02

Central Inverters
Sirio Central inverters allow direct connection to the low voltage grid ensuring
the galvanic separation compared to direct current installations. The generous
rating of the transformer and the other
inverter components provides a return
of the highest among the machines of
the same category.
Maximum energy and safety
The Maximum Power Point Tracking
(MPPT) research algorithm implemented in the control system of Sirio
Central inverters allows full use of the
photovoltaic generator in any radiation
and temperature conditions, making
the plant work constantly at maximum
efficiency. In the absence of solar radiation the converter goes on standby
and resumes normal operation when
there is radiation again. This feature reduces self-consumption to a minimum

and maximizes energy efficiency. The
use of speed-controlled fans helps to
optimize the overall efficiency of the inverter. Fan operation that is linked to
the temperature also increases the expected lifespan and reduces costs incurred for extraordinary maintenance.
All these design features, the careful
choice of components and guaranteed quality of production according to
ISO9001 standards make the threephase inverters Sirio extremely efficient
and reliable and guarantee maximum
energy production.

www.aros-solar.com

thermal derating
Derating as a function of temperature
aimed to safeguard against overheating
inverter semiconductors in the case of
environments with temperatures exceeding installation specifications or for
forced ventilation faults, without causing a complete block of the inverter
itself. Sirio Central models ensure rated
power output up to 45°C environment.
If this threshold is exceeded, the inverter gradually decreases the power fed
into the network in such a way as to
maintain heat sink temperature within
the maximum limit. Once back in the
range of thermal normal operation, the
inverter restores the optimal working
point, again ensuring maximum power
transfer.

www.aros-solar.com

easy installation and maintenance
The footprint of these devices has been
considerably reduced and there is no
need to leave space at the side or back
of the equipment since the electronics
and power components are fully accessible from the front. Fully automatic operation ensures ease of use and
facilitates installation and startup, thus
avoiding installation and configuration
errors which could lead to failures or
reduced plant productivity.
Personalized solutions
AROS is able on request to supply Sirio
Central inverters specific to the client’s
needs. Available options include the integrated isolation control and the pole/
earth connection kit (positive or negative) that is required for some kinds of
photovoltaic modules.

certificate of Factory inspection
Sirio Central inverters meet “Made in
EU” criteria as they are designed, manufactured and tested in Italy.

centRal inVeRteRs

49

02

48
50

02

Central Inverters
User interface
Sirio Central inverters provide a series
of new user interfaces composed of an
LCD colour touch screen in a convenient 4.3” format. The millions of colours and quantity of features greatly
enrich the user’s interaction experience
with the solar inverter.
Intuitive icons and brief messages in
the set language guide users through
the simple menu structure, allowing
them to access all reference, configuration and inverter control features. In
particular, it is possible to view a daily
energy production graph and the instantaneous value of power produced,
verify module temperatures and the
measurements of any installed analogue sensors.
The archive section allows viewing and
analysis of historical data, crossing measurements as desired (no longer two
sizes at a time). By scrolling a finger
along the screen, users can query values recorded in previous days, including in monthly or annual intervals, and
the graphs displayed can be sent via
e-mail. Internal storage allows for the
archiving of about 10 years of data. However, if necessary, it is possible to delete older years by means of a special
feature. Historical data produced by
the inverter and that of the system card
can be saved on a USB flash drive.

The device also allows users to change
the €/KWh ratio, adjust display brightness, change the system date and time,
assign an identification and label to the
plant it belongs to, configure and customise up to 4 external analogue sensors.
It also allows e-mails to be sent (for
which you can set the frequency) with
production data and graphs and, in the
case of abnormalities, any malfunction
or ignition failure alarms.
Finally, via special counters in the Info
section, users can consult data regarding total produced energy, the overall hours of operation, the economic
return of the plan and other technical
parameters, including the amount of
memory used for historical data. The
graphic interface is available in Italian,
English, French, Spanish and German.

network access
The touch screen device offers many
communication possibilities if a connection to the local network exists. The
inverter is compatible both with PVSER
proprietary protocol on the network and
with ModBUS/TCP, thus offering easy
insertion in any management BMS or
data analysis using an Ethernet network.
The display software can be easily and
quickly updated. Moreover, with a freeware software (VNC), users can remotely view the inverter screen or interact
with it from their computer or mobile
device.

www.aros-solar.com
53

Sirio

12

CENTRaL INVERTERS

gRiD connection
cRiteRia
The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

14 kWp max
9 kWp min
12 kW
13,2 kW

FeatURes
colour: RAL 7035

555

Dimensions (WxDxh): 555x720x1400 mm
Weight: 310 Kg
Protection level: IP20
acoustic noise: <66dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
36 Adc
390 Vdc
<1%
1
1
Screw terminals
400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
17,3 Aac
22,4 Aac
34 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Screw terminals

coMMUnication
Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP

555

stanDaRDs
eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

95,8%
94,8%
<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

1400

555

(1) These values can vary according to the local regulations

www.aros-solar.com

750 740

10

Approximate power of the photovoltaic field

sirio K12

555

GRID

MoDel

www.aros-solar.com

02

02

centRal inVeRteRs

52
55

Sirio

15

CENTRaL INVERTERS

gRiD connection
cRiteRia
The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

18 kWp max
12 kWp min
15 kW
17 kW

FeatURes
colour: RAL 7035

555

Dimensions (WxDxh): 555x720x1400 mm
Weight: 320 Kg
Protection level: IP20
acoustic noise: <66dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
54 Adc
390 Vdc
<1%
1
1
Screw terminals
400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
21,7 Aac
28,1 Aac
42 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Screw terminals

coMMUnication
Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP

555

stanDaRDs
eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

95,8%
94,8%
<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

1400

555

(1) These values can vary according to the local regulations

www.aros-solar.com

750 740

10

Approximate power of the photovoltaic field

sirio K15

555

GRID

MoDel

www.aros-solar.com

02

02

centRal inVeRteRs

54
57

Sirio

18

CENTRaL INVERTERS

gRiD connection
cRiteRia
The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

21 kWp max
16 kWp min
18 kW
20 kW

FeatURes
colour: RAL 7035

555

Dimensions (WxDxh): 555x720x1400 mm
Weight: 340 Kg
Protection level: IP20
acoustic noise: <66dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
63 Adc
390 Vdc
<1%
1
1
Screw terminals
400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
26 Aac
33 Aac
50 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Screw terminals

coMMUnication
Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP

555

stanDaRDs
eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

95,8%
94,8%
<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

1400

555

(1) These values can vary according to the local regulations

www.aros-solar.com

750 740

10

Approximate power of the photovoltaic field

sirio K18

555

GRID

MoDel

www.aros-solar.com

02

02

centRal inVeRteRs

56
59

Sirio

25 and

25 HV

CENTRaL INVERTERS

The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K25 hV

30 kWp max
20 kWp min
25 kW
28 kW

FeatURes
colour: RAL 7035

555

Dimensions (WxDxh): 555x720x1400 mm
Weight: 350 Kg
Protection level: IP20
acoustic noise: <66dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
80 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
59 Adc
540 Vdc

<1%
1
1
Screw terminals
400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
36 Aac
46 Aac
68 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Screw terminals
95,8%
94,9%

750 740

coMMUnication
Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)

10

gRiD connection
cRiteRia

sirio K25

Protocols: ModBUS and ModBUSTCP

555

stanDaRDs
eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

1400

96,4%
95,3%

555

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

GRID

MoDels

(1) These values can vary according to the local regulations

www.aros-solar.com

www.aros-solar.com

02

02

centRal inVeRteRs

58
61

Sirio

33 and

33 HV

CENTRaL INVERTERS

The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K33 hV

40 kWp max
30 kWp min
33 kW
36 kW

FeatURes
colour: RAL 7035

555

Dimensions (WxDxh): 555x720x1400 mm
Weight: 380 Kg
Protection level: IP20
acoustic noise: <66dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
105 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
79 Adc
540 Vdc

<1%
1
1
Screw terminals
400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
48 Aac
60 Aac
90 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Screw terminals
95,8%
94,9%

750 740

coMMUnication
Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)

10

gRiD connection
cRiteRia

sirio K33

Protocols: ModBUS and ModBUSTCP

555

stanDaRDs
eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

1400

96,3%
95,3%

555

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

GRID

MoDels

(1) These values can vary according to the local regulations

www.aros-solar.com

www.aros-solar.com

02

02

centRal inVeRteRs

60
63

Sirio

40 and

40 HV

CENTRaL INVERTERS

The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K40 hV

50kWp max
36kWp min
40kW
44kW

FeatURes
colour: RAL 7035

555

Dimensions (WxDxh): 555x720x1400 mm
Weight: 420 Kg
Protection level: IP20
acoustic noise: <66dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
130 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
98 Adc
540 Vdc

<1%
1
1
Screw terminals
400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
58 Aac
73 Aac
110 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Screw terminals
95,8%
95%

750 740

coMMUnication
Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)

10

gRiD connection
cRiteRia

sirio K40

Protocols: ModBUS and ModBUSTCP

555

stanDaRDs
eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

1400

96,2%
95,3%

555

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

GRID

MoDels

(1) These values can vary according to the local regulations

www.aros-solar.com

www.aros-solar.com

02

02

centRal inVeRteRs

62
65

Sirio

64 and

64 HV

CENTRaL INVERTERS

The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K64 hV

80 kWp max
55 kWp min
64 kW
71 kW

FeatURes
colour: RAL 7035

800

Dimensions (WxDxh): 800x800x1900 mm
Weight: 600 Kg
Protection level: IP20

810 797

acoustic noise: <68dBA
800 Vdc
330÷700 Vdc
330÷700 Vdc
205 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
157 Adc
540 Vdc
<1%
1
1
Bar

Display: Color LCD touch screen

800

communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP
stanDaRDs

400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
92 Aac
117 Aac
175 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Bar
96,1%
95%

coMMUnication
13

gRiD connection
cRiteRia

sirio K64

eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC

800

96,1%
94,9%

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

(1) These values can vary according to the local regulations

www.aros-solar.com

1900

grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

GRID

MoDels

www.aros-solar.com

02

02

centRal inVeRteRs

64
67

Sirio

80 and

80 HV

CENTRaL INVERTERS

The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K80 hV

100 kWp max
70 kWp min
80 kW
88 kW

FeatURes
colour: RAL 7035

800

Dimensions (WxDxh): 800x800x1900 mm
Weight: 650 Kg
Protection level: IP20

810 797

acoustic noise: <68dBA
800 Vdc
330÷700 Vdc
330÷700 Vdc
260 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
196 Adc
540 Vdc
<1%
1
1
Bar

Display: Color LCD touch screen

800

communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP
stanDaRDs

400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
115 Aac
146 Aac
219 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Bar
96,1%
95%

coMMUnication
13

gRiD connection
cRiteRia

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power

sirio K80

eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC

800

96,1%
95%

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

(1) These values can vary according to the local regulations

www.aros-solar.com

1900

grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

GRID

MoDels

www.aros-solar.com

02

02

centRal inVeRteRs

66
69

Sirio

100 and

100 H V

CENTRaL INVERTERS

The entire range can be
configured according to the
following standards:
- CEI 0-21
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K100 hV

125 kWp max
80 kWp min
100 kW
110 kW

FeatURes
colour: RAL 7035

800

Dimensions (WxDxh): 800x800x1900 mm
Weight: 720 Kg
Protection level: IP20

810 797

acoustic noise: <68dBA
800 Vdc
330÷700 Vdc
330÷700 Vdc
320 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
245 Adc
540 Vdc
<1%
1
1
Bar

Display: Color LCD touch screen

800

communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP
stanDaRDs

400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
145 Aac
182 Aac
274 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Bar
96,1%
95,1%

coMMUnication
13

gRiD connection
cRiteRia

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power

sirio K100

eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC

800

96,1%
95,1%

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

(1) These values can vary according to the local regulations

www.aros-solar.com

1900

grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105,
VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3

GRID

MoDels

www.aros-solar.com

02

02

centRal inVeRteRs

68
71

Sirio

200 and

200 H V

CENTRaL INVERTERS

gRiD connection
cRiteRia
The entire range can be
configured according to the
following standards:
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

Approximate power of the photovoltaic
field
Rated AC power
Maximum AC power
inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors
oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

sirio K200

sirio K200 hV

250 kWp max
180 kWp min
200 kW
220 kW

FeatURes
colour: RAL 7035
13

Dimensions (WxDxh): 1630x1000x1900 mm

1010
997

Weight: 1580 Kg
Protection level: IP20
acoustic noise: <72dBA

800 Vdc
330÷700 Vdc
330÷700 Vdc
650 Adc
390 Vdc

880 Vdc
450÷760 Vdc
450÷760 Vdc
500 Adc
540 Vdc
<1%
1
1
Bar

1630

Display: Color LCD touch screen
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP
stanDaRDs

400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
289 Aac
364 Aac
546 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Bar
96,2%
95,2%

coMMUnication

1630

eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2,
Real Decreto 1663-2000, PO12.3
1900

1630

96,3%
95,2%

<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

GRID

MoDels

(1) These values can vary according to the local regulations

www.aros-solar.com

www.aros-solar.com

02

02

centRal inVeRteRs

70
73

Sirio

250 HV

CENTRaL INVERTERS

Approximate power of the photovoltaic field

gRiD connection
cRiteRia
The entire range can be
configured according to the
following standards:
- CEI 0-16
- VDE aR-N-4105
- VDE 0126-1-1
- G59/2
- Real Decreto 1663-2000
- PO12.3

oPtion on ReQUest
- Pole/earth connection kit
(positive or negative)
- Overvoltage protection
(SPD)

sirio K250 hV

Rated AC power
Maximum AC power

320 kWp max
220 kWp min
250 kW
250 kW

inPUt
Maximum DC voltage in an open circuit
MPPT operating range
Working range
Maximum input current
Initial feeding voltage
Ripple voltage
Number of inputs
MPPT number
D.C. connectors

880 Vdc
450÷760 Vdc
450÷760 Vdc
590 Adc
540 Vdc
<1%
1
1
Bar

oUtPUt
Operating voltage
Operating interval
Maximum power range
Frequency range
Settable frequency range
Nominal current
Maximum current
Fault level contribution
Current Harmonic Distorsion (THDi)
Power factor
Galvanic separation
A.C. connectors
sYsteM
Maximum efficiency
European efficiency
Stand-by consumption
Night consumption
Internal protections
Off-Grid protection
Detecting earth leakage
Heat dissipation
Operating temperature
Storage temperature
Humidity

FeatURes
colour: RAL 7035
13

Dimensions (WxDxh): 1630x1000x1900 mm

1010
997

Weight: 1630 Kg
Protection level: IP20
acoustic noise: <72dBA

400 Vac
340÷460 Vac (1)
340÷460 Vac
47,5÷51,5 Hz (1)
47÷53 Hz
361 Aac
420 Aac
630 Aac
<3%
from 0,9 ind. to 0,9 cap. (1)
LF transformer
Bar

coMMUnication
communication interface: Ethernet, USB, 2xRS232 as standard,
RS485 optional (slot version)
Protocols: ModBUS and ModBUSTCP
stanDaRDs

1630

eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12
security: EN62109-1, EN62109-2
Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC
grid connection criteria: CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2,
Real Decreto 1663-2000, PO12.3
1900

1630

96,3%
95,3%
<32W
<32W
MCCB AC side, Switch DC side
Yes
Yes
controlled fans
0°C÷45°C (without derating)
-20°C÷70°C
0÷95% non-condensing

(1) These values can vary according to the local regulations

www.aros-solar.com

1630

Display: Color LCD touch screen

GRID

MoDel

www.aros-solar.com

02

02

centRal inVeRteRs

72

Weitere ähnliche Inhalte

Was ist angesagt?

Infineon Angle Sensors for Automotive Applications
Infineon Angle Sensors for Automotive ApplicationsInfineon Angle Sensors for Automotive Applications
Infineon Angle Sensors for Automotive Applications
Infineon4Engineers
 
Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013
ifm electronic gmbh
 
Tolomatic smart actuator series icr basic & plus brochure
Tolomatic smart actuator series   icr basic & plus brochureTolomatic smart actuator series   icr basic & plus brochure
Tolomatic smart actuator series icr basic & plus brochure
Electromate
 

Was ist angesagt? (20)

Catalog Biến tần Frenic Lift Fuji Electric-Beeteco.com
Catalog Biến tần Frenic Lift Fuji Electric-Beeteco.comCatalog Biến tần Frenic Lift Fuji Electric-Beeteco.com
Catalog Biến tần Frenic Lift Fuji Electric-Beeteco.com
 
Infineon Angle Sensors for Automotive Applications
Infineon Angle Sensors for Automotive ApplicationsInfineon Angle Sensors for Automotive Applications
Infineon Angle Sensors for Automotive Applications
 
Retrofit
RetrofitRetrofit
Retrofit
 
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.com
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.comCatalog biến tần Frenic Mega Fuji Electric-Beeteco.com
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.com
 
Catalog biến tần Frenic eHVAC - beeteco.com
Catalog biến tần Frenic eHVAC - beeteco.comCatalog biến tần Frenic eHVAC - beeteco.com
Catalog biến tần Frenic eHVAC - beeteco.com
 
Ecopowersupplies: Riello Sentinel Dual High Power UPS
Ecopowersupplies: Riello Sentinel Dual High Power UPSEcopowersupplies: Riello Sentinel Dual High Power UPS
Ecopowersupplies: Riello Sentinel Dual High Power UPS
 
Monitoring genset systems in standby mode to assure reliable startup
Monitoring genset systems in standby mode to assure reliable startupMonitoring genset systems in standby mode to assure reliable startup
Monitoring genset systems in standby mode to assure reliable startup
 
SMA 60kW Tri Power
SMA 60kW Tri PowerSMA 60kW Tri Power
SMA 60kW Tri Power
 
Vlt micro drive - Danfoss
Vlt micro drive - DanfossVlt micro drive - Danfoss
Vlt micro drive - Danfoss
 
Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013
 
Embedded World 2015: Sense2Go - 24GHz Sensor Solution for Industrial Applicat...
Embedded World 2015: Sense2Go - 24GHz Sensor Solution for Industrial Applicat...Embedded World 2015: Sense2Go - 24GHz Sensor Solution for Industrial Applicat...
Embedded World 2015: Sense2Go - 24GHz Sensor Solution for Industrial Applicat...
 
Vlt micro drive fc51
Vlt micro drive fc51Vlt micro drive fc51
Vlt micro drive fc51
 
Industrial Temperature Controller System
Industrial Temperature Controller SystemIndustrial Temperature Controller System
Industrial Temperature Controller System
 
Tolomatic smart actuator series icr basic & plus brochure
Tolomatic smart actuator series   icr basic & plus brochureTolomatic smart actuator series   icr basic & plus brochure
Tolomatic smart actuator series icr basic & plus brochure
 
Zxdu68 t601 product description v1.0 20101221 en
Zxdu68 t601 product description v1.0 20101221 enZxdu68 t601 product description v1.0 20101221 en
Zxdu68 t601 product description v1.0 20101221 en
 
Applying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlApplying Digital Isolators in Motor Control
Applying Digital Isolators in Motor Control
 
Smart – Optimizer ECOD
Smart – Optimizer ECODSmart – Optimizer ECOD
Smart – Optimizer ECOD
 
Compact Inverter WJ200 series
Compact Inverter WJ200 seriesCompact Inverter WJ200 series
Compact Inverter WJ200 series
 
Catalog Biến tần Frenic Aqua Fuji-Beeteco.com
Catalog Biến tần Frenic Aqua Fuji-Beeteco.comCatalog Biến tần Frenic Aqua Fuji-Beeteco.com
Catalog Biến tần Frenic Aqua Fuji-Beeteco.com
 
Hydrovar
HydrovarHydrovar
Hydrovar
 

Ähnlich wie Riello aros-central-transformer-based-solar-inverters

Ähnlich wie Riello aros-central-transformer-based-solar-inverters (20)

SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
 
Catalog Biến tần Frenic MINI mới nhất 2019
Catalog Biến tần Frenic MINI mới nhất 2019Catalog Biến tần Frenic MINI mới nhất 2019
Catalog Biến tần Frenic MINI mới nhất 2019
 
Riello aros-transformerless-solar-inverters
Riello aros-transformerless-solar-invertersRiello aros-transformerless-solar-inverters
Riello aros-transformerless-solar-inverters
 
Riello aros-transformerless-solar-inverters
Riello aros-transformerless-solar-invertersRiello aros-transformerless-solar-inverters
Riello aros-transformerless-solar-inverters
 
04 V4- K TSM 380V 50Hz.pdf
04 V4- K TSM 380V 50Hz.pdf04 V4- K TSM 380V 50Hz.pdf
04 V4- K TSM 380V 50Hz.pdf
 
Siemens catalog tong hop 3 uf simocode
Siemens catalog tong hop 3 uf simocodeSiemens catalog tong hop 3 uf simocode
Siemens catalog tong hop 3 uf simocode
 
Bien tan-mini
Bien tan-miniBien tan-mini
Bien tan-mini
 
SMA 3.0-5.0 Grid Tied Solar String Inverter
SMA 3.0-5.0 Grid Tied Solar String InverterSMA 3.0-5.0 Grid Tied Solar String Inverter
SMA 3.0-5.0 Grid Tied Solar String Inverter
 
single-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdfsingle-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdf
 
siprotec
siprotecsiprotec
siprotec
 
siprotec
siprotecsiprotec
siprotec
 
Ultisolar iT3415 iT4415 iT6415 iTracer User Manual
Ultisolar iT3415 iT4415 iT6415  iTracer User ManualUltisolar iT3415 iT4415 iT6415  iTracer User Manual
Ultisolar iT3415 iT4415 iT6415 iTracer User Manual
 
Solar Max MT 3 Phase Inverters
Solar Max MT 3 Phase InvertersSolar Max MT 3 Phase Inverters
Solar Max MT 3 Phase Inverters
 
ABB Trio
ABB TrioABB Trio
ABB Trio
 
IRJET- IoT based Industrial Automation
IRJET-  	  IoT based Industrial AutomationIRJET-  	  IoT based Industrial Automation
IRJET- IoT based Industrial Automation
 
Siemens MICRO VFD part 1
Siemens MICRO VFD part 1Siemens MICRO VFD part 1
Siemens MICRO VFD part 1
 
SolarMax P Series 'Battery Ready' Inverters.
SolarMax P Series 'Battery Ready' Inverters. SolarMax P Series 'Battery Ready' Inverters.
SolarMax P Series 'Battery Ready' Inverters.
 
Central Grid Tie Solar Inverter - InPhase Power
Central Grid Tie Solar Inverter - InPhase PowerCentral Grid Tie Solar Inverter - InPhase Power
Central Grid Tie Solar Inverter - InPhase Power
 
SMA Small
SMA Small SMA Small
SMA Small
 
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
 

Mehr von Electrical and renewable energy engineering

Mehr von Electrical and renewable energy engineering (20)

Riello vdc-xeb-flywheel-enery-storage-systems
Riello vdc-xeb-flywheel-enery-storage-systemsRiello vdc-xeb-flywheel-enery-storage-systems
Riello vdc-xeb-flywheel-enery-storage-systems
 
Riello vdc-xeb-flywheel-enery-storage-systems
Riello vdc-xeb-flywheel-enery-storage-systemsRiello vdc-xeb-flywheel-enery-storage-systems
Riello vdc-xeb-flywheel-enery-storage-systems
 
Riello ups-powerbox-containerised-ups
Riello ups-powerbox-containerised-upsRiello ups-powerbox-containerised-ups
Riello ups-powerbox-containerised-ups
 
Eaton 9sx-datasheet
Eaton 9sx-datasheetEaton 9sx-datasheet
Eaton 9sx-datasheet
 
Riello flywheel-energy-storge-systems
Riello flywheel-energy-storge-systemsRiello flywheel-energy-storge-systems
Riello flywheel-energy-storge-systems
 
Eaton 5130-ups-datasheet
Eaton 5130-ups-datasheetEaton 5130-ups-datasheet
Eaton 5130-ups-datasheet
 
Riello master-switch-sts-3p
Riello master-switch-sts-3pRiello master-switch-sts-3p
Riello master-switch-sts-3p
 
Riello multi-switch-ats-16a
Riello multi-switch-ats-16aRiello multi-switch-ats-16a
Riello multi-switch-ats-16a
 
Riello master-switch-sts-1p
Riello master-switch-sts-1pRiello master-switch-sts-1p
Riello master-switch-sts-1p
 
Eaton epdu-power-distribution-units
Eaton epdu-power-distribution-unitsEaton epdu-power-distribution-units
Eaton epdu-power-distribution-units
 
Riello master-frequency-converters
Riello master-frequency-convertersRiello master-frequency-converters
Riello master-frequency-converters
 
Riello master-ups-vdc
Riello master-ups-vdcRiello master-ups-vdc
Riello master-ups-vdc
 
Riello multi-switch-ats
Riello multi-switch-atsRiello multi-switch-ats
Riello multi-switch-ats
 
Eaton 5s-ups-datasheet
Eaton 5s-ups-datasheetEaton 5s-ups-datasheet
Eaton 5s-ups-datasheet
 
Sdmo telecoms-generator-solutions
Sdmo telecoms-generator-solutionsSdmo telecoms-generator-solutions
Sdmo telecoms-generator-solutions
 
Riello master-industrial-ups-datasheet
Riello master-industrial-ups-datasheetRiello master-industrial-ups-datasheet
Riello master-industrial-ups-datasheet
 
Riello master-wrap-around-static-bypass
Riello master-wrap-around-static-bypassRiello master-wrap-around-static-bypass
Riello master-wrap-around-static-bypass
 
Riello multi-guard-industrial-ups
Riello multi-guard-industrial-upsRiello multi-guard-industrial-ups
Riello multi-guard-industrial-ups
 
Eaton ellipse-eco-ups-datasheet
Eaton ellipse-eco-ups-datasheetEaton ellipse-eco-ups-datasheet
Eaton ellipse-eco-ups-datasheet
 
Eaton 3s-ups-datasheet
Eaton 3s-ups-datasheetEaton 3s-ups-datasheet
Eaton 3s-ups-datasheet
 

Kürzlich hochgeladen

Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service NoidaCall Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
dlhescort
 
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
daisycvs
 
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
amitlee9823
 
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
lizamodels9
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
Abortion pills in Kuwait Cytotec pills in Kuwait
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
amitlee9823
 

Kürzlich hochgeladen (20)

Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service NoidaCall Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
 
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
 
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceEluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
 
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
Nelamangala Call Girls: 🍓 7737669865 🍓 High Profile Model Escorts | Bangalore...
 
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
(Anamika) VIP Call Girls Napur Call Now 8617697112 Napur Escorts 24x7
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Falcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business PotentialFalcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business Potential
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
 
Falcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to ProsperityFalcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to Prosperity
 
Uneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration PresentationUneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration Presentation
 
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceMalegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
 
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
 
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
Cheap Rate Call Girls In Noida Sector 62 Metro 959961乂3876
 

Riello aros-central-transformer-based-solar-inverters

  • 1. 02 Central Inverters Sirio Central inverters allow direct connection to the low voltage grid ensuring the galvanic separation compared to direct current installations. The generous rating of the transformer and the other inverter components provides a return of the highest among the machines of the same category. Maximum energy and safety The Maximum Power Point Tracking (MPPT) research algorithm implemented in the control system of Sirio Central inverters allows full use of the photovoltaic generator in any radiation and temperature conditions, making the plant work constantly at maximum efficiency. In the absence of solar radiation the converter goes on standby and resumes normal operation when there is radiation again. This feature reduces self-consumption to a minimum and maximizes energy efficiency. The use of speed-controlled fans helps to optimize the overall efficiency of the inverter. Fan operation that is linked to the temperature also increases the expected lifespan and reduces costs incurred for extraordinary maintenance. All these design features, the careful choice of components and guaranteed quality of production according to ISO9001 standards make the threephase inverters Sirio extremely efficient and reliable and guarantee maximum energy production. www.aros-solar.com thermal derating Derating as a function of temperature aimed to safeguard against overheating inverter semiconductors in the case of environments with temperatures exceeding installation specifications or for forced ventilation faults, without causing a complete block of the inverter itself. Sirio Central models ensure rated power output up to 45°C environment. If this threshold is exceeded, the inverter gradually decreases the power fed into the network in such a way as to maintain heat sink temperature within the maximum limit. Once back in the range of thermal normal operation, the inverter restores the optimal working point, again ensuring maximum power transfer. www.aros-solar.com easy installation and maintenance The footprint of these devices has been considerably reduced and there is no need to leave space at the side or back of the equipment since the electronics and power components are fully accessible from the front. Fully automatic operation ensures ease of use and facilitates installation and startup, thus avoiding installation and configuration errors which could lead to failures or reduced plant productivity. Personalized solutions AROS is able on request to supply Sirio Central inverters specific to the client’s needs. Available options include the integrated isolation control and the pole/ earth connection kit (positive or negative) that is required for some kinds of photovoltaic modules. certificate of Factory inspection Sirio Central inverters meet “Made in EU” criteria as they are designed, manufactured and tested in Italy. centRal inVeRteRs 49 02 48
  • 2. 50 02 Central Inverters User interface Sirio Central inverters provide a series of new user interfaces composed of an LCD colour touch screen in a convenient 4.3” format. The millions of colours and quantity of features greatly enrich the user’s interaction experience with the solar inverter. Intuitive icons and brief messages in the set language guide users through the simple menu structure, allowing them to access all reference, configuration and inverter control features. In particular, it is possible to view a daily energy production graph and the instantaneous value of power produced, verify module temperatures and the measurements of any installed analogue sensors. The archive section allows viewing and analysis of historical data, crossing measurements as desired (no longer two sizes at a time). By scrolling a finger along the screen, users can query values recorded in previous days, including in monthly or annual intervals, and the graphs displayed can be sent via e-mail. Internal storage allows for the archiving of about 10 years of data. However, if necessary, it is possible to delete older years by means of a special feature. Historical data produced by the inverter and that of the system card can be saved on a USB flash drive. The device also allows users to change the €/KWh ratio, adjust display brightness, change the system date and time, assign an identification and label to the plant it belongs to, configure and customise up to 4 external analogue sensors. It also allows e-mails to be sent (for which you can set the frequency) with production data and graphs and, in the case of abnormalities, any malfunction or ignition failure alarms. Finally, via special counters in the Info section, users can consult data regarding total produced energy, the overall hours of operation, the economic return of the plan and other technical parameters, including the amount of memory used for historical data. The graphic interface is available in Italian, English, French, Spanish and German. network access The touch screen device offers many communication possibilities if a connection to the local network exists. The inverter is compatible both with PVSER proprietary protocol on the network and with ModBUS/TCP, thus offering easy insertion in any management BMS or data analysis using an Ethernet network. The display software can be easily and quickly updated. Moreover, with a freeware software (VNC), users can remotely view the inverter screen or interact with it from their computer or mobile device. www.aros-solar.com
  • 3. 53 Sirio 12 CENTRaL INVERTERS gRiD connection cRiteRia The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity 14 kWp max 9 kWp min 12 kW 13,2 kW FeatURes colour: RAL 7035 555 Dimensions (WxDxh): 555x720x1400 mm Weight: 310 Kg Protection level: IP20 acoustic noise: <66dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 36 Adc 390 Vdc <1% 1 1 Screw terminals 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 17,3 Aac 22,4 Aac 34 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Screw terminals coMMUnication Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP 555 stanDaRDs eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 95,8% 94,8% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing 1400 555 (1) These values can vary according to the local regulations www.aros-solar.com 750 740 10 Approximate power of the photovoltaic field sirio K12 555 GRID MoDel www.aros-solar.com 02 02 centRal inVeRteRs 52
  • 4. 55 Sirio 15 CENTRaL INVERTERS gRiD connection cRiteRia The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity 18 kWp max 12 kWp min 15 kW 17 kW FeatURes colour: RAL 7035 555 Dimensions (WxDxh): 555x720x1400 mm Weight: 320 Kg Protection level: IP20 acoustic noise: <66dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 54 Adc 390 Vdc <1% 1 1 Screw terminals 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 21,7 Aac 28,1 Aac 42 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Screw terminals coMMUnication Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP 555 stanDaRDs eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 95,8% 94,8% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing 1400 555 (1) These values can vary according to the local regulations www.aros-solar.com 750 740 10 Approximate power of the photovoltaic field sirio K15 555 GRID MoDel www.aros-solar.com 02 02 centRal inVeRteRs 54
  • 5. 57 Sirio 18 CENTRaL INVERTERS gRiD connection cRiteRia The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity 21 kWp max 16 kWp min 18 kW 20 kW FeatURes colour: RAL 7035 555 Dimensions (WxDxh): 555x720x1400 mm Weight: 340 Kg Protection level: IP20 acoustic noise: <66dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 63 Adc 390 Vdc <1% 1 1 Screw terminals 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 26 Aac 33 Aac 50 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Screw terminals coMMUnication Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP 555 stanDaRDs eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 95,8% 94,8% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing 1400 555 (1) These values can vary according to the local regulations www.aros-solar.com 750 740 10 Approximate power of the photovoltaic field sirio K18 555 GRID MoDel www.aros-solar.com 02 02 centRal inVeRteRs 56
  • 6. 59 Sirio 25 and 25 HV CENTRaL INVERTERS The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Approximate power of the photovoltaic field Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K25 hV 30 kWp max 20 kWp min 25 kW 28 kW FeatURes colour: RAL 7035 555 Dimensions (WxDxh): 555x720x1400 mm Weight: 350 Kg Protection level: IP20 acoustic noise: <66dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 80 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 59 Adc 540 Vdc <1% 1 1 Screw terminals 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 36 Aac 46 Aac 68 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Screw terminals 95,8% 94,9% 750 740 coMMUnication Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) 10 gRiD connection cRiteRia sirio K25 Protocols: ModBUS and ModBUSTCP 555 stanDaRDs eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 1400 96,4% 95,3% 555 <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing GRID MoDels (1) These values can vary according to the local regulations www.aros-solar.com www.aros-solar.com 02 02 centRal inVeRteRs 58
  • 7. 61 Sirio 33 and 33 HV CENTRaL INVERTERS The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Approximate power of the photovoltaic field Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K33 hV 40 kWp max 30 kWp min 33 kW 36 kW FeatURes colour: RAL 7035 555 Dimensions (WxDxh): 555x720x1400 mm Weight: 380 Kg Protection level: IP20 acoustic noise: <66dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 105 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 79 Adc 540 Vdc <1% 1 1 Screw terminals 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 48 Aac 60 Aac 90 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Screw terminals 95,8% 94,9% 750 740 coMMUnication Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) 10 gRiD connection cRiteRia sirio K33 Protocols: ModBUS and ModBUSTCP 555 stanDaRDs eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 1400 96,3% 95,3% 555 <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing GRID MoDels (1) These values can vary according to the local regulations www.aros-solar.com www.aros-solar.com 02 02 centRal inVeRteRs 60
  • 8. 63 Sirio 40 and 40 HV CENTRaL INVERTERS The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Approximate power of the photovoltaic field Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K40 hV 50kWp max 36kWp min 40kW 44kW FeatURes colour: RAL 7035 555 Dimensions (WxDxh): 555x720x1400 mm Weight: 420 Kg Protection level: IP20 acoustic noise: <66dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 130 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 98 Adc 540 Vdc <1% 1 1 Screw terminals 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 58 Aac 73 Aac 110 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Screw terminals 95,8% 95% 750 740 coMMUnication Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) 10 gRiD connection cRiteRia sirio K40 Protocols: ModBUS and ModBUSTCP 555 stanDaRDs eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 1400 96,2% 95,3% 555 <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing GRID MoDels (1) These values can vary according to the local regulations www.aros-solar.com www.aros-solar.com 02 02 centRal inVeRteRs 62
  • 9. 65 Sirio 64 and 64 HV CENTRaL INVERTERS The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Approximate power of the photovoltaic field Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K64 hV 80 kWp max 55 kWp min 64 kW 71 kW FeatURes colour: RAL 7035 800 Dimensions (WxDxh): 800x800x1900 mm Weight: 600 Kg Protection level: IP20 810 797 acoustic noise: <68dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 205 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 157 Adc 540 Vdc <1% 1 1 Bar Display: Color LCD touch screen 800 communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP stanDaRDs 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 92 Aac 117 Aac 175 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Bar 96,1% 95% coMMUnication 13 gRiD connection cRiteRia sirio K64 eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC 800 96,1% 94,9% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing (1) These values can vary according to the local regulations www.aros-solar.com 1900 grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 GRID MoDels www.aros-solar.com 02 02 centRal inVeRteRs 64
  • 10. 67 Sirio 80 and 80 HV CENTRaL INVERTERS The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K80 hV 100 kWp max 70 kWp min 80 kW 88 kW FeatURes colour: RAL 7035 800 Dimensions (WxDxh): 800x800x1900 mm Weight: 650 Kg Protection level: IP20 810 797 acoustic noise: <68dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 260 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 196 Adc 540 Vdc <1% 1 1 Bar Display: Color LCD touch screen 800 communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP stanDaRDs 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 115 Aac 146 Aac 219 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Bar 96,1% 95% coMMUnication 13 gRiD connection cRiteRia Approximate power of the photovoltaic field Rated AC power Maximum AC power sirio K80 eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC 800 96,1% 95% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing (1) These values can vary according to the local regulations www.aros-solar.com 1900 grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 GRID MoDels www.aros-solar.com 02 02 centRal inVeRteRs 66
  • 11. 69 Sirio 100 and 100 H V CENTRaL INVERTERS The entire range can be configured according to the following standards: - CEI 0-21 - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K100 hV 125 kWp max 80 kWp min 100 kW 110 kW FeatURes colour: RAL 7035 800 Dimensions (WxDxh): 800x800x1900 mm Weight: 720 Kg Protection level: IP20 810 797 acoustic noise: <68dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 320 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 245 Adc 540 Vdc <1% 1 1 Bar Display: Color LCD touch screen 800 communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP stanDaRDs 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 145 Aac 182 Aac 274 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Bar 96,1% 95,1% coMMUnication 13 gRiD connection cRiteRia Approximate power of the photovoltaic field Rated AC power Maximum AC power sirio K100 eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC 800 96,1% 95,1% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing (1) These values can vary according to the local regulations www.aros-solar.com 1900 grid connection criteria: CEI 0-21, CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 GRID MoDels www.aros-solar.com 02 02 centRal inVeRteRs 68
  • 12. 71 Sirio 200 and 200 H V CENTRaL INVERTERS gRiD connection cRiteRia The entire range can be configured according to the following standards: - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) Approximate power of the photovoltaic field Rated AC power Maximum AC power inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity sirio K200 sirio K200 hV 250 kWp max 180 kWp min 200 kW 220 kW FeatURes colour: RAL 7035 13 Dimensions (WxDxh): 1630x1000x1900 mm 1010 997 Weight: 1580 Kg Protection level: IP20 acoustic noise: <72dBA 800 Vdc 330÷700 Vdc 330÷700 Vdc 650 Adc 390 Vdc 880 Vdc 450÷760 Vdc 450÷760 Vdc 500 Adc 540 Vdc <1% 1 1 Bar 1630 Display: Color LCD touch screen communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP stanDaRDs 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 289 Aac 364 Aac 546 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Bar 96,2% 95,2% coMMUnication 1630 eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 1900 1630 96,3% 95,2% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing GRID MoDels (1) These values can vary according to the local regulations www.aros-solar.com www.aros-solar.com 02 02 centRal inVeRteRs 70
  • 13. 73 Sirio 250 HV CENTRaL INVERTERS Approximate power of the photovoltaic field gRiD connection cRiteRia The entire range can be configured according to the following standards: - CEI 0-16 - VDE aR-N-4105 - VDE 0126-1-1 - G59/2 - Real Decreto 1663-2000 - PO12.3 oPtion on ReQUest - Pole/earth connection kit (positive or negative) - Overvoltage protection (SPD) sirio K250 hV Rated AC power Maximum AC power 320 kWp max 220 kWp min 250 kW 250 kW inPUt Maximum DC voltage in an open circuit MPPT operating range Working range Maximum input current Initial feeding voltage Ripple voltage Number of inputs MPPT number D.C. connectors 880 Vdc 450÷760 Vdc 450÷760 Vdc 590 Adc 540 Vdc <1% 1 1 Bar oUtPUt Operating voltage Operating interval Maximum power range Frequency range Settable frequency range Nominal current Maximum current Fault level contribution Current Harmonic Distorsion (THDi) Power factor Galvanic separation A.C. connectors sYsteM Maximum efficiency European efficiency Stand-by consumption Night consumption Internal protections Off-Grid protection Detecting earth leakage Heat dissipation Operating temperature Storage temperature Humidity FeatURes colour: RAL 7035 13 Dimensions (WxDxh): 1630x1000x1900 mm 1010 997 Weight: 1630 Kg Protection level: IP20 acoustic noise: <72dBA 400 Vac 340÷460 Vac (1) 340÷460 Vac 47,5÷51,5 Hz (1) 47÷53 Hz 361 Aac 420 Aac 630 Aac <3% from 0,9 ind. to 0,9 cap. (1) LF transformer Bar coMMUnication communication interface: Ethernet, USB, 2xRS232 as standard, RS485 optional (slot version) Protocols: ModBUS and ModBUSTCP stanDaRDs 1630 eMc: EN61000-6-3, EN61000-6-2, EN61000-3-11, EN61000-3-12 security: EN62109-1, EN62109-2 Directives: Low Voltage Directive: 2006/95/EC, EMC Directive: 2004/108/EC grid connection criteria: CEI 0-16, A70, VDE AR-N-4105, VDE 0126-1-1, G59/2, Real Decreto 1663-2000, PO12.3 1900 1630 96,3% 95,3% <32W <32W MCCB AC side, Switch DC side Yes Yes controlled fans 0°C÷45°C (without derating) -20°C÷70°C 0÷95% non-condensing (1) These values can vary according to the local regulations www.aros-solar.com 1630 Display: Color LCD touch screen GRID MoDel www.aros-solar.com 02 02 centRal inVeRteRs 72