Harmonics
What are Harmonics? Can they impact AC Drive Sales
The greatest problem with Harmonics is the lack of information about harmonics. Our customers and the electric utilities
that service our customers are asking questions about harmonics from our drives using the IEEE 519 guide as the basis
for drive selection. There is a lot of confusion about what the IEEE guide means, so the tendency by our customers to fix
their requirements on the exact value for percent harmonic distortion defined in the IEEE guide. The intent of this
harmonic session is to show you how to use the harmonic analysis program contained on the energy saving diskette and
to prepare you to better assist your customers in dealing with their concerns, specifications requirements for the
equipment and utility rebate programs.
Let's start with the basics.
When we talk about ac we are talking about alternating current. The voltage pushing that current through the load circuit
is described in terms of frequency and amplitude. The frequency of the current will be identical to the frequency of the
voltage as long as the load resistance/impedance does not change. In a linear load, like a resistor, capacitor or inductor,
current and voltage will have the same frequency. As long as the characteristics of the load components do not change,
the frequency component of the current will not change. When we deal with non-linear loads such as switching power
supplies, transformers which saturate, capacitors which charge to the peak of the supply voltage, and converters used in
drives, the characteristics of the load are dynamic. As the amplitude of the voltage changes and the load impedance
changes, the frequency of the current will change. That changing current and resulting complex waveform is a result of:
these load changes. The complex current waveform can be described by defining each component of the waveform. The
component of any waveform can be defined in terms of dc, and all frequencies from 0 to infinity. The frequencies that
are normally dealt with using drives are 50 and 60 Hertz. By definition, these frequencies are termed fundamental in their
respective distribution systems.
Let's get into harmonics basics level II .
With three phase conversion equipment, such as drives, the current demand on the distribution system will depend on
three things. They are the characteristics of the input three phase voltage, the operating speed of the drive, and the
drive output load demand. Evaluating a single operating point of a drive will permit determining the input current demand
and the cause of the harmonic content of that input current.
Let's define the operating point for the evaluation.
Input voltage-line = 480 VAC, Full load amps = 100, Output Frequency 60 Hz These value will be used in the following
text as the example system.
The drawing shown indicates how current follows the frequency when the load is linear Only a phase angle change is
shown.
Fahad
know
ledge
centre
When the load become non-linear, the current is not continuous and will contain many Frequencies. Figure 2 shows what
the current might look like in a non-linear circuit.
Each current pulse will contain many frequencies. The frequencies will be made up of the fundamental, 60 Hz, and
frequencies which are a multiple or sub-multiple of the fundamental. The description can be mathematically defined by a
Fourier series. Since the pulses are of both polarities, the even order harmonics will be canceled. In a three phase
circuit, any harmonic divisible by 3 will be canceled in each phase. However, the sum of those harmonics divisible by 3
will be found in the neutral of the distribution system. It is for that reason the neutral wire in a distribution system is often
sized to carry up to three times the value of the phase currents.
For distribution systems which must handle a large percentage of non-linear loads, the percentage of harmonic currents
can be very high. It is important to remember that the greatest contributor to harmonic currents is single phase lighting
circuits which used magnetic or electronic lighting controls. The next largest contributor is computers. In fact, any single
phase device which contains a switching mode power supply, a SMPS, will cause high percentages of the third
harmonic. The third harmonic causes the greatest amount of current distortion on the ac line. In factories and office
buildings where the load type is lighting and computers, that type of load is often as much as 50% of the total power
used. The addition Of non-linear, 3 phase drive products, whether ac or dc, is usually less than 20% of the total load.
Since the most significant harmonic in a three phase load is the fifth harmonic, the current distortion caused by drives is
much less than caused by lighting and computer loads.
So why all the fuss about harmonic currents caused by drives?
The main reason for the concern is that drives must be considered since they can add to the harmonic currents already
present. It the harmonic currents are not considered, it would be like ignoring some of the loading when picking a
transformer or the wire size in a distribution system. If the transformer is sized too small, it could cause a fire. Using a
standard transformer, with exactly the listed KVA load for each drive or non-linear load is like using too small a
transformer. A 50 KVA SMPS lighting load would require 65 KVA due to the 33% additional 3rd harmonic current load.
The higher frequency harmonic current will cause more transformer heating because of eddy current losses in the core
and higher wire resistance caused by skin effect.
There are two main affects of harmonic currents on a distribution system. The first is that harmonic currents add to the
RMS value of the fundamental. This additional current will increase losses in wire, bus bars, transformers and power
factor correction capacitors used in the distribution system. A typical value for the additional RMS loss would be 3% if
skin effect and core losses could be ignored. Unfortunately, they can not be ignored. The second affect is the additional
heating caused by each of the harmonic currents. Transformers, capacitors, circuit breakers, wires and bus bars must
be designed to handle the higher frequency currents. If these components are not correctly sized for the harmonic
currents, the harmonic currents can cause additional heating in those components. This heating can result in premature
component failure and the possibility of fire. New transformer ratings will soon be on the market. These ratings will cover
transformers for non-linear loads. Underwriters Laboratory, UL will begin to rate transformer based on the percentage of
non-linear loads, whether single phase or three phase.
Fahad
know
ledge
centre
In a six pulse converter or 3 phase full-wave bridge, the most significant harmonics are the number of pulses ±±1. That
means a six pulse converter will create harmonic currents with a frequency 5 times 60 Hz and 7 times 60 Hz. The
amplitude of those harmonics will be approximately 1/5 and 1/7 of the amplitude of the fundamental current. In the
example, a fundamental or 60 Hz current of 100 amps would contain a 300 Hz current with an amplitude of 1/5 times 100
or 20 amps and a 420 Hz current with an amplitude of If 7 times 100 or 14.3 amps. In RMS terms, the harmonic current
distortion value will only amount to approximately:
2 2 2
100 20 143 102 98+ + =. .
This additional 3% RMS current would not significantly overheat the components in a distribution system that is not
overloaded and used components rated for non-linear loads. 1t linear load rated transformers and capacitors are used,
the heating caused by 20% of the 5th harmonic and 14.3% of the 7th harmonic could cause destructive heating if the
components are not derated. The chief concern with harmonic currents is that their characteristic are known so that
correct sizing can take place.
How can harmonic currents affect AC drive sales?
Our principle concern should be how to deal with the concern or “fear” that our customers are likely to have regarding
harmonic currents. We need to provide as much "good" information as possible without confusing the customer. These
basic facts can be given to the customer concerned with harmonic currents and IEEE 519 guideline for harmonic
currents.
1. Harmonic currents can cause overheating of distribution system equipment.
2. Harmonic currents are caused by any electrical equipment that used SMPS.
3. Distribution system loading by non-linear equipment can cause older dry type transformers to overheat if not derated.
4. Lighting accounts for 55% of all electrical power used. An estimated 90% of that power is controlled by some type of
switching mode power supply (SMPS). That means that 50% of all power used can have harmonic currents
overloading transformers, capacitors and other components on the distribution system.
5. Motors account for 40% of all electrical power used. An estimated 20~ Of that power is controlled by some type of 3
phase SMPS. That means that 8% of all power used for controlling motors can have harmonic currents overloading
transformers, capacitors and other components on the distribution system.
6: Harmonic current will cause .voltage distortion The amount of distortion is much less than the distortion caused by the
normal line current. Voltage distortion by high frequencies will be a percentage of the voltage drop caused by the
fundamental current. A 5% drop in line voltage due to the fundamental load current will be increased by the 5th
harmonics by 20% of 5% or an additional 1%.
7. Transformers, circuit breakers, and other distribution system components ratings within any facility Should be
reviewed based on the original selection and any changes or additions in non-linear loads.
8. Single phase loads, such as lighting loads should be reviewed to determine what level of harmonic current distortion
already exists in a system before adding additional non-linear loads to that system.
9. 0f the different types of AC drives on the market, the AC drive which causes the lest amount of harmonic current and
voltage distortion over the operating speed range is a PWM AC drive which contains an internal dc bus reactor. The
second best is a PWM AC drive with an AC line reactor before the drive.
10. The use of line filters before a drive will add more losses to the electrical system and could create line ringing and
large voltage transients. These conditions could results in greater damage to other components on the distribution
system. Even if correctly designed for an installation, the filter may have to be modified every time an additional
piece of equipment is added to that distribution system.
Fahad
know
ledge
centre
Fahad
know
ledge
centre

Weitere ähnliche Inhalte

Was ist angesagt?

Analysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system usingAnalysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system using
IAEME Publication
 
Thesis on harmonic distortion ps
Thesis on harmonic distortion psThesis on harmonic distortion ps
Thesis on harmonic distortion ps
kavithasasidharan
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
Minh Anh Nguyen
 

Was ist angesagt? (20)

Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System LtdHarmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
Harmonics Presentation by Baldev Raj Narang CEO Clariant Power System Ltd
 
Vivek harmonics
Vivek harmonicsVivek harmonics
Vivek harmonics
 
Analysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system usingAnalysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system using
 
Harmonic presentation 11 6-2018
Harmonic presentation 11 6-2018Harmonic presentation 11 6-2018
Harmonic presentation 11 6-2018
 
overview
overviewoverview
overview
 
2010 August Harmonics & Energy Efficiency
2010 August Harmonics & Energy Efficiency2010 August Harmonics & Energy Efficiency
2010 August Harmonics & Energy Efficiency
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics Effects in Power System
Harmonics Effects in Power SystemHarmonics Effects in Power System
Harmonics Effects in Power System
 
Thesis on harmonic distortion ps
Thesis on harmonic distortion psThesis on harmonic distortion ps
Thesis on harmonic distortion ps
 
WHY HARMONICS IS UNWANTED ?
WHY HARMONICS IS UNWANTED ?WHY HARMONICS IS UNWANTED ?
WHY HARMONICS IS UNWANTED ?
 
Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?
 
Harmonics
HarmonicsHarmonics
Harmonics
 
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
POWER HARMONICS- SOURCES, ISSUES AND MITIGATIONPOWER HARMONICS- SOURCES, ISSUES AND MITIGATION
POWER HARMONICS- SOURCES, ISSUES AND MITIGATION
 
Harmonics in power system
Harmonics in power systemHarmonics in power system
Harmonics in power system
 
Harmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and MinimizationHarmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and Minimization
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and Effects
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentationProduct: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
 

Andere mochten auch

Onederland travel visits
Onederland travel visitsOnederland travel visits
Onederland travel visits
Heatmorr38
 
Beer system troubleshooting 10 16-13
Beer system troubleshooting 10 16-13Beer system troubleshooting 10 16-13
Beer system troubleshooting 10 16-13
Parikshit kakkar
 
Magnetic levitation(5)
Magnetic levitation(5)Magnetic levitation(5)
Magnetic levitation(5)
Fahad Shaikh
 

Andere mochten auch (15)

100 ways
100 ways100 ways
100 ways
 
Draught beer basics
Draught beer basicsDraught beer basics
Draught beer basics
 
Onederland travel visits
Onederland travel visitsOnederland travel visits
Onederland travel visits
 
Beer system troubleshooting 10 16-13
Beer system troubleshooting 10 16-13Beer system troubleshooting 10 16-13
Beer system troubleshooting 10 16-13
 
Wine guide
Wine guideWine guide
Wine guide
 
Presentation2
Presentation2Presentation2
Presentation2
 
レビューの仕方
レビューの仕方レビューの仕方
レビューの仕方
 
Perlick wine guide_web
Perlick wine guide_webPerlick wine guide_web
Perlick wine guide_web
 
Hydro p-s
Hydro p-sHydro p-s
Hydro p-s
 
Draught beer basics
Draught beer basicsDraught beer basics
Draught beer basics
 
Magnetic levitation(5)
Magnetic levitation(5)Magnetic levitation(5)
Magnetic levitation(5)
 
ATM
ATMATM
ATM
 
Napa technology
Napa technologyNapa technology
Napa technology
 
What is nfc (4)
What is nfc (4)What is nfc (4)
What is nfc (4)
 
Hts cable (6)
Hts cable (6)Hts cable (6)
Hts cable (6)
 

Ähnlich wie Harmonics

Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
Power System Operation
 
Electrical fundamentals terms
Electrical fundamentals termsElectrical fundamentals terms
Electrical fundamentals terms
Rajneesh Budania
 
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution NetworkDesign of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
ijtsrd
 
06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf
ROCIOMAMANIALATA1
 

Ähnlich wie Harmonics (20)

Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdfFUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
 
Electrical fundamentals terms
Electrical fundamentals termsElectrical fundamentals terms
Electrical fundamentals terms
 
An Overview of Harmonic Sources in Power System
An Overview of Harmonic Sources in Power SystemAn Overview of Harmonic Sources in Power System
An Overview of Harmonic Sources in Power System
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
 
Electrical fundamentals terms
Electrical fundamentals termsElectrical fundamentals terms
Electrical fundamentals terms
 
Active filter iora 2 consul
Active filter iora 2 consulActive filter iora 2 consul
Active filter iora 2 consul
 
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution NetworkDesign of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
 
Power System Harmonics
Power System HarmonicsPower System Harmonics
Power System Harmonics
 
IRJET- Harmonics Reduction using Harmonics Injection Method
IRJET- Harmonics Reduction using Harmonics Injection MethodIRJET- Harmonics Reduction using Harmonics Injection Method
IRJET- Harmonics Reduction using Harmonics Injection Method
 
Estimation of Harmonics in Three-phase and Six-phase (Multi- phase) Load Circ...
Estimation of Harmonics in Three-phase and Six-phase (Multi- phase) Load Circ...Estimation of Harmonics in Three-phase and Six-phase (Multi- phase) Load Circ...
Estimation of Harmonics in Three-phase and Six-phase (Multi- phase) Load Circ...
 
Determination of voltage regulation and power system losses
Determination of voltage regulation and power system lossesDetermination of voltage regulation and power system losses
Determination of voltage regulation and power system losses
 
Determination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system lossesDetermination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system losses
 
Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)
 
06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Analysis of harmonic at different level on distribution system ,its effect a...
Analysis of harmonic at different level on distribution system ,its effect  a...Analysis of harmonic at different level on distribution system ,its effect  a...
Analysis of harmonic at different level on distribution system ,its effect a...
 
Paper id 29201412
Paper id 29201412Paper id 29201412
Paper id 29201412
 
Harmonics in Power2.pptx
Harmonics in Power2.pptxHarmonics in Power2.pptx
Harmonics in Power2.pptx
 

Mehr von Fahad Shaikh (9)

Renewable energy sources
Renewable energy sourcesRenewable energy sources
Renewable energy sources
 
Reproduction (life of cycle)
Reproduction (life of cycle)Reproduction (life of cycle)
Reproduction (life of cycle)
 
Propogation of light
Propogation of lightPropogation of light
Propogation of light
 
Gps mobile based human position (2)
Gps mobile based human position (2)Gps mobile based human position (2)
Gps mobile based human position (2)
 
What is nfc (3)
What is nfc  (3)What is nfc  (3)
What is nfc (3)
 
Harmonics mitigation solutions
Harmonics mitigation solutionsHarmonics mitigation solutions
Harmonics mitigation solutions
 
Gil
GilGil
Gil
 
Structure of an atom new
Structure of an atom newStructure of an atom new
Structure of an atom new
 
Industrial health and safety seminar
Industrial health and safety seminarIndustrial health and safety seminar
Industrial health and safety seminar
 

Kürzlich hochgeladen

Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
kauryashika82
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
negromaestrong
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
QucHHunhnh
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
QucHHunhnh
 

Kürzlich hochgeladen (20)

General Principles of Intellectual Property: Concepts of Intellectual Proper...
General Principles of Intellectual Property: Concepts of Intellectual  Proper...General Principles of Intellectual Property: Concepts of Intellectual  Proper...
General Principles of Intellectual Property: Concepts of Intellectual Proper...
 
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptxSKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
SKILL OF INTRODUCING THE LESSON MICRO SKILLS.pptx
 
Third Battle of Panipat detailed notes.pptx
Third Battle of Panipat detailed notes.pptxThird Battle of Panipat detailed notes.pptx
Third Battle of Panipat detailed notes.pptx
 
Accessible Digital Futures project (20/03/2024)
Accessible Digital Futures project (20/03/2024)Accessible Digital Futures project (20/03/2024)
Accessible Digital Futures project (20/03/2024)
 
Sociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning ExhibitSociology 101 Demonstration of Learning Exhibit
Sociology 101 Demonstration of Learning Exhibit
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
Python Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docxPython Notes for mca i year students osmania university.docx
Python Notes for mca i year students osmania university.docx
 
Unit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptxUnit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptx
 
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in DelhiRussian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
Russian Escort Service in Delhi 11k Hotel Foreigner Russian Call Girls in Delhi
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
How to Manage Global Discount in Odoo 17 POS
How to Manage Global Discount in Odoo 17 POSHow to Manage Global Discount in Odoo 17 POS
How to Manage Global Discount in Odoo 17 POS
 
Seal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptxSeal of Good Local Governance (SGLG) 2024Final.pptx
Seal of Good Local Governance (SGLG) 2024Final.pptx
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17How to Create and Manage Wizard in Odoo 17
How to Create and Manage Wizard in Odoo 17
 
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docx
 
Making communications land - Are they received and understood as intended? we...
Making communications land - Are they received and understood as intended? we...Making communications land - Are they received and understood as intended? we...
Making communications land - Are they received and understood as intended? we...
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
 

Harmonics

  • 1. Harmonics What are Harmonics? Can they impact AC Drive Sales The greatest problem with Harmonics is the lack of information about harmonics. Our customers and the electric utilities that service our customers are asking questions about harmonics from our drives using the IEEE 519 guide as the basis for drive selection. There is a lot of confusion about what the IEEE guide means, so the tendency by our customers to fix their requirements on the exact value for percent harmonic distortion defined in the IEEE guide. The intent of this harmonic session is to show you how to use the harmonic analysis program contained on the energy saving diskette and to prepare you to better assist your customers in dealing with their concerns, specifications requirements for the equipment and utility rebate programs. Let's start with the basics. When we talk about ac we are talking about alternating current. The voltage pushing that current through the load circuit is described in terms of frequency and amplitude. The frequency of the current will be identical to the frequency of the voltage as long as the load resistance/impedance does not change. In a linear load, like a resistor, capacitor or inductor, current and voltage will have the same frequency. As long as the characteristics of the load components do not change, the frequency component of the current will not change. When we deal with non-linear loads such as switching power supplies, transformers which saturate, capacitors which charge to the peak of the supply voltage, and converters used in drives, the characteristics of the load are dynamic. As the amplitude of the voltage changes and the load impedance changes, the frequency of the current will change. That changing current and resulting complex waveform is a result of: these load changes. The complex current waveform can be described by defining each component of the waveform. The component of any waveform can be defined in terms of dc, and all frequencies from 0 to infinity. The frequencies that are normally dealt with using drives are 50 and 60 Hertz. By definition, these frequencies are termed fundamental in their respective distribution systems. Let's get into harmonics basics level II . With three phase conversion equipment, such as drives, the current demand on the distribution system will depend on three things. They are the characteristics of the input three phase voltage, the operating speed of the drive, and the drive output load demand. Evaluating a single operating point of a drive will permit determining the input current demand and the cause of the harmonic content of that input current. Let's define the operating point for the evaluation. Input voltage-line = 480 VAC, Full load amps = 100, Output Frequency 60 Hz These value will be used in the following text as the example system. The drawing shown indicates how current follows the frequency when the load is linear Only a phase angle change is shown. Fahad know ledge centre
  • 2. When the load become non-linear, the current is not continuous and will contain many Frequencies. Figure 2 shows what the current might look like in a non-linear circuit. Each current pulse will contain many frequencies. The frequencies will be made up of the fundamental, 60 Hz, and frequencies which are a multiple or sub-multiple of the fundamental. The description can be mathematically defined by a Fourier series. Since the pulses are of both polarities, the even order harmonics will be canceled. In a three phase circuit, any harmonic divisible by 3 will be canceled in each phase. However, the sum of those harmonics divisible by 3 will be found in the neutral of the distribution system. It is for that reason the neutral wire in a distribution system is often sized to carry up to three times the value of the phase currents. For distribution systems which must handle a large percentage of non-linear loads, the percentage of harmonic currents can be very high. It is important to remember that the greatest contributor to harmonic currents is single phase lighting circuits which used magnetic or electronic lighting controls. The next largest contributor is computers. In fact, any single phase device which contains a switching mode power supply, a SMPS, will cause high percentages of the third harmonic. The third harmonic causes the greatest amount of current distortion on the ac line. In factories and office buildings where the load type is lighting and computers, that type of load is often as much as 50% of the total power used. The addition Of non-linear, 3 phase drive products, whether ac or dc, is usually less than 20% of the total load. Since the most significant harmonic in a three phase load is the fifth harmonic, the current distortion caused by drives is much less than caused by lighting and computer loads. So why all the fuss about harmonic currents caused by drives? The main reason for the concern is that drives must be considered since they can add to the harmonic currents already present. It the harmonic currents are not considered, it would be like ignoring some of the loading when picking a transformer or the wire size in a distribution system. If the transformer is sized too small, it could cause a fire. Using a standard transformer, with exactly the listed KVA load for each drive or non-linear load is like using too small a transformer. A 50 KVA SMPS lighting load would require 65 KVA due to the 33% additional 3rd harmonic current load. The higher frequency harmonic current will cause more transformer heating because of eddy current losses in the core and higher wire resistance caused by skin effect. There are two main affects of harmonic currents on a distribution system. The first is that harmonic currents add to the RMS value of the fundamental. This additional current will increase losses in wire, bus bars, transformers and power factor correction capacitors used in the distribution system. A typical value for the additional RMS loss would be 3% if skin effect and core losses could be ignored. Unfortunately, they can not be ignored. The second affect is the additional heating caused by each of the harmonic currents. Transformers, capacitors, circuit breakers, wires and bus bars must be designed to handle the higher frequency currents. If these components are not correctly sized for the harmonic currents, the harmonic currents can cause additional heating in those components. This heating can result in premature component failure and the possibility of fire. New transformer ratings will soon be on the market. These ratings will cover transformers for non-linear loads. Underwriters Laboratory, UL will begin to rate transformer based on the percentage of non-linear loads, whether single phase or three phase. Fahad know ledge centre
  • 3. In a six pulse converter or 3 phase full-wave bridge, the most significant harmonics are the number of pulses ±±1. That means a six pulse converter will create harmonic currents with a frequency 5 times 60 Hz and 7 times 60 Hz. The amplitude of those harmonics will be approximately 1/5 and 1/7 of the amplitude of the fundamental current. In the example, a fundamental or 60 Hz current of 100 amps would contain a 300 Hz current with an amplitude of 1/5 times 100 or 20 amps and a 420 Hz current with an amplitude of If 7 times 100 or 14.3 amps. In RMS terms, the harmonic current distortion value will only amount to approximately: 2 2 2 100 20 143 102 98+ + =. . This additional 3% RMS current would not significantly overheat the components in a distribution system that is not overloaded and used components rated for non-linear loads. 1t linear load rated transformers and capacitors are used, the heating caused by 20% of the 5th harmonic and 14.3% of the 7th harmonic could cause destructive heating if the components are not derated. The chief concern with harmonic currents is that their characteristic are known so that correct sizing can take place. How can harmonic currents affect AC drive sales? Our principle concern should be how to deal with the concern or “fear” that our customers are likely to have regarding harmonic currents. We need to provide as much "good" information as possible without confusing the customer. These basic facts can be given to the customer concerned with harmonic currents and IEEE 519 guideline for harmonic currents. 1. Harmonic currents can cause overheating of distribution system equipment. 2. Harmonic currents are caused by any electrical equipment that used SMPS. 3. Distribution system loading by non-linear equipment can cause older dry type transformers to overheat if not derated. 4. Lighting accounts for 55% of all electrical power used. An estimated 90% of that power is controlled by some type of switching mode power supply (SMPS). That means that 50% of all power used can have harmonic currents overloading transformers, capacitors and other components on the distribution system. 5. Motors account for 40% of all electrical power used. An estimated 20~ Of that power is controlled by some type of 3 phase SMPS. That means that 8% of all power used for controlling motors can have harmonic currents overloading transformers, capacitors and other components on the distribution system. 6: Harmonic current will cause .voltage distortion The amount of distortion is much less than the distortion caused by the normal line current. Voltage distortion by high frequencies will be a percentage of the voltage drop caused by the fundamental current. A 5% drop in line voltage due to the fundamental load current will be increased by the 5th harmonics by 20% of 5% or an additional 1%. 7. Transformers, circuit breakers, and other distribution system components ratings within any facility Should be reviewed based on the original selection and any changes or additions in non-linear loads. 8. Single phase loads, such as lighting loads should be reviewed to determine what level of harmonic current distortion already exists in a system before adding additional non-linear loads to that system. 9. 0f the different types of AC drives on the market, the AC drive which causes the lest amount of harmonic current and voltage distortion over the operating speed range is a PWM AC drive which contains an internal dc bus reactor. The second best is a PWM AC drive with an AC line reactor before the drive. 10. The use of line filters before a drive will add more losses to the electrical system and could create line ringing and large voltage transients. These conditions could results in greater damage to other components on the distribution system. Even if correctly designed for an installation, the filter may have to be modified every time an additional piece of equipment is added to that distribution system. Fahad know ledge centre