Vi binh jaydeep_team_ele-791 control of distributed generation - team project
1. Single Phase to Ground Fault
Current in Three Phase Inverter with
Balanced and Unbalanced Load
Presented By
Jaydeep Satyajit Sathe & Vi Binh Quang Le
ELE-791 Control of Distributed Generation
Syracuse University
April 19, 2017
2. Outline
Introduction
Technical Background of Inverters
Inverters Applications
Advantages and Disadvantages of Inverters
Inverter for Current Ground Fault
Simulation and Results
Conclusions and Future Research
References
Vi Binh Quang Le & Jaydeep Satyajit Sathe 24/19/2017
3. Introduction
Inverter is an electronic device, which
converts direct current (DC) input to
alternating current (AC) output and
also known as DC-AC converter.
Due to the problem of dependent on
nonrenewable fossil fuels, a demand
of a development of renewable
energy (clean power) is significant.
Thus, inverters are used as interface
between power generators (wind,
solar, hydro, etc.) and the distribution
grid to maintain the stability,
reliability, controllability, and
efficiency of the grid. [1]
Vi Binh Quang Le & Jaydeep Satyajit Sathe 34/19/2017
4. Technical Background of Inverter
Inverter technology was initially
found by Toshiba Corporation in
1980s, and the technology is still
applied widely in industries,
especially to the renewable
energy filed.
Basic structure of inverter
device consists of multiple
transistors as displayed in the
figure on the side.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 44/19/2017
5. Technical Background of Inverter (Cont.)
Single Phase Inverter : this inverter
circuit consists of two transistors Q1
and Q2 and two diodes connected as
on the diagram. Q1 and Q2 are in
turn on and off to generate a voltage
Vo = Vs/2 cross the load. This is also
known as Half Bridge Inverter. [2]
Application: H-bridge inverter is used
to convert 12 Vdc into a 120 Vac
square wave using a transformer with
a 10:1 turns ratio [7]
Vi Binh Quang Le & Jaydeep Satyajit Sathe 54/19/2017
6. Technical Background of Inverter (Cont.)
Three phase inverter: it is used
for energy processing of PV and
wind power.
A three-phase inverter has three
legs, one for each phase. Each
inverter leg operates as a single-
phase inverter.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 64/19/2017
7. Inverter Applications
Solar power
Fuel cell (FC) plants
Wind turbines and microturbines
Power-hydro
Variable-frequencies drives
Uninterruptible power supplies
Electronic ballasts and induction heater
Storage devices as local energy sources
Vi Binh Quang Le & Jaydeep Satyajit Sathe 74/19/2017
8. Advantages and Disadvantages of Inverters in
Solar Energy
String Inverters
Advantages
Lower cost
Easier to install and maintain
Disadvantages
Problem if one panel fail, the
entire string fail
Difficult to fix
Occupy more space
Vi Binh Quang Le & Jaydeep Satyajit Sathe 84/19/2017
9. Advantages and Disadvantages of Inverters in
Solar Energy (Cont.)
Micro Inverter
Advantages
All panels are independent, failure
of one panel will not impact other
Easy to fix and maintain
Occupy less space
Disadvantages
High cost
Difficult to install and maintain
Vi Binh Quang Le & Jaydeep Satyajit Sathe 94/19/2017
10. Inverters for Ground Fault Current in
Microgrid
What is the inverters for ground fault current in microgrid?
Ground fault current in microgrid is technically abnormal current. This could
be one or all the currents in the single or three phase of the inverter in the
distributed grid (also known as a short circuit).
In order to protect the components devices in the grid systems, inverters are
required to limit their fault current capability. This is accomplished through
reduction in the internal voltage during faults. [6]
Possibility methods of controlling the ground fault current
Fault behavior of an inverter is determined by its control, which in turn is
based on the inverter topology (three phase three wire, three phase four
wire, single phase) and topology of the network to which the inverter is
connected as balanced or unbalanced load).
Vi Binh Quang Le & Jaydeep Satyajit Sathe 104/19/2017
11. Inverters for Ground Fault Current in
Microgrid (Cont.)
Techniques used to control in single phase and three phase inverters
can be broadly divided into the following three categories [6]:
• Control in synchronously rotating dq0 reference frame
• Control in stationary frame
• Control in natural reference frame
Control in rotating reference frame is the most popular approach where
measured output voltages and currents are transformed into their equivalent
by rotating frame dq0 of reference [6]
In this presentation, observing the effects on the inverter output
current due to a single phase to ground fault with balanced and
unbalanced loads will be analyzed
Vi Binh Quang Le & Jaydeep Satyajit Sathe 114/19/2017
12. Inverters for Ground Fault Current in
Microgrid (Cont.)
A single phase ground to fault in the three phase inverter with
balanced load
• In this stage, the inverter is implement with parameters described in the
gain.m file (which was attached to the research report)
A single phase ground to fault in the three phase inverter with
unbalanced load. In this case, the parameters used in the simulation
have been chosen as follows:
• Current limit is set to 110% of the inverter peak current limit
• Three unbalanced loads:
o Phase A : 50 kVA
o Phase B : 20 kVA
o Phase C : 5 kVA
Vi Binh Quang Le & Jaydeep Satyajit Sathe 124/19/2017
14. Our results have 3 partsPart 1
We observe the effects of a single phase fault in phase A (short
circuited to ground) for two cases – with balanced load and with
unbalanced load. Here we set inverter current limit to be constant at
300%, and Rsc (short-circuit resistance) to be constant at 1%.
Part 2
We change the inverter current limit to 110%, 300% and 562% and
observe the effects of the single phase fault on the inverter current. We
do this for balanced and unbalanced loads. We set Rsc to be constant
at 1%.
Part 3
We change the values of Rsc to 1%, 7.5% and 15% and observe its
effects on the inverter currents and voltages. We do this for balanced
load, and we set current limit to be constant at 300%.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 144/19/2017
15. Part 1(A) – Balanced load, Phase A fault
Iinv: Phase A, B, C load = 80 KVA
Vi Binh Quang Le & Jaydeep Satyajit Sathe 154/19/2017
19. Part 1(B) – Unbalanced load, Phase A Fault
Phase A load: 50 KVA, Phase B load = 20 KVA, Phase C load = 5 KVA
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 194/19/2017
23. Part 1 Conclusion
The waveforms observed are as expected, and the main difference
between Part 1(A) and Part 1(B) is the balanced and unbalanced loads.
In both cases, when phase A is shorted with the ground:
The I inv current for phases B and C increases and reaches the inverter
current limit, but that for phase A remains the same.
The V inv voltage for phase C decreases, but that for phases A and C
remains almost the same.
The I load for phase A increases, but that for phases B and C remains the
same.
The V load voltage for phase A decreases significantly, but that for phases
B and C increases slightly.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 234/19/2017
24. Part 2 – Changing Inverter Current Limits
For I limit = 110% = 293.2722 A, Balanced load
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 244/19/2017
25. I limit = 110% = 293.2722 A, Unbalanced load
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 254/19/2017
26. I limit = 300% = 799.8334 A, Balanced load
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 264/19/2017
27. I limit = 300% = 799.8334 A, Unbalanced load
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 274/19/2017
28. I limit = 562% = 1500 A, Balanced load
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 284/19/2017
29. I limit = 562% = 1500 A, Unbalanced load
Iinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 294/19/2017
30. Part 2 Conclusion
From Part 2, we observe that if phase A is shorted with the ground:
The Iinv for phase A remains almost the same (except for the effect of
harmonics), but the Iinv for phases B and C reach the inverter current
limit.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 304/19/2017
31. Part 3 – Changing Rsc valuesRsc = 1% = 0.01
V inv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 314/19/2017
32. I load
Vi Binh Quang Le & Jaydeep Satyajit Sathe 324/19/2017
33. V load:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 334/19/2017
34. Rsc = 7.5% = 0.075
V inv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 344/19/2017
35. I load:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 354/19/2017
36. V load:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 364/19/2017
37. Rsc = 15% = 0.15
Vinv:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 374/19/2017
38. I load:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 384/19/2017
39. V load:
Vi Binh Quang Le & Jaydeep Satyajit Sathe 394/19/2017
40. Part 3 Conclusion
From Part 3, we observe that when Rsc is increased:
The V inv voltage for phase C increases, but that for phases A and C
remains the same.
The I load for phase A decreases, but that for phases B and C remains
the same.
The V load voltage for phase A increases, but that for phases B and C
remains the same.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 404/19/2017
41. Future Work
Based on the simulation results, appropriate fault models and
protection systems for such microgrid will be developed and tested.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 414/19/2017
42. References
[1] Ali Keyhani, Mohammad N. Marwali, Min Dai, “ Integration of
Green and Renewable Energy in Electric Power Systems,” 2010 by
John Wiley & Sons, Inc. pg 1-4
[2] Manoj Kumar Swami, “ Inverter,” www.slideshare.net
[3] Eric Glover, Studen Member, IEEE, Chung-Ching Chang, Student
Member, IEEE, Dimitry Gorinevsky*, Fellow, IEEE, and Sanjay Lall,
Senior Member, IEEE, “Frequency Stability for Distribued
Generation Connected through Grid-Tie Inverter,” IEEE International
Conference on Power System Technology (POWERCON), 2012
[4] P. Bhanu Teja, “Advancements in Inverter Technology,” National
Institute of Technology Calicut, www.slideshare.net
Vi Binh Quang Le & Jaydeep Satyajit Sathe 424/19/2017
43. References (Cont.)
[5] Dr. Tomislav Bujanovic, “ELE 791 Control of Distributed
Generation,” Modeling of Power Converter, Department of
Electrical Engineering and Computer Science, Syracuse University
[6] S.P. Plkharel, Satish Ranade, “Modeling and Simulation of Three
Phase Inverter for Fault Study of Microgrids,” Conference Paper,
September 2012
[7] Jim Dunlop Solar, “Inverter,” Definitions and Terminology∙Types and
Applications ∙ Functions and Features ∙ Selection and Sizing
∙Monitoring and Communications, 2012
[8] “History of Inverter Technology,” Mitsubishi, Heavy Industries, LTD.
Vi Binh Quang Le & Jaydeep Satyajit Sathe 434/19/2017
Hello everyone!
I’m Binh Le from Texas state.
I was assigned with Jaydeep to do this project, the Single Phase to Ground Fault Current in Three Phases Inverter with Balanced and Unbalanced Load. So, what does Single phase to ground fault current mean? This means one of the three phase inverter has its current going wrong, abnormal. And what balanced and unbalanced load. Balance load means all the three have the same loads, and unbalanced load means the three loads of the inverter are not equal.
Ok, let’s start it. In this Outline, I will talk about the introduction, technical background of inverter, inveters applications, advantages and disadvantages, and inverter with current fault. And Jaydeep will take care of the rest.
Inverter is an electronic device that takes in dc and gives output as ac. Inverter is also known as dc-ac converter.
Inverter is used as an interface between power generator and the distribution grid to keep the grid stable, reliable, controllable, and efficient.
About technical background of inverter, inverter technology was 1st come in 1981 by Toshiba corporation and this technology is still applied vastly in industries and especially in the renewable energy filed. My research has indicated that all inverters have been constructed by many transistors. This picture is one the ones.
Inverter can be divided into two groups: single inverter and three phase inverters. The Single-phase inverter is constructed like this. Here, Q1 and Q2 are alternatively turn on and off, not on or off at the same time. Depend on either Q1 on or Q2 on, the circuit will generate a voltage Vsource/2 of the C1 or C2 be generated. The inverter with this configuration is known as Half-bridge inteverter. Hafl-bridge inverter is applied to convert 12-volt dc into 120-volt ac by using a transformer with a 10:1 turn ratio.
The second popular type of inverter is called three phase inverters, and this has three legs, one leg for each phase. Each leg operates as a single-phase inverter. This three-phase inverter is used for solar energy and wind power.
Inverter applications. Here are some of the applications of the inverter
Inverter applications. Here are some of the applications of the inverter. The applications of the inverter have its advantages and disadvantages. Here, I just talk about the advance and disadvantage of the string inverter in PV energy.
Inverter applications. Here are some of the applications of the inverter. The applications of the inverter have its advantages and disadvantages. Here, I just talk about the advance and disadvantage of the Micro inverter in PV energy.
Inverters for ground fault current in microgrid. As I have mentioned on the first slide, ground fault current is abnormal current in the grid. It could damage the components in the grid if we don’t recognize it by observing the output signal. One of the benefits of knowing the abnormal current is that we can adjust the voltage of the inverter to prevent the component from the damage due to the short circuit. My research has shown that there are three ways to control the single phase and three phase in inverter:
Control in synchronously rotating dq0 reference frame
Control in stationary frame
Control in natural reference frame
In the three methods above, the 1st one is the most like it.
Inverters for ground fault current in microgrid. As I have mentioned on the first slide, ground fault current is abnormal current in the grid. It could damage the components in the grid if we don’t recognize it by observing the output signal. One of the benefits of knowing the abnormal current is that we can adjust the voltage of the inverter to prevent the component from the damage due to the short circuit. My research has shown that there are three ways to control the single phase and three phase in inverter:
Control in synchronously rotating dq0 reference frame
Control in stationary frame
Control in natural reference frame
In the three methods above, the 1st one is the most like it.
As I understand in this class, we use the dq0 reference frame technique to simulate the inverter. In our project, for the balanced load, we use the parameters given in the Gain.m file to run simulations and to observe the output of current inverter, voltage inverter, and voltage of the loads. And for the unbalanced load, we set the current limit to 110% instead of 300% given the Gain.m file. We also set the load unequally to the three phases: Phase A 50 kVA, Phase B 20 kVA, and phase C 5 kVA.
Now, it is the simulation and result. This is very interested part of our project and Jaydeep will talk with us about this one. Before Jaydeep starts, do you have questions for me?
If not, I’m done. Thank you! Jaydeep, are you ready?