Presented By:
Prof. (Dr.) Pravat Kumar Rout
Sheetal Chandak, Senior Research Fellow, CSIR, India
Department of Electrical and Electronics Engineering
Siksha ‘O’ Anusandhan University
 A power outage (also called a power cut, a power
out, a power blackout, power failure or
a blackout) is the loss of the electrical
power network supply to an end user.
 Power outages are categorized into three different
phenomena, relating to the duration and effect of the
outage:
➢ Faults.
➢ Brownouts.
➢ Blackouts.
 A Brownouts is an intentional or unintentional drop
in voltage in an electrical power supply system. Intentional
brownouts are used for load reduction in an emergency.
 The reduction lasts for minutes or hours, as opposed to short-
term voltage sag (or dip). The term brownout comes from the
dimming experienced by incandescent lighting when the
voltage sags.
 A voltage reduction may be an effect of disruption of
an electrical grid, or may occasionally be imposed in an effort
to reduce load and prevent a power outage, known as
a blackout.
 Blackout occurs when electricity demand exceed the
supply. In that case, an imbalance is said to exist between
generation and consumption.
 These cause load imbalance which can lead to frequency
decay, initial power deficiency, dangerous cascade effects, or
even shutdown of one or more generators.
▪ Blackouts affects utilities, ships,
refineries, mines, industrial
processes and almost every
power system in the world.
 Three main factors generally cause collapse incidents
worldwide.
✓First factor is loading limitation of transmission
line.
✓Second factor is load behaviour including on load
tap changer performance.
✓Third factor is the influence of protection and
control systems.
 The largest power outage in world history that
occurred in New Delhi in July 2012.
Factors for collapse included:
✓Weak interregional power transmission corridors
caused by multiple outages.
✓High loading on the 400 kV Bina–Gwalior–Agra
link, leading to the mis-operation of its protection
scheme.
✓Balancing excess generation caused by the load
shed.
Number of power outage in different parts of world [1]
 A selective power cut is a controlled shutdown
(Load Shedding) of the power supply in a given
area, so as to avoid a blackout.
 Various load shedding (LS) strategies adopted to
restore the generated and absorbed power balance.
 Load shedding is a way to distribute demand
for electrical power across multiple power sources.
 Load shedding is occurred by the deliberate electric power in
parts of a power distribution network to prevent the failure of
the entire system when demand exceeds supply.
 It is used to relieve stress on a primary energy source when
demand for electricity is greater than the primary power
source can supply.
 Stage 1 allows for up to 1000 MW of the
national load to be shed.
 Stage 2 allows for up to 2000 MW of the
national load to be shed.
 Stage 3 allows for up to 3000 MW of the national
load to be shed.
 Stage 4 allows for up to 4000 MW of the
national load to be shed.
Three main issues have to be considered for load
shedding:
 The amount of load for shedding,
 The timing to execute load shedding event,
 The appropriate location for load shedding.
 Tripping appropriate amount of load is a crucial deciding
factor in restoring the instability of a power system
network.
 Tripping fewer loads than necessary will not effectively
overcome voltage collapse.
 Tripping an excessive amount of load may raise a new
concern, which is the over frequency condition, because the
system will generate load in excess of the load demand.
 Load characteristics serve an important function in
determining the capability of an unstable power system to
regain its stability after the disturbance.
 Two types of load models that influence the amount of load
curtailment are static and dynamic loads.
 Static loads represent the active and reactive power consumed
by the load at a particular instant of time as a function of the
bus voltage and frequency at that instant.
 In steady state power analysis, system frequency is considered
constant, such that the power consumed is a function of the
bus voltage alone.
 By contrast, dynamic load models consider the time-varying
nature of the operating characteristics of power system
components, including induction motors, discharge-type
lamps, as well as thermostatically controlled loads, such as air
conditioners and under load tap changers.
 The load buses are usually categorized in the order of
the weakest bus to the strongest bus.
 Graphically obtained from the PQ curve, the weakest
bus tends to have the highest dV/dQ component and
tends to be more susceptible to voltage collapse.
 Consequently, the weakest bus is the most appropriate
candidate for load shedding.
 The timing of load shedding performance should consider the
amount of load shed and the location.
 Various system components attempt recovery at different time
frames.
 The minimum amount of time allowed before a LSS is activated is
the time taken from the commencement of system parameters
collapse.
 Moreover, the maximum amount of time allowed before a LSS is
triggered is the time taken for all the intervening system
components to attempt system recovery.
 Research undertaken to compute for the timing of load shedding
occurrence involves dynamic simulations for load shedding.
Load Shedding Strategies
(LSS)
Conventional
Load Shedding
Strategies
Adaptive Load
Shedding Strategies
Intelligent Load
Shedding Strategies
Under
Frequency
LSS
Under Voltage
LSS
Artificial
Neural
Network LSS
Fuzzy Logic
Control LSS
Adaptive Neuro
Fuzzy Inference
System
Optimisation
Algorithm
 The basic guideline in designing a UVLS scheme developed by the
Technical Studies Subcommittee of Under voltage Load Shedding Task
Force of Western Systems Coordinating Council (WSCC) :
i. Load shedding scheme should be designed to coordinate with protective
devices and control schemes for momentary voltage dips, sustained faults,
low voltages caused by stalled air conditioners, and so on.
ii. Time delay to initiate load dropping should be in seconds, not in cycles. A
typical time delay varies between 3 seconds and 10 seconds.
iii. UVLS relays must be on PTs that are connected above automatic LTCs.
iv. Voltage pick-up points for the tripping signal should be set reasonably
higher than the “nose point” of the critical P-V or Q-V curve.
v. Voltage pick-up points and the time delays of the local neighbouring
systems should be checked and coordinated.
vi. Redundancy and adequate intelligence should be built into the
scheme to ensure reliable operation and to prevent false tripping.
vii. Sufficient load should be shed to bring voltages to the minimum
operating voltage levels or higher.
 The VAR margin should be maintained according to the Voltage
Stability Criteria of the WSCC.
 UVLS has become the preferred strategy of power utilities because
it is a cost-effective solution to address voltage stability issues.
 The European Network of Transmission System Operators for
Electricity (ENTSOE) with a system of 50Hz has recommended
the following steps for under frequency load shedding:
i. The first stage of automatic load shedding should be initiated at 49
Hz.
ii. At 49 Hz, at least 5% of total consumption should be shed.
iii. A stepwise 50% of the nominal load should be disconnected by
using under frequency relays in the frequency range of 49.0–48.0
Hz.
iv. In each step of load shedding, a disconnection of no more than 10%
of the load is advised.
v. The maximum disconnection delay should be 350 ms including
breakers’ operating time.
 Recommendation for power plants to attain safe operation:
i. At 49.8 Hz, ‘quick-start’ plants should be connected to the grid.
ii. For a power system operating within 50 Hz (60 Hz) frequency, the
minimum allowable operating frequency usually specified by the
manufacturer according to the turbine type is 47.5 Hz (57.5 Hz) .
 This is necessary because
✓ The protection of the generator and its auxiliary equipment because
power plant auxiliary services begin to malfunction at a frequency
of 47.5 Hz; the situation becomes critical at about 44–46 Hz.
✓ Generator operation at 47.5 Hz or below could damage the turbine
blades and reduce its lifespan .
 Disadvantage :
✓ It does not estimate the actual
amount of the power imbalance.
 Thus result in either of the two:
✓ Over-shedding, which affects power
quality.
✓ Under-shedding, which leads to
tripping of electricity service.
Flowchart of the conventional LSS
 The strategy employs power swing
equation to shed the required amount of
loads.
 The power imbalance within the system
can be obtained by:
 Whenever system disturbance, there is a
variation in frequency as well as rate of
change of frequency(ROCOF).
 Using the equation, the power imbalance
is estimated, which helps to calculate the
required amount of load to be shed.
t
f
f
H
P


=
2
Flowchart of the adaptive LSS
 Advantages:
✓ This approach of load shedding can be applied to an
isolated power system with a single generation unit as well
as to an interconnected power system.
✓ Enhances the reliability of frequency and voltage stability.
✓ Enhanced transient behaviour when encountering severe
disturbance.
 Disadvantages:
✓ The values of ROCOF are different for similar amount of
load variations at base and peak capacity.
✓ Strategy suffers un-optimum estimation of power
imbalance due to the variations in ROCOF.
 The term ‘computational intelligence techniques (CIT)’
generally refers to a set of techniques that are applied to mimic
human intelligence.
 These techniques include:
✓ Artificial neural networks (ANN),
✓ Adaptive neuro-fuzzy inference system (ANFIS),
✓ Fuzzy logic control (FLC),
✓ Genetic algorithms (GA), and
✓ Particle swarm optimizations (PSO).
 These techniques can easily solve those nonlinear, multi-
objective problems in power systems that cannot be solved by
the conventional methods with the desired speed and accuracy
 ANN is a mathematical model based on human neural systems.
 The ANN training process:
✓ Three inputs – total generation, total load demand, and
frequency decay rate
✓ One output – minimum amount of load shedding.
 Advantage: The proposed ANN technique performed load
shedding more quickly as compared with the conventional
technique.
 Disadvantage: ANN can provide satisfactory results for known
(trained) cases only. ANN fails to predict accurate results for
unknown (untrained) or varying cases.
 FLC is a mathematical tool suitable for modelling a system
which is too complex and not well defined by mathematical
formulation.
 Some of these applications include load frequency control,
unified power flow controller (UPFC) application, flexible AC
transmission system (FACTS) application, and reactive
power/voltage control.
 The proposed technique was formulated on frequency (f),
rate of change of frequency (df/dt), and load prioritization.
 The ANFIS method is based on the combination of
artificial neural networks and fuzzy logic control.
 It combines the learning abilities of ANN with the fuzzy
interpretation of the FLC system.
 Drawbacks: It can only work with Sugeno-type systems.
 Genetic algorithms (GA) are the global optimization
technique for solving non-linear, multi-objective problems.
 The database for load shedding problems is obtained from a
power flow study and is successfully implemented on the
power system.
 The results indicate that the GA-based technique is feasible
and effective in providing optimal load shedding.
 Drawbacks:
✓ It has been observed that the computation time of GAs to
determine the amount of load shed is very large.
✓ This slow response limits their usage for online application.
 PSO has been proved as a robust and fast technique in solving
non-linear, multi-objective problems.
 PSO finds the global optimum solution more quickly as
compared to genetic algorithms.
 PSO ability of taking only minimal time may encourage its
implementation for real-time optimal load shedding in power
systems.
 Disadvantage: PSO is easily interrupted by partial
optimization.
 The GA and PSO techniques were used to solve generator
outage and line outage cases, and were validated on the
IEEE 30-bus system.
 The responses of GA and PSO in all the case studies,
results to show that: in terms of computation time ,PSO is
faster than GA; the minimum amount of load is shed by
GA
 Recent power blackouts that have occurred around the world make
the reliability of conventional UFLS techniques questionable.
 Conventional UFLS techniques are not suitable for today’s large
and complex power systems.
 Computational intelligence techniques have the ability to deal with
such modern power systems efficiently.
 Computational intelligence techniques in load shedding can reduce
the possibility of blackouts, and enhance the power system’s
reliability.
 Improvements are still needed to make these techniques compatible
with real-time applications.
 Verayiah, R., Mohamed, A., Shareef, H., & Abidin, I. Z. (2014). Review of under-
voltage load shedding schemes in power system operation. Przegląd
elektrotechniczny, 90(7), 99-103.
 Shoaib, M., & Ahmed, F. (2016, December). A Systematic Literature Review of
Optimal Load Shedding Models. In Proc. of Second Int. Multi-Disciplinary
Conf (Vol. 19, p. 20).
 Laghari, J. A., Mokhlis, H., Bakar, A. H. A., & Mohamad, H. (2013). Application
of computational intelligence techniques for load shedding in power systems: A
review. Energy conversion and management, 75, 130-140.
 Chang, L., & Wu, Z. (2011). Performance and reliability of electrical power grids
under cascading failures. International Journal of Electrical Power & Energy
Systems, 33(8), 1410-1419.
 Chandak, S., Bhowmik, P., & Rout, P. K. (2019). Load shedding strategy
coordinated with storage device and D-STATCOM to enhance the microgrid
stability. Protection and Control of Modern Power Systems, 4(1), 22.
 Chandak, S., Bhowmik, P., & Rout, P. K. (2019). Robust power balancing scheme
for the grid-forming microgrid. IET Renewable Power Generation, 14(1), 154-163.
 Mollah, K., Bahadornejad, M., Nair, N. K., & Ancell, G. (2012, July). Automatic
under-voltage load shedding: A systematic review. In 2012 IEEE Power and
Energy Society General Meeting (pp. 1-7). IEEE.
 Bakar, N. N. A., Hassan, M. Y., Sulaima, M. F., Na’im Mohd Nasir, M., & Khamis,
A. (2017). Microgrid and load shedding scheme during islanded mode: A
review. Renewable and Sustainable Energy Reviews, 71, 161-169.
 Lakra, P., & Kirar, M. (2015). Load shedding techniques for system with
cogeneration: A review. Electrical and Electronics Engineering: An
International, 4(3).
 Mollah, K. U. Z., Bahadornejad, M., & Nair, N. K. (2011, September). Automatic
under-frequency load shedding in New Zealand power system—A systematic
review. In AUPEC 2011 (pp. 1-7). IEEE.
Class 16 load shedding

Weitere ähnliche Inhalte

Was ist angesagt?

Was ist angesagt? (20)

Facts controllers
Facts controllersFacts controllers
Facts controllers
 
Small signal stability analysis
Small signal stability analysisSmall signal stability analysis
Small signal stability analysis
 
Distributed Generation
Distributed Generation Distributed Generation
Distributed Generation
 
Microgrid
MicrogridMicrogrid
Microgrid
 
Protection and control of Microgrid
Protection and control of MicrogridProtection and control of Microgrid
Protection and control of Microgrid
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Power quality ppt
Power quality pptPower quality ppt
Power quality ppt
 
WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)
 
statcom
statcomstatcom
statcom
 
Power System Stabilizer
Power System StabilizerPower System Stabilizer
Power System Stabilizer
 
POWER QUALITY IMPROVEMENT BY DSTATCOM
POWER QUALITY IMPROVEMENT BY DSTATCOMPOWER QUALITY IMPROVEMENT BY DSTATCOM
POWER QUALITY IMPROVEMENT BY DSTATCOM
 
FACTS DEVICES
FACTS DEVICESFACTS DEVICES
FACTS DEVICES
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Unit commitment
Unit commitmentUnit commitment
Unit commitment
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENT
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoring
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issues
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 

Ähnlich wie Class 16 load shedding

IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET Journal
 
Voltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideVoltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load side
eSAT Journals
 
Under frequency load shedding for energy management using anfis case study
Under frequency load shedding for energy management using anfis case studyUnder frequency load shedding for energy management using anfis case study
Under frequency load shedding for energy management using anfis case study
IAEME Publication
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
pamu17
 
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
ssuser3793c8
 

Ähnlich wie Class 16 load shedding (20)

Voltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powerVoltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive power
 
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
 
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
 
Et33879883
Et33879883Et33879883
Et33879883
 
Et33879883
Et33879883Et33879883
Et33879883
 
Voltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideVoltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load side
 
WAMS Applications , Wide Area Monitoring Systems WAMS
WAMS Applications , Wide Area Monitoring Systems WAMSWAMS Applications , Wide Area Monitoring Systems WAMS
WAMS Applications , Wide Area Monitoring Systems WAMS
 
Under voltage load shedding for contingency analysis to optimize power loss ...
Under voltage load shedding for contingency analysis to  optimize power loss ...Under voltage load shedding for contingency analysis to  optimize power loss ...
Under voltage load shedding for contingency analysis to optimize power loss ...
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
Energy Management by Adaptive Neuro-Fuzzy For Under Frequency Load Shedding/C...
Energy Management by Adaptive Neuro-Fuzzy For Under Frequency Load Shedding/C...Energy Management by Adaptive Neuro-Fuzzy For Under Frequency Load Shedding/C...
Energy Management by Adaptive Neuro-Fuzzy For Under Frequency Load Shedding/C...
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationEfficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
 
Under frequency load shedding for energy management using anfis case study
Under frequency load shedding for energy management using anfis case studyUnder frequency load shedding for energy management using anfis case study
Under frequency load shedding for energy management using anfis case study
 
An Automatic Load Controller for Domestic Applications
An Automatic Load Controller for Domestic ApplicationsAn Automatic Load Controller for Domestic Applications
An Automatic Load Controller for Domestic Applications
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
 
Under voltage load shedding
Under voltage load sheddingUnder voltage load shedding
Under voltage load shedding
 
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
 
CHAPTER- 4.ppt
CHAPTER- 4.pptCHAPTER- 4.ppt
CHAPTER- 4.ppt
 
The Enhanced Performance SVC for Transient Instability Oscillation Damping
The Enhanced Performance SVC for Transient Instability Oscillation DampingThe Enhanced Performance SVC for Transient Instability Oscillation Damping
The Enhanced Performance SVC for Transient Instability Oscillation Damping
 
voltage stability by compensating reactive power
voltage stability by compensating reactive powervoltage stability by compensating reactive power
voltage stability by compensating reactive power
 

Mehr von Siksha 'O' Anusandhan (Deemed to be University )

Mehr von Siksha 'O' Anusandhan (Deemed to be University ) (20)

Defining the Research Problem .pdf
Defining the Research Problem .pdfDefining the Research Problem .pdf
Defining the Research Problem .pdf
 
phd Thesis and Paper writing.pdf
phd Thesis and Paper writing.pdfphd Thesis and Paper writing.pdf
phd Thesis and Paper writing.pdf
 
Presentation.pdf
Presentation.pdfPresentation.pdf
Presentation.pdf
 
An Introduction to Research Methodology.pdf
An Introduction to Research Methodology.pdfAn Introduction to Research Methodology.pdf
An Introduction to Research Methodology.pdf
 
Dr. P.K. Rout Final_my jouney.pdf
Dr. P.K. Rout Final_my jouney.pdfDr. P.K. Rout Final_my jouney.pdf
Dr. P.K. Rout Final_my jouney.pdf
 
VIRTUAL POWER PLANT (VPP).pdf
VIRTUAL POWER PLANT (VPP).pdfVIRTUAL POWER PLANT (VPP).pdf
VIRTUAL POWER PLANT (VPP).pdf
 
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
 
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
Robust Active Power Filter Controller Design for Microgrid and Electric Vehic...
 
Design and implementation of active power filter for harmonic elimination and...
Design and implementation of active power filter for harmonic elimination and...Design and implementation of active power filter for harmonic elimination and...
Design and implementation of active power filter for harmonic elimination and...
 
Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...
Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...
Topologies and Controls for Optimal Energy Bifurcation in AC, DC, and Hybrid ...
 
Final talk trident-05-10-2021- dr p k rout-converted
Final talk trident-05-10-2021- dr p k rout-convertedFinal talk trident-05-10-2021- dr p k rout-converted
Final talk trident-05-10-2021- dr p k rout-converted
 
Role of teachers in technical education
Role of teachers in technical educationRole of teachers in technical education
Role of teachers in technical education
 
Technical presentation format for M.Tech, Ph.D. students
Technical presentation format for M.Tech, Ph.D. students Technical presentation format for M.Tech, Ph.D. students
Technical presentation format for M.Tech, Ph.D. students
 
Integrated protection and control strategies for microgrid
Integrated protection and control strategies for microgrid Integrated protection and control strategies for microgrid
Integrated protection and control strategies for microgrid
 
Integrated protection and control strategies for microgrid
Integrated protection and control strategies for microgridIntegrated protection and control strategies for microgrid
Integrated protection and control strategies for microgrid
 
Differential evolution optimization technique
Differential evolution optimization techniqueDifferential evolution optimization technique
Differential evolution optimization technique
 
Hebb network
Hebb networkHebb network
Hebb network
 
Mc culloch pitts neuron
Mc culloch pitts neuronMc culloch pitts neuron
Mc culloch pitts neuron
 
Defuzzification
DefuzzificationDefuzzification
Defuzzification
 
Fuzzy relations and fuzzy compositional rules
Fuzzy relations  and fuzzy compositional rulesFuzzy relations  and fuzzy compositional rules
Fuzzy relations and fuzzy compositional rules
 

Kürzlich hochgeladen

+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
Health
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 

Kürzlich hochgeladen (20)

Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Bridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxBridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptx
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Air Compressor reciprocating single stage
Air Compressor reciprocating single stageAir Compressor reciprocating single stage
Air Compressor reciprocating single stage
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
Rums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfRums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdf
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 

Class 16 load shedding

  • 1. Presented By: Prof. (Dr.) Pravat Kumar Rout Sheetal Chandak, Senior Research Fellow, CSIR, India Department of Electrical and Electronics Engineering Siksha ‘O’ Anusandhan University
  • 2.  A power outage (also called a power cut, a power out, a power blackout, power failure or a blackout) is the loss of the electrical power network supply to an end user.  Power outages are categorized into three different phenomena, relating to the duration and effect of the outage: ➢ Faults. ➢ Brownouts. ➢ Blackouts.
  • 3.  A Brownouts is an intentional or unintentional drop in voltage in an electrical power supply system. Intentional brownouts are used for load reduction in an emergency.  The reduction lasts for minutes or hours, as opposed to short- term voltage sag (or dip). The term brownout comes from the dimming experienced by incandescent lighting when the voltage sags.  A voltage reduction may be an effect of disruption of an electrical grid, or may occasionally be imposed in an effort to reduce load and prevent a power outage, known as a blackout.
  • 4.  Blackout occurs when electricity demand exceed the supply. In that case, an imbalance is said to exist between generation and consumption.  These cause load imbalance which can lead to frequency decay, initial power deficiency, dangerous cascade effects, or even shutdown of one or more generators. ▪ Blackouts affects utilities, ships, refineries, mines, industrial processes and almost every power system in the world.
  • 5.  Three main factors generally cause collapse incidents worldwide. ✓First factor is loading limitation of transmission line. ✓Second factor is load behaviour including on load tap changer performance. ✓Third factor is the influence of protection and control systems.
  • 6.  The largest power outage in world history that occurred in New Delhi in July 2012. Factors for collapse included: ✓Weak interregional power transmission corridors caused by multiple outages. ✓High loading on the 400 kV Bina–Gwalior–Agra link, leading to the mis-operation of its protection scheme. ✓Balancing excess generation caused by the load shed.
  • 7. Number of power outage in different parts of world [1]
  • 8.  A selective power cut is a controlled shutdown (Load Shedding) of the power supply in a given area, so as to avoid a blackout.  Various load shedding (LS) strategies adopted to restore the generated and absorbed power balance.  Load shedding is a way to distribute demand for electrical power across multiple power sources.
  • 9.  Load shedding is occurred by the deliberate electric power in parts of a power distribution network to prevent the failure of the entire system when demand exceeds supply.  It is used to relieve stress on a primary energy source when demand for electricity is greater than the primary power source can supply.
  • 10.  Stage 1 allows for up to 1000 MW of the national load to be shed.  Stage 2 allows for up to 2000 MW of the national load to be shed.  Stage 3 allows for up to 3000 MW of the national load to be shed.  Stage 4 allows for up to 4000 MW of the national load to be shed.
  • 11. Three main issues have to be considered for load shedding:  The amount of load for shedding,  The timing to execute load shedding event,  The appropriate location for load shedding.
  • 12.  Tripping appropriate amount of load is a crucial deciding factor in restoring the instability of a power system network.  Tripping fewer loads than necessary will not effectively overcome voltage collapse.  Tripping an excessive amount of load may raise a new concern, which is the over frequency condition, because the system will generate load in excess of the load demand.  Load characteristics serve an important function in determining the capability of an unstable power system to regain its stability after the disturbance.
  • 13.  Two types of load models that influence the amount of load curtailment are static and dynamic loads.  Static loads represent the active and reactive power consumed by the load at a particular instant of time as a function of the bus voltage and frequency at that instant.  In steady state power analysis, system frequency is considered constant, such that the power consumed is a function of the bus voltage alone.  By contrast, dynamic load models consider the time-varying nature of the operating characteristics of power system components, including induction motors, discharge-type lamps, as well as thermostatically controlled loads, such as air conditioners and under load tap changers.
  • 14.  The load buses are usually categorized in the order of the weakest bus to the strongest bus.  Graphically obtained from the PQ curve, the weakest bus tends to have the highest dV/dQ component and tends to be more susceptible to voltage collapse.  Consequently, the weakest bus is the most appropriate candidate for load shedding.
  • 15.  The timing of load shedding performance should consider the amount of load shed and the location.  Various system components attempt recovery at different time frames.  The minimum amount of time allowed before a LSS is activated is the time taken from the commencement of system parameters collapse.  Moreover, the maximum amount of time allowed before a LSS is triggered is the time taken for all the intervening system components to attempt system recovery.  Research undertaken to compute for the timing of load shedding occurrence involves dynamic simulations for load shedding.
  • 16. Load Shedding Strategies (LSS) Conventional Load Shedding Strategies Adaptive Load Shedding Strategies Intelligent Load Shedding Strategies Under Frequency LSS Under Voltage LSS Artificial Neural Network LSS Fuzzy Logic Control LSS Adaptive Neuro Fuzzy Inference System Optimisation Algorithm
  • 17.  The basic guideline in designing a UVLS scheme developed by the Technical Studies Subcommittee of Under voltage Load Shedding Task Force of Western Systems Coordinating Council (WSCC) : i. Load shedding scheme should be designed to coordinate with protective devices and control schemes for momentary voltage dips, sustained faults, low voltages caused by stalled air conditioners, and so on. ii. Time delay to initiate load dropping should be in seconds, not in cycles. A typical time delay varies between 3 seconds and 10 seconds. iii. UVLS relays must be on PTs that are connected above automatic LTCs. iv. Voltage pick-up points for the tripping signal should be set reasonably higher than the “nose point” of the critical P-V or Q-V curve.
  • 18. v. Voltage pick-up points and the time delays of the local neighbouring systems should be checked and coordinated. vi. Redundancy and adequate intelligence should be built into the scheme to ensure reliable operation and to prevent false tripping. vii. Sufficient load should be shed to bring voltages to the minimum operating voltage levels or higher.  The VAR margin should be maintained according to the Voltage Stability Criteria of the WSCC.  UVLS has become the preferred strategy of power utilities because it is a cost-effective solution to address voltage stability issues.
  • 19.  The European Network of Transmission System Operators for Electricity (ENTSOE) with a system of 50Hz has recommended the following steps for under frequency load shedding: i. The first stage of automatic load shedding should be initiated at 49 Hz. ii. At 49 Hz, at least 5% of total consumption should be shed. iii. A stepwise 50% of the nominal load should be disconnected by using under frequency relays in the frequency range of 49.0–48.0 Hz. iv. In each step of load shedding, a disconnection of no more than 10% of the load is advised. v. The maximum disconnection delay should be 350 ms including breakers’ operating time.
  • 20.  Recommendation for power plants to attain safe operation: i. At 49.8 Hz, ‘quick-start’ plants should be connected to the grid. ii. For a power system operating within 50 Hz (60 Hz) frequency, the minimum allowable operating frequency usually specified by the manufacturer according to the turbine type is 47.5 Hz (57.5 Hz) .  This is necessary because ✓ The protection of the generator and its auxiliary equipment because power plant auxiliary services begin to malfunction at a frequency of 47.5 Hz; the situation becomes critical at about 44–46 Hz. ✓ Generator operation at 47.5 Hz or below could damage the turbine blades and reduce its lifespan .
  • 21.  Disadvantage : ✓ It does not estimate the actual amount of the power imbalance.  Thus result in either of the two: ✓ Over-shedding, which affects power quality. ✓ Under-shedding, which leads to tripping of electricity service. Flowchart of the conventional LSS
  • 22.  The strategy employs power swing equation to shed the required amount of loads.  The power imbalance within the system can be obtained by:  Whenever system disturbance, there is a variation in frequency as well as rate of change of frequency(ROCOF).  Using the equation, the power imbalance is estimated, which helps to calculate the required amount of load to be shed. t f f H P   = 2 Flowchart of the adaptive LSS
  • 23.  Advantages: ✓ This approach of load shedding can be applied to an isolated power system with a single generation unit as well as to an interconnected power system. ✓ Enhances the reliability of frequency and voltage stability. ✓ Enhanced transient behaviour when encountering severe disturbance.  Disadvantages: ✓ The values of ROCOF are different for similar amount of load variations at base and peak capacity. ✓ Strategy suffers un-optimum estimation of power imbalance due to the variations in ROCOF.
  • 24.  The term ‘computational intelligence techniques (CIT)’ generally refers to a set of techniques that are applied to mimic human intelligence.  These techniques include: ✓ Artificial neural networks (ANN), ✓ Adaptive neuro-fuzzy inference system (ANFIS), ✓ Fuzzy logic control (FLC), ✓ Genetic algorithms (GA), and ✓ Particle swarm optimizations (PSO).  These techniques can easily solve those nonlinear, multi- objective problems in power systems that cannot be solved by the conventional methods with the desired speed and accuracy
  • 25.  ANN is a mathematical model based on human neural systems.  The ANN training process: ✓ Three inputs – total generation, total load demand, and frequency decay rate ✓ One output – minimum amount of load shedding.  Advantage: The proposed ANN technique performed load shedding more quickly as compared with the conventional technique.  Disadvantage: ANN can provide satisfactory results for known (trained) cases only. ANN fails to predict accurate results for unknown (untrained) or varying cases.
  • 26.  FLC is a mathematical tool suitable for modelling a system which is too complex and not well defined by mathematical formulation.  Some of these applications include load frequency control, unified power flow controller (UPFC) application, flexible AC transmission system (FACTS) application, and reactive power/voltage control.  The proposed technique was formulated on frequency (f), rate of change of frequency (df/dt), and load prioritization.
  • 27.  The ANFIS method is based on the combination of artificial neural networks and fuzzy logic control.  It combines the learning abilities of ANN with the fuzzy interpretation of the FLC system.  Drawbacks: It can only work with Sugeno-type systems.
  • 28.  Genetic algorithms (GA) are the global optimization technique for solving non-linear, multi-objective problems.  The database for load shedding problems is obtained from a power flow study and is successfully implemented on the power system.  The results indicate that the GA-based technique is feasible and effective in providing optimal load shedding.  Drawbacks: ✓ It has been observed that the computation time of GAs to determine the amount of load shed is very large. ✓ This slow response limits their usage for online application.
  • 29.  PSO has been proved as a robust and fast technique in solving non-linear, multi-objective problems.  PSO finds the global optimum solution more quickly as compared to genetic algorithms.  PSO ability of taking only minimal time may encourage its implementation for real-time optimal load shedding in power systems.  Disadvantage: PSO is easily interrupted by partial optimization.
  • 30.  The GA and PSO techniques were used to solve generator outage and line outage cases, and were validated on the IEEE 30-bus system.  The responses of GA and PSO in all the case studies, results to show that: in terms of computation time ,PSO is faster than GA; the minimum amount of load is shed by GA
  • 31.  Recent power blackouts that have occurred around the world make the reliability of conventional UFLS techniques questionable.  Conventional UFLS techniques are not suitable for today’s large and complex power systems.  Computational intelligence techniques have the ability to deal with such modern power systems efficiently.  Computational intelligence techniques in load shedding can reduce the possibility of blackouts, and enhance the power system’s reliability.  Improvements are still needed to make these techniques compatible with real-time applications.
  • 32.  Verayiah, R., Mohamed, A., Shareef, H., & Abidin, I. Z. (2014). Review of under- voltage load shedding schemes in power system operation. Przegląd elektrotechniczny, 90(7), 99-103.  Shoaib, M., & Ahmed, F. (2016, December). A Systematic Literature Review of Optimal Load Shedding Models. In Proc. of Second Int. Multi-Disciplinary Conf (Vol. 19, p. 20).  Laghari, J. A., Mokhlis, H., Bakar, A. H. A., & Mohamad, H. (2013). Application of computational intelligence techniques for load shedding in power systems: A review. Energy conversion and management, 75, 130-140.  Chang, L., & Wu, Z. (2011). Performance and reliability of electrical power grids under cascading failures. International Journal of Electrical Power & Energy Systems, 33(8), 1410-1419.  Chandak, S., Bhowmik, P., & Rout, P. K. (2019). Load shedding strategy coordinated with storage device and D-STATCOM to enhance the microgrid stability. Protection and Control of Modern Power Systems, 4(1), 22.
  • 33.  Chandak, S., Bhowmik, P., & Rout, P. K. (2019). Robust power balancing scheme for the grid-forming microgrid. IET Renewable Power Generation, 14(1), 154-163.  Mollah, K., Bahadornejad, M., Nair, N. K., & Ancell, G. (2012, July). Automatic under-voltage load shedding: A systematic review. In 2012 IEEE Power and Energy Society General Meeting (pp. 1-7). IEEE.  Bakar, N. N. A., Hassan, M. Y., Sulaima, M. F., Na’im Mohd Nasir, M., & Khamis, A. (2017). Microgrid and load shedding scheme during islanded mode: A review. Renewable and Sustainable Energy Reviews, 71, 161-169.  Lakra, P., & Kirar, M. (2015). Load shedding techniques for system with cogeneration: A review. Electrical and Electronics Engineering: An International, 4(3).  Mollah, K. U. Z., Bahadornejad, M., & Nair, N. K. (2011, September). Automatic under-frequency load shedding in New Zealand power system—A systematic review. In AUPEC 2011 (pp. 1-7). IEEE.