11. Branch A, Station 7, 34 feet in
Clay Pipe and yard drain in poor condition with exposed rebar.
12. Branch A, Station 7, 88 feet in
12â Concrete pipe in good condition with low flow. A poor seal
around the bottom of the pipe is causing minor infiltration.
13. Branch A, Station 8, 4 feet in
Pipe joint with minor spalling and exposed rebar.
14. Branch A, Station 8, 22 feet in
4â PVC pipe in good condition with no flow.
15. Branch A, Station 8, 44 feet in
Pipe joint with minor spalling at joint.
16. Branch A, Station 8, 90 feet in
15â Concrete pipe in good condition with low flow. A poor seal
around the pipe is causing some minor infiltration.
17. Branch A, Station 8, 95 feet in
15â concrete pipe in good condition with low flow. A poor seal around the connection causes minor
infiltration. Some exposed rebar is also apparent.
18. Branch A, Station 9, 50 feet in
Cast iron pipe in good condition with low flow. A poor seal around
the pipe causes some minor infiltration.
19. Branch A, Station 10, 8 feet in
Pipe joint with minor spalling around the joint itself.
20. Branch A, Station 10, 75 feet in
12â Concrete pipe in good condition with low flow but minor
infiltration.
21. Branch A, Station 13, 83 feet in
42â concrete pipe in good condition with low flow.
22. Branch A, Station 13, 95 feet in
18â concrete pipe in good condition with low flow and minor
infiltration at the bottom of the pipe.
23. Branch A, Station 14, 32 feet in
12â concrete pipe is bulk-headed with no flow. Exposed rebar is
apparent as well as evidence of infiltration around pipe connection.
25. Branch A, Station 17, 34 feet in
Beehive inlet with poor seal and exposed rebar.
26. Branch A, Station 18, 53 feet in
Beehive inlet with poor seal around casting and vegetation over
grate.
27. Branch A, Station 21, 70 feet in
12â concrete pipe in good condition with slight flow. Mineral
deposits have built up at the discharge point.
28. Branch A, Station 23, 94 feet in
18â bulk headed inlet in good condition
29. Branch A, Station 23, 94 feet in
18â bulk headed inlet in good condition
30. Branch A, Station 24, 3 feet in
12â Concrete pipe in good condition. However there is a poor connection because the pipe is partially
blocked due to an insufficient cut into the main. Exposed rebar is apparent.
31. Branch A, Station 25, 34 feet in
12â clay pipe in poor condition, offset joint, no flow. Poor connection with exposed rebar.
32. Branch A, Station 28, 91 feet in
15â Concrete pipe in good condition with low flow. Mineral deposit build up at discharge point.
33. Branch A, Station 28, 91 feet in
12â Concrete pipe in good condition with slight flow.
34. Branch A, Station 32, 54 feet in
Junction chamber in good condition; concrete block
35. Branch A, Station 32, 54 feet in
Junction chamber in good condition; concrete block
49. Branch C, Station 1, 83 feet in
Inlet in good condition with low flow. Minor sediment at inlet
and debris on grate are apparent.
50. Branch C, Station 1, 83 feet in
Inlet in good condition with low flow. Minor sediment at inlet
and debris on grate are apparent.
51. Branch âDâ Inspection
Branch D is reinforced concrete pipe 60â in diameter. All pipe
joints are in good condition with no spalling of the main.