SlideShare ist ein Scribd-Unternehmen logo
1 von 61
Power System Protection
    Fundamentals


What should we teach students
about power system protection?



                            Copyright © SEL 2008
Agenda

   Why protection is needed
   Principles and elements of the protection
    system
   Basic protection schemes
   Digital relay advantages and enhancements




                                           Copyright © SEL 2008
Disturbances: Light or Severe
   The power system must maintain acceptable
    operation 24 hours a day
       Voltage and frequency must stay within certain
        limits

   Small disturbances
       The control system can handle these
       Example: variation in transformer or generator load

   Severe disturbances require a protection
    system
       They can jeopardize the entire power system
       They cannot be overcome by a control system Copyright © SEL 2008
Power System Protection

Operation during severe disturbances:
      System element protection
      System protection
      Automatic reclosing
      Automatic transfer to alternate power
       supplies
      Automatic synchronization


                                               Copyright © SEL 2008
Electric Power System Exposure to
          External Agents




                               Copyright © SEL 2008
Damage to Main Equipment




                           Copyright © SEL 2008
Protection System


 A series of devices whose main purpose
 is to protect persons and primary electric
power equipment from the effects of faults



            The “Sentinels”




                                         Copyright © SEL 2008
Blackouts

    Characteristics            Main Causes
   Loss of service in a      Overreaction of the
    large area or              protection system
    population region
                              Bad design of the
   Hazard to human life       protection system
   May result in
    enormous economic
    losses


                                            Copyright © SEL 2008
Short Circuits Produce High
             Currents

                        Three-Phase Line
                                                     a
                                                     b
                                                     c
                             I

       Substation                     Fault


Thousands of Amps   I
                                    Wire

                                              Copyright © SEL 2008
Electrical Equipment Thermal Damage
                  t



        Damage                   Damage Curve
          Time




                                                 I
                      In   Imd   Short-Circuit
    Rated Value
                                   Current
                                                 Copyright © SEL 2008
Mechanical Damage During
                   Short Circuits
    Very destructive in busbars, isolators, supports,
     transformers, and machines
    Damage is instantaneous
 Mechanical
  Forces
         f1                   f2
    i1
                   i2

Rigid Conductors        f1(t) = k i1(t) i2(t)
                                                Copyright © SEL 2008
The Fuse




           Fuse




           Transformer




                  Copyright © SEL 2008
Protection System Elements

   Protective relays
   Circuit breakers
   Current and voltage transducers
   Communications channels
   DC supply system
   Control cables

                                  Copyright © SEL 2008
Three-Phase Diagram of the Protection
               Team




                                 Copyright © SEL 2008
DC Tripping Circuit




                      Copyright © SEL 2008
Circuit Breakers




                   Copyright © SEL 2008
Current Transformers




Very High Voltage CT
                       Medium-Voltage CT


                                  Copyright © SEL 2008
Voltage Transformers




                     Medium Voltage



               Note: Voltage transformers
               are also known as potential
High Voltage   transformers
                                    Copyright © SEL 2008
Protective Relays




                    Copyright © SEL 2008
Examples of Relay Panels




                        Microprocessor-
                         Based Relay

Old Electromechanical



                                  Copyright © SEL 2008
How Do Relays Detect Faults?
   When a fault takes place, the current, voltage,
    frequency, and other electrical variables
    behave in a peculiar way. For example:
       Current suddenly increases
       Voltage suddenly decreases

   Relays can measure the currents and the
    voltages and detect that there is an
    overcurrent, or an undervoltage, or a
    combination of both
   Many other detection principles determine the
    design of protective relays
                                             Copyright © SEL 2008
Main Protection Requirements
         Reliability
             Dependability
             Security
         Selectivity
         Speed
             System stability
             Equipment damage
             Power quality
         Sensitivity
             High-impedance faults
             Dispersed generation    Copyright © SEL 2008
Primary Protection




                     Copyright © SEL 2008
Primary Protection Zone Overlapping
 Protection
 Zone A
                    52      Protection
                            Zone B
   To Zone A
   Relays
                            To Zone B
                            Relays


 Protection
 Zone A
               52          Protection
                           Zone B
   To Zone A
   Relays                   To Zone B
                            Relays
                                 Copyright © SEL 2008
Backup Protection

                     Breaker 5
                       Fails
             C                   D
A                                              E

    1    2       5         6         11   12


             T
B                                              F

    3    4       7         8         9    10




                                               Copyright © SEL 2008
Typical Short-Circuit Type
          Distribution

Single-Phase-Ground:   70–80%
Phase-Phase-Ground:    17–10%
Phase-Phase:           10–8%
Three-Phase:           3–2%



                                Copyright © SEL 2008
Balanced vs.
      Unbalanced Conditions
                               Ia
Ic
                     Ic

              Ia



 Ib
                               Ib
Balanced System    Unbalanced System
                                Copyright © SEL 2008
Decomposition of an Unbalanced
           System




                           Copyright © SEL 2008
Power Line Protection Principles

    Overcurrent (50, 51, 50N, 51N)
    Directional Overcurrent (67, 67N)
    Distance (21, 21N)
    Differential (87)




                                      Copyright © SEL 2008
Application of Inverse-Type
          Relays
       Relay                     t
       Operation
       Time


I
            Radial Line


               Fault      Load

                                 Copyright © SEL 2008
Inverse-Time Relay Coordination


I


                            Distance
t


         }   ∆T   } ∆T    } ∆T
                            Distance
                             Copyright © SEL 2008
Addition of Instantaneous OC
           Element

         Relay                    t
       Operation
           Time


 I
            Radial Line


                   Fault   Load

                                      Copyright © SEL 2008
50/51 Relay Coordination


I



                           Distance
t


           } ∆T    } ∆T    } ∆T
                           Distance
                               Copyright © SEL 2008
Directional Overcurrent Protection
        Basic Applications




             K




              L

                              Copyright © SEL 2008
Directional Overcurrent Protection
                Basic Principle
                     V             I


           F2                            F1

                           Relay

      Reverse Fault (F2)               Forward Fault (F1)
  I
                                                     V

                      V                  I
                                                    Copyright © SEL 2008
Overcurrent Relay Problem

                                       E
                 I SETTING    ≈
                                Z S1 + (0.8) Z L1

 Relay     operates when the following condition
  holds:
                   I FAULT = I a > I SETTING

 As Z s1
        changes, the relay’s “reach” will change,
  since setting is fixed
                                               E
                 I FAULT ( LIMIT )   =
                                         ′
                                       Z S1 + (0.8) Z L1
                                                           Copyright © SEL 2008
Distance Relay Principle
                                          L
                        d
                    I a , Ib , Ic

                                                   Radial
                    21              Three-Phase
Va ,Vb ,Vc                                          Line
                                     Solid Fault




Suppose Relay Is Designed to Operate
When:
             | Va |≤ (0.8) | Z L1 || I a |
                                                   Copyright © SEL 2008
The Impedance Relay Characteristic

                R 2 + X 2 ≤ Z r21

                      X        Plain Impedance Relay
    Operation Zone

     Z ≤ Z r1                       Radius Zr1
                             Zr1

                                           R




                                                 Copyright © SEL 2008
Need for Directionality

        F2                F1
    1         2      3            4    5       6


    RELAY 3                   X
    Operation Zone
                                  F1

                         F2                R
Nonselective
Relay Operation

                                               Copyright © SEL 2008
Directionality Improvement
           F2                  F1
      1           2    3             4    5         6


  RELAY 3                  X
  Operation Zone                     Directional Impedance
                                F1   Relay Characteristic


                      F2                      R
The Relay Will
Not Operate for
This Fault
                                                     Copyright © SEL 2008
Mho Element Characteristic
(Directional Impedance Relay)

 Operates when:   V ≤ I Z M cos( ϕ − ϕ MT )
                  Z ≤ Z M cos( ϕ − ϕ MT )




                                            Copyright © SEL 2008
Three-Zone Distance Protection
Time

                               Zone 3
                     Zone 2
       Zone 1

       1         2     3        4    5    6




                                          Time
                Zone 1 Is Instantaneous
                                           Copyright © SEL 2008
Line Protection With Mho Elements
            X

                           C

                       B




               A
                               R
                   D


           E
                                   Copyright © SEL 2008
Circular Distance Relay Characteristics
      X               X
          PLAIN               OFFSET
          IMPEDANCE           MHO (2)

             R

                              R
                          X
      X
                              LENS
            MHO               (RESTRICTED MHO 1)



                 R                R

      X               X

          OFFSET              TOMATO
          MHO (1)             (RESTRICTED MHO 2)



                 R            R

                                        Copyright © SEL 2008
Semi-Plane Type Characteristics
    X                    X
           DIRECTIONAL
                                   RESTRICTED
                                   DIRECTIONAL

             R

                                   R
    X                        X

        REACTANCE                RESTRICTED
                                 REACTANCE


                  R                    R

    X                    X

                 OHM
                                 QUADRILATERAL

                  R
                                   R

                                           Copyright © SEL 2008
Distance Protection
                  Summary

   Current and voltage information
   Phase elements: more sensitive than 67
    elements
   Ground elements: less sensitive than
    67N elements
   Application: looped and parallel lines

                                        Copyright © SEL 2008
Directional Comparison
Pilot Protection Systems




                           Copyright © SEL 2008
Permissive Overreaching
     Transfer Trip




                          Copyright © SEL 2008
Basic POTT Logic


                             Key XMTR




Zone 2 Elements
                       AND                      Trip
          RCVR




                                        Copyright © SEL 2008
Directional Comparison
   Blocking Scheme




                         Copyright © SEL 2008
Basic DCB Logic


Zone 3                          Key XMTR

         Carrier Coordination

            Time Delay
               CC
Zone 2              0
                                    Trip
RCVR

                                     Copyright © SEL 2008
Differential Protection Principle

             Balanced CT Ratio

      CT                             CT
                Protected
                Equipment                 External
                                          Fault




                 50       IDIF = 0

No Relay Operation if CTs Are Considered Ideal
                                          Copyright © SEL 2008
Differential Protection Principle


    CTR                            CTR
            Protected
            Equipment
                  Internal
                    Fault


             50       IDIF > ISETTING


          Relay Operates
                                         Copyright © SEL 2008
Problem of Unequal CT Performance
             CT                          CT
                      Protected
                      Equipment               External
                                              Fault



                      50      IDIF ¹ 0

    False differential current can occur if a CT
     saturates during a through-fault
    Use some measure of through-current to
     desensitize the relay when high currents are
     present                                   Copyright © SEL 2008
Possible Scheme – Percentage
Differential Protection Principle
           ĪSP                         ĪRP
    CTR           Protected                  CTR
                  Equipment


             ĪS                   ĪR

                    Relay
                     (87)

     Compares:        I OP = I S + I R
                                   | IS | + | IR |
                      k ×I RT   =k×
                                          2          Copyright © SEL 2008
Differential Protection Applications
       Bus protection
       Transformer protection
       Generator protection
       Line protection
       Large motor protection
       Reactor protection
       Capacitor bank protection
       Compound equipment protection
                                        Copyright © SEL 2008
Differential Protection
                     Summary
   The overcurrent differential scheme is simple
    and economical, but it does not respond well to
    unequal current transformer performance
   The percentage differential scheme responds
    better to CT saturation
   Percentage differential protection can be
    analyzed in the relay and the alpha plane
   Differential protection is the best alternative
    selectivity/speed with present technology
                                                Copyright © SEL 2008
Multiple Input Differential Schemes
                             Examples

          Differential Protection Zone
                                              ĪSP                ĪRP



                                                    ĪT

     I1         I2     I3     I4
                                                         OP



Bus Differential: Several Inputs
                                         Three-Winding Transformer
                                          Differential: Three Inputs

                                                              Copyright © SEL 2008
Advantages of Digital Relays

                    Compatibility with
                                         Low maintenance
 Multifunctional    digital integrated
                                         (self-supervision)
                         systems



Highly sensitive,
                                           Highly reliable
  secure, and           Adaptive
                                         (self-supervision)
   selective



Reduced burden
                     Programmable
      on                                     Low Cost
                        Versatile
 CTs and VTs



                                                        Copyright © SEL 2008
Synchrophasors Provide a
“Snapshot” of the Power System




                           Copyright © SEL 2008
The Future
   Improvements in computer-based
    protection
   Highly reliable and viable communication
    systems (satellite, optical fiber, etc.)
   Integration of control, command,
    protection, and communication
   Improvements to human-machine
    interface
   Much more                          Copyright © SEL 2008

Weitere ähnliche Inhalte

Was ist angesagt?

RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfJayWin2
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordinationmichaeljmack
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Lineprotection basics june2008
Lineprotection basics june2008Lineprotection basics june2008
Lineprotection basics june2008lankeshdb
 
transmission-line-protection.ppt
transmission-line-protection.ppttransmission-line-protection.ppt
transmission-line-protection.pptssuser0132001
 
Over current Relays
Over current RelaysOver current Relays
Over current RelaysASWANTH6270
 
Protection settings calculation
Protection settings calculationProtection settings calculation
Protection settings calculationLANOGWA RODGERS
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...jbpatel7290
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection SystemHarshalJain48
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYRaviraj solanki
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zonesSlides Hub
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection Salim Palayi
 
Calculation of short circuit currents
Calculation of short circuit currents Calculation of short circuit currents
Calculation of short circuit currents Maria Romina Angustia
 

Was ist angesagt? (20)

Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 
RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdf
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Lineprotection basics june2008
Lineprotection basics june2008Lineprotection basics june2008
Lineprotection basics june2008
 
transmission-line-protection.ppt
transmission-line-protection.ppttransmission-line-protection.ppt
transmission-line-protection.ppt
 
Over current Relays
Over current RelaysOver current Relays
Over current Relays
 
Protection settings calculation
Protection settings calculationProtection settings calculation
Protection settings calculation
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection System
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Autoreclose
AutorecloseAutoreclose
Autoreclose
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection
 
Circuit Breaker
Circuit BreakerCircuit Breaker
Circuit Breaker
 
Calculation of short circuit currents
Calculation of short circuit currents Calculation of short circuit currents
Calculation of short circuit currents
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 

Ähnlich wie Protection primer

Protection primer
Protection primerProtection primer
Protection primerluonglt
 
protectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.pptprotectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.pptThien Phan Bản
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptxLecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptxssuserb444c3
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptThien Phan Bản
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptThien Phan Bản
 
Delta Sinewave Converter Overview
Delta Sinewave Converter   OverviewDelta Sinewave Converter   Overview
Delta Sinewave Converter OverviewDonald Nasca
 
Esd the broad impact and design challenges part2of2
Esd the broad impact and design challenges part2of2Esd the broad impact and design challenges part2of2
Esd the broad impact and design challenges part2of2ASQ Reliability Division
 
Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...IDES Editor
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.pptSalim Palayi
 
Power System Protection Technique: A Review
Power System Protection Technique: A ReviewPower System Protection Technique: A Review
Power System Protection Technique: A Reviewsahid raja khan
 
Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017
Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017
Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017Daniel Lang, P.Eng.
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guidePrasad RVS
 
Overcoming 25 year life reliability challenges in solar electronics
Overcoming 25 year life reliability challenges in solar electronicsOvercoming 25 year life reliability challenges in solar electronics
Overcoming 25 year life reliability challenges in solar electronicsGreg Caswell
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substationPanneerselvam Rathinam
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Dr. Rohit Babu
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. katoAgrey Kato
 

Ähnlich wie Protection primer (20)

Protection primer
Protection primerProtection primer
Protection primer
 
protectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.pptprotectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.ppt
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptxLecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
 
Delta Sinewave Converter Overview
Delta Sinewave Converter   OverviewDelta Sinewave Converter   Overview
Delta Sinewave Converter Overview
 
Esd the broad impact and design challenges part2of2
Esd the broad impact and design challenges part2of2Esd the broad impact and design challenges part2of2
Esd the broad impact and design challenges part2of2
 
Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
Power System Protection Technique: A Review
Power System Protection Technique: A ReviewPower System Protection Technique: A Review
Power System Protection Technique: A Review
 
Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017
Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017
Technical Brief_Quantifying Arcing Fault Damage_Rev0_30 Jan 2017
 
Transformer guide
Transformer guideTransformer guide
Transformer guide
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guide
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
Overcoming 25 year life reliability challenges in solar electronics
Overcoming 25 year life reliability challenges in solar electronicsOvercoming 25 year life reliability challenges in solar electronics
Overcoming 25 year life reliability challenges in solar electronics
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Adaptive Relaying,Report
Adaptive Relaying,ReportAdaptive Relaying,Report
Adaptive Relaying,Report
 

Kürzlich hochgeladen

The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxMalak Abu Hammad
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsMaria Levchenko
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...apidays
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...Neo4j
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?Antenna Manufacturer Coco
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxKatpro Technologies
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfsudhanshuwaghmare1
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessPixlogix Infotech
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)wesley chun
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking MenDelhi Call girls
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024The Digital Insurer
 

Kürzlich hochgeladen (20)

The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptx
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your Business
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024
 

Protection primer

  • 1. Power System Protection Fundamentals What should we teach students about power system protection? Copyright © SEL 2008
  • 2. Agenda  Why protection is needed  Principles and elements of the protection system  Basic protection schemes  Digital relay advantages and enhancements Copyright © SEL 2008
  • 3. Disturbances: Light or Severe  The power system must maintain acceptable operation 24 hours a day  Voltage and frequency must stay within certain limits  Small disturbances  The control system can handle these  Example: variation in transformer or generator load  Severe disturbances require a protection system  They can jeopardize the entire power system  They cannot be overcome by a control system Copyright © SEL 2008
  • 4. Power System Protection Operation during severe disturbances:  System element protection  System protection  Automatic reclosing  Automatic transfer to alternate power supplies  Automatic synchronization Copyright © SEL 2008
  • 5. Electric Power System Exposure to External Agents Copyright © SEL 2008
  • 6. Damage to Main Equipment Copyright © SEL 2008
  • 7. Protection System A series of devices whose main purpose is to protect persons and primary electric power equipment from the effects of faults The “Sentinels” Copyright © SEL 2008
  • 8. Blackouts Characteristics Main Causes  Loss of service in a  Overreaction of the large area or protection system population region  Bad design of the  Hazard to human life protection system  May result in enormous economic losses Copyright © SEL 2008
  • 9. Short Circuits Produce High Currents Three-Phase Line a b c I Substation Fault Thousands of Amps I Wire Copyright © SEL 2008
  • 10. Electrical Equipment Thermal Damage t Damage Damage Curve Time I In Imd Short-Circuit Rated Value Current Copyright © SEL 2008
  • 11. Mechanical Damage During Short Circuits  Very destructive in busbars, isolators, supports, transformers, and machines  Damage is instantaneous Mechanical Forces f1 f2 i1 i2 Rigid Conductors f1(t) = k i1(t) i2(t) Copyright © SEL 2008
  • 12. The Fuse Fuse Transformer Copyright © SEL 2008
  • 13. Protection System Elements  Protective relays  Circuit breakers  Current and voltage transducers  Communications channels  DC supply system  Control cables Copyright © SEL 2008
  • 14. Three-Phase Diagram of the Protection Team Copyright © SEL 2008
  • 15. DC Tripping Circuit Copyright © SEL 2008
  • 16. Circuit Breakers Copyright © SEL 2008
  • 17. Current Transformers Very High Voltage CT Medium-Voltage CT Copyright © SEL 2008
  • 18. Voltage Transformers Medium Voltage Note: Voltage transformers are also known as potential High Voltage transformers Copyright © SEL 2008
  • 19. Protective Relays Copyright © SEL 2008
  • 20. Examples of Relay Panels Microprocessor- Based Relay Old Electromechanical Copyright © SEL 2008
  • 21. How Do Relays Detect Faults?  When a fault takes place, the current, voltage, frequency, and other electrical variables behave in a peculiar way. For example:  Current suddenly increases  Voltage suddenly decreases  Relays can measure the currents and the voltages and detect that there is an overcurrent, or an undervoltage, or a combination of both  Many other detection principles determine the design of protective relays Copyright © SEL 2008
  • 22. Main Protection Requirements  Reliability  Dependability  Security  Selectivity  Speed  System stability  Equipment damage  Power quality  Sensitivity  High-impedance faults  Dispersed generation Copyright © SEL 2008
  • 23. Primary Protection Copyright © SEL 2008
  • 24. Primary Protection Zone Overlapping Protection Zone A 52 Protection Zone B To Zone A Relays To Zone B Relays Protection Zone A 52 Protection Zone B To Zone A Relays To Zone B Relays Copyright © SEL 2008
  • 25. Backup Protection Breaker 5 Fails C D A E 1 2 5 6 11 12 T B F 3 4 7 8 9 10 Copyright © SEL 2008
  • 26. Typical Short-Circuit Type Distribution Single-Phase-Ground: 70–80% Phase-Phase-Ground: 17–10% Phase-Phase: 10–8% Three-Phase: 3–2% Copyright © SEL 2008
  • 27. Balanced vs. Unbalanced Conditions Ia Ic Ic Ia Ib Ib Balanced System Unbalanced System Copyright © SEL 2008
  • 28. Decomposition of an Unbalanced System Copyright © SEL 2008
  • 29. Power Line Protection Principles  Overcurrent (50, 51, 50N, 51N)  Directional Overcurrent (67, 67N)  Distance (21, 21N)  Differential (87) Copyright © SEL 2008
  • 30. Application of Inverse-Type Relays Relay t Operation Time I Radial Line Fault Load Copyright © SEL 2008
  • 31. Inverse-Time Relay Coordination I Distance t } ∆T } ∆T } ∆T Distance Copyright © SEL 2008
  • 32. Addition of Instantaneous OC Element Relay t Operation Time I Radial Line Fault Load Copyright © SEL 2008
  • 33. 50/51 Relay Coordination I Distance t } ∆T } ∆T } ∆T Distance Copyright © SEL 2008
  • 34. Directional Overcurrent Protection Basic Applications K L Copyright © SEL 2008
  • 35. Directional Overcurrent Protection Basic Principle V I F2 F1 Relay Reverse Fault (F2) Forward Fault (F1) I V V I Copyright © SEL 2008
  • 36. Overcurrent Relay Problem E I SETTING ≈ Z S1 + (0.8) Z L1  Relay operates when the following condition holds: I FAULT = I a > I SETTING  As Z s1 changes, the relay’s “reach” will change, since setting is fixed E I FAULT ( LIMIT ) = ′ Z S1 + (0.8) Z L1 Copyright © SEL 2008
  • 37. Distance Relay Principle L d I a , Ib , Ic Radial 21 Three-Phase Va ,Vb ,Vc Line Solid Fault Suppose Relay Is Designed to Operate When: | Va |≤ (0.8) | Z L1 || I a | Copyright © SEL 2008
  • 38. The Impedance Relay Characteristic R 2 + X 2 ≤ Z r21 X Plain Impedance Relay Operation Zone Z ≤ Z r1 Radius Zr1 Zr1 R Copyright © SEL 2008
  • 39. Need for Directionality F2 F1 1 2 3 4 5 6 RELAY 3 X Operation Zone F1 F2 R Nonselective Relay Operation Copyright © SEL 2008
  • 40. Directionality Improvement F2 F1 1 2 3 4 5 6 RELAY 3 X Operation Zone Directional Impedance F1 Relay Characteristic F2 R The Relay Will Not Operate for This Fault Copyright © SEL 2008
  • 41. Mho Element Characteristic (Directional Impedance Relay) Operates when: V ≤ I Z M cos( ϕ − ϕ MT ) Z ≤ Z M cos( ϕ − ϕ MT ) Copyright © SEL 2008
  • 42. Three-Zone Distance Protection Time Zone 3 Zone 2 Zone 1 1 2 3 4 5 6 Time Zone 1 Is Instantaneous Copyright © SEL 2008
  • 43. Line Protection With Mho Elements X C B A R D E Copyright © SEL 2008
  • 44. Circular Distance Relay Characteristics X X PLAIN OFFSET IMPEDANCE MHO (2) R R X X LENS MHO (RESTRICTED MHO 1) R R X X OFFSET TOMATO MHO (1) (RESTRICTED MHO 2) R R Copyright © SEL 2008
  • 45. Semi-Plane Type Characteristics X X DIRECTIONAL RESTRICTED DIRECTIONAL R R X X REACTANCE RESTRICTED REACTANCE R R X X OHM QUADRILATERAL R R Copyright © SEL 2008
  • 46. Distance Protection Summary  Current and voltage information  Phase elements: more sensitive than 67 elements  Ground elements: less sensitive than 67N elements  Application: looped and parallel lines Copyright © SEL 2008
  • 47. Directional Comparison Pilot Protection Systems Copyright © SEL 2008
  • 48. Permissive Overreaching Transfer Trip Copyright © SEL 2008
  • 49. Basic POTT Logic Key XMTR Zone 2 Elements AND Trip RCVR Copyright © SEL 2008
  • 50. Directional Comparison Blocking Scheme Copyright © SEL 2008
  • 51. Basic DCB Logic Zone 3 Key XMTR Carrier Coordination Time Delay CC Zone 2 0 Trip RCVR Copyright © SEL 2008
  • 52. Differential Protection Principle Balanced CT Ratio CT CT Protected Equipment External Fault 50 IDIF = 0 No Relay Operation if CTs Are Considered Ideal Copyright © SEL 2008
  • 53. Differential Protection Principle CTR CTR Protected Equipment Internal Fault 50 IDIF > ISETTING Relay Operates Copyright © SEL 2008
  • 54. Problem of Unequal CT Performance CT CT Protected Equipment External Fault 50 IDIF ¹ 0  False differential current can occur if a CT saturates during a through-fault  Use some measure of through-current to desensitize the relay when high currents are present Copyright © SEL 2008
  • 55. Possible Scheme – Percentage Differential Protection Principle ĪSP ĪRP CTR Protected CTR Equipment ĪS ĪR Relay (87) Compares: I OP = I S + I R | IS | + | IR | k ×I RT =k× 2 Copyright © SEL 2008
  • 56. Differential Protection Applications  Bus protection  Transformer protection  Generator protection  Line protection  Large motor protection  Reactor protection  Capacitor bank protection  Compound equipment protection Copyright © SEL 2008
  • 57. Differential Protection Summary  The overcurrent differential scheme is simple and economical, but it does not respond well to unequal current transformer performance  The percentage differential scheme responds better to CT saturation  Percentage differential protection can be analyzed in the relay and the alpha plane  Differential protection is the best alternative selectivity/speed with present technology Copyright © SEL 2008
  • 58. Multiple Input Differential Schemes Examples Differential Protection Zone ĪSP ĪRP ĪT I1 I2 I3 I4 OP Bus Differential: Several Inputs Three-Winding Transformer Differential: Three Inputs Copyright © SEL 2008
  • 59. Advantages of Digital Relays Compatibility with Low maintenance Multifunctional digital integrated (self-supervision) systems Highly sensitive, Highly reliable secure, and Adaptive (self-supervision) selective Reduced burden Programmable on Low Cost Versatile CTs and VTs Copyright © SEL 2008
  • 60. Synchrophasors Provide a “Snapshot” of the Power System Copyright © SEL 2008
  • 61. The Future  Improvements in computer-based protection  Highly reliable and viable communication systems (satellite, optical fiber, etc.)  Integration of control, command, protection, and communication  Improvements to human-machine interface  Much more Copyright © SEL 2008