Estimation of Re-striking Transient Overvoltages
 in a 3-Phase 132KV Gas insulated Substation
                                     M. Kondalu1, Dr. P.S. Subramanyam2
                      Electrical & Electronics Engineering, JNT University. Hyderabad.
                                          1
                                            Kondalu_m@yahoo.com
                                   Joginpally B.R. Engineering College, Hyderabad
                                           2
                                               subramanyamps@gmail.com
                                                VBIT, Ghatkesar,Hyderabad



Abstract: --This paper presents the most significant results of a         A GIS system comprising of an Input Cable, Spacer,
Very fast transient Overvoltages generated due to switching         Dis-connector Switch, Bus bar of 10mts length and load has
operations have been analyzed and presented. Since the contact      been considered for modelling into electrical network and
speed of dis-connector switches is low, re-striking occurs many     analysis [6]. The Fast Transient Over voltage waveform
times before the current interruption is completed .Each re-
striking generates transient overvoltage with level of magnitude.
                                                                    generated during Closing and Opening operation of Dis-
These transient have travelling wave behaviour, they travel to      connector Switch and 3-phase faults has been considered for
the external systems through enclosures, bushings, cable joints     calculations.
etc.. and cause damage to the outside equipment. They can lead               Spacers are simulated by lumped Capacitance. The
secondary break downs in GIS and may give rise to                   Inductance of the bus duct is calculated from the diameters of
electromagnetic interference. The Earth faults give rise to TEV     Conductor and Enclosure. Capacitances are calculated on the
which can interfere with the operation and control of secondary     basis of actual diameters of inner and outer cylinders of
equipment in a 3-phase 132kv GIS. Thus it is important to           central conductor and outer enclosure [7]. Cone Insulators
develop a suitable MATLAB7.8 models for estimation of these         used for supporting inner conductor against outer enclosure
overvoltages.                                                       are assumed to be disk type for approximate calculation of
Keywords—Gas Insulated Substation (GIS), very fast Transient
                                                                    spacer capacitance [8].
overvoltages, 3phase faults, MATLAB 7.8 software and Control
circuitry                                                                    The busduct can be modelled as a series of Pi-
                                                                    network or as sequence parameters. However in this model, it
                      I. INTRODUCTION                               is considered as distributed Pi-network. The Schematic
          For accurate analysis of transients, it is essential to   Diagram of a Typical Gas Insulated System (GIS) is shown in
find the VFTO‘s and circuit parameters. Due to the travelling       below figure 3.
nature of the transients the modelling of GIS makes use of
electrical equivalent circuits composed by lumped elements             Frequency nature, the VFTO imposed on the transformers
and especially by distributed parameter lines, surge                connected directly to the GIS would not be distributed evenly
impedances and travelling times. The simulation depends on          on all transformer windings. Some windings, e.g. the first few
the quality of the model of each individual GIS component [1].      turns connecting to the 132kV GIS, would be subject to a
In order to achieve reasonable results in GIS structures highly     higher magnitude of overvoltage, posing a potential risk of
accurate models for each internal equipment and also for            insulation breakdown of the transformers[9][10].
components connected to the GIS are necessary [2].
                                                                       II. MODELLING OF 132KV GAS INSULATED SUBSTATION:
         The dis-connector spark itself has to be taken into         During the current operation of dis-connector switch in a GIS,
account by transient resistance according to the Toepler‘s          re-strikes(pre-strikes) occur because of low speed of the dis-
equation and subsequent arc resistance of a few ohms [3][4].        connector switch moving contact, hence Very fast Transient
The wave shape of the over voltage surge due to dis-connector       Over voltage are developed. These VFTO‘s are caused by
switch is affected by all GIS elements. Accordingly, the            switching operations and 3-phase fault
simulation of transients in GIS assumes an establishment of                 When a dis-connector switch is opened on a floating
the models for the Bus, Bushing, Elbow, Transformers, Surge         section of switchgear, trapped charge may be left on the
Arresters, Breakers, Spacers, dis-connectors, and Enclosures        floating section. In the opening operation of dis-connector
and so on[5].                                                       switch, transients are produced and the magnitude of these




                                                                                                                                           22
                                          All Rights Reserved © 2012 IJARCET
ISSN: 2278 – 1323
                                                               International Journal of Advanced Research in Computer Engineering & Technology
                                                                                                                    Volume 1, Issue 4, June 2012


Transients and rise times depends on the circuits parameters.                 Breakdown and thus first re-strike occurs. Both
When there is a fault occurs, there is a short circuit in the        electrodes are there by electrically connected by conducting
system. Transients are also produced due to the faults in the        spark, whereby GIS section with initial voltage U2 is very
system. Due to this VFTO‘s are caused by switching operation         rapidly charged to instantaneous value of U1. The transient
can also lead to secondary breakdown with in GIS. Re-striking        current flowing through the spark then interrupts as soon as
surges generated by the dis-connector switches at GIS                the GIS have been charged to U1 and spark extinguishes.
generally possess extremely high frequencies ranging from
several hundred KHz to several MHz . For the development of                    The voltage U2 now remains constant with time,
equivalent circuit low voltage step response measurements of         while the voltage U1.on the side of supply keeps changing.
the main GIS components have been made. Using MATLAB                 This continues until the second re- strike occurs with an
7.8 of the equivalent models is developed.                           increased breakdown voltage UB as a consequence of larger
                                                                     separation. Hence U2 follows U1, until finally at the end of
                                                                     the switching process the gap no longer can be broken down.
During opening of Dis- connector switch (DS), transients are         Transients are also produced due to faults in the system. When
produced due to internal oscillations. The magnitude of              there is a fault, there will be short circuit in the system. Due to
transients and rise times depends on the circuit parameters like     this, oscillations occur due to presence of inductance and
inductance, Capacitance and connected Load. Assuming that            capacitance on both sides of the fault section causing
some trapped charge is left is left during operating operation;      transients.
transients can be calculated during closing operation of DS.                   Dis-connector Switch (DS) operation typically
                                                                     involves slow moving contacts which results in numerous
    Fast transient over voltages generated during Dis-               discharges during operation .For example, a floating section of
connector Switch operation are a sequence of voltage of              switchgear between a disconnect switch and an open breaker
voltage steps created by voltage collapse across the gas at re-      (load side may be disconnected from an energized Gas
striking specific over voltage shape is formed by multiple           insulated system (supply side).
reflections and refractions. Operation of Dis-connector Switch             For capacitive currents below—1 amp, are-strike occurs
(DS) can be shown by using the fig 1                                 every time the voltage between the connects exceeds the
                                                                     dielectric strength of the gaseous medium between them.
                                                                       Each re-strike generates a spark, which equalizes the
Where            L1 = Inductance of Source                           potentials between the switch contacts. Following spark
                   C1 = Capacitance of Source                        extinction, the supply and load side potentials will deviate
                   C2 = Capacitance of GIS Open part                 according to the AC supply voltage variation and the
                   U1 = Power Frequency Voltage                      discharge characteristics of the load side respectively. Another
                   U2 = Power GIS Voltage                            spark will result when the voltage across the electrode gap
                                                                     dependent breakdown voltage UB and the potential difference
 The more frequent service situation of the isolator is its use to   of the load and supply side U.
connect or dis-connect unloaded parts of the installation as is            Each Dis-connector Switch (DS) operation generates a
shown in fig 1 for example apart of the of the GIS is dis-           large number of ignitions between the moving contacts. The
connected by an isolator from an overhead supply line. Where         number of ignitions depends on the speed of the contacts. The
by the self-capacitance C2 of this part of circuit can be up to      largest and steepest surge voltages are generated only by those
several nF, depending on its length. First re-strike across the      breakdowns at the largest contact gap. Therefore, only by
gap occurs when voltage across the gap exceeds the                   those breakdowns (10-50) need be considered for dielectric
breakdown voltage. The occurrence of re-strikes is described         purpose.
with the following Fig 2
                                                                     A. Calculation of variable arc resistance
The voltage across the gap is the difference between U1 and             The Variable arc resistance is calculated using the
U2, if it is assumed that the breakdown voltage UB of the gap        formula:
increases with increasing separation and therefore with time as                                            𝐾 𝑇 ×𝑙
shown in fig 2.Then the curve U2 can be constructed as
                                                                                                𝑅=          𝑡
                                                                                                      𝑞 0 + 0 𝑖 𝑡 𝑑𝑡
follows. At the instant of mechanical contact separation, U1            Where,
and U2 have the same value, the voltage U2 continues to
                                                                          𝐾 𝑇 = Toepler‘s constant
retain this value, while U1 changes with power frequency, the
                                                                         = 0.005 volt.sec/mt for SF6 under uniform field
voltage (U2-U1)
                                                                         conditions
                                                                         L = spark length in meters
         Across the gap of the isolator also changes. As soon
as, (U2-U1) exceeds the dielectric strength UB of the gap, a              𝑞0 = Initial charge or charge at the instant of breakdown
                                                                         T = spark collapse time in sec.




                                                                                                                                            23
                                                All Rights Reserved © 2012 IJARCET
ISSN: 2278 – 1323
                                     International Journal of Advanced Research in Computer Engineering & Technology
                                                                                          Volume 1, Issue 4, June 2012




                 Fig. 1 Electric Circuit for explaining re-strikes




            Fig 2 Voltage of the open –ended GIS side of the Isolator




         Fig. 3 Schematic diagram of a typical Gas Insulated Substation




Fig. 4. 132kv GIS MATLAB implemented circuit when CB in Re-Striking Condition




                                                                                                                  24
                     All Rights Reserved © 2012 IJARCET
ISSN: 2278 – 1323
                                                          International Journal of Advanced Research in Computer Engineering & Technology
                                                                                                               Volume 1, Issue 4, June 2012


   The value of time varying spark resistance R(t) is                                               TABLE I
calculated until it reaches a value of 1 to 3 ohms. The
                                                                     TRANSIENT DUE TO VARIATION OF RE-STRIKE               VOLTAGE ON
integral in the denominator sums up the absolute value of
                                                                                                 LODE SIDE
current ‗i‘ through the resistance R(t) over the time
beginning at breakdown inception. Thus, it corresponds to              S.no          Load side             Magnitude of           Rise Time
the charge conducted through the spark channel up to                                  Voltage             the voltage (p.u)        (Nanos)
time‗t‘.                                                                               (p.u)
          The busduct can be modelled as a series of Pi-                  1             -1.0                     2.45                  10
network or as sequence parameters. However in this model,                 2             -0.9                     2.39                  13
it is considered as distributed Pi-network. The Schematic                 3             -0.8                     2.19                  12
Diagram of a Typical Gas Insulated System (GIS) is                        4             -0.7                     2.15                  10
shown in below figure 3.                                                  5             -0.6                     2.03                  12
   Assuming that some trapped charge is left on the                       6             -0.5                     1.96                  11
floating section of switchgear during opening operation of                7             -0.4                     1.82                  10
dis-connector switch, a voltage of certain value is                       8             -0.3                     1.77                  13
considered during MATLAB                                                  9             -0.2                     1.53                  12
   The apparatus as disconnected with an earthing switch,                10             -0.1                     1.45                   9
three disc type Spencer‘s , a load bus bar above to 10mts
long width three post type spacers and a 132kv gas
bushing containing stress capacitor.
                                                                                                    TABLE II
    .
                                                                      TRANSIENTS DUE TO VARIATION OF        RE-STRIKE VOLTAGE
                                                                                              ON SOURCE SIDE
III. 3-PHASE   EQUIVALENT CIRCUIT FOR 132KV GIS SYSTEM
                      FOR 10MTS LENGTH
                                                                       S.no        Source side             Magnitude of           Rise Time
                                                                                   Voltage (p.u)          the voltage (p.u)        (nanos)
                                                                          1             1.0                     2.43                   9
          The bus duct is dividing into three sections of                 2             0.9                     2.37                  10
length 1mts, 4mts, and 5mts from load side. The GIS
                                                                          3             0.8                     2.17                  11
bushing is represented by a capacitance of 125pf. The
                                                                          4             0.7                     2.11                  10
resistance of 1 ohm spark channel is connected in series
with circuit breaker. MATLAB Circuit for 10 mts. length                   5             0.6                     2.01                   9
in a 3-phase 132kv GIS shown in the fig. 4.                               6             0.5                     1.91                  10
   Due to trapped charge some voltage remains on the                      7             0.4                     1.79                   9
floating section which can create severe conditions                       8             0.3                     1.71                  12
because the first re-strike can occur at the peak of power                9             0.2                     1.42                  11
frequency voltage giving a voltage of 2.0 p.u. On re-strike              10             0.1                     1.39                   9
the voltage on each side will collapse initially zero and
hence creating two 1.0pu voltage steps of opposite
polarities. In this, it is assumed that re-striking is created at                    IV. RESULTS AND DISCUSSION
1.0 p.u. respectively on either side of dis-connector switch
(DS). The transients due to closing of the circuit breaker                 The phenomenon that occurs during the DS closing
are calculated and maximum voltage obtained with a rise             into a capacitive load is very nearly the reserve of
time.                                                               processes that occur during its opening. Here, the first
    This method implemented on MATLAB 7.8. the                      restrike occurs due to the residual voltage left behind by a
voltage before and after circuit breaker is taken to be 1.0         previous opening on the load side. Circuit breaker or load
pu and -1.0pu as the most enormous condition but                    break switch closing or openings also generate VFTO in
depending on the time of closing of circuit breaker the             the case of re-strikes but the number of such VFTO is
magnitude of the voltage on the load side changes.                  much lower than those generated by DS operation. The
                                                                    various transient voltage and current at different positions
      For different values of voltages on the load side the
                                                                    in a 3 phase 132kv GIS for the first switching operation
magnitudes and rise time of the voltage wave are
                                                                    presented in results.
calculated keeping source side voltages as constant as
                                                                          Assumed that there is a second re-strike another
1.0p.u the values are tabulated in table I.
                                                                    switch is connected in parallel to the circuit breaker for
   Similarly by changing the magnitudes of the voltage on           simulation in MATLAB modeling. Transients are
the source side, keeping voltage on load side constant at           calculated by closing this switch when voltage difference
1.0p.u. Then the transient due to variation of voltage on           across the contacts of the circuit breaker reaches maximum
source side obtained. The values are tabulated in Table II.         value.


                                                                                                                                       25
                                              All Rights Reserved © 2012 IJARCET
ISSN: 2278 – 1323
                                                    International Journal of Advanced Research in Computer Engineering & Technology
                                                                                                         Volume 1, Issue 4, June 2012


    During Re-strike operation (source & Load) the voltage       To introduce the current chopping, the circuit breaker is
through the resistance of the circuit breaker is shown in     opened remains. Hence to calculate transients due to
fig.5 and fig.6. From the graph it was found the maximum      opening operation the CB is opened at 12ns. The transients
current is 25A at a rise time of 13ns.                        are obtained and show in fig.7.
                                                                 The transient calculated due to re-strike gives the peak
                                                              voltage of 2.45p.u at a rise time of 112ns show in fig.8.




 Fig. 5 Transient voltage waveform during Re-strike for
     10mts from source side in a 3-phase 132kv GIS


                                                               Fig.8 Current waveform during Re-strike for 10mts from
                                                                          Load side in a 3-phase 132kv GIS

                                                                                             TABLE III
                                                                  THE ANALYSIS VALUES ARE TABULATED AS FOLLOWS:

                                                                         Mode of               Magnitude of            Rise time
                                                                        operation              voltage(p.u)           (Nano sec)
                                                                      During closing
                                                                                                    2.46                    69
                                                                        operation
                                                                     During opening
                                                                                                    1.22                    56
   Fig 6Transient voltage waveform during Re-strike for                operation
      10mts from Load side in a 3-phase 132kv GIS                     During second
                                                                                                    2.45                   112
                                                                        re-strike



                                                                                   V. CONCLUSION
                                                                       A model is Developed for the prediction of the
                                                              VFTO phenomena in the circuit of voltage and current
                                                              transformers in GIS. The main advantage of such model is
                                                              to enable the transient analysis of GIS.A spark collapse
                                                              time was correctly simulated by the variable resistor. By
                                                              this spark collapse time, resistance of the VFTO is
                                                              extended, and the component caused by short surge
                                                              impedance discontinuities such as spacers, dis-connectors
                                                              and short bus branches were damped.

                                                                      A GIS system comprising of spacers, bus bar and
                                                              dis-connectors has been considered for modelling into
Fig 7 Current waveform during Re-strike for 10mts from        electric network. The inductance of the bus bar is
           source side in a 3-phase 132kv GIS                 calculated from diameters of conductors and enclosure

                                                                                                                                 26
                                         All Rights Reserved © 2012 IJARCET
ISSN: 2278 – 1323
                                                             International Journal of Advanced Research in Computer Engineering & Technology
                                                                                                                  Volume 1, Issue 4, June 2012


using standard formulae. Cone insulators used for
supporting inner conductor against outer enclosure are
assumed to be disk type for approximate calculation of
spacer capacitance is calculated using formulae for
concentric cylinders. The entire bus length is modelled as
distributed pi-network. The peak magnitude of fast
transient currents generated during switching event
changes from one position to another in a 132kv GIS for a
particular switching operation. These transients over
voltages are reduced by connecting suitable resistor in an
equivalent circuit during closing and opening operation.


                         VI. REFERENCES

[1]     S.Ogawa, E. Haginomori, S. Nishiwaki, T.Yoshida,
        K. Terasaka,―Estimation of Re-striking Transient Over Voltage
       on Disconnecting Switch for GIS”, IEEE Trans. on PS, Vol.
       PWRD-1, No-2, April 1986, pp.95-101
[2] Li Liu-ling, Hu Pan-feng, Qiu Yu-chang, Analysis of
       Very Fast Transient Overvoltage Calculation Affected
       by Different Transformer Winding Models, Journal
       of Xi‘an Jiaotong University, 2005(10) Vol.39
       No.10:1160-1164.
[3] Yang Linghui, Zhang Jiamin, Research on transient
       Overvoltage during operation of 500kV GIS
       Disconnecting switch, East China Electric Power, Jan.2004,
       Vol.32 No.1:37-41
[4] Shibuya Y, Fujita S, Shimomura T. Effects of very
       fast transient over-    Voltages on Transformer [J].IEE
       Proceedings, Part C,1999,146(4): 459-464.
 [5] H. Hiesinger, RWitzmann. Very fast Transient
       Breakdown at a needle Shaped Protrusion, IX Int.
      Conf. on Gas Dis. and Their Applied. Sep 1988.
 [6] MohanaRao M., Naidu M.S. (199% 'Estimation of
      Fast Transient      Overvoltages in the case of
      Disconnnector operation in a GIS', 3d workshop & conference
      on EHV Technology, IISC Bangalore.
[7] J.B. Kim,M.S. Kim,K.S.Park, W.P.Son.,.D.S. Kim,
       G.S. Kil. Development of monitoring and diagnostic
       System for SF6 gas insulated switchgear.
       IEEE Conference Record of the 2002 IEEE
      International Symposium on Electrical Insulation.
      Boston, Massachusetts, UnitedStates, pp.453-456, 2002.
[8] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam,‖
      Estimation Transientover voltages in gas insulated bus
     duct from 220kv gas       insulated substation‖,
     International journal of Computer
     Applications, (0975-8887) volume 20-no.8 April 2011.
[9] M.kondalu, G.Sreekanthreddy,Dr. P.S. subramanyam,‖
     Analysis and Calculation of very fast transient over
     Voltages in 220kv gas insulated substation international
      Journal of Engineering& techscience vol 2(4)      2011
[10] D. Povh, H. Schmitt, O. Volcker, R. Witzmann,
    ―Modelling and Analysis Guidelines for Very Fast
       Transients‖. IEEE Trans. on PD, Vol.11 No.4,
       October 1996, pp.2028-2035.




                                                                                                                                          27
                                                 All Rights Reserved © 2012 IJARCET

Weitere ähnliche Inhalte

Was ist angesagt?

Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationseSAT Publishing House
 
Darkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEDarkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEAbdallah Darkawi
 
New bhgat ram ppt 7793005660
New bhgat ram ppt 7793005660New bhgat ram ppt 7793005660
New bhgat ram ppt 7793005660bhagat ram meena
 
Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...
Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...
Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...Associate Professor in VSB Coimbatore
 
Topic 3 Bioelectrodes-sensors-transducers
Topic 3 Bioelectrodes-sensors-transducersTopic 3 Bioelectrodes-sensors-transducers
Topic 3 Bioelectrodes-sensors-transducersGhansyam Rathod
 
Analysis and Design of CMOS Source Followers and Super Source Follower
Analysis and Design of CMOS Source Followers and Super Source FollowerAnalysis and Design of CMOS Source Followers and Super Source Follower
Analysis and Design of CMOS Source Followers and Super Source FollowerIDES Editor
 
Dq31551563
Dq31551563Dq31551563
Dq31551563IJMER
 
International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)ijceronline
 
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET Journal
 
Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...
Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...
Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...IJERA Editor
 
A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...
A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...
A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...JAYAPRAKASH JPINFOTECH
 
PROJECT REPORT ON WIRELESS POWER TRANSMISSION
PROJECT REPORT ON WIRELESS POWER TRANSMISSIONPROJECT REPORT ON WIRELESS POWER TRANSMISSION
PROJECT REPORT ON WIRELESS POWER TRANSMISSIONVipul Jangir
 
Concept of energy transmission & distribution
Concept of energy transmission & distribution Concept of energy transmission & distribution
Concept of energy transmission & distribution ZunAib Ali
 

Was ist angesagt? (19)

C231924
C231924C231924
C231924
 
R01043105113
R01043105113R01043105113
R01043105113
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
Darkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEDarkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEE
 
New bhgat ram ppt 7793005660
New bhgat ram ppt 7793005660New bhgat ram ppt 7793005660
New bhgat ram ppt 7793005660
 
Bidirectional Resonant DC-DC converter for Microgrid Applications
Bidirectional Resonant DC-DC converter for Microgrid ApplicationsBidirectional Resonant DC-DC converter for Microgrid Applications
Bidirectional Resonant DC-DC converter for Microgrid Applications
 
Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...
Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...
Improved Power Gating Techniques for Reduction of Noise and Leakage Power in ...
 
Topic 3 Bioelectrodes-sensors-transducers
Topic 3 Bioelectrodes-sensors-transducersTopic 3 Bioelectrodes-sensors-transducers
Topic 3 Bioelectrodes-sensors-transducers
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Analysis and Design of CMOS Source Followers and Super Source Follower
Analysis and Design of CMOS Source Followers and Super Source FollowerAnalysis and Design of CMOS Source Followers and Super Source Follower
Analysis and Design of CMOS Source Followers and Super Source Follower
 
Dq31551563
Dq31551563Dq31551563
Dq31551563
 
International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
 
Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...
Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...
Phase locked loop control of 50-150 KHz Half Bridge Resonant type Inverter fo...
 
A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...
A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...
A High-Speed and Power-Efficient Voltage Level Shifter for Dual-Supply Applic...
 
PROJECT REPORT ON WIRELESS POWER TRANSMISSION
PROJECT REPORT ON WIRELESS POWER TRANSMISSIONPROJECT REPORT ON WIRELESS POWER TRANSMISSION
PROJECT REPORT ON WIRELESS POWER TRANSMISSION
 
3.corrected 3 phase 39-47
3.corrected 3 phase   39-473.corrected 3 phase   39-47
3.corrected 3 phase 39-47
 
Concept of energy transmission & distribution
Concept of energy transmission & distribution Concept of energy transmission & distribution
Concept of energy transmission & distribution
 

Andere mochten auch (9)

18 23
18 2318 23
18 23
 
134 138
134 138134 138
134 138
 
331 340
331 340331 340
331 340
 
172 179
172 179172 179
172 179
 
213 221
213 221213 221
213 221
 
158 162
158 162158 162
158 162
 
51 59
51 5951 59
51 59
 
106 110
106 110106 110
106 110
 
699 703
699 703699 703
699 703
 

Ähnlich wie Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV GIS

Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationIRJET Journal
 
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...ijceronline
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationseSAT Journals
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Projectsagnikchoudhury
 
Introduction gadgets have gained a lot of attention.pdf
Introduction gadgets have gained a lot of attention.pdfIntroduction gadgets have gained a lot of attention.pdf
Introduction gadgets have gained a lot of attention.pdfbkbk37
 
Reliability improvement of micro inverter through ac-ripples voltage compensator
Reliability improvement of micro inverter through ac-ripples voltage compensatorReliability improvement of micro inverter through ac-ripples voltage compensator
Reliability improvement of micro inverter through ac-ripples voltage compensatorhunypink
 
ECE 6030 Device Electronics.docx
ECE 6030 Device Electronics.docxECE 6030 Device Electronics.docx
ECE 6030 Device Electronics.docxwrite31
 
Kumaresh_ISLANDING.pptx
Kumaresh_ISLANDING.pptxKumaresh_ISLANDING.pptx
Kumaresh_ISLANDING.pptxRishikabhakat
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
Accurate leakage current models for MOSFET nanoscale devices
Accurate leakage current models for MOSFET nanoscale devices Accurate leakage current models for MOSFET nanoscale devices
Accurate leakage current models for MOSFET nanoscale devices IJECEIAES
 
Wireless Power Transfer Project
Wireless Power Transfer  ProjectWireless Power Transfer  Project
Wireless Power Transfer Projectsagnikchoudhury
 
final year project report
final year project reportfinal year project report
final year project reportAnuj Kumar
 
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution SystemsIRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution SystemsIRJET Journal
 
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution SystemsIRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution SystemsIRJET Journal
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...ecij
 
Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...
Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...
Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...IJSRD
 
Design and Implementation of EMI Filter for DC-DC Power Converter
Design and Implementation of EMI Filter for DC-DC Power ConverterDesign and Implementation of EMI Filter for DC-DC Power Converter
Design and Implementation of EMI Filter for DC-DC Power ConverterIRJET Journal
 

Ähnlich wie Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV GIS (20)

Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
 
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Project
 
Introduction gadgets have gained a lot of attention.pdf
Introduction gadgets have gained a lot of attention.pdfIntroduction gadgets have gained a lot of attention.pdf
Introduction gadgets have gained a lot of attention.pdf
 
Reliability improvement of micro inverter through ac-ripples voltage compensator
Reliability improvement of micro inverter through ac-ripples voltage compensatorReliability improvement of micro inverter through ac-ripples voltage compensator
Reliability improvement of micro inverter through ac-ripples voltage compensator
 
Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...
Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...
Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...
 
ECE 6030 Device Electronics.docx
ECE 6030 Device Electronics.docxECE 6030 Device Electronics.docx
ECE 6030 Device Electronics.docx
 
Kumaresh_ISLANDING.pptx
Kumaresh_ISLANDING.pptxKumaresh_ISLANDING.pptx
Kumaresh_ISLANDING.pptx
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
Accurate leakage current models for MOSFET nanoscale devices
Accurate leakage current models for MOSFET nanoscale devices Accurate leakage current models for MOSFET nanoscale devices
Accurate leakage current models for MOSFET nanoscale devices
 
Wireless Power Transfer Project
Wireless Power Transfer  ProjectWireless Power Transfer  Project
Wireless Power Transfer Project
 
final year project report
final year project reportfinal year project report
final year project report
 
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution SystemsIRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
 
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution SystemsIRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
IRJET- ARC Fault and Flash Signal Analysis in DC Distribution Systems
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
 
3.3V DC output at -16dBm sensitivity and 77% PCE rectifier for RF energy harv...
3.3V DC output at -16dBm sensitivity and 77% PCE rectifier for RF energy harv...3.3V DC output at -16dBm sensitivity and 77% PCE rectifier for RF energy harv...
3.3V DC output at -16dBm sensitivity and 77% PCE rectifier for RF energy harv...
 
Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...
Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...
Power Dissipation of VLSI Circuits and Modern Techniques of Designing Low Pow...
 
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEMISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
 
Design and Implementation of EMI Filter for DC-DC Power Converter
Design and Implementation of EMI Filter for DC-DC Power ConverterDesign and Implementation of EMI Filter for DC-DC Power Converter
Design and Implementation of EMI Filter for DC-DC Power Converter
 

Mehr von Editor IJARCET

Electrically small antennas: The art of miniaturization
Electrically small antennas: The art of miniaturizationElectrically small antennas: The art of miniaturization
Electrically small antennas: The art of miniaturizationEditor IJARCET
 
Volume 2-issue-6-2205-2207
Volume 2-issue-6-2205-2207Volume 2-issue-6-2205-2207
Volume 2-issue-6-2205-2207Editor IJARCET
 
Volume 2-issue-6-2195-2199
Volume 2-issue-6-2195-2199Volume 2-issue-6-2195-2199
Volume 2-issue-6-2195-2199Editor IJARCET
 
Volume 2-issue-6-2200-2204
Volume 2-issue-6-2200-2204Volume 2-issue-6-2200-2204
Volume 2-issue-6-2200-2204Editor IJARCET
 
Volume 2-issue-6-2190-2194
Volume 2-issue-6-2190-2194Volume 2-issue-6-2190-2194
Volume 2-issue-6-2190-2194Editor IJARCET
 
Volume 2-issue-6-2186-2189
Volume 2-issue-6-2186-2189Volume 2-issue-6-2186-2189
Volume 2-issue-6-2186-2189Editor IJARCET
 
Volume 2-issue-6-2177-2185
Volume 2-issue-6-2177-2185Volume 2-issue-6-2177-2185
Volume 2-issue-6-2177-2185Editor IJARCET
 
Volume 2-issue-6-2173-2176
Volume 2-issue-6-2173-2176Volume 2-issue-6-2173-2176
Volume 2-issue-6-2173-2176Editor IJARCET
 
Volume 2-issue-6-2165-2172
Volume 2-issue-6-2165-2172Volume 2-issue-6-2165-2172
Volume 2-issue-6-2165-2172Editor IJARCET
 
Volume 2-issue-6-2159-2164
Volume 2-issue-6-2159-2164Volume 2-issue-6-2159-2164
Volume 2-issue-6-2159-2164Editor IJARCET
 
Volume 2-issue-6-2155-2158
Volume 2-issue-6-2155-2158Volume 2-issue-6-2155-2158
Volume 2-issue-6-2155-2158Editor IJARCET
 
Volume 2-issue-6-2148-2154
Volume 2-issue-6-2148-2154Volume 2-issue-6-2148-2154
Volume 2-issue-6-2148-2154Editor IJARCET
 
Volume 2-issue-6-2143-2147
Volume 2-issue-6-2143-2147Volume 2-issue-6-2143-2147
Volume 2-issue-6-2143-2147Editor IJARCET
 
Volume 2-issue-6-2119-2124
Volume 2-issue-6-2119-2124Volume 2-issue-6-2119-2124
Volume 2-issue-6-2119-2124Editor IJARCET
 
Volume 2-issue-6-2139-2142
Volume 2-issue-6-2139-2142Volume 2-issue-6-2139-2142
Volume 2-issue-6-2139-2142Editor IJARCET
 
Volume 2-issue-6-2130-2138
Volume 2-issue-6-2130-2138Volume 2-issue-6-2130-2138
Volume 2-issue-6-2130-2138Editor IJARCET
 
Volume 2-issue-6-2125-2129
Volume 2-issue-6-2125-2129Volume 2-issue-6-2125-2129
Volume 2-issue-6-2125-2129Editor IJARCET
 
Volume 2-issue-6-2114-2118
Volume 2-issue-6-2114-2118Volume 2-issue-6-2114-2118
Volume 2-issue-6-2114-2118Editor IJARCET
 
Volume 2-issue-6-2108-2113
Volume 2-issue-6-2108-2113Volume 2-issue-6-2108-2113
Volume 2-issue-6-2108-2113Editor IJARCET
 
Volume 2-issue-6-2102-2107
Volume 2-issue-6-2102-2107Volume 2-issue-6-2102-2107
Volume 2-issue-6-2102-2107Editor IJARCET
 

Mehr von Editor IJARCET (20)

Electrically small antennas: The art of miniaturization
Electrically small antennas: The art of miniaturizationElectrically small antennas: The art of miniaturization
Electrically small antennas: The art of miniaturization
 
Volume 2-issue-6-2205-2207
Volume 2-issue-6-2205-2207Volume 2-issue-6-2205-2207
Volume 2-issue-6-2205-2207
 
Volume 2-issue-6-2195-2199
Volume 2-issue-6-2195-2199Volume 2-issue-6-2195-2199
Volume 2-issue-6-2195-2199
 
Volume 2-issue-6-2200-2204
Volume 2-issue-6-2200-2204Volume 2-issue-6-2200-2204
Volume 2-issue-6-2200-2204
 
Volume 2-issue-6-2190-2194
Volume 2-issue-6-2190-2194Volume 2-issue-6-2190-2194
Volume 2-issue-6-2190-2194
 
Volume 2-issue-6-2186-2189
Volume 2-issue-6-2186-2189Volume 2-issue-6-2186-2189
Volume 2-issue-6-2186-2189
 
Volume 2-issue-6-2177-2185
Volume 2-issue-6-2177-2185Volume 2-issue-6-2177-2185
Volume 2-issue-6-2177-2185
 
Volume 2-issue-6-2173-2176
Volume 2-issue-6-2173-2176Volume 2-issue-6-2173-2176
Volume 2-issue-6-2173-2176
 
Volume 2-issue-6-2165-2172
Volume 2-issue-6-2165-2172Volume 2-issue-6-2165-2172
Volume 2-issue-6-2165-2172
 
Volume 2-issue-6-2159-2164
Volume 2-issue-6-2159-2164Volume 2-issue-6-2159-2164
Volume 2-issue-6-2159-2164
 
Volume 2-issue-6-2155-2158
Volume 2-issue-6-2155-2158Volume 2-issue-6-2155-2158
Volume 2-issue-6-2155-2158
 
Volume 2-issue-6-2148-2154
Volume 2-issue-6-2148-2154Volume 2-issue-6-2148-2154
Volume 2-issue-6-2148-2154
 
Volume 2-issue-6-2143-2147
Volume 2-issue-6-2143-2147Volume 2-issue-6-2143-2147
Volume 2-issue-6-2143-2147
 
Volume 2-issue-6-2119-2124
Volume 2-issue-6-2119-2124Volume 2-issue-6-2119-2124
Volume 2-issue-6-2119-2124
 
Volume 2-issue-6-2139-2142
Volume 2-issue-6-2139-2142Volume 2-issue-6-2139-2142
Volume 2-issue-6-2139-2142
 
Volume 2-issue-6-2130-2138
Volume 2-issue-6-2130-2138Volume 2-issue-6-2130-2138
Volume 2-issue-6-2130-2138
 
Volume 2-issue-6-2125-2129
Volume 2-issue-6-2125-2129Volume 2-issue-6-2125-2129
Volume 2-issue-6-2125-2129
 
Volume 2-issue-6-2114-2118
Volume 2-issue-6-2114-2118Volume 2-issue-6-2114-2118
Volume 2-issue-6-2114-2118
 
Volume 2-issue-6-2108-2113
Volume 2-issue-6-2108-2113Volume 2-issue-6-2108-2113
Volume 2-issue-6-2108-2113
 
Volume 2-issue-6-2102-2107
Volume 2-issue-6-2102-2107Volume 2-issue-6-2102-2107
Volume 2-issue-6-2102-2107
 

Kürzlich hochgeladen

New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfSeasiaInfotech2
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage CostLeverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage CostZilliz
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
SAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxSAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxNavinnSomaal
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsMemoori
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Enterprise Knowledge
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsMiki Katsuragi
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Scott Keck-Warren
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Manik S Magar
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesZilliz
 
My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024The Digital Insurer
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr LapshynFwdays
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 

Kürzlich hochgeladen (20)

New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdf
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage CostLeverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
Leverage Zilliz Serverless - Up to 50X Saving for Your Vector Storage Cost
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
SAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxSAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptx
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial Buildings
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering Tips
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector Databases
 
My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV GIS

  • 1. ISSN: 2278 – 1323 International Journal of Advanced Research in Computer Engineering & Technology Volume 1, Issue 4, June 2012 Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com Joginpally B.R. Engineering College, Hyderabad 2 subramanyamps@gmail.com VBIT, Ghatkesar,Hyderabad Abstract: --This paper presents the most significant results of a A GIS system comprising of an Input Cable, Spacer, Very fast transient Overvoltages generated due to switching Dis-connector Switch, Bus bar of 10mts length and load has operations have been analyzed and presented. Since the contact been considered for modelling into electrical network and speed of dis-connector switches is low, re-striking occurs many analysis [6]. The Fast Transient Over voltage waveform times before the current interruption is completed .Each re- striking generates transient overvoltage with level of magnitude. generated during Closing and Opening operation of Dis- These transient have travelling wave behaviour, they travel to connector Switch and 3-phase faults has been considered for the external systems through enclosures, bushings, cable joints calculations. etc.. and cause damage to the outside equipment. They can lead Spacers are simulated by lumped Capacitance. The secondary break downs in GIS and may give rise to Inductance of the bus duct is calculated from the diameters of electromagnetic interference. The Earth faults give rise to TEV Conductor and Enclosure. Capacitances are calculated on the which can interfere with the operation and control of secondary basis of actual diameters of inner and outer cylinders of equipment in a 3-phase 132kv GIS. Thus it is important to central conductor and outer enclosure [7]. Cone Insulators develop a suitable MATLAB7.8 models for estimation of these used for supporting inner conductor against outer enclosure overvoltages. are assumed to be disk type for approximate calculation of Keywords—Gas Insulated Substation (GIS), very fast Transient spacer capacitance [8]. overvoltages, 3phase faults, MATLAB 7.8 software and Control circuitry The busduct can be modelled as a series of Pi- network or as sequence parameters. However in this model, it I. INTRODUCTION is considered as distributed Pi-network. The Schematic For accurate analysis of transients, it is essential to Diagram of a Typical Gas Insulated System (GIS) is shown in find the VFTO‘s and circuit parameters. Due to the travelling below figure 3. nature of the transients the modelling of GIS makes use of electrical equivalent circuits composed by lumped elements Frequency nature, the VFTO imposed on the transformers and especially by distributed parameter lines, surge connected directly to the GIS would not be distributed evenly impedances and travelling times. The simulation depends on on all transformer windings. Some windings, e.g. the first few the quality of the model of each individual GIS component [1]. turns connecting to the 132kV GIS, would be subject to a In order to achieve reasonable results in GIS structures highly higher magnitude of overvoltage, posing a potential risk of accurate models for each internal equipment and also for insulation breakdown of the transformers[9][10]. components connected to the GIS are necessary [2]. II. MODELLING OF 132KV GAS INSULATED SUBSTATION: The dis-connector spark itself has to be taken into During the current operation of dis-connector switch in a GIS, account by transient resistance according to the Toepler‘s re-strikes(pre-strikes) occur because of low speed of the dis- equation and subsequent arc resistance of a few ohms [3][4]. connector switch moving contact, hence Very fast Transient The wave shape of the over voltage surge due to dis-connector Over voltage are developed. These VFTO‘s are caused by switch is affected by all GIS elements. Accordingly, the switching operations and 3-phase fault simulation of transients in GIS assumes an establishment of When a dis-connector switch is opened on a floating the models for the Bus, Bushing, Elbow, Transformers, Surge section of switchgear, trapped charge may be left on the Arresters, Breakers, Spacers, dis-connectors, and Enclosures floating section. In the opening operation of dis-connector and so on[5]. switch, transients are produced and the magnitude of these 22 All Rights Reserved © 2012 IJARCET
  • 2. ISSN: 2278 – 1323 International Journal of Advanced Research in Computer Engineering & Technology Volume 1, Issue 4, June 2012 Transients and rise times depends on the circuits parameters. Breakdown and thus first re-strike occurs. Both When there is a fault occurs, there is a short circuit in the electrodes are there by electrically connected by conducting system. Transients are also produced due to the faults in the spark, whereby GIS section with initial voltage U2 is very system. Due to this VFTO‘s are caused by switching operation rapidly charged to instantaneous value of U1. The transient can also lead to secondary breakdown with in GIS. Re-striking current flowing through the spark then interrupts as soon as surges generated by the dis-connector switches at GIS the GIS have been charged to U1 and spark extinguishes. generally possess extremely high frequencies ranging from several hundred KHz to several MHz . For the development of The voltage U2 now remains constant with time, equivalent circuit low voltage step response measurements of while the voltage U1.on the side of supply keeps changing. the main GIS components have been made. Using MATLAB This continues until the second re- strike occurs with an 7.8 of the equivalent models is developed. increased breakdown voltage UB as a consequence of larger separation. Hence U2 follows U1, until finally at the end of the switching process the gap no longer can be broken down. During opening of Dis- connector switch (DS), transients are Transients are also produced due to faults in the system. When produced due to internal oscillations. The magnitude of there is a fault, there will be short circuit in the system. Due to transients and rise times depends on the circuit parameters like this, oscillations occur due to presence of inductance and inductance, Capacitance and connected Load. Assuming that capacitance on both sides of the fault section causing some trapped charge is left is left during operating operation; transients. transients can be calculated during closing operation of DS. Dis-connector Switch (DS) operation typically involves slow moving contacts which results in numerous Fast transient over voltages generated during Dis- discharges during operation .For example, a floating section of connector Switch operation are a sequence of voltage of switchgear between a disconnect switch and an open breaker voltage steps created by voltage collapse across the gas at re- (load side may be disconnected from an energized Gas striking specific over voltage shape is formed by multiple insulated system (supply side). reflections and refractions. Operation of Dis-connector Switch For capacitive currents below—1 amp, are-strike occurs (DS) can be shown by using the fig 1 every time the voltage between the connects exceeds the dielectric strength of the gaseous medium between them. Each re-strike generates a spark, which equalizes the Where L1 = Inductance of Source potentials between the switch contacts. Following spark C1 = Capacitance of Source extinction, the supply and load side potentials will deviate C2 = Capacitance of GIS Open part according to the AC supply voltage variation and the U1 = Power Frequency Voltage discharge characteristics of the load side respectively. Another U2 = Power GIS Voltage spark will result when the voltage across the electrode gap dependent breakdown voltage UB and the potential difference The more frequent service situation of the isolator is its use to of the load and supply side U. connect or dis-connect unloaded parts of the installation as is Each Dis-connector Switch (DS) operation generates a shown in fig 1 for example apart of the of the GIS is dis- large number of ignitions between the moving contacts. The connected by an isolator from an overhead supply line. Where number of ignitions depends on the speed of the contacts. The by the self-capacitance C2 of this part of circuit can be up to largest and steepest surge voltages are generated only by those several nF, depending on its length. First re-strike across the breakdowns at the largest contact gap. Therefore, only by gap occurs when voltage across the gap exceeds the those breakdowns (10-50) need be considered for dielectric breakdown voltage. The occurrence of re-strikes is described purpose. with the following Fig 2 A. Calculation of variable arc resistance The voltage across the gap is the difference between U1 and The Variable arc resistance is calculated using the U2, if it is assumed that the breakdown voltage UB of the gap formula: increases with increasing separation and therefore with time as 𝐾 𝑇 ×𝑙 shown in fig 2.Then the curve U2 can be constructed as 𝑅= 𝑡 𝑞 0 + 0 𝑖 𝑡 𝑑𝑡 follows. At the instant of mechanical contact separation, U1 Where, and U2 have the same value, the voltage U2 continues to 𝐾 𝑇 = Toepler‘s constant retain this value, while U1 changes with power frequency, the = 0.005 volt.sec/mt for SF6 under uniform field voltage (U2-U1) conditions L = spark length in meters Across the gap of the isolator also changes. As soon as, (U2-U1) exceeds the dielectric strength UB of the gap, a 𝑞0 = Initial charge or charge at the instant of breakdown T = spark collapse time in sec. 23 All Rights Reserved © 2012 IJARCET
  • 3. ISSN: 2278 – 1323 International Journal of Advanced Research in Computer Engineering & Technology Volume 1, Issue 4, June 2012 Fig. 1 Electric Circuit for explaining re-strikes Fig 2 Voltage of the open –ended GIS side of the Isolator Fig. 3 Schematic diagram of a typical Gas Insulated Substation Fig. 4. 132kv GIS MATLAB implemented circuit when CB in Re-Striking Condition 24 All Rights Reserved © 2012 IJARCET
  • 4. ISSN: 2278 – 1323 International Journal of Advanced Research in Computer Engineering & Technology Volume 1, Issue 4, June 2012 The value of time varying spark resistance R(t) is TABLE I calculated until it reaches a value of 1 to 3 ohms. The TRANSIENT DUE TO VARIATION OF RE-STRIKE VOLTAGE ON integral in the denominator sums up the absolute value of LODE SIDE current ‗i‘ through the resistance R(t) over the time beginning at breakdown inception. Thus, it corresponds to S.no Load side Magnitude of Rise Time the charge conducted through the spark channel up to Voltage the voltage (p.u) (Nanos) time‗t‘. (p.u) The busduct can be modelled as a series of Pi- 1 -1.0 2.45 10 network or as sequence parameters. However in this model, 2 -0.9 2.39 13 it is considered as distributed Pi-network. The Schematic 3 -0.8 2.19 12 Diagram of a Typical Gas Insulated System (GIS) is 4 -0.7 2.15 10 shown in below figure 3. 5 -0.6 2.03 12 Assuming that some trapped charge is left on the 6 -0.5 1.96 11 floating section of switchgear during opening operation of 7 -0.4 1.82 10 dis-connector switch, a voltage of certain value is 8 -0.3 1.77 13 considered during MATLAB 9 -0.2 1.53 12 The apparatus as disconnected with an earthing switch, 10 -0.1 1.45 9 three disc type Spencer‘s , a load bus bar above to 10mts long width three post type spacers and a 132kv gas bushing containing stress capacitor. TABLE II . TRANSIENTS DUE TO VARIATION OF RE-STRIKE VOLTAGE ON SOURCE SIDE III. 3-PHASE EQUIVALENT CIRCUIT FOR 132KV GIS SYSTEM FOR 10MTS LENGTH S.no Source side Magnitude of Rise Time Voltage (p.u) the voltage (p.u) (nanos) 1 1.0 2.43 9 The bus duct is dividing into three sections of 2 0.9 2.37 10 length 1mts, 4mts, and 5mts from load side. The GIS 3 0.8 2.17 11 bushing is represented by a capacitance of 125pf. The 4 0.7 2.11 10 resistance of 1 ohm spark channel is connected in series with circuit breaker. MATLAB Circuit for 10 mts. length 5 0.6 2.01 9 in a 3-phase 132kv GIS shown in the fig. 4. 6 0.5 1.91 10 Due to trapped charge some voltage remains on the 7 0.4 1.79 9 floating section which can create severe conditions 8 0.3 1.71 12 because the first re-strike can occur at the peak of power 9 0.2 1.42 11 frequency voltage giving a voltage of 2.0 p.u. On re-strike 10 0.1 1.39 9 the voltage on each side will collapse initially zero and hence creating two 1.0pu voltage steps of opposite polarities. In this, it is assumed that re-striking is created at IV. RESULTS AND DISCUSSION 1.0 p.u. respectively on either side of dis-connector switch (DS). The transients due to closing of the circuit breaker The phenomenon that occurs during the DS closing are calculated and maximum voltage obtained with a rise into a capacitive load is very nearly the reserve of time. processes that occur during its opening. Here, the first This method implemented on MATLAB 7.8. the restrike occurs due to the residual voltage left behind by a voltage before and after circuit breaker is taken to be 1.0 previous opening on the load side. Circuit breaker or load pu and -1.0pu as the most enormous condition but break switch closing or openings also generate VFTO in depending on the time of closing of circuit breaker the the case of re-strikes but the number of such VFTO is magnitude of the voltage on the load side changes. much lower than those generated by DS operation. The various transient voltage and current at different positions For different values of voltages on the load side the in a 3 phase 132kv GIS for the first switching operation magnitudes and rise time of the voltage wave are presented in results. calculated keeping source side voltages as constant as Assumed that there is a second re-strike another 1.0p.u the values are tabulated in table I. switch is connected in parallel to the circuit breaker for Similarly by changing the magnitudes of the voltage on simulation in MATLAB modeling. Transients are the source side, keeping voltage on load side constant at calculated by closing this switch when voltage difference 1.0p.u. Then the transient due to variation of voltage on across the contacts of the circuit breaker reaches maximum source side obtained. The values are tabulated in Table II. value. 25 All Rights Reserved © 2012 IJARCET
  • 5. ISSN: 2278 – 1323 International Journal of Advanced Research in Computer Engineering & Technology Volume 1, Issue 4, June 2012 During Re-strike operation (source & Load) the voltage To introduce the current chopping, the circuit breaker is through the resistance of the circuit breaker is shown in opened remains. Hence to calculate transients due to fig.5 and fig.6. From the graph it was found the maximum opening operation the CB is opened at 12ns. The transients current is 25A at a rise time of 13ns. are obtained and show in fig.7. The transient calculated due to re-strike gives the peak voltage of 2.45p.u at a rise time of 112ns show in fig.8. Fig. 5 Transient voltage waveform during Re-strike for 10mts from source side in a 3-phase 132kv GIS Fig.8 Current waveform during Re-strike for 10mts from Load side in a 3-phase 132kv GIS TABLE III THE ANALYSIS VALUES ARE TABULATED AS FOLLOWS: Mode of Magnitude of Rise time operation voltage(p.u) (Nano sec) During closing 2.46 69 operation During opening 1.22 56 Fig 6Transient voltage waveform during Re-strike for operation 10mts from Load side in a 3-phase 132kv GIS During second 2.45 112 re-strike V. CONCLUSION A model is Developed for the prediction of the VFTO phenomena in the circuit of voltage and current transformers in GIS. The main advantage of such model is to enable the transient analysis of GIS.A spark collapse time was correctly simulated by the variable resistor. By this spark collapse time, resistance of the VFTO is extended, and the component caused by short surge impedance discontinuities such as spacers, dis-connectors and short bus branches were damped. A GIS system comprising of spacers, bus bar and dis-connectors has been considered for modelling into Fig 7 Current waveform during Re-strike for 10mts from electric network. The inductance of the bus bar is source side in a 3-phase 132kv GIS calculated from diameters of conductors and enclosure 26 All Rights Reserved © 2012 IJARCET
  • 6. ISSN: 2278 – 1323 International Journal of Advanced Research in Computer Engineering & Technology Volume 1, Issue 4, June 2012 using standard formulae. Cone insulators used for supporting inner conductor against outer enclosure are assumed to be disk type for approximate calculation of spacer capacitance is calculated using formulae for concentric cylinders. The entire bus length is modelled as distributed pi-network. The peak magnitude of fast transient currents generated during switching event changes from one position to another in a 132kv GIS for a particular switching operation. These transients over voltages are reduced by connecting suitable resistor in an equivalent circuit during closing and opening operation. VI. REFERENCES [1] S.Ogawa, E. Haginomori, S. Nishiwaki, T.Yoshida, K. Terasaka,―Estimation of Re-striking Transient Over Voltage on Disconnecting Switch for GIS”, IEEE Trans. on PS, Vol. PWRD-1, No-2, April 1986, pp.95-101 [2] Li Liu-ling, Hu Pan-feng, Qiu Yu-chang, Analysis of Very Fast Transient Overvoltage Calculation Affected by Different Transformer Winding Models, Journal of Xi‘an Jiaotong University, 2005(10) Vol.39 No.10:1160-1164. [3] Yang Linghui, Zhang Jiamin, Research on transient Overvoltage during operation of 500kV GIS Disconnecting switch, East China Electric Power, Jan.2004, Vol.32 No.1:37-41 [4] Shibuya Y, Fujita S, Shimomura T. Effects of very fast transient over- Voltages on Transformer [J].IEE Proceedings, Part C,1999,146(4): 459-464. [5] H. Hiesinger, RWitzmann. Very fast Transient Breakdown at a needle Shaped Protrusion, IX Int. Conf. on Gas Dis. and Their Applied. Sep 1988. [6] MohanaRao M., Naidu M.S. (199% 'Estimation of Fast Transient Overvoltages in the case of Disconnnector operation in a GIS', 3d workshop & conference on EHV Technology, IISC Bangalore. [7] J.B. Kim,M.S. Kim,K.S.Park, W.P.Son.,.D.S. Kim, G.S. Kil. Development of monitoring and diagnostic System for SF6 gas insulated switchgear. IEEE Conference Record of the 2002 IEEE International Symposium on Electrical Insulation. Boston, Massachusetts, UnitedStates, pp.453-456, 2002. [8] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam,‖ Estimation Transientover voltages in gas insulated bus duct from 220kv gas insulated substation‖, International journal of Computer Applications, (0975-8887) volume 20-no.8 April 2011. [9] M.kondalu, G.Sreekanthreddy,Dr. P.S. subramanyam,‖ Analysis and Calculation of very fast transient over Voltages in 220kv gas insulated substation international Journal of Engineering& techscience vol 2(4) 2011 [10] D. Povh, H. Schmitt, O. Volcker, R. Witzmann, ―Modelling and Analysis Guidelines for Very Fast Transients‖. IEEE Trans. on PD, Vol.11 No.4, October 1996, pp.2028-2035. 27 All Rights Reserved © 2012 IJARCET