International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 147
CODAL COMPARISON OF IS-875 (PART 3) 1987 AND IS-875 (PART 3)
2015 FOR WIND ANALYSIS OF HIGH RISE BUILDING USING ETABS
Sreenidhi H M1, Shivaraju G D2, Dr. T V Mallesh³, S R Ramesh⁴
1M.Tech Student, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India
²Assistant Professor, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India
³Professor & Head, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India
⁴Professor, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India
---------------------------------------------------------------------***----------------------------------------------------------------------
Abstract - Buildings are constructed to provide shelter for
people and for commercial uses. Due to rapid increment in
population and higher rate of growth in industries there is a
large demand for land. In design practices, randomly varying
phenomenon is a wind which is having significant dynamic
effect on structures especially on flexible high rise building.
The main objective of this paper is to compare Indian
Standard code of practice for wind loads i.e. IS-875 (part 3)
1987and IS-875 (part 3) 2015 for dynamic loading on G+17
storey high rise building for zone 4 with terrain category 3
using ETABS software. It is performed on building to identify
the gust factor, lateral force, intensity, storey drift and
displacement, comparison of results which is obtained from
software after assigning the data along both “X” and “Y”
direction are plotted in graph i.e. storey level verses gust
factor, storey level verses lateral load, storey level verses
intensity, storey level verses storey drift, storey level verses
displacement.
Key Words: Dynamic effect, Gust factor, Lateral load,
Intensity, Storey drift, Displacement, High rise building,
IS-875 (part 3) 1987, IS-875 (part 3) 2015.
1. INTRODUCTION
In design practices, randomly varyingphenomenon
is a wind which is having significant dynamic effect on
structures especially on flexible high rise building. In
general, wind is considered for design of high rise building,
when a building comes in contact with wind both positive
and negative pressures will occurs simultaneously. The
building must have sufficient strength to resist thispressure
to prevent wind induced building failure
The nature of wind is very unpredictable, even for
the same locality the wind speeds are extremely different
and one may experience the effect of gusts lasting for few
seconds. In convection current the radiation results acts in
both direction i.e. upward and downward. Geographic
location and obstruction near the structures are some of the
factors on which the effect of wind on structure depends;
much variation may causes due to air flow and also
characteristics of building itself. For estimating dynamic
effect on high rise structures, most of international codes
and standards have utilized Gust Loading Factor (GLF). In
1967, Davenport was the first to introduce the concept of
GLF. Wind loading is a complex live loadwhichvariesbothin
space and time. In dynamic interactions it may occurs
between wind and structure. . Dynamic analysis of structure
is essential for tall, long span and slender buildings, wind
gust which causes fluctuation forces on structure whichalso
includes large dynamic motion and oscillations.
2. METHODOLOGY
1. Geometric and material properties are defined.
2. Support conditions, loadings are assignedandanalyseis
carried out.
3. Wind force for the structure is calculated.
4. Lateral (wind) forces are assigned in both “X” and “Y”
direction as per IS guidelines and analysis is carriedout.
3. DESIGN PARAMETER
BASIC WIND SPEED 47 M/SEC
ZONE IV
CITY DELHI
TERRAIN CATEGORY 3
CLASS C
4. MODEL
The Finite Element Model is created using ETABS software,
for performing structural analysis.
FIG 1: 3D model of G+17 building.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 148
FIG 2: Plan of the building.
5. LOAD CALCULATION
A. Dead Load (DL)
Self weight of the building (Slab, Beam & columns) is
automatically computed in the software. Floor Finish =
1.0kN/m2, Additional DL =0.5kN/m2 appliedasuniformarea
load on slabs.
B. Live Load (LL)
Live load on floors = 3kN/m²
(As per IS: 875 Part II)
C. Wind Load (WL)
I. IS: 875 (PART3) 1987:
a. Design wind speed (Vz):
Design wind speed is given by the equation
Vz = Vb K1 K2 K3
= 33.323m/sec.
Where,
Vb = 47m/sec (Basic wind speed in m/s)
K1 = 1, (Risk Coefficient)
K2 =0.709, (Terrain, height and structure size factor)
K3 = 1 (Topography factor)
Gust Factor as per IS-875 (part 3) 1987:
(Along “X” direction)
B = 0.78 (Back ground factor)
S = 0.054 (Size reduction factor)
E = 0.05 (Measure of available energy in the wind stream at
the natural frequency of the structure)
∅= This is considered only for the building heightislessthan
75m in terrain category 4 and height of the building is less
than 25m in terrain category 3 and for all other type of
building or structure it is considered as zero. Therefore∅=0.
= 0.016 (Damping coefficient)
G = 2.44 (Gust factor)
b. Wind load:
F= Cf Pz G Ae
= 143.15kN
Where,
Cf = 1.3, (Force coefficient)
Ae= 67.62m², (Effective frontal area)
Pz = 0.6 (Vz)² (Design wind pressure)
Pz = 0.66625 N/m²
G = 2.44 (Gust factor)
Gust Factor as per IS-875 (part 3) 1987:
(Along “Y” direction)
B = 0.78 (Back ground factor)
S = 0.047 (Size reduction factor)
E = 0.05 (Measure of available energy in the wind stream at
the natural frequency of the structure)
∅= This is considered only for the building heightislessthan
75m in terrain category 4 and height of the building is less
than 25m in terrain category 3 and for all other type of
building or structure it is considered as zero. Therefore∅=0.
= 0.016 (Damping coefficient)
G = 2.46 (Gust factor)
c. Wind load:
F= Cf Pz G Ae
= 140.82kN
Where,
Cf = 1.27, (Force coefficient)
Ae= 62.73m², (Effective frontal area)
Pz = 0.6 (Vz)² (Design wind pressure)
Pz = 0.66625 N/m²
G = 2.46 (Gust factor)
II. IS: 875 (PART 3) 2015:
a. Hourly mean wind speed (Vzh):
Vzd = Vzh k1 k3 k4
= 33.585m/sec
Where,
Vz = 47m/sec (Design wind speed at height z, in m/s)
k1 = 1 (Terrain, height and structural size factor)
k2 = 0.715 (Terrain roughness and height facto)
k3 = 1 (Topography factor)
k4 = 1 (Importance factor for the cyclonic region)
Gust Factor as per IS-875 (part 3) 2015:
(Along “X” direction)
Where,
r = 0.3605 (Roughness factor)
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 149
gv = 4 (peak factor for upwind velocity fluctuation, 3 for
category 1 and 2 terrains and 4 for category3and4terrains)
Bs =0.9 (Background factor)
= 0.342 (Factor to account for second order turbulence
intensity)
Hs = 2 (Height factor for resonance response)
g = 4.034 (Peak factor for resonant response)
S = 0.043 (Size reduction factor)
E = 0.038 (Spectrum of turbulence)
= 0.02 (Damping coefficient of the building or structure)
G = 2.922 (Gust factor)
b. Wind load:
F= Cf Pz G Ae
Where,
Cf = 1.3 (Force coefficient)
Ae= 67.62m² (Effective frontal area)
Pz =0.6 (Vzh)2 (Design wind pressure)
Pz = 0.676kN/m²
G = 2.922 (Gust factor)
Gust Factor as per IS-875 (part 3) 2015:
(Along “Y” direction)
Where,
r = 0.3606 (Roughness factor)
gv = 4 (peak factor for upwind velocity fluctuation, 3 for
category 1 and 2 terrains and 4 for category3and4terrains)
Bs =0.9 (Background factor)
= 0.342 (Factor to account for second order turbulence
intensity)
Hs = 2 (Height factor for resonance response)
g = 4.025 (Peak factor for resonant response)
S = 0.043 (Size reduction factor)
E = 0.039 (Spectrum of turbulence)
= 0.02 (Damping coefficient of the building or structure)
G = 2.943 (Gust factor)
c. Wind load:
F= Cf Pz G Ae
= 158.68kNz
Where,
Cf = 1.27 (Force coefficient)
Ae= 62.738m² (Effective frontal area)
Pz =0.6 (Vzh)2 (Design wind pressure)
Pz = 0.676kN/m²
G = 2.943 (Gust factor)
6. REVISION DETAILS IN NEW CODE
a. Aerodynamic roughness heights for each terrain
categories had been explicitly included, and are used to
derive turbulence depth and mean hourly wind seed
profiles.
b. The preceding type of structures into B class & C class
has been deleted and for that reason the k1 is renamed
as terrain roughness and height aspect.
c. The values of k2 factor similar to preceding class A type
structure are retained in this code.
d. An additional factor, termed as importance factor has
been introduced for cyclonic area.
e. Easy empirical expressions were recommended for
height variations of hourly mean wind speed and also
turbulence intensity in distinct terrains.
7. RESULTS AND DISCUSSION
Results and discussions of different parameter such as
Gust factor, Lateral force, Intensity, Storey Drift and
displacement are shown with the help of graphs.
Gust factor:
FIG 3: Variance in gust factor along “X” direction.
This gust effectiveness factor method is used to study the
criticality of wind loads for the design of tall buildings.Inthe
peak storey the gust factor along “X” direction for new code
is 2.922 where as in old code gust factor is 2.44. The
percentage of gust factor increase in new code when
compared with the old code is 19.56%. FIG 3: shows the
variance in the gust factor for both old and new code.
FIG 4: Variance in gust factor along “Y” direction.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 150
In the peak storey the gust factor in “Y” direction for new
code is 2.943 where as in old code gust factor is 2.461. The
percentage of gust factor increase in new code when
compared with the old code is 19.59%. FIG 4: shows the
variance in the gust factor for both old and new code.
Lateral load:
FIG 5: Variance in lateral force along “X” direction.
The Lateral force in the peak storey along “X” direction in
new code is 173.85kN where as in old code the lateral force
along “X” direction is 143.16kN. In lateral force the
percentage of increase in new code whencomparedwiththe
old code is 21.44%. FIG 5: shows the variance in lateral force
for both old and new code.
FIG 6: Variance in lateral force along “Y” direction.
The Lateral force in the peak storey along “Y” direction in
new code is 158.68kN where as in old code the lateral force
along “Y” direction is 140.82kN. In lateral force the
percentage of increase in new code whencomparedwiththe
old code is 12.68%. FIG 6: shows the varianceinlateral force
for both old and new code.
Intensity:
FIG 7: Variance in intensity along “X” direction.
In above table it is found that the intensity will increases
with the increase in the height of the structure. Intensity for
new code is 2.57kN/m² and intensity for old code is
2.12kN/m² i.e. 21.23 % of intensity has been increased and
consequence stress will be more in the new code FIG 7:
shows the variance in Intensity for both old and new code.
FIG 8: Variance in intensity along “Y” direction.
In above table it is found that the intensity will increases
with the increase in the height of the structure. Intensity for
new code is 2.53kN/m² and intensity for old code is
2.24kN/m² i.e. 12.95 % of intensity has been increased and
consequence stress will be more in the new code FIG 8:
shows the variance in Intensity for both old and new code.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 151
Storey drift:
FIG 9: Variance in storey drift along “X” direction.
Peak storey drift in old code storey drift along “X” direction
is 0.000444mm and in new code storey drift along “X”
direction is 0.000535mm.In storey drift the percentage of
increase in new code when compared with the old code is
20.50%. FIG 9: shows the variance in storey drift along “X”
direction.
FIG 10: Variance in storey drift along “Y” direction.
Peak storey drift in old code storey drift along “Y” direction
is 0.001045mm and in new code storey drift along “Y”
direction is 0.001165mm. In storey drift the percentage of
increase in new code when compared with the old code is
11.48%. FIG 10: shows the variance in storey drift along “Y”
direction.
Displacement:
FIG 11: Variance in displacement along “X” direction.
Peak storey displacement in old code storey drift along “X”
direction is 26.5mm and in new code storey drift along “X”
direction is 31.4mm.In storey displacement the percentage
of increase in new code when compared with the old code is
18.05%. FIG 11: shows the variance in storey displacement
along “X” direction.
FIG 12: Variance in displacement along “Y” direction.
Peak storey displacement in old code storey drift along “Y”
direction is 53.9mm and in new code storey drift along “Y”
direction is 59.3mm.In storey displacement the percentage
of increase in new code when compared with the old code is
10.39%. FIG 12: shows the variance in storey displacement
along “Y” direction.
8. CONCLUSIONS
From the obtained results we can concluded that:
1. Gust factor has been increased for [IS: 875 (Part 3)
2015] as compared to [IS: 875 (Part 3) 1987].
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 152
2. Lateral force has been increased as per the new code
[IS: 875 (Part 3) 2015] due to the increase in the gust
factor. Percentage increased is 21.44% along “X”
direction and 12.68% along “Y” direction.
3. Intensity has been increased as per the new code [IS:
875 (Part 3) 2015]. Percentage increased is 21.23%
along “X” direction and 12.95% along “Y” direction.
4. Displacement for the top most storey of G+17 storey
building as per new code 18.05% as been increased
along “X” direction and along “Y” direction as per new
code 10.39% as been increased in new code when
compared with old code
5. Storey drift for the top most storey of G+17 storey
building as per new code 20.50% along “X” direction as
been increased and along “Y” direction as per new code
11.48% as been increased in new code when compared
with old code
6. From the above results it can be concluded that new IS
Code [IS: 875 – (Part 3) – 2015] will provide high safety
to the structure for dynamicanalysisascomparedtoOld
IS Code because IS 875 (part 3): 2015 included
mathematical expressions fordifferentparameterssuch
as terrain factor (K2), background factor (Bs), size
reduction factor (S), roughness factor (r) etc.
REFERENCES
1. Alkesh Bhalerao (2016) “Effect of structural shape on
wind analysis of multi storied RCC structures”.
2. B. S. Mashalkar“ Effect of Plan Shapes ontheResponseof
Buildings Subjected To Wind Vibrations” IOSR Journal of
Mechanical and Civil Engineering (IOSR-JMCE)
3. MeghaKalra, S S S Purnima Bajpai and Dilpreet Singh
(2016) “Effect of Wind on Multi Storey Buildings of
Different Shapes”.
4. Md Ahesan, Md Hameed “Comparative Study on Wind
Load Analysis Using Different Standards” Vol. 7, Special
Issue 3, March 2018.
5. Ravindra Jori ,OmkarKamble, EklavyaSarnaik, Pooja
Niphade (IJETSRVolume 5, Issue 3 2018) “Gust analysis
of tall building by is 875(part3)-1987 and by ETABS
software”.
6. Shaikh Muffassir (2016) “Comparative Study on Wind
Analysis of Multi-story RCC and CompositeStructurefor
Different Plan Configuration”.
7. Srikanth and B Vamsi Krishna (2014) “Study on the
effect of gust loads on tall buildings” Vol. 3, No.3,August
2014 © 2014 IJSCER.
8. U. Dhiyaanesh (Volume 119 No. 16 2018) “Comparative
analysis of wind load on different non-circular shaped
buildings”.
9. Vikrant Trivedi “Wind Analysis and Design of G+11
Storied Building Using STAAD-Pro” International
Research Journal ofEngineeringandTechnology(IRJET)
e-ISSN: 2395-0056 Volume: 05 Issue: 03 Mar-2018.
10. Code of Practice for design loads for building and
structures, Part-3 wind loads IS-875 (PART-3) 1987.
Published by Bureau of Indian Standards.
11. Code of Practice for design loads for building and
structures, Part-3 wind loads IS-875 (PART-3) 2015.
Published by Bureau of Indian Standards.
BIOGRAPHIES
Sreenidhi H M
M.Tech student, Department of
Civil Engineering,SSIT,Tumakuru-
Karnataka, India
Shivaraju G D
Assistant Professor,Departmentof
Civil Engineering,SSIT,Tumakuru-
Karnataka, India
Dr. T V Mallesh
Professor & Head of Department,
Civil Engineering,SSIT,Tumakuru-
Karnataka, India
S R Ramesh
Professor, Department of Civil
Engineering, SSIT, Tumakuru-
Karnataka, India

Weitere ähnliche Inhalte

Was ist angesagt?

Depremyonetmeligiing
DepremyonetmeligiingDepremyonetmeligiing
Depremyonetmeligiing
__cyber__
 

Was ist angesagt? (20)

IRJET- Analysis of Irregular Structure under Linear Time History
IRJET- Analysis of Irregular Structure under Linear Time HistoryIRJET- Analysis of Irregular Structure under Linear Time History
IRJET- Analysis of Irregular Structure under Linear Time History
 
P-Delta Analysis in the Design of Tall RC Structures
P-Delta Analysis in the Design of Tall RC StructuresP-Delta Analysis in the Design of Tall RC Structures
P-Delta Analysis in the Design of Tall RC Structures
 
IRJET- Seismic Evaluation of RC Building Connected with and without Braced Fr...
IRJET- Seismic Evaluation of RC Building Connected with and without Braced Fr...IRJET- Seismic Evaluation of RC Building Connected with and without Braced Fr...
IRJET- Seismic Evaluation of RC Building Connected with and without Braced Fr...
 
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
 
Depremyonetmeligiing
DepremyonetmeligiingDepremyonetmeligiing
Depremyonetmeligiing
 
IRJET- Progressive Collapse of RCC Structure Due to Earthquake and Wind Load
IRJET-  Progressive Collapse of RCC Structure Due to Earthquake and Wind LoadIRJET-  Progressive Collapse of RCC Structure Due to Earthquake and Wind Load
IRJET- Progressive Collapse of RCC Structure Due to Earthquake and Wind Load
 
IRJET-Seismic Analysis of the Multistory Building Frames with different Geome...
IRJET-Seismic Analysis of the Multistory Building Frames with different Geome...IRJET-Seismic Analysis of the Multistory Building Frames with different Geome...
IRJET-Seismic Analysis of the Multistory Building Frames with different Geome...
 
Lf3519191924
Lf3519191924Lf3519191924
Lf3519191924
 
Seismic Evaluation of Multi-Storey Building using E-tabs
Seismic Evaluation of Multi-Storey Building using E-tabsSeismic Evaluation of Multi-Storey Building using E-tabs
Seismic Evaluation of Multi-Storey Building using E-tabs
 
IRJET- Evaluation of R.C. Multi-Storey Building Response under the Effect of ...
IRJET- Evaluation of R.C. Multi-Storey Building Response under the Effect of ...IRJET- Evaluation of R.C. Multi-Storey Building Response under the Effect of ...
IRJET- Evaluation of R.C. Multi-Storey Building Response under the Effect of ...
 
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratiosModal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
 
IRJET- Estimation of Ductility for High Rise Buildings for a Different Plan A...
IRJET- Estimation of Ductility for High Rise Buildings for a Different Plan A...IRJET- Estimation of Ductility for High Rise Buildings for a Different Plan A...
IRJET- Estimation of Ductility for High Rise Buildings for a Different Plan A...
 
Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...
Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...
Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...
 
Cost Analysis and Comparison of a Composite Diagrid Frame with Bare Frame und...
Cost Analysis and Comparison of a Composite Diagrid Frame with Bare Frame und...Cost Analysis and Comparison of a Composite Diagrid Frame with Bare Frame und...
Cost Analysis and Comparison of a Composite Diagrid Frame with Bare Frame und...
 
Analysis of a RCC frame Tall Structure using Staad Pro on Different Seismic Z...
Analysis of a RCC frame Tall Structure using Staad Pro on Different Seismic Z...Analysis of a RCC frame Tall Structure using Staad Pro on Different Seismic Z...
Analysis of a RCC frame Tall Structure using Staad Pro on Different Seismic Z...
 
Effect of Orientation on Response Spectrum Analysis of Plan Irregular Building
Effect of Orientation on Response Spectrum Analysis of Plan Irregular BuildingEffect of Orientation on Response Spectrum Analysis of Plan Irregular Building
Effect of Orientation on Response Spectrum Analysis of Plan Irregular Building
 
Comparision of Base Shear Capacity of RC Frame by IDA and SPA
Comparision of Base Shear Capacity of RC Frame by IDA and SPAComparision of Base Shear Capacity of RC Frame by IDA and SPA
Comparision of Base Shear Capacity of RC Frame by IDA and SPA
 
IRJET- Analysis of Steel Framed Structure using Steel Bracing System for ...
IRJET-  	  Analysis of Steel Framed Structure using Steel Bracing System for ...IRJET-  	  Analysis of Steel Framed Structure using Steel Bracing System for ...
IRJET- Analysis of Steel Framed Structure using Steel Bracing System for ...
 
Incremental Dynamic Analysis of RC Frames
Incremental Dynamic Analysis of RC FramesIncremental Dynamic Analysis of RC Frames
Incremental Dynamic Analysis of RC Frames
 
“Analysis and design of multi storeyed load bearing reinforced masonry struct...
“Analysis and design of multi storeyed load bearing reinforced masonry struct...“Analysis and design of multi storeyed load bearing reinforced masonry struct...
“Analysis and design of multi storeyed load bearing reinforced masonry struct...
 

Ähnlich wie IRJET- Codal Comparison of IS-875 (Part 3) 1987 and IS-875 (Part 3) 2015 for Wind Analysis of High Rise Building using ETabs

Ähnlich wie IRJET- Codal Comparison of IS-875 (Part 3) 1987 and IS-875 (Part 3) 2015 for Wind Analysis of High Rise Building using ETabs (20)

Dynamic Wind Analysis of High-Rise Building
Dynamic Wind Analysis of High-Rise BuildingDynamic Wind Analysis of High-Rise Building
Dynamic Wind Analysis of High-Rise Building
 
Wind Analysis and Design of G+11 Storied Building using STAAD-Pro
Wind Analysis and Design of G+11 Storied Building using STAAD-ProWind Analysis and Design of G+11 Storied Building using STAAD-Pro
Wind Analysis and Design of G+11 Storied Building using STAAD-Pro
 
Effects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildingsEffects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildings
 
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABSStudy of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
 
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
 
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
 
IRJET- Analysis of Diagrid Structure
IRJET-  	  Analysis of Diagrid StructureIRJET-  	  Analysis of Diagrid Structure
IRJET- Analysis of Diagrid Structure
 
IRJET- Effect of Bracing Pattern on the Most Structurally Stable Rectangular ...
IRJET- Effect of Bracing Pattern on the Most Structurally Stable Rectangular ...IRJET- Effect of Bracing Pattern on the Most Structurally Stable Rectangular ...
IRJET- Effect of Bracing Pattern on the Most Structurally Stable Rectangular ...
 
IRJET- Comparative Study of Performance of 60 Storey Steel Buildings with...
IRJET-  	  Comparative Study of Performance of 60 Storey Steel Buildings with...IRJET-  	  Comparative Study of Performance of 60 Storey Steel Buildings with...
IRJET- Comparative Study of Performance of 60 Storey Steel Buildings with...
 
IRJET- Analysis & Design of Industrial Building using Staad PRO
IRJET-  	  Analysis & Design of Industrial Building using Staad PROIRJET-  	  Analysis & Design of Industrial Building using Staad PRO
IRJET- Analysis & Design of Industrial Building using Staad PRO
 
IRJET- Effective Control of Response of a Building Under Wind Vibration using...
IRJET- Effective Control of Response of a Building Under Wind Vibration using...IRJET- Effective Control of Response of a Building Under Wind Vibration using...
IRJET- Effective Control of Response of a Building Under Wind Vibration using...
 
IRJET- Securing an IoT Based Home using Digital Image Processing and an Andro...
IRJET- Securing an IoT Based Home using Digital Image Processing and an Andro...IRJET- Securing an IoT Based Home using Digital Image Processing and an Andro...
IRJET- Securing an IoT Based Home using Digital Image Processing and an Andro...
 
IRJET- Effect of Bracing Pattern on the L Shape of RCC Tall Building due to W...
IRJET- Effect of Bracing Pattern on the L Shape of RCC Tall Building due to W...IRJET- Effect of Bracing Pattern on the L Shape of RCC Tall Building due to W...
IRJET- Effect of Bracing Pattern on the L Shape of RCC Tall Building due to W...
 
Critical Comparative Study of Dynamic Wind Response of Tall Buildings Using G...
Critical Comparative Study of Dynamic Wind Response of Tall Buildings Using G...Critical Comparative Study of Dynamic Wind Response of Tall Buildings Using G...
Critical Comparative Study of Dynamic Wind Response of Tall Buildings Using G...
 
IRJET- Design and Analysis of Residential Building
IRJET-  	  Design and Analysis of Residential BuildingIRJET-  	  Design and Analysis of Residential Building
IRJET- Design and Analysis of Residential Building
 
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODECOMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
 
P-Delta Effects on Tall RC Buildings with and Without Shear Wall
P-Delta Effects on Tall RC Buildings with and Without Shear WallP-Delta Effects on Tall RC Buildings with and Without Shear Wall
P-Delta Effects on Tall RC Buildings with and Without Shear Wall
 
Blast Resistant Buildings
Blast Resistant BuildingsBlast Resistant Buildings
Blast Resistant Buildings
 
Comparative Analysis of an RC framed building under Seismic Conditions
Comparative Analysis of an RC framed building under Seismic ConditionsComparative Analysis of an RC framed building under Seismic Conditions
Comparative Analysis of an RC framed building under Seismic Conditions
 
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
 

Mehr von IRJET Journal

Mehr von IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Kürzlich hochgeladen

Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 

Kürzlich hochgeladen (20)

Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 

IRJET- Codal Comparison of IS-875 (Part 3) 1987 and IS-875 (Part 3) 2015 for Wind Analysis of High Rise Building using ETabs

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 147 CODAL COMPARISON OF IS-875 (PART 3) 1987 AND IS-875 (PART 3) 2015 FOR WIND ANALYSIS OF HIGH RISE BUILDING USING ETABS Sreenidhi H M1, Shivaraju G D2, Dr. T V Mallesh³, S R Ramesh⁴ 1M.Tech Student, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India ²Assistant Professor, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India ³Professor & Head, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India ⁴Professor, Department of Civil Engineering, SSIT, Tumakuru-Karnataka, India ---------------------------------------------------------------------***---------------------------------------------------------------------- Abstract - Buildings are constructed to provide shelter for people and for commercial uses. Due to rapid increment in population and higher rate of growth in industries there is a large demand for land. In design practices, randomly varying phenomenon is a wind which is having significant dynamic effect on structures especially on flexible high rise building. The main objective of this paper is to compare Indian Standard code of practice for wind loads i.e. IS-875 (part 3) 1987and IS-875 (part 3) 2015 for dynamic loading on G+17 storey high rise building for zone 4 with terrain category 3 using ETABS software. It is performed on building to identify the gust factor, lateral force, intensity, storey drift and displacement, comparison of results which is obtained from software after assigning the data along both “X” and “Y” direction are plotted in graph i.e. storey level verses gust factor, storey level verses lateral load, storey level verses intensity, storey level verses storey drift, storey level verses displacement. Key Words: Dynamic effect, Gust factor, Lateral load, Intensity, Storey drift, Displacement, High rise building, IS-875 (part 3) 1987, IS-875 (part 3) 2015. 1. INTRODUCTION In design practices, randomly varyingphenomenon is a wind which is having significant dynamic effect on structures especially on flexible high rise building. In general, wind is considered for design of high rise building, when a building comes in contact with wind both positive and negative pressures will occurs simultaneously. The building must have sufficient strength to resist thispressure to prevent wind induced building failure The nature of wind is very unpredictable, even for the same locality the wind speeds are extremely different and one may experience the effect of gusts lasting for few seconds. In convection current the radiation results acts in both direction i.e. upward and downward. Geographic location and obstruction near the structures are some of the factors on which the effect of wind on structure depends; much variation may causes due to air flow and also characteristics of building itself. For estimating dynamic effect on high rise structures, most of international codes and standards have utilized Gust Loading Factor (GLF). In 1967, Davenport was the first to introduce the concept of GLF. Wind loading is a complex live loadwhichvariesbothin space and time. In dynamic interactions it may occurs between wind and structure. . Dynamic analysis of structure is essential for tall, long span and slender buildings, wind gust which causes fluctuation forces on structure whichalso includes large dynamic motion and oscillations. 2. METHODOLOGY 1. Geometric and material properties are defined. 2. Support conditions, loadings are assignedandanalyseis carried out. 3. Wind force for the structure is calculated. 4. Lateral (wind) forces are assigned in both “X” and “Y” direction as per IS guidelines and analysis is carriedout. 3. DESIGN PARAMETER BASIC WIND SPEED 47 M/SEC ZONE IV CITY DELHI TERRAIN CATEGORY 3 CLASS C 4. MODEL The Finite Element Model is created using ETABS software, for performing structural analysis. FIG 1: 3D model of G+17 building.
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 148 FIG 2: Plan of the building. 5. LOAD CALCULATION A. Dead Load (DL) Self weight of the building (Slab, Beam & columns) is automatically computed in the software. Floor Finish = 1.0kN/m2, Additional DL =0.5kN/m2 appliedasuniformarea load on slabs. B. Live Load (LL) Live load on floors = 3kN/m² (As per IS: 875 Part II) C. Wind Load (WL) I. IS: 875 (PART3) 1987: a. Design wind speed (Vz): Design wind speed is given by the equation Vz = Vb K1 K2 K3 = 33.323m/sec. Where, Vb = 47m/sec (Basic wind speed in m/s) K1 = 1, (Risk Coefficient) K2 =0.709, (Terrain, height and structure size factor) K3 = 1 (Topography factor) Gust Factor as per IS-875 (part 3) 1987: (Along “X” direction) B = 0.78 (Back ground factor) S = 0.054 (Size reduction factor) E = 0.05 (Measure of available energy in the wind stream at the natural frequency of the structure) ∅= This is considered only for the building heightislessthan 75m in terrain category 4 and height of the building is less than 25m in terrain category 3 and for all other type of building or structure it is considered as zero. Therefore∅=0. = 0.016 (Damping coefficient) G = 2.44 (Gust factor) b. Wind load: F= Cf Pz G Ae = 143.15kN Where, Cf = 1.3, (Force coefficient) Ae= 67.62m², (Effective frontal area) Pz = 0.6 (Vz)² (Design wind pressure) Pz = 0.66625 N/m² G = 2.44 (Gust factor) Gust Factor as per IS-875 (part 3) 1987: (Along “Y” direction) B = 0.78 (Back ground factor) S = 0.047 (Size reduction factor) E = 0.05 (Measure of available energy in the wind stream at the natural frequency of the structure) ∅= This is considered only for the building heightislessthan 75m in terrain category 4 and height of the building is less than 25m in terrain category 3 and for all other type of building or structure it is considered as zero. Therefore∅=0. = 0.016 (Damping coefficient) G = 2.46 (Gust factor) c. Wind load: F= Cf Pz G Ae = 140.82kN Where, Cf = 1.27, (Force coefficient) Ae= 62.73m², (Effective frontal area) Pz = 0.6 (Vz)² (Design wind pressure) Pz = 0.66625 N/m² G = 2.46 (Gust factor) II. IS: 875 (PART 3) 2015: a. Hourly mean wind speed (Vzh): Vzd = Vzh k1 k3 k4 = 33.585m/sec Where, Vz = 47m/sec (Design wind speed at height z, in m/s) k1 = 1 (Terrain, height and structural size factor) k2 = 0.715 (Terrain roughness and height facto) k3 = 1 (Topography factor) k4 = 1 (Importance factor for the cyclonic region) Gust Factor as per IS-875 (part 3) 2015: (Along “X” direction) Where, r = 0.3605 (Roughness factor)
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 149 gv = 4 (peak factor for upwind velocity fluctuation, 3 for category 1 and 2 terrains and 4 for category3and4terrains) Bs =0.9 (Background factor) = 0.342 (Factor to account for second order turbulence intensity) Hs = 2 (Height factor for resonance response) g = 4.034 (Peak factor for resonant response) S = 0.043 (Size reduction factor) E = 0.038 (Spectrum of turbulence) = 0.02 (Damping coefficient of the building or structure) G = 2.922 (Gust factor) b. Wind load: F= Cf Pz G Ae Where, Cf = 1.3 (Force coefficient) Ae= 67.62m² (Effective frontal area) Pz =0.6 (Vzh)2 (Design wind pressure) Pz = 0.676kN/m² G = 2.922 (Gust factor) Gust Factor as per IS-875 (part 3) 2015: (Along “Y” direction) Where, r = 0.3606 (Roughness factor) gv = 4 (peak factor for upwind velocity fluctuation, 3 for category 1 and 2 terrains and 4 for category3and4terrains) Bs =0.9 (Background factor) = 0.342 (Factor to account for second order turbulence intensity) Hs = 2 (Height factor for resonance response) g = 4.025 (Peak factor for resonant response) S = 0.043 (Size reduction factor) E = 0.039 (Spectrum of turbulence) = 0.02 (Damping coefficient of the building or structure) G = 2.943 (Gust factor) c. Wind load: F= Cf Pz G Ae = 158.68kNz Where, Cf = 1.27 (Force coefficient) Ae= 62.738m² (Effective frontal area) Pz =0.6 (Vzh)2 (Design wind pressure) Pz = 0.676kN/m² G = 2.943 (Gust factor) 6. REVISION DETAILS IN NEW CODE a. Aerodynamic roughness heights for each terrain categories had been explicitly included, and are used to derive turbulence depth and mean hourly wind seed profiles. b. The preceding type of structures into B class & C class has been deleted and for that reason the k1 is renamed as terrain roughness and height aspect. c. The values of k2 factor similar to preceding class A type structure are retained in this code. d. An additional factor, termed as importance factor has been introduced for cyclonic area. e. Easy empirical expressions were recommended for height variations of hourly mean wind speed and also turbulence intensity in distinct terrains. 7. RESULTS AND DISCUSSION Results and discussions of different parameter such as Gust factor, Lateral force, Intensity, Storey Drift and displacement are shown with the help of graphs. Gust factor: FIG 3: Variance in gust factor along “X” direction. This gust effectiveness factor method is used to study the criticality of wind loads for the design of tall buildings.Inthe peak storey the gust factor along “X” direction for new code is 2.922 where as in old code gust factor is 2.44. The percentage of gust factor increase in new code when compared with the old code is 19.56%. FIG 3: shows the variance in the gust factor for both old and new code. FIG 4: Variance in gust factor along “Y” direction.
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 150 In the peak storey the gust factor in “Y” direction for new code is 2.943 where as in old code gust factor is 2.461. The percentage of gust factor increase in new code when compared with the old code is 19.59%. FIG 4: shows the variance in the gust factor for both old and new code. Lateral load: FIG 5: Variance in lateral force along “X” direction. The Lateral force in the peak storey along “X” direction in new code is 173.85kN where as in old code the lateral force along “X” direction is 143.16kN. In lateral force the percentage of increase in new code whencomparedwiththe old code is 21.44%. FIG 5: shows the variance in lateral force for both old and new code. FIG 6: Variance in lateral force along “Y” direction. The Lateral force in the peak storey along “Y” direction in new code is 158.68kN where as in old code the lateral force along “Y” direction is 140.82kN. In lateral force the percentage of increase in new code whencomparedwiththe old code is 12.68%. FIG 6: shows the varianceinlateral force for both old and new code. Intensity: FIG 7: Variance in intensity along “X” direction. In above table it is found that the intensity will increases with the increase in the height of the structure. Intensity for new code is 2.57kN/m² and intensity for old code is 2.12kN/m² i.e. 21.23 % of intensity has been increased and consequence stress will be more in the new code FIG 7: shows the variance in Intensity for both old and new code. FIG 8: Variance in intensity along “Y” direction. In above table it is found that the intensity will increases with the increase in the height of the structure. Intensity for new code is 2.53kN/m² and intensity for old code is 2.24kN/m² i.e. 12.95 % of intensity has been increased and consequence stress will be more in the new code FIG 8: shows the variance in Intensity for both old and new code.
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 151 Storey drift: FIG 9: Variance in storey drift along “X” direction. Peak storey drift in old code storey drift along “X” direction is 0.000444mm and in new code storey drift along “X” direction is 0.000535mm.In storey drift the percentage of increase in new code when compared with the old code is 20.50%. FIG 9: shows the variance in storey drift along “X” direction. FIG 10: Variance in storey drift along “Y” direction. Peak storey drift in old code storey drift along “Y” direction is 0.001045mm and in new code storey drift along “Y” direction is 0.001165mm. In storey drift the percentage of increase in new code when compared with the old code is 11.48%. FIG 10: shows the variance in storey drift along “Y” direction. Displacement: FIG 11: Variance in displacement along “X” direction. Peak storey displacement in old code storey drift along “X” direction is 26.5mm and in new code storey drift along “X” direction is 31.4mm.In storey displacement the percentage of increase in new code when compared with the old code is 18.05%. FIG 11: shows the variance in storey displacement along “X” direction. FIG 12: Variance in displacement along “Y” direction. Peak storey displacement in old code storey drift along “Y” direction is 53.9mm and in new code storey drift along “Y” direction is 59.3mm.In storey displacement the percentage of increase in new code when compared with the old code is 10.39%. FIG 12: shows the variance in storey displacement along “Y” direction. 8. CONCLUSIONS From the obtained results we can concluded that: 1. Gust factor has been increased for [IS: 875 (Part 3) 2015] as compared to [IS: 875 (Part 3) 1987].
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 08 | Aug 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.34 | ISO 9001:2008 Certified Journal | Page 152 2. Lateral force has been increased as per the new code [IS: 875 (Part 3) 2015] due to the increase in the gust factor. Percentage increased is 21.44% along “X” direction and 12.68% along “Y” direction. 3. Intensity has been increased as per the new code [IS: 875 (Part 3) 2015]. Percentage increased is 21.23% along “X” direction and 12.95% along “Y” direction. 4. Displacement for the top most storey of G+17 storey building as per new code 18.05% as been increased along “X” direction and along “Y” direction as per new code 10.39% as been increased in new code when compared with old code 5. Storey drift for the top most storey of G+17 storey building as per new code 20.50% along “X” direction as been increased and along “Y” direction as per new code 11.48% as been increased in new code when compared with old code 6. From the above results it can be concluded that new IS Code [IS: 875 – (Part 3) – 2015] will provide high safety to the structure for dynamicanalysisascomparedtoOld IS Code because IS 875 (part 3): 2015 included mathematical expressions fordifferentparameterssuch as terrain factor (K2), background factor (Bs), size reduction factor (S), roughness factor (r) etc. REFERENCES 1. Alkesh Bhalerao (2016) “Effect of structural shape on wind analysis of multi storied RCC structures”. 2. B. S. Mashalkar“ Effect of Plan Shapes ontheResponseof Buildings Subjected To Wind Vibrations” IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) 3. MeghaKalra, S S S Purnima Bajpai and Dilpreet Singh (2016) “Effect of Wind on Multi Storey Buildings of Different Shapes”. 4. Md Ahesan, Md Hameed “Comparative Study on Wind Load Analysis Using Different Standards” Vol. 7, Special Issue 3, March 2018. 5. Ravindra Jori ,OmkarKamble, EklavyaSarnaik, Pooja Niphade (IJETSRVolume 5, Issue 3 2018) “Gust analysis of tall building by is 875(part3)-1987 and by ETABS software”. 6. Shaikh Muffassir (2016) “Comparative Study on Wind Analysis of Multi-story RCC and CompositeStructurefor Different Plan Configuration”. 7. Srikanth and B Vamsi Krishna (2014) “Study on the effect of gust loads on tall buildings” Vol. 3, No.3,August 2014 © 2014 IJSCER. 8. U. Dhiyaanesh (Volume 119 No. 16 2018) “Comparative analysis of wind load on different non-circular shaped buildings”. 9. Vikrant Trivedi “Wind Analysis and Design of G+11 Storied Building Using STAAD-Pro” International Research Journal ofEngineeringandTechnology(IRJET) e-ISSN: 2395-0056 Volume: 05 Issue: 03 Mar-2018. 10. Code of Practice for design loads for building and structures, Part-3 wind loads IS-875 (PART-3) 1987. Published by Bureau of Indian Standards. 11. Code of Practice for design loads for building and structures, Part-3 wind loads IS-875 (PART-3) 2015. Published by Bureau of Indian Standards. BIOGRAPHIES Sreenidhi H M M.Tech student, Department of Civil Engineering,SSIT,Tumakuru- Karnataka, India Shivaraju G D Assistant Professor,Departmentof Civil Engineering,SSIT,Tumakuru- Karnataka, India Dr. T V Mallesh Professor & Head of Department, Civil Engineering,SSIT,Tumakuru- Karnataka, India S R Ramesh Professor, Department of Civil Engineering, SSIT, Tumakuru- Karnataka, India