GENERATOR PROTECTION
By – Parimal Bhagat
B.E Electrical, PG Diploma In Sub
T&D(NPTI,Bengaluru)
SYSTEM OVERVIEW
There are two Generator protection panel installed.
GRP Cubicle A & GRP Cubicle B
Both protection cubicles are having following IED’s
1) Micom P344 Generator Protection
2) Micom P342 Generator Protection
3) Micom P141 Excitation Transformer Protection
MICOM P344 RELAY INCORPORATED WITH
FOLLOWING PROTECTIONS
1) Generator Differential Protection (87G)
2) Inter turn fault Protection (50G1)
3) Negative sequence Over Current Protection (46G)
4) Stator Over Load(Current) Protection (50GS)
5) Voltage Restrained Over Current Protection (51V)
6) Dead Machine (61B)
7) Back Up Impedance (21G)
8) Over Fluxing (99G)
9) 95% Stator Earth Fault Protection (64G1)
10) 100% Stator Earth Fault (64G2)
11) Breaker failure (50LBB)
12) Loss Of excitation with under voltage (27/40G)
13) Generator Rotor Earth fault (64F)
14) Generator Pole Slipping(Out of step) Protection (78G)
PROTECTION SCHEME TESTING
Generator Differential Protection (87G)
It operates on principle that current entering & leaving protection zone should be equal. Any
difference between that indicates fault current present in protected zone.
HEALTHY CIRCUIT :
By lenz law secondary current in healthy circuit will be just opposite to primary
current.
Since primary current is equal then circulating current also will be the same.
Id = i1-i2 =0Amp
where i1=i2
Heavy through current arising from external faults can cause one
CT to saturate more than other, resulting in difference between
secondary current produced by each CT’s, its essential to stabilize
the protection for these condition. A biasing technique where the
relay setting increased as the through current increased. The
through current is calculated as the average of the scalar sum of
current entering & leaving the zone of protection, this calculated
through current is then used to apply a percentage bias to increase
the differential setting.
RELAY SETTINGS :
INTER TURN FAULT PROTECTION (50G1)
In healthy 3 phase power system the addition of each phase to earth is normally
zero, as it is vector addition of three balanced vectors at 120° to another.
However when inter turn fault or earth fault occurs on primary system this balance
upset and residual voltage produced.
The neutral displacement voltage can be measured directly via the open delta PT .
RELAY SETTINGS:
STATOR OVER LOAD(50GS)
Protection reacts on current flowing on stator winding coil to protect winding from
overheat.
Overload can result in stator temp. rise which exceeds the thermal limits of windings.
Due to relatively large heat storage capacity of electric machine, infrequent
overload of short duration may not damage the machine, however sustained
overload of few percentage may result in premature aging and failure of insulation.
RELAY SETTINGS :
Over-load (50GS)
PHASE O/C
Menu text
Setting range
Setting
Min Max
I>1 Function
Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK
Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST
Inverse
DT
I>1 Direction Non-directional, Directional Fwd, Directional Rev Non-directional
I>1 Current Set 0.08 In 4.0 In 4.50A
I>1 Time Delay 0 100 5s (reduce load)
I>2 Function
Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK
Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST
Inverse
IEC E inverse
I>2 Direction Non-directional, Directional Fwd, Directional Rev Non-directional
I>2 Current Set 0.08 In 4.0 In 4.75A
I>2 Time Delay 0 100
I>2 TMS 0.025 1.2 0.45
VOLTAGE RESTRAINED OVER CURRENT (51V)
This protection reacts on voltage, negative sequence voltage and current as a back up
protection to detect grounding and phase to phase short circuits.
The voltage restrained over current adjust the pickup setting and characteristic curve of the
overcurrent function based on the system voltage. The relay is set pickup current greater
than overload, and sensitivity increase as the voltage drops.
The voltage controlled overcurrent relays uses and under voltage element to the supervise
the operation of overcurrent element.
When voltage drops below the set value the under voltage element permits the operation
of the time over current units.
Voltage Restrained Overcurrent (51V)
I>3 Status Disabled or Enabled Enabled
I>3 Direction Non-directional, Directional Fwd, Directional Rev Non-directional
I>3 Current Set 0.08 In 32 In 5.15A
I>3 Time Delay 0 s 100 s 0.0s
I>Function Link
Bit 0=VTS Blocks I>1, Bit 1=VTS Blocks I>2, Bit 2=VTS Blocks I
>3, Bit 3=VTS Block I>4, Bits 4~7 are not used.
Bit 3=VTS Block I>4
NEGATIVE SEQUENCE OVER CURRENT (46G)
NPS protection is provided to protect generator against the unbalanced load and as a back
up for uncleared unsymmetrical faults.
The Negative sequence current create magnetic flux in the air gap which rotates in
opposition to the rotor. This flux induce eddy current as twice the fundamental frequency in
the rotor which cause overheating of rotor body, wedged and retaining rings. The rotor body
gets heated instantaneously.
RELAY SETTINGS :
95% STATOR EARTH FAULT PROTECTION (64G1)
There is a limit on the percentage of winding that can be protected by stator earth fault
element. For the earth fault close to generator neutral side, the driving voltage will very low
and hence fault current will be severely reduced. In practice approximately 95% of stator
winding will can be protected for the fault in last 5% of winding the fault current is very low
which can not be detected by this type of earth fault.
Single phase earth fault with in 85%-95% range from terminal of stator winding can be
protected by fundamental zero-sequence overvoltage protection.
SCHEME ARRANGEMENT FOR 95% & 100% STATOR
EARTH FAULT PROTECTION :
RELAY SETTING :
100% STATOR EARTH FAULT PROTECTION (64G2)
In this protection 100% stator winding is covered in protection zone. Low probability
fault occurring in 5% of the stator winding near to star point is due to mechanical
damage such as creepage of conductors, loosening of boult etc.
Most of the generator produce third harmonic voltage due to non linearities in
magnetic circuit of generator design, under normal operating condition distribution of
third harmonic voltage along the stator winding. The value increases with the load.
To detect the fault in last 5% of winding the relay is provided with under & over
voltage element.
The third harmonic under voltage element is applicable when the neutral voltage measured
is available at the neutral end of the generator.
To prevent false tripping operation when the machine is dead or under no load condition
power interlock is used to detect load.
SCHEME ARRANGEMENT FOR 95% & 100% STATOR
EARTH FAULT PROTECTION :
RELAY SETTING :
V<Inhibit Set 80V
P<Inhibit set Disabled, Enabled Enabled
P<Inhibit set 20.00W
Q<Inhibit set Disabled, Enabled Disabled
S<Inhibit set Disabled, Enabled Disabled
POLE SLIPPING PROTECTION (78G)
Sudden changes or shock in electrical system such as line switching operation, transient
system fault, generator governor failure, excitation system failure, reconnection of islanding
system without synchronization, large jumps in load or fault may lead to power system
oscillations which appears as regular variations of current and angular separation between
systems.
At times, this power swing becomes so sever that it can lead lost of synchronism between
generator and system, this condition recognized as out of step or pole slipping.
OVER FLUXING PROTECTION (99G)
Over fluxing or over excitation of generator can increase if the ratio of voltage to
frequency (V/HZ) increased certain limits. High voltage or low frequency can rise V/Hz
ratio, it will produce high flux densities in magnetic core of machines, this can cause core of
generator to be saturated & stary flux to be induced in un laminated components that have
not been designed to carry this flux, the resulting eddy current in solid components (e.g. core,
bolts & supporting structure) can cause rapid overheating & damage.
Over fluxing likely to occur during machine start up & shutdown while the generator is not
connected to the system.
Failure in automatic control of excitation system or errors in manual control of machine field
current, could allow excessive voltage to be generated.
Sudden loss of load could cause an overvoltage condition, if generator excitation system
does not respond properly.
BREAKER FAILURE PROTECTION (50LBB)
The LBB protection is used as back up protection of main protection, during this
protection, relay sense the breaker position, flow of current & trip command
generated by itself.
RELAY SETTINGS
BACK UP IMPEDANCE PROTECTION (27G)
Generator is source of power & it will supply fault current until they are cleared by
the protection system.
Back up protection applied at the generator so that faults are cleared in the event of
downstream protection/breaker fails to operate.
Under impedance element is set to monitor the system impedance at machine
terminal, if the measured impedance falls below set value then relay will operate.
DEAD MACHINE (61B)
Accidental energization of breaker when machine is not running can cause severe
damage to machine.
If the breaker is closed when machine is not running then generator will began act as
induction motor with the surface of rotor core & rotor winding slot wedges acting as
rotor conductor ,this abnormal current will result in overheating and damaged.
The relay element is enabled when the machine is not running ,there for element can
have very low current setting, the undervoltage threshold typically set to 85% of
nominal voltage to ensure that machine is not running.
RELAY SETTINGS :
LOSS OF EXCITATION WITH UNDER
VOLTAGE(27/40)
Complete loss of excitation may arise as a result of accidental tripping of excitation
system, failure of field breaker , an open circuit or short circuit happened in DC
circuit, flashover of any slip ring or failure of excitation source.
When excitation of synchronous generator fails its internal emf will decay and output
of active power will reduce and it will draw large reactive power grid, hence
machine will act as a induction generator, after filed failure circulating current will
induce in rotor core and rotor heat, also stator winding may get damaged severely.
RELAY SETTING
ROTOR GROUND FAULT PROTECTION (64R)
The Generator rotor earth fault protection is provided to protect the generator rotor
and exciter rotor winding against earth fault. The rotor earth fault relay sense the
resistance between rotor winding and ground through carbon brushes mounted on slip
rings.
MICOM P342 RELAY INCORPORATED WITH FOLLOWING
PROTECTIONS :
1. Low Forward Power Protection (37G)
2. Reverse Power Protection (32G)
3. Under frequency Protection (81U)
4. Over frequency Protection (81O)
5. Over Voltage Protection (59G)
6. Under Voltage Protection (27G)
7. Generator Stator Water flow minimum
8. Excitation system failure
9. Excitation transformer temp. high
LOW FORWARD POWER PROTECTION (37G)
When machine is generating and CB connecting the generator to the system is
tripped, the electrical load on the generator is cut, this could lead to generator over
speed if the machine input power is not reduced quickly.
Trapped system in the turbine, risk of over speed damage to such sets, interlock is
used for non urgent tripping of the generator breaker and excitation system with a
low forward power check.
Relay Settings
REVERSE POWER PROTECTION (32G)
It is back up protection to low forward protection. If the generator prime mover falls,
generator is connected in parallel with another source of electrical supply will begin as
“Motor” . The generator will operator as a synchronous motor and drive the turbine. Here in
this condition draw the real power (MW) from the bus & and export reactive power (MVAR)
to grid.
If the filed breaker closed but field current is zero, the generator will act as an induction
motor. Here in this condition generator will draw real power as well as reactive power from
the grid
In this condition generator will not be harmed by synchronous motoring but steam
turbine can be harmed due to winding loss of causing overheating of turbine blade if
continued long enough.
The sensitivity and setting of the relay is depending on the type of prime movers.
Causes of Reverse Power Protection :
Two or more machines are running in parallel and prime mover of machine fails.
RELAY SETTINGS
OVER VOLTAGE (59G)
The over voltage protection will act as a back up protection of the over fluxing
protection. The over voltage protection is required to protect the stator conductor
insulation of the generator. This is directly connected to Gen. phase side PT secondary
terminals.
Causes of over voltage :
Prime mover over speed due to sudden loss of load.
Voltage regulator (AVR) is defective.
RELAY SETTING
OVER FREQUENCY PROTECTION (81O)
The over frequency protection is provided to protect the generator against over
speed. Sever high speed operation of generator set could result in damaged.
Causes of over frequency :
Demand of active power suddenly decreased in power grid
Full or partial load rejection (Load thrown off)
Over shedding of load during major disturbance. Generator CB oprn during load.
RELAY SETTING :
UNDER FREQUENCY PROTECTION (81U)
The under frequency protection is used to protect the generator against operation at
low frequency.
If the frequency goes down, the speed of turbine get reduced, hence the steam may
get condensed on turbine blades and damage them.
Causes of under frequency :
Demand of active power suddenly increased in grid.
Islanded system two or more system running in parallel on more than 70% load &
outage of nay machine due to fault increased the load to another machine will result
in under frequency operation.
RELAY SETTING :
UNDER VOLTAGE (27G)
Generator are usually designed to operate continuously at a minimum voltage of 95% of its
rated voltage, while generate power at rated frequency.
Generator terminal voltage goes lower than 85% of its rated voltage may result in
undesirable effects such as reduction in stability limits, import of excessive reactive power
from grid, malfunctioning of voltage sensing devices and equipment.
The under voltage relay works in secondary value if PT which is connected with generator
output terminals.
RELAY SETTING:
NON DIRECT PROTECTION
❑Generator stator water flow minimum
Generator CW flow minimum link to be closed, protection simulated from C&I cabinet ( if
stator water pump not running then signal will come high)
❑Excitation system fault
Protection simulated from AVR end at micom P342 relay assigned o/p becomes high & EXT
trip LED becomes high.
❑Excitation transformer temp. high
Protection simulated from excitation transformer end for low setting at P342 relay o/p
assigned becomes high.
For high setting at P342 assigned relay becomes high.
Thank You

Weitere ähnliche Inhalte

Was ist angesagt?

MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxrajkumarmaurya31
 
transformer protection
transformer protection transformer protection
transformer protection jason adidela
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Motor protection
Motor protectionMotor protection
Motor protectionH. Kheir
 
Different types of Transformers used in Generating Station
Different types of Transformers used in Generating StationDifferent types of Transformers used in Generating Station
Different types of Transformers used in Generating StationVasanthan Ravichandran
 
Esp rectifier transformer
Esp rectifier transformerEsp rectifier transformer
Esp rectifier transformerMolla Morshad
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance Molla Morshad
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEMBHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEMyash Natani
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
A presentation on turbogenerator and excitor
A presentation on turbogenerator and excitorA presentation on turbogenerator and excitor
A presentation on turbogenerator and excitorPRAKHAR MEHROTRA
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformerKapil Singh
 
Design turbo generator
Design turbo generatorDesign turbo generator
Design turbo generatorMolla Morshad
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 

Was ist angesagt? (20)

MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
 
Generator capability curve
Generator capability curve Generator capability curve
Generator capability curve
 
transformer protection
transformer protection transformer protection
transformer protection
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Motor protection
Motor protectionMotor protection
Motor protection
 
Different types of Transformers used in Generating Station
Different types of Transformers used in Generating StationDifferent types of Transformers used in Generating Station
Different types of Transformers used in Generating Station
 
Esp rectifier transformer
Esp rectifier transformerEsp rectifier transformer
Esp rectifier transformer
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEMBHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
A presentation on turbogenerator and excitor
A presentation on turbogenerator and excitorA presentation on turbogenerator and excitor
A presentation on turbogenerator and excitor
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformer
 
Turbo generator
Turbo generator Turbo generator
Turbo generator
 
Design turbo generator
Design turbo generatorDesign turbo generator
Design turbo generator
 
220kv substation
220kv substation220kv substation
220kv substation
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 

Ähnlich wie Generator protection

Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
 
Generator protection
Generator protectionGenerator protection
Generator protectionSSVASAVA
 
Generator protection
Generator protectionGenerator protection
Generator protectionKeshar Rawal
 
An-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfAn-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfRamprasadSarkar1
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.pptsanipriadi1
 
class on Protection.pptx
class on Protection.pptxclass on Protection.pptx
class on Protection.pptxSubhroSen9
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarBhushan Kumbhalkar
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2Rahaf Waheep
 
Generator Transformer Protections.
Generator Transformer  Protections.Generator Transformer  Protections.
Generator Transformer Protections.Nischal Popat
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
 
Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...Mohammad Raza
 
Protection Systems for Power generators
Protection Systems for Power generators Protection Systems for Power generators
Protection Systems for Power generators Nicholas Naing
 
Report BQPS II- Saad Janjua
Report BQPS II- Saad JanjuaReport BQPS II- Saad Janjua
Report BQPS II- Saad JanjuaSaad Janjua
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. katoAgrey Kato
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protectionDinesh Sharma
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power Systemvkmalik
 

Ähnlich wie Generator protection (20)

Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
An-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfAn-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdf
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt
 
class on Protection.pptx
class on Protection.pptxclass on Protection.pptx
class on Protection.pptx
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
protection Training.pptx
protection Training.pptxprotection Training.pptx
protection Training.pptx
 
Generator Transformer Protections.
Generator Transformer  Protections.Generator Transformer  Protections.
Generator Transformer Protections.
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...Backup fault protection for generators in case of a failure at the generation...
Backup fault protection for generators in case of a failure at the generation...
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
Protection Systems for Power generators
Protection Systems for Power generators Protection Systems for Power generators
Protection Systems for Power generators
 
Report BQPS II- Saad Janjua
Report BQPS II- Saad JanjuaReport BQPS II- Saad Janjua
Report BQPS II- Saad Janjua
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
5010566.ppt
5010566.ppt5010566.ppt
5010566.ppt
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
 

Kürzlich hochgeladen

Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 

Kürzlich hochgeladen (20)

young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 

Generator protection

  • 1. GENERATOR PROTECTION By – Parimal Bhagat B.E Electrical, PG Diploma In Sub T&D(NPTI,Bengaluru)
  • 2. SYSTEM OVERVIEW There are two Generator protection panel installed. GRP Cubicle A & GRP Cubicle B Both protection cubicles are having following IED’s 1) Micom P344 Generator Protection 2) Micom P342 Generator Protection 3) Micom P141 Excitation Transformer Protection
  • 3. MICOM P344 RELAY INCORPORATED WITH FOLLOWING PROTECTIONS 1) Generator Differential Protection (87G) 2) Inter turn fault Protection (50G1) 3) Negative sequence Over Current Protection (46G) 4) Stator Over Load(Current) Protection (50GS) 5) Voltage Restrained Over Current Protection (51V) 6) Dead Machine (61B) 7) Back Up Impedance (21G) 8) Over Fluxing (99G)
  • 4. 9) 95% Stator Earth Fault Protection (64G1) 10) 100% Stator Earth Fault (64G2) 11) Breaker failure (50LBB) 12) Loss Of excitation with under voltage (27/40G) 13) Generator Rotor Earth fault (64F) 14) Generator Pole Slipping(Out of step) Protection (78G)
  • 5. PROTECTION SCHEME TESTING Generator Differential Protection (87G) It operates on principle that current entering & leaving protection zone should be equal. Any difference between that indicates fault current present in protected zone.
  • 7. By lenz law secondary current in healthy circuit will be just opposite to primary current. Since primary current is equal then circulating current also will be the same. Id = i1-i2 =0Amp where i1=i2
  • 8. Heavy through current arising from external faults can cause one CT to saturate more than other, resulting in difference between secondary current produced by each CT’s, its essential to stabilize the protection for these condition. A biasing technique where the relay setting increased as the through current increased. The through current is calculated as the average of the scalar sum of current entering & leaving the zone of protection, this calculated through current is then used to apply a percentage bias to increase the differential setting.
  • 9.
  • 11. INTER TURN FAULT PROTECTION (50G1) In healthy 3 phase power system the addition of each phase to earth is normally zero, as it is vector addition of three balanced vectors at 120° to another. However when inter turn fault or earth fault occurs on primary system this balance upset and residual voltage produced. The neutral displacement voltage can be measured directly via the open delta PT .
  • 13. STATOR OVER LOAD(50GS) Protection reacts on current flowing on stator winding coil to protect winding from overheat. Overload can result in stator temp. rise which exceeds the thermal limits of windings. Due to relatively large heat storage capacity of electric machine, infrequent overload of short duration may not damage the machine, however sustained overload of few percentage may result in premature aging and failure of insulation.
  • 14. RELAY SETTINGS : Over-load (50GS) PHASE O/C Menu text Setting range Setting Min Max I>1 Function Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse DT I>1 Direction Non-directional, Directional Fwd, Directional Rev Non-directional I>1 Current Set 0.08 In 4.0 In 4.50A I>1 Time Delay 0 100 5s (reduce load) I>2 Function Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse IEC E inverse I>2 Direction Non-directional, Directional Fwd, Directional Rev Non-directional I>2 Current Set 0.08 In 4.0 In 4.75A I>2 Time Delay 0 100 I>2 TMS 0.025 1.2 0.45
  • 15. VOLTAGE RESTRAINED OVER CURRENT (51V) This protection reacts on voltage, negative sequence voltage and current as a back up protection to detect grounding and phase to phase short circuits. The voltage restrained over current adjust the pickup setting and characteristic curve of the overcurrent function based on the system voltage. The relay is set pickup current greater than overload, and sensitivity increase as the voltage drops. The voltage controlled overcurrent relays uses and under voltage element to the supervise the operation of overcurrent element. When voltage drops below the set value the under voltage element permits the operation of the time over current units.
  • 16. Voltage Restrained Overcurrent (51V) I>3 Status Disabled or Enabled Enabled I>3 Direction Non-directional, Directional Fwd, Directional Rev Non-directional I>3 Current Set 0.08 In 32 In 5.15A I>3 Time Delay 0 s 100 s 0.0s I>Function Link Bit 0=VTS Blocks I>1, Bit 1=VTS Blocks I>2, Bit 2=VTS Blocks I >3, Bit 3=VTS Block I>4, Bits 4~7 are not used. Bit 3=VTS Block I>4
  • 17. NEGATIVE SEQUENCE OVER CURRENT (46G) NPS protection is provided to protect generator against the unbalanced load and as a back up for uncleared unsymmetrical faults. The Negative sequence current create magnetic flux in the air gap which rotates in opposition to the rotor. This flux induce eddy current as twice the fundamental frequency in the rotor which cause overheating of rotor body, wedged and retaining rings. The rotor body gets heated instantaneously.
  • 19. 95% STATOR EARTH FAULT PROTECTION (64G1) There is a limit on the percentage of winding that can be protected by stator earth fault element. For the earth fault close to generator neutral side, the driving voltage will very low and hence fault current will be severely reduced. In practice approximately 95% of stator winding will can be protected for the fault in last 5% of winding the fault current is very low which can not be detected by this type of earth fault. Single phase earth fault with in 85%-95% range from terminal of stator winding can be protected by fundamental zero-sequence overvoltage protection.
  • 20. SCHEME ARRANGEMENT FOR 95% & 100% STATOR EARTH FAULT PROTECTION :
  • 22. 100% STATOR EARTH FAULT PROTECTION (64G2) In this protection 100% stator winding is covered in protection zone. Low probability fault occurring in 5% of the stator winding near to star point is due to mechanical damage such as creepage of conductors, loosening of boult etc. Most of the generator produce third harmonic voltage due to non linearities in magnetic circuit of generator design, under normal operating condition distribution of third harmonic voltage along the stator winding. The value increases with the load. To detect the fault in last 5% of winding the relay is provided with under & over voltage element.
  • 23. The third harmonic under voltage element is applicable when the neutral voltage measured is available at the neutral end of the generator. To prevent false tripping operation when the machine is dead or under no load condition power interlock is used to detect load.
  • 24. SCHEME ARRANGEMENT FOR 95% & 100% STATOR EARTH FAULT PROTECTION :
  • 25. RELAY SETTING : V<Inhibit Set 80V P<Inhibit set Disabled, Enabled Enabled P<Inhibit set 20.00W Q<Inhibit set Disabled, Enabled Disabled S<Inhibit set Disabled, Enabled Disabled
  • 26. POLE SLIPPING PROTECTION (78G) Sudden changes or shock in electrical system such as line switching operation, transient system fault, generator governor failure, excitation system failure, reconnection of islanding system without synchronization, large jumps in load or fault may lead to power system oscillations which appears as regular variations of current and angular separation between systems. At times, this power swing becomes so sever that it can lead lost of synchronism between generator and system, this condition recognized as out of step or pole slipping.
  • 27. OVER FLUXING PROTECTION (99G) Over fluxing or over excitation of generator can increase if the ratio of voltage to frequency (V/HZ) increased certain limits. High voltage or low frequency can rise V/Hz ratio, it will produce high flux densities in magnetic core of machines, this can cause core of generator to be saturated & stary flux to be induced in un laminated components that have not been designed to carry this flux, the resulting eddy current in solid components (e.g. core, bolts & supporting structure) can cause rapid overheating & damage. Over fluxing likely to occur during machine start up & shutdown while the generator is not connected to the system. Failure in automatic control of excitation system or errors in manual control of machine field current, could allow excessive voltage to be generated. Sudden loss of load could cause an overvoltage condition, if generator excitation system does not respond properly.
  • 28. BREAKER FAILURE PROTECTION (50LBB) The LBB protection is used as back up protection of main protection, during this protection, relay sense the breaker position, flow of current & trip command generated by itself.
  • 30. BACK UP IMPEDANCE PROTECTION (27G) Generator is source of power & it will supply fault current until they are cleared by the protection system. Back up protection applied at the generator so that faults are cleared in the event of downstream protection/breaker fails to operate. Under impedance element is set to monitor the system impedance at machine terminal, if the measured impedance falls below set value then relay will operate.
  • 31. DEAD MACHINE (61B) Accidental energization of breaker when machine is not running can cause severe damage to machine. If the breaker is closed when machine is not running then generator will began act as induction motor with the surface of rotor core & rotor winding slot wedges acting as rotor conductor ,this abnormal current will result in overheating and damaged. The relay element is enabled when the machine is not running ,there for element can have very low current setting, the undervoltage threshold typically set to 85% of nominal voltage to ensure that machine is not running.
  • 33. LOSS OF EXCITATION WITH UNDER VOLTAGE(27/40) Complete loss of excitation may arise as a result of accidental tripping of excitation system, failure of field breaker , an open circuit or short circuit happened in DC circuit, flashover of any slip ring or failure of excitation source. When excitation of synchronous generator fails its internal emf will decay and output of active power will reduce and it will draw large reactive power grid, hence machine will act as a induction generator, after filed failure circulating current will induce in rotor core and rotor heat, also stator winding may get damaged severely.
  • 35. ROTOR GROUND FAULT PROTECTION (64R) The Generator rotor earth fault protection is provided to protect the generator rotor and exciter rotor winding against earth fault. The rotor earth fault relay sense the resistance between rotor winding and ground through carbon brushes mounted on slip rings.
  • 36. MICOM P342 RELAY INCORPORATED WITH FOLLOWING PROTECTIONS : 1. Low Forward Power Protection (37G) 2. Reverse Power Protection (32G) 3. Under frequency Protection (81U) 4. Over frequency Protection (81O) 5. Over Voltage Protection (59G) 6. Under Voltage Protection (27G) 7. Generator Stator Water flow minimum 8. Excitation system failure 9. Excitation transformer temp. high
  • 37. LOW FORWARD POWER PROTECTION (37G) When machine is generating and CB connecting the generator to the system is tripped, the electrical load on the generator is cut, this could lead to generator over speed if the machine input power is not reduced quickly. Trapped system in the turbine, risk of over speed damage to such sets, interlock is used for non urgent tripping of the generator breaker and excitation system with a low forward power check.
  • 39. REVERSE POWER PROTECTION (32G) It is back up protection to low forward protection. If the generator prime mover falls, generator is connected in parallel with another source of electrical supply will begin as “Motor” . The generator will operator as a synchronous motor and drive the turbine. Here in this condition draw the real power (MW) from the bus & and export reactive power (MVAR) to grid. If the filed breaker closed but field current is zero, the generator will act as an induction motor. Here in this condition generator will draw real power as well as reactive power from the grid
  • 40. In this condition generator will not be harmed by synchronous motoring but steam turbine can be harmed due to winding loss of causing overheating of turbine blade if continued long enough. The sensitivity and setting of the relay is depending on the type of prime movers. Causes of Reverse Power Protection : Two or more machines are running in parallel and prime mover of machine fails.
  • 42. OVER VOLTAGE (59G) The over voltage protection will act as a back up protection of the over fluxing protection. The over voltage protection is required to protect the stator conductor insulation of the generator. This is directly connected to Gen. phase side PT secondary terminals. Causes of over voltage : Prime mover over speed due to sudden loss of load. Voltage regulator (AVR) is defective.
  • 44. OVER FREQUENCY PROTECTION (81O) The over frequency protection is provided to protect the generator against over speed. Sever high speed operation of generator set could result in damaged. Causes of over frequency : Demand of active power suddenly decreased in power grid Full or partial load rejection (Load thrown off) Over shedding of load during major disturbance. Generator CB oprn during load.
  • 46. UNDER FREQUENCY PROTECTION (81U) The under frequency protection is used to protect the generator against operation at low frequency. If the frequency goes down, the speed of turbine get reduced, hence the steam may get condensed on turbine blades and damage them. Causes of under frequency : Demand of active power suddenly increased in grid. Islanded system two or more system running in parallel on more than 70% load & outage of nay machine due to fault increased the load to another machine will result in under frequency operation.
  • 48. UNDER VOLTAGE (27G) Generator are usually designed to operate continuously at a minimum voltage of 95% of its rated voltage, while generate power at rated frequency. Generator terminal voltage goes lower than 85% of its rated voltage may result in undesirable effects such as reduction in stability limits, import of excessive reactive power from grid, malfunctioning of voltage sensing devices and equipment. The under voltage relay works in secondary value if PT which is connected with generator output terminals.
  • 50. NON DIRECT PROTECTION ❑Generator stator water flow minimum Generator CW flow minimum link to be closed, protection simulated from C&I cabinet ( if stator water pump not running then signal will come high) ❑Excitation system fault Protection simulated from AVR end at micom P342 relay assigned o/p becomes high & EXT trip LED becomes high. ❑Excitation transformer temp. high Protection simulated from excitation transformer end for low setting at P342 relay o/p assigned becomes high. For high setting at P342 assigned relay becomes high.