          Automation and Information Management for a
            Large Urban Power Distribution Network
                                       Dr. K Rajamani and Ranjeet Vaishnav, Member, IEEE




      Abstract— Rapid economic growth mounts immense pressure
  on the electric power generation, transmission and distribution
  infrastructure. Matching the rapid growth in a large metropolis
  poses several techno-economic challenges on utilities in order to
  operate the power supply distribution network efficiently and
  reliably. Utilities need to look at innovative ways to utilize the
  latest developments in information and communication
  technologies (ICT) to meet the new demands being placed on
  them. This paper discusses the experiences of Reliance Energy
  Limited, India’s largest integrated private sector power utility
  company, in deploying a large scale integrated SCADA/DMS
  system which utilizes a state-of-the art SDH communication
  network, a mobile phone network for secondary network
  automation and the use of latest technologies for data                      Fig.1. Typical Network for a Utility. The bottleneck is in Distribution.
  warehousing and data mining apart from the cutting edge
  SCADA technology.                                                          The peak loads of major cities (as per 2006 conditions) are
                                                                          shown in Fig. 2. In order to be able to distribute this quantum
     Index Terms—Code Division Multi Access, Data Mining,                 of power, the level of automation in the distribution network
  Distribution Automation, Fault Passage Indicator, SCADA                 has to be high. Distribution Automation is not an addendum to
  Systems, Synchronous Digital Hierarchy
                                                                          primary infrastructure but needs to be built as part of the
                                                                          infrastructure itself. Otherwise primary infrastructure itself
                          I. INTRODUCTION
                                                                          will fail to deliver.

  T    HE generation and transmission networks are easy to
       manage as the spread is limited. Distribution networks of
  a utility are wide-spread and involve kilometers of
  cables/conductors and thousands of substations with
  switchgear and transformers. The last mile reliability is
  heavily dependent on the efficient functioning of these
  network elements. Distribution is also where the highest
  technical and commercial losses occur. High technical losses
  are primarily due to inadequate investments over the years for
  system improvement works, which has resulted in unplanned
  extensions of the distribution lines, overloading of the
  network elements and lack of adequate reactive power
  support. The commercial losses are mainly due to low
  metering efficiency, theft and pilferages. A typical network                                Fig.2. Load Demand for Mega Cities
  for a utility is given in Fig. 1.
                                                                                                 II. UTILITY OPERATIONS

                                                                          A. Pre-Automation Days
                                                                             The operation of a distribution utility that does not utilize
                                                                          automation systems is characterized by the following:
      Dr. K Rajamani is Chief Consultant with Reliance Energy Limited
                                                                             o   System operation is largely dependent on the
  (www.rel.co.in),       Mumbai,       MH-400055     India     (e-mail:          knowledge, skills, experience and dedication of a
  rajamani.krishnamurti@relianceada.com).                                        relatively few individuals who staff and manage the
      Ranjeet Vaishnav is a member of IEEE and is with Tata Consultancy
                                                                                 various control centres.
  Services Limited (www.tcs.com), Mumbai, MH-400093 India (e-mail:
  ranjeet.vaishnav@tcs.com).                                                 o   There is no central visibility of the network on a real-


©2008 IEEE.
2

        time basis and snapshots of network operations are          real-time control room system employing modern concepts of
        not possible. Network operators use schematic               operating system maintenance, system status monitoring and
        operating diagrams produced in a variety of forms           decision tools for efficient management of control room
        targeted at the different levels of the control hierarchy   processes. The transition from manual operations to
        (zone, district circle levels).                             automated operations follows a stepwise procedure.
  o     Knowledge about the state of the network at any
        given time is limited.
  o     Logs and asset records are many and are manually
        written and maintained at most control levels.
        Updating of the asset records to the present network
        status is manual and not an inherent feature of the
        process which leads to inconsistency of data between
        various locations. Moreover, the records become too
        fragmented and complex for a human mind to
        comprehend and make efficient conclusions out of it.
  o     Customer Information System is largely unreliable
                                                                         Fig.3. Transition from manual operations to automated operations.
        due to paucity of information on the fault repair times
        and knowledge of crew activities leading to low
                                                                          III. INTEGRATED DISTRIBUTION AUTOMATION FOR
        confidence levels of consumers.
                                                                                    INFORMATION MANAGEMENT
B. Present Operating Environment
                                                                    A. Design Considerations for Integrated Distribution
  The present operations of utilities are hugely influenced by
                                                                    Automation
the ongoing restructuring of the power sector and regulatory
pressures. The following key drivers are seen as influencing           Distribution Automation is an umbrella concept that
the utility operations:                                             embraces all the real-time and operational functions for the
   o      Greater emphasis on improving efficiency of               distribution network. Within this umbrella, SCADA and
          operations                                                Distribution Management applications (DMS) form the heart
   o      Meeting regulatory requirements                           of the system which is then interfaced with other business
   o      Striving to become customer centric                       processes to create a truly integrated utility. A typical
   o      Timely revenue realization and reducing commercial        integrated distribution automation system with following
          losses                                                    elements is shown in Fig.4:
   o      Energy trading and sourcing of power from varied             o     Supervisory Control & Data Acquisition Systems
          sources to minimize cost of purchase and optimize                  (SCADA)
          operations.                                                  o     Distribution Management System (DMS)
                                                                       o     Geographical Information System (GIS)
C. Need for Automation
                                                                       o     Automatic Meter Reading System (AMR)
The above factors influence a utility to automate operations.          o     Outage Management System (OMS)
The utilities go in for automation to:                                 o     Communication Systems
   o     Improve reliability and quality at optimum cost.              o     Billing and Business Process Automation
   o     Improve their Customer Relationship Management                o     Enterprise Resource Planning (ERP) Systems
         (CRM).
   o     Have better knowledge of network leading to
         optimum operations.
   o     Be able to carry out load shedding intelligently
         instead of doing it in an ad-hoc manner.
   o     Timely      update      data    on     actual  system
         state/performance available to all decision makers
         (management, planners and operators).
   o     Coordinate documentation and information on
         network assets.
   o     Streamline business and operating processes.
   o     Reduce losses - technical and commercial
                                                                                       Fig.4. Integrated Automation System
D. Transition
  Distribution utilities need to move from a distributed,              The key design parameters for an integrated automation
manual intensive, paper based process relying on a few long         system are:
experienced, very senior staff to a central computer based             o    User interface response time
3

  o     Communication media                                     (SCADA) and Distribution Management System (DMS) was
  o     Type, frequency and quantity of data flow               one such step.
  o     Data flows between different elements of the
                                                                A. SCADA/DMS Subsystems and Field Implementation
        SCADA/DMS network
   o    RTU to Control Center communication                        In the first step, SCADA system was commissioned which
   o    Hardware sizing (SCADA/DMS servers, RTU)                integrated the monitoring and control of generation,
   o    Scalability for future expansion                        transmission and distribution network. Today full monitoring
   o    Data flows between SCADA/DMS and other IT               and control is exercised up to the receiving stations, situated
        systems                                                 all over the REL distribution area. Intelligent Electronic
  The industry recommended best practices for distribution      Devices (IEDs) such as numerical relays, digital tap-changers,
system automation are:                                          and energy meters of several makes have been successfully
   o    All primary substations to be unmanned with central     integrated for better post mortem analysis after an abnormal
        decision making processes                               occurrence. Visibility of all the network elements, like
   o    Decision making based on real-time accurate and         generation transmission and distribution at one place has
        consistent information                                  greatly improved response and decision making during a
   o    Remote control of all key field equipment devices       contingency. Islanding scheme after grid failure and automatic
   o    Selected distribution substations (11kV/415V) control   load shedding scheme post islanding is implemented in the
   o    Monitoring of all data required to support              new SCADA system.
        contingency                                                In the next step, REL implemented secondary SCADA
   o    Monitoring of power system equipment                    with a set of network analysis applications which is termed
   o    Remote monitoring of protective relay performance       Distribution Management System (DMS). It involves
                                                                automating Ring Main Units (RMUs) emanating from a
B. SCADA/DMS Functionalities                                    receiving station and ending in same or different primary
   The major functionalities of a SCADA/DMS are:                substation (called Receiving Station). Refer Fig. 5. Each ring
   o   Monitoring and Control of EHV and HV network             approximately caters to 12 to 20 substations. The incoming
   o   Distribution Network Power Flow: to execute real-        and outgoing supplies at substation are controlled by RMUs
       time power flow studies for optimal switching            which are basically switches or isolators. Around 800 such
   o   Switching Procedure Management: to execute               locations, out of a total of 5000 locations, had been earmarked
       switching orders and inverted switching orders           for automation. The locations were chosen after careful study
   o   Voltage and VAR Control: for optimal switching of        of network configuration to derive maximum benefit on
       Capacitor banks and OLTC control                         investment and minimizing interruption to consumers. The
   o   Outage Management System (OMS): to keep records          11kV RMUs or switches at these locations will ultimately be
       of forced and planned outages                            operated from remote.
   o   Load shedding and restoration
   o   Short Term Load Forecasting and Calculation of
       Quality Service Indices
   o   Optimal Feeder Reconfiguration (OFR): for judicious
       network switching to reduce losses and voltage
       problems
   o   Energy Balance: to give insight into the energy flow
       and losses in the network
   o   Fault Location, Isolation and Service Restoration
       (FLISR): to determine the location of feeder faults
       and recommend actions to isolate the faulty sections
       and restore supply to the healthy sections of feeders.

      IV. AUTOMATION & INFORMATION MANAGEMENT AT                                     Fig. 5. Typical Ring Main
          RELIANCE ENERGY LIMITED (REL), MUMBAI
                                                                B. Fault Location, Isolation and Supply Restoration (FLISR)
    REL supplies power to 2.5 million consumers in the
suburban areas of Mumbai. The total load served is about            FLISR is the most powerful and useful network application
1400 MW. Mumbai enjoys the reputation of providing one of       for REL which has helped in faster location, isolation of faults
the most reliable power supplies to the consumers in the        and supply restoration. The fault isolation and supply
whole country. To maintain high standards of availability and   restoration procedure pre and post DMS is explained below.
reliability, REL had been continuously introducing new            i) Fault Isolation and Restoration before DMS
technologies in their network and processes. Commissioning            implementation
the State of the art Supervisory Control and Data Acquisition       Before DMS implementation, fault isolation was done by
4

trial and error method. Refer Fig. 6. In case of fault at F, the
breaker A at receiving station trips and all substations on the
ring up to NOP1 (A-B-C) looses power. Then the field crews
are physically sent to a substation (say B) to open the switch
or isolator. This might take anywhere between 10 to 30
minutes in a congested city like Mumbai. A ‘test charge’ is
then taken from control centre by closing the breaker A at the
receiving station. If it holds, the fault is beyond substation B.
Between B and NOP, again by trial-and-error, the faulty
section is identified (DE). Total fault isolation time is
approximately 40 to 60 minutes.

                                                                                Fig.7. Fault Isolation after DMS Implementation

                                                                    C. Fault Passage Indicators (FPI)
                                                                       This device basically detects earth faults in cable system
                                                                    since majority of system faults (more than 70%) is earth
                                                                    faults. It consists of a sensor - split core CT (CBCT) and
                                                                    indicator. Refer Fig. 8.




               Fig. 6. Fault Isolation before DMS Implementation

 ii) Fault Isolation and Restoration after DMS
      implementation
    Under DMS implementation, typically three isolators in a
ring are automated. In automated RMUs, isolator operations                           Fig.8. FPI with CBCT and Indicator
are done by motors which can be remotely controlled. The
opening or closing of isolator is done remotely from control           Split core CT is wrapped around the cable under
centre. All automated RMUs have built in Fault Passage              observation. CBCT works on summated flux principle. Under
Indicators (FPIs). Apart from this, FPIs are installed              normal conditions, fluxes produced by three phase currents
separately at every non-automated RMU stations. Let us              IR, IY and IB add to zero. In case of earth fault on one phase,
analyze the previous case with DMS in place. Refer Fig. 7. In       there is a net flux and voltage is induced on secondary. This is
case of fault at F, the breaker A at receiving station trips and    used to drive the indicator.
all substations on the ring up to NOP (A-B-C) looses power.            Refer Fig. 9. When earth fault occurs between section X
This scenario is same with or without DMS. However with             and Y, FPIs in substations from A to X will glow but FPI at
DMS in place, FPI indication at B is available at control           substation Y will not glow. The fault is in the section between
centre. If FPI indicates through-fault, the operator can            glowing FPI (at X) and non-glowing FPI (at Y). The field
immediately open the isolator at substation and close the           personnel can narrow down the faulty section after observing
breaker at receiving station remotely from control room. This       the status of FPIs. This avoids trial end error method of
takes less than a minute compared to 10 to 30 minutes without       locating the faulty section reducing ‘unnecessary’ test
DMS. Power is restored to the substations in the section AB         charges. The stress on the equipment is less since closing on
within a minute, a dramatic reduction in outage time. Also          to fault is eliminated. This increases the life of the
location of faulty portion (section DE) is now done more            equipment. Also power quality improves as every test charge
rationally using the FPI indications. On the whole this results     on fault creates dip in bus voltage.
in reduction in outage time and reduction in number of test
charges being taken for fault isolation and supply restoration.




   1
       Normally Open Point
5

                                                                     o    All communication channels are path-protected
                                                                     o    Network Management features to enable monitoring
                                                                          of the communication network




              Fig.9. Fault Section Identification with FPI

D. Communication Networks for Primary & Secondary
Network Automation
    The architecture of DMS system and communication
system is shown in Fig. 10 and Fig.11 respectively. Fig. 11
shows remote operation of RMU from Control Centre through
Code Division Multi Access (CDMA) network. This has been
engineered through integration of different elements of DMS
                                                                          Fig.11. Secondary Communication Automation Architecture
i.e. automated RMU, field RTU (FRTU), CDMA modems and
a Front-End Processor (FEP) at Control Centre.                    E. Data Warehousing
   The remote operation and monitoring of 33/22/11kV                 Data collected by the SCADA/DMS is stored in a Utility
receiving station elements is carried out through an SDH Fiber    Data Warehouse (UDW) for historical data analysis. The Data
Optic network. Remote terminal units (RTU) are located in         Warehouse (Oracle based) is a component that archives
each receiving station for collecting field data. The Fiber       selected portions of the SCADA database for years without
Optic WAN (Wide-Area Network) consists of several fiber           loss of data resolution or accuracy. Once data to be archived
rings covering the five zones of the service area of REL. The     is identified in the data engineering environment, it is
communication with some of the older RTUs is over serial          recorded in the warehouse database as it is updated in the
protocol whereas the new RTUs communicate over IEC 870-           real-time database. The users can start or stop the archiving of
5-104 protocol. The five important transmission stations at the   any data point including status values, accumulator values,
220kV level, including the REL Generating Station at              analog values, quality flags, sequence of event points (with
Dahanu, are connected over dedicated 10 Mbps links with the       millisecond time resolution), alarms and events.
Control Center. The transmission stations are connected              The data warehouse subsystem is highly flexible and
through OPGW for SCADA communications.                            accommodates large amounts of data input from many
                                                                  sources, and provides powerful data mining capability for
                                                                  various purposes such as reporting, trending and analyzing
                                                                  past data to make informed decisions about the network
                                                                  operations and maintenance of assets. The warehouse is an
                                                                  extremely important subsystem in the Distribution
                                                                  Automation architecture of REL as it provides the operations,
                                                                  maintenance and planning teams with critical information
                                                                  about network operations which helps optimize maintenance
                                                                  and planning activities tremendously.
                                                                  F. Use of International Standards
                                                                     As the project involves collecting data from several
                                                                  sources and sharing the same with third party IT systems, it
                                                                  was important to follow international standards and avoid
            Fig.10. Primary Communication Network – SDH
                                                                  potential roadblocks in integration.
   Some of the important features of this communication              o    Using standard communication protocols such as
network are:                                                              Modbus and IEC 60870-5-103 for ‘device to sub-
   o   The communication network handles both the                         device’ level integration meant that it was possible to
       SCADA as well as the IT requirements of REL                        integrate meters, numerical relays and digital RTCCs
   o   Hardware complies to EMI/EMC requirements of                       of various makes with the substation RTUs.
       harsh substation environments                                 o    Similarly, by using IEC 60870-5-101 and -104
6

         protocols for ‘device to host’ communication                    o    Equipment subjected to less stress leading to better
         facilitated integration of substation RTUs from                      equipment condition
         different vendors with host computers systems at the
         control center system.                                                                 V. CONCLUSION
  o      ICCP is used to share data with the SCADA/EMS at             Summarizing, in a short period automation has yielded
         the Regional Load Despatch Center.                        tangible benefits in terms of operational flexibility, reduction
  o      The deployed SCADA/DMS is the central element in          in outage time and improved quality of supply in REL
         the utility’s goal to integrate various enterprise IT     network. Experience gained from deploying a large
         systems (such as GIS, AMR). CIM standards have            SCADA/DMS has brought out several aspects that utilities
         been used to describe the logical (analytical) model of   should be careful about while planning similar initiatives. It is
         an electrical network and related entities in the         often seen that utilities are not able to derive the optimum
         SCADA/DMS with the purpose of providing a                 benefits of an automation system because of the following
         common language for describing exactly what data is       reasons:
         required to be exchanged between different                   o     Inadequate specification of requirements
         applications.                                                o     Unclear objectives
G. Benefits of Automation in REL network                              o     Overly ambitious goals – too many features are
                                                                            desired especially while targeting integration at not
  o    Integrated view of Generation, Transmission and
                                                                            only device and sub-device level but also at the
       Distribution
                                                                            enterprise level between various IT systems, for
  o    Centralized remote monitoring and control of
                                                                            information exchange
       network elements
                                                                      o     Not ready with data to kick start the project
  o    Reliable Islanding after grid collapse and Optimal
                                                                      o     Lack of know-how within organization
       load shedding after islanding
                                                                      o     Poor implementation
  o    Network reconfiguration and load transfer switching
                                                                      o     Lack of training
       performed remotely for most situations. This has led
                                                                      o     Primary equipment compatibility not factored
       to optimum manpower utilization.
  o    Centralized storage of event logs, fault analysis and
                                                                                           VI. ACKNOWLEDGEMENT
       report generation.
  o    Real-time alarm on a network fault or abnormality           The authors would like to thank the management of Reliance
  o    Better assistance to field staff in pin-pointing faulty     Energy Limited for the help and support while writing this
       section by utilizing FPIs at all sub-stations. This has     paper. Special thanks to Ms. Bina Mitra and Mr. Shrikant
       led to reduction in time for fault identification.          Yeole for their contribution towards this paper.
  o    Interruption time reduction due to remote operation
       of switches. It has led to reduction in customer hour                                   VII. REFERENCES
       loss by 50%. SAIFI and SAIDI calculated for the
                                                                         Papers Presented at Conferences (Unpublished):
       whole system is not much influenced by DMS                  [1]    Dr. K Rajamani, "Automation in Distribution Systems" Key Note Speech
       implementation. Effect of DMS is reflected in                      delivered at the National Conference on Distribution Automation held at
       Customer Average Interruption Duration Index                       CPRI, Bangalore between 29th and 31st October 2007.
       (CAIDI) apportioned to HT tripping as DMS is
       applied only for 11kV (HT) system. The figures given                                   VIII. BIOGRAPHIES
       in the table below indicates CAIDI after                                            Dr. K Rajamani obtained his PhD in Electrical Power
                                                                                           Systems from IIT Mumbai in 1975. From 1976 to
       implementation of DMS in one of the zones in REL
                                                                                           1996, he was with Tata Consulting Engineers,
       network.                                                                            Mumbai. He was involved in design of electrical
                              TABLE 1                                                      systems for thermal and nuclear power plants and
      IMPROVEMENT IN CAIDI BEFORE AND AFTER IMPLEMENTING DMS                               Static VAR compensators for rolling mill applications.
                                                                                           From 1997 to 1998, he was with General Electric,
        Central Zone      Nr. of HT      Nr. of      CAIDI in                              Schenectady, USA working on dynamic stability
                                                                                           simulations for integrated operations of gas turbines
        (Jul-Sep)         Trippings    consumers      minutes                              with steel plant loads. From 1999 to 2002, he was with
        Pre DMS (Y-                                                Power Linkers, Mumbai working on specialized protection problems and
                             102          577,010        95. 16    islanding. From 2003, he is with Reliance Energy, Mumbai. He is involved in
        2006)                                                      implementation of SCADA-DMS. His other areas of interest are protection and
        Post DMS (Y-                                               power quality.
                             103          599,376        50.24
        2007)
                                                                                          Ranjeet Vaishnav has a B.E. in Electrical Engineering
                                                                                          (1994) from BVM Engineering College, Sardar Patel
  o      Improved power supply quality due to reduced test                                University (Gujarat). He has 13 years of experience in
         charges.                                                                         the field of Control & Automation systems for Electric
                                                                                          Utilities as well as for Plant Electrical Networks in the
7

Oil & Gas industries. He has worked in various roles in Design & Engineering,
Installation & Commissioning, Project Management and Technical Presales in
the business of Automation & IT Systems for Electric Utilities. He is working
with Tata Consultancy Services Limited on power systems related initiatives.
Ranjeet is a member of IEEE and of The IET, UK.

Weitere ähnliche Inhalte

Was ist angesagt?

Classification of data center operations technology management tools
Classification of data center operations technology management toolsClassification of data center operations technology management tools
Classification of data center operations technology management toolsSchneider Electric India
 
ANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARD
ANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARDANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARD
ANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARDIAEME Publication
 
T Light Benefits
T Light BenefitsT Light Benefits
T Light BenefitsRay Wescott
 
Energy efficiency data center overview
Energy efficiency data center overviewEnergy efficiency data center overview
Energy efficiency data center overviewSchneider Electric
 
Data Center Infrastructure Management
Data Center Infrastructure ManagementData Center Infrastructure Management
Data Center Infrastructure Managementshahzad ahmed
 
Carrier-Class Availability for Enterprises
Carrier-Class Availability for EnterprisesCarrier-Class Availability for Enterprises
Carrier-Class Availability for EnterprisesSheri Determan
 
Rorotika Self-Organising Network Solution (SON)
Rorotika Self-Organising Network Solution (SON)Rorotika Self-Organising Network Solution (SON)
Rorotika Self-Organising Network Solution (SON)Frans_Joubert
 
SELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEY
SELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEYSELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEY
SELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEYIJNSA Journal
 
Fault Management System (OSS)
Fault Management System (OSS)Fault Management System (OSS)
Fault Management System (OSS)Riswan
 
Automating power distribution
Automating power distributionAutomating power distribution
Automating power distributionNavas Azeez
 
Volume 2-issue-6-2068-2072
Volume 2-issue-6-2068-2072Volume 2-issue-6-2068-2072
Volume 2-issue-6-2068-2072Editor IJARCET
 
Information technology in power sectors
Information technology in power sectorsInformation technology in power sectors
Information technology in power sectorsGanesh Kumar Gawande
 
Mobile backhaul solution guide
Mobile backhaul solution guideMobile backhaul solution guide
Mobile backhaul solution guideNir Cohen
 

Was ist angesagt? (17)

Classification of data center operations technology management tools
Classification of data center operations technology management toolsClassification of data center operations technology management tools
Classification of data center operations technology management tools
 
ANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARD
ANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARDANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARD
ANALYSIS OF NETWORK PERFORMANCE MANAGEMENT DASHBOARD
 
T Light Benefits
T Light BenefitsT Light Benefits
T Light Benefits
 
Energy efficiency data center overview
Energy efficiency data center overviewEnergy efficiency data center overview
Energy efficiency data center overview
 
10 fn s32
10 fn s3210 fn s32
10 fn s32
 
Sgcp12 faulkner-cal
Sgcp12 faulkner-calSgcp12 faulkner-cal
Sgcp12 faulkner-cal
 
The Substation of the Future; CIGRE
The Substation of the Future; CIGREThe Substation of the Future; CIGRE
The Substation of the Future; CIGRE
 
Data Center Infrastructure Management
Data Center Infrastructure ManagementData Center Infrastructure Management
Data Center Infrastructure Management
 
Carrier-Class Availability for Enterprises
Carrier-Class Availability for EnterprisesCarrier-Class Availability for Enterprises
Carrier-Class Availability for Enterprises
 
Rorotika Self-Organising Network Solution (SON)
Rorotika Self-Organising Network Solution (SON)Rorotika Self-Organising Network Solution (SON)
Rorotika Self-Organising Network Solution (SON)
 
SELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEY
SELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEYSELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEY
SELF-ORGANIZATION AND AUTONOMOUS NETWORK SURVEY
 
Fault Management System (OSS)
Fault Management System (OSS)Fault Management System (OSS)
Fault Management System (OSS)
 
Automating power distribution
Automating power distributionAutomating power distribution
Automating power distribution
 
Volume 2-issue-6-2068-2072
Volume 2-issue-6-2068-2072Volume 2-issue-6-2068-2072
Volume 2-issue-6-2068-2072
 
StruxureWare DCIM
StruxureWare DCIMStruxureWare DCIM
StruxureWare DCIM
 
Information technology in power sectors
Information technology in power sectorsInformation technology in power sectors
Information technology in power sectors
 
Mobile backhaul solution guide
Mobile backhaul solution guideMobile backhaul solution guide
Mobile backhaul solution guide
 

Ähnlich wie 04596361

How the Convergence of IT and OT Enables Smart Grid Development
How the Convergence of IT and OT Enables Smart Grid DevelopmentHow the Convergence of IT and OT Enables Smart Grid Development
How the Convergence of IT and OT Enables Smart Grid DevelopmentSchneider Electric
 
Smart distribution system the need of automation & it application in powe...
Smart distribution system the need of automation & it application in powe...Smart distribution system the need of automation & it application in powe...
Smart distribution system the need of automation & it application in powe...SoumyaRanjanDas13
 
Intelligent management of electrical systems in industries
Intelligent management of electrical systems in industriesIntelligent management of electrical systems in industries
Intelligent management of electrical systems in industriespushpeswar reddy
 
Performance management leaflet
Performance management leafletPerformance management leaflet
Performance management leafletnerdic
 
EPR coverage-smart meter
EPR coverage-smart meterEPR coverage-smart meter
EPR coverage-smart meterethandoyle
 
A Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdf
A Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdfA Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdf
A Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdfAnil
 
Designing of an automated power meter reading
Designing of an automated power meter readingDesigning of an automated power meter reading
Designing of an automated power meter readingManoj Kollam
 
Designing of an automated power meter reading
Designing of an automated power meter readingDesigning of an automated power meter reading
Designing of an automated power meter readingManoj Kollam
 
Ieeepro techno solutions 2013 ieee embedded project an integrated design fr...
Ieeepro techno solutions   2013 ieee embedded project an integrated design fr...Ieeepro techno solutions   2013 ieee embedded project an integrated design fr...
Ieeepro techno solutions 2013 ieee embedded project an integrated design fr...srinivasanece7
 
intelligent-automation-guide.pdf
intelligent-automation-guide.pdfintelligent-automation-guide.pdf
intelligent-automation-guide.pdfssuser818de4
 
IRJET - A Review on Analysis of Location Management in Mobile Computing
IRJET -  	  A Review on Analysis of Location Management in Mobile ComputingIRJET -  	  A Review on Analysis of Location Management in Mobile Computing
IRJET - A Review on Analysis of Location Management in Mobile ComputingIRJET Journal
 
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...Dhana Raj Markandu
 
Advanced Metering Infrastructure Standards and protocol
Advanced Metering Infrastructure Standards and protocolAdvanced Metering Infrastructure Standards and protocol
Advanced Metering Infrastructure Standards and protocolEklavya Sharma
 
IT in power,Smart Grid,OMS & DMS
IT in power,Smart Grid,OMS & DMSIT in power,Smart Grid,OMS & DMS
IT in power,Smart Grid,OMS & DMSChanmeet Singh
 
eMeter EnergyIP Data Sheet
eMeter EnergyIP Data SheeteMeter EnergyIP Data Sheet
eMeter EnergyIP Data SheetMichaline Todd
 
RightITnow Whitepaper
RightITnow WhitepaperRightITnow Whitepaper
RightITnow WhitepaperMarc Ferrie
 

Ähnlich wie 04596361 (20)

How the Convergence of IT and OT Enables Smart Grid Development
How the Convergence of IT and OT Enables Smart Grid DevelopmentHow the Convergence of IT and OT Enables Smart Grid Development
How the Convergence of IT and OT Enables Smart Grid Development
 
Smart distribution system the need of automation & it application in powe...
Smart distribution system the need of automation & it application in powe...Smart distribution system the need of automation & it application in powe...
Smart distribution system the need of automation & it application in powe...
 
Intelligent management of electrical systems in industries
Intelligent management of electrical systems in industriesIntelligent management of electrical systems in industries
Intelligent management of electrical systems in industries
 
Performance management leaflet
Performance management leafletPerformance management leaflet
Performance management leaflet
 
EPR coverage-smart meter
EPR coverage-smart meterEPR coverage-smart meter
EPR coverage-smart meter
 
A Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdf
A Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdfA Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdf
A Fascinating Behind the Scenes Look at Wireless Design Services - Techwave.pdf
 
Designing of an automated power meter reading
Designing of an automated power meter readingDesigning of an automated power meter reading
Designing of an automated power meter reading
 
Designing of an automated power meter reading
Designing of an automated power meter readingDesigning of an automated power meter reading
Designing of an automated power meter reading
 
On the Path to a Smarter World
On the Path to a Smarter WorldOn the Path to a Smarter World
On the Path to a Smarter World
 
Ieeepro techno solutions 2013 ieee embedded project an integrated design fr...
Ieeepro techno solutions   2013 ieee embedded project an integrated design fr...Ieeepro techno solutions   2013 ieee embedded project an integrated design fr...
Ieeepro techno solutions 2013 ieee embedded project an integrated design fr...
 
intelligent-automation-guide.pdf
intelligent-automation-guide.pdfintelligent-automation-guide.pdf
intelligent-automation-guide.pdf
 
Enterprise network management
Enterprise network managementEnterprise network management
Enterprise network management
 
IRJET - A Review on Analysis of Location Management in Mobile Computing
IRJET -  	  A Review on Analysis of Location Management in Mobile ComputingIRJET -  	  A Review on Analysis of Location Management in Mobile Computing
IRJET - A Review on Analysis of Location Management in Mobile Computing
 
Trends in Soft Grid 2014
Trends in Soft Grid 2014Trends in Soft Grid 2014
Trends in Soft Grid 2014
 
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
 
391 394
391 394391 394
391 394
 
Advanced Metering Infrastructure Standards and protocol
Advanced Metering Infrastructure Standards and protocolAdvanced Metering Infrastructure Standards and protocol
Advanced Metering Infrastructure Standards and protocol
 
IT in power,Smart Grid,OMS & DMS
IT in power,Smart Grid,OMS & DMSIT in power,Smart Grid,OMS & DMS
IT in power,Smart Grid,OMS & DMS
 
eMeter EnergyIP Data Sheet
eMeter EnergyIP Data SheeteMeter EnergyIP Data Sheet
eMeter EnergyIP Data Sheet
 
RightITnow Whitepaper
RightITnow WhitepaperRightITnow Whitepaper
RightITnow Whitepaper
 

Kürzlich hochgeladen

How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityEric T. Tung
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptxnandhinijagan9867
 
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGBerhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGpr788182
 
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...Falcon Invoice Discounting
 
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service AvailableNashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service Availablepr788182
 
Pre Engineered Building Manufacturers Hyderabad.pptx
Pre Engineered  Building Manufacturers Hyderabad.pptxPre Engineered  Building Manufacturers Hyderabad.pptx
Pre Engineered Building Manufacturers Hyderabad.pptxRoofing Contractor
 
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTSJAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTSkajalroy875762
 
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book nowGUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book nowkapoorjyoti4444
 
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAIGetting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAITim Wilson
 
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NSCROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NSpanmisemningshen123
 
PHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPanhandleOilandGas
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 MonthsIndeedSEO
 
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...meghakumariji156
 
Kalyan Call Girl 98350*37198 Call Girls in Escort service book now
Kalyan Call Girl 98350*37198 Call Girls in Escort service book nowKalyan Call Girl 98350*37198 Call Girls in Escort service book now
Kalyan Call Girl 98350*37198 Call Girls in Escort service book nowranineha57744
 
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...pujan9679
 
Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...
Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...
Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...pujan9679
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGpr788182
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon investment
 

Kürzlich hochgeladen (20)

How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGBerhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
 
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service AvailableNashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
Nashik Call Girl Just Call 7091819311 Top Class Call Girl Service Available
 
Pre Engineered Building Manufacturers Hyderabad.pptx
Pre Engineered  Building Manufacturers Hyderabad.pptxPre Engineered  Building Manufacturers Hyderabad.pptx
Pre Engineered Building Manufacturers Hyderabad.pptx
 
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTSJAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
 
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book nowGUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
 
Buy gmail accounts.pdf buy Old Gmail Accounts
Buy gmail accounts.pdf buy Old Gmail AccountsBuy gmail accounts.pdf buy Old Gmail Accounts
Buy gmail accounts.pdf buy Old Gmail Accounts
 
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAIGetting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
 
WheelTug Short Pitch Deck 2024 | Byond Insights
WheelTug Short Pitch Deck 2024 | Byond InsightsWheelTug Short Pitch Deck 2024 | Byond Insights
WheelTug Short Pitch Deck 2024 | Byond Insights
 
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NSCROSS CULTURAL NEGOTIATION BY PANMISEM NS
CROSS CULTURAL NEGOTIATION BY PANMISEM NS
 
PHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation Final
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
 
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
Escorts in Nungambakkam Phone 8250092165 Enjoy 24/7 Escort Service Enjoy Your...
 
Kalyan Call Girl 98350*37198 Call Girls in Escort service book now
Kalyan Call Girl 98350*37198 Call Girls in Escort service book nowKalyan Call Girl 98350*37198 Call Girls in Escort service book now
Kalyan Call Girl 98350*37198 Call Girls in Escort service book now
 
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
 
Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...
Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...
Chennai Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Av...
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 

04596361

  • 1. 1 Automation and Information Management for a Large Urban Power Distribution Network Dr. K Rajamani and Ranjeet Vaishnav, Member, IEEE Abstract— Rapid economic growth mounts immense pressure on the electric power generation, transmission and distribution infrastructure. Matching the rapid growth in a large metropolis poses several techno-economic challenges on utilities in order to operate the power supply distribution network efficiently and reliably. Utilities need to look at innovative ways to utilize the latest developments in information and communication technologies (ICT) to meet the new demands being placed on them. This paper discusses the experiences of Reliance Energy Limited, India’s largest integrated private sector power utility company, in deploying a large scale integrated SCADA/DMS system which utilizes a state-of-the art SDH communication network, a mobile phone network for secondary network automation and the use of latest technologies for data Fig.1. Typical Network for a Utility. The bottleneck is in Distribution. warehousing and data mining apart from the cutting edge SCADA technology. The peak loads of major cities (as per 2006 conditions) are shown in Fig. 2. In order to be able to distribute this quantum Index Terms—Code Division Multi Access, Data Mining, of power, the level of automation in the distribution network Distribution Automation, Fault Passage Indicator, SCADA has to be high. Distribution Automation is not an addendum to Systems, Synchronous Digital Hierarchy primary infrastructure but needs to be built as part of the infrastructure itself. Otherwise primary infrastructure itself I. INTRODUCTION will fail to deliver. T HE generation and transmission networks are easy to manage as the spread is limited. Distribution networks of a utility are wide-spread and involve kilometers of cables/conductors and thousands of substations with switchgear and transformers. The last mile reliability is heavily dependent on the efficient functioning of these network elements. Distribution is also where the highest technical and commercial losses occur. High technical losses are primarily due to inadequate investments over the years for system improvement works, which has resulted in unplanned extensions of the distribution lines, overloading of the network elements and lack of adequate reactive power support. The commercial losses are mainly due to low metering efficiency, theft and pilferages. A typical network Fig.2. Load Demand for Mega Cities for a utility is given in Fig. 1. II. UTILITY OPERATIONS A. Pre-Automation Days The operation of a distribution utility that does not utilize automation systems is characterized by the following: Dr. K Rajamani is Chief Consultant with Reliance Energy Limited o System operation is largely dependent on the (www.rel.co.in), Mumbai, MH-400055 India (e-mail: knowledge, skills, experience and dedication of a rajamani.krishnamurti@relianceada.com). relatively few individuals who staff and manage the Ranjeet Vaishnav is a member of IEEE and is with Tata Consultancy various control centres. Services Limited (www.tcs.com), Mumbai, MH-400093 India (e-mail: ranjeet.vaishnav@tcs.com). o There is no central visibility of the network on a real- ©2008 IEEE.
  • 2. 2 time basis and snapshots of network operations are real-time control room system employing modern concepts of not possible. Network operators use schematic operating system maintenance, system status monitoring and operating diagrams produced in a variety of forms decision tools for efficient management of control room targeted at the different levels of the control hierarchy processes. The transition from manual operations to (zone, district circle levels). automated operations follows a stepwise procedure. o Knowledge about the state of the network at any given time is limited. o Logs and asset records are many and are manually written and maintained at most control levels. Updating of the asset records to the present network status is manual and not an inherent feature of the process which leads to inconsistency of data between various locations. Moreover, the records become too fragmented and complex for a human mind to comprehend and make efficient conclusions out of it. o Customer Information System is largely unreliable Fig.3. Transition from manual operations to automated operations. due to paucity of information on the fault repair times and knowledge of crew activities leading to low III. INTEGRATED DISTRIBUTION AUTOMATION FOR confidence levels of consumers. INFORMATION MANAGEMENT B. Present Operating Environment A. Design Considerations for Integrated Distribution The present operations of utilities are hugely influenced by Automation the ongoing restructuring of the power sector and regulatory pressures. The following key drivers are seen as influencing Distribution Automation is an umbrella concept that the utility operations: embraces all the real-time and operational functions for the o Greater emphasis on improving efficiency of distribution network. Within this umbrella, SCADA and operations Distribution Management applications (DMS) form the heart o Meeting regulatory requirements of the system which is then interfaced with other business o Striving to become customer centric processes to create a truly integrated utility. A typical o Timely revenue realization and reducing commercial integrated distribution automation system with following losses elements is shown in Fig.4: o Energy trading and sourcing of power from varied o Supervisory Control & Data Acquisition Systems sources to minimize cost of purchase and optimize (SCADA) operations. o Distribution Management System (DMS) o Geographical Information System (GIS) C. Need for Automation o Automatic Meter Reading System (AMR) The above factors influence a utility to automate operations. o Outage Management System (OMS) The utilities go in for automation to: o Communication Systems o Improve reliability and quality at optimum cost. o Billing and Business Process Automation o Improve their Customer Relationship Management o Enterprise Resource Planning (ERP) Systems (CRM). o Have better knowledge of network leading to optimum operations. o Be able to carry out load shedding intelligently instead of doing it in an ad-hoc manner. o Timely update data on actual system state/performance available to all decision makers (management, planners and operators). o Coordinate documentation and information on network assets. o Streamline business and operating processes. o Reduce losses - technical and commercial Fig.4. Integrated Automation System D. Transition Distribution utilities need to move from a distributed, The key design parameters for an integrated automation manual intensive, paper based process relying on a few long system are: experienced, very senior staff to a central computer based o User interface response time
  • 3. 3 o Communication media (SCADA) and Distribution Management System (DMS) was o Type, frequency and quantity of data flow one such step. o Data flows between different elements of the A. SCADA/DMS Subsystems and Field Implementation SCADA/DMS network o RTU to Control Center communication In the first step, SCADA system was commissioned which o Hardware sizing (SCADA/DMS servers, RTU) integrated the monitoring and control of generation, o Scalability for future expansion transmission and distribution network. Today full monitoring o Data flows between SCADA/DMS and other IT and control is exercised up to the receiving stations, situated systems all over the REL distribution area. Intelligent Electronic The industry recommended best practices for distribution Devices (IEDs) such as numerical relays, digital tap-changers, system automation are: and energy meters of several makes have been successfully o All primary substations to be unmanned with central integrated for better post mortem analysis after an abnormal decision making processes occurrence. Visibility of all the network elements, like o Decision making based on real-time accurate and generation transmission and distribution at one place has consistent information greatly improved response and decision making during a o Remote control of all key field equipment devices contingency. Islanding scheme after grid failure and automatic o Selected distribution substations (11kV/415V) control load shedding scheme post islanding is implemented in the o Monitoring of all data required to support new SCADA system. contingency In the next step, REL implemented secondary SCADA o Monitoring of power system equipment with a set of network analysis applications which is termed o Remote monitoring of protective relay performance Distribution Management System (DMS). It involves automating Ring Main Units (RMUs) emanating from a B. SCADA/DMS Functionalities receiving station and ending in same or different primary The major functionalities of a SCADA/DMS are: substation (called Receiving Station). Refer Fig. 5. Each ring o Monitoring and Control of EHV and HV network approximately caters to 12 to 20 substations. The incoming o Distribution Network Power Flow: to execute real- and outgoing supplies at substation are controlled by RMUs time power flow studies for optimal switching which are basically switches or isolators. Around 800 such o Switching Procedure Management: to execute locations, out of a total of 5000 locations, had been earmarked switching orders and inverted switching orders for automation. The locations were chosen after careful study o Voltage and VAR Control: for optimal switching of of network configuration to derive maximum benefit on Capacitor banks and OLTC control investment and minimizing interruption to consumers. The o Outage Management System (OMS): to keep records 11kV RMUs or switches at these locations will ultimately be of forced and planned outages operated from remote. o Load shedding and restoration o Short Term Load Forecasting and Calculation of Quality Service Indices o Optimal Feeder Reconfiguration (OFR): for judicious network switching to reduce losses and voltage problems o Energy Balance: to give insight into the energy flow and losses in the network o Fault Location, Isolation and Service Restoration (FLISR): to determine the location of feeder faults and recommend actions to isolate the faulty sections and restore supply to the healthy sections of feeders. IV. AUTOMATION & INFORMATION MANAGEMENT AT Fig. 5. Typical Ring Main RELIANCE ENERGY LIMITED (REL), MUMBAI B. Fault Location, Isolation and Supply Restoration (FLISR) REL supplies power to 2.5 million consumers in the suburban areas of Mumbai. The total load served is about FLISR is the most powerful and useful network application 1400 MW. Mumbai enjoys the reputation of providing one of for REL which has helped in faster location, isolation of faults the most reliable power supplies to the consumers in the and supply restoration. The fault isolation and supply whole country. To maintain high standards of availability and restoration procedure pre and post DMS is explained below. reliability, REL had been continuously introducing new i) Fault Isolation and Restoration before DMS technologies in their network and processes. Commissioning implementation the State of the art Supervisory Control and Data Acquisition Before DMS implementation, fault isolation was done by
  • 4. 4 trial and error method. Refer Fig. 6. In case of fault at F, the breaker A at receiving station trips and all substations on the ring up to NOP1 (A-B-C) looses power. Then the field crews are physically sent to a substation (say B) to open the switch or isolator. This might take anywhere between 10 to 30 minutes in a congested city like Mumbai. A ‘test charge’ is then taken from control centre by closing the breaker A at the receiving station. If it holds, the fault is beyond substation B. Between B and NOP, again by trial-and-error, the faulty section is identified (DE). Total fault isolation time is approximately 40 to 60 minutes. Fig.7. Fault Isolation after DMS Implementation C. Fault Passage Indicators (FPI) This device basically detects earth faults in cable system since majority of system faults (more than 70%) is earth faults. It consists of a sensor - split core CT (CBCT) and indicator. Refer Fig. 8. Fig. 6. Fault Isolation before DMS Implementation ii) Fault Isolation and Restoration after DMS implementation Under DMS implementation, typically three isolators in a ring are automated. In automated RMUs, isolator operations Fig.8. FPI with CBCT and Indicator are done by motors which can be remotely controlled. The opening or closing of isolator is done remotely from control Split core CT is wrapped around the cable under centre. All automated RMUs have built in Fault Passage observation. CBCT works on summated flux principle. Under Indicators (FPIs). Apart from this, FPIs are installed normal conditions, fluxes produced by three phase currents separately at every non-automated RMU stations. Let us IR, IY and IB add to zero. In case of earth fault on one phase, analyze the previous case with DMS in place. Refer Fig. 7. In there is a net flux and voltage is induced on secondary. This is case of fault at F, the breaker A at receiving station trips and used to drive the indicator. all substations on the ring up to NOP (A-B-C) looses power. Refer Fig. 9. When earth fault occurs between section X This scenario is same with or without DMS. However with and Y, FPIs in substations from A to X will glow but FPI at DMS in place, FPI indication at B is available at control substation Y will not glow. The fault is in the section between centre. If FPI indicates through-fault, the operator can glowing FPI (at X) and non-glowing FPI (at Y). The field immediately open the isolator at substation and close the personnel can narrow down the faulty section after observing breaker at receiving station remotely from control room. This the status of FPIs. This avoids trial end error method of takes less than a minute compared to 10 to 30 minutes without locating the faulty section reducing ‘unnecessary’ test DMS. Power is restored to the substations in the section AB charges. The stress on the equipment is less since closing on within a minute, a dramatic reduction in outage time. Also to fault is eliminated. This increases the life of the location of faulty portion (section DE) is now done more equipment. Also power quality improves as every test charge rationally using the FPI indications. On the whole this results on fault creates dip in bus voltage. in reduction in outage time and reduction in number of test charges being taken for fault isolation and supply restoration. 1 Normally Open Point
  • 5. 5 o All communication channels are path-protected o Network Management features to enable monitoring of the communication network Fig.9. Fault Section Identification with FPI D. Communication Networks for Primary & Secondary Network Automation The architecture of DMS system and communication system is shown in Fig. 10 and Fig.11 respectively. Fig. 11 shows remote operation of RMU from Control Centre through Code Division Multi Access (CDMA) network. This has been engineered through integration of different elements of DMS Fig.11. Secondary Communication Automation Architecture i.e. automated RMU, field RTU (FRTU), CDMA modems and a Front-End Processor (FEP) at Control Centre. E. Data Warehousing The remote operation and monitoring of 33/22/11kV Data collected by the SCADA/DMS is stored in a Utility receiving station elements is carried out through an SDH Fiber Data Warehouse (UDW) for historical data analysis. The Data Optic network. Remote terminal units (RTU) are located in Warehouse (Oracle based) is a component that archives each receiving station for collecting field data. The Fiber selected portions of the SCADA database for years without Optic WAN (Wide-Area Network) consists of several fiber loss of data resolution or accuracy. Once data to be archived rings covering the five zones of the service area of REL. The is identified in the data engineering environment, it is communication with some of the older RTUs is over serial recorded in the warehouse database as it is updated in the protocol whereas the new RTUs communicate over IEC 870- real-time database. The users can start or stop the archiving of 5-104 protocol. The five important transmission stations at the any data point including status values, accumulator values, 220kV level, including the REL Generating Station at analog values, quality flags, sequence of event points (with Dahanu, are connected over dedicated 10 Mbps links with the millisecond time resolution), alarms and events. Control Center. The transmission stations are connected The data warehouse subsystem is highly flexible and through OPGW for SCADA communications. accommodates large amounts of data input from many sources, and provides powerful data mining capability for various purposes such as reporting, trending and analyzing past data to make informed decisions about the network operations and maintenance of assets. The warehouse is an extremely important subsystem in the Distribution Automation architecture of REL as it provides the operations, maintenance and planning teams with critical information about network operations which helps optimize maintenance and planning activities tremendously. F. Use of International Standards As the project involves collecting data from several sources and sharing the same with third party IT systems, it was important to follow international standards and avoid Fig.10. Primary Communication Network – SDH potential roadblocks in integration. Some of the important features of this communication o Using standard communication protocols such as network are: Modbus and IEC 60870-5-103 for ‘device to sub- o The communication network handles both the device’ level integration meant that it was possible to SCADA as well as the IT requirements of REL integrate meters, numerical relays and digital RTCCs o Hardware complies to EMI/EMC requirements of of various makes with the substation RTUs. harsh substation environments o Similarly, by using IEC 60870-5-101 and -104
  • 6. 6 protocols for ‘device to host’ communication o Equipment subjected to less stress leading to better facilitated integration of substation RTUs from equipment condition different vendors with host computers systems at the control center system. V. CONCLUSION o ICCP is used to share data with the SCADA/EMS at Summarizing, in a short period automation has yielded the Regional Load Despatch Center. tangible benefits in terms of operational flexibility, reduction o The deployed SCADA/DMS is the central element in in outage time and improved quality of supply in REL the utility’s goal to integrate various enterprise IT network. Experience gained from deploying a large systems (such as GIS, AMR). CIM standards have SCADA/DMS has brought out several aspects that utilities been used to describe the logical (analytical) model of should be careful about while planning similar initiatives. It is an electrical network and related entities in the often seen that utilities are not able to derive the optimum SCADA/DMS with the purpose of providing a benefits of an automation system because of the following common language for describing exactly what data is reasons: required to be exchanged between different o Inadequate specification of requirements applications. o Unclear objectives G. Benefits of Automation in REL network o Overly ambitious goals – too many features are desired especially while targeting integration at not o Integrated view of Generation, Transmission and only device and sub-device level but also at the Distribution enterprise level between various IT systems, for o Centralized remote monitoring and control of information exchange network elements o Not ready with data to kick start the project o Reliable Islanding after grid collapse and Optimal o Lack of know-how within organization load shedding after islanding o Poor implementation o Network reconfiguration and load transfer switching o Lack of training performed remotely for most situations. This has led o Primary equipment compatibility not factored to optimum manpower utilization. o Centralized storage of event logs, fault analysis and VI. ACKNOWLEDGEMENT report generation. o Real-time alarm on a network fault or abnormality The authors would like to thank the management of Reliance o Better assistance to field staff in pin-pointing faulty Energy Limited for the help and support while writing this section by utilizing FPIs at all sub-stations. This has paper. Special thanks to Ms. Bina Mitra and Mr. Shrikant led to reduction in time for fault identification. Yeole for their contribution towards this paper. o Interruption time reduction due to remote operation of switches. It has led to reduction in customer hour VII. REFERENCES loss by 50%. SAIFI and SAIDI calculated for the Papers Presented at Conferences (Unpublished): whole system is not much influenced by DMS [1] Dr. K Rajamani, "Automation in Distribution Systems" Key Note Speech implementation. Effect of DMS is reflected in delivered at the National Conference on Distribution Automation held at Customer Average Interruption Duration Index CPRI, Bangalore between 29th and 31st October 2007. (CAIDI) apportioned to HT tripping as DMS is applied only for 11kV (HT) system. The figures given VIII. BIOGRAPHIES in the table below indicates CAIDI after Dr. K Rajamani obtained his PhD in Electrical Power Systems from IIT Mumbai in 1975. From 1976 to implementation of DMS in one of the zones in REL 1996, he was with Tata Consulting Engineers, network. Mumbai. He was involved in design of electrical TABLE 1 systems for thermal and nuclear power plants and IMPROVEMENT IN CAIDI BEFORE AND AFTER IMPLEMENTING DMS Static VAR compensators for rolling mill applications. From 1997 to 1998, he was with General Electric, Central Zone Nr. of HT Nr. of CAIDI in Schenectady, USA working on dynamic stability simulations for integrated operations of gas turbines (Jul-Sep) Trippings consumers minutes with steel plant loads. From 1999 to 2002, he was with Pre DMS (Y- Power Linkers, Mumbai working on specialized protection problems and 102 577,010 95. 16 islanding. From 2003, he is with Reliance Energy, Mumbai. He is involved in 2006) implementation of SCADA-DMS. His other areas of interest are protection and Post DMS (Y- power quality. 103 599,376 50.24 2007) Ranjeet Vaishnav has a B.E. in Electrical Engineering (1994) from BVM Engineering College, Sardar Patel o Improved power supply quality due to reduced test University (Gujarat). He has 13 years of experience in charges. the field of Control & Automation systems for Electric Utilities as well as for Plant Electrical Networks in the
  • 7. 7 Oil & Gas industries. He has worked in various roles in Design & Engineering, Installation & Commissioning, Project Management and Technical Presales in the business of Automation & IT Systems for Electric Utilities. He is working with Tata Consultancy Services Limited on power systems related initiatives. Ranjeet is a member of IEEE and of The IET, UK.