Load Flow Analysis
in
DIgSILENT PowerFactory
Load Flow Analysis in DIgSILENT PowerFactory 2
Load Flow Applications
• Why run load flows?
- Check loading, losses and voltage profile
Are there any overloaded elements? Are the voltage constraits
respected?
• When to perform load flows?
– Network planning and operation
– Generation scheduling, optimization
– Steady state initial conditions for short circuit and stability calculations
2
Load Flow Analysis in DIgSILENT PowerFactory 3
General Procedure
• For each element 2 quantities can be defined
(e.g. P and Q, or P and V)
• The other quantities are results of the load flow calculation
• The grid must contain one element without power dispatch
(“Slack” element, in most cases the “External Grid”)
• According Node Types: PQ, PV, SL
Load flow calculation with PowerFactory
3
Load Flow Analysis in DIgSILENT PowerFactory 5
Model set-up before calculation
Dispatch of generators
Setpoints of loads Define bus type of External grid
Load Flow Analysis in DIgSILENT PowerFactory 6
Load Flow Calculation Options
• Basic options:
– Balanced / unbalanced load flow
– AC or DC load flow method
– Automatic adjustment of taps and
shunts
– Consider/ neglect reactive power limits
– Consider/ neglect voltage dependency
• Active power control (according to
inertia, secondary control etc.)
• Iteration control (number of iterations,
calculation accuracy etc.)
4
Load Flow Analysis in DIgSILENT PowerFactory 7
AC and DC Load Flow
• AC load flow
– The calculation requires the solving of a set of non-linear equations.
– Therefore done iteratively
– Accurate, but complex
– Voltages, angles, active and reactive powers calculated
• DC load flow
– The calculation requires the solving of a set of linear equations
– Approximate solution
– No iterations, fast, no convergence problems
• All node voltage magnitudes fixed at 1.0 per unit.
• Only Active Power and Voltage Angles calculated
• Losses neglected
Load Flow Analysis in DIgSILENT PowerFactory 8
Troubleshooting Load Flow Calculations (1)
• Study output window - find cause.
– information messages, warnings and error messages.
• Error messages could be generated by PowerFactory‘s data
checking function, e.g. “DIgSI/err - missing type !”
– Open element dialogue window or ‘mark in graphic’.
– Use the data-verification tool
• Evaluate importance of warnings.
– Example: Exceeding Mvar limit range may not be acceptable.
• Use graphic colouring.
– Find problematic elements.
5
Load Flow Analysis in DIgSILENT PowerFactory 9
Troubleshooting Load Flow Calculations (2)
• A network area is isolated, if no galvanic connection exist to the slack
bus bar.
• If this isolated area is not connected to a generator, then it is
‚isolated and not suplied‘.
• It is recommended to check, if the isolated areas are meant to be
isolated.
Explanation of „Isolated Areas“
Load Flow Analysis in DIgSILENT PowerFactory 10
Accessing Results & Reporting
1. Result and Text Boxes on the single line
diagram
2. Results in form of Tabular Data (export results
to Microsoft Office tools, windows clipboard)
3. Predefined PowerFactory Reports
4. Verification and Convergence Reports
6
Load Flow Analysis in DIgSILENT PowerFactory 11
Load Flow Analysis in PowerFactory
PowerFactory Models
for Load-Flow Analysis
Load Flow Analysis in DIgSILENT PowerFactory 12
Synchronous Generator Model in PowerFactory
• Type data:
– Rated power, voltage, power factor
– Reactances, inertia, time constants
– Saturation characteristic
– Etc.
• Element data
– PV or PQ machine, reference machine
– Dispatched power, voltage / reactive power
– Mvar limits
– Reference to station controller & secondary controller, Virtual Power Plant
– Etc.
7
Load Flow Analysis in DIgSILENT PowerFactory 13
...Synchronous Generator Model
1. Large machines: P,V (or PU)
2. Smaller machines (in distribution networks): often P,Q (or P cos ø)
3. Reference machine (slack): U,δ
UU δ,
dx II δ,
00, UU δ
maxQ
minQ
)cos(, ϕ1. P
U2. P,
U3. U δ,
Load Flow Analysis in DIgSILENT PowerFactory 14
Mvar limit curves
Capability Diagram shows
following limits:
•Stator Current Limit
•Prime Mover Maximum Output
•Rotor Current Limit
•Under-Excitation Limit
Colour Convention:
• Physical Capability Curve in
blue
• User-Defined operational
limits in red
• Operating Point in green/red
Max. Exciter
Current
Max. Stator
Current
Stability-/
MinimumExcitation
8
Load Flow Analysis in DIgSILENT PowerFactory 15
Mvar Limits Capability Curves
Scaling
Application for:
• Synchronous Generators
• Static Generators
Mvar Limits depend on:
• Active Power
• Voltage (optional)
Max. Exciter
Current
Max. Stator
Current
Stability-/
Minimum
Excitation
Prime Mover
Maximum
Load Flow Analysis in DIgSILENT PowerFactory 16
Static Generator
Application for:
• Photovoltaic
• Wind Power
• Fuel Cells
• Battery Systems
• Other Storage Systems
• HVDC Terminals
• Reactive Power Compensations
• Other Renewable Energy Generators
9
Load Flow Analysis in DIgSILENT PowerFactory 17
General Load Model
• A general load model can be defined as having a constant
active and reactive power, P and Q
• But the load can also be defined to be voltage-dependent:
• Consider voltage dependency of loads on the load flow
command.
Load Flow Analysis in DIgSILENT PowerFactory 18
Transformer model in PowerFactory
• Type data:
– Rated power, voltages, vector group
– Reactances and resistances
– Tap changer location, step size, range
– Etc.
• Element data
– Tap position
– Tap controller details
– Etc.
• Some element data is classified as operational data
– e.g. Tap position
10
Load Flow Analysis in DIgSILENT PowerFactory 19
Transformer Model (example)
2 winding transformer model
• Tap changer can be modeled on any winding
• Impedance can be tap-dependent
• Tap controller includes time constant
Schematic of tap changer with time constant
Load Flow Analysis in DIgSILENT PowerFactory 20
Transformer Model (cont...)
Open-circuit voltage vectors
Ordinary power transformer:
t
1
(1 + t)
ϕt
ϕu
o
t 0≈ϕ
Quad booster transformer:
o
t 90±≈ϕ
11
Load Flow Analysis in DIgSILENT PowerFactory 21
R´ L´
G´/2 G´/2C´/2 C´/2
lLjlRlZZ ⋅′⋅+⋅′=⋅′= ωπ
( )lCjlGlYY ⋅′⋅+⋅′⋅=⋅′⋅= ωπ
2
1
2
1
Transmission Line Models
Lumped Parameter Model (or PI-Nominal):
• Cascade connection of many sections and complex transposition schemes
• Z´and Y´ in ohm/km (line type) or calculated from a tower geometry (tower
type with conductor types).
• Good accuracy for short lines (<150km)
Load Flow Analysis in DIgSILENT PowerFactory 22
Transmission Line Models
Distributed Parameter Model (or PI-Equivalent):
l
l
lZlZZ C
⋅
⋅
⋅⋅′=⋅⋅=
γ
γ
γπ
sinh
sinh
2
2
2
1
sinh
1cosh
l
l
thg
lY
lZ
l
Y
C
⋅





 ⋅
⋅⋅′⋅=
⋅⋅
−⋅
=
γ
γ
γ
γ
π
• Z´and Y´ in ohm/km (line type) or calculated from a tower geometry
(tower type with conductor types).
• Good accuracy even for long lines (>150km)
12
Load Flow Analysis in DIgSILENT PowerFactory 23
Asynchronous Machine
Model, Single Cage Rotor
Load Flow Analysis in DIgSILENT PowerFactory 24
Asynchronous Machine
Double Cage Rotor:
13
Load Flow Analysis in DIgSILENT PowerFactory 25
Asynchronous Machine Parameters Calculation
• Rated Mechanical Power (pgn)
• Rated Load Factor (cosn)
• Efficiency in Rated Operation (effic)
• Rated mech. Frequency (anend)
• Ratio ILR (LockedRotor)/Ir (aiazn)
• Max. Torque (amkzn)
• Locked-Rotor Torque (amazn)
Load Flow Analysis in DIgSILENT PowerFactory 26
Load Flow Analysis in PowerFactory
Reactive Power
&
Voltage Control
14
Load Flow Analysis in DIgSILENT PowerFactory 27
Transformer Automatic Tap Changer
• Summary of tap type info)
• Tap position
• Automatic tap changer for load
flow calculation
– Taps adjusted to reach
voltage setpoint
– Error if final voltage not within
band
– Warning if tap limit reached
– Time constant used to
influence priorities amongst
transformers
Load Flow Analysis in DIgSILENT PowerFactory 28
Station Controller
• Participants: generators, transformers, static var systems etc.
• Control by:
– Separate ‘controllers’
– Station controller for a group of devices
Voltage
Control 1
Voltage
Control 2
Voltage
Control 3
Generator 1
Generator 2
Generator 3
Station
Control
Ue QG
U
Set Value
Set Value
Set Value
Contribution
Ue
Ue
QG
QG
Busbar
15
Load Flow Analysis in DIgSILENT PowerFactory 29
Load Flow Analysis in PowerFactory
Active Power Control
Load Flow Analysis in DIgSILENT PowerFactory 30
Control of Power Exchange
G
G
G
G
G
G
G
G
G
Netw. 1
Netw. 2
Netw. 3
Power Exchange
Power Exchange
16
Load Flow Analysis in DIgSILENT PowerFactory 31
Active Power Control – Secondary control
• How to balance supply (generation) and demand (load):
– As dispatched + reference machine
– According to secondary frequency control
Turbine 1
Turbine 2
Turbine 3
Generator 1
Generator 2
Generator 3
Network
Secondary
Control
PT PG
PT PG
PT PG
f PA
Set Value
Set Value
Set Value
Contribution
Load Flow Analysis in DIgSILENT PowerFactory 32
Load Flow Analysis in PowerFactory
Analysis of
Radially Operated Grids
17
Load Flow Analysis in DIgSILENT PowerFactory 33
Feeders
• Purpose: Automatic load scaling in DNO networks.
• Related functions:
– Colouring according to feeder definitions
– Load flow results can be displayed for individual feeders
• Maximum loading
• Minimum voltage
• Load scaling must be enabled in the load flow command
Option: “Feeder Load Scaling”
Load Flow Analysis in DIgSILENT PowerFactory 34
Radial Feeders
Approx 10MW Known 20MW Approx 10MW
Measured 50MW
Scale Do not scale Scale
15MW 20MW 15MW
18
Load Flow Analysis in DIgSILENT PowerFactory 35
Feeders into meshed network
Measured total 350MW
• Power flow in each feeder depends on interconnections in meshed network.
• Cannot set power of each feeder independently.
• Can scale loads to achieve required total for all feeders.
Load Flow Analysis in DIgSILENT PowerFactory 36
Feeder Definitions
• Used for :
- Automatic loadscaling
- Voltage profile diagrams
• Colouring to feeder definitions
• Loadflow results per feeder:
- Losses
- max. Loading
- min. Voltage
19
Load Flow Analysis in DIgSILENT PowerFactory 37
Voltage Profile
5.004.003.002.001.000.0-1.00 [km]
789
2924
2445
4218
459
245
Infeed
0.984
0.980
0.976
0.972
0.968
0.964
0.960
[p.u.]
Voltage, Magnitude
LowerLimity=0.962p.u.
4.037 km
1.000 km
0.975 p.u.
DIgSILENT
Feeder Voltage Profile Voltage Profile Date: 8/23/2000
Annex: Distr.2 /1
DIgSILENT
Voltage profile, overloading and limits in one diagram
Load Flow Analysis in DIgSILENT PowerFactory 38
Load Scaling
• Load Scaling:
- Edit or create feeder definition:
- Options:
a ) no scaling
b) scaling to measured reactive power
c) scaling to measured active power
d) scaling to measured current
• Loads that are to be scaled in order to match the measured value must be
marked as such
Option in the load „Adjusted by Load Scaling”
• Load scaling must be enabled in the loadflow command
Option: „Feeder Load Scaling”
20
Load Flow Analysis in DIgSILENT PowerFactory 39
Load Scaling

Weitere ähnliche Inhalte

Was ist angesagt?

FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation ControlMINAL RADE
 
Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filterRanganath
 
Inductance of transmission line
Inductance of transmission lineInductance of transmission line
Inductance of transmission lineAnisur Rahman
 
An introduction to FACTS
An introduction to FACTSAn introduction to FACTS
An introduction to FACTSAyyarao T S L V
 
Unit 5 Economic Load Dispatch and Unit Commitment
Unit 5 Economic Load Dispatch and Unit CommitmentUnit 5 Economic Load Dispatch and Unit Commitment
Unit 5 Economic Load Dispatch and Unit CommitmentSANTOSH GADEKAR
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flowAhmed M. Elkholy
 
Gate ee 2003 with solutions
Gate ee 2003 with solutionsGate ee 2003 with solutions
Gate ee 2003 with solutionskhemraj298
 
Power flow solution
Power flow solutionPower flow solution
Power flow solutionBalaram Das
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and EffectsLeonardo ENERGY
 
PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:Duddu Rajesh
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault AnalysisSANTOSH GADEKAR
 
3 reactive power and voltage control
3 reactive power and voltage control3 reactive power and voltage control
3 reactive power and voltage control8141245710
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power systemsneh pratap singh
 
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDYLOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDYijiert bestjournal
 

Was ist angesagt? (20)

FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
Shunt active power filter
Shunt active power filterShunt active power filter
Shunt active power filter
 
Inductance of transmission line
Inductance of transmission lineInductance of transmission line
Inductance of transmission line
 
Load flow studies
Load flow studiesLoad flow studies
Load flow studies
 
An introduction to FACTS
An introduction to FACTSAn introduction to FACTS
An introduction to FACTS
 
Unit 5 Economic Load Dispatch and Unit Commitment
Unit 5 Economic Load Dispatch and Unit CommitmentUnit 5 Economic Load Dispatch and Unit Commitment
Unit 5 Economic Load Dispatch and Unit Commitment
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flow
 
Gate ee 2003 with solutions
Gate ee 2003 with solutionsGate ee 2003 with solutions
Gate ee 2003 with solutions
 
Power flow solution
Power flow solutionPower flow solution
Power flow solution
 
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEMISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and Effects
 
PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:
 
HVDC presentation
HVDC presentationHVDC presentation
HVDC presentation
 
Power System Stablity
Power System StablityPower System Stablity
Power System Stablity
 
Per unit analysis
Per unit analysisPer unit analysis
Per unit analysis
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
 
3 reactive power and voltage control
3 reactive power and voltage control3 reactive power and voltage control
3 reactive power and voltage control
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDYLOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
 

Ähnlich wie DigSILENT PF - 03 load flow analysis

2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...
2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...
2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...OPAL-RT TECHNOLOGIES
 
chapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.pptchapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.pptLiewChiaPing
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfLiewChiaPing
 
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAnalyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAushiq Ali Memon
 
Switching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdf
Switching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdfSwitching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdf
Switching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdfssuserfe5963
 
DigSILENT PF - 06 irena additional exercises
DigSILENT PF - 06 irena  additional exercisesDigSILENT PF - 06 irena  additional exercises
DigSILENT PF - 06 irena additional exercisesHimmelstern
 
Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...
Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...
Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...IJSRD
 
Detection of power grid synchronization failure on sensing of frequency and v...
Detection of power grid synchronization failure on sensing of frequency and v...Detection of power grid synchronization failure on sensing of frequency and v...
Detection of power grid synchronization failure on sensing of frequency and v...bharath nidumolu
 
SCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTION
SCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTIONSCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTION
SCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTIONcscpconf
 
Sudden three phase short-circuit test
Sudden three phase short-circuit testSudden three phase short-circuit test
Sudden three phase short-circuit testDonald Stephen
 
Imperix - Rapid control prototyping solutions for power electronics
Imperix - Rapid control prototyping solutions for power electronicsImperix - Rapid control prototyping solutions for power electronics
Imperix - Rapid control prototyping solutions for power electronicsimperix
 
Load flow studies ppt1
Load flow studies ppt1Load flow studies ppt1
Load flow studies ppt1Srinivas Katta
 
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMLOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMASWATHYSANAND1
 
15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD
15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD
15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWDsuresh386785
 
103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt
103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt
103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.pptkEWQ865k
 

Ähnlich wie DigSILENT PF - 03 load flow analysis (20)

4771_doc_1
4771_doc_14771_doc_1
4771_doc_1
 
2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...
2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...
2017 Atlanta Regional User Seminar - Real-Time Volt/Var Optimization Scheme f...
 
chapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.pptchapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.ppt
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdf
 
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeedAnalyses of reactive power compensation schemes in MV/LV Networks with RE infeed
Analyses of reactive power compensation schemes in MV/LV Networks with RE infeed
 
Fg25969973
Fg25969973Fg25969973
Fg25969973
 
Switching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdf
Switching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdfSwitching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdf
Switching Over Voltages (SOV)_Temporary Over Voltage (TOV).pdf
 
DigSILENT PF - 06 irena additional exercises
DigSILENT PF - 06 irena  additional exercisesDigSILENT PF - 06 irena  additional exercises
DigSILENT PF - 06 irena additional exercises
 
SST
SSTSST
SST
 
Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...
Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...
Field Programmable Gate Array (FPGA) - Based Pulse Width Modulation for Singl...
 
Detection of power grid synchronization failure on sensing of frequency and v...
Detection of power grid synchronization failure on sensing of frequency and v...Detection of power grid synchronization failure on sensing of frequency and v...
Detection of power grid synchronization failure on sensing of frequency and v...
 
SCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTION
SCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTIONSCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTION
SCAN CHAINS TESTING FOR LATCHES TO REDUCE AREA AND THE POWER CONSUMPTION
 
Sudden three phase short-circuit test
Sudden three phase short-circuit testSudden three phase short-circuit test
Sudden three phase short-circuit test
 
Imperix - Rapid control prototyping solutions for power electronics
Imperix - Rapid control prototyping solutions for power electronicsImperix - Rapid control prototyping solutions for power electronics
Imperix - Rapid control prototyping solutions for power electronics
 
Apfc final seminar
Apfc final seminarApfc final seminar
Apfc final seminar
 
Load flow studies ppt1
Load flow studies ppt1Load flow studies ppt1
Load flow studies ppt1
 
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMLOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
 
15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD
15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD
15.02.2024.pptxDSD3E23DSDSDQWE23EWQDSDSDQWD
 
103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt
103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt
103479026-Expert-Lecture-on-Power-System-Modelling-and-Simulation.ppt
 
Two Quadrant chopper
Two Quadrant chopperTwo Quadrant chopper
Two Quadrant chopper
 

Kürzlich hochgeladen

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01KreezheaRecto
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 

Kürzlich hochgeladen (20)

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 

DigSILENT PF - 03 load flow analysis

  • 1. 1 Load Flow Analysis in DIgSILENT PowerFactory Load Flow Analysis in DIgSILENT PowerFactory 2 Load Flow Applications • Why run load flows? - Check loading, losses and voltage profile Are there any overloaded elements? Are the voltage constraits respected? • When to perform load flows? – Network planning and operation – Generation scheduling, optimization – Steady state initial conditions for short circuit and stability calculations
  • 2. 2 Load Flow Analysis in DIgSILENT PowerFactory 3 General Procedure • For each element 2 quantities can be defined (e.g. P and Q, or P and V) • The other quantities are results of the load flow calculation • The grid must contain one element without power dispatch (“Slack” element, in most cases the “External Grid”) • According Node Types: PQ, PV, SL Load flow calculation with PowerFactory
  • 3. 3 Load Flow Analysis in DIgSILENT PowerFactory 5 Model set-up before calculation Dispatch of generators Setpoints of loads Define bus type of External grid Load Flow Analysis in DIgSILENT PowerFactory 6 Load Flow Calculation Options • Basic options: – Balanced / unbalanced load flow – AC or DC load flow method – Automatic adjustment of taps and shunts – Consider/ neglect reactive power limits – Consider/ neglect voltage dependency • Active power control (according to inertia, secondary control etc.) • Iteration control (number of iterations, calculation accuracy etc.)
  • 4. 4 Load Flow Analysis in DIgSILENT PowerFactory 7 AC and DC Load Flow • AC load flow – The calculation requires the solving of a set of non-linear equations. – Therefore done iteratively – Accurate, but complex – Voltages, angles, active and reactive powers calculated • DC load flow – The calculation requires the solving of a set of linear equations – Approximate solution – No iterations, fast, no convergence problems • All node voltage magnitudes fixed at 1.0 per unit. • Only Active Power and Voltage Angles calculated • Losses neglected Load Flow Analysis in DIgSILENT PowerFactory 8 Troubleshooting Load Flow Calculations (1) • Study output window - find cause. – information messages, warnings and error messages. • Error messages could be generated by PowerFactory‘s data checking function, e.g. “DIgSI/err - missing type !” – Open element dialogue window or ‘mark in graphic’. – Use the data-verification tool • Evaluate importance of warnings. – Example: Exceeding Mvar limit range may not be acceptable. • Use graphic colouring. – Find problematic elements.
  • 5. 5 Load Flow Analysis in DIgSILENT PowerFactory 9 Troubleshooting Load Flow Calculations (2) • A network area is isolated, if no galvanic connection exist to the slack bus bar. • If this isolated area is not connected to a generator, then it is ‚isolated and not suplied‘. • It is recommended to check, if the isolated areas are meant to be isolated. Explanation of „Isolated Areas“ Load Flow Analysis in DIgSILENT PowerFactory 10 Accessing Results & Reporting 1. Result and Text Boxes on the single line diagram 2. Results in form of Tabular Data (export results to Microsoft Office tools, windows clipboard) 3. Predefined PowerFactory Reports 4. Verification and Convergence Reports
  • 6. 6 Load Flow Analysis in DIgSILENT PowerFactory 11 Load Flow Analysis in PowerFactory PowerFactory Models for Load-Flow Analysis Load Flow Analysis in DIgSILENT PowerFactory 12 Synchronous Generator Model in PowerFactory • Type data: – Rated power, voltage, power factor – Reactances, inertia, time constants – Saturation characteristic – Etc. • Element data – PV or PQ machine, reference machine – Dispatched power, voltage / reactive power – Mvar limits – Reference to station controller & secondary controller, Virtual Power Plant – Etc.
  • 7. 7 Load Flow Analysis in DIgSILENT PowerFactory 13 ...Synchronous Generator Model 1. Large machines: P,V (or PU) 2. Smaller machines (in distribution networks): often P,Q (or P cos ø) 3. Reference machine (slack): U,δ UU δ, dx II δ, 00, UU δ maxQ minQ )cos(, ϕ1. P U2. P, U3. U δ, Load Flow Analysis in DIgSILENT PowerFactory 14 Mvar limit curves Capability Diagram shows following limits: •Stator Current Limit •Prime Mover Maximum Output •Rotor Current Limit •Under-Excitation Limit Colour Convention: • Physical Capability Curve in blue • User-Defined operational limits in red • Operating Point in green/red Max. Exciter Current Max. Stator Current Stability-/ MinimumExcitation
  • 8. 8 Load Flow Analysis in DIgSILENT PowerFactory 15 Mvar Limits Capability Curves Scaling Application for: • Synchronous Generators • Static Generators Mvar Limits depend on: • Active Power • Voltage (optional) Max. Exciter Current Max. Stator Current Stability-/ Minimum Excitation Prime Mover Maximum Load Flow Analysis in DIgSILENT PowerFactory 16 Static Generator Application for: • Photovoltaic • Wind Power • Fuel Cells • Battery Systems • Other Storage Systems • HVDC Terminals • Reactive Power Compensations • Other Renewable Energy Generators
  • 9. 9 Load Flow Analysis in DIgSILENT PowerFactory 17 General Load Model • A general load model can be defined as having a constant active and reactive power, P and Q • But the load can also be defined to be voltage-dependent: • Consider voltage dependency of loads on the load flow command. Load Flow Analysis in DIgSILENT PowerFactory 18 Transformer model in PowerFactory • Type data: – Rated power, voltages, vector group – Reactances and resistances – Tap changer location, step size, range – Etc. • Element data – Tap position – Tap controller details – Etc. • Some element data is classified as operational data – e.g. Tap position
  • 10. 10 Load Flow Analysis in DIgSILENT PowerFactory 19 Transformer Model (example) 2 winding transformer model • Tap changer can be modeled on any winding • Impedance can be tap-dependent • Tap controller includes time constant Schematic of tap changer with time constant Load Flow Analysis in DIgSILENT PowerFactory 20 Transformer Model (cont...) Open-circuit voltage vectors Ordinary power transformer: t 1 (1 + t) ϕt ϕu o t 0≈ϕ Quad booster transformer: o t 90±≈ϕ
  • 11. 11 Load Flow Analysis in DIgSILENT PowerFactory 21 R´ L´ G´/2 G´/2C´/2 C´/2 lLjlRlZZ ⋅′⋅+⋅′=⋅′= ωπ ( )lCjlGlYY ⋅′⋅+⋅′⋅=⋅′⋅= ωπ 2 1 2 1 Transmission Line Models Lumped Parameter Model (or PI-Nominal): • Cascade connection of many sections and complex transposition schemes • Z´and Y´ in ohm/km (line type) or calculated from a tower geometry (tower type with conductor types). • Good accuracy for short lines (<150km) Load Flow Analysis in DIgSILENT PowerFactory 22 Transmission Line Models Distributed Parameter Model (or PI-Equivalent): l l lZlZZ C ⋅ ⋅ ⋅⋅′=⋅⋅= γ γ γπ sinh sinh 2 2 2 1 sinh 1cosh l l thg lY lZ l Y C ⋅       ⋅ ⋅⋅′⋅= ⋅⋅ −⋅ = γ γ γ γ π • Z´and Y´ in ohm/km (line type) or calculated from a tower geometry (tower type with conductor types). • Good accuracy even for long lines (>150km)
  • 12. 12 Load Flow Analysis in DIgSILENT PowerFactory 23 Asynchronous Machine Model, Single Cage Rotor Load Flow Analysis in DIgSILENT PowerFactory 24 Asynchronous Machine Double Cage Rotor:
  • 13. 13 Load Flow Analysis in DIgSILENT PowerFactory 25 Asynchronous Machine Parameters Calculation • Rated Mechanical Power (pgn) • Rated Load Factor (cosn) • Efficiency in Rated Operation (effic) • Rated mech. Frequency (anend) • Ratio ILR (LockedRotor)/Ir (aiazn) • Max. Torque (amkzn) • Locked-Rotor Torque (amazn) Load Flow Analysis in DIgSILENT PowerFactory 26 Load Flow Analysis in PowerFactory Reactive Power & Voltage Control
  • 14. 14 Load Flow Analysis in DIgSILENT PowerFactory 27 Transformer Automatic Tap Changer • Summary of tap type info) • Tap position • Automatic tap changer for load flow calculation – Taps adjusted to reach voltage setpoint – Error if final voltage not within band – Warning if tap limit reached – Time constant used to influence priorities amongst transformers Load Flow Analysis in DIgSILENT PowerFactory 28 Station Controller • Participants: generators, transformers, static var systems etc. • Control by: – Separate ‘controllers’ – Station controller for a group of devices Voltage Control 1 Voltage Control 2 Voltage Control 3 Generator 1 Generator 2 Generator 3 Station Control Ue QG U Set Value Set Value Set Value Contribution Ue Ue QG QG Busbar
  • 15. 15 Load Flow Analysis in DIgSILENT PowerFactory 29 Load Flow Analysis in PowerFactory Active Power Control Load Flow Analysis in DIgSILENT PowerFactory 30 Control of Power Exchange G G G G G G G G G Netw. 1 Netw. 2 Netw. 3 Power Exchange Power Exchange
  • 16. 16 Load Flow Analysis in DIgSILENT PowerFactory 31 Active Power Control – Secondary control • How to balance supply (generation) and demand (load): – As dispatched + reference machine – According to secondary frequency control Turbine 1 Turbine 2 Turbine 3 Generator 1 Generator 2 Generator 3 Network Secondary Control PT PG PT PG PT PG f PA Set Value Set Value Set Value Contribution Load Flow Analysis in DIgSILENT PowerFactory 32 Load Flow Analysis in PowerFactory Analysis of Radially Operated Grids
  • 17. 17 Load Flow Analysis in DIgSILENT PowerFactory 33 Feeders • Purpose: Automatic load scaling in DNO networks. • Related functions: – Colouring according to feeder definitions – Load flow results can be displayed for individual feeders • Maximum loading • Minimum voltage • Load scaling must be enabled in the load flow command Option: “Feeder Load Scaling” Load Flow Analysis in DIgSILENT PowerFactory 34 Radial Feeders Approx 10MW Known 20MW Approx 10MW Measured 50MW Scale Do not scale Scale 15MW 20MW 15MW
  • 18. 18 Load Flow Analysis in DIgSILENT PowerFactory 35 Feeders into meshed network Measured total 350MW • Power flow in each feeder depends on interconnections in meshed network. • Cannot set power of each feeder independently. • Can scale loads to achieve required total for all feeders. Load Flow Analysis in DIgSILENT PowerFactory 36 Feeder Definitions • Used for : - Automatic loadscaling - Voltage profile diagrams • Colouring to feeder definitions • Loadflow results per feeder: - Losses - max. Loading - min. Voltage
  • 19. 19 Load Flow Analysis in DIgSILENT PowerFactory 37 Voltage Profile 5.004.003.002.001.000.0-1.00 [km] 789 2924 2445 4218 459 245 Infeed 0.984 0.980 0.976 0.972 0.968 0.964 0.960 [p.u.] Voltage, Magnitude LowerLimity=0.962p.u. 4.037 km 1.000 km 0.975 p.u. DIgSILENT Feeder Voltage Profile Voltage Profile Date: 8/23/2000 Annex: Distr.2 /1 DIgSILENT Voltage profile, overloading and limits in one diagram Load Flow Analysis in DIgSILENT PowerFactory 38 Load Scaling • Load Scaling: - Edit or create feeder definition: - Options: a ) no scaling b) scaling to measured reactive power c) scaling to measured active power d) scaling to measured current • Loads that are to be scaled in order to match the measured value must be marked as such Option in the load „Adjusted by Load Scaling” • Load scaling must be enabled in the loadflow command Option: „Feeder Load Scaling”
  • 20. 20 Load Flow Analysis in DIgSILENT PowerFactory 39 Load Scaling