energieoptimiertes Rechenzentrum mit
Grundwasserkühlung
2. Rechenzentrum der IGN GmbH München mit Grundwasserkühlung
Inbetriebnahme 04/2011
Rackstellfläche 380 m² für bis zu 230
Racks à 2,5 kW
PUE-Wert 1,2
600 kW Kühlleistung
Grundwasserkühlung 2N-redundant
Klimatechnik N+2-redundant
USV-Stromversorgung 2(N+1)-
redundant
3. Ausgangslage, Zielsetzung, Herausforderung
Ausgangslage
Verteilte IT-Systeme in mehreren kommerziellen RZ
Keine weiteren Kapazitäten verfügbar
Durchschnittliche PUE-Werte zwischen 2,0 und 2,5
Ziel
Konsolidierung mit Senkung von Energiekosten und Umweltbelastung um 50 Prozent
o durch Senkung des direkten Energieverbrauchs um 15 Prozent
o durch Senkung des indirekten Energieverbrauchs um Prozent
Nutzung von Grundwasser für die Kaltwasseraufbereitung
Erhöhung der Ausfallsicherheit
Herausforderung
RZ mit PUE-Wert besser als 1,4 erforderlich
Kein passendes kommerzielles RZ verfügbar
4. Vorbereitung
Standortsuche mit Hilfe eines
Geologenteams
Abstimmung mit dem Bauträger
Einholen der Zustimmung des Bauträgers
Weiterführende Gutachten
Erste Planungen für eine Brunnenanlage
5. Planung
Rittal als Generalunternehmer für Planung und Bauausführung des RZ
Antrag für Bau und Betrieb einer Brunnenanlage bei Stadt München
und Wasserwirtschaftsamt mit Bauträger und Grundstückseigentümer
Probebohrungen und Pumpversuche zur Ermittlung von Grundwasser-
Leistungsfähigkeit und -Qualität
Antrag für Entnahme von 90 m³/h Wasser und Temperaturdifferenz
Entnahme / Einleitung von 5° C
Abstimmung mit Bauträger über Gebäude-Anpassungen für energie-
optimierte RZ-Infrastruktur
6. Umsetzung Brunnenkühlung für RZ
Brunnen
Bau von zwei Saug- und zwei Schluckbrunnen
Primärer Kühlkreislauf
Grundwasser-Entnahme aus Saugbrunnen
Vorbeiführen an Wärmetauschern
Rückspeisung in Grundwasserstrom über Schluckbrunnen
Sekundärer Kühlkreislauf
Wasser als Kältemittel zur Versorgung der Klimasysteme
Klimageräte blasen gekühlte Luft in die Kaltgänge
Passive Warmluft-Rückführung über die Raumdecke
7. Umsetzung Klima-Lösung
Klimageräte mit elektronisch geregelten
Ventilatormotoren
Energieoptimaler Teillastbetrieb der Klimageräte
und Pumpen
Optimierte Kaltluftführung zur Reduktion des
Energiebedarfs für die Luftzirkulation:
o Klimaschränke an der Längsseite der Rackstellfläche
o Ventilatoren unter den Klimageräten ohne
Umlenkverluste
o Stromschienen und IP-Leitung in Strömungsrichtung
o 90-cm-Doppelboden mit hohem Auslass-Querschnitt
o Passive Warmluft-Rückführung über die Raumdecke
8. Aufwand & Kosten
Zweijährige Vorlaufphase
Aufwendiges Antrags- und Genehmigungsverfahren
Koordination sehr vieler Fachinstanzen erforderlich
Individuelle Planung erforderlich
Planerische Risiken
Standort-Abhängigkeit der Kosten (Brunnenbau)
Kosten ein Drittel höher als für kompressorgekühltes RZ
Folgekosten wie Brunnen-Wartung
Folgekosten für Untersuchungen von Temperatur und
Wärmefahne des rückgespeisten Wassers
9. Nutzen & Nachhaltigkeit
Kälteerzeugung fast ohne Stromverbrauch
PUE-Wert von 1,2 ab einer Auslastung von 60 Prozent
Nur ca. 20 Prozent des Energiebedarfes eines RZ mit PUE-Wert 2,0
Vermeidung von 2.500 Tonnen CO2 jährlich
Nutzungszeit der Brunnenanlage 30 bis 40 Jahre
Investitionskosten über Nutzungszeiten 50 Prozent geringer als Kaltwasser-Sätze
RZ-Betrieb unabhängig von fortschreitender Klimaerwärmung
Wasser als Kühlmittel im sekundären Kühlkreislauf
Keine Verunreinigung des entnommenen Grundwassers
Kein Verlust des entnommenen Grundwassers