Project Data Sheet & contents
Project electro mechanical system
HVAC System
Theoretical approach
Case study
Fire fighting System
Theoretical approach
Case study
Fire safety
Fire alarm System
1. Cairo university
faculty of engineering
department of architecture
masters studies 2004
Integrated building systems
measures & evaluation
Case study
arcadia mall &
residential complex
2. Cairo university
faculty of engineering
department of architecture
masters studies 2004
Contents :
Project Data Sheet & contents
Project electro mechanical system
HVAC System
Theoretical approach
Case study
Fire fighting System
Theoretical approach
Case study
Fire safety
Fire alarm System
3. Cairo university
faculty of engineering
department of architecture
masters studies 2004
Arcadia project:
•Residential sector covering 8
floors height
•Seven floors for commercial uses
covers 53,000m2
•Food court consisting of 14 fast
food outlets
•Four cinemas with 400 seats each
( now used as fun planet )
•Ice skating arena 140m2 on the
ground floor
( now used as a cafeteria )
•Parking area of 20,000 m2 with a
600 cars capacity
•Data Fact :
Location:
cornice el Nile
Client :
al Ahly real Estate
Development
Consultant :
Sabbour Associates
Architects :
afzxfzdfzs
4- Parking
Sector
•Project Contents:
•Thee panoramic elevators from
parking level to all levels
•Atrium area 300m2 on the 1st
level then it enlarges up to 660 m2
at the 7th level
1
2
3
4
3- Fun planet &
office Sector
2- Commercial
Sector
1- Residential
Sector
4. Cairo university
faculty of engineering
department of architecture
masters studies 2004
Arcadia project:
•Heating , ventilation &
air –conditioning
•Smoke pressurization
system
•Fire protection systems
•Vertical transportation
systems
(elevators & escalators )
•Drinking water booster
system
•Emergency stand – by
diesel generating sets
•Fuel supply system
•Dewatering & waste
pumping sets
•Plumping & drainage
systems
•Telephone & intercom.
Systems
•Fire alarm system
•TV & satellite system
•Electrical systems
•Electro – Mechanical Systems
1
2
3
4
3
555
6
77
8
1. Mall main ent.
2. Mall sec ent
3. Residential
ent.
4. E. stairs &
service zone
5. Residential
core
6. F.F tanks
7. Machine room
8. HVAC room
5
5. Cairo university
faculty of engineering
department of architecture
masters studies 2004
H.V.A.C SYSTEM
•Heat sorce
•Theoretical Introduction:
•Comfort zone •Building outerconditions
6. Cairo university
faculty of engineering
department of architecture
masters studies 2004
H.V.A.C SYSTEM
•Heat lose cases
•Theoretical Introduction:
•Insulation system •AC cycle •Types of grills
7. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•Riser diagram
•Water cooling system
h.v.a.c system
1 425
3
1. Primacy pump
(P.P)
CAP.2400
GPM 60 HP
2. Secondary
Pump
zone1(P.S-1)
CAP.2600
GMP 150 HP
3. Booster Pump
zone1 (B.P-1)
CAP …….
50HP
4. Secondary
pump zone2
(P.S-2) CAP.
2200 GPM
125 HP
5. Booster pump
zone2 (B.P-2)
CAP ……..
40HP
•Zone 2 •Zone 1
•Closed water cycle.
8. Cairo university
faculty of engineering
department of architecture
masters studies 2004
H.V.A.C SYSTEM
1. Round doors in the entrances
2. AHU in the atrium
3. AC grills in corridors
4. AHU in the a shop
5. Upright AHU in food court
6. AC grills in the computer center
7. AC ducts in basement
8. AC ducts in basement
2 3
7
4 5 6
8
1
9. Cairo university
faculty of engineering
department of architecture
masters studies 2004
Fire fighting system
•Smoke movement & control
•Theoretical Introduction:
•Mechanism of smoke production •Smoke control in fire area
10. Cairo university
faculty of engineering
department of architecture
masters studies 2004
Fire fighting system
•Theoretical Introduction:
•Smoke control in escape
routes
11. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•Riser diagram
•Hazard Zones
2 3 4 5 6
1. Mall main ent.
2. Mall sec ent
3. Residential
ent.
4. E. stairs &
service zone
5. Residential
core
6. F.F tanks
7. Machine room
8. HVAC room
Open spray spr. &
deluge system
Atrium Zone
7
Combined sprinkler
system
Commercial Zone
Combined sprinkler
system
Parking Zone
Clean approved
agent system
Control Zone
C02 auto firef
system
Electrical Zone
High exp Foam
System
Diesel generators
6
Wet stand pipe
system
Residential Zone
1
7
2
1
Fire fighting system
12. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•According to NFPA For any leakage or pressure drop the jokey pump
intiates the system
•If pressure drops excees limitation the 2 main pump works together
•The 2 pumps have to be of different energy sources
•System Structure …
1. Sub header 1
to residential
2. Sub header 2
to commercial
& parking
3. To foam-
water system
4. Main header
Fdc max distance
from system is 18m
Used to enable fd
connects to the ff
system externally
Fire department
connection
2
1
Fire fighting system
3
50 GPM sec F.F.
pump starts at
small pressure dec.
or sprinklers
leakage
Jockey pump
3000 gallon
capacity for 90 min
Double cell help in
maintenance
Double cell water
tank
4
1500 GPM main
F.F. pump
Electrical pump
1500 GPM main
F.F. pump
Diesel pump
•Pump & tank
room in basement
13. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•The sub header 1 splits into 4 risers to
cover each of the residential cores found in
the complex
•The system covers the corridors only
•Each riser contains 14 hose reel cabinets
•System Structure …
1. Sub header 1
to residential
2. Riser for each
zone
3. FDC
4. HRC hose reel
cabinet
2 1
Fire fighting system
3
4
•Residential section
14. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•The depressurized pipes enables
quick & powerful water injection
•The open sp. Act as water
curtains to prevent smoke spread
•The system is called the deluge
system
•Infrared detectors are the only
detectors having the ability to
initiate the system
•Mechanical windows acts as
smoke vents
•System Structure …
1. Sub header 1
to residential
2. Sub header 2
to commercial
& parking
3. FDC
4. Depressurized
pipes
2
1
Fire fighting system
4
3
•Atrium zone
15. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•The system is combined with heat & smoke detectors
•The blank off is used for future expansion
•System Structure …
1. Sub header 1
to residential
2. Sub header 2
to commercial
& parking
3. FDC
4. Risers for zone
5. Sprinklers
controllers
2
1
Fire fighting system
4
3
•Upright sprink.
•Commercial &
parking zone
5
16. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•Commercial examples …
1. Sub header 1
to residential
2. Sub header 2
to commercial
& parking
3. FDC
4. Risers for zone
5. Sprinklers
controllers
Fire fighting system
•Upright sprink.
•Commercial &
parking zone
• example for used sprinkles in different spaces in the
mall. And other shops doesn’t have any fire fighting
system.
17. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•Using stair
pressurization
system to keep
smoke out of the
staircase
•The fan power
is calculated
depending on no
of doors
•Staircase …
1. Residential em.
Exits
2. Mall em. Exits
3. Panoramic
elevators
4. Office em. exit
2
1
Fire safety system
4
3
11 1
•Escalators …
•Downward escalators
are only used for fire
escape and it has side
water curtains for
human safety from fire.
•Elevators …
•All elevators go to
ground level incase of
any fire or other
emergency
•Corridors…
• In
corridors
They use
coned
shaped
lighting
and
escape
signs
• only
used fire
escape
staircase
18. Cairo university
faculty of engineering
department of architecture
masters studies 2004
•The mall has an
alarm system
that avoids false
alarm and makes
the following
actions:
• detect the fire
in the first stages
by the detectors
(smoke , infrared
and heat
detectors) and
the place is
shown on the
info board.
• when fire is
detected the info
board acts the
following
actions:
send messages
for the alarm for
the building
send messages
for the A.H.U to
stop to avoid fire
spreading.
send messages
for elevators
•Fire alarm…
Fire alarm system
send messages
for smoke duct
system
• the main info
board works to
be sure that the
fire fighting
system is
working and
safety system.
• it also is
responsible of
fighting fire by
different agents
in different
spaces such as
mechanical .
Electrical room
and elevators.
• the building
contains
emergency
speaker system.
• the building
contains an
automatic
emergency caller.
•speakers
•Smoke duct.
•Deluge detector
•detector •Alarm.
•The alarm
system is an
automatic one but
also can be used as
a manual one in
emergency cases