International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014
184
Smoke Evacuation in Industrial Buildings
Ayşen Gamze Saygılı Doğuç
Uludağ University
Faculty of Engineering Master Student
Görükle, Bursa, Turkiye.
Dr. Zuhal Şimşek
Research Asistant
Uludağ University
Faculty of Architecture
Architecture Depatment
Görükle, Bursa, Turkiye
Dr. NurettinYamankaradeniz
Prelector
Uludağ University
Vocational School of Technical Sciences
Görükle, Bursa, Turkiye.
Abstract
Smoke occurs as a result of solid and liquid particles carried in the air from the burning of materials created
from the combustion of gases. A dark colored smoke screen is formed. It may be toxic and explosive which make
evacuation and responding to the fire more difficult. All these problems can be overcome with an appropriate
smoke evacuation system. Smoke evacuation systems can be divided into two categories as natural and
mechanical systems. However, they can vary according to needs, the people intensity; materials found in the
structure and area, architectural features and design standards. The modelling based on the scenario planned for
the most appropriate smoke evacuation system was carried out in compliance with international standards and
local regulations. In this study, a vehicle part warehouse belonging to the Oyak Renault automobile factory was
established inexactly the same way as the original. Using the CDF based PHONEICS system it was designed that
a fire broke out in the warehouse and in the design, parking lot fire data were taken into consideration as given
in British Standard (BS) standards ‘Components for smoke and heat control systems’ section 7. Vehicle parts
found in the warehouse were in parallel with vehicles which had installation completed in the parking lot without
a sprinkler. The smoke emerging as a result of the fire, which had an area of 5×5 m2
and 8MW magnitude and
broke out in the warehouse (without sprinkler) whose area and volume were 4680m2 and 37206m3 respectively,
was tested with 6 smoke evacuation fans activated at the beginning of the fire. The Total Fan capacity was
designed as 10 volume/hour and 15 volume/hour, evaluated according to the maximum CO amount, vision and
temperature by simulation for both situations. As a result of the tests performed, ideal visibility distance for
evacuation and intervention was ensured with smoke fans at a capacity of 15 volume/hour.
Keywords: Smoke evacuation, CFD, Smoke evacuation, Fire safety in industrial buildings
1. Introduction
Ignition source, fuel and oxygen combine resulting in combustion. Chemical changes are observed on the
structures of objects after they reach ignition temperature. Solid-liquid particles of burning materials and gases
form smoke. The majority of deaths in building fires are caused by poisoning from emitted gases rather than
structural collapses or burning (19).
© Center for Promoting Ideas, USA www.ijastnet.com
185
The toxic and asphyxiation properties of smoke are the main cause of deaths. Smoke mass expanding gradually
during combustion causes the increase of environmental temperature and the spread of the fire. Gases emitted
with the fire obstruct evacuation by creating a smoke cloud that limits visibility distance. This situation increases
the risk of death by extending the time during which people are exposed to toxic and asphyxiating gases (13). In
addition, the smoke cloud caused by the fire prevents the fire department from reaching the scene and responding
to the fire. The same situation also prevents the medical department from helping people who are exposed to
poisonous smoke. Time losses affect the health of people who are at the scene of the fire and trying to find exits
for evacuation. This danger is more dominant in multi-storied buildings. Smoke reaches upper floors by spreading
through areas such as stairs and elevator shafts, giving more damage to the people on upper floors when they are
trying to leave the building by the stairs.
2. Smoke Control in Industrial Buildings
Smoke caused by a fire breaking out in industrial buildings affects the health of the operators working in the area.
In addition, chemicals are exposed to heat and explosions may occur (1). These can only be prevented by taking
smoke under control with some precautions. It is important to prevent the spread of smoke through safe
environments and create safe environment conditions at the scene of the fire by evacuating the necessary areas
(13). Smoke control can be ensured by carrying out the following;
 Division with smoke curtains
 Evacuating smoke mechanically or naturally,
 Compression,
 Providing a clean air supply.
In designing smoke evacuation systems the followings are taken into consideration;
 The structure of the building,
 Physical features,
 Intended use,
 Fire load.
The design aim of smoke evacuation systems changes according to the intended use of the building. In buildings
such as shopping centers, cinemas and schools, creating safe escape routes is the most important criterion.
Therefore, it is aimed to create a smokeless area necessary for evacuation by holding smoke 2-3 m above the floor
(10). In these kinds of buildings a compression system is set up in stairwells where smoke can spread by moving
through other floors. The aim of compression is to ensure that environment pressure is higher than the pressure
value of the fire location by providing a clear air supply to the environment. In this situation, smoke can spread
through the environment when doors are opened for evacuation in case of fire and this should be prevented by
taking the precautions mentioned above.
As warehouses, manufacturing workshops and industrial facilities have high ceilings and non-segmented areas,
compression systems are not sufficient. Therefore, different solutions should be offered in order to control smoke.
In these structures, smoke can be removed to the external environment through evacuation dampers opened in the
ceiling of the structure. Smoke evacuation dampers found on the ceiling of the structure can be opened by
connecting to the central automation system. In addition, the system can be opened as a result of melting the wires
which keep the dampers closed. The working principles of a designed smoke control system can be created
depending on the scenarios covering automatic detection and extinguishing systems. However, smoke screens can
lose their effect depending on ceiling height. In such a situation, the building is divided into zones and smoke can
be controlled with evacuation dampers and clean air fans for every zone.
A second method in smoke evacuation in multi-storied buildings is the implementation of mechanical smoke
evacuation systems. In buildings with sprinklers, smoke evacuation zones are placed in parallel with sprinkler
zones and fire is extinguished at the point it begins. Smoke is evacuated from this area before spreading.
In an industrial building, the biggest factor with an impact on the amount of smoke is the fire load. Fires are
divided into three categories of small, medium and great by taking fire load into consideration. Fire load is
obtained by multiplying lower calorific vales and weights of materials and then dividing the result by the area in
which they are found.
International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014
186
Fan capacities in mechanical evacuation systems can be identified according to the smoke flow rate calculated
accordingly (3). If natural clearance is used, smoke amount is also taken into consideration in the calculation of
optimum clearance.
3. Material and Method
In this study, an evaluation was made of the environment conditions caused by a fire breaking out in a vehicle
parts warehouse of an automobile factory and the suction power of the most appropriate system necessary for the
evacuation of smoke. The modelled warehouse was a large area and of 7.5 m in height. In the structure, there was
no sprinkler or smoke evacuation system. There was a fire risk because of the flammable properties of the vehicle
parts stored in the warehouse. There were no permanent employees working in the area. Periodically, four people
at most comprising logistics operators and specialists undertake duties for stock control, loading and unloading.
The existing emergency doors are open and their positions meet the requirements of fire regulations. Therefore, it
is thought that there will not be a problem in terms of evacuating smoke.
In the modelling, the aim was to create a clean sub-region for evacuating smoke quickly, making the intervention
of the fire department easier and to be able to save parts with the least damage. In order for the fire department to
respond to the fire effectively, the field of vision should be open. In warehouse fires, saving the stored raw
materials or products as well as employees working in the warehouse or environment is of vital importance.
Furthermore, workplace management should act within the scope of the projected budget in order to maintain its
existence. Therefore, choosing the most ideal, appropriate and economic smoke evacuation system is very
important in the modelling.
The program we chose for the study that we carried out was the CDF based PHONEICS program (12). This
program is used to perform simulations for evaluating the tests that are necessary for the appropriate smoke
evacuation system. With this program, smoke movement, temperature and visibility distance can be tracked
through three dimensional images. CDF (Computational Fluid Dynamics) (1) is a programming system that
analyses the movement of fluids. With classical fluid dynamics, simple flat sheet solutions can be easily
performed but for complicated geometries and variable viscosities CDF analyses are more reliable and
appropriate. CDF gives the opportunity for analysis of many different parameters and does not cause deterioration
of the fluid property.
In the program, the t2 fire model included in NFPA 92 was used. In this modelling, the square of fire growing
duration increases in direct proportion to calorific power. The point at which the fire reaches fixed calorific power
is its largest point. Calorific load does not increase from this point and continues to be fixed. In evaluating
scenarios, the duration taken for the fire to reach its highest calorific power is considered to be the fire duration
and smoke control system modelling for the evacuation of smoke is studied.
In the program, the required data regarding the designed warehouse (control volume) was obtained at different
moments and heights thanks to the detector (propre) placed in the area where the fire might have broken out. Due
to this data, the correct fan was selected.
As the warehouse is an area where only vehicle parts are stored, the fire load of our control volume was accepted
as 8MW which is the parking lot (without sprinkler) fire load given in the BS standards. The fire generating area
was accepted as 5x5m2 which is again given in the same standards and in compliance with the layout of control
volume (4).
The sprinkler system is a factor which considerably affects fire load. If there is a sprinkler, the fire load in the
control volume decreases to 4MW.
To respond to a fire in the warehouse the most important matters are temperature and field of vision. In this
environment, there are no permanent employees and the area is large. Therefore, the density of toxic gases will be
low. Temperature and field of vision should be analyzed and evaluated for the fire department to respond to the
fire more easily and for employees to be evacuated quickly. The most appropriate evaluation height was
determined as 2m by considering the average human height. This value is a little higher than the average human
height (2). For safety purposes, PPM values at 2m height and different heights were also checked.
© Center for Promoting Ideas, USA www.ijastnet.com
187
General Data of the Vehicle Parts Warehouse of the Automobile Factory:
The dimensions of the warehouse in question are 130x36x7.95 meters. It is rectangular shaped and has a total area
of 4680m2
. The walls are made of 10 cm thick rock wool filled between metal sheets, and 2-hour fire-resistant
metal sandwich panels. The roof coating is a single layer metal sheet. There are two 3.5x4 m guillotine doors on
the northern side of the building, another 3.5x4 m guillotine door on the southern side of the building towards the
middle of that side and another 3.5x4 m guillotine door on the east corner of the northern wall of the building. In
total 4 guillotine doors with a total area of 14m2 are kept open for materials supply. Two of the operator entry
doors with a width of 90 cm and height of 220 cm, are located on the northeast and southwest corners towards the
opposite directions while the other two are located on the northern wall 30 meters apart. The doors are barred and
open outwards. They are kept closed while not in use.
15m2 guillotine doors are used to provide fresh air on 3 fronts of the building, providing 60m2 ventilation areas in
total. Boundary conditions are considered as fresh air entrance from the doors. The smoke coming out of the
guillotine doors during the fire was not taken into account assuming that it must be within the minimum range.
2 scenarios were assayed for the logistics warehouse in this study. The duration of the fire was determined as 600
seconds for both scenarios. A setting was prepared where the vehicle parts were burning slowly because of an
electrical installation breakdown and the fire reached its highest fire load value at the end of 600 seconds (Table
3.1).
Table 3.1 Development of Fire Duration Values According to Fire the Type of Combustible (NFPA 92)
Burnig rate according to fire the type of combustible Development of fire duration value
Slow 600
Medium 300
Fast 150
Ultra-fast 75
4. Evaluation
Scenario 1:
A 10 volume/hour air exchange was divided among 6 fans and each fan made smoke evacuation 62010m3
per
hour. The 600 seconds were evaluated taking into account that the fire reached its peak in 600 seconds. At the end
of this period PPM value was 1321 and the temperature was approximately 21,20⁰C, posing no risk. Nevertheless,
the visibility distance was insufficient for the firefighters arriving 10 minutes after the fire broke out (Figures 3.1-
3.2-3.3). Consequently, a second scenario was tried.
Diagram 4.1: (Volume/Time)Slen Distance Depends on the Height of the Smoke Discharge Capacity at 600
S. (Scenario 1)
International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014
188
Diagram 4.2: PPM Status at 2m.height from Basement at the End of 600 Seconds
Diagram 4.3: Temperature Values 2m height from Basement at the End of 600 Seconds
Slen
Hight
Diagram 4.4.Slen Distance Depends On the Height of the Smoke Discharge Capacity at 600s (Scenario2)
© Center for Promoting Ideas, USA www.ijastnet.com
189
Scenario 2:
The smoke evacuation fan capacity which was set as 10 volume/hour and understood to be insufficient was
increased to 15 volume/hour. The capacity of each fan was readjusted as 25,8372 m3/seconds. They were
activated as soon as the fire broke out just as in scenario 1. 300 iterations were estimated in the program for the
600 seconds long fire. The condition of the fire was checked every two seconds.
Visibility at 2 meters of height increased from 3,7 m to 20,16 m in the second trial (Figure 4.4). This is an
appropriate visibility distance both for evacuation and intervention. 10 minutes is a very long duration for
evacuation in a building in which there is a maximum of 4 people. Thus the evacuation would be completed
before the fire reaches its peak unless there is an exceptional situation such as an accident. The temperature was
21.20⁰C and the PPM value was 3081 at 2 meters above the floor at the end of 600 seconds (Figures 4.5-4.6). The
temperature and PPM values do not pose any risk for the firefighter teams.
Diagram 4.5: Temperature Values at 2m height from Basement at the End of 600 Seconds
Diagram 4.6.PPM status about 2 meters height from basement at the end of 600 seconds
5. Conclusion
The study covers a vehicle fire reaching up to 8MV thermal power which started in an area of 5×5 m2
in the 7.95
m high warehouse without a sprinkler with a floor area of 4608 m2
. The CFD based flair programme was used for
the fire. 6 fans making 10 volume/hour air exchanges in total were active during 600 seconds, which resulted in
3m visibility distance at 2 meters above the floor, which is known as the highest level of clearance below the
smoke.
International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014
190
The possibility of people still being evacuated in the building in the 10th
minute of the fire was very low
considering the number of people in the building. However, for whatever reason, the fire department arrived on
the scene after 10 minutes and 3m of visibility distance was not sufficient for intervention. Finding the center of
the fire, then bringing the equipment to the center is very dangerous and difficult in smoke density with only 3m
of visibility distance. Temperature and PPM did not pose any danger (14).
A trial-and-error method was implemented to find the most appropriate smoke evacuation fan flow rate. The
capacity of the fans was increased up to 50 % considering the smoke density produced by the vehicle parts. In
total 15 volume/hour air exchange smoke evacuation continued for 600 minutes during the last trial. The lowest
visibility distance at 2 meters of height detected during and at the end of these 600 minutes was 20.16 meters.
This visibility clearance is suitable for both evacuation and intervention according to NFPA 92. The smoke
density increased rapidly starting at 2.2 meters and the visibility decreased to less than 1 meter parallel to the
height.
It is understood from this study that a smoke evacuation system with industrial fans at 15 volume/hour air
exchange provides an appropriate clear bottom height in the warehouse of an automobile factory.
References
Anonim, 2005.Teskon 2005 program bildirileri/yayın-33
Anonim. 2014. Türkiye İstatistik Kurumuverileri, ortalamatürkerkekboyu 167,2cm.
Arpacı, V.S., Larsen, P.S. 1984. Convection Heat Transfer, Prentice-Hall,New Jersey
British Standard Components for smoke and heat control systems ,part 7
British Standard Component for smoke and heat control systems
CIBSE GUIDE E. 1997. Fire Engineering, The Chartered Institution of Building Services Engineers,
London.
Hansell G.O., Morgan H.P. 1994. Design Approaches for Smoke Control in Atrium Buildings, Building
Research Establishment Report, Gartso
Kılıç A.,İ.T.ÜMakineMühendisliğiDersnotları; YangınYükü
Klote,J.H.andMilke J.A. ,1992 Design of Smoke Management Systems, ASHRAE Inc.,Atlanta,
http://www.epa.gov/iaq/co.html
NFPA 92 Standart for smoke control systems 2009
NFPA Life safety code handbook 2009
Patankar, S.V. 1980. Numeric Heat Transfer and Fluid Flow, Hemisphere Publishing , New YORK
Gültek S., Selvi U., Endüstriyelyapılardayangındumanınıncebrivedoğalyollatahliyekriterleri
White F.M. 1974 ViscousFluide Flow ,Mc-Glaw –Hill ,New York
http://www.birimmuhendislik-tr.com/tr-TR/Default.aspx?c=23
http://www.cdc.gov/niosh/idlh/630080.html
http://www.cob.nl/fileadmin/user_upload/Documenten
http://www.cpsc.gov/en/safety-education/safety-education-centers
http://www.desica.com.tr/cfd_nedir.html
http://support.engenuity.com/literature/articles_whitepapers
http://www.yangin.org/dosyalar/duman_kontrol_gereklilig.pdf

Weitere ähnliche Inhalte

Was ist angesagt?

Bservice report
Bservice report Bservice report
Bservice report YeeQun
 
Case Study Report: The Summit
Case Study Report: The SummitCase Study Report: The Summit
Case Study Report: The Summit마 이환
 
Building Services Project 2 Diary
Building Services Project 2 DiaryBuilding Services Project 2 Diary
Building Services Project 2 DiaryNekumi Kida
 
Fire & safety
Fire & safetyFire & safety
Fire & safetyReliance
 
Final building service (assignment)
Final   building service (assignment)Final   building service (assignment)
Final building service (assignment)Chee Lee
 
Report: Data Logging
Report: Data LoggingReport: Data Logging
Report: Data Loggingaimi fatihah
 

Was ist angesagt? (7)

Bservice report
Bservice report Bservice report
Bservice report
 
Case Study Report: The Summit
Case Study Report: The SummitCase Study Report: The Summit
Case Study Report: The Summit
 
Building Services Project 2 Diary
Building Services Project 2 DiaryBuilding Services Project 2 Diary
Building Services Project 2 Diary
 
Fire & safety
Fire & safetyFire & safety
Fire & safety
 
Final building service (assignment)
Final   building service (assignment)Final   building service (assignment)
Final building service (assignment)
 
Data Logging Report
Data Logging ReportData Logging Report
Data Logging Report
 
Report: Data Logging
Report: Data LoggingReport: Data Logging
Report: Data Logging
 

Andere mochten auch

Dynamic modeling and control of vehicle using fuzzy logic controller 2
Dynamic modeling and control of vehicle using fuzzy logic controller 2Dynamic modeling and control of vehicle using fuzzy logic controller 2
Dynamic modeling and control of vehicle using fuzzy logic controller 2IAEME Publication
 
A Presentation on Innovations in suspension mechanisms.
A Presentation on Innovations in suspension mechanisms.A Presentation on Innovations in suspension mechanisms.
A Presentation on Innovations in suspension mechanisms.Suhas Rao
 
Design and analysis of a shock absorber
Design and analysis of a shock absorberDesign and analysis of a shock absorber
Design and analysis of a shock absorbereSAT Journals
 
Effect of modeling of infill walls on performance of multi story rc building
Effect of modeling of infill walls on performance of multi story rc buildingEffect of modeling of infill walls on performance of multi story rc building
Effect of modeling of infill walls on performance of multi story rc buildingIAEME Publication
 
An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...
An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...
An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...IJSRD
 
Innovations in suspension mechanisms
Innovations in suspension mechanismsInnovations in suspension mechanisms
Innovations in suspension mechanismsSuhas Rao
 
Suspension system-in-automobiles
Suspension system-in-automobilesSuspension system-in-automobiles
Suspension system-in-automobilesDanish Iqbal
 
Air suspension system
Air suspension systemAir suspension system
Air suspension systemMayank Rai
 
Active Air Suspension System
Active Air Suspension SystemActive Air Suspension System
Active Air Suspension SystemSuchit Moon
 
Electromagnetic Regenerative Shock Absorbers
Electromagnetic Regenerative Shock AbsorbersElectromagnetic Regenerative Shock Absorbers
Electromagnetic Regenerative Shock AbsorbersNoufal Nizar
 
Dynamic weight transfer in vehicle
Dynamic weight transfer in vehicleDynamic weight transfer in vehicle
Dynamic weight transfer in vehicleRohan Sahdev
 

Andere mochten auch (13)

Dynamic modeling and control of vehicle using fuzzy logic controller 2
Dynamic modeling and control of vehicle using fuzzy logic controller 2Dynamic modeling and control of vehicle using fuzzy logic controller 2
Dynamic modeling and control of vehicle using fuzzy logic controller 2
 
A Presentation on Innovations in suspension mechanisms.
A Presentation on Innovations in suspension mechanisms.A Presentation on Innovations in suspension mechanisms.
A Presentation on Innovations in suspension mechanisms.
 
Design and analysis of a shock absorber
Design and analysis of a shock absorberDesign and analysis of a shock absorber
Design and analysis of a shock absorber
 
Effect of modeling of infill walls on performance of multi story rc building
Effect of modeling of infill walls on performance of multi story rc buildingEffect of modeling of infill walls on performance of multi story rc building
Effect of modeling of infill walls on performance of multi story rc building
 
An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...
An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...
An Experimental and Theoretical Analysis & Modification of a Shock Absorber o...
 
Rocker bogie 1
Rocker bogie 1Rocker bogie 1
Rocker bogie 1
 
Innovations in suspension mechanisms
Innovations in suspension mechanismsInnovations in suspension mechanisms
Innovations in suspension mechanisms
 
Suspension system-in-automobiles
Suspension system-in-automobilesSuspension system-in-automobiles
Suspension system-in-automobiles
 
Project PPT
Project PPTProject PPT
Project PPT
 
Air suspension system
Air suspension systemAir suspension system
Air suspension system
 
Active Air Suspension System
Active Air Suspension SystemActive Air Suspension System
Active Air Suspension System
 
Electromagnetic Regenerative Shock Absorbers
Electromagnetic Regenerative Shock AbsorbersElectromagnetic Regenerative Shock Absorbers
Electromagnetic Regenerative Shock Absorbers
 
Dynamic weight transfer in vehicle
Dynamic weight transfer in vehicleDynamic weight transfer in vehicle
Dynamic weight transfer in vehicle
 

Ähnlich wie Smoke evacuation in industrial building

Building Services: Elderly care center services
Building Services: Elderly care center servicesBuilding Services: Elderly care center services
Building Services: Elderly care center servicesEuxuan Ong
 
Building services in public buildings report (1)
Building services in public buildings report (1)Building services in public buildings report (1)
Building services in public buildings report (1)ChengWei Chia
 
Building Services in Public Buildings
Building Services in Public BuildingsBuilding Services in Public Buildings
Building Services in Public BuildingsAndy Heng
 
Case Study of Building Service in Public buildings
Case Study of Building Service in Public buildingsCase Study of Building Service in Public buildings
Case Study of Building Service in Public buildingsChong Chin Pin
 
Data collection
Data collectionData collection
Data collectionTeh Yang
 
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)Nekumi Kida
 
Building Services Case Study
Building Services Case StudyBuilding Services Case Study
Building Services Case StudyBolin Loong
 
Building Services in Public Buildings | Elderly Centre
Building Services in Public Buildings | Elderly CentreBuilding Services in Public Buildings | Elderly Centre
Building Services in Public Buildings | Elderly CentreJoyce Wee
 
B.serve report (1)
B.serve report (1)B.serve report (1)
B.serve report (1)suzzanekan
 
Building Services_Project_02
Building Services_Project_02Building Services_Project_02
Building Services_Project_02Winnie Ang
 
Fire Safety Network for Fertilizers Industries.pdf
Fire Safety Network for Fertilizers Industries.pdfFire Safety Network for Fertilizers Industries.pdf
Fire Safety Network for Fertilizers Industries.pdfPremBaboo4
 
Hazardous Locations 101 by Pepperl+Fuchs
Hazardous Locations 101 by Pepperl+FuchsHazardous Locations 101 by Pepperl+Fuchs
Hazardous Locations 101 by Pepperl+FuchsKristen_Barbour_PF
 
Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...
Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...
Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...Anchal Soni
 
Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)
Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)
Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)Ong Seng Peng Jeff
 
Building services report
Building services report Building services report
Building services report yungkeat74
 
Explosion protection theory and practice
Explosion protection   theory and practiceExplosion protection   theory and practice
Explosion protection theory and practiceDavid Pires
 

Ähnlich wie Smoke evacuation in industrial building (20)

Building Services: Elderly care center services
Building Services: Elderly care center servicesBuilding Services: Elderly care center services
Building Services: Elderly care center services
 
Building services in public buildings report (1)
Building services in public buildings report (1)Building services in public buildings report (1)
Building services in public buildings report (1)
 
Building Services in Public Buildings
Building Services in Public BuildingsBuilding Services in Public Buildings
Building Services in Public Buildings
 
Case Study of Building Service in Public buildings
Case Study of Building Service in Public buildingsCase Study of Building Service in Public buildings
Case Study of Building Service in Public buildings
 
Data collection
Data collectionData collection
Data collection
 
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
 
Building Services Case Study
Building Services Case StudyBuilding Services Case Study
Building Services Case Study
 
Building Services in Public Buildings | Elderly Centre
Building Services in Public Buildings | Elderly CentreBuilding Services in Public Buildings | Elderly Centre
Building Services in Public Buildings | Elderly Centre
 
B.serve report (1)
B.serve report (1)B.serve report (1)
B.serve report (1)
 
Building Services_Project_02
Building Services_Project_02Building Services_Project_02
Building Services_Project_02
 
Fire Safety Network for Fertilizers Industries.pdf
Fire Safety Network for Fertilizers Industries.pdfFire Safety Network for Fertilizers Industries.pdf
Fire Safety Network for Fertilizers Industries.pdf
 
Hazardous Locations 101 by Pepperl+Fuchs
Hazardous Locations 101 by Pepperl+FuchsHazardous Locations 101 by Pepperl+Fuchs
Hazardous Locations 101 by Pepperl+Fuchs
 
Combustible Dust Hazards
Combustible Dust HazardsCombustible Dust Hazards
Combustible Dust Hazards
 
sujit & karan
sujit & karansujit & karan
sujit & karan
 
Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...
Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...
Flare radiation-mitigation-analysis-of-onshore-oil-gas-production-refining-fa...
 
Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)
Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)
Building Service Project 2 Year 2016 (Taylors University Lakeside Campus)
 
Building services report
Building services report Building services report
Building services report
 
Garazi
GaraziGarazi
Garazi
 
Explosion protection theory and practice
Explosion protection   theory and practiceExplosion protection   theory and practice
Explosion protection theory and practice
 
Fire protection engineering design and sustainability
Fire protection engineering design and sustainabilityFire protection engineering design and sustainability
Fire protection engineering design and sustainability
 

Mehr von Zuhal Şimşek

Providing the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in FoundationProviding the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in FoundationZuhal Şimşek
 
COMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRES
COMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRESCOMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRES
COMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRESZuhal Şimşek
 
Providing the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in FoundationProviding the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in FoundationZuhal Şimşek
 
Fire resistant concrete design 2
Fire resistant concrete design 2Fire resistant concrete design 2
Fire resistant concrete design 2Zuhal Şimşek
 
An Evaluation of Hospital Evacuation Strategies with an Example
An Evaluation of Hospital Evacuation Strategies with an ExampleAn Evaluation of Hospital Evacuation Strategies with an Example
An Evaluation of Hospital Evacuation Strategies with an ExampleZuhal Şimşek
 
FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...
FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...
FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...Zuhal Şimşek
 

Mehr von Zuhal Şimşek (6)

Providing the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in FoundationProviding the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in Foundation
 
COMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRES
COMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRESCOMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRES
COMPARATIVE ANALYSIS OF TWO MAJOR HOSPITAL FIRES
 
Providing the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in FoundationProviding the Sustainability with the Pozzuolana Concrete Used in Foundation
Providing the Sustainability with the Pozzuolana Concrete Used in Foundation
 
Fire resistant concrete design 2
Fire resistant concrete design 2Fire resistant concrete design 2
Fire resistant concrete design 2
 
An Evaluation of Hospital Evacuation Strategies with an Example
An Evaluation of Hospital Evacuation Strategies with an ExampleAn Evaluation of Hospital Evacuation Strategies with an Example
An Evaluation of Hospital Evacuation Strategies with an Example
 
FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...
FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...
FIRE SAFETY PRECAUTIONS TAKEN AS A RESULT OF FIRE ENVIRONMENT ANALYSIS IN INT...
 

Kürzlich hochgeladen

Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01KreezheaRecto
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 

Kürzlich hochgeladen (20)

(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 

Smoke evacuation in industrial building

  • 1. International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014 184 Smoke Evacuation in Industrial Buildings Ayşen Gamze Saygılı Doğuç Uludağ University Faculty of Engineering Master Student Görükle, Bursa, Turkiye. Dr. Zuhal Şimşek Research Asistant Uludağ University Faculty of Architecture Architecture Depatment Görükle, Bursa, Turkiye Dr. NurettinYamankaradeniz Prelector Uludağ University Vocational School of Technical Sciences Görükle, Bursa, Turkiye. Abstract Smoke occurs as a result of solid and liquid particles carried in the air from the burning of materials created from the combustion of gases. A dark colored smoke screen is formed. It may be toxic and explosive which make evacuation and responding to the fire more difficult. All these problems can be overcome with an appropriate smoke evacuation system. Smoke evacuation systems can be divided into two categories as natural and mechanical systems. However, they can vary according to needs, the people intensity; materials found in the structure and area, architectural features and design standards. The modelling based on the scenario planned for the most appropriate smoke evacuation system was carried out in compliance with international standards and local regulations. In this study, a vehicle part warehouse belonging to the Oyak Renault automobile factory was established inexactly the same way as the original. Using the CDF based PHONEICS system it was designed that a fire broke out in the warehouse and in the design, parking lot fire data were taken into consideration as given in British Standard (BS) standards ‘Components for smoke and heat control systems’ section 7. Vehicle parts found in the warehouse were in parallel with vehicles which had installation completed in the parking lot without a sprinkler. The smoke emerging as a result of the fire, which had an area of 5×5 m2 and 8MW magnitude and broke out in the warehouse (without sprinkler) whose area and volume were 4680m2 and 37206m3 respectively, was tested with 6 smoke evacuation fans activated at the beginning of the fire. The Total Fan capacity was designed as 10 volume/hour and 15 volume/hour, evaluated according to the maximum CO amount, vision and temperature by simulation for both situations. As a result of the tests performed, ideal visibility distance for evacuation and intervention was ensured with smoke fans at a capacity of 15 volume/hour. Keywords: Smoke evacuation, CFD, Smoke evacuation, Fire safety in industrial buildings 1. Introduction Ignition source, fuel and oxygen combine resulting in combustion. Chemical changes are observed on the structures of objects after they reach ignition temperature. Solid-liquid particles of burning materials and gases form smoke. The majority of deaths in building fires are caused by poisoning from emitted gases rather than structural collapses or burning (19).
  • 2. © Center for Promoting Ideas, USA www.ijastnet.com 185 The toxic and asphyxiation properties of smoke are the main cause of deaths. Smoke mass expanding gradually during combustion causes the increase of environmental temperature and the spread of the fire. Gases emitted with the fire obstruct evacuation by creating a smoke cloud that limits visibility distance. This situation increases the risk of death by extending the time during which people are exposed to toxic and asphyxiating gases (13). In addition, the smoke cloud caused by the fire prevents the fire department from reaching the scene and responding to the fire. The same situation also prevents the medical department from helping people who are exposed to poisonous smoke. Time losses affect the health of people who are at the scene of the fire and trying to find exits for evacuation. This danger is more dominant in multi-storied buildings. Smoke reaches upper floors by spreading through areas such as stairs and elevator shafts, giving more damage to the people on upper floors when they are trying to leave the building by the stairs. 2. Smoke Control in Industrial Buildings Smoke caused by a fire breaking out in industrial buildings affects the health of the operators working in the area. In addition, chemicals are exposed to heat and explosions may occur (1). These can only be prevented by taking smoke under control with some precautions. It is important to prevent the spread of smoke through safe environments and create safe environment conditions at the scene of the fire by evacuating the necessary areas (13). Smoke control can be ensured by carrying out the following;  Division with smoke curtains  Evacuating smoke mechanically or naturally,  Compression,  Providing a clean air supply. In designing smoke evacuation systems the followings are taken into consideration;  The structure of the building,  Physical features,  Intended use,  Fire load. The design aim of smoke evacuation systems changes according to the intended use of the building. In buildings such as shopping centers, cinemas and schools, creating safe escape routes is the most important criterion. Therefore, it is aimed to create a smokeless area necessary for evacuation by holding smoke 2-3 m above the floor (10). In these kinds of buildings a compression system is set up in stairwells where smoke can spread by moving through other floors. The aim of compression is to ensure that environment pressure is higher than the pressure value of the fire location by providing a clear air supply to the environment. In this situation, smoke can spread through the environment when doors are opened for evacuation in case of fire and this should be prevented by taking the precautions mentioned above. As warehouses, manufacturing workshops and industrial facilities have high ceilings and non-segmented areas, compression systems are not sufficient. Therefore, different solutions should be offered in order to control smoke. In these structures, smoke can be removed to the external environment through evacuation dampers opened in the ceiling of the structure. Smoke evacuation dampers found on the ceiling of the structure can be opened by connecting to the central automation system. In addition, the system can be opened as a result of melting the wires which keep the dampers closed. The working principles of a designed smoke control system can be created depending on the scenarios covering automatic detection and extinguishing systems. However, smoke screens can lose their effect depending on ceiling height. In such a situation, the building is divided into zones and smoke can be controlled with evacuation dampers and clean air fans for every zone. A second method in smoke evacuation in multi-storied buildings is the implementation of mechanical smoke evacuation systems. In buildings with sprinklers, smoke evacuation zones are placed in parallel with sprinkler zones and fire is extinguished at the point it begins. Smoke is evacuated from this area before spreading. In an industrial building, the biggest factor with an impact on the amount of smoke is the fire load. Fires are divided into three categories of small, medium and great by taking fire load into consideration. Fire load is obtained by multiplying lower calorific vales and weights of materials and then dividing the result by the area in which they are found.
  • 3. International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014 186 Fan capacities in mechanical evacuation systems can be identified according to the smoke flow rate calculated accordingly (3). If natural clearance is used, smoke amount is also taken into consideration in the calculation of optimum clearance. 3. Material and Method In this study, an evaluation was made of the environment conditions caused by a fire breaking out in a vehicle parts warehouse of an automobile factory and the suction power of the most appropriate system necessary for the evacuation of smoke. The modelled warehouse was a large area and of 7.5 m in height. In the structure, there was no sprinkler or smoke evacuation system. There was a fire risk because of the flammable properties of the vehicle parts stored in the warehouse. There were no permanent employees working in the area. Periodically, four people at most comprising logistics operators and specialists undertake duties for stock control, loading and unloading. The existing emergency doors are open and their positions meet the requirements of fire regulations. Therefore, it is thought that there will not be a problem in terms of evacuating smoke. In the modelling, the aim was to create a clean sub-region for evacuating smoke quickly, making the intervention of the fire department easier and to be able to save parts with the least damage. In order for the fire department to respond to the fire effectively, the field of vision should be open. In warehouse fires, saving the stored raw materials or products as well as employees working in the warehouse or environment is of vital importance. Furthermore, workplace management should act within the scope of the projected budget in order to maintain its existence. Therefore, choosing the most ideal, appropriate and economic smoke evacuation system is very important in the modelling. The program we chose for the study that we carried out was the CDF based PHONEICS program (12). This program is used to perform simulations for evaluating the tests that are necessary for the appropriate smoke evacuation system. With this program, smoke movement, temperature and visibility distance can be tracked through three dimensional images. CDF (Computational Fluid Dynamics) (1) is a programming system that analyses the movement of fluids. With classical fluid dynamics, simple flat sheet solutions can be easily performed but for complicated geometries and variable viscosities CDF analyses are more reliable and appropriate. CDF gives the opportunity for analysis of many different parameters and does not cause deterioration of the fluid property. In the program, the t2 fire model included in NFPA 92 was used. In this modelling, the square of fire growing duration increases in direct proportion to calorific power. The point at which the fire reaches fixed calorific power is its largest point. Calorific load does not increase from this point and continues to be fixed. In evaluating scenarios, the duration taken for the fire to reach its highest calorific power is considered to be the fire duration and smoke control system modelling for the evacuation of smoke is studied. In the program, the required data regarding the designed warehouse (control volume) was obtained at different moments and heights thanks to the detector (propre) placed in the area where the fire might have broken out. Due to this data, the correct fan was selected. As the warehouse is an area where only vehicle parts are stored, the fire load of our control volume was accepted as 8MW which is the parking lot (without sprinkler) fire load given in the BS standards. The fire generating area was accepted as 5x5m2 which is again given in the same standards and in compliance with the layout of control volume (4). The sprinkler system is a factor which considerably affects fire load. If there is a sprinkler, the fire load in the control volume decreases to 4MW. To respond to a fire in the warehouse the most important matters are temperature and field of vision. In this environment, there are no permanent employees and the area is large. Therefore, the density of toxic gases will be low. Temperature and field of vision should be analyzed and evaluated for the fire department to respond to the fire more easily and for employees to be evacuated quickly. The most appropriate evaluation height was determined as 2m by considering the average human height. This value is a little higher than the average human height (2). For safety purposes, PPM values at 2m height and different heights were also checked.
  • 4. © Center for Promoting Ideas, USA www.ijastnet.com 187 General Data of the Vehicle Parts Warehouse of the Automobile Factory: The dimensions of the warehouse in question are 130x36x7.95 meters. It is rectangular shaped and has a total area of 4680m2 . The walls are made of 10 cm thick rock wool filled between metal sheets, and 2-hour fire-resistant metal sandwich panels. The roof coating is a single layer metal sheet. There are two 3.5x4 m guillotine doors on the northern side of the building, another 3.5x4 m guillotine door on the southern side of the building towards the middle of that side and another 3.5x4 m guillotine door on the east corner of the northern wall of the building. In total 4 guillotine doors with a total area of 14m2 are kept open for materials supply. Two of the operator entry doors with a width of 90 cm and height of 220 cm, are located on the northeast and southwest corners towards the opposite directions while the other two are located on the northern wall 30 meters apart. The doors are barred and open outwards. They are kept closed while not in use. 15m2 guillotine doors are used to provide fresh air on 3 fronts of the building, providing 60m2 ventilation areas in total. Boundary conditions are considered as fresh air entrance from the doors. The smoke coming out of the guillotine doors during the fire was not taken into account assuming that it must be within the minimum range. 2 scenarios were assayed for the logistics warehouse in this study. The duration of the fire was determined as 600 seconds for both scenarios. A setting was prepared where the vehicle parts were burning slowly because of an electrical installation breakdown and the fire reached its highest fire load value at the end of 600 seconds (Table 3.1). Table 3.1 Development of Fire Duration Values According to Fire the Type of Combustible (NFPA 92) Burnig rate according to fire the type of combustible Development of fire duration value Slow 600 Medium 300 Fast 150 Ultra-fast 75 4. Evaluation Scenario 1: A 10 volume/hour air exchange was divided among 6 fans and each fan made smoke evacuation 62010m3 per hour. The 600 seconds were evaluated taking into account that the fire reached its peak in 600 seconds. At the end of this period PPM value was 1321 and the temperature was approximately 21,20⁰C, posing no risk. Nevertheless, the visibility distance was insufficient for the firefighters arriving 10 minutes after the fire broke out (Figures 3.1- 3.2-3.3). Consequently, a second scenario was tried. Diagram 4.1: (Volume/Time)Slen Distance Depends on the Height of the Smoke Discharge Capacity at 600 S. (Scenario 1)
  • 5. International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014 188 Diagram 4.2: PPM Status at 2m.height from Basement at the End of 600 Seconds Diagram 4.3: Temperature Values 2m height from Basement at the End of 600 Seconds Slen Hight Diagram 4.4.Slen Distance Depends On the Height of the Smoke Discharge Capacity at 600s (Scenario2)
  • 6. © Center for Promoting Ideas, USA www.ijastnet.com 189 Scenario 2: The smoke evacuation fan capacity which was set as 10 volume/hour and understood to be insufficient was increased to 15 volume/hour. The capacity of each fan was readjusted as 25,8372 m3/seconds. They were activated as soon as the fire broke out just as in scenario 1. 300 iterations were estimated in the program for the 600 seconds long fire. The condition of the fire was checked every two seconds. Visibility at 2 meters of height increased from 3,7 m to 20,16 m in the second trial (Figure 4.4). This is an appropriate visibility distance both for evacuation and intervention. 10 minutes is a very long duration for evacuation in a building in which there is a maximum of 4 people. Thus the evacuation would be completed before the fire reaches its peak unless there is an exceptional situation such as an accident. The temperature was 21.20⁰C and the PPM value was 3081 at 2 meters above the floor at the end of 600 seconds (Figures 4.5-4.6). The temperature and PPM values do not pose any risk for the firefighter teams. Diagram 4.5: Temperature Values at 2m height from Basement at the End of 600 Seconds Diagram 4.6.PPM status about 2 meters height from basement at the end of 600 seconds 5. Conclusion The study covers a vehicle fire reaching up to 8MV thermal power which started in an area of 5×5 m2 in the 7.95 m high warehouse without a sprinkler with a floor area of 4608 m2 . The CFD based flair programme was used for the fire. 6 fans making 10 volume/hour air exchanges in total were active during 600 seconds, which resulted in 3m visibility distance at 2 meters above the floor, which is known as the highest level of clearance below the smoke.
  • 7. International Journal of Applied Science and Technology Vol. 4, No. 3; May 2014 190 The possibility of people still being evacuated in the building in the 10th minute of the fire was very low considering the number of people in the building. However, for whatever reason, the fire department arrived on the scene after 10 minutes and 3m of visibility distance was not sufficient for intervention. Finding the center of the fire, then bringing the equipment to the center is very dangerous and difficult in smoke density with only 3m of visibility distance. Temperature and PPM did not pose any danger (14). A trial-and-error method was implemented to find the most appropriate smoke evacuation fan flow rate. The capacity of the fans was increased up to 50 % considering the smoke density produced by the vehicle parts. In total 15 volume/hour air exchange smoke evacuation continued for 600 minutes during the last trial. The lowest visibility distance at 2 meters of height detected during and at the end of these 600 minutes was 20.16 meters. This visibility clearance is suitable for both evacuation and intervention according to NFPA 92. The smoke density increased rapidly starting at 2.2 meters and the visibility decreased to less than 1 meter parallel to the height. It is understood from this study that a smoke evacuation system with industrial fans at 15 volume/hour air exchange provides an appropriate clear bottom height in the warehouse of an automobile factory. References Anonim, 2005.Teskon 2005 program bildirileri/yayın-33 Anonim. 2014. Türkiye İstatistik Kurumuverileri, ortalamatürkerkekboyu 167,2cm. Arpacı, V.S., Larsen, P.S. 1984. Convection Heat Transfer, Prentice-Hall,New Jersey British Standard Components for smoke and heat control systems ,part 7 British Standard Component for smoke and heat control systems CIBSE GUIDE E. 1997. Fire Engineering, The Chartered Institution of Building Services Engineers, London. Hansell G.O., Morgan H.P. 1994. Design Approaches for Smoke Control in Atrium Buildings, Building Research Establishment Report, Gartso Kılıç A.,İ.T.ÜMakineMühendisliğiDersnotları; YangınYükü Klote,J.H.andMilke J.A. ,1992 Design of Smoke Management Systems, ASHRAE Inc.,Atlanta, http://www.epa.gov/iaq/co.html NFPA 92 Standart for smoke control systems 2009 NFPA Life safety code handbook 2009 Patankar, S.V. 1980. Numeric Heat Transfer and Fluid Flow, Hemisphere Publishing , New YORK Gültek S., Selvi U., Endüstriyelyapılardayangındumanınıncebrivedoğalyollatahliyekriterleri White F.M. 1974 ViscousFluide Flow ,Mc-Glaw –Hill ,New York http://www.birimmuhendislik-tr.com/tr-TR/Default.aspx?c=23 http://www.cdc.gov/niosh/idlh/630080.html http://www.cob.nl/fileadmin/user_upload/Documenten http://www.cpsc.gov/en/safety-education/safety-education-centers http://www.desica.com.tr/cfd_nedir.html http://support.engenuity.com/literature/articles_whitepapers http://www.yangin.org/dosyalar/duman_kontrol_gereklilig.pdf