SlideShare ist ein Scribd-Unternehmen logo
1 von 8
Downloaden Sie, um offline zu lesen
International Journal of Engineering Science Invention
ISSN (Online): 2319 – 6734, ISSN (Print): 2319 – 6726
www.ijesi.org Volume 2 Issue 10ǁ October 2013 ǁ PP.48-55

Improved Method for Winding Deformation Detection Sensitivity
in Transformer
Arivamudhan M, Santhi S*
Department of Instrumentation Engineering, Annamalai University, Annamalai Nagar, Tamil Nadu India.

ABSTRACT : Power transformers are one of the most vital as well as expensive equipment in an electric
power system. Transformers may be subjected to various types of faults. Of these, the structural fault namely the
winding deformation due to either dynamic effect of short circuit current or vibration during transportation or
due to short circuit in nearby equipments is severe and needs attentive condition monitoring. The fault may
cause a change in the physical condition of transformer which would reflect as variation in the electrical
parameters- resistance, inductance and capacitance of the winding. Detection of winding deformation is
possible by observing the variation in characteristic resonant frequency of winding due to change in electrical
parameters as a result of winding deformation. This paper aims at detection of winding deformation with
improvement in detection sensitivity by the use of different test input signal. The proposed method is validated
through simulation using lumped parameter model of a transformer winding.

KEYWORDS : Transformer, winding deformation, Lightning impulse, detection sensitivity
I.

INTRODUCTION

Transformers are a critical and expensive component of the power system. Failure of a transformer
may be potentially severe and may affect safety of personnel and the environment. Due to the long time for
repair and replacement of transformers, a major goal of transformer protection is limiting the damage of a
transformer that has experienced a fault condition. This necessitates that monitoring and diagnostic methods be
developed at various stages starting from design, testing, commissioning and during operation.As windings are
the heart of the transformer, assessing the integrity of the winding becomes an essential task. The structural
integrity of the winding is sought to be ensured by short circuit tests. The winding deformation in transformers
may occur either when the transformer is subjected to short circuit test or during transportation or due to ageing
[1].The objective of the short circuit test is to assess the capability of winding to withstand thermal and
dynamic effects caused by the short circuit current, which can be many times full load current [2]. From
manufacturing view point the test is important part in continually improving design [3]. Details regarding the
test current magnitude, the frequency of the test supply, the number of tests to be conducted, the test procedure
and the detection of faults and evaluation of test results are documented in standards such as IEC 60076 Part
V, 2000 [4]. The ability to withstand the dynamic effects of short circuit shall be demonstrated if required by
the consumer, either by tests or by calculation and design consideration. Conventionally reactance
measurement was utilized as a diagnostic tool to indicate whether the transformer has passed the test. A
method based on cycle to cycle impedance measurement has also been proposed [5]. Determination of transfer
function for winding deformation detection using low voltage impulse (LVI) method was proposed in [6],[7]
and use of LVI for detection of impulse faults have been proposed in [8],[9]. In this paper a method of winding
deformation detection that employs a different test input for improving the detection sensitivity is proposed and
validated.
II.
CAUSES OF WINDING DEFORMATION IN TRANSFORMER
Most of the failures are caused by transformer winding faults and the faults are generated by lightning
and switching surges. As a transformer experiences a fault, it may suffer mechanical shock that gradually
displaces and distorts the windings [10]. In the process of winding movement the insulation between the turns
can be abraded causing a short circuit and damage to the windings. Mechanical vibration initiated by short
circuit forces causes loosening of clamping pressure and collapse winding. The other causes of winding
movement may be extensive vibration during transformer transportation.As the winding experiences vibrations
it may slacken and subsequently becomes unable to withstand mechanical forces exerted during faults. Ageing
also contributes to winding looseness.

www.ijesi.org

48 | Page
Improved Method For Winding

In addition harmonics generated under normal operating conditions may cause winding and core
vibration. Short circuit forces are potentially very destructive because if the clamping pressure is not capable
of restraining the forces involved, substantial permanent winding deformation or collapse can occur almost
instantaneously often accompanied by shorted turns. During short circuit condition the axial and radial fluxes in
the air gap interact with the short circuit current and produce the short circuit forces that tend to deform the
winding. Since windings are characterized by their resonant frequencies, the deformation in windings can be
detected by observing changes in resonant frequency as a result of change in electrical parameter.

III.

PROBLEM FORMULATION

In general large power transformers are validated for their short circuit withstand capability through
short circuit test. As mentioned in the procedure, the short circuit test is performed by short circuiting the low
voltage winding and exciting the high voltage winding. In the existing low voltage impulse (LVI) method of
winding deformation detection, low voltage impulse is applied to the HV winding and the winding current
through it is observed. The winding deformation that may occur due to high short circuit current results in shift
in natural resonant frequencies of the winding.Since low voltage impulse signal in frequency domain indicates
that the amplitude decreases monotonically with increase in frequency, the winding deformation detection may
not be possible with good sensitivity if the resonant frequency lies in the high frequency region. Hence a
different test input is required for winding deformation detection for improvement in detection sensitivity. This
paper emerged to seek for a solution to this problem.

IV.

TEST SIGNAL FOR IMPROVEMENT IN DETECTION SENSITIVITY

The low voltage impulse excitation that is similar to standard lightning impulse (LI) of 1V, 1.2/50”s
front time and fall time respectively is initially defined as the test signal to simulate the lumped parameter model
of a transformer winding. Fig.1 shows the lightning impulse excitation (LI) in time domain defined in the circuit
simulation package.

Fig.1 LI excitation in time domain
The LI excitation signal is exported to Matlab package to determine its characteristics in frequency
domain and the same is shown in Fig.2. It is observed from Fig.2 that the magnitude of LI excitation decreases
monotonically as the frequency is increased. Based on the frequency response measurement concept the input
signal magnitude is to be kept constant and as the input signal’s frequency is increased, the response of DUT is
to be observed to study the frequency domain characteristics. Application of LI to determine the frequency
response may not provide the necessary constant input excitation at all frequencies of measurement.

Fig. 2 LI excitation in frequency domain

www.ijesi.org

49 | Page
Improved Method For Winding

In order to overcome this problem, a different excitation namely oscillating impulse (OLI) has been
proposed as described below. The OLI is generated by super imposing with a standard LI, a sinusoidal signal
with frequency equal to the resonant frequency of the winding. The resonant frequencies of the winding exhibits
shift in frequency domain as a result of winding deformation. In case if the resonant frequency happens to be in
the order of hundreds of KHz, the LI excitation may not indicate the same with good sensitivity. Where as if
OLI in which the sinusoidal frequency is defined to be the resonant frequency of interest then that frequency
component can be observed with better sensitivity. Fig.3 shows the OLI excitation in which sinusoidal signal of
27 KHz is super imposed with LI. Fig.4 shows the OLI excitation in frequency domain indicating dominantly
27 KHz frequency component.

Fig.3 OLI excitation in time domain
From Fig.4, it is observed that the resonant frequency of interest could be studied with input having
magnitude not in the noise region and there by improvement in detection sensitivity.

Fig.4 OLI excitation in frequency domain

V.

DEVICE UNDER TEST (DUT)

In order to demonstrate the method that improves detection sensitivity, a transformer winding model is
essential, to carry out the simulation. The simulation work requires a lumped parameter model of the
transformer winding that needs to be considered as the device under test. The model parameters of layer
winding and interleaved winding as mentioned in [11] have been used to carry out the simulation.
The parameters of the interleaved winding (DUT 1) are as given below
Inductance of each section
=0.5mH
Ground capacitance of each section =0.4nF
Series capacitance of each section =12.8nF

www.ijesi.org

50 | Page
Improved Method For Winding

The parameters of the layer winding (DUT 2) are as given below
Inductance of each section
=0.5mH
Ground capacitance of each section =0.4nF
Series capacitance of each section =0.1nF
The mutual inductances for both interleaved and layer windings are M 1-2=0.25mH, M1-3=0.167mH, M1M1-6=0.0833mH, M1-7=0.071mH,
M1-8=0.0625mH, M1-9=0.0556mH, M14=0.125mH, M1-5=0.10mH,
M1-3= M2-4= M3-5

.= M8-10. M1-4= M2-5= M1-2= M310=0.050mH and M1-2= M2-3= M3-4


= M9-10,
6

..= M7-10 and so on. Figure 5 shows the ten section lumped parameter model of a transformer winding in
general.

Fig. 5 Ten section lumped parameter model
VI.
RESULTS AND DISCUSSION
The validation of proposed method is achieved through simulation of lumped parameter model of
winding using LI and OLI excitations. In this regard, the lumped parameter model of interleaved winding
(DUT1) is simulated to record the winding current using LI excitation. The winding current Iw through a current
viewing resistor R as shown in Fig.5 is analyzed in frequency domain using MATLAB software. The winding
current of DUT1 when LI excitation applied is shown in Fig.6 and the corresponding frequency domain
response is shown in Fig.7.

Fig.6 Response of DUT 1 with LI excitation

Fig.7 Winding current of DUT 1 in frequency domain with LI excitation

www.ijesi.org

51 | Page
Improved Method For Winding

The resonant frequencies of DUT 1 with LI excitation are tabulated in Table 1. Next the winding
current of DUT 1 with OLI excitation (LI super imposed with sinusoidal signal frequency of 37 KHz) applied is
recorded and its frequency domain response is shown in Fig.8. Table 1 indicates resonant frequencies of DUT 1
with OLI excitation.
Table. 1 Resonant frequencies of DUT 1 with LI and OLI excitation
Excitation
LI

OLI

Resonant frequency in
KHz
29
35
37
39
29
35
37
39

Magnitude in
dB
-10.19
-23.70
-23.97
-25.29
-3.986
-7.389
2.815
-16.05

It is observed from Table I that the resonant frequency of interest (37 KHz) could be observed with
higher magnitude (2.815 dB) than its corresponding value (-23.97 dB) with LI excitation.

Fig.8 Response of DUT 1 with OLI excitation
The frequency response of interleaved winding model shows only four resonant frequencies in the
order of tens of KHz. It would be better if the method is demonstrated for a model that has resonant frequencies
occurring in high frequency region which is more prone to noise.

Fig.9 Winding current of DUT 2 in time domain with LI excitation

www.ijesi.org

52 | Page
Improved Method For Winding


Fig.10 Winding current of DUT 2 in frequency domain with LI excitation
The simulation of lumped parameter model with LI and OLI excitation is repeated for the case of
DUT 2.Winding current of DUT 2 when LI excitation applied is shown in Fig.9 and the same in frequency
domain is shown in Fig.10. The resonant frequencies of DUT 2 are tabulated in Table 2. Consider the resonant
frequency 284 KHz with magnitude -20.87 dB. To observe the effectiveness of OLI excitation to this resonant
frequency the winding current of DUT 2 with OLI excitation (LI super imposed with sinusoidal signal
frequency of 284 KHz) applied is recorded and its response in frequency domain is shown in Fig.11. Table 2
indicates resonant frequencies of DUT 2 with OLI excitation.
Table. 2 Resonant frequencies of DUT 2 with LI and OLI excitation
Excitation

LI

OLI

Resonant frequency in KHz
58
119
175
221
257
284
303
316
323
58
119
175
221
257
284
303
316
323

Magnitude in dB
-0.1392
-6.345
-10.33
-13.57
-16.75
-20.87
-26.36
-32.85
-41.99
-0.0497
-5.829
-8.931
-6.773
-4.521
26.86
-9.576
-12.12
-20.25

It is observed from Table 2 that the resonant frequency of interest (284 KHz) could be observed with higher
magnitude (26.86 dB) than its corresponding value (-20.87 dB) with LI excitation.

Fig.11 Winding current of DUT 2 in frequency domain with OLI excitation

www.ijesi.org

53 | Page
Improved Method For Winding

In order to validate the proposed excitation for improving the detection sensitivity, winding
deformation has to be simulated in the lumped parameter model. By introducing change in the model parameters
the winding deformation can be simulated. In order to simulate radial deformation, shunt capacitance (Cg) in
fifth section (middle of winding in a ten section lumped parameter model) is changed from 0.4nF to 0.5nF. The
response of DUT 2 with LI and OLI excitation under no fault and fault introduced conditions are recorded and
transformed to frequency domain as shown in Fig.12.

Fig.12 Response of DUT 2 for LI and OLI excitation under no fault and fault condition
Table. 3 Resonant frequencies of DUT 2 with LI and OLI excitation under no fault and fault condition
Excitation

LI

OLI

With no fault
Resonant
Magnitude in dB
frequency in
KHz
58
-0.1392
119
-6.345
175
-10.33
221
-13.57
257
-16.75
284
-20.87
303
-26.36
316
-32.85
323
-41.99
58
-0.0497
119
-5.829
175
-8.931
221
-6.773
257
-4.521
284
26.86
303
-9.576
316
-12.12
323
-20.25

With fault
Resonant
Magnitude in dB
frequency in
KHz
56
-0.8999
119
-6.334
171
-11.64
221
-13.54
253
-16.47
284
-20.88
299
-27.35
316
-33.07
320
-40.45
56
-0.8948
119
-5.813
171
-10.77
221
-6.735
253
-5.548
284
26.90
299
-5.855
316
-12.16
320
-18.25

Table 3 shows the variation in resonant frequencies with LI and OLI excitation under no fault and
fault introduced conditions. The shift in resonant frequencies and their corresponding magnitude change under
no fault and fault introduced condition are indicated. Consider the resonant frequency 284 KHz that has a
magnitude of -20.87 dB under no fault and -20.88 dB with fault introduced condition. The magnitude level of
this resonant frequency of interest is increased from -20.88 dB to 26.86 dB under no fault and from -20.88 dB
to 26.90 dB under fault introduced condition. This proves the effectiveness of OLI excitation for winding
deformation detection. Hence it can be appreciated from Table 3 that the proposed excitation improves the
winding deformation detection sensitivity.

www.ijesi.org

54 | Page
Improved Method For Winding

VII.

CONCLUSION

This paper dealt with comparison of the winding deformation detection sensitivities of transformer
windings for different test inputs through a simulation study. The winding deformation is simulated by
introducing changes in the model parameter (shunt capacitance value in section 5) of the lumped parameter
model to simulate radial deformation. The fault detection sensitivities of the winding model with low voltage
impulse signal and oscillatory low voltage impulse signal are compared. It is observed that the OLI is more
sensitive than LI test signal for the detection of winding deformation.

REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]

K.Karsai,D. Kerenyi.D and l. Kiss, Large power transformers (New York: Elsevier Science Publishers, 1987).
T.Olsson, 800 kV AC transformers built for reliability, Seventh international conference on transformers (TRAFOTECH-2006),
Mumbai, India, 2006, 1-6.
R.P.P. Smeets and L.H.Le. Paske, An update test experiments with short circuit test withstand capability of large power
transformer, Seventh international conference on transformers (TRAFOTECH-2006), Mumbai, India, 2006, 31-38.
IEC 60076 – Pt V, Power transformers – Ability to withstand short circuit, (Switzerland: IEC Geneva, 2000).
S. Santhi,V. Jayashankar, Continual assessment of winding deformation during a short circuit test, Transactions of IEE Japan,
Power and Energy, 126(7), 2006, 712-713.
M. Florkowski and J.Furgal, Detection of transformer winding deformations based on the transfer function measurements and
simulations, Measurement Science and Technology, 14(11), 2003, 1986-1992.
M.Arivamudhan,S.Santhi, Model based approach for fault detection in power transformers using Particle swarm intelligence,
Recent advancements in System Modelling applications, Lecture Notes in Electrical Engineering Springer, 188,2013, 287-300.
R. Malewski and B.Poulin, Impulse testing of power transformer using the transfer function method, IEEE Transactions on
Power Delivery, 3(2), 1988, 476-489.
T. Leibfried, and K Feser, Monitoring of power transformers using the transfer function method, IEEE Transactions on Power
Delivery, 14(4), 1999, 1333-1341.
S.Kulkarni, S.A.Khaparde, Transformer engineering, design and practice (New York: Marcel Decker Inc, 2004).
L.Satish, Anurag Jain, Structure of transfer function of transformers with special reference to interleaved windings, IEEE
Transactions on Power Delivery, 17(3), 2002, 754-760.

www.ijesi.org

55 | Page

Weitere Àhnliche Inhalte

Was ist angesagt?

Was ist angesagt? (20)

Introduction to microwaves
Introduction to microwavesIntroduction to microwaves
Introduction to microwaves
 
En34855860
En34855860En34855860
En34855860
 
C231924
C231924C231924
C231924
 
O01062110113
O01062110113O01062110113
O01062110113
 
Detection and Location of Faults in 11KV Underground Cable by using Continuou...
Detection and Location of Faults in 11KV Underground Cable by using Continuou...Detection and Location of Faults in 11KV Underground Cable by using Continuou...
Detection and Location of Faults in 11KV Underground Cable by using Continuou...
 
Studies on Effect of Waveguide Dimensions on Resonant Frequency of Shunt Tee ...
Studies on Effect of Waveguide Dimensions on Resonant Frequency of Shunt Tee ...Studies on Effect of Waveguide Dimensions on Resonant Frequency of Shunt Tee ...
Studies on Effect of Waveguide Dimensions on Resonant Frequency of Shunt Tee ...
 
Substrate integrated waveguide power divider, circulator and coupler in [10 1...
Substrate integrated waveguide power divider, circulator and coupler in [10 1...Substrate integrated waveguide power divider, circulator and coupler in [10 1...
Substrate integrated waveguide power divider, circulator and coupler in [10 1...
 
Study tour to optcl
Study tour to optclStudy tour to optcl
Study tour to optcl
 
Q34108113
Q34108113Q34108113
Q34108113
 
Waveguide for Microwave Communication
Waveguide for Microwave CommunicationWaveguide for Microwave Communication
Waveguide for Microwave Communication
 
transmission-line-and-waveguide-ppt
transmission-line-and-waveguide-ppttransmission-line-and-waveguide-ppt
transmission-line-and-waveguide-ppt
 
transmission lineprotection_20100513_web
 transmission lineprotection_20100513_web transmission lineprotection_20100513_web
transmission lineprotection_20100513_web
 
Development of Single Channel and Phased Array
Development of Single Channel and Phased ArrayDevelopment of Single Channel and Phased Array
Development of Single Channel and Phased Array
 
Microwave Engineering Lecture Notes
Microwave Engineering Lecture NotesMicrowave Engineering Lecture Notes
Microwave Engineering Lecture Notes
 
waveguide-1
waveguide-1waveguide-1
waveguide-1
 
Performance Comparison of CMOS and Finfet Based Circuits At 45nm Technology U...
Performance Comparison of CMOS and Finfet Based Circuits At 45nm Technology U...Performance Comparison of CMOS and Finfet Based Circuits At 45nm Technology U...
Performance Comparison of CMOS and Finfet Based Circuits At 45nm Technology U...
 
Chapter 2 passive components, resonators and impedance matching
Chapter 2 passive components, resonators and impedance matchingChapter 2 passive components, resonators and impedance matching
Chapter 2 passive components, resonators and impedance matching
 
Characteristic and Surge Impedance Variation Impact on Transmission Line Perf...
Characteristic and Surge Impedance Variation Impact on Transmission Line Perf...Characteristic and Surge Impedance Variation Impact on Transmission Line Perf...
Characteristic and Surge Impedance Variation Impact on Transmission Line Perf...
 
SUBMISSION_FINAL1 (2)
SUBMISSION_FINAL1 (2)SUBMISSION_FINAL1 (2)
SUBMISSION_FINAL1 (2)
 
A Survey on Classification of Power Quality Disturbances in a Power System
A Survey on Classification of Power Quality Disturbances in a Power SystemA Survey on Classification of Power Quality Disturbances in a Power System
A Survey on Classification of Power Quality Disturbances in a Power System
 

Andere mochten auch

La cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres Jovien
La cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres JovienLa cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres Jovien
La cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres Jovien
jonatot
 
Manne Donation Press Release
Manne Donation Press ReleaseManne Donation Press Release
Manne Donation Press Release
Andrew Coffey
 
Kinematika ruhu materialnoyi toshki
Kinematika ruhu materialnoyi toshkiKinematika ruhu materialnoyi toshki
Kinematika ruhu materialnoyi toshki
Ilona Bacurovska
 
Termodinamica en el corte de metales
Termodinamica en el corte de metales Termodinamica en el corte de metales
Termodinamica en el corte de metales
itzayannaa
 
Si impersonale e passivante
Si impersonale e passivanteSi impersonale e passivante
Si impersonale e passivante
Lyceum Italy
 
Kinematika ruhu materialnoi tochki
Kinematika ruhu materialnoi tochkiKinematika ruhu materialnoi tochki
Kinematika ruhu materialnoi tochki
Ilona Bacurovska
 

Andere mochten auch (20)

Creating a fresh new view
Creating a fresh new viewCreating a fresh new view
Creating a fresh new view
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI) International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
Sparkcamp stratasingapore
Sparkcamp stratasingaporeSparkcamp stratasingapore
Sparkcamp stratasingapore
 
Tarea Informatica
Tarea InformaticaTarea Informatica
Tarea Informatica
 
La cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres Jovien
La cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres JovienLa cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres Jovien
La cultura, La ciudad Y AcciĂłn Colectiva por Jhonatan Torres Jovien
 
Manne Donation Press Release
Manne Donation Press ReleaseManne Donation Press Release
Manne Donation Press Release
 
Kinematika ruhu materialnoyi toshki
Kinematika ruhu materialnoyi toshkiKinematika ruhu materialnoyi toshki
Kinematika ruhu materialnoyi toshki
 
Termodinamica en el corte de metales
Termodinamica en el corte de metales Termodinamica en el corte de metales
Termodinamica en el corte de metales
 
Top 10 tips
Top 10 tipsTop 10 tips
Top 10 tips
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI) International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI) International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
Đ­ĐșŃĐżĐ”Ń€ĐžĐŒĐ”ĐœŃ‚ с ĐżĐŸĐ»ĐșĐŸĐč (Ń€Đ”ŃˆĐ”ĐœĐžŃ бОС ĐČ Đ°ĐżŃ‚Đ”Ń‡ĐœĐŸĐč сДтО)
Đ­ĐșŃĐżĐ”Ń€ĐžĐŒĐ”ĐœŃ‚ с ĐżĐŸĐ»ĐșĐŸĐč (Ń€Đ”ŃˆĐ”ĐœĐžŃ бОС ĐČ Đ°ĐżŃ‚Đ”Ń‡ĐœĐŸĐč сДтО)Đ­ĐșŃĐżĐ”Ń€ĐžĐŒĐ”ĐœŃ‚ с ĐżĐŸĐ»ĐșĐŸĐč (Ń€Đ”ŃˆĐ”ĐœĐžŃ бОС ĐČ Đ°ĐżŃ‚Đ”Ń‡ĐœĐŸĐč сДтО)
Đ­ĐșŃĐżĐ”Ń€ĐžĐŒĐ”ĐœŃ‚ с ĐżĐŸĐ»ĐșĐŸĐč (Ń€Đ”ŃˆĐ”ĐœĐžŃ бОС ĐČ Đ°ĐżŃ‚Đ”Ń‡ĐœĐŸĐč сДтО)
 
Pordenone itinerario turistico, Isis Stringher. Itinerary in Pordenone, North...
Pordenone itinerario turistico, Isis Stringher. Itinerary in Pordenone, North...Pordenone itinerario turistico, Isis Stringher. Itinerary in Pordenone, North...
Pordenone itinerario turistico, Isis Stringher. Itinerary in Pordenone, North...
 
Communication and media
Communication and mediaCommunication and media
Communication and media
 
Si impersonale e passivante
Si impersonale e passivanteSi impersonale e passivante
Si impersonale e passivante
 
Grafoaas
GrafoaasGrafoaas
Grafoaas
 
Manner of achieving minimum public shareholding regulation 38 Sebi lodr
Manner of achieving minimum public shareholding regulation 38 Sebi lodr Manner of achieving minimum public shareholding regulation 38 Sebi lodr
Manner of achieving minimum public shareholding regulation 38 Sebi lodr
 
Aisha Matrimonial Review
Aisha Matrimonial ReviewAisha Matrimonial Review
Aisha Matrimonial Review
 
Periféricos de procesamiento de datos
Periféricos de procesamiento de datosPeriféricos de procesamiento de datos
Periféricos de procesamiento de datos
 
Kinematika ruhu materialnoi tochki
Kinematika ruhu materialnoi tochkiKinematika ruhu materialnoi tochki
Kinematika ruhu materialnoi tochki
 

Ähnlich wie International Journal of Engineering and Science Invention (IJESI)

Ähnlich wie International Journal of Engineering and Science Invention (IJESI) (20)

Frequency response analysis for transformer tap changer damage detection
Frequency response analysis for transformer tap changer damage detectionFrequency response analysis for transformer tap changer damage detection
Frequency response analysis for transformer tap changer damage detection
 
CMOS ring oscillator delay cell performance: a comparative study
CMOS ring oscillator delay cell performance: a comparative studyCMOS ring oscillator delay cell performance: a comparative study
CMOS ring oscillator delay cell performance: a comparative study
 
Comparison of coupling capacitors and the inverter filter in partial discharg...
Comparison of coupling capacitors and the inverter filter in partial discharg...Comparison of coupling capacitors and the inverter filter in partial discharg...
Comparison of coupling capacitors and the inverter filter in partial discharg...
 
Control of Dvr with Battery Energy Storage System Using Srf Theory
Control of Dvr with Battery Energy Storage System Using Srf TheoryControl of Dvr with Battery Energy Storage System Using Srf Theory
Control of Dvr with Battery Energy Storage System Using Srf Theory
 
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over...
 
Fault identification in transformer winding
Fault identification in transformer windingFault identification in transformer winding
Fault identification in transformer winding
 
Fault identification in transformer winding
Fault identification in transformer windingFault identification in transformer winding
Fault identification in transformer winding
 
20120140506014
2012014050601420120140506014
20120140506014
 
G010144450
G010144450G010144450
G010144450
 
Design of ring vco using nine stages of differential amplifier
Design of ring vco using nine stages of differential amplifierDesign of ring vco using nine stages of differential amplifier
Design of ring vco using nine stages of differential amplifier
 
Study of Different Types of Inverters and FFT Analysis of Output of SPWM Inve...
Study of Different Types of Inverters and FFT Analysis of Output of SPWM Inve...Study of Different Types of Inverters and FFT Analysis of Output of SPWM Inve...
Study of Different Types of Inverters and FFT Analysis of Output of SPWM Inve...
 
Design of vco using current mode logic with low supply
Design of vco using current mode logic with low supplyDesign of vco using current mode logic with low supply
Design of vco using current mode logic with low supply
 
Design of vco using current mode logic with low supply sensitivity
Design of vco using current mode logic with low supply sensitivityDesign of vco using current mode logic with low supply sensitivity
Design of vco using current mode logic with low supply sensitivity
 
I010246467
I010246467I010246467
I010246467
 
wireless power transfer
wireless power transferwireless power transfer
wireless power transfer
 
DYNAMICS OF AN OSCILLATOR FOR SINUSOIDAL INPUT
DYNAMICS OF AN OSCILLATOR FOR SINUSOIDAL INPUTDYNAMICS OF AN OSCILLATOR FOR SINUSOIDAL INPUT
DYNAMICS OF AN OSCILLATOR FOR SINUSOIDAL INPUT
 
40220130405008
4022013040500840220130405008
40220130405008
 
Neutral Current and Frequency Response Analysis of Single and Multiple Turn F...
Neutral Current and Frequency Response Analysis of Single and Multiple Turn F...Neutral Current and Frequency Response Analysis of Single and Multiple Turn F...
Neutral Current and Frequency Response Analysis of Single and Multiple Turn F...
 
O0704080084
O0704080084O0704080084
O0704080084
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 

KĂŒrzlich hochgeladen

Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...
Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...
Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...
Anamikakaur10
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
Abortion pills in Kuwait Cytotec pills in Kuwait
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
amitlee9823
 
Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...
Sheetaleventcompany
 
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
daisycvs
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
amitlee9823
 

KĂŒrzlich hochgeladen (20)

Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
BAGALUR CALL GIRL IN 98274*61493 ❀CALL GIRLS IN ESCORT SERVICE❀CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❀CALL GIRLS IN ESCORT SERVICE❀CALL GIRLBAGALUR CALL GIRL IN 98274*61493 ❀CALL GIRLS IN ESCORT SERVICE❀CALL GIRL
BAGALUR CALL GIRL IN 98274*61493 ❀CALL GIRLS IN ESCORT SERVICE❀CALL GIRL
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Eluru Call Girls Service ☎ 93326-06886 â€ïžâ€đŸ”„ Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ 93326-06886 â€ïžâ€đŸ”„ Enjoy 24/7 Escort ServiceEluru Call Girls Service ☎ 93326-06886 â€ïžâ€đŸ”„ Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ 93326-06886 â€ïžâ€đŸ”„ Enjoy 24/7 Escort Service
 
Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...
Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...
Call Now â˜ŽïžđŸ” 9332606886🔝 Call Girls ❀ Service In Bhilwara Female Escorts Serv...
 
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 MonthsSEO Case Study: How I Increased SEO Traffic & Ranking by 50-60%  in 6 Months
SEO Case Study: How I Increased SEO Traffic & Ranking by 50-60% in 6 Months
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...
Chandigarh Escorts Service 📞8868886958📞 JustđŸ“Č Call Nihal Chandigarh Call Girl...
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai KuwaitThe Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
The Abortion pills for sale in Qatar@Doha [+27737758557] []Deira Dubai Kuwait
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
Uneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration PresentationUneak White's Personal Brand Exploration Presentation
Uneak White's Personal Brand Exploration Presentation
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
 

International Journal of Engineering and Science Invention (IJESI)

  • 1. International Journal of Engineering Science Invention ISSN (Online): 2319 – 6734, ISSN (Print): 2319 – 6726 www.ijesi.org Volume 2 Issue 10ǁ October 2013 ǁ PP.48-55 Improved Method for Winding Deformation Detection Sensitivity in Transformer Arivamudhan M, Santhi S* Department of Instrumentation Engineering, Annamalai University, Annamalai Nagar, Tamil Nadu India. ABSTRACT : Power transformers are one of the most vital as well as expensive equipment in an electric power system. Transformers may be subjected to various types of faults. Of these, the structural fault namely the winding deformation due to either dynamic effect of short circuit current or vibration during transportation or due to short circuit in nearby equipments is severe and needs attentive condition monitoring. The fault may cause a change in the physical condition of transformer which would reflect as variation in the electrical parameters- resistance, inductance and capacitance of the winding. Detection of winding deformation is possible by observing the variation in characteristic resonant frequency of winding due to change in electrical parameters as a result of winding deformation. This paper aims at detection of winding deformation with improvement in detection sensitivity by the use of different test input signal. The proposed method is validated through simulation using lumped parameter model of a transformer winding. KEYWORDS : Transformer, winding deformation, Lightning impulse, detection sensitivity I. INTRODUCTION Transformers are a critical and expensive component of the power system. Failure of a transformer may be potentially severe and may affect safety of personnel and the environment. Due to the long time for repair and replacement of transformers, a major goal of transformer protection is limiting the damage of a transformer that has experienced a fault condition. This necessitates that monitoring and diagnostic methods be developed at various stages starting from design, testing, commissioning and during operation.As windings are the heart of the transformer, assessing the integrity of the winding becomes an essential task. The structural integrity of the winding is sought to be ensured by short circuit tests. The winding deformation in transformers may occur either when the transformer is subjected to short circuit test or during transportation or due to ageing [1].The objective of the short circuit test is to assess the capability of winding to withstand thermal and dynamic effects caused by the short circuit current, which can be many times full load current [2]. From manufacturing view point the test is important part in continually improving design [3]. Details regarding the test current magnitude, the frequency of the test supply, the number of tests to be conducted, the test procedure and the detection of faults and evaluation of test results are documented in standards such as IEC 60076 Part V, 2000 [4]. The ability to withstand the dynamic effects of short circuit shall be demonstrated if required by the consumer, either by tests or by calculation and design consideration. Conventionally reactance measurement was utilized as a diagnostic tool to indicate whether the transformer has passed the test. A method based on cycle to cycle impedance measurement has also been proposed [5]. Determination of transfer function for winding deformation detection using low voltage impulse (LVI) method was proposed in [6],[7] and use of LVI for detection of impulse faults have been proposed in [8],[9]. In this paper a method of winding deformation detection that employs a different test input for improving the detection sensitivity is proposed and validated. II. CAUSES OF WINDING DEFORMATION IN TRANSFORMER Most of the failures are caused by transformer winding faults and the faults are generated by lightning and switching surges. As a transformer experiences a fault, it may suffer mechanical shock that gradually displaces and distorts the windings [10]. In the process of winding movement the insulation between the turns can be abraded causing a short circuit and damage to the windings. Mechanical vibration initiated by short circuit forces causes loosening of clamping pressure and collapse winding. The other causes of winding movement may be extensive vibration during transformer transportation.As the winding experiences vibrations it may slacken and subsequently becomes unable to withstand mechanical forces exerted during faults. Ageing also contributes to winding looseness. www.ijesi.org 48 | Page
  • 2. Improved Method For Winding
 In addition harmonics generated under normal operating conditions may cause winding and core vibration. Short circuit forces are potentially very destructive because if the clamping pressure is not capable of restraining the forces involved, substantial permanent winding deformation or collapse can occur almost instantaneously often accompanied by shorted turns. During short circuit condition the axial and radial fluxes in the air gap interact with the short circuit current and produce the short circuit forces that tend to deform the winding. Since windings are characterized by their resonant frequencies, the deformation in windings can be detected by observing changes in resonant frequency as a result of change in electrical parameter. III. PROBLEM FORMULATION In general large power transformers are validated for their short circuit withstand capability through short circuit test. As mentioned in the procedure, the short circuit test is performed by short circuiting the low voltage winding and exciting the high voltage winding. In the existing low voltage impulse (LVI) method of winding deformation detection, low voltage impulse is applied to the HV winding and the winding current through it is observed. The winding deformation that may occur due to high short circuit current results in shift in natural resonant frequencies of the winding.Since low voltage impulse signal in frequency domain indicates that the amplitude decreases monotonically with increase in frequency, the winding deformation detection may not be possible with good sensitivity if the resonant frequency lies in the high frequency region. Hence a different test input is required for winding deformation detection for improvement in detection sensitivity. This paper emerged to seek for a solution to this problem. IV. TEST SIGNAL FOR IMPROVEMENT IN DETECTION SENSITIVITY The low voltage impulse excitation that is similar to standard lightning impulse (LI) of 1V, 1.2/50”s front time and fall time respectively is initially defined as the test signal to simulate the lumped parameter model of a transformer winding. Fig.1 shows the lightning impulse excitation (LI) in time domain defined in the circuit simulation package. Fig.1 LI excitation in time domain The LI excitation signal is exported to Matlab package to determine its characteristics in frequency domain and the same is shown in Fig.2. It is observed from Fig.2 that the magnitude of LI excitation decreases monotonically as the frequency is increased. Based on the frequency response measurement concept the input signal magnitude is to be kept constant and as the input signal’s frequency is increased, the response of DUT is to be observed to study the frequency domain characteristics. Application of LI to determine the frequency response may not provide the necessary constant input excitation at all frequencies of measurement. Fig. 2 LI excitation in frequency domain www.ijesi.org 49 | Page
  • 3. Improved Method For Winding
 In order to overcome this problem, a different excitation namely oscillating impulse (OLI) has been proposed as described below. The OLI is generated by super imposing with a standard LI, a sinusoidal signal with frequency equal to the resonant frequency of the winding. The resonant frequencies of the winding exhibits shift in frequency domain as a result of winding deformation. In case if the resonant frequency happens to be in the order of hundreds of KHz, the LI excitation may not indicate the same with good sensitivity. Where as if OLI in which the sinusoidal frequency is defined to be the resonant frequency of interest then that frequency component can be observed with better sensitivity. Fig.3 shows the OLI excitation in which sinusoidal signal of 27 KHz is super imposed with LI. Fig.4 shows the OLI excitation in frequency domain indicating dominantly 27 KHz frequency component. Fig.3 OLI excitation in time domain From Fig.4, it is observed that the resonant frequency of interest could be studied with input having magnitude not in the noise region and there by improvement in detection sensitivity. Fig.4 OLI excitation in frequency domain V. DEVICE UNDER TEST (DUT) In order to demonstrate the method that improves detection sensitivity, a transformer winding model is essential, to carry out the simulation. The simulation work requires a lumped parameter model of the transformer winding that needs to be considered as the device under test. The model parameters of layer winding and interleaved winding as mentioned in [11] have been used to carry out the simulation. The parameters of the interleaved winding (DUT 1) are as given below Inductance of each section =0.5mH Ground capacitance of each section =0.4nF Series capacitance of each section =12.8nF www.ijesi.org 50 | Page
  • 4. Improved Method For Winding
 The parameters of the layer winding (DUT 2) are as given below Inductance of each section =0.5mH Ground capacitance of each section =0.4nF Series capacitance of each section =0.1nF The mutual inductances for both interleaved and layer windings are M 1-2=0.25mH, M1-3=0.167mH, M1M1-6=0.0833mH, M1-7=0.071mH, M1-8=0.0625mH, M1-9=0.0556mH, M14=0.125mH, M1-5=0.10mH, M1-3= M2-4= M3-5

.= M8-10. M1-4= M2-5= M1-2= M310=0.050mH and M1-2= M2-3= M3-4


= M9-10, 6

..= M7-10 and so on. Figure 5 shows the ten section lumped parameter model of a transformer winding in general. Fig. 5 Ten section lumped parameter model VI. RESULTS AND DISCUSSION The validation of proposed method is achieved through simulation of lumped parameter model of winding using LI and OLI excitations. In this regard, the lumped parameter model of interleaved winding (DUT1) is simulated to record the winding current using LI excitation. The winding current Iw through a current viewing resistor R as shown in Fig.5 is analyzed in frequency domain using MATLAB software. The winding current of DUT1 when LI excitation applied is shown in Fig.6 and the corresponding frequency domain response is shown in Fig.7. Fig.6 Response of DUT 1 with LI excitation Fig.7 Winding current of DUT 1 in frequency domain with LI excitation www.ijesi.org 51 | Page
  • 5. Improved Method For Winding
 The resonant frequencies of DUT 1 with LI excitation are tabulated in Table 1. Next the winding current of DUT 1 with OLI excitation (LI super imposed with sinusoidal signal frequency of 37 KHz) applied is recorded and its frequency domain response is shown in Fig.8. Table 1 indicates resonant frequencies of DUT 1 with OLI excitation. Table. 1 Resonant frequencies of DUT 1 with LI and OLI excitation Excitation LI OLI Resonant frequency in KHz 29 35 37 39 29 35 37 39 Magnitude in dB -10.19 -23.70 -23.97 -25.29 -3.986 -7.389 2.815 -16.05 It is observed from Table I that the resonant frequency of interest (37 KHz) could be observed with higher magnitude (2.815 dB) than its corresponding value (-23.97 dB) with LI excitation. Fig.8 Response of DUT 1 with OLI excitation The frequency response of interleaved winding model shows only four resonant frequencies in the order of tens of KHz. It would be better if the method is demonstrated for a model that has resonant frequencies occurring in high frequency region which is more prone to noise. Fig.9 Winding current of DUT 2 in time domain with LI excitation www.ijesi.org 52 | Page
  • 6. Improved Method For Winding
 Fig.10 Winding current of DUT 2 in frequency domain with LI excitation The simulation of lumped parameter model with LI and OLI excitation is repeated for the case of DUT 2.Winding current of DUT 2 when LI excitation applied is shown in Fig.9 and the same in frequency domain is shown in Fig.10. The resonant frequencies of DUT 2 are tabulated in Table 2. Consider the resonant frequency 284 KHz with magnitude -20.87 dB. To observe the effectiveness of OLI excitation to this resonant frequency the winding current of DUT 2 with OLI excitation (LI super imposed with sinusoidal signal frequency of 284 KHz) applied is recorded and its response in frequency domain is shown in Fig.11. Table 2 indicates resonant frequencies of DUT 2 with OLI excitation. Table. 2 Resonant frequencies of DUT 2 with LI and OLI excitation Excitation LI OLI Resonant frequency in KHz 58 119 175 221 257 284 303 316 323 58 119 175 221 257 284 303 316 323 Magnitude in dB -0.1392 -6.345 -10.33 -13.57 -16.75 -20.87 -26.36 -32.85 -41.99 -0.0497 -5.829 -8.931 -6.773 -4.521 26.86 -9.576 -12.12 -20.25 It is observed from Table 2 that the resonant frequency of interest (284 KHz) could be observed with higher magnitude (26.86 dB) than its corresponding value (-20.87 dB) with LI excitation. Fig.11 Winding current of DUT 2 in frequency domain with OLI excitation www.ijesi.org 53 | Page
  • 7. Improved Method For Winding
 In order to validate the proposed excitation for improving the detection sensitivity, winding deformation has to be simulated in the lumped parameter model. By introducing change in the model parameters the winding deformation can be simulated. In order to simulate radial deformation, shunt capacitance (Cg) in fifth section (middle of winding in a ten section lumped parameter model) is changed from 0.4nF to 0.5nF. The response of DUT 2 with LI and OLI excitation under no fault and fault introduced conditions are recorded and transformed to frequency domain as shown in Fig.12. Fig.12 Response of DUT 2 for LI and OLI excitation under no fault and fault condition Table. 3 Resonant frequencies of DUT 2 with LI and OLI excitation under no fault and fault condition Excitation LI OLI With no fault Resonant Magnitude in dB frequency in KHz 58 -0.1392 119 -6.345 175 -10.33 221 -13.57 257 -16.75 284 -20.87 303 -26.36 316 -32.85 323 -41.99 58 -0.0497 119 -5.829 175 -8.931 221 -6.773 257 -4.521 284 26.86 303 -9.576 316 -12.12 323 -20.25 With fault Resonant Magnitude in dB frequency in KHz 56 -0.8999 119 -6.334 171 -11.64 221 -13.54 253 -16.47 284 -20.88 299 -27.35 316 -33.07 320 -40.45 56 -0.8948 119 -5.813 171 -10.77 221 -6.735 253 -5.548 284 26.90 299 -5.855 316 -12.16 320 -18.25 Table 3 shows the variation in resonant frequencies with LI and OLI excitation under no fault and fault introduced conditions. The shift in resonant frequencies and their corresponding magnitude change under no fault and fault introduced condition are indicated. Consider the resonant frequency 284 KHz that has a magnitude of -20.87 dB under no fault and -20.88 dB with fault introduced condition. The magnitude level of this resonant frequency of interest is increased from -20.88 dB to 26.86 dB under no fault and from -20.88 dB to 26.90 dB under fault introduced condition. This proves the effectiveness of OLI excitation for winding deformation detection. Hence it can be appreciated from Table 3 that the proposed excitation improves the winding deformation detection sensitivity. www.ijesi.org 54 | Page
  • 8. Improved Method For Winding
 VII. CONCLUSION This paper dealt with comparison of the winding deformation detection sensitivities of transformer windings for different test inputs through a simulation study. The winding deformation is simulated by introducing changes in the model parameter (shunt capacitance value in section 5) of the lumped parameter model to simulate radial deformation. The fault detection sensitivities of the winding model with low voltage impulse signal and oscillatory low voltage impulse signal are compared. It is observed that the OLI is more sensitive than LI test signal for the detection of winding deformation. REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] K.Karsai,D. Kerenyi.D and l. Kiss, Large power transformers (New York: Elsevier Science Publishers, 1987). T.Olsson, 800 kV AC transformers built for reliability, Seventh international conference on transformers (TRAFOTECH-2006), Mumbai, India, 2006, 1-6. R.P.P. Smeets and L.H.Le. Paske, An update test experiments with short circuit test withstand capability of large power transformer, Seventh international conference on transformers (TRAFOTECH-2006), Mumbai, India, 2006, 31-38. IEC 60076 – Pt V, Power transformers – Ability to withstand short circuit, (Switzerland: IEC Geneva, 2000). S. Santhi,V. Jayashankar, Continual assessment of winding deformation during a short circuit test, Transactions of IEE Japan, Power and Energy, 126(7), 2006, 712-713. M. Florkowski and J.Furgal, Detection of transformer winding deformations based on the transfer function measurements and simulations, Measurement Science and Technology, 14(11), 2003, 1986-1992. M.Arivamudhan,S.Santhi, Model based approach for fault detection in power transformers using Particle swarm intelligence, Recent advancements in System Modelling applications, Lecture Notes in Electrical Engineering Springer, 188,2013, 287-300. R. Malewski and B.Poulin, Impulse testing of power transformer using the transfer function method, IEEE Transactions on Power Delivery, 3(2), 1988, 476-489. T. Leibfried, and K Feser, Monitoring of power transformers using the transfer function method, IEEE Transactions on Power Delivery, 14(4), 1999, 1333-1341. S.Kulkarni, S.A.Khaparde, Transformer engineering, design and practice (New York: Marcel Decker Inc, 2004). L.Satish, Anurag Jain, Structure of transfer function of transformers with special reference to interleaved windings, IEEE Transactions on Power Delivery, 17(3), 2002, 754-760. www.ijesi.org 55 | Page