Unified Power Flow Controller: Modeling And Dynamic Characteristic Ho Dac Loc Hochiminh City University of Technology (HUTECH), Hochiminh City Abstract: - Unified power flow controller (UPFC) consists two converters. There are three purposes of this paper, firstly to illustrate the UPFC device based VSC designs, then to describe a decoupling method the UPFC’s controller into two separate control systems of the shunt and the series converters respectively in realizing an appropriate co-ordination between them. Finally, using the Matlab tool to build a discrete simulator for the UPFC with 12 pulse converters. The simulation results show that the developed UPFC model is reflected the static and dynamic characteristics of the UPFC. The harmonics of the output of the model are analyzed. Using the simple power system with UPFC as an example, the dynamics characteristics are studied. The fault status of the system with UPFC is analyzed too. Keyword list: - Times Roman, image area, acronyms, references 
I. INTRODUCTION 
The developing interest in tools for power flow control in a power system has increased significantly during the last 10 years. Demand for research in this field is motivated by rapid transformations in both technology and organization of the power system industry [1]. The deregulation and competitive environment in the contemporary power networks will imply a new scenario in terms of load and power flows condition and so causing problems of line transmission capacity. For this reason, Flexible AC Transmission System (FACTS) controllers has rapidly developed to meet the need for increasing transmission capacity and controlling power flows through predefined transmission corridors. Especially, the improvements in the field of power electronics have had a major impact on the development of this technology. The devices of new FACTS generation are based on the use of high power electronic components such as GTO (Gate Turn-Off Thyristor) and IGBT (Insulated Gate Bipolar Transistor) which makes them respond quickly to the control requirements. It is called by the FACTS technologies based on Voltage Sourced Converter (VSC) designs. The wider application of FATCS leads to numerous benefits for electrical transmission system infrastructure, including increased capacity at minimum cost; enhanced reliability through proven performance; higher levels of security by means of sophisticated control & protection; and improved system controllability with state-of-the-art technology concepts. Thereby, these FACTS devices are able to act almost instantaneously to changes in power system [2]. The most powerful in family of FACTS devices is the Unified Power Flow Controller (UPFC), because it can control simultaneously all three parameters of transmission power line (line impedance, voltage and phase angle). In practice, the UPFC device consists of two Voltage Source Converters (VSC) connected respectively in shunt and in series with the transmission line, and connected to each other by a common DC link including a storage capacitor. The shunt converter is used for voltage regulation at the point of connection injecting an opportune reactive power flow into the line and to balance the real power flow exchanged between the series converter and the transmission line. The series converter can be used to control the real and reactive line power flow inserting an opportune voltage with controllable magnitude and phase in series with the transmission line. Thereby, the UPFC can perform functions of reactive shunt compensation, active and reactive series compensation and phase shifting [3]. There are many different UPFC models have been investigated by several authors [4-6]. The three main purposes of the paper are firstly to illustrate the UPFC configuration based on VSC’s, and then describe a decoupling method the UPFC’s controller into two separate control systems of the shunt and the series converters respectively in realizing an appropriate co-ordination between them, and finally to simulate a new discrete UPFC model based on 12-pulse VSC using Matlab Power Block/Simulink as simulation program. Besides, PWM method is applied to decrease total of voltage harmonics in simulation output of converters. 
II. THE UPFC CONFIGURATION– BASED VOLTAGE SOURCE CONVERTER 
1. VSC design concept 
The single-line diagram of the UPFC is a combination of two VSC configurations shown in Figures 1. As shown in Figures 1, VSC designs are composed of two basic configurations: A) Shunt Connected VSC System, and
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 53 | P a g e 
B) Series Connected VSC System 
Figure 1 – the UPFC configuration. A basic schematic diagram of the VSC design is illustrated in Figure 2. As a typical configuration, the VSC is a six-pulse converter consisting of six power semiconductor switching devices (GTO, GCT, IGBT, etc) with anti-parallel connected diode together with heat sinks and auxiliary equipment for gating, monitoring and grading. In a high power converter, a number of semiconductor devices may be connected in series or in parallel. Some advanced configurations, for example connecting cascade of two six-pulse converters to twelve- pulse converter, have developed to reduce total of voltage harmonics of converter outputs in Fig. 3. 
Figure 2 – Basic VSC Schematic Diagram From a point of D.C. voltage source, provided by a charged capacitor CS, the converter produces a set of controllable three-phase output voltages at the fundamental harmonic frequency of the A.C. system voltage. The output voltage waveform may be a square waveform (Figure 4.a) or a pulse width modulated (PWM) waveform (Figure 4.b), depending on circuit topology and pulse modulation method. 
Figure 3 – 12 Pulse-VSC Schematic Diagram 
Shunt Converter 
Series Converter 
Shunt Transformer 
Series Transformer 
Power transmission line 
Power transmission line 
DC capacitor 
UPFC 
F 
F 
A 
B 
VDC 
vA 
vB 
vC 
iA 
iB 
iC 
iDC 
VDC 
v’A 
v’B 
v’C 
v’’A 
v’’B 
V’’C 
vA 
vB 
vC
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 54 | P a g e 
In order to eliminate harmonic content from the output voltage, various techniques can be adopted. A 
multiple-pulse arrangement by combining the output of cascade or parallel VSCs can be adopted as a solution 
using a multi-winding transformer or inter-phase transformer magnetic. The pulse width modulation (PWM) 
technique can be implemented to control harmonic content from the output voltage too. Moreover, harmonic 
filters can be also adopted in combination with the above techniques. In this paper PWM control is utilized, 
allowing for simplified two winding interconnecting transformer designs. 
Figure 4 – VSC Output Voltage Waveforms 
In the configuration of UPFC, there are two independent VSCs interconnected via coupling capacitor as Shunt 
converter and Series converter. 
Shunt Connected VSC – the VSC is connected to the power system via a shunt connected transformer. By 
varying the amplitude and the phase of the output voltages produced, the active power and the reactive power 
exchange between the converter and the A.C. system can be controlled in a manner similar to that of a rotating 
synchronous machine. If the amplitude of the output voltage is increased above that of the AC system voltage, 
the VSC generates reactive power to the power system. If the amplitude of the output voltage is decreased below 
that of the AC system voltage, the VSC absorbs reactive power from the power system. 
Series Connected VSC – the VSC is connected to the power system in series via a series connected 
transformer. By varying the amplitude and the phase of the output voltages produced, the magnitude and the 
angle of the injected voltage can be controlled. The VSC output voltage injected in series with the line acts as an 
AC voltage source. The current flowing through the VSC corresponds to the line current. The VA rating of the 
VSC is determined by the product of the maximum injected voltage and the maximum line current. 
2. Instantaneous power flow delivered by a VSC into a power system 
A converter connected to a power system, which is able of power exchange between the power system 
and the DC storage capacitor, can be represented by a three symmetrical sinusoidal voltage sources. A 
symmetrical three-phase system can be transformed into a synchronously-rotating orthogonal system. A new 
coordinate system, having the axes rotating at the synchronous angular speed of the fundamental network 
voltage , is defined on the basis of the d-q transformation. In the Fig. 2 the VSC is supplied by a voltage 
system vector VS = (VSA, VSB, VSC), with R and L are respectively the transformer equivalent resistances and 
inductances. The d-q transformation of the supply voltage system VS is made using the following equations: 
1 1 V 
V 1 SA 
SD 2 2 
V 
V 3 3 SB SQ 0 V 2 2 SC 
    
        
       
      
       
   
(1) 
where : 
SQ 
SD 
d 
; 
dt 
V 
arct g( ) 
V 
 
  
  
On the basis of this d-q transformation, the instantaneous active and reactive power flowing into the power 
system delivered by the VSC [6], neglecting transformer losses and balanced condition; and choose VSD 
=VSA, VSQ =0 are :
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 55 | P a g e 
SD SD 
SD SQ 
3 
P(t) V xI 
2 
3 
Q(t) V xI 
2 
 
 
(2) 
where VSD , VSQ, ISD, ISQ are vectors of d-q transition voltage and current respectively. 
III. DECOUPLING METHOD OF UPFC MODEL 
1. Series and Shunt converter control systems 
In the UPFC configuration two converters can work independently of each other by separating the DC side. In 
general operating mode of UPFC is possible as follow: 
 The series converter is operating in Automatic Power Flow Control mode: the reference inputs are value of 
P and Q to maintain on the transmission line despite system changes; and 
 the shunt converter operating in Automatic Voltage Control mode : the goal is to maintain the transmission 
voltage line as a reference value. 
In this paper it has been chosen a UPFC model in terms of two ideal controllable voltage sources, connected 
respectively in series and in shunt to the transmission line as in Fig. 1, to represent respectively the series and 
the shunt inverters. So, the two UPFC control systems must be developed in such a way to evaluate the 
amplitude and the phase angle of these two voltage sources on the basis of operating functions required UPFC. 
On the basis of (2) the instantaneous power flow at the receiving end, assuming VrD equal to the receiving end 
voltage amplitude vr and VRq = 0 results: 
r rD rD 
r rD rQ 
3 
p (t) v xi 
2 
3 
q (t) v xi 
2 
 
 (3) 
where irD and irQ are the d-q component values of line current. Thereby, the reference parameters of controller is 
possibly calculated as follows : 
* 
* r 
rD 
rD 
* 
* r 
rQ 
rD 
2 p 
i (t) 
3 v 
2 q 
i (t) 
3 v 
 
 
(4) 
with p* 
r , and q*r are the instantaneous active and reactive power flow required the receiving end. 
At the same way, the instantaneous active and reactive power flows provided by the shunt inverter are: 
Sh lD Sh,D 
Sh lD Sh,Q 
3 
p (t) v xi 
2 
3 
q (t) v xi 
2 
 
 
(5) 
also assuming VlD equal to the sending end voltage amplitude Vl and VlQ =0, with iSh,D and iSh,Q are the d-q 
current components injected by shunt inverter into the transmission line. So, the reference values of these two 
current components are evaluated as follows: 
* 
* Sh 
Sh,D 
lD 
* 
* Sh 
Sh,Q 
lD 
2 p 
i (t) 
3 v 
2 q 
i (t) 
3 v 
 
 
(6) 
where p* 
Sh , q* 
Sh are the instantaneous active and reactive power flows required to the shunt inverter. 
From Fig. 1, the circuit equation of shunt VSC of UPFC can be written in per unit as : 
Sh,A * Sh,A SA Sh,A 
Sh,B * Sh,B * SB Sh,B 
Sh,C Sh,C SC Sh,C 
i 1 0 0 i v e 
d R 1 
i 0 1 0 i v e 
dt L L 
i 0 0 1 i v e 
         
         
           
               
(7)
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 56 | P a g e 
From [] the output values of controller of Shunt Converter to evaluate the d-q components of equivalent output 
voltage source, VSh,D and VSh,Q can be shown as below : 
' 
Sh 
Sh,D lD 1Sh 
' ' 
Sh Sh 
Sh,Q lQ 2Sh 2Sh 
L 
v v y 
L L 
v v y y 
  
 
    
  
(8) 
' Sh 
Sh 
b 
L 
L 
z 
 
 (9) 
with assuming that Vl,D = |vl| ; Vl,Q = 0; the LSh = shunt transformer leakage inductance; Zb is the base 
impedance. Therefore, the module and displacement angle of equivalent voltage source of shunt converter are 
calculated as follows : 
2 2 
Sh Sh,D Sh,Q 
Sh,Q 
Sh 
Sh,D 
V v v 
v 
arctg 
v 
  
  
(10) 
At the same manner, the output variables y1Se , y2Se are used to evaluate the d-q components of series converter 
of equivalent voltage source , VSe,D and VSe,Q by following equations : 
' 
Se 
Se,D lD rD 1Se 
' 
Se 
Se,Q lQ rQ 2Se 
L 
v (v v ) y 
L 
v (v v ) y 
   
 
   
 
(12) 
' 1 Se 
Se 
b 
(L L ) 
L 
z 
  
 (13) 
2 2 
Se Se,D Se,Q 
Se,Q 
Se 
Se,D 
V v v 
v 
arctg 
v 
  
  
(14) 
with assuming that Vl,D = |vl| ; Vl,Q = 0; the LSe = shunt transformer leakage inductance, and L1 is the line 
inductance. Therefore, the module and displacement angle of equivalent voltage source of shunt converter are 
calculated as follows : 
2. Converter control technique 
On the basic of operation requirements, the scheme of switching the converter’s elements, such as GTO’s or 
IGBT’s, may be different. In this paper, as shown above, the PWM switching control technique has been 
considered. In this case the three phases of the output converter voltage result: 
yA y DC y 
0 
yB y DC y 
0 
yB y DC y 
1 
v m V sin( t ) 
2 
1 
v m V sin( t 120 ) 
2 
1 
v m V sin( t 240 ) 
2 
      
       
       
(15) 
here my , y are the amplitude modulation ratio and phase angle of converter output voltage. These 
control variables are the input control signals of converters of UPFC according to PWM switching technique. If 
we apply (12) for Shunt converter, then mSh is the index modulation and Sh is the phase displacement angle 
with respect to Vl (sending voltage). The same equation to Series converter, mSe is the index modulation and 
Se is the phase displacement angle with respect to Vl – Vr (compensation voltage). VDC is the value of voltage 
across the storage capacitor.
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 57 | P a g e 
Moreover the following relations are valid: 
2 2 
yD yQ 
y 
DC 
yQ 
y 
yD 
v v 
m 2 2 
V 
v 
arctg 
v 
 
 
  
    
  
  
(16) 
where vyD and vyQ are calculated by (8) and (11) respectively for the series and the shunt inverter. 
In both control schemes the PI controllers is applied with parameters in dependence of converter characteristics, 
(RSe, LSe), (RSh, LSh) respectively the equivalent impedance of the series and shunt transformer and (Rline, Lline ) 
the line equivalent impedance. 
3. DC-side control 
For normal operation of two VSC’s in an UPFC, the DC voltage across the DC storage capacitor CS must be 
kept constant. This implies that the active power exchanged 
between the UPFC and the power system is zero at steady state operation: 
pSe + pSh = 0 (17) 
that is, the active power delivered by the shunt inverter pSh is equal to the active power exchange between the 
series inverter and the transmission line, pSe. Hence, a DC voltage control system must be realized to keep Vdc 
constant by taking the actual value of vdc as the feedback signal against a dc reference signal V*dc []. Moreover, 
assuming negligible the losses of the shunt and series converters and coupling transformers the actual value of 
the DC capacitor voltage is computed as : 
DC Se Sh 
DC DC 
dv p p 
dt C v 
 
 (18) 
IV. SIMULATION AND RESULTS 
All the simulations were made using Matlab Power System Blockset and Simulink. The simulation 
results of the discrete UPFC model based 12 pulse-converter are the subject of this section. These results are 
obtained based on discrete modulation functions. A simple configuration of power system is applied to validate 
the new UPFC model based 12 pulse- converter. The test power system operates at 230 kV and is shown in 
Fig.5. The generator is assumed to be an ideal voltage source behind an equivalent Thevenin impedance. The 
UPFC model is located at the sending end of the transmission line and is controlled in such a way to follow the 
changes in reference values of the line active and reactive power. The Shunt converter and Series converter are 
based on 12 pulse-converter with two level ignition signals. Besides, PWM technique with 1080 Hz carrier 
frequency, which is modeled by the discrete PWM pulse generator, is used to generate output voltage pulses of 
converters. This technique is very suitable for pulse control of UPFC and reduce total harmonic distortion of 
output voltage and line current. In those devices, input control variables of converter, such as amplitude 
modulation ratio and phase angle are output variables of close-loop power flow controller and close-loop DC 
voltage controller. 
Fig.5 – Simple test system with UPFC. 
The Fig.8 displays DC voltage of UPFC. The real signal shape of DC voltage in discrete simulation is 
an oscillation curve around reference value according to pulses of PWM converter. In Fig.9 output voltage of 
Series converter is shown. It is a combination of two 6 pulse converters connected cascade together in which 
whole output voltage gains a better result of low harmonic content. This has a very important meaning in 
practice,…. 
In Fig.7, line current though UPFC is shown by discrete type. 
UPFC Sys 
P, Q 
Transmission line 
VS VR 
VIdeal 
ILine
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 58 | P a g e 
Moreover, this simulation proved that total harmonic content of line voltage at UPFC bus in new discrete 12 
pulse converter model is lower that of conventional 6 pulse converter. This is illustrated in Fig.10. 
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 
-0.2 
-0.15 
-0.1 
-0.05 
0 
0.05 
0.1 
0.15 
OUTPUT VOLTAGE OF 12 PULSE-SERIES CONVERTER 
WITH PWM TECHNIQUE 
TIME (ms) 
VOLTAGE (pu) 
Fig. 6 – Output voltage of 12 pulse series converter 
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 
-1.5 
-1 
-0.5 
0 
0.5 
1 
1.5 
2 
2.5 
LINE CURRENT WITH UPFC 
TIME (ms) 
CURRENT (pu) 
Fig. 7 – Current in transmission line 
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 
0 
0.02 
0.04 
0.06 
0.08 
0.1 
0.12 
DC VOLTAGE OF UPFC 
TIME (ms) 
VOLTAGE (pu) 
Fig.8 - DC voltage of UPFC 
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 
-1.5 
-1 
-0.5 
0 
0.5 
1 
1.5 
TIME (ms) 
VOLTAGE (pu) 
VOLTAGE OF UPFC BUS 
Fig.9 – Voltage in UPFC’ received bus of transmission line 
TIME (Sec) 
TIME (Sec) 
TIME (Sec) 
TIME (Sec)
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 59 | P a g e 
In particular, the UPFC series inverter is simulated to maintain a power flow at the receiving end at 2 
p.u. up to 5/60 sec. and after that at 4 p.u. as in Fig.11, and a reactive power flow is kept at 0.5 p.u. During 
simulation the active power exchange between the series converter and the power system is compensated by the 
active power exchange of the shunt converter, evaluated by the DC control system, so to maintain the dc voltage 
across the storage capacitor constant at the specified value as in Fig. 14. 
Fig.10- 
Fig.11 – Power flow characteristic of transmission line under dynamic control of UPFC 
Fig.12, Fig.13, and Fig.14 are the demonstration of dynamic operating of UPFC with power value reference as 
stated above. In these figures, both values and shapes of voltage and current in transmission line are changed 
according to changing of modulation control variables adapted with active power references. 
0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 
-0.1 
-0.05 
0 
0.05 
0.1 
0.15 
OUTPUT VOLTAGE OF 12 PULSE SERIES CONVERTER 
TIME (Sec.) 
VOLTAGE (pu) 
Fig.12 – Output voltage responses of 12 pulse series converter in dynamic states.
Unified Power Flow Controller: Modeling And Dynamic Characteristic 
International organization of Scientific Research 60 | P a g e 
0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 
-1.5 
-1 
-0.5 
0 
0.5 
1 
1.5 
VOLTAGE OF UPFC BUS IN DYNAMIC STATES 
TIME (Sec.) 
VOLTAGE (pu) 
Fig.13 – Voltage characteristic of transmission line under dynamic control of UPFC 
0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 
-5 
-4 
-3 
-2 
-1 
0 
1 
2 
3 
4 
5 
LINE CURRENT OF UPFC BUS 
TIME (sec.) 
CURRENT (pu) 
Fig.14 – Current characteristic of transmission line under dynamic control of UPFC 
V. CONCLUSIONS 
This paper after a brief summary of the UPFC configuration based converter, illustrates in detail the 
control system model of UPFC with two separate control systems for the series and shunt inverters and a control 
for their coordination. Finally, a discrete simulation of new UPFC model based 12 pulse converter using 
Matlab/Simulink as simulation program is shown and some simulation results are illustrated to validate the 
implemented this UPFC model. Especially, the simulation results have provided the practical operating 
processes of UPFC and converter. These give us the practical views of action of every part of devices and 
responses of power system under UPFC working. The results are obtained for a PWM-based control 
technique, but it's very simple to modify the converter control technique such as phase control. 
However, this new discrete UPFC model based on 12 pulse converter seems not to be suitable for application in 
contingency analysis because it is quite complex in separating control systems of Shunt converter and series 
converter properly with maintained control quality A UPFC with matrix converter is useful only for steady 
operation modes. 
This new discrete 12 pulse converter model will be modified to be able to perform a damping oscillation 
operating functions in such a way in the future researches. 
REFERENCES 
[1] L. Gyugyi, C.D. Shauder, S.L. Williams, T.R. Rietman, D.R. Torgerson, A. Edris. “The unified power 
flow controller: A new approach to power transmission control”, IEEE Trans. On Power Delivery, 
Vol.10, No.2, April 1995, pp.1085-1097. 
[2] H.Fujita, Y. Watanabe, H.Akagi. “Control and analysis of a unified power flow controller”. IEEE Trans. 
On Power Electronics, Vol.14, No.6, Nov. 1999.

Weitere ähnliche Inhalte

Was ist angesagt?

Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...IJMER
 
Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...AM Publications
 
An Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage RegulationAn Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage RegulationIJMTST Journal
 
Meet sarayni
Meet sarayniMeet sarayni
Meet saraynithavasik
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flowAhmed M. Elkholy
 
SHE Control for PV System Connected to the Grid
SHE Control for PV System Connected to the GridSHE Control for PV System Connected to the Grid
SHE Control for PV System Connected to the GridTELKOMNIKA JOURNAL
 
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...IJMER
 

Was ist angesagt? (16)

Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...
 
Presentación5
Presentación5Presentación5
Presentación5
 
Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...
 
An Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage RegulationAn Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage Regulation
 
Meet sarayni
Meet sarayniMeet sarayni
Meet sarayni
 
Performance Investigation of a Monopolar HVDC Transmission System Feeding a ...
Performance Investigation of a Monopolar HVDC Transmission  System Feeding a ...Performance Investigation of a Monopolar HVDC Transmission  System Feeding a ...
Performance Investigation of a Monopolar HVDC Transmission System Feeding a ...
 
Bh4201396402
Bh4201396402Bh4201396402
Bh4201396402
 
A1102010106
A1102010106A1102010106
A1102010106
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flow
 
Bee016 facts
Bee016 factsBee016 facts
Bee016 facts
 
SHE Control for PV System Connected to the Grid
SHE Control for PV System Connected to the GridSHE Control for PV System Connected to the Grid
SHE Control for PV System Connected to the Grid
 
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
A High Performance PWM Voltage Source Inverter Used for VAR Compensation and ...
 
Ijetr021124
Ijetr021124Ijetr021124
Ijetr021124
 
Icraie 2014-s mishra2
Icraie 2014-s mishra2Icraie 2014-s mishra2
Icraie 2014-s mishra2
 
facts introducrion
facts introducrion  facts introducrion
facts introducrion
 
Gran importancia
Gran importanciaGran importancia
Gran importancia
 

Ähnlich wie H04945260

POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERJournal For Research
 
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGESVSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGESIJERD Editor
 
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerAugmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerIJERA Editor
 
REACTIVE POWER COMPENSATION ppt.pptx
REACTIVE POWER COMPENSATION  ppt.pptxREACTIVE POWER COMPENSATION  ppt.pptx
REACTIVE POWER COMPENSATION ppt.pptxAryan630616
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...IRJET Journal
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemIOSR Journals
 
vsc hvdc fuzzy controller for improving the stability of acdc power system
vsc hvdc fuzzy controller for improving the stability of acdc power systemvsc hvdc fuzzy controller for improving the stability of acdc power system
vsc hvdc fuzzy controller for improving the stability of acdc power systemIndra S Wahyudi
 
Transformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine ApplicationsTransformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine ApplicationsIJMTST Journal
 
A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...IJERA Editor
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 
Simulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemSimulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemijsrd.com
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...IJITE
 
Control and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC TransmissionControl and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC Transmissionijsrd.com
 

Ähnlich wie H04945260 (20)

POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
 
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGESVSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
 
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerAugmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
 
REACTIVE POWER COMPENSATION ppt.pptx
REACTIVE POWER COMPENSATION  ppt.pptxREACTIVE POWER COMPENSATION  ppt.pptx
REACTIVE POWER COMPENSATION ppt.pptx
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
 
A04 05 0110
A04 05 0110A04 05 0110
A04 05 0110
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC System
 
D010121832
D010121832D010121832
D010121832
 
vsc hvdc fuzzy controller for improving the stability of acdc power system
vsc hvdc fuzzy controller for improving the stability of acdc power systemvsc hvdc fuzzy controller for improving the stability of acdc power system
vsc hvdc fuzzy controller for improving the stability of acdc power system
 
J1103035766
J1103035766J1103035766
J1103035766
 
Performance Investigation of a Monopolar HVDC Transmission System Feeding a W...
Performance Investigation of a Monopolar HVDC Transmission System Feeding a W...Performance Investigation of a Monopolar HVDC Transmission System Feeding a W...
Performance Investigation of a Monopolar HVDC Transmission System Feeding a W...
 
Transformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine ApplicationsTransformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine Applications
 
Ar4101248255
Ar4101248255Ar4101248255
Ar4101248255
 
A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
Simulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemSimulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution system
 
D010223139
D010223139D010223139
D010223139
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
 
Control and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC TransmissionControl and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC Transmission
 
I41045662
I41045662I41045662
I41045662
 

Mehr von IOSR-JEN

Mehr von IOSR-JEN (20)

C05921721
C05921721C05921721
C05921721
 
B05921016
B05921016B05921016
B05921016
 
A05920109
A05920109A05920109
A05920109
 
J05915457
J05915457J05915457
J05915457
 
I05914153
I05914153I05914153
I05914153
 
H05913540
H05913540H05913540
H05913540
 
G05913234
G05913234G05913234
G05913234
 
F05912731
F05912731F05912731
F05912731
 
E05912226
E05912226E05912226
E05912226
 
D05911621
D05911621D05911621
D05911621
 
C05911315
C05911315C05911315
C05911315
 
B05910712
B05910712B05910712
B05910712
 
A05910106
A05910106A05910106
A05910106
 
B05840510
B05840510B05840510
B05840510
 
I05844759
I05844759I05844759
I05844759
 
H05844346
H05844346H05844346
H05844346
 
G05843942
G05843942G05843942
G05843942
 
F05843238
F05843238F05843238
F05843238
 
E05842831
E05842831E05842831
E05842831
 
D05842227
D05842227D05842227
D05842227
 

Kürzlich hochgeladen

Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slidevu2urc
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreternaman860154
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhisoniya singh
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitecturePixlogix Infotech
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...gurkirankumar98700
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationRidwan Fadjar
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...shyamraj55
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Allon Mureinik
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesSinan KOZAK
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationSafe Software
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 3652toLead Limited
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxOnBoard
 

Kürzlich hochgeladen (20)

Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slide
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC Architecture
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 Presentation
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen Frames
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptx
 

H04945260

  • 1. IOSR Journal of Engineering (IOSRJEN) www.iosrjen.org ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), ||V4|| PP 52-60 International organization of Scientific Research 52 | P a g e Unified Power Flow Controller: Modeling And Dynamic Characteristic Ho Dac Loc Hochiminh City University of Technology (HUTECH), Hochiminh City Abstract: - Unified power flow controller (UPFC) consists two converters. There are three purposes of this paper, firstly to illustrate the UPFC device based VSC designs, then to describe a decoupling method the UPFC’s controller into two separate control systems of the shunt and the series converters respectively in realizing an appropriate co-ordination between them. Finally, using the Matlab tool to build a discrete simulator for the UPFC with 12 pulse converters. The simulation results show that the developed UPFC model is reflected the static and dynamic characteristics of the UPFC. The harmonics of the output of the model are analyzed. Using the simple power system with UPFC as an example, the dynamics characteristics are studied. The fault status of the system with UPFC is analyzed too. Keyword list: - Times Roman, image area, acronyms, references I. INTRODUCTION The developing interest in tools for power flow control in a power system has increased significantly during the last 10 years. Demand for research in this field is motivated by rapid transformations in both technology and organization of the power system industry [1]. The deregulation and competitive environment in the contemporary power networks will imply a new scenario in terms of load and power flows condition and so causing problems of line transmission capacity. For this reason, Flexible AC Transmission System (FACTS) controllers has rapidly developed to meet the need for increasing transmission capacity and controlling power flows through predefined transmission corridors. Especially, the improvements in the field of power electronics have had a major impact on the development of this technology. The devices of new FACTS generation are based on the use of high power electronic components such as GTO (Gate Turn-Off Thyristor) and IGBT (Insulated Gate Bipolar Transistor) which makes them respond quickly to the control requirements. It is called by the FACTS technologies based on Voltage Sourced Converter (VSC) designs. The wider application of FATCS leads to numerous benefits for electrical transmission system infrastructure, including increased capacity at minimum cost; enhanced reliability through proven performance; higher levels of security by means of sophisticated control & protection; and improved system controllability with state-of-the-art technology concepts. Thereby, these FACTS devices are able to act almost instantaneously to changes in power system [2]. The most powerful in family of FACTS devices is the Unified Power Flow Controller (UPFC), because it can control simultaneously all three parameters of transmission power line (line impedance, voltage and phase angle). In practice, the UPFC device consists of two Voltage Source Converters (VSC) connected respectively in shunt and in series with the transmission line, and connected to each other by a common DC link including a storage capacitor. The shunt converter is used for voltage regulation at the point of connection injecting an opportune reactive power flow into the line and to balance the real power flow exchanged between the series converter and the transmission line. The series converter can be used to control the real and reactive line power flow inserting an opportune voltage with controllable magnitude and phase in series with the transmission line. Thereby, the UPFC can perform functions of reactive shunt compensation, active and reactive series compensation and phase shifting [3]. There are many different UPFC models have been investigated by several authors [4-6]. The three main purposes of the paper are firstly to illustrate the UPFC configuration based on VSC’s, and then describe a decoupling method the UPFC’s controller into two separate control systems of the shunt and the series converters respectively in realizing an appropriate co-ordination between them, and finally to simulate a new discrete UPFC model based on 12-pulse VSC using Matlab Power Block/Simulink as simulation program. Besides, PWM method is applied to decrease total of voltage harmonics in simulation output of converters. II. THE UPFC CONFIGURATION– BASED VOLTAGE SOURCE CONVERTER 1. VSC design concept The single-line diagram of the UPFC is a combination of two VSC configurations shown in Figures 1. As shown in Figures 1, VSC designs are composed of two basic configurations: A) Shunt Connected VSC System, and
  • 2. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 53 | P a g e B) Series Connected VSC System Figure 1 – the UPFC configuration. A basic schematic diagram of the VSC design is illustrated in Figure 2. As a typical configuration, the VSC is a six-pulse converter consisting of six power semiconductor switching devices (GTO, GCT, IGBT, etc) with anti-parallel connected diode together with heat sinks and auxiliary equipment for gating, monitoring and grading. In a high power converter, a number of semiconductor devices may be connected in series or in parallel. Some advanced configurations, for example connecting cascade of two six-pulse converters to twelve- pulse converter, have developed to reduce total of voltage harmonics of converter outputs in Fig. 3. Figure 2 – Basic VSC Schematic Diagram From a point of D.C. voltage source, provided by a charged capacitor CS, the converter produces a set of controllable three-phase output voltages at the fundamental harmonic frequency of the A.C. system voltage. The output voltage waveform may be a square waveform (Figure 4.a) or a pulse width modulated (PWM) waveform (Figure 4.b), depending on circuit topology and pulse modulation method. Figure 3 – 12 Pulse-VSC Schematic Diagram Shunt Converter Series Converter Shunt Transformer Series Transformer Power transmission line Power transmission line DC capacitor UPFC F F A B VDC vA vB vC iA iB iC iDC VDC v’A v’B v’C v’’A v’’B V’’C vA vB vC
  • 3. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 54 | P a g e In order to eliminate harmonic content from the output voltage, various techniques can be adopted. A multiple-pulse arrangement by combining the output of cascade or parallel VSCs can be adopted as a solution using a multi-winding transformer or inter-phase transformer magnetic. The pulse width modulation (PWM) technique can be implemented to control harmonic content from the output voltage too. Moreover, harmonic filters can be also adopted in combination with the above techniques. In this paper PWM control is utilized, allowing for simplified two winding interconnecting transformer designs. Figure 4 – VSC Output Voltage Waveforms In the configuration of UPFC, there are two independent VSCs interconnected via coupling capacitor as Shunt converter and Series converter. Shunt Connected VSC – the VSC is connected to the power system via a shunt connected transformer. By varying the amplitude and the phase of the output voltages produced, the active power and the reactive power exchange between the converter and the A.C. system can be controlled in a manner similar to that of a rotating synchronous machine. If the amplitude of the output voltage is increased above that of the AC system voltage, the VSC generates reactive power to the power system. If the amplitude of the output voltage is decreased below that of the AC system voltage, the VSC absorbs reactive power from the power system. Series Connected VSC – the VSC is connected to the power system in series via a series connected transformer. By varying the amplitude and the phase of the output voltages produced, the magnitude and the angle of the injected voltage can be controlled. The VSC output voltage injected in series with the line acts as an AC voltage source. The current flowing through the VSC corresponds to the line current. The VA rating of the VSC is determined by the product of the maximum injected voltage and the maximum line current. 2. Instantaneous power flow delivered by a VSC into a power system A converter connected to a power system, which is able of power exchange between the power system and the DC storage capacitor, can be represented by a three symmetrical sinusoidal voltage sources. A symmetrical three-phase system can be transformed into a synchronously-rotating orthogonal system. A new coordinate system, having the axes rotating at the synchronous angular speed of the fundamental network voltage , is defined on the basis of the d-q transformation. In the Fig. 2 the VSC is supplied by a voltage system vector VS = (VSA, VSB, VSC), with R and L are respectively the transformer equivalent resistances and inductances. The d-q transformation of the supply voltage system VS is made using the following equations: 1 1 V V 1 SA SD 2 2 V V 3 3 SB SQ 0 V 2 2 SC                                    (1) where : SQ SD d ; dt V arct g( ) V      On the basis of this d-q transformation, the instantaneous active and reactive power flowing into the power system delivered by the VSC [6], neglecting transformer losses and balanced condition; and choose VSD =VSA, VSQ =0 are :
  • 4. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 55 | P a g e SD SD SD SQ 3 P(t) V xI 2 3 Q(t) V xI 2   (2) where VSD , VSQ, ISD, ISQ are vectors of d-q transition voltage and current respectively. III. DECOUPLING METHOD OF UPFC MODEL 1. Series and Shunt converter control systems In the UPFC configuration two converters can work independently of each other by separating the DC side. In general operating mode of UPFC is possible as follow:  The series converter is operating in Automatic Power Flow Control mode: the reference inputs are value of P and Q to maintain on the transmission line despite system changes; and  the shunt converter operating in Automatic Voltage Control mode : the goal is to maintain the transmission voltage line as a reference value. In this paper it has been chosen a UPFC model in terms of two ideal controllable voltage sources, connected respectively in series and in shunt to the transmission line as in Fig. 1, to represent respectively the series and the shunt inverters. So, the two UPFC control systems must be developed in such a way to evaluate the amplitude and the phase angle of these two voltage sources on the basis of operating functions required UPFC. On the basis of (2) the instantaneous power flow at the receiving end, assuming VrD equal to the receiving end voltage amplitude vr and VRq = 0 results: r rD rD r rD rQ 3 p (t) v xi 2 3 q (t) v xi 2   (3) where irD and irQ are the d-q component values of line current. Thereby, the reference parameters of controller is possibly calculated as follows : * * r rD rD * * r rQ rD 2 p i (t) 3 v 2 q i (t) 3 v   (4) with p* r , and q*r are the instantaneous active and reactive power flow required the receiving end. At the same way, the instantaneous active and reactive power flows provided by the shunt inverter are: Sh lD Sh,D Sh lD Sh,Q 3 p (t) v xi 2 3 q (t) v xi 2   (5) also assuming VlD equal to the sending end voltage amplitude Vl and VlQ =0, with iSh,D and iSh,Q are the d-q current components injected by shunt inverter into the transmission line. So, the reference values of these two current components are evaluated as follows: * * Sh Sh,D lD * * Sh Sh,Q lD 2 p i (t) 3 v 2 q i (t) 3 v   (6) where p* Sh , q* Sh are the instantaneous active and reactive power flows required to the shunt inverter. From Fig. 1, the circuit equation of shunt VSC of UPFC can be written in per unit as : Sh,A * Sh,A SA Sh,A Sh,B * Sh,B * SB Sh,B Sh,C Sh,C SC Sh,C i 1 0 0 i v e d R 1 i 0 1 0 i v e dt L L i 0 0 1 i v e                                             (7)
  • 5. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 56 | P a g e From [] the output values of controller of Shunt Converter to evaluate the d-q components of equivalent output voltage source, VSh,D and VSh,Q can be shown as below : ' Sh Sh,D lD 1Sh ' ' Sh Sh Sh,Q lQ 2Sh 2Sh L v v y L L v v y y          (8) ' Sh Sh b L L z   (9) with assuming that Vl,D = |vl| ; Vl,Q = 0; the LSh = shunt transformer leakage inductance; Zb is the base impedance. Therefore, the module and displacement angle of equivalent voltage source of shunt converter are calculated as follows : 2 2 Sh Sh,D Sh,Q Sh,Q Sh Sh,D V v v v arctg v     (10) At the same manner, the output variables y1Se , y2Se are used to evaluate the d-q components of series converter of equivalent voltage source , VSe,D and VSe,Q by following equations : ' Se Se,D lD rD 1Se ' Se Se,Q lQ rQ 2Se L v (v v ) y L v (v v ) y         (12) ' 1 Se Se b (L L ) L z    (13) 2 2 Se Se,D Se,Q Se,Q Se Se,D V v v v arctg v     (14) with assuming that Vl,D = |vl| ; Vl,Q = 0; the LSe = shunt transformer leakage inductance, and L1 is the line inductance. Therefore, the module and displacement angle of equivalent voltage source of shunt converter are calculated as follows : 2. Converter control technique On the basic of operation requirements, the scheme of switching the converter’s elements, such as GTO’s or IGBT’s, may be different. In this paper, as shown above, the PWM switching control technique has been considered. In this case the three phases of the output converter voltage result: yA y DC y 0 yB y DC y 0 yB y DC y 1 v m V sin( t ) 2 1 v m V sin( t 120 ) 2 1 v m V sin( t 240 ) 2                     (15) here my , y are the amplitude modulation ratio and phase angle of converter output voltage. These control variables are the input control signals of converters of UPFC according to PWM switching technique. If we apply (12) for Shunt converter, then mSh is the index modulation and Sh is the phase displacement angle with respect to Vl (sending voltage). The same equation to Series converter, mSe is the index modulation and Se is the phase displacement angle with respect to Vl – Vr (compensation voltage). VDC is the value of voltage across the storage capacitor.
  • 6. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 57 | P a g e Moreover the following relations are valid: 2 2 yD yQ y DC yQ y yD v v m 2 2 V v arctg v             (16) where vyD and vyQ are calculated by (8) and (11) respectively for the series and the shunt inverter. In both control schemes the PI controllers is applied with parameters in dependence of converter characteristics, (RSe, LSe), (RSh, LSh) respectively the equivalent impedance of the series and shunt transformer and (Rline, Lline ) the line equivalent impedance. 3. DC-side control For normal operation of two VSC’s in an UPFC, the DC voltage across the DC storage capacitor CS must be kept constant. This implies that the active power exchanged between the UPFC and the power system is zero at steady state operation: pSe + pSh = 0 (17) that is, the active power delivered by the shunt inverter pSh is equal to the active power exchange between the series inverter and the transmission line, pSe. Hence, a DC voltage control system must be realized to keep Vdc constant by taking the actual value of vdc as the feedback signal against a dc reference signal V*dc []. Moreover, assuming negligible the losses of the shunt and series converters and coupling transformers the actual value of the DC capacitor voltage is computed as : DC Se Sh DC DC dv p p dt C v   (18) IV. SIMULATION AND RESULTS All the simulations were made using Matlab Power System Blockset and Simulink. The simulation results of the discrete UPFC model based 12 pulse-converter are the subject of this section. These results are obtained based on discrete modulation functions. A simple configuration of power system is applied to validate the new UPFC model based 12 pulse- converter. The test power system operates at 230 kV and is shown in Fig.5. The generator is assumed to be an ideal voltage source behind an equivalent Thevenin impedance. The UPFC model is located at the sending end of the transmission line and is controlled in such a way to follow the changes in reference values of the line active and reactive power. The Shunt converter and Series converter are based on 12 pulse-converter with two level ignition signals. Besides, PWM technique with 1080 Hz carrier frequency, which is modeled by the discrete PWM pulse generator, is used to generate output voltage pulses of converters. This technique is very suitable for pulse control of UPFC and reduce total harmonic distortion of output voltage and line current. In those devices, input control variables of converter, such as amplitude modulation ratio and phase angle are output variables of close-loop power flow controller and close-loop DC voltage controller. Fig.5 – Simple test system with UPFC. The Fig.8 displays DC voltage of UPFC. The real signal shape of DC voltage in discrete simulation is an oscillation curve around reference value according to pulses of PWM converter. In Fig.9 output voltage of Series converter is shown. It is a combination of two 6 pulse converters connected cascade together in which whole output voltage gains a better result of low harmonic content. This has a very important meaning in practice,…. In Fig.7, line current though UPFC is shown by discrete type. UPFC Sys P, Q Transmission line VS VR VIdeal ILine
  • 7. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 58 | P a g e Moreover, this simulation proved that total harmonic content of line voltage at UPFC bus in new discrete 12 pulse converter model is lower that of conventional 6 pulse converter. This is illustrated in Fig.10. 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 -0.2 -0.15 -0.1 -0.05 0 0.05 0.1 0.15 OUTPUT VOLTAGE OF 12 PULSE-SERIES CONVERTER WITH PWM TECHNIQUE TIME (ms) VOLTAGE (pu) Fig. 6 – Output voltage of 12 pulse series converter 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 -1.5 -1 -0.5 0 0.5 1 1.5 2 2.5 LINE CURRENT WITH UPFC TIME (ms) CURRENT (pu) Fig. 7 – Current in transmission line 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0 0.02 0.04 0.06 0.08 0.1 0.12 DC VOLTAGE OF UPFC TIME (ms) VOLTAGE (pu) Fig.8 - DC voltage of UPFC 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 -1.5 -1 -0.5 0 0.5 1 1.5 TIME (ms) VOLTAGE (pu) VOLTAGE OF UPFC BUS Fig.9 – Voltage in UPFC’ received bus of transmission line TIME (Sec) TIME (Sec) TIME (Sec) TIME (Sec)
  • 8. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 59 | P a g e In particular, the UPFC series inverter is simulated to maintain a power flow at the receiving end at 2 p.u. up to 5/60 sec. and after that at 4 p.u. as in Fig.11, and a reactive power flow is kept at 0.5 p.u. During simulation the active power exchange between the series converter and the power system is compensated by the active power exchange of the shunt converter, evaluated by the DC control system, so to maintain the dc voltage across the storage capacitor constant at the specified value as in Fig. 14. Fig.10- Fig.11 – Power flow characteristic of transmission line under dynamic control of UPFC Fig.12, Fig.13, and Fig.14 are the demonstration of dynamic operating of UPFC with power value reference as stated above. In these figures, both values and shapes of voltage and current in transmission line are changed according to changing of modulation control variables adapted with active power references. 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 -0.1 -0.05 0 0.05 0.1 0.15 OUTPUT VOLTAGE OF 12 PULSE SERIES CONVERTER TIME (Sec.) VOLTAGE (pu) Fig.12 – Output voltage responses of 12 pulse series converter in dynamic states.
  • 9. Unified Power Flow Controller: Modeling And Dynamic Characteristic International organization of Scientific Research 60 | P a g e 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 -1.5 -1 -0.5 0 0.5 1 1.5 VOLTAGE OF UPFC BUS IN DYNAMIC STATES TIME (Sec.) VOLTAGE (pu) Fig.13 – Voltage characteristic of transmission line under dynamic control of UPFC 0.06 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 -5 -4 -3 -2 -1 0 1 2 3 4 5 LINE CURRENT OF UPFC BUS TIME (sec.) CURRENT (pu) Fig.14 – Current characteristic of transmission line under dynamic control of UPFC V. CONCLUSIONS This paper after a brief summary of the UPFC configuration based converter, illustrates in detail the control system model of UPFC with two separate control systems for the series and shunt inverters and a control for their coordination. Finally, a discrete simulation of new UPFC model based 12 pulse converter using Matlab/Simulink as simulation program is shown and some simulation results are illustrated to validate the implemented this UPFC model. Especially, the simulation results have provided the practical operating processes of UPFC and converter. These give us the practical views of action of every part of devices and responses of power system under UPFC working. The results are obtained for a PWM-based control technique, but it's very simple to modify the converter control technique such as phase control. However, this new discrete UPFC model based on 12 pulse converter seems not to be suitable for application in contingency analysis because it is quite complex in separating control systems of Shunt converter and series converter properly with maintained control quality A UPFC with matrix converter is useful only for steady operation modes. This new discrete 12 pulse converter model will be modified to be able to perform a damping oscillation operating functions in such a way in the future researches. REFERENCES [1] L. Gyugyi, C.D. Shauder, S.L. Williams, T.R. Rietman, D.R. Torgerson, A. Edris. “The unified power flow controller: A new approach to power transmission control”, IEEE Trans. On Power Delivery, Vol.10, No.2, April 1995, pp.1085-1097. [2] H.Fujita, Y. Watanabe, H.Akagi. “Control and analysis of a unified power flow controller”. IEEE Trans. On Power Electronics, Vol.14, No.6, Nov. 1999.