2. • Introduction
• Before hybrid power conditioner
• Hybrid power conditioner
• New hybrid power conditioner
• Three phase four wire hybrid filter
• System configuration
• Control principle
• Control block diagram
• Experimental results
• Advantages
• Applications
• Conclusions
• References
2
3. Proposed for suppressing harmonic currents and neutral
line current.
Employed in three phase four wire distribution system.
Consists of neutral line current attenuator and a hybrid
power filter.
Hybrid power filter consists of three phase power
convertor and three phase tuned power filter.
3
4. Zig-zag transformer: Connected to the load in
parallel depends the ratio between utility and zig-zag
transformer
Zig-zag transformer with single phase power converter :
inserted at neutral line fluctuation in the ground voltage of
the load
Series of active power filters: connected to the neutral line
between the utility and load fluctuation in ground voltage of
the load
4
5. Passive power filters :advantage of low hardware cost, affected
by system impedance, large volume, parallel resonance and
series resonance
Power semiconductor technology : Active power filters
suppress the neutral line current capacity and manufacturing
cost of power converter is very high
5
6. 6
Developed to solve the problems of active and passive power
conditioners
HPF consists of passive power filter and a power converter
Passive power filter reduce the capacity of power converter
Power converter improve the filter characteristics of
passive power filter
HPF is divided into series linked and shunt linked type
7. Power converter connected between the utility and load
through a linked transformer in series linked type.
Passive power filter is parallel to the load
Power converter is connected to the passive power filter in
series and then connected to load in parallel in shunt type.
7
8. Hybrid power conditioner: 1. neutral line current attenuator,
2. hybrid power filter.
Hybrid power filter : 1. three phase power converter, 2. three
phase tuned power filter
Neutral line current attenuator to attenuate neutral line current
Can effectively reduce the power rating of passive and active
elements
8
10. Configuration of a conventional shunt type hybrid power filter.
Power converter series with power filter connected to
the load in parallel.
Passive power filter three phase tuned power filters with an
inductor and a capacitor connected in series.
Utility voltage drop on the passive power filter dc bus
voltage and voltage rating reduced harmonic current and
fundamental reactive currents not diminished.
10
12. To reduce the power rating of the power converter.
Power convertor connected to the inductors of the three phase
tuned power filter in parallel.
Reactive current and harmonic current flows through the inductors
decreasing the current flowing through the power converter.
12
13. Major role is to filter the harmonic currents of the load.
Neutral line current of the load contains a fundamental
component in unbalanced three phase loads.
Conventional type cannot suppress the neutral line current
under the unbalanced load.
13
15. A neutral line current attenuator is integrated into the hybrid
filter
Advance the filter performance under the unbalanced load
With an increase in tuned frequency of the tuned power filters
volume and weight of the tuned power filter reduced
Neutral line current attenuator phase voltage drop on
capacitors volume and weight of the transformer reduced
15
16. Current mode control-to control the three phase power
converter of the hybrid power filter
Ica= K1Isah+K2VSA1
Icb=K1Isbh+K2Vsb1
Icc=K1Isch+K2Vsc1
Isah, Isbh , Isch = harmonic components of the three phase utility
currents.
VSA1 , Vsb1 Vsc1 =three phase fundamental voltages of the
utility.
First term - suppress the non zero sequence harmonics
Second term - regulate the dc bus voltage
Reactive current of tuned power filters and harmonic currents
of the load-flows through the inductors - suppression attained
16
17. Feedforward control- adopts in single phase power converter
Vcon=kcon Vm
kcon = gain of the single phase converter
Vm =modulation signal of the PWM circuit.
The gain of the single phase converter is
kcon=Vdc/Vtri
Vdc = bus voltage
Vtri = amplitude of the carrier of the PWM circuit.
Neutral line current of the utility is detected, amplified and
sent to PWM circuit.
Vcon= kconk3Isn , k3 =feedforward gain
17
18. Fig 4.Control block diagram of the three phase and single phase
power converters
18
19. The current references contain fundamental signal and
harmonic signal
The band stop filters are used to extract harmonic signals
Fundamental signal is obtained as the result from the
multiplier
The current references are sent to controllers
The output of controllers sent to PWM circuit
19
20. To control single phase converter
Neutral line current obtained by summing up detected three
phase utility currents
Output of amplifier circuit sent to PWM circuit
The control blocks of three phase and single phase power
converters can integrated into a digital signal processor chip
20
22. Fig 5. Balanced three phase load and hybrid power conditioner
under the balanced three phase load
Total harmonic distortion of the load current is 47% and neutral
line current of load is 11.2A
Shows the utility currents after being compensated by HPC
The three phase utility current are nearly sinusoidal and THD is
3.9% and neutral line current is .81A
22
23. Fig 6. Results of unbalanced three phase load and hybrid power
conditioner under the unbalanced three phase load
The results of unbalanced three phase load currents and neutral
load current
Only a single phase rectifier is applied between the phase a and
neutral line
Three phase utility currents are sinusoidal and THD are 7.35%
, 4.71% and 3.23% res. And neutral line current is .96A
23
24. Enhancing operation efficiency
The power capacity of power converters in the hybrid power
filter and neutral line current attenuator can be effectively
reduced
Suppress neutral line current and harmonic currents
24
25. Three phase four wire distribution systems applied to low
voltage applications
Applicable whether the load is balanced or not
25
26. A new hybrid power conditioner composed of a hybrid power
filter and a neutral line current attenuator is proposed.
Power capacity of power converters reduced and enhancing
the operation efficiency
Effective solution to the problems of harmonic currents and
neutral line current in three phase four wire distribution
system
26
27. [1]Jinn-Chang Wu,Hurng –Liahng Jou and Shun- Tian Xiao, “A
new hybrid power conditioner for suppressing harmonics and
neutral line current in three phase four wire distribution power
systems,”, IEEE Trans. Power Del., vol.29,no. 4 Aug 2014.
[2]B Singh, P. Jayaprakash and D.P.Kothari, “Reduced rating
VSC with a zig-zag transformer for current compensation in a
three phase four wire distribution system,” IEEE Trans. Power
Del., vol.24,no. 1,pp. 249-259,Jan. 2009.
[3]R. M.Ciric, L.F.Ochoa , A. Padilla-Feltrin and H. Nouri ,
“Fault analysis in four wire distribution networks,” Proc. Inst.
Elect .Eng., Gen., Transm . Distrib ., vol. 152,no.6,pp.977-
982,2005.