PNWS AWWA
2015 Conference
Presented By:
Tim Tobin, PE
425.289.7371
May 1, 2015
Water Storage Tank Safety
Standards
Scope of Presentation
•Manholes for interior access
•Fixed ladders for access to tank roofs
•Fixed stairs (industrial) with railings for steep
roof access
•Railings and toeboards
•Roof safety
•Fall restraint, fall arrest, and positioning
device systems
Goals for this Presentation
•Describe regulations and standards
governing the configuration of tank access
and safety features
•To stimulate thought regarding your reservoirs
versus current safety regulations and
standards
•To motivate you to look critically at your
facilities
•Where to look for standards and regulations
Caveats
• Just because a facility doesn’t meet current regulations
and standards doesn’t necessarily mean it’s unsafe and
requires immediate modification – but it should be
consciously evaluated by a “competent person” or a
“qualified person”.
• This content is introductory only – see regulations
• Abbreviated information on slides
Organization of this Presentation
• Applicable regulations, standards, and
references
• Manholes
• Fixed ladders
• Landings
• Railings
• Roof access hatches
• Roof stairway
• Fall restraint, fall arrest, and positioning
device systems
WISHA Regulations
• OSHA is the federal Occupational Safety
and Health Administration
• WISHA is Washington State’s version of OSHA
• WISHA regulations govern in State of
Washington except for federal facilities,
floating worksites, tribal lands
• WISHA regulations are found in RCW 49.17.
• WISHA implementing rules are found in WAC
Chapter 296
• WAC Chapter 296 is L&I’s safety and health
requirements for employers.
WAC Chapter 296 Regulations
WAC 296-24, Part J-1, - Working Surfaces,
Guarding Floors and Wall Openings
• WAC 296-24-75011 - Railing, toe boards
and cover specifications
• WAC 296-24-765 – Fixed industrial stairs
• WAC 296-24-810 – Fixed ladders
• WAC 296-155, Part C-1 – Fall Protection
Requirements for Construction - Safety
standards for construction work, defined
as construction, alteration, related
inspection, and or maintenance and
repair work, including painting.
• WAC 296-876 – Ladders, Portable and
Fixed
WAC Regulations Continued
Applicable Standards
• AWWA D100-11, Welded Carbon Steel Tanks for
Water Storage: This standard applies to design
of welded steel reservoirs and standpipes.
• AWWA D110-04, Prestressed Concrete Water
Tanks
• ANSI A14.3, American National Standard for
Ladders-Fixed-Safety Requirements
Additional References
• Fixed Ladders and Climbing Protection
Devices, National Safety Council Data Sheet
606 Rev. August 2007
• US Army Corps of Engineers Safety and
Health Requirements Manual, Appendix J
(EM 385-1-1, Appendix J)
Tank Shell Manholes
• AWWA D100: a minimum of 2 round or
elliptical shell manholes within first ring.
• Each a minimum of 24 inches in diameter or
18” x 22” elliptical.
• One shell manhole at least 30 inches in
diameter.
• If hatch weighs more than 50 lbs, then a
davit or hinges are required
Ladder Definitions
• “Fixed Ladder” – is a ladder permanently attached to a
structure.
• “Through ladder” – is a ladder from which a person getting off
on top must step through the ladder in order to reach the
landing.
• “Side Step Ladder” - a side step ladder is one from which a
person getting off at the top must step sideways from the
ladder in order to reach the landing.
• “Cage” - is an enclosure that is fastened to the side rails of the
fixed ladder part of the structure to encircle the climbing
space of the ladder for safety.
• “Well” - is a permanent complete enclosure around a fixed
ladder, which is attached to the walls of the well.
• “Ladder safety device” - is any device, other than a cage or
well, designed to eliminate or reduce the possibility of
accidental falls and which incorporate such features as life
belts, friction brakes, and sliding attachments.
Ladder Length Restrictions
• WAC 296-876-60065: fixed ladders over 24 feet in
height, on the exterior and interior of the tanks, must
be equipped with cages, wells or a ladder safety
device.
• WAC 296-876-60065: no length of fixed ladder shall
exceed 50 feet, except when a ladder safety
device is installed.
• Landing Platforms are required every 30 feet,
except where no cage, well, or ladder safety
device is provided, landing platforms shall be
provided at each 20 feet of height or fraction
thereof.
• Each ladder section shall be offset from all adjacent
sections.
Requirements for Fixed Ladders
• Ladder side rails must be uniform for the full length and easy to
grasp.
• Per AWWA 100-05, flat steel bar side rails must be at least 2.0
inch wide by 3/8” thick.
• At least 16 inches of clear space between ladder side rails,
except at the top of the ladder.
• Both side rails must extend 42 inches above platform or edge
of tank at top of ladder.
• Ladder rungs at least ¾ inch square, or in diameter, and
spaced a maximum of 12 inches on center.
• Each rung must support 250 lbs.
• Shape of rungs should not cause slipping.
Cages for Fixed Ladders
• Cages extend ≥ 42 inches above top of landing
• Cages extend down to a point ≥ 7 feet or ≤ 8 feet above
base of ladder, with bottom flared ≥ 4 inches
• Cages extend 27 inches to 28 inches from centerline of rungs
of ladder.
• Cage shall be ≥ 27 inches wide.
• Ladder wells clear width of 15 inches measured each way
from centerline.
• Smooth walled wells minimum 27 inches from centerline of
rungs to well wall on climbing side.
Landing Platforms
• Landing platforms required for step distance greater than 12
inches from rung to nearest edge of structure
• Landing platforms require standard railings and toeboards.
• Platforms shall not be less ≥ 24 inches wide and ≥ 30 inches
long.
• Ladder extensions: side rails of through or sidestep ladder
extensions shall extend 3.5 feet above landings.
Top of Fixed Ladders
• Top rung even with roof or platform upon which climber will
first step when exiting the ladder.
• 7-12 inches step through distance between top rung and
platform or tank edge.
• WAC 296-876-60050: 24-30 inches step-through clearance
between ladder side rails, at top of ladder, unless ladder has a
ladder safety device, in which case width may be as wide as
36 inches.
• Where climbers pass through a hatch, ladders rails must
extend to minimum height of 42 inches or horizontal grab bars
must be provided to height of 42 inches.
• At top of ladder, railings required around ladder to prevent
exposure to falls while engaging/disengaging ladder safety
device.
Clearances
• Ladders without wells or cages must be at least 30 inches
from nearest permanent object on climbing side, measured
perpendicular to ladder from centerline of rungs.
• Where ladders pass through hatches, hatch cover should be
counterbalanced and, if so, must open at least 70 degrees
from horizontal.
• Inside clear width of hatch must be a nominal thirty inches.
• Distance from centerline of rungs to edge of hatch opening
on climbing side, measured perpendicular to ladders, must
be between 24 and 30 inches.
• If clearance on climbing side of ladder is between 24 and 27
inches, a deflector plate must be installed and mounted with
an angle of sixty degrees from horizontal.
Roof Hatches
• Access hatch on tank roof must either be surrounded by a
guard rail or opening must have a 4-inch tall curb around
perimeter and a secure access cover.
• Roof access opening ≥ 24 inches wide. Sides of access cover
must extend down over curb a minimum of 2 inches.
Fixed Stairs (Industrial) WAC-24-765
• Fixed stairs must carry a load five times normal live load
anticipated, but not less than a moving concentrated load of
1,000 pounds.
• Treads slip resistant and nosings of nonslip finish.
• Welded bar grating treads without nosings ok if leading edge is
readily identified by personnel descending stairway and tread
is serrated or of nonslip design.
• Riser height and tread width uniform on flight of stairs. Fixed
stairs ≥ 22 inches wide.
• Fixed stairs must have a rise and run per table D-1 of WAC 296-
24-76513.
• Stairs shall have stair railings on both open sides.
Railing & Toeboards WAC 296-24-75011
• Standard railing shall have of top rail, intermediate rail and
posts.
• Vertical height of 42 inches + 3 inches.
• Intermediate rail approximately half way between top rail
and floor.
• Pipe rails should be 1.5 inches nominal with posts not more
than 8 feet on center.
• Standard toeboard ≥ 4 inches in vertical height from top
edge to floor with ≤ ¼-inch clearance from floor.
• Top rail able to withstand 200 pound load applied in any
direction.
Fall Protection System
When workers are exposed to falls of 4 feet or more, WAC 296-
155-24609 requires a fall protection system consisting of one or
more of the following:
• Guardrail system
• Fall restraint system
• Safety net system
• Catch platform
• Warning line
Roof Safety
• For tank roof pitch > 4 in 12, WAC 296-155-24609 requires
installation of a permanent perimeter railing or, alternatively,
a fall restraint, fall arrest, or positioning device system must be
provided to prevent or arrest falls from tank roof.
• For roof pitch ≤ 4 in 12, employment of a safety monitor and
warning line system, or a safety watch system, may be used in
lieu of railing or fall protection, fall restraint, or positioning
device systems.
• Safety watch: Fall protection system in which a competent
person monitors one worker who is engaged in a repair work
or servicing equipment on a low pitched roof.
• Warning line system: Barrier to warn employees that are
approaching an unprotected fall hazard.
• Safety monitor or safety watch is problematic for work near
edge of tanks as these systems cannot prevent or arrest falls.
Fall Restraint Systems
• Fall restraint system: System in which all necessary
components function together to restrain/prevent an
employee from falling to a lower level, including standard
guard systems, personal fall restraint systems, warning systems,
or a warning line system and safety monitor.
• Personal fall restraint: Fall restraint system that is worn by
employee to arrest employee in a fall from elevation.
• Restraint protection will be rigged to allow movement of
employees only as far as sides and edges of walking/working
surface.
• To limit movement to not exceed edges of tanks roofs, static
lines must be custom sized for each tank and identified and
stored so users can readily identify correct static lines.
• Anchorage points used for fall restraint will be capable of
supporting 4 times the intended load.
Fall Arrest Systems
• Fall arrest system: Fall protection system that will arrest a fall
from elevation and include personal fall arrest systems worn
by user , catch platforms, and safety nets.
• Anchorage for a fall arrest system must be capable of
supporting 5,000 lbs (static weight).
• Anchorage for a fall arrest system must be capable of
supporting 3,000 lbs (static weight) when used in conjunction
with either a self-retracting lifeline that limits the maximum
free fall distances to two feet or less or a shock absorbing
lanyard that restricts the forces on the body to 900 lbs or less.
Positioning Device System
• Positioning device system: Full body harness or positioning
harness worn by an employee and rigged to allow an
employee to be supported on an elevated vertical or
inclined surface, such as a wall, pole or column and work with
both hands free from the body support.
• Rigged to prevent fall of greater than 2 feet.
• Anchorage capable of supporting 3,000 lbs (static weight) or
twice potential impact load, whichever is greater
Questions?

Weitere ähnliche Inhalte

Was ist angesagt?

Sp20 masonry design_and_construction
Sp20 masonry design_and_constructionSp20 masonry design_and_construction
Sp20 masonry design_and_construction
Mohd Danish
 
Demolition of building and its precautionary measures as per IS code
Demolition of building and its precautionary measures as per IS codeDemolition of building and its precautionary measures as per IS code
Demolition of building and its precautionary measures as per IS code
jaimin1702
 
Retaining walls
Retaining wallsRetaining walls
Retaining walls
Rahul
 
PRINCIPLE OF CONCRETE MIX DESIGN
PRINCIPLE OF CONCRETE MIX DESIGNPRINCIPLE OF CONCRETE MIX DESIGN
PRINCIPLE OF CONCRETE MIX DESIGN
Swarna Rajan
 
Underpinning presentation chakamba
Underpinning presentation  chakambaUnderpinning presentation  chakamba
Underpinning presentation chakamba
John Chakamba
 

Was ist angesagt? (20)

Basic plumbing manual
Basic plumbing manualBasic plumbing manual
Basic plumbing manual
 
Composite slab
Composite slabComposite slab
Composite slab
 
Deep excavation
Deep excavationDeep excavation
Deep excavation
 
Sp20 masonry design_and_construction
Sp20 masonry design_and_constructionSp20 masonry design_and_construction
Sp20 masonry design_and_construction
 
Demolition of building and its precautionary measures as per IS code
Demolition of building and its precautionary measures as per IS codeDemolition of building and its precautionary measures as per IS code
Demolition of building and its precautionary measures as per IS code
 
Earth retaining 2
Earth retaining 2Earth retaining 2
Earth retaining 2
 
Retaining walls
Retaining wallsRetaining walls
Retaining walls
 
PRINCIPLE OF CONCRETE MIX DESIGN
PRINCIPLE OF CONCRETE MIX DESIGNPRINCIPLE OF CONCRETE MIX DESIGN
PRINCIPLE OF CONCRETE MIX DESIGN
 
Formwork
FormworkFormwork
Formwork
 
Underpinning presentation chakamba
Underpinning presentation  chakambaUnderpinning presentation  chakamba
Underpinning presentation chakamba
 
Foundation and its types and detailed explanation
Foundation and its types and detailed explanationFoundation and its types and detailed explanation
Foundation and its types and detailed explanation
 
1.2 Diaphragm walls.pptx
1.2 Diaphragm walls.pptx1.2 Diaphragm walls.pptx
1.2 Diaphragm walls.pptx
 
Prestressed concrete circular storage tanks
Prestressed concrete circular storage tanksPrestressed concrete circular storage tanks
Prestressed concrete circular storage tanks
 
Unit 4 maintenance & repair methods for masonry mrs
Unit 4 maintenance & repair methods for masonry mrsUnit 4 maintenance & repair methods for masonry mrs
Unit 4 maintenance & repair methods for masonry mrs
 
Building superstructure
Building superstructureBuilding superstructure
Building superstructure
 
Repair techniques : Grouting (RR&S)
Repair techniques : Grouting (RR&S)Repair techniques : Grouting (RR&S)
Repair techniques : Grouting (RR&S)
 
Precast elements
Precast elementsPrecast elements
Precast elements
 
BCT MODULE 2 - Caisson
BCT MODULE 2 - CaissonBCT MODULE 2 - Caisson
BCT MODULE 2 - Caisson
 
Maintenance and repair strategies
Maintenance and repair strategiesMaintenance and repair strategies
Maintenance and repair strategies
 
Column & Footing details
Column & Footing detailsColumn & Footing details
Column & Footing details
 

Ähnlich wie 4 water storage tank safety standards

HSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdf
HSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdfHSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdf
HSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdf
patelalok2
 
Scaffold safety email
Scaffold safety emailScaffold safety email
Scaffold safety email
vtsiri
 
SCAFFOLDING Safety Training
SCAFFOLDING Safety TrainingSCAFFOLDING Safety Training
SCAFFOLDING Safety Training
William York
 

Ähnlich wie 4 water storage tank safety standards (20)

Walking and Working Surfaces by FHMIC
Walking and Working Surfaces by FHMICWalking and Working Surfaces by FHMIC
Walking and Working Surfaces by FHMIC
 
Scaffolds by Safety Resources
Scaffolds by Safety ResourcesScaffolds by Safety Resources
Scaffolds by Safety Resources
 
Scaffold and Aerial Lift Safety by KTA
Scaffold and Aerial Lift Safety by KTAScaffold and Aerial Lift Safety by KTA
Scaffold and Aerial Lift Safety by KTA
 
Scaffold And Aerial Lift Training by KTA
Scaffold And Aerial Lift Training by KTAScaffold And Aerial Lift Training by KTA
Scaffold And Aerial Lift Training by KTA
 
Highlights of OSHA’s scaffolding standard 1926
Highlights of OSHA’s scaffolding standard 1926 Highlights of OSHA’s scaffolding standard 1926
Highlights of OSHA’s scaffolding standard 1926
 
Scaffolding
ScaffoldingScaffolding
Scaffolding
 
Supported Scaffold Safety
Supported Scaffold SafetySupported Scaffold Safety
Supported Scaffold Safety
 
Scaffolding by UTK
Scaffolding by UTKScaffolding by UTK
Scaffolding by UTK
 
Fixed and Portable Ladders by NPCA
Fixed and Portable Ladders by NPCAFixed and Portable Ladders by NPCA
Fixed and Portable Ladders by NPCA
 
Scaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&IScaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&I
 
Scaffolding by chakamba j
Scaffolding by chakamba jScaffolding by chakamba j
Scaffolding by chakamba j
 
Wellhead and christmas tree components, functions and more
Wellhead and christmas tree components, functions and moreWellhead and christmas tree components, functions and more
Wellhead and christmas tree components, functions and more
 
wellheads-170105153648 (1).pdf
wellheads-170105153648 (1).pdfwellheads-170105153648 (1).pdf
wellheads-170105153648 (1).pdf
 
HSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdf
HSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdfHSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdf
HSE-9523-TECSM02-Safe-Scaffolding-01 06-SEP-2022.pdf
 
Scaffold safety email
Scaffold safety emailScaffold safety email
Scaffold safety email
 
SCAFFOLDING Safety Training
SCAFFOLDING Safety TrainingSCAFFOLDING Safety Training
SCAFFOLDING Safety Training
 
Scaffolding2. CO3.ppt
Scaffolding2. CO3.pptScaffolding2. CO3.ppt
Scaffolding2. CO3.ppt
 
Ladder safety
Ladder safetyLadder safety
Ladder safety
 
Trulift presentation
Trulift presentationTrulift presentation
Trulift presentation
 
Aramco scaffolding safety presentation -1.pptx
Aramco scaffolding safety presentation -1.pptxAramco scaffolding safety presentation -1.pptx
Aramco scaffolding safety presentation -1.pptx
 

Kürzlich hochgeladen

Kürzlich hochgeladen (20)

04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Tech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfTech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdf
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUnderstanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 

4 water storage tank safety standards

  • 1. PNWS AWWA 2015 Conference Presented By: Tim Tobin, PE 425.289.7371 May 1, 2015 Water Storage Tank Safety Standards
  • 2. Scope of Presentation •Manholes for interior access •Fixed ladders for access to tank roofs •Fixed stairs (industrial) with railings for steep roof access •Railings and toeboards •Roof safety •Fall restraint, fall arrest, and positioning device systems
  • 3. Goals for this Presentation •Describe regulations and standards governing the configuration of tank access and safety features •To stimulate thought regarding your reservoirs versus current safety regulations and standards •To motivate you to look critically at your facilities •Where to look for standards and regulations
  • 4. Caveats • Just because a facility doesn’t meet current regulations and standards doesn’t necessarily mean it’s unsafe and requires immediate modification – but it should be consciously evaluated by a “competent person” or a “qualified person”. • This content is introductory only – see regulations • Abbreviated information on slides
  • 5. Organization of this Presentation • Applicable regulations, standards, and references • Manholes • Fixed ladders • Landings • Railings • Roof access hatches • Roof stairway • Fall restraint, fall arrest, and positioning device systems
  • 6. WISHA Regulations • OSHA is the federal Occupational Safety and Health Administration • WISHA is Washington State’s version of OSHA • WISHA regulations govern in State of Washington except for federal facilities, floating worksites, tribal lands • WISHA regulations are found in RCW 49.17. • WISHA implementing rules are found in WAC Chapter 296 • WAC Chapter 296 is L&I’s safety and health requirements for employers.
  • 7. WAC Chapter 296 Regulations WAC 296-24, Part J-1, - Working Surfaces, Guarding Floors and Wall Openings • WAC 296-24-75011 - Railing, toe boards and cover specifications • WAC 296-24-765 – Fixed industrial stairs • WAC 296-24-810 – Fixed ladders
  • 8. • WAC 296-155, Part C-1 – Fall Protection Requirements for Construction - Safety standards for construction work, defined as construction, alteration, related inspection, and or maintenance and repair work, including painting. • WAC 296-876 – Ladders, Portable and Fixed WAC Regulations Continued
  • 9. Applicable Standards • AWWA D100-11, Welded Carbon Steel Tanks for Water Storage: This standard applies to design of welded steel reservoirs and standpipes. • AWWA D110-04, Prestressed Concrete Water Tanks • ANSI A14.3, American National Standard for Ladders-Fixed-Safety Requirements
  • 10. Additional References • Fixed Ladders and Climbing Protection Devices, National Safety Council Data Sheet 606 Rev. August 2007 • US Army Corps of Engineers Safety and Health Requirements Manual, Appendix J (EM 385-1-1, Appendix J)
  • 11. Tank Shell Manholes • AWWA D100: a minimum of 2 round or elliptical shell manholes within first ring. • Each a minimum of 24 inches in diameter or 18” x 22” elliptical. • One shell manhole at least 30 inches in diameter. • If hatch weighs more than 50 lbs, then a davit or hinges are required
  • 12.
  • 13. Ladder Definitions • “Fixed Ladder” – is a ladder permanently attached to a structure. • “Through ladder” – is a ladder from which a person getting off on top must step through the ladder in order to reach the landing. • “Side Step Ladder” - a side step ladder is one from which a person getting off at the top must step sideways from the ladder in order to reach the landing. • “Cage” - is an enclosure that is fastened to the side rails of the fixed ladder part of the structure to encircle the climbing space of the ladder for safety. • “Well” - is a permanent complete enclosure around a fixed ladder, which is attached to the walls of the well. • “Ladder safety device” - is any device, other than a cage or well, designed to eliminate or reduce the possibility of accidental falls and which incorporate such features as life belts, friction brakes, and sliding attachments.
  • 14. Ladder Length Restrictions • WAC 296-876-60065: fixed ladders over 24 feet in height, on the exterior and interior of the tanks, must be equipped with cages, wells or a ladder safety device. • WAC 296-876-60065: no length of fixed ladder shall exceed 50 feet, except when a ladder safety device is installed. • Landing Platforms are required every 30 feet, except where no cage, well, or ladder safety device is provided, landing platforms shall be provided at each 20 feet of height or fraction thereof. • Each ladder section shall be offset from all adjacent sections.
  • 15. Requirements for Fixed Ladders • Ladder side rails must be uniform for the full length and easy to grasp. • Per AWWA 100-05, flat steel bar side rails must be at least 2.0 inch wide by 3/8” thick. • At least 16 inches of clear space between ladder side rails, except at the top of the ladder. • Both side rails must extend 42 inches above platform or edge of tank at top of ladder. • Ladder rungs at least ¾ inch square, or in diameter, and spaced a maximum of 12 inches on center. • Each rung must support 250 lbs. • Shape of rungs should not cause slipping.
  • 16.
  • 17. Cages for Fixed Ladders • Cages extend ≥ 42 inches above top of landing • Cages extend down to a point ≥ 7 feet or ≤ 8 feet above base of ladder, with bottom flared ≥ 4 inches • Cages extend 27 inches to 28 inches from centerline of rungs of ladder. • Cage shall be ≥ 27 inches wide. • Ladder wells clear width of 15 inches measured each way from centerline. • Smooth walled wells minimum 27 inches from centerline of rungs to well wall on climbing side.
  • 18. Landing Platforms • Landing platforms required for step distance greater than 12 inches from rung to nearest edge of structure • Landing platforms require standard railings and toeboards. • Platforms shall not be less ≥ 24 inches wide and ≥ 30 inches long. • Ladder extensions: side rails of through or sidestep ladder extensions shall extend 3.5 feet above landings.
  • 19.
  • 20. Top of Fixed Ladders • Top rung even with roof or platform upon which climber will first step when exiting the ladder. • 7-12 inches step through distance between top rung and platform or tank edge. • WAC 296-876-60050: 24-30 inches step-through clearance between ladder side rails, at top of ladder, unless ladder has a ladder safety device, in which case width may be as wide as 36 inches. • Where climbers pass through a hatch, ladders rails must extend to minimum height of 42 inches or horizontal grab bars must be provided to height of 42 inches. • At top of ladder, railings required around ladder to prevent exposure to falls while engaging/disengaging ladder safety device.
  • 21.
  • 22.
  • 23. Clearances • Ladders without wells or cages must be at least 30 inches from nearest permanent object on climbing side, measured perpendicular to ladder from centerline of rungs. • Where ladders pass through hatches, hatch cover should be counterbalanced and, if so, must open at least 70 degrees from horizontal. • Inside clear width of hatch must be a nominal thirty inches. • Distance from centerline of rungs to edge of hatch opening on climbing side, measured perpendicular to ladders, must be between 24 and 30 inches. • If clearance on climbing side of ladder is between 24 and 27 inches, a deflector plate must be installed and mounted with an angle of sixty degrees from horizontal.
  • 24.
  • 25. Roof Hatches • Access hatch on tank roof must either be surrounded by a guard rail or opening must have a 4-inch tall curb around perimeter and a secure access cover. • Roof access opening ≥ 24 inches wide. Sides of access cover must extend down over curb a minimum of 2 inches.
  • 26.
  • 27. Fixed Stairs (Industrial) WAC-24-765 • Fixed stairs must carry a load five times normal live load anticipated, but not less than a moving concentrated load of 1,000 pounds. • Treads slip resistant and nosings of nonslip finish. • Welded bar grating treads without nosings ok if leading edge is readily identified by personnel descending stairway and tread is serrated or of nonslip design. • Riser height and tread width uniform on flight of stairs. Fixed stairs ≥ 22 inches wide. • Fixed stairs must have a rise and run per table D-1 of WAC 296- 24-76513. • Stairs shall have stair railings on both open sides.
  • 28. Railing & Toeboards WAC 296-24-75011 • Standard railing shall have of top rail, intermediate rail and posts. • Vertical height of 42 inches + 3 inches. • Intermediate rail approximately half way between top rail and floor. • Pipe rails should be 1.5 inches nominal with posts not more than 8 feet on center. • Standard toeboard ≥ 4 inches in vertical height from top edge to floor with ≤ ¼-inch clearance from floor. • Top rail able to withstand 200 pound load applied in any direction.
  • 29. Fall Protection System When workers are exposed to falls of 4 feet or more, WAC 296- 155-24609 requires a fall protection system consisting of one or more of the following: • Guardrail system • Fall restraint system • Safety net system • Catch platform • Warning line
  • 30. Roof Safety • For tank roof pitch > 4 in 12, WAC 296-155-24609 requires installation of a permanent perimeter railing or, alternatively, a fall restraint, fall arrest, or positioning device system must be provided to prevent or arrest falls from tank roof. • For roof pitch ≤ 4 in 12, employment of a safety monitor and warning line system, or a safety watch system, may be used in lieu of railing or fall protection, fall restraint, or positioning device systems. • Safety watch: Fall protection system in which a competent person monitors one worker who is engaged in a repair work or servicing equipment on a low pitched roof. • Warning line system: Barrier to warn employees that are approaching an unprotected fall hazard. • Safety monitor or safety watch is problematic for work near edge of tanks as these systems cannot prevent or arrest falls.
  • 31.
  • 32. Fall Restraint Systems • Fall restraint system: System in which all necessary components function together to restrain/prevent an employee from falling to a lower level, including standard guard systems, personal fall restraint systems, warning systems, or a warning line system and safety monitor. • Personal fall restraint: Fall restraint system that is worn by employee to arrest employee in a fall from elevation. • Restraint protection will be rigged to allow movement of employees only as far as sides and edges of walking/working surface. • To limit movement to not exceed edges of tanks roofs, static lines must be custom sized for each tank and identified and stored so users can readily identify correct static lines. • Anchorage points used for fall restraint will be capable of supporting 4 times the intended load.
  • 33. Fall Arrest Systems • Fall arrest system: Fall protection system that will arrest a fall from elevation and include personal fall arrest systems worn by user , catch platforms, and safety nets. • Anchorage for a fall arrest system must be capable of supporting 5,000 lbs (static weight). • Anchorage for a fall arrest system must be capable of supporting 3,000 lbs (static weight) when used in conjunction with either a self-retracting lifeline that limits the maximum free fall distances to two feet or less or a shock absorbing lanyard that restricts the forces on the body to 900 lbs or less.
  • 34. Positioning Device System • Positioning device system: Full body harness or positioning harness worn by an employee and rigged to allow an employee to be supported on an elevated vertical or inclined surface, such as a wall, pole or column and work with both hands free from the body support. • Rigged to prevent fall of greater than 2 feet. • Anchorage capable of supporting 3,000 lbs (static weight) or twice potential impact load, whichever is greater