SlideShare ist ein Scribd-Unternehmen logo
1 von 38
CHAPTER I 
INTRODUCTION 
1.1 INTRODUCTION 
Our Power system is a large interconnected system, which consisting of 
Generators, transformers, transmission and distribution circuits, it is inevitable that 
sooner or later some failure will occur somewhere in the system. When a failure 
occurs on any part of the system, it must be quickly detected and disconnected from 
the system. 
There are Principal reasons for it: 
 Firstly, if the fault is not cleared quickly, it may cause unnecessary 
interruption of service to the customers. 
 Secondly, rapid disconnection of faulted apparatus limits the amount of 
damage to it and prevents the effects of the fault from spreading into the 
system. 
 A Protective relay is a device that detects the fault and initiates the 
operation of the circuit breaker to isolate the defective element from the 
rest of the system. 
Hence the Role of the circuit breaker play a major role in the power system 
interconnected system 
1.2 CIRCUIT BREAKER 
A circuit breaker is an automatically operated electrical switch designed to 
protect an electrical circuit from damage caused by overload or short circuit. Its 
basic function is to detect a fault condition and interrupt current flow. Unlike a fuse, 
which operates once and then must be replaced, a circuit breaker can be reset (either 
manually or automatically) to resume normal operation. Circuit breakers are made in 
varying sizes, from small devices that protect an individual household appliance up 
to large switchgear designed to protect high voltage circuits feeding an entire city. 
SCITS, KARIMNAGAR 1 DEPARTMENT OF EEE
The modern power system deals with huge power network and huge 
numbers of associated electrical equipment. During short circuit fault or any other 
types of electrical fault these equipment as well as the power network suffer a high 
stress of fault current in then which may damage the equipment and networks 
permanently. For saving these equipment and the power networks the fault current 
should be cleared from the system as quickly as possible. Again after the fault is 
cleared, the system must come to its normal working condition as soon as possible 
for supplying reliable quality of power to receiving ends. In addition to that for 
proper controlling of power system, different switching operations are required to be 
performed. So for timely disconnecting and reconnecting different parts of power 
system network for protection and control, there must be some special type of 
switching devices which can be operated safely under huge current carrying 
condition, During interruption of huge current, there would be large arcing in 
between switching contacts, so care should be taken to quench these arcs in circuit 
breaker in safe manner .The circuit breaker is the special device which does all the 
required switching operations during current carrying condition. This was the basic 
Introduction to Circuit Breaker. 
Circuit breakers are a piece of electrical device that 
1. Make or break a circuit either manually or by remote control under 
normal conditions. 
2. Break a circuit automatically under fault conditions. 
3. Make a circuit either manually or by remote control under fault 
conditions. 
SCITS, KARIMNAGAR 2 DEPARTMENT OF EEE
CHAPTER II 
CIRCUIT BREAKERS 
2.1 INTRODUCTION 
Circuit Breaker is a critical component of an electrical system they are 
used to connect and disconnect transmission lines under normal operating conditions. 
They are also used to a clear section of transmission grid should a short circuit occur 
in the system, isolating the fault. The technology of circuit breaker evolved based on 
primarily on the media in which the circuit breaker contacts are located. Every circuit 
breaker used a dielectric media. When system voltages and current levels increased 
oil circuit breakers are introduced later compressed air circuit breakers are developed 
followed by SF6 and working breakers which is preferred technology for high voltage 
circuit breaker. 
The main purpose of a circuit breaker is to: 
 Switch load currents 
 Make on to a fault 
 Break normal and fault currents 
 Carry fault currents without blowing itself open. 
The important characteristics from a protection point of view are: 
 The speed with which the main current is opened after a tripping impulse is 
received. 
 The capacity of the circuit that the main contacts are capable of interrupting 
(rupturing capacity). 
 The first characteristics are referred to as the ‘tripping time’ and are expressed 
in cycles. 
 Modern high speed circuit breakers having tripping times between 3 to 8 
cycles. 
SCITS, KARIMNAGAR 3 DEPARTMENT OF EEE
The Tripping or total clearing or breaking time is made up as follows: 
 Opening time: the time between instant of application of tripping power to the 
instant of separation of the main contacts. 
 Arcing time: the time between the instant of separation of the main circuit breaker 
contacts to the instant of arc extinction of short circuit current. 
 Total break or clearing time: The sum of the above (opening time + Arcing 
time). 
Some of the manufacturers are ABB, Alstom, General Electric, Hitachi, HYOSUNG 
(HICO), Hyundai Heavy Industry (HHI), Mitsubishi Electric, Pennsylvania Breaker, 
Siemens, Toshiba, Končar HVS, BHEL, CGL, and Becker/SMC (SMC Electrical 
Products). 
Fig 2.1 Fault Clearing Time 
SCITS, KARIMNAGAR 4 DEPARTMENT OF EEE
2.1.1 ORIGIN 
An early form of circuit breaker was described by Thomas Edison in an 
1879 patent application, although his commercial power distribution system used 
fuses. Its purpose was to protect lighting circuit wiring from accidental short-circuits 
and overloads. A modern miniature circuit breaker similar to the ones now in use was 
patented by Brown, Boveri & Cie in 1924. Hugo Stotz, an engineer who had sold his 
company, to BBC, was credited as the inventor on DRP (Deutsches Reichspatent). 
Stotz's invention was the forerunner of the modern thermal-magnetic breaker 
commonly used in household load centers to this day. 
Interconnection of multiple generator sources into an electrical grid 
required development of circuit breakers with increasing voltage ratings and 
increased ability to safely interrupt the increasing short circuit currents produced by 
networks. Simple air-break manual switches produced hazardous arcs when 
interrupting high currents; these gave way to oil-enclosed contacts, and various forms 
using directed flow of pressurized air, or of pressurized oil, to cool and interrupt the 
arc. By 1935, the specially constructed circuit breakers used at the Boulder Dam 
project use eight series breaks and pressurized oil flow to interrupt faults of up to 
2,500 MVA, in three cycles of the AC power frequency. 
2.1.2 SHORT CIRUIT CURRENT 
Circuit breakers are rated both by the normal current that they are 
expected to carry, and the maximum short-circuit current that they can safely interrupt. 
Under short-circuit conditions; the calculated maximum prospective short 
circuit current may be many times the normal, rated current of the circuit. When 
electrical contacts open to interrupt a large current, there is a tendency for an arc to form 
between the opened contacts, which would allow the current to continue. This condition 
can create conductive ionized gases and molten or vaporized metal, which can cause 
further continuation of the arc, or creation of additional short circuits, potentially 
resulting in the explosion of the circuit breaker and the equipment that it is installed in. 
SCITS, KARIMNAGAR 5 DEPARTMENT OF EEE
Therefore, circuit breakers must incorporate various features to divide and extinguish the 
arc. 
In air-insulated and miniature breakers an arc chutes structure consisting (often) of 
metal plates or ceramic ridges cools the arc, and magnetic blowout coils deflect the arc 
into the arc chute. Larger circuit breakers such as those used in electrical power 
distribution may use vacuum, an inert gas such as sulfur hexafluoride or have contacts 
immersed in oil to suppress the arc. 
The maximum short-circuit current that a breaker can interrupt is determined by 
testing. Application of a breaker in a circuit with a prospective short-circuit current 
higher than the breaker's interrupting capacity rating may result in failure of the 
breaker to safely interrupt a fault. In a worst-case scenario the breaker may 
successfully interrupt the fault, only to explode when reset. 
MCB used to protect control circuits or small appliances may not have sufficient 
interrupting capacity to use at a panel board; these circuit breakers are called 
"supplemental circuit protectors" to distinguish them from distribution-type circuit 
breakers. 
2.1.3 ARC INTERRUPTION 
Low-voltage MCB uses air alone to extinguish the arc. Larger ratings have metal 
plates or non-metallic arc chutes to divide and cool the arc. Magnetic blowout coils or 
permanent magnets deflect the arc into the arc chute. 
In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to 
blast a jet of oil through the arc. 
Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using 
a magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride 
(SF6) to quench the stretched arc. 
SCITS, KARIMNAGAR 6 DEPARTMENT OF EEE
Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other 
than the contact material), so the arc quenches when it is stretched a very small 
amount (less than 2–3 mm (0.079–0.118 in)). Vacuum circuit breakers are frequently 
used in modern medium-voltage switchgear to 38,000 volts. 
Air circuit breakers may use compressed air to blow out the arc, or alternatively, 
the contacts are rapidly swung into a small sealed chamber, the escaping of the 
displaced air thus blowing out the arc. 
Circuit breakers are usually able to terminate all current very quickly: typically 
the arc is extinguished between 30 ms and 150 ms after the mechanism has been 
tripped, depending upon age and construction of the device. 
2.1.4 STANDARD CURRENT RATINGS 
Circuit breakers are manufactured in standard sizes, using a system of preferred 
numbers to cover a range of ratings. Miniature circuit breakers have a fixed trip 
setting; changing the operating current value requires changing the whole circuit 
breaker. Larger circuit breakers can have adjustable trip settings, allowing 
standardized elements to be applied but with a setting intended to improve protection. 
For example, a circuit breaker with a 400 ampere "frame size" might have its over 
current detection set to operate at only 300 amperes, to protect a feeder cable. 
International Standard--- IEC 60898-1 and European Standard EN 60898-1 
define the rated current I of a circuit breaker for low voltage distribution applications 
as the maximum current that the breaker is designed to carry continuously (at an 
ambient air temperature of 30 °C). The commonly-available preferred values for the 
rated current are 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 
100 A and 125 A. 
SCITS, KARIMNAGAR 7 DEPARTMENT OF EEE
2.2 TYPES OF CIRCUIT BREAKERS 
Many different classifications of circuit breakers can be made, based on 
their features such as voltage class, construction type, interrupting type, and structural 
features, the types of breakers basically refer to the medium in which the breaker 
opens and closes. The medium could be 
 OIL 
 AIR BLAST 
 SF6 
 VACUUM 
Fig 2.2 Types of circuit Brekers 
SCITS, KARIMNAGAR 8 DEPARTMENT OF EEE
1. Arc control Device 
Fig 2.2.1 Arc chamber 
A breaker consists of moving and fixed contact, and during the breaker 
operation, the contacts are broken and the arc created during such separation needs to 
be controlled. The arc control devices, otherwise known as turbulator or explosion 
plot achieves this: 
1. Turbulence caused by Arc bubble. 
2. Magnetic forces tend to force main contacts a art and movements causes 
oil to be sucked in through ports and squirted past gap. 
3. When arc extinguished (at current zero), ionized gases get swept away and 
prevents re-striking of the arc. 
2.2.1 OIL CIRCUIT BREAKERS 
Oil Circuit breakers are high voltage circuit breakers that are 
usually operated mechanically, using a powerful spring press but use oil to insulate 
and therefore, minimize the foot print occupied by circuit breaker. As the medium for 
extinguish dark created when the circuit breaker trips under fault condition. 
Oil Circuit breakers are used in voltage range in between 11Kv to 132Kv. 
SCITS, KARIMNAGAR 9 DEPARTMENT OF EEE
1. In modern installations, oil circuit breakers, which are becoming obsolete, are 
being replaced by vaccum and SF6 breakers. 
2. The main contacts are immersed in oil and the oil acts as the ionizing medium 
between the contacts. The oil is mineral type, with high dielectric strength to 
withstand the voltage across the contacts under normal conditions. 
3. Arc energy decomposes oil into 70% hydrogen, 22% acetylene, 5% methane and 
3% ethylene. Arc is in a bubble of gas surrounded by oil. 
Fig 2.3 Oil Circuit breaker 
SCITS, KARIMNAGAR 10 DEPARTMENT OF EEE
ADVANTAGES: 
1. Ability of cool oil to flow into the space after current zero and arc goes out 
2. Cooling surface presented by oil 
3. Absorption of energy by decomposition of oil. 
4. Action of oil as an insulator lending to more compact design of switchgear. 
DISADVANTAGES: 
1. Inflammability (Especially if there is any air near hydrogen) 
2. Maintenance (changing and purifying). 
3. Not suitable for high current interruption at low voltages due to carbonization of 
oil. 
4. The whole breaker unit is immersed in the oil. 
2.2.2 TYPES OF OIL CIRCUIT BREAKERS 
1) Bulk oil circuit breakers 
a) Plain break oil circuit breaker 
b) Arc control oil circuit breakers 
i) Self-blast oil circuit breaker 
(1) Plain explosion pot. 
(2) Cross jet explosion pot 
(3) Self-compensated explosion pot 
ii) Forced-blast oil circuit breaker 
2) Low oil circuit breakers 
SCITS, KARIMNAGAR 11 DEPARTMENT OF EEE
2.2.3 PLAIN BREAK OIL CIRCUIT BREAKER 
The plain-break oil circuit breaker is the earliest type from which all other circuit 
breakers have developed. It has a very simple construction. It consist of fixed and 
moving contacts enclosed in a strong weather tight earthed tank containing oil up to 
certain level and air cushion above the oil level . The air cushion provides sufficient 
room to allow for the circuit breaker. 
 WORKING PRINCIPLE 
1. The hydrogen gas bubble generated around the arc cools the arc column and aids 
the deionization of the medium between the contacts. 
2. The gas sets up turbulence in the coil and helps in eliminating the arcing products 
from the arc path. 
3. As the arc lengthens due to the separating contacts, the dielectric strength of the 
medium is increased. 
Fig 2.4 Plain Oil C.B 
 ADVANTAGES 
1. For successful interruption long arc length is necessary and it is formed here. 
SCITS, KARIMNAGAR 12 DEPARTMENT OF EEE
 DISADVANTAGES 
1. There is no special control over the arc other than the increase in length by 
separating the moving contacts. 
2. These breakers do not permit high speed interruption. 
2.2.4 SELF-BLAST OIL CIRCUIT BREAKER 
In this type of circuit breaker, the gases produced during arcing are confined to a 
small volume by the use of an insulating rigid pressure chamber or pot surrounding the 
contacts. 
a) Plain explosion pot: 
It is a rigid cylinder of insulating material and encloses the fixed and moving 
contacts. The moving contact is a cylindrical rod passing through a restricted opening (Called 
throat) at the bottom. When a fault occurs, the contacts get separated and an arc is struck 
between them. The principal limitation of this type of pot is that it cannot be used for very lower 
for very high fault currents. 
b) Cross jet explosion pot: 
This type of pot is just a modification of plain explosion pot. It is made of 
insulating material and has channels on one side which act as arc splitters. The arc 
splitters help in increasing the arc length, thus facilitating are extinction. 
When a fault occurs, the moving contact of the circuit breaker begins to 
separate .as the moving contact is withdrawn, the arc is initially struck h in the stop of 
the pot. The gas generated by the arc exerts pressure on the oil in the back passage. 
When the moving contact uncovers the arc splitter ducts, fresh oil so forced across the 
arc path. The arc is therefore driven sideways into the arc splitters which increase the 
arc length, causing arc extinction. The cross jet explosion pot is quite efficient for 
interrupting heavy fault currents. However, for low fault currents, the gas pressure is 
small and consequently the pot does not give a satisfactory operation. 
SCITS, KARIMNAGAR 13 DEPARTMENT OF EEE
c) Self-compensated explosion pot: 
This type of pot is essentially a combination of plain explosion pot and 
cross jet explosion pot.therefore; it can interrupt low as well as heavy short circuit 
currents with reasonable accuracy. 
Fig 2.5 Self compensated 
2.2.5 FORCED –BLAST OIL CIRCUIT BREAKER 
In a forced –blast oil circuit breaker, oil pressure is created by the piston-cylinder 
arrangement. The movement of the piston is mechanically coupled to the 
moving contact .when a fault occurs, the contacts get separated by the protective 
system and an arc is struck between the contacts .the piston forces a jet of oil towards 
the contact gap to extinguish the arc. It may be noted that necessary oil pressure 
produced does not in any way depend upon the fault current to be broken. 
SCITS, KARIMNAGAR 14 DEPARTMENT OF EEE
 ADVANTAGES 
1. The quantity of oil required is reduced considerably. 
2. The performance at low currents is more consistent than with self-blast oil circuit 
breakers. 
 APPLICATIONS OF BULK OIL CIRCUIT BREAKER 
1. Used up to to12Kv,500MVA 
 MERITS 
1. Simplicity in construction. 
2. High rupturing capacity 
3. Suitability for automatic as well as manual operation. 
4. Possibility of locating CT’s in bushings. 
 DEMERITS 
1. Large size and greater weight. 
2. Unsuitable for indoor installation. 
3. Greater wear and tear of the contacts resulting in their frequent replacement. 
4. Fire hazard. 
2.2.6 LOW OIL CIRCUIT BREAKERS 
1. It is found only a small percentage of oil is actually used for arc extinction while 
major part is utilized for insulation purposes. 
2. For this reason, the quantity of oil in bulk oil reaches a very high figure as the 
system voltage increases. 
3. This not only increase the expenses, tank size and weight of the breaker but it also 
increases the fire risk and maintenance problems. 
SCITS, KARIMNAGAR 15 DEPARTMENT OF EEE
Fig 2.6 Minimum Oil Circuit breaker 
SCITS, KARIMNAGAR 16 DEPARTMENT OF EEE
 WORKING 
In a minimum oil circuit breaker, the arc drawn across the current carrying 
conductor is contained inside the arcing chamber; hence the hydrogen bubble 
formed by the vaporized oil is trapped inside the chamber. As the contacts 
continue to move, after its certain travel an exit vent becomes available for 
exhausting the trapped hydrogen gas. There are two different types of arcing 
chamber is available in terms of venting are provided in the arcing chambers. One 
is axial venting and other is radial venting. In axial venting gases (mostly 
hydrogen), produced due to vaporization of oil and decomposition during arc, will 
sweep the arc in axial or longitudinal direction. 
Fig 2.7 MOCB working 
Fig 2.8 MOCB Arcing chamber 
SCITS, KARIMNAGAR 17 DEPARTMENT OF EEE
Fig 2.9 MOCB Arc Formation 
Fig 2.10 MOCB Arc Extinction 
 MERITS 
1. It requires lesser quantity of oil & it requires smaller space. 
2. There is reduced risk of fire 
3. Maintenance problems are reduced. 
 DEMERITS 
1. Due to smaller quantity of oil, the degree of carbonization is increased. 
2. There is a difficulty of removing the gases from the contact space in time. 
3. The dielectric strength of the oil deteriotes rapidly due to high degree of 
carbonization 
SCITS, KARIMNAGAR 18 DEPARTMENT OF EEE
2.3 AIR BLAST CIRCUIT BREAKER 
 These breakers employ a high pressure air blast as an arc quenching medium 
 Arc is chopped into a number of small arcs by the Arc-Shute as it rises due to heat 
and magnetic forces. 
 The contacts are opened in a flow of air blast 
 The air circuit breakers are normally employed for 380-480V distribution. 
 Suitable for high current interruption at low voltages. 
2.3.1 PRINCIPAL OF OPERATION 
Fig 2.11 Air blast C.B Principle of operation 
SCITS, KARIMNAGAR 19 DEPARTMENT OF EEE
2.3.2 TYPES OF AIR BLAST CIRCUIT BREAKER 
1. Axial-blast CB 
2. Cross-blast CB 
3. Radial-blast CB 
Fig 2.12 Types of Air Blast C.B 
 ADVANTAGES 
 The risk of fire is eliminated. 
 The arcing products are completely removed by the blast. 
 The arcing time is very small due to the rapid buildup of dielectric 
strength between contacts. 
 DISADVANTAGES 
 Air has relatively inferior arc extinguishing properties. 
 Air blast circuit breakers are very sensitive to the variations in the rate of 
restriking voltage. 
 Considerable maintenance is required for the compressor plant which 
supplies the air blast. 
 APPLICATIONS 
The air blast circuit breakers are finding wide applications in high voltage 
installations. Majority of the circuit breakers for voltages beyond 110 kV are of this type. 
SCITS, KARIMNAGAR 20 DEPARTMENT OF EEE
2.4 SULPHUR HEXAFLOURIDE GAS (SF6) 
A circuit breaker in which the current carrying contacts operate in sulphur 
hexafluoride or SF6 gas is known as an SF6 circuit breaker. 
SF6 has excellent insulating property. SF6 has high electro-negativity. That means 
it has high affinity of absorbing free electron. Whenever a free electron collides with 
the SF6 gas molecule, it is absorbed by that gas molecule and forms a negative ion. 
The attachment of electron with SF6 gas molecules may occur in two different 
ways, 
These negative ions obviously much heavier than a free electron and therefore 
over all mobility of the charged particle in the SF6 gas is much less as compared other 
common gases. We know that mobility of charged particle is majorly responsible for 
conducting current through a gas. 
Fig 2.13 SF6 C.B 
SCITS, KARIMNAGAR 21 DEPARTMENT OF EEE
2.4.1 WORKING OF SF6 
The working of SF6 CB of first generation was quite simple it is some extent 
similar to air blast circuit breaker. Here SF6 gas was compressed and stored in a high 
pressure reservoir. During operation of SF6 circuit breaker this highly compressed 
gas is released through the arc in breaker and collected to relatively low pressure 
reservoir and then it pumped back to the high pressure reservoir for re utilize. 
The working of SF6 circuit breaker is little bit different in modern time. 
Innovation of puffer type design makes operation of SF6 CB much easier. In buffer 
type design, the arc energy is utilized to develop pressure in the arcing chamber for 
arc quenching. 
Fig 2.14 SF6 CB Working 
SCITS, KARIMNAGAR 22 DEPARTMENT OF EEE
Fig 2.15 SF6 CB Operation 
Hence, for heavier and less mobile charged particles in SF6 gas, it acquires very 
high dielectric strength. Not only the gas has a good dielectric strength but also it has the 
unique property of fast recombination after the source energizing the spark is removed. 
The gas has also very good heat transfer property. Due to its low gaseous viscosity 
(because of less molecular mobility) SF6 gas can efficiently transfer heat by convection. 
So due to its high dielectric strength and high cooling effect SF6 gas is approximately 100 
times more effective arc quenching media than air. Due to these unique properties of this 
gas SF6 circuit breaker is used in complete range of medium voltage and high voltage 
electrical power system. These circuit breakers are available for the voltage ranges from 
33KV to 800KV and even more. 
SCITS, KARIMNAGAR 23 DEPARTMENT OF EEE
Types of SF6 Circuit Breaker 
There are mainly three types of SF6 CB depending upon the voltage level of 
application- 
1. Single interrupter SF6 CB applied for up to 245 KV (220 KV) system. 
2. Two interrupter SF6 CB applied for up to 420 KV (400 KV) system. 
3. Four interrupter SF6 CB applied for up to 800 KV (715 KV) system. 
 ADVANTAGES 
 Excellent insulating, arc extinguishing, physical and chemical properties 
of SF6 gas is greater advantage of SF6 circuit breakers 
 Electrical clearances are very much reduced because of high dielectric 
strength of SF6 
 Its performance is not affected due to variation in atmospheric conditions 
 It gives noiseless operation it does not make sound like air-blast circuit 
breaker during operation 
 Same gas is re-circulated into the circuit thereby reducing the requirement 
of SF6 gas. 
 No over voltage problem. The arc is extinguished at natural current zero 
without the current chopping and associated over-voltages originating 
across the circuit breaker terminals 
 DISADVANTAGES 
 Imperfect joints leading to leakage of the SF6 gas. Continuous monitoring 
devices are required 
 Arced SF6 gas is poisonous and should not be inhaled 
 The internal parts need thorough cleaning during periodic maintenance 
under clean and dry environment. Dust of Teflon and sulphides should be 
removed 
 APPLICATIONS 
 SF6 Circuit breakers are mostly employed for High voltage applications 
SCITS, KARIMNAGAR 24 DEPARTMENT OF EEE
2.5 TESTING OF CIRCUIT BREAKERS 
Why test circuit breakers? 
Some of the most important of the many reasons for testing circuit breakers 
are to ensure they are: 
1. Provide protection for expensive equipment. 
2. Prevent outages that lead to loss of income. 
3. Ensure reliability of the electricity supply. 
4. Prevent downtime and darkness. 
5. Verify breaker performance. 
Substation breaker testing is an important task for any power utility .The 
breakers are there to facilitate the flow of current during normal operation and to 
interrupt current flow in the event of a fault.however,all electricity operated 
devices are, sooner or later, likely to experience some kind of failure. That failure 
can be caused by many facors, including ageing and external faults. The power 
utility operator has to be prepared and have a plan in place to handle every 
situation. 
Testing of circuit breakers is more difficult than other electrical equipment 
like transformer or machine because the short circuit current are very large .Also 
there is no satisfactory method of testing circuit breaker at reduced power. 
The testing plan of circuit breaker consists of essentially of a specially 
designed alternator capable of giving about 2000MVA under short circuit 
condition the prime mover of the alternator is 750KV motor end is disconnected 
just before the short circuiting is done. The kinetic energy of rotor is sufficient to 
give the desired energy for testing purpose. 
Testing of circuit breaker can be classified in to two main groups 
SCITS, KARIMNAGAR 25 DEPARTMENT OF EEE
 TYPE TEST 
 ROUTINE TEST 
TYPE TEST 
These test are conducted on first few proto type circuit breakers of each 
type for the purpose of providing the capabilities and confirming the rated 
characteristics of the circuit breaker of that design. Such test is conducted in 
specially built testing laboratories. 
Type test are broadly classified as 
 Mechanical Performance test. 
 Thermal test. 
 Insulation test 
 Short circuit test 
 MECHANICAL TEST 
These are mechanical endurance type tests involving repeated opening and 
closing of the circuit breaker. A circuit breaker must open and close at the correct 
speed and perform its designated duty and operation without mechanical failure. 
 THERMAL TEST 
Thermal test are carried out to check the thermal behavior of the circuit 
breakers. The breaker under test is subjected to study state temperature rise due to 
flow of its rated current through its poles in closed condition. The temperature rise 
for rated current should not exceed 40oC for current less than 800A normal 
current and 50oC for normal value of current 800A and above. 
In such sets the contact drops or contact resistances are also measured as 
these contacts surfaces are responsible for generation of heat and subsequent 
temperature rise. 
SCITS, KARIMNAGAR 26 DEPARTMENT OF EEE
 DIELECTRIC TESTS 
These tests are performed to check power frequency and impulse voltage 
withstand capacity. 
Power frequency tests are conducted on clean new circuit breaker, the test 
voltage varies with circuit breaker rated voltage. The test voltage with a frequency 
between 15 to 100HZ is applied as follows. 
 Between poles with circuit breaker closed 
 Between poles and earth with circuit breaker open. 
 Across terminals with circuit breaker open 
The voltage is gradually increased and maintained at test value for one 
minute. In impulse voltage of specified shape and magnitude applied to the 
breaker. For outdoor circuit dry and wet test are conducted. 
 SHORT CIRCUIT TESTS 
Circuit breakers are subjected to sudden short circuit in the short circuit 
test laboratories and oscillograms are taken to know the behavior of circuit 
breaker at the time of switching in, during contact breaking and after arc 
extinction. The oscillograms are studied with particular reference to the making 
and braking currents, both symmetrical and asymmetrical. 
 ROUTINE TEST 
Once type tests are conducted and a particular design is found to be 
satisfactory the product becomes prototype and a large number of circuit breaker 
of similar design manufactured. However, each and every circuit breaker still 
subjected to a few more tests before commissioning. These tests are called routine 
test. 
SCITS, KARIMNAGAR 27 DEPARTMENT OF EEE
2.6 APPLICATIONS OF CIRCUIT BREAKER 
Depending on its application in the network the CB’s Service life differs. 
For instance, line circuit breakers operate seldom and have a longer service life 
than. 
 Generator CB 
 High Voltage CB 
 Capacitor CB 
 Reactor CB 
 High voltage DC CB 
 Distribution CB 
 Traction CB 
 Industrial CB 
SCITS, KARIMNAGAR 28 DEPARTMENT OF EEE
CHAPTER III 
VACCUM CCIRCUIT BREAKER 
3.1 INTRODUCTION 
A vacuum circuit breaker is such kind of circuit breaker where the arc 
quenching takes place in vacuum. The technology is suitable for mainly medium 
voltage application. For higher voltage vacuum technology has been developed 
but not commercially viable. The operation of opening and closing of current 
carrying contacts and associated arc interruption take place in a vacuum chamber 
in the breaker which is called vacuum interrupter. The vacuum interrupter consists 
of a steel arc chamber in the centre symmetrically arranged ceramic insulators. 
The material used for current carrying contacts plays an important role in 
the performance of the vacuum circuit breaker. CuCr is the most ideal material to 
make VCB contacts. Vacuum interrupter technology was first introduced in the 
year of 1960. But still it is a developing technology. As time goes on, the size of 
the vacuum interrupter is being reducing from its early 1960’s size due to 
different technical developments in this field of engineering. The contact 
geometry is also improving with time, from butt contact of early days it gradually 
changes to spiral shape, cup shape and axial magnetic field contact. The vacuum 
circuit breaker is today recognized as most reliable current interruption 
technology for medium voltage switchgear. It requires minimum maintenance 
compared to other circuit breaker technologies 
3.2 PRINCIPLE 
Two contacts called electrode remains closed under normal operating 
conditions. When fault occurs on any part of the system, the trip coil of the 
Vaccum circuit breaker gets energized and contacts are separated by the vaccum 
pressure which is having around (10-7 to 10-5 torr). The arc is quickly 
SCITS, KARIMNAGAR 29 DEPARTMENT OF EEE
extinguished because the metallic vapors, electrons, and ions produced during arc 
condense quickly on the surfaces of the circuit breaker 
3.3 OPERATION 
The main aim of any circuit breaker is to quench arc during current zero 
crossing, by establishing high dielectric strength in between the contacts so that 
reestablishment of arc after current zero becomes impossible. The dielectric 
strength of vacuum is eight times greater than that of air and four times greater 
than that of SF6 gas. This high dielectric strength makes it possible to quench a 
vacuum arc within very small contact gap. For short contact gap, low contact 
mass and no compression of medium the drive energy required in vacuum circuit 
breaker is minimum. When two face to face contact areas are just being separated 
to each other, they do not be separated instantly, contact area on the contact face 
is being reduced and ultimately comes to a point and then they are finally de-touched. 
Although this happens in a fraction of micro second but it is the fact. At 
this instant of de-touching of contacts in a vacuum, the current through the 
contacts concentrated on that last contact point on the contact surface and makes a 
hot spot. As it is vacuum, the metal on the contact surface is easily vaporized due 
to that hot spot and create a conducting media for arc path. Then the arc will be 
initiated and continued until the next current zero. 
3.4 CONSTRUCTION 
A schematic diagram of the vaccum C.B is shown in below fig .it is a very 
simple device as compared to an air or oil C.B. The outer envelope is normally 
made of glass due to the ease of joining it to the metallic end caps and also 
because the glass envelope makes it easy to examine from outside state of the 
contacts after the breaker has interrupted the current. This is important since a 
change from a silvery mirror like finish to a milky white color shows that the 
baffle is losing its vacuum. A sputter shield is provided in between the contacts 
and the envelope in order to prevent the metal vapour reaching the envelope as it 
SCITS, KARIMNAGAR 30 DEPARTMENT OF EEE
reduces the breakdown strength between the contacts. This is generally made of 
stainless steel. Inside the sputter shield the breaker has two contacts, one fixed 
and the other moving contact which moves through a short distance of 5 to 10 mm 
depending upon the operating voltage. The metallic bellows made of stainless 
steel is used to move the lower contact. The design of the bellows is very 
important as the life of vacuum breaker depends upon the ability of this part to 
perform repeated operations satisfactorily. 
Fig 3.1 Vaccum Circuit Breaker 
SCITS, KARIMNAGAR 31 DEPARTMENT OF EEE
The periphery of the end cap is sealed to the envelope and the fixed contact 
stem is an integral part of one end cap .one end of the fixed as well as moving 
contact is brought out of the chamber for external connections. The lower end of 
the circuit breaker is fixed to a spring operated or solenoid operated mechanism 
so that the metallic bellows inside the chamber are moved downward and upward 
during opening and closing operation respectively. It is to be noted that the 
operating mechanism should provide sufficient pressure for a good concentration 
between the contacts and should avoid any bouncing action 
Fig 3.2 Front view 
Fig 3.3 Rear view 
SCITS, KARIMNAGAR 32 DEPARTMENT OF EEE
Fig 3.4 Cross section view of VCB 
3.5 THE VACUUM ARC 
The vacuum arc results from the neutral atoms, ions and electrons emitted 
from the electrodes themselves. As the current carrying contacts are separated, 
cathode spots are formed depending upon the current to be interrupted. For low 
currents a highly mobile cathode spot is formed and for large currents a multiple 
number of cathode spots are formed. These spots constitute the main source of 
vapour in the arc. The processes involved in drawing the arc will be due to high 
electric field between the contacts or resistive heating produced at the point of 
operation or a combination of the two. The cathode surfaces normally are not 
perfectly smooth but have many micro projections. When the contacts are 
separating, the current flowing in the circuit will be concentrated in these 
projections as they form the last point of contact. Due to their small area of cross 
section, the projections will suffer explosive evaporation by resistive hating and 
supply sufficient quantity of vapour for the arc formation. Since in case of 
vaccum breakers the emission occurs only at the cathode spots and not from the 
entire surface of the cathode, the vaccum arc is also known as cold cathode arc. In 
cold cathode the emission of electrons could be due to any of the combinations of 
the following mechanisms: 
 Field emission 
 Thermionic emission 
SCITS, KARIMNAGAR 33 DEPARTMENT OF EEE
 Field and thermionic emission 
 Secondary emission by positive ion bombardment 
 Secondary emission by photons 
 Pinch effect. 
3.6 VACUUM ARC STABILITY 
In a.c. circuit the current passes through zero value 100 times in a second. 
It is desirable to interrupt the current chopping .Therefore, it is necessary for 
successful arc interruption that it be stable for half cycle duration and particularly 
it should continue to exist when the current approaches zero. The stability of arc 
in vacuum depends upon 
 The contact material and its vapour pressure. 
 Circuit parameters such as voltage,current,inductance and capacitance 
3.7 VACUUM ARC-RECOVERY PHENOMENON 
When the arc interruption is over, the space between the surrounding the 
electrodes is filled with vapour and plasma. The presence of this residue affects 
very much the ability of an interrupter to withstand high voltages. the process by 
which this residue decays and by which the vaccum gap regains its dielectric 
strength is known as arc recovery phenomenon at current zero the cathode spot 
extinguishes within in 10-8 second and after this the original dielectric strength is 
established very soon this quick build up of dielectric strength is due to the 
condensing, quick diffusion and of metal vapour to the glass walls in absence of 
gas molecules. After the arc is interrupted, the recovery strength during the first 
few micro seconds is 1kV/μsec for an arc current of 100A, as compared with 
50V/μsec in case of air gap. 
SCITS, KARIMNAGAR 34 DEPARTMENT OF EEE
3.8 CURRENT CHOPPING PHENOMENON 
Post-arc current phenomena that occur when interrupting high currents 
with vacuum circuit breakers have been investigated. High resolution measuring 
equipment has been used to measure both the post-arc current and the arc voltage 
in the current-zero regions. Three examples of frequently observed phenomena 
are described. The first describes the phenomenon that in the event of a current-chopping, 
the current is zero for a short period of time just before the natural 
alternating current zero, but continues to flow afterwards, in the form of a post-arc 
current. The second and third example deal with the post-arc phenomena after 
currents those are much higher than the test breakers rated short-circuit current. 
These examples show a low-voltage period after current-zero. Apparently, during 
this post-arc period, the residual plasma between the breaker's contacts conduct 
well. In addition to the voltage-zero periods, the voltage trace in the third example 
also shows evidence of current-chopping. This means that the plasma conducts 
poorly just before current-zero, but conducts well immediately afterwards. 
Fig 3.5 Current chopping phenomenon 
SCITS, KARIMNAGAR 35 DEPARTMENT OF EEE
3.9 SPECIFICATIONS 
 It is designed for medium voltage range (3.3-33kv). 
 This consists of vacuum of pressure (10-7 to 10-5) inside arc extinction 
chamber. 
 Vacuum is used as an arc quenching medium 
 At high voltage, its rate of dielectric strength recovery is very high. 
 Have greatest insulating strength 
 ADVANTAGES 
 Free from arc and fire hazards. 
 Low cost for maintenance & simpler mechanism. 
 Low arcing time & arc extinction is very fast. 
 Silent and less vibrational operation. 
 Can interrupt any fault current. 
 It has higher dielectric strength. 
 Requires small amount of power for operation 
 APPLICATIONS 
 For outdoor applications ranging from 11 KV to 33 KV. 
 Suitable for majority of applications in rural area. 
 They can be used where the switching frequency is high. 
 They can be used along with static over current relays. 
 This gives a fast RRRV and vacuum circuit breakers are the best solutions. 
SCITS, KARIMNAGAR 36 DEPARTMENT OF EEE
CHAPTER IV 
CONCLUSION 
A vacuum circuit breaker (VCB) has demonstrated its ability to interrupt short 
circuits with faster than normal rates of rise of transient recovery voltage (TRV) at levels 
greater than those produced by most transformer secondary faults. Two recent 
exploratory test programs evaluated the interrupting ability of a 15 kV VCB containing 
interrupters of the rotating arc type with contacts made from a chromium-copper powder 
metal mixture. The interrupting conditions covered a wide range of currents from 10% to 
130% of the 28 kA rated short circuit current of the tested circuit breaker and a wide 
range of TRV rates of rise. These tests showed that the interrupting performance of the 
tested VCB was unaffected by the TRV rate of rise to the fastest rates available in the test 
laboratory. Such a VCB can therefore be used without TRV modifying capacitors to slow 
down the rate of rise provided by the power system. This ability is particularly important 
if analysis shows that the expected TRV from a transformer secondary fault has a fast 
rate of rise beyond the recognized ability of an older circuit breaker to acceptably 
interrupt. 
SCITS, KARIMNAGAR 37 DEPARTMENT OF EEE
REFERENCES 
1.Electrical power systems by C.L.Wadhwa, New Age international Publishers. 
2.Switch Gear Protection and Power Systems by Sunil S.Rao, Khanna Publishers. 
3.Modern Power System Analysis by D. P Kothari & I.J Nagrath. Eastern 
Economy Edition. 
4.Power Systems by J.B GUPTA, Katson Books. 
5.Power system Protection and Switchgear, by B.Ravindranath and Michener, 
Wiley Eastern 
SCITS, KARIMNAGAR 38 DEPARTMENT OF EEE

Weitere ähnliche Inhalte

Was ist angesagt?

Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsanuphowlader1
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in IndiaSystem Protection
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakersali raza
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakersPrasant Kumar
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Oil circuit breakers
Oil circuit breakersOil circuit breakers
Oil circuit breakersNaveena Navi
 
Get Complete Information about Circuit Breaker
Get Complete Information about Circuit BreakerGet Complete Information about Circuit Breaker
Get Complete Information about Circuit BreakerSystem Protection
 
Circuit breaker presentation
Circuit breaker presentationCircuit breaker presentation
Circuit breaker presentationravi kant
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis pptkarikalan123
 
Interlocking on switchgear principles
Interlocking on switchgear principlesInterlocking on switchgear principles
Interlocking on switchgear principlesBryan Johnson
 
Fuses vs. Circuit Breakers
Fuses vs. Circuit BreakersFuses vs. Circuit Breakers
Fuses vs. Circuit BreakersSima Yildirim
 

Was ist angesagt? (20)

Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applications
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
Protective relay
Protective relay Protective relay
Protective relay
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakers
 
IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Oil circuit breakers
Oil circuit breakersOil circuit breakers
Oil circuit breakers
 
Get Complete Information about Circuit Breaker
Get Complete Information about Circuit BreakerGet Complete Information about Circuit Breaker
Get Complete Information about Circuit Breaker
 
Circuit breaker presentation
Circuit breaker presentationCircuit breaker presentation
Circuit breaker presentation
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
INSULATORS AND ITS TYPES
INSULATORS AND ITS TYPESINSULATORS AND ITS TYPES
INSULATORS AND ITS TYPES
 
Circuit breakers basics
Circuit breakers   basicsCircuit breakers   basics
Circuit breakers basics
 
Lightning arrester
Lightning arresterLightning arrester
Lightning arrester
 
Interlocking on switchgear principles
Interlocking on switchgear principlesInterlocking on switchgear principles
Interlocking on switchgear principles
 
Fuses vs. Circuit Breakers
Fuses vs. Circuit BreakersFuses vs. Circuit Breakers
Fuses vs. Circuit Breakers
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 

Andere mochten auch

Vacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersVacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersshubham_bharadia
 
Er. rahul sharma circuit breaker
Er. rahul sharma circuit breakerEr. rahul sharma circuit breaker
Er. rahul sharma circuit breakerRahul Ruddra
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersShailendra Shakya
 
BT2-series FUJI AIR CIRCUIT BREAKER - Fuji Electric
BT2-series FUJI AIR CIRCUIT BREAKER - Fuji ElectricBT2-series FUJI AIR CIRCUIT BREAKER - Fuji Electric
BT2-series FUJI AIR CIRCUIT BREAKER - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Circuitbreaker 140425132435nn
Circuitbreaker 140425132435nnCircuitbreaker 140425132435nn
Circuitbreaker 140425132435nnPonlue Smile
 
Circuitbreakers 140527053033AA
Circuitbreakers 140527053033AACircuitbreakers 140527053033AA
Circuitbreakers 140527053033AAPonlue Smile
 
Hybrid circuit breaker
Hybrid circuit breakerHybrid circuit breaker
Hybrid circuit breakerVishal Bhimani
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARashwini kumar
 

Andere mochten auch (20)

Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Vacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersVacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakers
 
Circuit breakers
Circuit breakers Circuit breakers
Circuit breakers
 
Study of circuit breakers
Study of circuit breakersStudy of circuit breakers
Study of circuit breakers
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Er. rahul sharma circuit breaker
Er. rahul sharma circuit breakerEr. rahul sharma circuit breaker
Er. rahul sharma circuit breaker
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit Breakers
 
BABER HAYAT
BABER HAYATBABER HAYAT
BABER HAYAT
 
circuit breaker
circuit breakercircuit breaker
circuit breaker
 
BT2-series FUJI AIR CIRCUIT BREAKER - Fuji Electric
BT2-series FUJI AIR CIRCUIT BREAKER - Fuji ElectricBT2-series FUJI AIR CIRCUIT BREAKER - Fuji Electric
BT2-series FUJI AIR CIRCUIT BREAKER - Fuji Electric
 
Circuitbreaker 140425132435nn
Circuitbreaker 140425132435nnCircuitbreaker 140425132435nn
Circuitbreaker 140425132435nn
 
Circuitbreakers 140527053033AA
Circuitbreakers 140527053033AACircuitbreakers 140527053033AA
Circuitbreakers 140527053033AA
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Baseband processor final rev
Baseband processor final revBaseband processor final rev
Baseband processor final rev
 
Psg 5 2 mark
Psg 5 2 markPsg 5 2 mark
Psg 5 2 mark
 
vacuum CBs
vacuum CBsvacuum CBs
vacuum CBs
 
SF6 circuit breaker
SF6 circuit breakerSF6 circuit breaker
SF6 circuit breaker
 
GIS-NESCL-6
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
 
Hybrid circuit breaker
Hybrid circuit breakerHybrid circuit breaker
Hybrid circuit breaker
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
 

Ähnlich wie Vaccum Circuit Breaker

Circuit breaker
Circuit breakerCircuit breaker
Circuit breakerdipak doud
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breakerdipak doud
 
Components of LT Switchgear.pptx
Components of LT Switchgear.pptxComponents of LT Switchgear.pptx
Components of LT Switchgear.pptxSwaroopMallick2
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationabu jubayer
 
Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01rana usman
 
Electrical Installation.pptx
Electrical Installation.pptxElectrical Installation.pptx
Electrical Installation.pptxbharath364108
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgearAdnan Sayed
 
Switchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsSwitchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsNicola Cochrane
 
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...rohit nadella
 
High voltage circuit breakers
High voltage circuit breakersHigh voltage circuit breakers
High voltage circuit breakersKabilesh K
 
highvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdfhighvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdfNagsSuresh
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBMANOJ964697
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptxAsif682330
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentationKamal Mittal
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptxAsif682330
 
Experiments manual
Experiments manual Experiments manual
Experiments manual Ramesh Meti
 
Circuit interruption
Circuit interruptionCircuit interruption
Circuit interruptionjawaharramaya
 

Ähnlich wie Vaccum Circuit Breaker (20)

Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Mcb Breaker
Mcb Breaker Mcb Breaker
Mcb Breaker
 
Report on MCB
Report on MCBReport on MCB
Report on MCB
 
Components of LT Switchgear.pptx
Components of LT Switchgear.pptxComponents of LT Switchgear.pptx
Components of LT Switchgear.pptx
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentation
 
Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01
 
Electrical Installation.pptx
Electrical Installation.pptxElectrical Installation.pptx
Electrical Installation.pptx
 
ms ppt.ppt
ms ppt.pptms ppt.ppt
ms ppt.ppt
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgear
 
Switchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsSwitchgear and Protection of HV Systems
Switchgear and Protection of HV Systems
 
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
 
High voltage circuit breakers
High voltage circuit breakersHigh voltage circuit breakers
High voltage circuit breakers
 
highvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdfhighvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdf
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptx
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx
 
Experiments manual
Experiments manual Experiments manual
Experiments manual
 
Circuit interruption
Circuit interruptionCircuit interruption
Circuit interruption
 

Kürzlich hochgeladen

Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitterShivangiSharma879191
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
Comparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization TechniquesComparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization Techniquesugginaramesh
 

Kürzlich hochgeladen (20)

Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
Comparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization TechniquesComparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization Techniques
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 

Vaccum Circuit Breaker

  • 1. CHAPTER I INTRODUCTION 1.1 INTRODUCTION Our Power system is a large interconnected system, which consisting of Generators, transformers, transmission and distribution circuits, it is inevitable that sooner or later some failure will occur somewhere in the system. When a failure occurs on any part of the system, it must be quickly detected and disconnected from the system. There are Principal reasons for it:  Firstly, if the fault is not cleared quickly, it may cause unnecessary interruption of service to the customers.  Secondly, rapid disconnection of faulted apparatus limits the amount of damage to it and prevents the effects of the fault from spreading into the system.  A Protective relay is a device that detects the fault and initiates the operation of the circuit breaker to isolate the defective element from the rest of the system. Hence the Role of the circuit breaker play a major role in the power system interconnected system 1.2 CIRCUIT BREAKER A circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and interrupt current flow. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small devices that protect an individual household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city. SCITS, KARIMNAGAR 1 DEPARTMENT OF EEE
  • 2. The modern power system deals with huge power network and huge numbers of associated electrical equipment. During short circuit fault or any other types of electrical fault these equipment as well as the power network suffer a high stress of fault current in then which may damage the equipment and networks permanently. For saving these equipment and the power networks the fault current should be cleared from the system as quickly as possible. Again after the fault is cleared, the system must come to its normal working condition as soon as possible for supplying reliable quality of power to receiving ends. In addition to that for proper controlling of power system, different switching operations are required to be performed. So for timely disconnecting and reconnecting different parts of power system network for protection and control, there must be some special type of switching devices which can be operated safely under huge current carrying condition, During interruption of huge current, there would be large arcing in between switching contacts, so care should be taken to quench these arcs in circuit breaker in safe manner .The circuit breaker is the special device which does all the required switching operations during current carrying condition. This was the basic Introduction to Circuit Breaker. Circuit breakers are a piece of electrical device that 1. Make or break a circuit either manually or by remote control under normal conditions. 2. Break a circuit automatically under fault conditions. 3. Make a circuit either manually or by remote control under fault conditions. SCITS, KARIMNAGAR 2 DEPARTMENT OF EEE
  • 3. CHAPTER II CIRCUIT BREAKERS 2.1 INTRODUCTION Circuit Breaker is a critical component of an electrical system they are used to connect and disconnect transmission lines under normal operating conditions. They are also used to a clear section of transmission grid should a short circuit occur in the system, isolating the fault. The technology of circuit breaker evolved based on primarily on the media in which the circuit breaker contacts are located. Every circuit breaker used a dielectric media. When system voltages and current levels increased oil circuit breakers are introduced later compressed air circuit breakers are developed followed by SF6 and working breakers which is preferred technology for high voltage circuit breaker. The main purpose of a circuit breaker is to:  Switch load currents  Make on to a fault  Break normal and fault currents  Carry fault currents without blowing itself open. The important characteristics from a protection point of view are:  The speed with which the main current is opened after a tripping impulse is received.  The capacity of the circuit that the main contacts are capable of interrupting (rupturing capacity).  The first characteristics are referred to as the ‘tripping time’ and are expressed in cycles.  Modern high speed circuit breakers having tripping times between 3 to 8 cycles. SCITS, KARIMNAGAR 3 DEPARTMENT OF EEE
  • 4. The Tripping or total clearing or breaking time is made up as follows:  Opening time: the time between instant of application of tripping power to the instant of separation of the main contacts.  Arcing time: the time between the instant of separation of the main circuit breaker contacts to the instant of arc extinction of short circuit current.  Total break or clearing time: The sum of the above (opening time + Arcing time). Some of the manufacturers are ABB, Alstom, General Electric, Hitachi, HYOSUNG (HICO), Hyundai Heavy Industry (HHI), Mitsubishi Electric, Pennsylvania Breaker, Siemens, Toshiba, Končar HVS, BHEL, CGL, and Becker/SMC (SMC Electrical Products). Fig 2.1 Fault Clearing Time SCITS, KARIMNAGAR 4 DEPARTMENT OF EEE
  • 5. 2.1.1 ORIGIN An early form of circuit breaker was described by Thomas Edison in an 1879 patent application, although his commercial power distribution system used fuses. Its purpose was to protect lighting circuit wiring from accidental short-circuits and overloads. A modern miniature circuit breaker similar to the ones now in use was patented by Brown, Boveri & Cie in 1924. Hugo Stotz, an engineer who had sold his company, to BBC, was credited as the inventor on DRP (Deutsches Reichspatent). Stotz's invention was the forerunner of the modern thermal-magnetic breaker commonly used in household load centers to this day. Interconnection of multiple generator sources into an electrical grid required development of circuit breakers with increasing voltage ratings and increased ability to safely interrupt the increasing short circuit currents produced by networks. Simple air-break manual switches produced hazardous arcs when interrupting high currents; these gave way to oil-enclosed contacts, and various forms using directed flow of pressurized air, or of pressurized oil, to cool and interrupt the arc. By 1935, the specially constructed circuit breakers used at the Boulder Dam project use eight series breaks and pressurized oil flow to interrupt faults of up to 2,500 MVA, in three cycles of the AC power frequency. 2.1.2 SHORT CIRUIT CURRENT Circuit breakers are rated both by the normal current that they are expected to carry, and the maximum short-circuit current that they can safely interrupt. Under short-circuit conditions; the calculated maximum prospective short circuit current may be many times the normal, rated current of the circuit. When electrical contacts open to interrupt a large current, there is a tendency for an arc to form between the opened contacts, which would allow the current to continue. This condition can create conductive ionized gases and molten or vaporized metal, which can cause further continuation of the arc, or creation of additional short circuits, potentially resulting in the explosion of the circuit breaker and the equipment that it is installed in. SCITS, KARIMNAGAR 5 DEPARTMENT OF EEE
  • 6. Therefore, circuit breakers must incorporate various features to divide and extinguish the arc. In air-insulated and miniature breakers an arc chutes structure consisting (often) of metal plates or ceramic ridges cools the arc, and magnetic blowout coils deflect the arc into the arc chute. Larger circuit breakers such as those used in electrical power distribution may use vacuum, an inert gas such as sulfur hexafluoride or have contacts immersed in oil to suppress the arc. The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher than the breaker's interrupting capacity rating may result in failure of the breaker to safely interrupt a fault. In a worst-case scenario the breaker may successfully interrupt the fault, only to explode when reset. MCB used to protect control circuits or small appliances may not have sufficient interrupting capacity to use at a panel board; these circuit breakers are called "supplemental circuit protectors" to distinguish them from distribution-type circuit breakers. 2.1.3 ARC INTERRUPTION Low-voltage MCB uses air alone to extinguish the arc. Larger ratings have metal plates or non-metallic arc chutes to divide and cool the arc. Magnetic blowout coils or permanent magnets deflect the arc into the arc chute. In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil through the arc. Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF6) to quench the stretched arc. SCITS, KARIMNAGAR 6 DEPARTMENT OF EEE
  • 7. Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the contact material), so the arc quenches when it is stretched a very small amount (less than 2–3 mm (0.079–0.118 in)). Vacuum circuit breakers are frequently used in modern medium-voltage switchgear to 38,000 volts. Air circuit breakers may use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air thus blowing out the arc. Circuit breakers are usually able to terminate all current very quickly: typically the arc is extinguished between 30 ms and 150 ms after the mechanism has been tripped, depending upon age and construction of the device. 2.1.4 STANDARD CURRENT RATINGS Circuit breakers are manufactured in standard sizes, using a system of preferred numbers to cover a range of ratings. Miniature circuit breakers have a fixed trip setting; changing the operating current value requires changing the whole circuit breaker. Larger circuit breakers can have adjustable trip settings, allowing standardized elements to be applied but with a setting intended to improve protection. For example, a circuit breaker with a 400 ampere "frame size" might have its over current detection set to operate at only 300 amperes, to protect a feeder cable. International Standard--- IEC 60898-1 and European Standard EN 60898-1 define the rated current I of a circuit breaker for low voltage distribution applications as the maximum current that the breaker is designed to carry continuously (at an ambient air temperature of 30 °C). The commonly-available preferred values for the rated current are 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 100 A and 125 A. SCITS, KARIMNAGAR 7 DEPARTMENT OF EEE
  • 8. 2.2 TYPES OF CIRCUIT BREAKERS Many different classifications of circuit breakers can be made, based on their features such as voltage class, construction type, interrupting type, and structural features, the types of breakers basically refer to the medium in which the breaker opens and closes. The medium could be  OIL  AIR BLAST  SF6  VACUUM Fig 2.2 Types of circuit Brekers SCITS, KARIMNAGAR 8 DEPARTMENT OF EEE
  • 9. 1. Arc control Device Fig 2.2.1 Arc chamber A breaker consists of moving and fixed contact, and during the breaker operation, the contacts are broken and the arc created during such separation needs to be controlled. The arc control devices, otherwise known as turbulator or explosion plot achieves this: 1. Turbulence caused by Arc bubble. 2. Magnetic forces tend to force main contacts a art and movements causes oil to be sucked in through ports and squirted past gap. 3. When arc extinguished (at current zero), ionized gases get swept away and prevents re-striking of the arc. 2.2.1 OIL CIRCUIT BREAKERS Oil Circuit breakers are high voltage circuit breakers that are usually operated mechanically, using a powerful spring press but use oil to insulate and therefore, minimize the foot print occupied by circuit breaker. As the medium for extinguish dark created when the circuit breaker trips under fault condition. Oil Circuit breakers are used in voltage range in between 11Kv to 132Kv. SCITS, KARIMNAGAR 9 DEPARTMENT OF EEE
  • 10. 1. In modern installations, oil circuit breakers, which are becoming obsolete, are being replaced by vaccum and SF6 breakers. 2. The main contacts are immersed in oil and the oil acts as the ionizing medium between the contacts. The oil is mineral type, with high dielectric strength to withstand the voltage across the contacts under normal conditions. 3. Arc energy decomposes oil into 70% hydrogen, 22% acetylene, 5% methane and 3% ethylene. Arc is in a bubble of gas surrounded by oil. Fig 2.3 Oil Circuit breaker SCITS, KARIMNAGAR 10 DEPARTMENT OF EEE
  • 11. ADVANTAGES: 1. Ability of cool oil to flow into the space after current zero and arc goes out 2. Cooling surface presented by oil 3. Absorption of energy by decomposition of oil. 4. Action of oil as an insulator lending to more compact design of switchgear. DISADVANTAGES: 1. Inflammability (Especially if there is any air near hydrogen) 2. Maintenance (changing and purifying). 3. Not suitable for high current interruption at low voltages due to carbonization of oil. 4. The whole breaker unit is immersed in the oil. 2.2.2 TYPES OF OIL CIRCUIT BREAKERS 1) Bulk oil circuit breakers a) Plain break oil circuit breaker b) Arc control oil circuit breakers i) Self-blast oil circuit breaker (1) Plain explosion pot. (2) Cross jet explosion pot (3) Self-compensated explosion pot ii) Forced-blast oil circuit breaker 2) Low oil circuit breakers SCITS, KARIMNAGAR 11 DEPARTMENT OF EEE
  • 12. 2.2.3 PLAIN BREAK OIL CIRCUIT BREAKER The plain-break oil circuit breaker is the earliest type from which all other circuit breakers have developed. It has a very simple construction. It consist of fixed and moving contacts enclosed in a strong weather tight earthed tank containing oil up to certain level and air cushion above the oil level . The air cushion provides sufficient room to allow for the circuit breaker.  WORKING PRINCIPLE 1. The hydrogen gas bubble generated around the arc cools the arc column and aids the deionization of the medium between the contacts. 2. The gas sets up turbulence in the coil and helps in eliminating the arcing products from the arc path. 3. As the arc lengthens due to the separating contacts, the dielectric strength of the medium is increased. Fig 2.4 Plain Oil C.B  ADVANTAGES 1. For successful interruption long arc length is necessary and it is formed here. SCITS, KARIMNAGAR 12 DEPARTMENT OF EEE
  • 13.  DISADVANTAGES 1. There is no special control over the arc other than the increase in length by separating the moving contacts. 2. These breakers do not permit high speed interruption. 2.2.4 SELF-BLAST OIL CIRCUIT BREAKER In this type of circuit breaker, the gases produced during arcing are confined to a small volume by the use of an insulating rigid pressure chamber or pot surrounding the contacts. a) Plain explosion pot: It is a rigid cylinder of insulating material and encloses the fixed and moving contacts. The moving contact is a cylindrical rod passing through a restricted opening (Called throat) at the bottom. When a fault occurs, the contacts get separated and an arc is struck between them. The principal limitation of this type of pot is that it cannot be used for very lower for very high fault currents. b) Cross jet explosion pot: This type of pot is just a modification of plain explosion pot. It is made of insulating material and has channels on one side which act as arc splitters. The arc splitters help in increasing the arc length, thus facilitating are extinction. When a fault occurs, the moving contact of the circuit breaker begins to separate .as the moving contact is withdrawn, the arc is initially struck h in the stop of the pot. The gas generated by the arc exerts pressure on the oil in the back passage. When the moving contact uncovers the arc splitter ducts, fresh oil so forced across the arc path. The arc is therefore driven sideways into the arc splitters which increase the arc length, causing arc extinction. The cross jet explosion pot is quite efficient for interrupting heavy fault currents. However, for low fault currents, the gas pressure is small and consequently the pot does not give a satisfactory operation. SCITS, KARIMNAGAR 13 DEPARTMENT OF EEE
  • 14. c) Self-compensated explosion pot: This type of pot is essentially a combination of plain explosion pot and cross jet explosion pot.therefore; it can interrupt low as well as heavy short circuit currents with reasonable accuracy. Fig 2.5 Self compensated 2.2.5 FORCED –BLAST OIL CIRCUIT BREAKER In a forced –blast oil circuit breaker, oil pressure is created by the piston-cylinder arrangement. The movement of the piston is mechanically coupled to the moving contact .when a fault occurs, the contacts get separated by the protective system and an arc is struck between the contacts .the piston forces a jet of oil towards the contact gap to extinguish the arc. It may be noted that necessary oil pressure produced does not in any way depend upon the fault current to be broken. SCITS, KARIMNAGAR 14 DEPARTMENT OF EEE
  • 15.  ADVANTAGES 1. The quantity of oil required is reduced considerably. 2. The performance at low currents is more consistent than with self-blast oil circuit breakers.  APPLICATIONS OF BULK OIL CIRCUIT BREAKER 1. Used up to to12Kv,500MVA  MERITS 1. Simplicity in construction. 2. High rupturing capacity 3. Suitability for automatic as well as manual operation. 4. Possibility of locating CT’s in bushings.  DEMERITS 1. Large size and greater weight. 2. Unsuitable for indoor installation. 3. Greater wear and tear of the contacts resulting in their frequent replacement. 4. Fire hazard. 2.2.6 LOW OIL CIRCUIT BREAKERS 1. It is found only a small percentage of oil is actually used for arc extinction while major part is utilized for insulation purposes. 2. For this reason, the quantity of oil in bulk oil reaches a very high figure as the system voltage increases. 3. This not only increase the expenses, tank size and weight of the breaker but it also increases the fire risk and maintenance problems. SCITS, KARIMNAGAR 15 DEPARTMENT OF EEE
  • 16. Fig 2.6 Minimum Oil Circuit breaker SCITS, KARIMNAGAR 16 DEPARTMENT OF EEE
  • 17.  WORKING In a minimum oil circuit breaker, the arc drawn across the current carrying conductor is contained inside the arcing chamber; hence the hydrogen bubble formed by the vaporized oil is trapped inside the chamber. As the contacts continue to move, after its certain travel an exit vent becomes available for exhausting the trapped hydrogen gas. There are two different types of arcing chamber is available in terms of venting are provided in the arcing chambers. One is axial venting and other is radial venting. In axial venting gases (mostly hydrogen), produced due to vaporization of oil and decomposition during arc, will sweep the arc in axial or longitudinal direction. Fig 2.7 MOCB working Fig 2.8 MOCB Arcing chamber SCITS, KARIMNAGAR 17 DEPARTMENT OF EEE
  • 18. Fig 2.9 MOCB Arc Formation Fig 2.10 MOCB Arc Extinction  MERITS 1. It requires lesser quantity of oil & it requires smaller space. 2. There is reduced risk of fire 3. Maintenance problems are reduced.  DEMERITS 1. Due to smaller quantity of oil, the degree of carbonization is increased. 2. There is a difficulty of removing the gases from the contact space in time. 3. The dielectric strength of the oil deteriotes rapidly due to high degree of carbonization SCITS, KARIMNAGAR 18 DEPARTMENT OF EEE
  • 19. 2.3 AIR BLAST CIRCUIT BREAKER  These breakers employ a high pressure air blast as an arc quenching medium  Arc is chopped into a number of small arcs by the Arc-Shute as it rises due to heat and magnetic forces.  The contacts are opened in a flow of air blast  The air circuit breakers are normally employed for 380-480V distribution.  Suitable for high current interruption at low voltages. 2.3.1 PRINCIPAL OF OPERATION Fig 2.11 Air blast C.B Principle of operation SCITS, KARIMNAGAR 19 DEPARTMENT OF EEE
  • 20. 2.3.2 TYPES OF AIR BLAST CIRCUIT BREAKER 1. Axial-blast CB 2. Cross-blast CB 3. Radial-blast CB Fig 2.12 Types of Air Blast C.B  ADVANTAGES  The risk of fire is eliminated.  The arcing products are completely removed by the blast.  The arcing time is very small due to the rapid buildup of dielectric strength between contacts.  DISADVANTAGES  Air has relatively inferior arc extinguishing properties.  Air blast circuit breakers are very sensitive to the variations in the rate of restriking voltage.  Considerable maintenance is required for the compressor plant which supplies the air blast.  APPLICATIONS The air blast circuit breakers are finding wide applications in high voltage installations. Majority of the circuit breakers for voltages beyond 110 kV are of this type. SCITS, KARIMNAGAR 20 DEPARTMENT OF EEE
  • 21. 2.4 SULPHUR HEXAFLOURIDE GAS (SF6) A circuit breaker in which the current carrying contacts operate in sulphur hexafluoride or SF6 gas is known as an SF6 circuit breaker. SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has high affinity of absorbing free electron. Whenever a free electron collides with the SF6 gas molecule, it is absorbed by that gas molecule and forms a negative ion. The attachment of electron with SF6 gas molecules may occur in two different ways, These negative ions obviously much heavier than a free electron and therefore over all mobility of the charged particle in the SF6 gas is much less as compared other common gases. We know that mobility of charged particle is majorly responsible for conducting current through a gas. Fig 2.13 SF6 C.B SCITS, KARIMNAGAR 21 DEPARTMENT OF EEE
  • 22. 2.4.1 WORKING OF SF6 The working of SF6 CB of first generation was quite simple it is some extent similar to air blast circuit breaker. Here SF6 gas was compressed and stored in a high pressure reservoir. During operation of SF6 circuit breaker this highly compressed gas is released through the arc in breaker and collected to relatively low pressure reservoir and then it pumped back to the high pressure reservoir for re utilize. The working of SF6 circuit breaker is little bit different in modern time. Innovation of puffer type design makes operation of SF6 CB much easier. In buffer type design, the arc energy is utilized to develop pressure in the arcing chamber for arc quenching. Fig 2.14 SF6 CB Working SCITS, KARIMNAGAR 22 DEPARTMENT OF EEE
  • 23. Fig 2.15 SF6 CB Operation Hence, for heavier and less mobile charged particles in SF6 gas, it acquires very high dielectric strength. Not only the gas has a good dielectric strength but also it has the unique property of fast recombination after the source energizing the spark is removed. The gas has also very good heat transfer property. Due to its low gaseous viscosity (because of less molecular mobility) SF6 gas can efficiently transfer heat by convection. So due to its high dielectric strength and high cooling effect SF6 gas is approximately 100 times more effective arc quenching media than air. Due to these unique properties of this gas SF6 circuit breaker is used in complete range of medium voltage and high voltage electrical power system. These circuit breakers are available for the voltage ranges from 33KV to 800KV and even more. SCITS, KARIMNAGAR 23 DEPARTMENT OF EEE
  • 24. Types of SF6 Circuit Breaker There are mainly three types of SF6 CB depending upon the voltage level of application- 1. Single interrupter SF6 CB applied for up to 245 KV (220 KV) system. 2. Two interrupter SF6 CB applied for up to 420 KV (400 KV) system. 3. Four interrupter SF6 CB applied for up to 800 KV (715 KV) system.  ADVANTAGES  Excellent insulating, arc extinguishing, physical and chemical properties of SF6 gas is greater advantage of SF6 circuit breakers  Electrical clearances are very much reduced because of high dielectric strength of SF6  Its performance is not affected due to variation in atmospheric conditions  It gives noiseless operation it does not make sound like air-blast circuit breaker during operation  Same gas is re-circulated into the circuit thereby reducing the requirement of SF6 gas.  No over voltage problem. The arc is extinguished at natural current zero without the current chopping and associated over-voltages originating across the circuit breaker terminals  DISADVANTAGES  Imperfect joints leading to leakage of the SF6 gas. Continuous monitoring devices are required  Arced SF6 gas is poisonous and should not be inhaled  The internal parts need thorough cleaning during periodic maintenance under clean and dry environment. Dust of Teflon and sulphides should be removed  APPLICATIONS  SF6 Circuit breakers are mostly employed for High voltage applications SCITS, KARIMNAGAR 24 DEPARTMENT OF EEE
  • 25. 2.5 TESTING OF CIRCUIT BREAKERS Why test circuit breakers? Some of the most important of the many reasons for testing circuit breakers are to ensure they are: 1. Provide protection for expensive equipment. 2. Prevent outages that lead to loss of income. 3. Ensure reliability of the electricity supply. 4. Prevent downtime and darkness. 5. Verify breaker performance. Substation breaker testing is an important task for any power utility .The breakers are there to facilitate the flow of current during normal operation and to interrupt current flow in the event of a fault.however,all electricity operated devices are, sooner or later, likely to experience some kind of failure. That failure can be caused by many facors, including ageing and external faults. The power utility operator has to be prepared and have a plan in place to handle every situation. Testing of circuit breakers is more difficult than other electrical equipment like transformer or machine because the short circuit current are very large .Also there is no satisfactory method of testing circuit breaker at reduced power. The testing plan of circuit breaker consists of essentially of a specially designed alternator capable of giving about 2000MVA under short circuit condition the prime mover of the alternator is 750KV motor end is disconnected just before the short circuiting is done. The kinetic energy of rotor is sufficient to give the desired energy for testing purpose. Testing of circuit breaker can be classified in to two main groups SCITS, KARIMNAGAR 25 DEPARTMENT OF EEE
  • 26.  TYPE TEST  ROUTINE TEST TYPE TEST These test are conducted on first few proto type circuit breakers of each type for the purpose of providing the capabilities and confirming the rated characteristics of the circuit breaker of that design. Such test is conducted in specially built testing laboratories. Type test are broadly classified as  Mechanical Performance test.  Thermal test.  Insulation test  Short circuit test  MECHANICAL TEST These are mechanical endurance type tests involving repeated opening and closing of the circuit breaker. A circuit breaker must open and close at the correct speed and perform its designated duty and operation without mechanical failure.  THERMAL TEST Thermal test are carried out to check the thermal behavior of the circuit breakers. The breaker under test is subjected to study state temperature rise due to flow of its rated current through its poles in closed condition. The temperature rise for rated current should not exceed 40oC for current less than 800A normal current and 50oC for normal value of current 800A and above. In such sets the contact drops or contact resistances are also measured as these contacts surfaces are responsible for generation of heat and subsequent temperature rise. SCITS, KARIMNAGAR 26 DEPARTMENT OF EEE
  • 27.  DIELECTRIC TESTS These tests are performed to check power frequency and impulse voltage withstand capacity. Power frequency tests are conducted on clean new circuit breaker, the test voltage varies with circuit breaker rated voltage. The test voltage with a frequency between 15 to 100HZ is applied as follows.  Between poles with circuit breaker closed  Between poles and earth with circuit breaker open.  Across terminals with circuit breaker open The voltage is gradually increased and maintained at test value for one minute. In impulse voltage of specified shape and magnitude applied to the breaker. For outdoor circuit dry and wet test are conducted.  SHORT CIRCUIT TESTS Circuit breakers are subjected to sudden short circuit in the short circuit test laboratories and oscillograms are taken to know the behavior of circuit breaker at the time of switching in, during contact breaking and after arc extinction. The oscillograms are studied with particular reference to the making and braking currents, both symmetrical and asymmetrical.  ROUTINE TEST Once type tests are conducted and a particular design is found to be satisfactory the product becomes prototype and a large number of circuit breaker of similar design manufactured. However, each and every circuit breaker still subjected to a few more tests before commissioning. These tests are called routine test. SCITS, KARIMNAGAR 27 DEPARTMENT OF EEE
  • 28. 2.6 APPLICATIONS OF CIRCUIT BREAKER Depending on its application in the network the CB’s Service life differs. For instance, line circuit breakers operate seldom and have a longer service life than.  Generator CB  High Voltage CB  Capacitor CB  Reactor CB  High voltage DC CB  Distribution CB  Traction CB  Industrial CB SCITS, KARIMNAGAR 28 DEPARTMENT OF EEE
  • 29. CHAPTER III VACCUM CCIRCUIT BREAKER 3.1 INTRODUCTION A vacuum circuit breaker is such kind of circuit breaker where the arc quenching takes place in vacuum. The technology is suitable for mainly medium voltage application. For higher voltage vacuum technology has been developed but not commercially viable. The operation of opening and closing of current carrying contacts and associated arc interruption take place in a vacuum chamber in the breaker which is called vacuum interrupter. The vacuum interrupter consists of a steel arc chamber in the centre symmetrically arranged ceramic insulators. The material used for current carrying contacts plays an important role in the performance of the vacuum circuit breaker. CuCr is the most ideal material to make VCB contacts. Vacuum interrupter technology was first introduced in the year of 1960. But still it is a developing technology. As time goes on, the size of the vacuum interrupter is being reducing from its early 1960’s size due to different technical developments in this field of engineering. The contact geometry is also improving with time, from butt contact of early days it gradually changes to spiral shape, cup shape and axial magnetic field contact. The vacuum circuit breaker is today recognized as most reliable current interruption technology for medium voltage switchgear. It requires minimum maintenance compared to other circuit breaker technologies 3.2 PRINCIPLE Two contacts called electrode remains closed under normal operating conditions. When fault occurs on any part of the system, the trip coil of the Vaccum circuit breaker gets energized and contacts are separated by the vaccum pressure which is having around (10-7 to 10-5 torr). The arc is quickly SCITS, KARIMNAGAR 29 DEPARTMENT OF EEE
  • 30. extinguished because the metallic vapors, electrons, and ions produced during arc condense quickly on the surfaces of the circuit breaker 3.3 OPERATION The main aim of any circuit breaker is to quench arc during current zero crossing, by establishing high dielectric strength in between the contacts so that reestablishment of arc after current zero becomes impossible. The dielectric strength of vacuum is eight times greater than that of air and four times greater than that of SF6 gas. This high dielectric strength makes it possible to quench a vacuum arc within very small contact gap. For short contact gap, low contact mass and no compression of medium the drive energy required in vacuum circuit breaker is minimum. When two face to face contact areas are just being separated to each other, they do not be separated instantly, contact area on the contact face is being reduced and ultimately comes to a point and then they are finally de-touched. Although this happens in a fraction of micro second but it is the fact. At this instant of de-touching of contacts in a vacuum, the current through the contacts concentrated on that last contact point on the contact surface and makes a hot spot. As it is vacuum, the metal on the contact surface is easily vaporized due to that hot spot and create a conducting media for arc path. Then the arc will be initiated and continued until the next current zero. 3.4 CONSTRUCTION A schematic diagram of the vaccum C.B is shown in below fig .it is a very simple device as compared to an air or oil C.B. The outer envelope is normally made of glass due to the ease of joining it to the metallic end caps and also because the glass envelope makes it easy to examine from outside state of the contacts after the breaker has interrupted the current. This is important since a change from a silvery mirror like finish to a milky white color shows that the baffle is losing its vacuum. A sputter shield is provided in between the contacts and the envelope in order to prevent the metal vapour reaching the envelope as it SCITS, KARIMNAGAR 30 DEPARTMENT OF EEE
  • 31. reduces the breakdown strength between the contacts. This is generally made of stainless steel. Inside the sputter shield the breaker has two contacts, one fixed and the other moving contact which moves through a short distance of 5 to 10 mm depending upon the operating voltage. The metallic bellows made of stainless steel is used to move the lower contact. The design of the bellows is very important as the life of vacuum breaker depends upon the ability of this part to perform repeated operations satisfactorily. Fig 3.1 Vaccum Circuit Breaker SCITS, KARIMNAGAR 31 DEPARTMENT OF EEE
  • 32. The periphery of the end cap is sealed to the envelope and the fixed contact stem is an integral part of one end cap .one end of the fixed as well as moving contact is brought out of the chamber for external connections. The lower end of the circuit breaker is fixed to a spring operated or solenoid operated mechanism so that the metallic bellows inside the chamber are moved downward and upward during opening and closing operation respectively. It is to be noted that the operating mechanism should provide sufficient pressure for a good concentration between the contacts and should avoid any bouncing action Fig 3.2 Front view Fig 3.3 Rear view SCITS, KARIMNAGAR 32 DEPARTMENT OF EEE
  • 33. Fig 3.4 Cross section view of VCB 3.5 THE VACUUM ARC The vacuum arc results from the neutral atoms, ions and electrons emitted from the electrodes themselves. As the current carrying contacts are separated, cathode spots are formed depending upon the current to be interrupted. For low currents a highly mobile cathode spot is formed and for large currents a multiple number of cathode spots are formed. These spots constitute the main source of vapour in the arc. The processes involved in drawing the arc will be due to high electric field between the contacts or resistive heating produced at the point of operation or a combination of the two. The cathode surfaces normally are not perfectly smooth but have many micro projections. When the contacts are separating, the current flowing in the circuit will be concentrated in these projections as they form the last point of contact. Due to their small area of cross section, the projections will suffer explosive evaporation by resistive hating and supply sufficient quantity of vapour for the arc formation. Since in case of vaccum breakers the emission occurs only at the cathode spots and not from the entire surface of the cathode, the vaccum arc is also known as cold cathode arc. In cold cathode the emission of electrons could be due to any of the combinations of the following mechanisms:  Field emission  Thermionic emission SCITS, KARIMNAGAR 33 DEPARTMENT OF EEE
  • 34.  Field and thermionic emission  Secondary emission by positive ion bombardment  Secondary emission by photons  Pinch effect. 3.6 VACUUM ARC STABILITY In a.c. circuit the current passes through zero value 100 times in a second. It is desirable to interrupt the current chopping .Therefore, it is necessary for successful arc interruption that it be stable for half cycle duration and particularly it should continue to exist when the current approaches zero. The stability of arc in vacuum depends upon  The contact material and its vapour pressure.  Circuit parameters such as voltage,current,inductance and capacitance 3.7 VACUUM ARC-RECOVERY PHENOMENON When the arc interruption is over, the space between the surrounding the electrodes is filled with vapour and plasma. The presence of this residue affects very much the ability of an interrupter to withstand high voltages. the process by which this residue decays and by which the vaccum gap regains its dielectric strength is known as arc recovery phenomenon at current zero the cathode spot extinguishes within in 10-8 second and after this the original dielectric strength is established very soon this quick build up of dielectric strength is due to the condensing, quick diffusion and of metal vapour to the glass walls in absence of gas molecules. After the arc is interrupted, the recovery strength during the first few micro seconds is 1kV/μsec for an arc current of 100A, as compared with 50V/μsec in case of air gap. SCITS, KARIMNAGAR 34 DEPARTMENT OF EEE
  • 35. 3.8 CURRENT CHOPPING PHENOMENON Post-arc current phenomena that occur when interrupting high currents with vacuum circuit breakers have been investigated. High resolution measuring equipment has been used to measure both the post-arc current and the arc voltage in the current-zero regions. Three examples of frequently observed phenomena are described. The first describes the phenomenon that in the event of a current-chopping, the current is zero for a short period of time just before the natural alternating current zero, but continues to flow afterwards, in the form of a post-arc current. The second and third example deal with the post-arc phenomena after currents those are much higher than the test breakers rated short-circuit current. These examples show a low-voltage period after current-zero. Apparently, during this post-arc period, the residual plasma between the breaker's contacts conduct well. In addition to the voltage-zero periods, the voltage trace in the third example also shows evidence of current-chopping. This means that the plasma conducts poorly just before current-zero, but conducts well immediately afterwards. Fig 3.5 Current chopping phenomenon SCITS, KARIMNAGAR 35 DEPARTMENT OF EEE
  • 36. 3.9 SPECIFICATIONS  It is designed for medium voltage range (3.3-33kv).  This consists of vacuum of pressure (10-7 to 10-5) inside arc extinction chamber.  Vacuum is used as an arc quenching medium  At high voltage, its rate of dielectric strength recovery is very high.  Have greatest insulating strength  ADVANTAGES  Free from arc and fire hazards.  Low cost for maintenance & simpler mechanism.  Low arcing time & arc extinction is very fast.  Silent and less vibrational operation.  Can interrupt any fault current.  It has higher dielectric strength.  Requires small amount of power for operation  APPLICATIONS  For outdoor applications ranging from 11 KV to 33 KV.  Suitable for majority of applications in rural area.  They can be used where the switching frequency is high.  They can be used along with static over current relays.  This gives a fast RRRV and vacuum circuit breakers are the best solutions. SCITS, KARIMNAGAR 36 DEPARTMENT OF EEE
  • 37. CHAPTER IV CONCLUSION A vacuum circuit breaker (VCB) has demonstrated its ability to interrupt short circuits with faster than normal rates of rise of transient recovery voltage (TRV) at levels greater than those produced by most transformer secondary faults. Two recent exploratory test programs evaluated the interrupting ability of a 15 kV VCB containing interrupters of the rotating arc type with contacts made from a chromium-copper powder metal mixture. The interrupting conditions covered a wide range of currents from 10% to 130% of the 28 kA rated short circuit current of the tested circuit breaker and a wide range of TRV rates of rise. These tests showed that the interrupting performance of the tested VCB was unaffected by the TRV rate of rise to the fastest rates available in the test laboratory. Such a VCB can therefore be used without TRV modifying capacitors to slow down the rate of rise provided by the power system. This ability is particularly important if analysis shows that the expected TRV from a transformer secondary fault has a fast rate of rise beyond the recognized ability of an older circuit breaker to acceptably interrupt. SCITS, KARIMNAGAR 37 DEPARTMENT OF EEE
  • 38. REFERENCES 1.Electrical power systems by C.L.Wadhwa, New Age international Publishers. 2.Switch Gear Protection and Power Systems by Sunil S.Rao, Khanna Publishers. 3.Modern Power System Analysis by D. P Kothari & I.J Nagrath. Eastern Economy Edition. 4.Power Systems by J.B GUPTA, Katson Books. 5.Power system Protection and Switchgear, by B.Ravindranath and Michener, Wiley Eastern SCITS, KARIMNAGAR 38 DEPARTMENT OF EEE