Impact Analysis of Midpoint Connected STATCOM on
Distance Relay Performance
R. Ilango1*
, T. Sree Renga Raja2
1
MAM School of Engineering, Tiruchirappalli, Tamil Nadu, India, 621105
2
Anna University, Anna University BIT Campus, Tiruchirappalli, Tamil Nadu, India, 620024
*Corresponding author, e-mail: ilangorengaraju@gmail.com
Abstract
This paper presents the impact of the Static Synchronous Compensator (STATCOM) on the
performance of distance protection of EHV transmission lines. A 400kV transmission system having
midpoint connected STATCOM with its control circuit is modeled using MATLAB/SIMULINK software. The
impact of STATCOM on distance relay for different fault conditions and different fault locations is analyzed.
Simulation results indicate that the presence of the STATCOM in the transmission system significantly
changes the line impedance seen by the distance relay to be lower or higher than the actual line
impedance. Due to this the performance of the distance relay changes, either overreaches or under
reaches.
Keywords: distance relay protection, flexible AC transmission system (FACTS), static synchronous
compensators (STATCOM), EHV transmission line
Copyright © 2015 Institute of Advanced Engineering and Science. All rights reserved.
1. Introduction
The demand of electrical power is growing day by day with a very fast rate. To meet out
this a significant modification in the conventional power system is required. The recent
development of power electronics provides a solution by the way of using FACTS devices in the
power systems. The FACTS devices which are connected in parallel, series or combination of
both in the power system, enhance the system controllability and also increasing power transfer
capability [1, 2]. Static synchronous compensator (STATCOM) is the most used shunt
connected FACTS device which controls the connecting point bus voltage near stable and also
enhance system stability by injecting or absorbing reactive power into the transmission system
[3, 4].
Impedance based distance protection relays are widely used for protecting EHV/HV
transmission lines due to their simple operating principle. The relay measures the apparent
impedance of the fault loop by considering the voltage and current signals at the relay location,
then the relay calculates the fault location by using this apparent impedance [5, 6]
In distance relay due to the presence of STATCOM in the fault loop the measured
voltage and current signals are changed. The measured current at the relay point decreases
when the STATCOM injects reactive power into the power system and increases when the
STATCOM draws reactive power from the system. Due to this change in the voltage and current
signals the apparent impedance calculated by the distance relay changes. The distance relay
will be over reach if the measured impedance is less than the actual measurement and the relay
will be under reach when the impedance is greater than the actual measurement. So due to the
presence of STATCOM in the fault loop the distance relay characteristics will be affected.
Therefore, nowadays it is important to analyze the impact of STATCOM on the distance relay to
design an adaptive protective scheme to get accurate fault location.
Some researches have been done on the impact of different FACTS devices on the
distance relay. K. El-Arroudi, G. Joos, and D. T. McGillis [7] present the analytical results based
on the steady - state model of STATCOM, and outline the impact of STATCOM on different load
levels. In [8] and [9] a comprehensive analysis of the impact of thyristor-controlled series
capacitor (TCSC) on the protection of transmission lines has been presented showing that
TCSC not only affects the protection of its line, but also the protection of adjacent line. The
study in [10], demonstrates the impact of FACTS controllers and their location in the
 ISSN: 2302-4046
TELKOMNIKA Vol. 13, No. 2, February 2015 : 257 – 263
258
transmission line on the trip boundary of a digital multifunctional protective relay. The work in
[11], derivates apparent impedance calculation seen by a distance relay in the presence of a
unified power flow controller (UPFC) based on the power frequency sequence component and
also explains the effect of UPFC operational mode as well as its control parameters. Previous
work [12] presents the Impact analysis of static synchronous series compensator (SSSC) on the
performance of the digital distance relaying. In [13] various distance protection schemes for a
midpoint compensated transmission line has been compared. The work reported in [14],
demonstrates the impact of TCSC on the parameters of protective transmission line during a
single phase to ground fault conditions.
In this paper, the impact of midpoint connected STATCOM of the transmission line on
distance relay protection is analyzed. First, a detailed model of STATCOM is presented then the
performance of the distance relay for different fault conditions at different fault locations in the
presence of STATCOM is analyzed and finally the results have been presented.
2. Study Test System
The impact of the STATCOM on the performance of distance relays is studied using the
model developed by the MATLAB/SIMULINK software [15]. The test transmission system
model with STATCOM and distance relay are described in this section.
2.1. Transmission System Model with STATCOM
The simulation diagram of the test system under analysis is shown in Figure 1. The test
system consists of a 400kV 50 Hz, 300 km length transmission line, with two equivalent
sources, source 1 and source 2 connected at the sending and receiving end respectively. The
positive sequence resistance and zero sequence resistance of the line is 0.03 ohm/km and 0.25
ohm/km respectively. Similarly the positive sequence inductance and zero sequence inductance
of the line is 1.01 mH/km and 3.73 mH/km respectively. The distance relay connected near the
sending end source is considered for analysis.
A 100 MVA, 48 pulse voltage source inverter based STATCOM is connected at the
midpoint of the transmission line. The main objective of the STATCOM controller is to regulate
the connecting point voltage of the transmission line to the setting value (Vref) by supplying or
absorbing the reactive current [16, 17].
Figure 1. Test transmission simulation system implemented in MATLAB
2.2. Distance Relay model
The distance relay model used for this analysis consists of six Mho distance elements,
three elements for phase-to-phase loops and three elements for the phase- to-ground loops.
TELKOMNIKA ISSN: 2302-4046 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (R. Ilango)
259
The distance relay calculates the apparent impedance of the fault line considering the voltage
and current signals at the relay location, then the fault location is calculated by considering the
positive sequence impedance of the line [18]. The relay is assumed to be set to protect 80%
(240km) of the transmission line. The Figure 2 shows the modeling of one element (“A” phase-
to-ground element) of the distance relay used to locate the faults which occur in “A” phase.
Figure 2. One element of the distance relay model
3. Simulation Results and Analysis
To study the impact of STATCOM on the performance of distance relay various types
of faults have been applied on the test transmission system at various locations. Although
several cases involving all types of faults with different fault resistances at different locations of
the transmission line have been simulated, only two cases, namely, “A” phase to ground fault
with a fault resistance of zero ohm and three phase to ground fault with a fault resistance of
zero ohm are presented.
3.1. The Effect of Single Phase Fault
The test results of the test system with STATCOM and without STATCOM for “A” phase
to ground fault is shown in Table 1. It clearly shows that, when the fault occurs between the
relay point and the STATCOM location (between 10 and 150 kilometers in this case), there is no
much change on the apparent impedance, measured by the distance relay i.e. the measured
impedance is almost the same as that for the system without STATCOM.
Table 1. Variations of the apparent impedance for single phase-to- ground fault
Fault location in Km
Apparent impedance
in ohms
Without STATCOM
Apparent impedance
in ohms
With STATCOM
20 06.35 06.37
40 12.69 12.73
60 19.00 19.08
80 25.28 25.42
100 31.53 31.53
120 37.77 37.75
140 43.28 43.43
160 50.18 51.05
180 56.59 58.01
200 62.59 65.11
220 68.83 72.38
240 75.15 79.94
260 81.65 87.94
280 88.54 96.80
 ISSN: 2302-4046
TELKOMNIKA Vol. 13, No. 2, February 2015 : 257 – 263
260
For example, when the fault is occurring at 140 km, the apparent impedance measured
by the distance relay without connecting the STATCOM in the fault line is 43.28 ohms, and with
the STATCOM is 43.43 ohms. This is due to the fact, that when the STATCOM is not present in
the fault loop for zero fault resistance, the measured impedance is equal to the actual line
impedance of the line section between the relay point and the fault point.
When the fault (‘A’ phase-to-ground fault) occurs beyond the STATCOM location,
(between 150 and 300 kilometers in this case) the apparent impedance of the system is greater
than that for the system without STATCOM, since the STATCOM involves in the fault loop; the
injected/absorbed current of the STATCOM changes the apparent impedance measured by the
distance relay.
The apparent impedance seen by the distance relay with STATCOM and without
STATCOM for single phase fault occurring for fault distance of 240 km is shown in Figure 3;
from this it is evident that the apparent impedance seen by the distance relay is higher than that
of the system without STATCOM. So the protection zone of the distance relay under reaches its
setting and does not give the trip signal.
Figure 3. The apparent impedance seen by the relay for single phase fault
The plot of apparent resistance measured at the relay location for “A” phase to ground
fault created at various locations of the transmission line with STATCOM and without
STATCOM is depicted in Figure 4. It shows that when the fault occurs before the STATCOM
location (i.e., <150km), the apparent resistance is almost same as that of the apparent
resistance without STATCOM, but when the fault occurs after the STATCOM location the
apparent resistance decreases.
Figure 4. Apparent resistance versus fault location plots for single phase fault
-20 -10 0 10 20 30 40 50 60 70 80
-10
0
10
20
30
40
50
60
70
80
90
100
apparent resistance (ohms)
apparentreactance(ohms)
With STATCOM
Without STATCOM
0 50 100 150 200 250 300
0
5
10
15
20
25
30
distance (km)
apparentresistance(ohms)
Without STATCOM
With STATCOM
TELKOMNIKA ISSN: 2302-4046 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (R. Ilango)
261
Figure 5 shows the plot of apparent reactance measured at the relay location for “A”
phase to ground fault created at various locations of the transmission line with STATCOM and
without STATCOM. It is apparent that when the fault occurs before the STATCOM location the
apparent reactance is almost same, but when the fault occurs after the STATCOM location the
apparent reactance increases compared to the apparent reactance of the system without
STATCOM.
Figure 5. Apparent reactance versus fault location plots for single phase fault
This is mainly due to the fact that when the fault occurs after the STATCOM location the
STATCOM supplies the reactive power to the connecting point, so the apparent reactance of
the transmission line increases and the apparent resistance of the transmission line decreases.
Further from analysis, it is apparent that the presence of the STATCOM in the
transmission system significantly affects the apparent resistance and apparent reactance
measured by the distance relay under single phase fault conditions.
3.2. The Effect of Three Phase Fault
When three phase fault is created at a distance of 240 km, the apparent impedance
measured by the distance relay with STATCOM is 83.40 ohms, and without STATCOM is 78.75
ohms respectively.
The impedance trajectory of the distance relay for three phase faults created at a
distance of 240 km with STATCOM and without STATCOM is shown in Figure 6; it clearly
shows that the apparent impedance seen by the relay is greater than that of the system without
STATCOM. So the protection zone of the distance relay under reaches its setting and does not
give the trip signal.
Figure 6. The apparent impedance seen by the relay for three phase fault
0 50 100 150 200 250 300
0
20
40
60
80
100
120
distance (km)
apparentreactance(ohms)
With STATCOM
Without STATCOM
-40 -20 0 20 40 60 80
-10
0
10
20
30
40
50
60
70
80
90
100
apparent resistance (ohms)
apparentreactance(ohms)
Without STATCOM
With STATCOM
 ISSN: 2302-4046
TELKOMNIKA Vol. 13, No. 2, February 2015 : 257 – 263
262
The apparent resistance versus fault location and apparent reactance versus fault location
plots of transmission system with and without STATCOM for three phase fault are shown in
Figure 7 and Figure 8 respectively.
Figure 7. Apparent resistance versus fault location plots for three phase fault
Figure 8. Apparent reactance versus fault location plots for three phase fault
The inference of the Figure 7 and Figure 8 shows that, when the three phase fault
occurs between the relay point and the STATCOM location the measured apparent resistance
and reactance of the system are almost same as that of the system without STATCOM.
However, when the fault occurs beyond the STATCOM location, both the apparent resistance
and reactance of the system are greater than that of the system without STATCOM.
It is evident that like single phase fault the three phase fault also having the same
impact on the performance of the distance relay in the presence of the STATCOM in the
transmission system.
4. Conclusion
The performance of the distance relay in the presence of STATCOM has been
analyzed for different fault conditions and different fault locations. From the simulation results it
is evident that during a fault, the injected or absorbed current of the STATCOM produces an
error in impedance measurement and because of this under /over reach of the distance relay
happens.
The results clearly show that the connection of the STATCOM at the midpoint of the
transmission line affects the performance of the distance relay. Therefore, when a transmission
line system is connected with STATCOM, the conventional distance relay characteristics are not
usable. So there is a need for distance relay to adjust to new settings in its characteristics and
to be adapted to the system conditions in order to avoid mal operation.
0 50 100 150 200 250 300
0
2
4
6
8
10
12
distance (km)
apparentresistance(ohms)
Without STATCOM
With STATCOM
0 50 100 150 200 250 300
0
10
20
30
40
50
60
70
80
90
100
distance (km)
apparentreactance(ohms)
With STATCOM
Without STATCOM
TELKOMNIKA ISSN: 2302-4046 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (R. Ilango)
263
References
[1] Hingorani NG, Gyugyi L. Understanding FACTS: Concepts and Technology of Flexible Transmission
Systems. New York: IEEE Press. 2000.
[2] Hingorani NG. FACTS-Flexible AC Transmission System. Proceedings of 5th International
Conference on AC and DC Power Transmission. IEE Conference. 1991; 345: 1-7.
[3] Adido MA. Power System Stability Enhancement Using FACTS Controllers: A Review. The Arabian
Journal for Science and Engineering. 2009; 34 (1B): 153-172.
[4] Haniyeh Marefatjou, Mohammad Sarvi. Power Flow Study and Performance of STATCOM and TCSC
in Improvement Voltage Stability and Loadability Amplification in Power System. International Journal
of Applied Power Engineering. 2013; 2(1):15-26.
[5] Phadke AG, lbrahim M, Hblika T. Fundamental Basis for Distance Relaying with Symmetrical
Components. IEEE Transactions on Power Apparatus and Systems. 1977; 635-676.
[6] AREVA TD. Network Protection & Automation Guide. Second edition. France. AREVA. 2010.
[7] El-Arroudi K, Joos G, McGillis DT. Operation of impedance protection relays with the STATCOM.
IEEE Transaction on Power Delivery. 2002; 17(2): 381–387.
[8] Khederzadeh M, Sidhu TS. Impact of TCSC on the protection of transmission lines. IEEE Transaction
on Power Delivery. 2006; 21(1): 80–87.
[9] Sidhu TS, Khederzadeh M. TCSC impact on communication aided distance protection schemes and
its mitigation. IEE Proc. Generation, Transmission and Distribution. 2005; 152(5): 714– 728.
[10] Khederzadeh M. The impact of FACTS device on digital multifunctional protective relays. T & D
Conference and Exhibition IEEE/PES. Asia Pacific. 2002; 3: 2043–2048.
[11] Zhou X, Wang H, Aggarwal RK, Beaumont P. Performance evaluation of a distance relay as applied
to a transmission system with UPFC. IEEE Transaction on Power Delivery. 2006; 21 (3):1137– 1147.
[12] Khederzadeh M, Ghorbani A, Salemnia A. Impact of SSSC on the digital distance relaying.
IEEE/PES, Power &Energy Society General Meeting. PES’09. 2009; 1-8.
[13] Albasri FA, Sidhu TS, Varma RK. Performance comparison of distance protection schemes for shunt-
FACTS compensated transmission lines. IEEE Transaction on Power Del. 2007; 22(4): 2116-2125.
[14] Mohamed Zellagui, Abdelaziz Chaghi. Impact of Thyristor Controlled Series Capacitor Insertion on
Short-Circuit Calculation in Presence Phase to Earth Fault. International Journal of Applied Power
Engineering. 2012; 1 (2): 93-104.
[15] Sybille G, Le-Huy, Hoang. Digital simulation of power systems and power electronic using the
MATLAB/Simulink Power System Blockset. Power Engineering Society Winter Meeting. 2000; 4:
2973-2981.
[16] EI-Moursi MS, Haraf AM. Novel controllers for the 48- pulse VSC STATCOM and SSSC for voltage
regulation and reactive power compensation. IEEE Transaction on Power System. 2005; 20(4):1985-
1987.
[17] Pranesh Rao, Crow ML, Zhiping Yang. STATCOM Control for Power System Voltage Control
Applications. IEEE Trans. On Power Delivery. 2000; 15(4): 1311-1317.
[18] Zigler G. Numerical Distance Protection: Principles and Applications. Third edition. Germany. Publics
Corporate. 2008.

Weitere ähnliche Inhalte

Was ist angesagt?

Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limitsMeeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Raymund Cortez
 
A new cost effective sensorless commutation
A new cost effective sensorless commutationA new cost effective sensorless commutation
A new cost effective sensorless commutation
Hemchand Immaneni
 

Was ist angesagt? (20)

Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
 
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS) POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
 
Minor project
Minor projectMinor project
Minor project
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution network
 
Unit1 8
Unit1 8Unit1 8
Unit1 8
 
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limitsMeeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
 
Practical of Power System Analysis (PSA)
Practical of Power System Analysis (PSA)Practical of Power System Analysis (PSA)
Practical of Power System Analysis (PSA)
 
A new cost effective sensorless commutation
A new cost effective sensorless commutationA new cost effective sensorless commutation
A new cost effective sensorless commutation
 
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
 
Power System Modelling And Simulation Lab
Power System Modelling And Simulation LabPower System Modelling And Simulation Lab
Power System Modelling And Simulation Lab
 
199833536 ee2404-lab-manual
199833536 ee2404-lab-manual199833536 ee2404-lab-manual
199833536 ee2404-lab-manual
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
 
IRJET- A Placement Method of Fuzzy based UPFC to Enhance Voltage Stability Ma...
IRJET- A Placement Method of Fuzzy based UPFC to Enhance Voltage Stability Ma...IRJET- A Placement Method of Fuzzy based UPFC to Enhance Voltage Stability Ma...
IRJET- A Placement Method of Fuzzy based UPFC to Enhance Voltage Stability Ma...
 
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
 
“An Assessment of Voltage Stability based on Line Voltage Stability Indices a...
“An Assessment of Voltage Stability based on Line Voltage Stability Indices a...“An Assessment of Voltage Stability based on Line Voltage Stability Indices a...
“An Assessment of Voltage Stability based on Line Voltage Stability Indices a...
 
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
 
M356872
M356872M356872
M356872
 
Power System Simulation Laboratory Manual
Power System Simulation Laboratory Manual Power System Simulation Laboratory Manual
Power System Simulation Laboratory Manual
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 

Ähnlich wie Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance

Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
MohammadMomani26
 
Svpwm based 3 level statcom for reactive power management under line-line
Svpwm based 3 level statcom for reactive power management under line-lineSvpwm based 3 level statcom for reactive power management under line-line
Svpwm based 3 level statcom for reactive power management under line-line
IAEME Publication
 

Ähnlich wie Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (20)

Performance Analysis of the Distance Relay Characteristics in a Compensated T...
Performance Analysis of the Distance Relay Characteristics in a Compensated T...Performance Analysis of the Distance Relay Characteristics in a Compensated T...
Performance Analysis of the Distance Relay Characteristics in a Compensated T...
 
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
Modelling and Testing of a Numerical Pilot Distance Relay for Compensated Tra...
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
 
Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...
 
A Performance Analysis of Statcom on Distance Protection Relay
A Performance Analysis of Statcom on Distance Protection RelayA Performance Analysis of Statcom on Distance Protection Relay
A Performance Analysis of Statcom on Distance Protection Relay
 
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOM
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOMOptimal Reactive Power Compensation in Electric Transmission Line using STATCOM
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOM
 
IRJET- Distance Algorithm for Transmission Line with Mid-Point Connected ...
IRJET-  	  Distance Algorithm for Transmission Line with Mid-Point Connected ...IRJET-  	  Distance Algorithm for Transmission Line with Mid-Point Connected ...
IRJET- Distance Algorithm for Transmission Line with Mid-Point Connected ...
 
Svpwm based 3 level statcom for reactive power management under line-line
Svpwm based 3 level statcom for reactive power management under line-lineSvpwm based 3 level statcom for reactive power management under line-line
Svpwm based 3 level statcom for reactive power management under line-line
 
Three zone detection and distance relay co-ordination of power system protect...
Three zone detection and distance relay co-ordination of power system protect...Three zone detection and distance relay co-ordination of power system protect...
Three zone detection and distance relay co-ordination of power system protect...
 
Errors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devicesErrors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devices
 
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
 Wavelet based detection and location of faults in 400kv, 50km Underground Po... Wavelet based detection and location of faults in 400kv, 50km Underground Po...
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
 
Optimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlOptimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow Control
 
B0461015
B0461015B0461015
B0461015
 
Wavelet Based Fault Detection, Classification in Transmission System with TCS...
Wavelet Based Fault Detection, Classification in Transmission System with TCS...Wavelet Based Fault Detection, Classification in Transmission System with TCS...
Wavelet Based Fault Detection, Classification in Transmission System with TCS...
 
A detailed analysis on the performance
A detailed analysis on the performanceA detailed analysis on the performance
A detailed analysis on the performance
 
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMDistance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
 
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationEfficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
 
FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
 FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Load Flow Based Voltage Stability Indices for Voltage Stability and Contingen...
Load Flow Based Voltage Stability Indices for Voltage Stability and Contingen...Load Flow Based Voltage Stability Indices for Voltage Stability and Contingen...
Load Flow Based Voltage Stability Indices for Voltage Stability and Contingen...
 

Mehr von Radita Apriana

Mehr von Radita Apriana (20)

Dynamic RWX ACM Model Optimizing the Risk on Real Time Unix File System
Dynamic RWX ACM Model Optimizing the Risk on Real Time Unix File SystemDynamic RWX ACM Model Optimizing the Risk on Real Time Unix File System
Dynamic RWX ACM Model Optimizing the Risk on Real Time Unix File System
 
False Node Recovery Algorithm for a Wireless Sensor Network
False Node Recovery Algorithm for a Wireless Sensor NetworkFalse Node Recovery Algorithm for a Wireless Sensor Network
False Node Recovery Algorithm for a Wireless Sensor Network
 
ESL Reading Research Based on Eye Tracking Techniques
ESL Reading Research Based on Eye Tracking TechniquesESL Reading Research Based on Eye Tracking Techniques
ESL Reading Research Based on Eye Tracking Techniques
 
A New Approach to Linear Estimation Problem in Multiuser Massive MIMO Systems
A New Approach to Linear Estimation Problem in Multiuser Massive MIMO SystemsA New Approach to Linear Estimation Problem in Multiuser Massive MIMO Systems
A New Approach to Linear Estimation Problem in Multiuser Massive MIMO Systems
 
Internet Access Using Ethernet over PDH Technology for Remote Area
Internet Access Using Ethernet over PDH Technology for Remote AreaInternet Access Using Ethernet over PDH Technology for Remote Area
Internet Access Using Ethernet over PDH Technology for Remote Area
 
A New Ozone Concentration Regulator
A New Ozone Concentration RegulatorA New Ozone Concentration Regulator
A New Ozone Concentration Regulator
 
Identifying of the Cielab Space Color for the Balinese Papyrus Characters
Identifying of the Cielab Space Color for the Balinese Papyrus CharactersIdentifying of the Cielab Space Color for the Balinese Papyrus Characters
Identifying of the Cielab Space Color for the Balinese Papyrus Characters
 
Filtering Based Illumination Normalization Techniques for Face Recognition
Filtering Based Illumination Normalization Techniques for Face RecognitionFiltering Based Illumination Normalization Techniques for Face Recognition
Filtering Based Illumination Normalization Techniques for Face Recognition
 
Analysis and Estimation of Harmonics Using Wavelet Technique
Analysis and Estimation of Harmonics Using Wavelet TechniqueAnalysis and Estimation of Harmonics Using Wavelet Technique
Analysis and Estimation of Harmonics Using Wavelet Technique
 
A Novel Method for Sensing Obscene Videos using Scene Change Detection
A Novel Method for Sensing Obscene Videos using Scene Change DetectionA Novel Method for Sensing Obscene Videos using Scene Change Detection
A Novel Method for Sensing Obscene Videos using Scene Change Detection
 
Robust SINS/GNSS Integration Method for High Dynamic Applications
Robust SINS/GNSS Integration Method for High Dynamic ApplicationsRobust SINS/GNSS Integration Method for High Dynamic Applications
Robust SINS/GNSS Integration Method for High Dynamic Applications
 
Study on Adaptive PID Control Algorithm Based on RBF Neural Network
Study on Adaptive PID Control Algorithm Based on RBF Neural NetworkStudy on Adaptive PID Control Algorithm Based on RBF Neural Network
Study on Adaptive PID Control Algorithm Based on RBF Neural Network
 
Solving Method of H-Infinity Model Matching Based on the Theory of the Model ...
Solving Method of H-Infinity Model Matching Based on the Theory of the Model ...Solving Method of H-Infinity Model Matching Based on the Theory of the Model ...
Solving Method of H-Infinity Model Matching Based on the Theory of the Model ...
 
A Review to AC Modeling and Transfer Function of DCDC Converters
A Review to AC Modeling and Transfer Function of DCDC ConvertersA Review to AC Modeling and Transfer Function of DCDC Converters
A Review to AC Modeling and Transfer Function of DCDC Converters
 
DTC Method for Vector Control of 3-Phase Induction Motor under Open-Phase Fault
DTC Method for Vector Control of 3-Phase Induction Motor under Open-Phase FaultDTC Method for Vector Control of 3-Phase Induction Motor under Open-Phase Fault
DTC Method for Vector Control of 3-Phase Induction Motor under Open-Phase Fault
 
Optimal Placement and Sizing of Distributed Generation Units Using Co-Evoluti...
Optimal Placement and Sizing of Distributed Generation Units Using Co-Evoluti...Optimal Placement and Sizing of Distributed Generation Units Using Co-Evoluti...
Optimal Placement and Sizing of Distributed Generation Units Using Co-Evoluti...
 
Similarity and Variance of Color Difference Based Demosaicing
Similarity and Variance of Color Difference Based DemosaicingSimilarity and Variance of Color Difference Based Demosaicing
Similarity and Variance of Color Difference Based Demosaicing
 
Energy Efficient RF Remote Control for Dimming the Household Applainces
Energy Efficient RF Remote Control for Dimming the Household ApplaincesEnergy Efficient RF Remote Control for Dimming the Household Applainces
Energy Efficient RF Remote Control for Dimming the Household Applainces
 
A Novel and Advanced Data Mining Model Based Hybrid Intrusion Detection Frame...
A Novel and Advanced Data Mining Model Based Hybrid Intrusion Detection Frame...A Novel and Advanced Data Mining Model Based Hybrid Intrusion Detection Frame...
A Novel and Advanced Data Mining Model Based Hybrid Intrusion Detection Frame...
 
Optimal Warranty Policy Considering Two-dimensional Imperfect Preventive Main...
Optimal Warranty Policy Considering Two-dimensional Imperfect Preventive Main...Optimal Warranty Policy Considering Two-dimensional Imperfect Preventive Main...
Optimal Warranty Policy Considering Two-dimensional Imperfect Preventive Main...
 

Kürzlich hochgeladen

Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
Health
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 

Kürzlich hochgeladen (20)

AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 

Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance

  • 1. TELKOMNIKA Indonesian Journal of Electrical Engineering Vol. 13, No. 2, February 2015, pp. 257 ~ 263 DOI: 10.11591/telkomnika.v13i2.6987  257 Received November 7, 2014; Revised December 25, 2014; Accepted January 10, 2015 Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance R. Ilango1* , T. Sree Renga Raja2 1 MAM School of Engineering, Tiruchirappalli, Tamil Nadu, India, 621105 2 Anna University, Anna University BIT Campus, Tiruchirappalli, Tamil Nadu, India, 620024 *Corresponding author, e-mail: ilangorengaraju@gmail.com Abstract This paper presents the impact of the Static Synchronous Compensator (STATCOM) on the performance of distance protection of EHV transmission lines. A 400kV transmission system having midpoint connected STATCOM with its control circuit is modeled using MATLAB/SIMULINK software. The impact of STATCOM on distance relay for different fault conditions and different fault locations is analyzed. Simulation results indicate that the presence of the STATCOM in the transmission system significantly changes the line impedance seen by the distance relay to be lower or higher than the actual line impedance. Due to this the performance of the distance relay changes, either overreaches or under reaches. Keywords: distance relay protection, flexible AC transmission system (FACTS), static synchronous compensators (STATCOM), EHV transmission line Copyright © 2015 Institute of Advanced Engineering and Science. All rights reserved. 1. Introduction The demand of electrical power is growing day by day with a very fast rate. To meet out this a significant modification in the conventional power system is required. The recent development of power electronics provides a solution by the way of using FACTS devices in the power systems. The FACTS devices which are connected in parallel, series or combination of both in the power system, enhance the system controllability and also increasing power transfer capability [1, 2]. Static synchronous compensator (STATCOM) is the most used shunt connected FACTS device which controls the connecting point bus voltage near stable and also enhance system stability by injecting or absorbing reactive power into the transmission system [3, 4]. Impedance based distance protection relays are widely used for protecting EHV/HV transmission lines due to their simple operating principle. The relay measures the apparent impedance of the fault loop by considering the voltage and current signals at the relay location, then the relay calculates the fault location by using this apparent impedance [5, 6] In distance relay due to the presence of STATCOM in the fault loop the measured voltage and current signals are changed. The measured current at the relay point decreases when the STATCOM injects reactive power into the power system and increases when the STATCOM draws reactive power from the system. Due to this change in the voltage and current signals the apparent impedance calculated by the distance relay changes. The distance relay will be over reach if the measured impedance is less than the actual measurement and the relay will be under reach when the impedance is greater than the actual measurement. So due to the presence of STATCOM in the fault loop the distance relay characteristics will be affected. Therefore, nowadays it is important to analyze the impact of STATCOM on the distance relay to design an adaptive protective scheme to get accurate fault location. Some researches have been done on the impact of different FACTS devices on the distance relay. K. El-Arroudi, G. Joos, and D. T. McGillis [7] present the analytical results based on the steady - state model of STATCOM, and outline the impact of STATCOM on different load levels. In [8] and [9] a comprehensive analysis of the impact of thyristor-controlled series capacitor (TCSC) on the protection of transmission lines has been presented showing that TCSC not only affects the protection of its line, but also the protection of adjacent line. The study in [10], demonstrates the impact of FACTS controllers and their location in the
  • 2.  ISSN: 2302-4046 TELKOMNIKA Vol. 13, No. 2, February 2015 : 257 – 263 258 transmission line on the trip boundary of a digital multifunctional protective relay. The work in [11], derivates apparent impedance calculation seen by a distance relay in the presence of a unified power flow controller (UPFC) based on the power frequency sequence component and also explains the effect of UPFC operational mode as well as its control parameters. Previous work [12] presents the Impact analysis of static synchronous series compensator (SSSC) on the performance of the digital distance relaying. In [13] various distance protection schemes for a midpoint compensated transmission line has been compared. The work reported in [14], demonstrates the impact of TCSC on the parameters of protective transmission line during a single phase to ground fault conditions. In this paper, the impact of midpoint connected STATCOM of the transmission line on distance relay protection is analyzed. First, a detailed model of STATCOM is presented then the performance of the distance relay for different fault conditions at different fault locations in the presence of STATCOM is analyzed and finally the results have been presented. 2. Study Test System The impact of the STATCOM on the performance of distance relays is studied using the model developed by the MATLAB/SIMULINK software [15]. The test transmission system model with STATCOM and distance relay are described in this section. 2.1. Transmission System Model with STATCOM The simulation diagram of the test system under analysis is shown in Figure 1. The test system consists of a 400kV 50 Hz, 300 km length transmission line, with two equivalent sources, source 1 and source 2 connected at the sending and receiving end respectively. The positive sequence resistance and zero sequence resistance of the line is 0.03 ohm/km and 0.25 ohm/km respectively. Similarly the positive sequence inductance and zero sequence inductance of the line is 1.01 mH/km and 3.73 mH/km respectively. The distance relay connected near the sending end source is considered for analysis. A 100 MVA, 48 pulse voltage source inverter based STATCOM is connected at the midpoint of the transmission line. The main objective of the STATCOM controller is to regulate the connecting point voltage of the transmission line to the setting value (Vref) by supplying or absorbing the reactive current [16, 17]. Figure 1. Test transmission simulation system implemented in MATLAB 2.2. Distance Relay model The distance relay model used for this analysis consists of six Mho distance elements, three elements for phase-to-phase loops and three elements for the phase- to-ground loops.
  • 3. TELKOMNIKA ISSN: 2302-4046  Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (R. Ilango) 259 The distance relay calculates the apparent impedance of the fault line considering the voltage and current signals at the relay location, then the fault location is calculated by considering the positive sequence impedance of the line [18]. The relay is assumed to be set to protect 80% (240km) of the transmission line. The Figure 2 shows the modeling of one element (“A” phase- to-ground element) of the distance relay used to locate the faults which occur in “A” phase. Figure 2. One element of the distance relay model 3. Simulation Results and Analysis To study the impact of STATCOM on the performance of distance relay various types of faults have been applied on the test transmission system at various locations. Although several cases involving all types of faults with different fault resistances at different locations of the transmission line have been simulated, only two cases, namely, “A” phase to ground fault with a fault resistance of zero ohm and three phase to ground fault with a fault resistance of zero ohm are presented. 3.1. The Effect of Single Phase Fault The test results of the test system with STATCOM and without STATCOM for “A” phase to ground fault is shown in Table 1. It clearly shows that, when the fault occurs between the relay point and the STATCOM location (between 10 and 150 kilometers in this case), there is no much change on the apparent impedance, measured by the distance relay i.e. the measured impedance is almost the same as that for the system without STATCOM. Table 1. Variations of the apparent impedance for single phase-to- ground fault Fault location in Km Apparent impedance in ohms Without STATCOM Apparent impedance in ohms With STATCOM 20 06.35 06.37 40 12.69 12.73 60 19.00 19.08 80 25.28 25.42 100 31.53 31.53 120 37.77 37.75 140 43.28 43.43 160 50.18 51.05 180 56.59 58.01 200 62.59 65.11 220 68.83 72.38 240 75.15 79.94 260 81.65 87.94 280 88.54 96.80
  • 4.  ISSN: 2302-4046 TELKOMNIKA Vol. 13, No. 2, February 2015 : 257 – 263 260 For example, when the fault is occurring at 140 km, the apparent impedance measured by the distance relay without connecting the STATCOM in the fault line is 43.28 ohms, and with the STATCOM is 43.43 ohms. This is due to the fact, that when the STATCOM is not present in the fault loop for zero fault resistance, the measured impedance is equal to the actual line impedance of the line section between the relay point and the fault point. When the fault (‘A’ phase-to-ground fault) occurs beyond the STATCOM location, (between 150 and 300 kilometers in this case) the apparent impedance of the system is greater than that for the system without STATCOM, since the STATCOM involves in the fault loop; the injected/absorbed current of the STATCOM changes the apparent impedance measured by the distance relay. The apparent impedance seen by the distance relay with STATCOM and without STATCOM for single phase fault occurring for fault distance of 240 km is shown in Figure 3; from this it is evident that the apparent impedance seen by the distance relay is higher than that of the system without STATCOM. So the protection zone of the distance relay under reaches its setting and does not give the trip signal. Figure 3. The apparent impedance seen by the relay for single phase fault The plot of apparent resistance measured at the relay location for “A” phase to ground fault created at various locations of the transmission line with STATCOM and without STATCOM is depicted in Figure 4. It shows that when the fault occurs before the STATCOM location (i.e., <150km), the apparent resistance is almost same as that of the apparent resistance without STATCOM, but when the fault occurs after the STATCOM location the apparent resistance decreases. Figure 4. Apparent resistance versus fault location plots for single phase fault -20 -10 0 10 20 30 40 50 60 70 80 -10 0 10 20 30 40 50 60 70 80 90 100 apparent resistance (ohms) apparentreactance(ohms) With STATCOM Without STATCOM 0 50 100 150 200 250 300 0 5 10 15 20 25 30 distance (km) apparentresistance(ohms) Without STATCOM With STATCOM
  • 5. TELKOMNIKA ISSN: 2302-4046  Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (R. Ilango) 261 Figure 5 shows the plot of apparent reactance measured at the relay location for “A” phase to ground fault created at various locations of the transmission line with STATCOM and without STATCOM. It is apparent that when the fault occurs before the STATCOM location the apparent reactance is almost same, but when the fault occurs after the STATCOM location the apparent reactance increases compared to the apparent reactance of the system without STATCOM. Figure 5. Apparent reactance versus fault location plots for single phase fault This is mainly due to the fact that when the fault occurs after the STATCOM location the STATCOM supplies the reactive power to the connecting point, so the apparent reactance of the transmission line increases and the apparent resistance of the transmission line decreases. Further from analysis, it is apparent that the presence of the STATCOM in the transmission system significantly affects the apparent resistance and apparent reactance measured by the distance relay under single phase fault conditions. 3.2. The Effect of Three Phase Fault When three phase fault is created at a distance of 240 km, the apparent impedance measured by the distance relay with STATCOM is 83.40 ohms, and without STATCOM is 78.75 ohms respectively. The impedance trajectory of the distance relay for three phase faults created at a distance of 240 km with STATCOM and without STATCOM is shown in Figure 6; it clearly shows that the apparent impedance seen by the relay is greater than that of the system without STATCOM. So the protection zone of the distance relay under reaches its setting and does not give the trip signal. Figure 6. The apparent impedance seen by the relay for three phase fault 0 50 100 150 200 250 300 0 20 40 60 80 100 120 distance (km) apparentreactance(ohms) With STATCOM Without STATCOM -40 -20 0 20 40 60 80 -10 0 10 20 30 40 50 60 70 80 90 100 apparent resistance (ohms) apparentreactance(ohms) Without STATCOM With STATCOM
  • 6.  ISSN: 2302-4046 TELKOMNIKA Vol. 13, No. 2, February 2015 : 257 – 263 262 The apparent resistance versus fault location and apparent reactance versus fault location plots of transmission system with and without STATCOM for three phase fault are shown in Figure 7 and Figure 8 respectively. Figure 7. Apparent resistance versus fault location plots for three phase fault Figure 8. Apparent reactance versus fault location plots for three phase fault The inference of the Figure 7 and Figure 8 shows that, when the three phase fault occurs between the relay point and the STATCOM location the measured apparent resistance and reactance of the system are almost same as that of the system without STATCOM. However, when the fault occurs beyond the STATCOM location, both the apparent resistance and reactance of the system are greater than that of the system without STATCOM. It is evident that like single phase fault the three phase fault also having the same impact on the performance of the distance relay in the presence of the STATCOM in the transmission system. 4. Conclusion The performance of the distance relay in the presence of STATCOM has been analyzed for different fault conditions and different fault locations. From the simulation results it is evident that during a fault, the injected or absorbed current of the STATCOM produces an error in impedance measurement and because of this under /over reach of the distance relay happens. The results clearly show that the connection of the STATCOM at the midpoint of the transmission line affects the performance of the distance relay. Therefore, when a transmission line system is connected with STATCOM, the conventional distance relay characteristics are not usable. So there is a need for distance relay to adjust to new settings in its characteristics and to be adapted to the system conditions in order to avoid mal operation. 0 50 100 150 200 250 300 0 2 4 6 8 10 12 distance (km) apparentresistance(ohms) Without STATCOM With STATCOM 0 50 100 150 200 250 300 0 10 20 30 40 50 60 70 80 90 100 distance (km) apparentreactance(ohms) With STATCOM Without STATCOM
  • 7. TELKOMNIKA ISSN: 2302-4046  Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance (R. Ilango) 263 References [1] Hingorani NG, Gyugyi L. Understanding FACTS: Concepts and Technology of Flexible Transmission Systems. New York: IEEE Press. 2000. [2] Hingorani NG. FACTS-Flexible AC Transmission System. Proceedings of 5th International Conference on AC and DC Power Transmission. IEE Conference. 1991; 345: 1-7. [3] Adido MA. Power System Stability Enhancement Using FACTS Controllers: A Review. The Arabian Journal for Science and Engineering. 2009; 34 (1B): 153-172. [4] Haniyeh Marefatjou, Mohammad Sarvi. Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage Stability and Loadability Amplification in Power System. International Journal of Applied Power Engineering. 2013; 2(1):15-26. [5] Phadke AG, lbrahim M, Hblika T. Fundamental Basis for Distance Relaying with Symmetrical Components. IEEE Transactions on Power Apparatus and Systems. 1977; 635-676. [6] AREVA TD. Network Protection & Automation Guide. Second edition. France. AREVA. 2010. [7] El-Arroudi K, Joos G, McGillis DT. Operation of impedance protection relays with the STATCOM. IEEE Transaction on Power Delivery. 2002; 17(2): 381–387. [8] Khederzadeh M, Sidhu TS. Impact of TCSC on the protection of transmission lines. IEEE Transaction on Power Delivery. 2006; 21(1): 80–87. [9] Sidhu TS, Khederzadeh M. TCSC impact on communication aided distance protection schemes and its mitigation. IEE Proc. Generation, Transmission and Distribution. 2005; 152(5): 714– 728. [10] Khederzadeh M. The impact of FACTS device on digital multifunctional protective relays. T & D Conference and Exhibition IEEE/PES. Asia Pacific. 2002; 3: 2043–2048. [11] Zhou X, Wang H, Aggarwal RK, Beaumont P. Performance evaluation of a distance relay as applied to a transmission system with UPFC. IEEE Transaction on Power Delivery. 2006; 21 (3):1137– 1147. [12] Khederzadeh M, Ghorbani A, Salemnia A. Impact of SSSC on the digital distance relaying. IEEE/PES, Power &Energy Society General Meeting. PES’09. 2009; 1-8. [13] Albasri FA, Sidhu TS, Varma RK. Performance comparison of distance protection schemes for shunt- FACTS compensated transmission lines. IEEE Transaction on Power Del. 2007; 22(4): 2116-2125. [14] Mohamed Zellagui, Abdelaziz Chaghi. Impact of Thyristor Controlled Series Capacitor Insertion on Short-Circuit Calculation in Presence Phase to Earth Fault. International Journal of Applied Power Engineering. 2012; 1 (2): 93-104. [15] Sybille G, Le-Huy, Hoang. Digital simulation of power systems and power electronic using the MATLAB/Simulink Power System Blockset. Power Engineering Society Winter Meeting. 2000; 4: 2973-2981. [16] EI-Moursi MS, Haraf AM. Novel controllers for the 48- pulse VSC STATCOM and SSSC for voltage regulation and reactive power compensation. IEEE Transaction on Power System. 2005; 20(4):1985- 1987. [17] Pranesh Rao, Crow ML, Zhiping Yang. STATCOM Control for Power System Voltage Control Applications. IEEE Trans. On Power Delivery. 2000; 15(4): 1311-1317. [18] Zigler G. Numerical Distance Protection: Principles and Applications. Third edition. Germany. Publics Corporate. 2008.