SlideShare ist ein Scribd-Unternehmen logo
1 von 5
Downloaden Sie, um offline zu lesen
Abstract—Distribution substations feed power to the actual
consumers through distributors and service lines. The main
equipments are generators and transformers. To protected these
equipments and for stability purpose, over-voltages and over currents
protection are important to consider. Lightning is one of the most
serious causes of over-voltage. If the power equipments especially at
outdoor substation are not protected, the over-voltage will cause
burning of insulation. Lightning arrester can protect the damages of
equipments. This paper describes the arrester type, lightning terminal
and earthing plan of Dagon East substation in Myanmar. DynaVar
station class and intermediated arrester (Vrated = 72kV and I charge
(max) = 10kA) are used in this substation. Most of substation
equipments are designed to match with the insulation coordination. If
the insulation equipments are higher, the cost is also high. So, to
relax this, the lightning arrester must be put in front of the protected
equipments and protected zone. For this purposes, this paper
specially indicates the safety and saving cost of equipments for over-
voltage protection in distribution substation.
Keywords—Lightning arrester, Earthing plan, DynaVar station,
Intermediated arrester.
I. INTRODUCTION
UBSTATION design involves more than installing
apparatus, protective devices and equipment. The
significant momentary investment and required reliable
continuous operation of the facility requires detailed attention
to preventing surges from entering the substation facility. The
effects of disturbances with limiting in a power system, which
if allow to persist, may damage plant and interrupt the supply
of electrical energy. Lightning is one of the most serious
causes of over voltage. If the power equipment especially at
outdoor substation is not protected the over-voltage will cause
burning of insulation. Thus it results into complete shutdown
of the power and the loss may run into cores of kyat. Electrical
equipment can be damage due to over-voltage such as
switching surge over-voltage, Lightning surge over-voltage,
transient recovery voltage and power frequency temporary
over-voltage in transmission line and receiving end of
substation. It is important to protect power equipment against
them wherever possible, consistent with sound economic.
Lightning Arrester can protect the damages of electrical
equipments. So, Lightning Arrester needed to install in the
terminal end of the transmission line, substation, high voltage
Miss NayKyiHtwe is a student of Mandalay Technological University.
(e-mail :naykyihtwe08@ gmail.com).
transformers and low voltage transformer. The analysis of
electromagnetic transient is depended on operating voltage,
lengths of the lines and contactor configuration. So, it can be
chosen correctly the technical specifications of the apparatus
of Lightning Arrester base on the amounts of receiving over-
voltage.
II. PHYSICAL PHENOMENON OF LIGHTNING
Lightning is a huge spark caused by the electrical discharge
taking place between the clouds, within the same cloud and
between the clouds and the earth. The turmoil that is apparent
inside a thundercloud is most impressive to the viewer. It
shape changes continually, and one notes especially the
development of the towering ‘thunderhead’. It is very easy to
imagine the fierce updrafts with the cloud and the downdrafts
near it surface which are matters of practical experience for
aviators. It is generally accepted that the updraft is responsible
for charge separation within the cloud, like some gigantic
electrostatic generator, which leads to the creation of electric
fields within and around the cloud and ultimately to the
electric breakdown that is called lightning.
III. WAVE SHAPE OF LIGHTNING STROKE
The lightning stroke current rises to crest value very quickly
and then starts decaying at a low rate as illustrated in Figure.1.
The generalized wave shape can be characterized as:
1. Crest or peak value and it have been observed that
the maximum value of this current is 400 kA.
2. The wave front line varies from 1 t 10 sec.
3. The time at which the stroke current reduces to 50
percent value of that crest value and it has been
estimated that the time varies from 10 to 100 sec.
Figure.1 Generalized wave shape of lightning stroke
Analysis and Design Selection of Lightning
Arrester for Distribution Substation
Nay Kyi Htwe
S
World Academy of Science, Engineering and Technology 48 2008
174
IV. STATIC CHARGING OF THE CONDUCTOR DUE TO A
CHARG CLOUD
Suppose that the cloud is positively charged, then the line
will be charged to a negative potential by the electrostatic
induction. This negative charge will be present right under the
cloud and the portions of the line away from this point will be
charge positively as illustrated in Figure.2.
Figure.2 Static charging of the line due to a cloud
The charge on the line will not flow since it is a bound
charge. The positive charge on the far ends of the line will
however leak to the earth slowly through insulators metallic
parts etc, thus leaving only the negative charge on the line.
Due to a direct discharge occurring between this cloud and
another passing by cloud the charge on the cloud is neutralized
then the charge on the line is no more a bound charge and is
free to travel in both directions in the form of traveling waves.
V. OVERVOLTAGE DUE TO LIGHTNING STROKE
In case of direct strokes, a line having a surge impedance of
Zs and the discharge current be Id, then the over-voltage due to
a direct stroke is
sdd ZIV ×= (1)
When the traveling waves flow in one direction, the
equation is true. However, when they travel in both directions,
the current is halved and the over-voltage is
2
ZI
V sd
d
×
= (2)
When the lightning stroke is on the earth wire or top of a
tower, the over-voltage is
t
i
ccdd
d
d
lZIV +×= (3)
Where Z c is the impedance of the earth conductor and l c is
the inductance of the line conductor.
VI. INTERACTION BETWEEN LIGHTNING AND THE POWER
SYSTEM
When lightning strikes a power line, a current is injected
into the power system. This is very useful concept. This
current will give rise to depend upon its wave shape and the
impedances through which it flows. If a tower is struck, the
impedance of the tower will be of concern. The voltage drop
down the tower will appear across the line insulation. If this is
excessive, flashover of the insulation will occur and a fault will
be placed on the system.
The current comings into a tower have been postulated by
lightning stroke from a cloud, and then disappear into the
ground. A useful concept is to think of the cloud and earth as
forming a vast capacitor which is being discharge by the
stroke. The return circuit would be completed by displacement
current in the electric field. This is suggested by Figure.3.
Stroke
Earth
cloud
Figure.3 Lightning stroke from cloud to earth discharges a
vast Capacitor
VII. LIGHTNING ARRESTER
Lightning arresters are the most effective means of
protecting an electrical apparatus against traveling voltage
waves caused by lightning and switching. Lightning arresters
are connected across and apparatus to provide a Low-
resistance path to ground, thus limiting the transient voltages
below the Basic Impulse Level of the apparatus. There are four
different classes of arrester.
1. Station
2. Intermediate
3. Distribution, and
4. Secondary
The functions of a lightning arrester are
1. To act like an open circuit during the normal
operation of the system i.e., to hold off the system
voltage,
2. To limit the transient voltage to a safe level with
the minimum delay and fitter, and
3. To bring the system back to its normal operation
mode as soon as the transient voltage is
suppressed, i.e., to interrupt the power-follow
current and to reseal itself.
The normal operation or operational mode includes the
system under faulted condition. Under several types of system
faults, such as the single line-to-ground faults, the voltage to
ground across the unfaulted phases will rise above the normal
voltage level. The arrester must not go into conduction during
this fault condition. It should also be able to interrupt the
power-follow current and reseal itself under system fault
conditions when the power-frequency voltage across it rises.
VIII. SELECTION OF LIGHTNING ARRESTER
The lightning arresters are designated by the crest
magnitude of the discharge current having 10×20 second
wave shape which the arrester can safely pass without damage.
The lightning arresters are designated as 8, 10, 20 KA. They
World Academy of Science, Engineering and Technology 48 2008
175
can safely discharge these current crests. As the arrester is a
protective device, if is a general impression that if should be
rated for most severe conditions of discharge currents says 20
A. The discharge current from the arrester varies from a few
hundred amperes to kilo-amperes and sometimes if is even 20
KA. Maximum discharge voltage and discharge factor for the
arrester is defined the maximum value of voltage which
appears across the arrester terminals at the time of discharging
if rated current determines its impulse level of protection. The
discharge factor if is,
DF=
arrestertheofvalue)(RMSvoltageRated
arrestertheofvalue)(crestvoltagedischarge
(5)
In the early designs of arresters, this discharge factor was
quite high (about 5.6) but due to the advent of better material
and Modern research it has been reduced varying to 2.4 to 3.0.
The above ratio for arresters manufactured by different firms
varies from 1.5 to 1.7, so, the average value may be taken as
1.6 E is the rated arrester voltage KV (R.M.S) and LS is the
minimum impulse insulation level in kV (crest valve) its value
after allowing 10% as tolerance factor and 25% as margin
factor can be obtained.
LS= E
0.8
21.61.11.25 ×××
=3.88E (6)
In case Extra High Voltage system LP in kV,
LP = 2.3 × power frequency withstand voltage in kV (RMS)
= 2.3 × EL (7)
For 75% arrester,
LP = 2.37 EL (8)
For 80% arrester,
LP=2.53EL (9)
IX. EARTHING SYSTEM
The frame of every generator, stationary motor, and so far
as particable, portable motor, and metallic parts of all
transformer and regulating and controlling apparatus
connected with supply shall be earthed by the owner by
separate and distinct connection with earth.
Every conductor used on earthing shall be of stranded as
solid copper or suitable copper alloy, and shall be protected
wherever liable to mechanical damage and also, where
necessary, against corrosion, particular attention being given in
these respects to the earthing leads at its point of connection
with the earth electrode. The coefficient of earthing is below
80 percent. On four wire distribution systems, with solidly
ground transformer neutral at every voltage level, coefficient
of earthing is generally less than 80%. On high voltage
transmission systems the coefficient of earthing does not
exceed 75%.
In resistance of Common Types of Earth-electrode, there are
three types.
1. Plates
2. Pipes and rods
3. Strip or conductor electrodes
X. INTERMEDIATE CLASS DYNAVAR ARRESTER
Application is based upon the maximum continuous
operation voltage, line to neutral, at the arrester location. For
grounded neutral systems, this is computed as maximum
system voltage divided by √3. For historical comparison, the
maximum continuous operating voltage is 81% of the
conventional 71% arrester installed on an affectively grounded
neutral system.
Figure.4 Section view of typical unit
A. Lightning Arrester Design
At Dagon East substation, DynaVar station class and
intermediate surge arresters are used. The system voltage is 66
kV and maximum continuous operation voltage is 48 kV rms.
The duty cycle rating is 60 kV rms and maximum discharge
current is 10 kA.
1. Maximum 0.5µs discharge voltage = 163.5 kV
2. Maximum switching surge protective level=116.4 kV
3. Maximum discharge voltage using an 8/20=148.8 kV
Current wave-kV
The maximum discharge voltage for a10kA impulse current
wave produces a voltage wave cresting in 0.5µs.
B. Structure of Lightning Arrester
In Figure.5, PVN 48.0kV maximum continuous operation
voltage arrester is shown. It has 0.56 diameter holes, clamp
type terminal, arrester name plate. Its internal diameter is 9.3
diameters.
Figure.5 PVN 48.0 kV maximum continuous operation
voltage Arrester
9.3
1.7
Clamp Type Terminals Suitable
for Use with CU DR AL
Conductor 0.25 to 0.81 Dia
0.56 Dia 3 Holes at
120˚ On 10.0 Dia BC
1.750.56
Diameter 4
Holes
Arrester Nameplate
32.
3
World Academy of Science, Engineering and Technology 48 2008
176
C. Specification of Lightning Arrester for Incoming Side
Incoming side of Dagon East substation, the
specifications of lightning arrester are as follow.
Figure.6 One Line Diagram of East Dagon 30MVA
Substation
System nominal voltage = 66kV
Rated normal Voltage = 66 × 1.1 = 72.6kV
Continuous Operating Voltage (kV) rms = 48.0kV
Normal Discharge Current (8 /20µs) kA = 10kA
1/50 Impulse Spark over Voltage = 163.5kV
Frequency (Hz) = 50Hz
Type = outdoor
D. Specifications of Lightning Arrester for Outgoing Side
The followings are the specifications of lightning arrester
for outgoing side of Dagon East substation.
System nominal voltage = 33kV
Rated normal Voltage = 33 × 1.1 = 36kV
Continuous Operating Voltage (kV) rms = 24kV
Normal Discharge Current (8 /20µs) (kA) = 10kA
Frequency (Hz) = 50Hz
Type = outdoor
XI. LIGHTNING EARTHING
In earthing system, lightning arresters with PVC coated
wire and cable lug are used.
1. 66kV Lighting Arrester(70mm2
PVC Coated Wire)
= 50'
2. 33kV Lighting Arrester(70mm2
PVC Coated Wire)
= 100'
3. 70mm2
Cable Lug = 2 No
Figure.7 shows the earthing plan of Dagon East substation.
XII. DETAILED DESIGN DATA
For incoming side and outgoing side, the discharge
voltage, insulation level, minimum impulse insulation level
and power frequency withstand voltage base on 100% arrester
are as shown in Table.1. Ground voltage peak value and
switching surge withstand voltage are also shown in Table.1.
Table.1. Detailed Design Data Sheet
System
Voltage
66kV for
Incoming Side
33kV for
Outgoing Side
Rated Voltage (kV) 72.6 36
Discharge Voltage
on 100% Arrester (kV)
188.76 93.6
Insulation Level for
100% Arrester (kV)
284.78 164.4
Minimum Impulse
Insulation Level on
100%(kV)
732.389 363.168
Power Frequency
withstand Voltage on
100% (kV)
151.8 75.9
Ground Voltage
Peak Value(kV)
59.28 29.63
Require Switching
Surge Withstand
Voltage (kV)
215.6 107.8
XIII.CONCLUSION
In this paper, the basis theory of lightning, lightning
shielding and design of lightning arrester are presented.
DynaVar station class and intermediate arresters are used. The
type of arrester is outdoor type. The rated voltages of arresters
are 72kV and 36kV, the maximum discharge current is 10kA
and MCOV are 48kVrms and 24kVrms. The lightning arrester
in this paper is provided for overvoltage protection in
distribution substation. This paper will help and give the
electrical knowledge of the protection system in distribution
substation which coach to the technicians, the professional
engineers, the students who facing the overvoltage condition
and protection coordination of distribution substation.
ACKNOWLEDGMENT
Firstly, the author would like to express her indebtedness
and gratitude to her beloved parents, for their kindness,
support, understanding during the whole course of this work
and encouragement to attain ambition without any trouble. The
author is indebted to all her teachers who give her knowledge
from M.T.U and Y.T.U in Myanmar.
REFERENCES
[1] Allan Greenwood 1923 “Electrical Transients in Power System”
Second Edition, John Willey & Sons, Inc
[2] Anderson 1987 “Transmission Line Reference Book”, Second
Edition Substations Committee
[3] ANSI/ IEEE 1989 ” IEEE Standard for Gapped Silicon-Carbide
Surge Arresters for AC Power Circuit”
[4] Franked- Graham 1970 “New Electric Library” Vol-2
[5] IEEE Std 998- 1996 “Guide for Direct Lightning Stroke Shielding of
Substation”, IEEE Working Group D5,
[6] U Tin Swe “Power System Analysis Part 3”
World Academy of Science, Engineering and Technology 48 2008
177
Figure.7 Dagon East Sub-station Earthing Plan
66kV TR:
30 MVA
R = 2
66kV LA
66kV Switch
Yard
33kV LA
33kV TR:
10 MVA
100kVA
Transformer
Switch Gear Panel Earth Ring System
10MVA×R
Neutral Earth
100VA
Neutral Earth
Lightning
Arrester
Lightning
Arrester
Body Earth
LA Earth
LA Earth
DS Earth
R = 1.8
2 Pole DS LA PT CT CB CB CT PT DS
CB CT PT DS
10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´10´ 10´10´ 10´
R = 2
Lightning Earth
R = 2 R = 2
Lightning Earth
30MVA
Body
Earth
30MVA×
R
World Academy of Science, Engineering and Technology 48 2008
178

Weitere ähnliche Inhalte

Was ist angesagt?

Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesPower System Operation
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission linesHamzaAbbas43
 
Conductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersConductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersGilberto Mejía
 
transmission-lines
transmission-linestransmission-lines
transmission-linesATTO RATHORE
 
Protection system
Protection systemProtection system
Protection systemAIRMANGESH
 
Surge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformerSurge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformerVIKAS KUMAR MANJHI
 
Corona effect, corona ring and any other topics
Corona effect, corona ring and any other topicsCorona effect, corona ring and any other topics
Corona effect, corona ring and any other topicsMithilesh Raj
 
6654882 presentation-on-insulation-co ordination
6654882 presentation-on-insulation-co ordination6654882 presentation-on-insulation-co ordination
6654882 presentation-on-insulation-co ordinationRui Zhang
 
Surge Arresters construction and working
Surge Arresters construction and workingSurge Arresters construction and working
Surge Arresters construction and workingMuhammad Faisal Ikram
 
58808269 microwave-manual
58808269 microwave-manual58808269 microwave-manual
58808269 microwave-manualkeerthi vasan
 
Power capacity of transmission lines
Power capacity of transmission linesPower capacity of transmission lines
Power capacity of transmission linesAlexander Decker
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission linemd muzahidul haque
 
Over voltages in power system
Over voltages in power systemOver voltages in power system
Over voltages in power systemSANGEETHA S
 

Was ist angesagt? (20)

Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & Types
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission lines
 
Electrical q
Electrical qElectrical q
Electrical q
 
Conductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersConductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arresters
 
transmission-lines
transmission-linestransmission-lines
transmission-lines
 
EE6701 - HVE
EE6701 - HVEEE6701 - HVE
EE6701 - HVE
 
Protection system
Protection systemProtection system
Protection system
 
Lighting arrester
Lighting arresterLighting arrester
Lighting arrester
 
Surge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformerSurge arrester and surge suppressor on transformer
Surge arrester and surge suppressor on transformer
 
Corona effect, corona ring and any other topics
Corona effect, corona ring and any other topicsCorona effect, corona ring and any other topics
Corona effect, corona ring and any other topics
 
Trapatt diode
Trapatt diode Trapatt diode
Trapatt diode
 
6654882 presentation-on-insulation-co ordination
6654882 presentation-on-insulation-co ordination6654882 presentation-on-insulation-co ordination
6654882 presentation-on-insulation-co ordination
 
Lightning Arrestar
Lightning ArrestarLightning Arrestar
Lightning Arrestar
 
Surge Arresters construction and working
Surge Arresters construction and workingSurge Arresters construction and working
Surge Arresters construction and working
 
58808269 microwave-manual
58808269 microwave-manual58808269 microwave-manual
58808269 microwave-manual
 
Power capacity of transmission lines
Power capacity of transmission linesPower capacity of transmission lines
Power capacity of transmission lines
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission line
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
 
Over voltages in power system
Over voltages in power systemOver voltages in power system
Over voltages in power system
 
ECE2708 Microwave Engineering Lab Joournal
ECE2708 Microwave Engineering Lab JoournalECE2708 Microwave Engineering Lab Joournal
ECE2708 Microwave Engineering Lab Joournal
 

Andere mochten auch

Lightning Protection Systems: Surge Protection
Lightning Protection Systems: Surge ProtectionLightning Protection Systems: Surge Protection
Lightning Protection Systems: Surge ProtectionAplicaciones Tecnológicas
 
Lightning protection to structures and power systems
Lightning protection to structures and power systemsLightning protection to structures and power systems
Lightning protection to structures and power systemsSuryanarayana Danturti
 
**Lightning Arrester Presentation**
**Lightning Arrester Presentation****Lightning Arrester Presentation**
**Lightning Arrester Presentation**SKPAMB
 
Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...
Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...
Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...Living Online
 

Andere mochten auch (7)

Lightning Protection Systems: Surge Protection
Lightning Protection Systems: Surge ProtectionLightning Protection Systems: Surge Protection
Lightning Protection Systems: Surge Protection
 
Lightning protection to structures and power systems
Lightning protection to structures and power systemsLightning protection to structures and power systems
Lightning protection to structures and power systems
 
Lightning arrester
Lightning arresterLightning arrester
Lightning arrester
 
Lightning arresters
Lightning arrestersLightning arresters
Lightning arresters
 
**Lightning Arrester Presentation**
**Lightning Arrester Presentation****Lightning Arrester Presentation**
**Lightning Arrester Presentation**
 
Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...
Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...
Lightning, Surge Protection & Earthing of Electrical & Electronic Systems in ...
 
Lightning protection
Lightning protectionLightning protection
Lightning protection
 

Ähnlich wie Arrester

Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltageMuhammedArifTanoli
 
How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?Fang Sam
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINEIRJET Journal
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Jaydeep Chauhan
 
ECE611_paper_Hyusein_Abibe
ECE611_paper_Hyusein_AbibeECE611_paper_Hyusein_Abibe
ECE611_paper_Hyusein_AbibeAbibe Hyusein
 
SUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptxSUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptxHimanshuShrivastava74
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant ProtectionMike Nager
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iiiILDTECH
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Milton Sarker
 
Light Triggering Thyristor for HVDC and other Applications
Light Triggering Thyristor for HVDC and other ApplicationsLight Triggering Thyristor for HVDC and other Applications
Light Triggering Thyristor for HVDC and other ApplicationsIDES Editor
 
Transient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesTransient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesBruno De Wachter
 

Ähnlich wie Arrester (20)

E04523236
E04523236E04523236
E04523236
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
Study tour to optcl
Study tour to optclStudy tour to optcl
Study tour to optcl
 
How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?
 
Shruthi
ShruthiShruthi
Shruthi
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
 
Emi unit iv ppt
Emi unit iv pptEmi unit iv ppt
Emi unit iv ppt
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
 
2b.pptx
2b.pptx2b.pptx
2b.pptx
 
ECE611_paper_Hyusein_Abibe
ECE611_paper_Hyusein_AbibeECE611_paper_Hyusein_Abibe
ECE611_paper_Hyusein_Abibe
 
SUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptxSUBSTATION DESIGN powerpoint presentation.pptx
SUBSTATION DESIGN powerpoint presentation.pptx
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant Protection
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iii
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
Witricity
WitricityWitricity
Witricity
 
D.pdf
D.pdfD.pdf
D.pdf
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.
 
Light Triggering Thyristor for HVDC and other Applications
Light Triggering Thyristor for HVDC and other ApplicationsLight Triggering Thyristor for HVDC and other Applications
Light Triggering Thyristor for HVDC and other Applications
 
Transient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesTransient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surges
 

Kürzlich hochgeladen

FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756dollysharma2066
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageMatteo Carbone
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptxnandhinijagan9867
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...lizamodels9
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLSeo
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Serviceritikaroy0888
 
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...lizamodels9
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1kcpayne
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service NoidaCall Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service Noidadlhescort
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLBAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLkapoorjyoti4444
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfAmzadHosen3
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876dlhescort
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with CultureSeta Wicaksana
 

Kürzlich hochgeladen (20)

FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
Call Girls From Pari Chowk Greater Noida ❤️8448577510 ⊹Best Escorts Service I...
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service NoidaCall Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLBAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
 
Falcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in indiaFalcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in india
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdf
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 

Arrester

  • 1. Abstract—Distribution substations feed power to the actual consumers through distributors and service lines. The main equipments are generators and transformers. To protected these equipments and for stability purpose, over-voltages and over currents protection are important to consider. Lightning is one of the most serious causes of over-voltage. If the power equipments especially at outdoor substation are not protected, the over-voltage will cause burning of insulation. Lightning arrester can protect the damages of equipments. This paper describes the arrester type, lightning terminal and earthing plan of Dagon East substation in Myanmar. DynaVar station class and intermediated arrester (Vrated = 72kV and I charge (max) = 10kA) are used in this substation. Most of substation equipments are designed to match with the insulation coordination. If the insulation equipments are higher, the cost is also high. So, to relax this, the lightning arrester must be put in front of the protected equipments and protected zone. For this purposes, this paper specially indicates the safety and saving cost of equipments for over- voltage protection in distribution substation. Keywords—Lightning arrester, Earthing plan, DynaVar station, Intermediated arrester. I. INTRODUCTION UBSTATION design involves more than installing apparatus, protective devices and equipment. The significant momentary investment and required reliable continuous operation of the facility requires detailed attention to preventing surges from entering the substation facility. The effects of disturbances with limiting in a power system, which if allow to persist, may damage plant and interrupt the supply of electrical energy. Lightning is one of the most serious causes of over voltage. If the power equipment especially at outdoor substation is not protected the over-voltage will cause burning of insulation. Thus it results into complete shutdown of the power and the loss may run into cores of kyat. Electrical equipment can be damage due to over-voltage such as switching surge over-voltage, Lightning surge over-voltage, transient recovery voltage and power frequency temporary over-voltage in transmission line and receiving end of substation. It is important to protect power equipment against them wherever possible, consistent with sound economic. Lightning Arrester can protect the damages of electrical equipments. So, Lightning Arrester needed to install in the terminal end of the transmission line, substation, high voltage Miss NayKyiHtwe is a student of Mandalay Technological University. (e-mail :naykyihtwe08@ gmail.com). transformers and low voltage transformer. The analysis of electromagnetic transient is depended on operating voltage, lengths of the lines and contactor configuration. So, it can be chosen correctly the technical specifications of the apparatus of Lightning Arrester base on the amounts of receiving over- voltage. II. PHYSICAL PHENOMENON OF LIGHTNING Lightning is a huge spark caused by the electrical discharge taking place between the clouds, within the same cloud and between the clouds and the earth. The turmoil that is apparent inside a thundercloud is most impressive to the viewer. It shape changes continually, and one notes especially the development of the towering ‘thunderhead’. It is very easy to imagine the fierce updrafts with the cloud and the downdrafts near it surface which are matters of practical experience for aviators. It is generally accepted that the updraft is responsible for charge separation within the cloud, like some gigantic electrostatic generator, which leads to the creation of electric fields within and around the cloud and ultimately to the electric breakdown that is called lightning. III. WAVE SHAPE OF LIGHTNING STROKE The lightning stroke current rises to crest value very quickly and then starts decaying at a low rate as illustrated in Figure.1. The generalized wave shape can be characterized as: 1. Crest or peak value and it have been observed that the maximum value of this current is 400 kA. 2. The wave front line varies from 1 t 10 sec. 3. The time at which the stroke current reduces to 50 percent value of that crest value and it has been estimated that the time varies from 10 to 100 sec. Figure.1 Generalized wave shape of lightning stroke Analysis and Design Selection of Lightning Arrester for Distribution Substation Nay Kyi Htwe S World Academy of Science, Engineering and Technology 48 2008 174
  • 2. IV. STATIC CHARGING OF THE CONDUCTOR DUE TO A CHARG CLOUD Suppose that the cloud is positively charged, then the line will be charged to a negative potential by the electrostatic induction. This negative charge will be present right under the cloud and the portions of the line away from this point will be charge positively as illustrated in Figure.2. Figure.2 Static charging of the line due to a cloud The charge on the line will not flow since it is a bound charge. The positive charge on the far ends of the line will however leak to the earth slowly through insulators metallic parts etc, thus leaving only the negative charge on the line. Due to a direct discharge occurring between this cloud and another passing by cloud the charge on the cloud is neutralized then the charge on the line is no more a bound charge and is free to travel in both directions in the form of traveling waves. V. OVERVOLTAGE DUE TO LIGHTNING STROKE In case of direct strokes, a line having a surge impedance of Zs and the discharge current be Id, then the over-voltage due to a direct stroke is sdd ZIV ×= (1) When the traveling waves flow in one direction, the equation is true. However, when they travel in both directions, the current is halved and the over-voltage is 2 ZI V sd d × = (2) When the lightning stroke is on the earth wire or top of a tower, the over-voltage is t i ccdd d d lZIV +×= (3) Where Z c is the impedance of the earth conductor and l c is the inductance of the line conductor. VI. INTERACTION BETWEEN LIGHTNING AND THE POWER SYSTEM When lightning strikes a power line, a current is injected into the power system. This is very useful concept. This current will give rise to depend upon its wave shape and the impedances through which it flows. If a tower is struck, the impedance of the tower will be of concern. The voltage drop down the tower will appear across the line insulation. If this is excessive, flashover of the insulation will occur and a fault will be placed on the system. The current comings into a tower have been postulated by lightning stroke from a cloud, and then disappear into the ground. A useful concept is to think of the cloud and earth as forming a vast capacitor which is being discharge by the stroke. The return circuit would be completed by displacement current in the electric field. This is suggested by Figure.3. Stroke Earth cloud Figure.3 Lightning stroke from cloud to earth discharges a vast Capacitor VII. LIGHTNING ARRESTER Lightning arresters are the most effective means of protecting an electrical apparatus against traveling voltage waves caused by lightning and switching. Lightning arresters are connected across and apparatus to provide a Low- resistance path to ground, thus limiting the transient voltages below the Basic Impulse Level of the apparatus. There are four different classes of arrester. 1. Station 2. Intermediate 3. Distribution, and 4. Secondary The functions of a lightning arrester are 1. To act like an open circuit during the normal operation of the system i.e., to hold off the system voltage, 2. To limit the transient voltage to a safe level with the minimum delay and fitter, and 3. To bring the system back to its normal operation mode as soon as the transient voltage is suppressed, i.e., to interrupt the power-follow current and to reseal itself. The normal operation or operational mode includes the system under faulted condition. Under several types of system faults, such as the single line-to-ground faults, the voltage to ground across the unfaulted phases will rise above the normal voltage level. The arrester must not go into conduction during this fault condition. It should also be able to interrupt the power-follow current and reseal itself under system fault conditions when the power-frequency voltage across it rises. VIII. SELECTION OF LIGHTNING ARRESTER The lightning arresters are designated by the crest magnitude of the discharge current having 10×20 second wave shape which the arrester can safely pass without damage. The lightning arresters are designated as 8, 10, 20 KA. They World Academy of Science, Engineering and Technology 48 2008 175
  • 3. can safely discharge these current crests. As the arrester is a protective device, if is a general impression that if should be rated for most severe conditions of discharge currents says 20 A. The discharge current from the arrester varies from a few hundred amperes to kilo-amperes and sometimes if is even 20 KA. Maximum discharge voltage and discharge factor for the arrester is defined the maximum value of voltage which appears across the arrester terminals at the time of discharging if rated current determines its impulse level of protection. The discharge factor if is, DF= arrestertheofvalue)(RMSvoltageRated arrestertheofvalue)(crestvoltagedischarge (5) In the early designs of arresters, this discharge factor was quite high (about 5.6) but due to the advent of better material and Modern research it has been reduced varying to 2.4 to 3.0. The above ratio for arresters manufactured by different firms varies from 1.5 to 1.7, so, the average value may be taken as 1.6 E is the rated arrester voltage KV (R.M.S) and LS is the minimum impulse insulation level in kV (crest valve) its value after allowing 10% as tolerance factor and 25% as margin factor can be obtained. LS= E 0.8 21.61.11.25 ××× =3.88E (6) In case Extra High Voltage system LP in kV, LP = 2.3 × power frequency withstand voltage in kV (RMS) = 2.3 × EL (7) For 75% arrester, LP = 2.37 EL (8) For 80% arrester, LP=2.53EL (9) IX. EARTHING SYSTEM The frame of every generator, stationary motor, and so far as particable, portable motor, and metallic parts of all transformer and regulating and controlling apparatus connected with supply shall be earthed by the owner by separate and distinct connection with earth. Every conductor used on earthing shall be of stranded as solid copper or suitable copper alloy, and shall be protected wherever liable to mechanical damage and also, where necessary, against corrosion, particular attention being given in these respects to the earthing leads at its point of connection with the earth electrode. The coefficient of earthing is below 80 percent. On four wire distribution systems, with solidly ground transformer neutral at every voltage level, coefficient of earthing is generally less than 80%. On high voltage transmission systems the coefficient of earthing does not exceed 75%. In resistance of Common Types of Earth-electrode, there are three types. 1. Plates 2. Pipes and rods 3. Strip or conductor electrodes X. INTERMEDIATE CLASS DYNAVAR ARRESTER Application is based upon the maximum continuous operation voltage, line to neutral, at the arrester location. For grounded neutral systems, this is computed as maximum system voltage divided by √3. For historical comparison, the maximum continuous operating voltage is 81% of the conventional 71% arrester installed on an affectively grounded neutral system. Figure.4 Section view of typical unit A. Lightning Arrester Design At Dagon East substation, DynaVar station class and intermediate surge arresters are used. The system voltage is 66 kV and maximum continuous operation voltage is 48 kV rms. The duty cycle rating is 60 kV rms and maximum discharge current is 10 kA. 1. Maximum 0.5µs discharge voltage = 163.5 kV 2. Maximum switching surge protective level=116.4 kV 3. Maximum discharge voltage using an 8/20=148.8 kV Current wave-kV The maximum discharge voltage for a10kA impulse current wave produces a voltage wave cresting in 0.5µs. B. Structure of Lightning Arrester In Figure.5, PVN 48.0kV maximum continuous operation voltage arrester is shown. It has 0.56 diameter holes, clamp type terminal, arrester name plate. Its internal diameter is 9.3 diameters. Figure.5 PVN 48.0 kV maximum continuous operation voltage Arrester 9.3 1.7 Clamp Type Terminals Suitable for Use with CU DR AL Conductor 0.25 to 0.81 Dia 0.56 Dia 3 Holes at 120˚ On 10.0 Dia BC 1.750.56 Diameter 4 Holes Arrester Nameplate 32. 3 World Academy of Science, Engineering and Technology 48 2008 176
  • 4. C. Specification of Lightning Arrester for Incoming Side Incoming side of Dagon East substation, the specifications of lightning arrester are as follow. Figure.6 One Line Diagram of East Dagon 30MVA Substation System nominal voltage = 66kV Rated normal Voltage = 66 × 1.1 = 72.6kV Continuous Operating Voltage (kV) rms = 48.0kV Normal Discharge Current (8 /20µs) kA = 10kA 1/50 Impulse Spark over Voltage = 163.5kV Frequency (Hz) = 50Hz Type = outdoor D. Specifications of Lightning Arrester for Outgoing Side The followings are the specifications of lightning arrester for outgoing side of Dagon East substation. System nominal voltage = 33kV Rated normal Voltage = 33 × 1.1 = 36kV Continuous Operating Voltage (kV) rms = 24kV Normal Discharge Current (8 /20µs) (kA) = 10kA Frequency (Hz) = 50Hz Type = outdoor XI. LIGHTNING EARTHING In earthing system, lightning arresters with PVC coated wire and cable lug are used. 1. 66kV Lighting Arrester(70mm2 PVC Coated Wire) = 50' 2. 33kV Lighting Arrester(70mm2 PVC Coated Wire) = 100' 3. 70mm2 Cable Lug = 2 No Figure.7 shows the earthing plan of Dagon East substation. XII. DETAILED DESIGN DATA For incoming side and outgoing side, the discharge voltage, insulation level, minimum impulse insulation level and power frequency withstand voltage base on 100% arrester are as shown in Table.1. Ground voltage peak value and switching surge withstand voltage are also shown in Table.1. Table.1. Detailed Design Data Sheet System Voltage 66kV for Incoming Side 33kV for Outgoing Side Rated Voltage (kV) 72.6 36 Discharge Voltage on 100% Arrester (kV) 188.76 93.6 Insulation Level for 100% Arrester (kV) 284.78 164.4 Minimum Impulse Insulation Level on 100%(kV) 732.389 363.168 Power Frequency withstand Voltage on 100% (kV) 151.8 75.9 Ground Voltage Peak Value(kV) 59.28 29.63 Require Switching Surge Withstand Voltage (kV) 215.6 107.8 XIII.CONCLUSION In this paper, the basis theory of lightning, lightning shielding and design of lightning arrester are presented. DynaVar station class and intermediate arresters are used. The type of arrester is outdoor type. The rated voltages of arresters are 72kV and 36kV, the maximum discharge current is 10kA and MCOV are 48kVrms and 24kVrms. The lightning arrester in this paper is provided for overvoltage protection in distribution substation. This paper will help and give the electrical knowledge of the protection system in distribution substation which coach to the technicians, the professional engineers, the students who facing the overvoltage condition and protection coordination of distribution substation. ACKNOWLEDGMENT Firstly, the author would like to express her indebtedness and gratitude to her beloved parents, for their kindness, support, understanding during the whole course of this work and encouragement to attain ambition without any trouble. The author is indebted to all her teachers who give her knowledge from M.T.U and Y.T.U in Myanmar. REFERENCES [1] Allan Greenwood 1923 “Electrical Transients in Power System” Second Edition, John Willey & Sons, Inc [2] Anderson 1987 “Transmission Line Reference Book”, Second Edition Substations Committee [3] ANSI/ IEEE 1989 ” IEEE Standard for Gapped Silicon-Carbide Surge Arresters for AC Power Circuit” [4] Franked- Graham 1970 “New Electric Library” Vol-2 [5] IEEE Std 998- 1996 “Guide for Direct Lightning Stroke Shielding of Substation”, IEEE Working Group D5, [6] U Tin Swe “Power System Analysis Part 3” World Academy of Science, Engineering and Technology 48 2008 177
  • 5. Figure.7 Dagon East Sub-station Earthing Plan 66kV TR: 30 MVA R = 2 66kV LA 66kV Switch Yard 33kV LA 33kV TR: 10 MVA 100kVA Transformer Switch Gear Panel Earth Ring System 10MVA×R Neutral Earth 100VA Neutral Earth Lightning Arrester Lightning Arrester Body Earth LA Earth LA Earth DS Earth R = 1.8 2 Pole DS LA PT CT CB CB CT PT DS CB CT PT DS 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´ 10´10´ 10´10´ 10´ R = 2 Lightning Earth R = 2 R = 2 Lightning Earth 30MVA Body Earth 30MVA× R World Academy of Science, Engineering and Technology 48 2008 178