Preventing Circulating Currents in Parallel Generator
Applications
Today’s Presenter
•  Prior to joining Mirus, Tony was the
Chief Facilities Electrical Engineer
at an IBM manufacturing facility in
Toronto
•  Tony is a professional engineer
•  Tony is also a member of IEEE,
and has published multiple
research papers on power quality
© 2015 Mirus International | All Rights Reserved
Preventing Circulating Current in
Parallel Generator Applications
© 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International
Scope of Presentation
•  Generator Pitch and Harmonics
•  How paralleling dissimilarly pitched generators creates
neutral circulating current
•  Traditional methods used to prevent generator circulating
current
•  GENLINK Dissimilar Pitch Neutral Limiter (DPNL)
•  Case Studies:
–  Martin Brower Distribution Facility
•  750kW and 1000kW Generators
–  Arkansas University
•  2 x 800kW Generators with 1500kVA Utility Transformer
–  City of Waterloo Power Plant Expansion
•  New 7200kW 13.8kV Turbine Generator
•  Summary
© 2015 Mirus International | All Rights Reserved
Generator Pitch and Harmonics
Coil Pitch:
The angular distance between
the two sides of an individual
coil of an AC armature winding
Pole Pitch:
The angular distance between
centers of adjacent field poles
Winding Pitch:
The ratio of Coil Pitch to Pole
Pitch
Full Pitch Winding:
When Coil Pitch is exactly
equal to Pole Pitch Full Pitch Generator
Coil Pitch = 90°, Pole Pitch = 90°
Generator	
  Pitch	
  &	
  
Harmonics	
  
Circula4ng	
  Currents	
  
problems	
  
Preven4ng	
  Generator	
  
Circula4ng	
  Current	
  
GENLINK	
  DPNL	
   Case	
  Studies	
  
© 2015 Mirus International | All Rights Reserved
Generator Pitch and Harmonics
Fractional Pitch Winding:
When Coil Pitch is less
than Pole Pitch
Advantages of Fractional
Pitch Generators:
–  Shorter end
connections to reduce
copper
–  More sinusoidal
waveform and
therefore, less
harmonics
2/3 Pitch Generator
Coil Pitch = 60°, Pole Pitch = 90°
© 2015 Mirus International | All Rights Reserved
Generator Pitch and Harmonics
•  Voltage waveform produced by a generator will vary
slightly with respect to winding pitch
•  Harmonic content in voltage will also vary based on
winding pitch
–  Pitch factors below are used to predict harmonic
voltages based on respective harmonic fluxes
Reference: ‘Generator Winding Pitch and Harmonics, Engine Data Sheet EDS 70.4,
Caterpillar, March 1993 ’
Pitch Fund. 3rd
5th
7th
9th
2/3 0.866 0.0 0.866 0.866 0.866
4/5 0.951 0.588 0.0 0.588 0.951
5/6 0.966 0.707 0.259 0.259 0.966
6/7 0.975 0.782 0.434 0.0 0.782
© 2015 Mirus International | All Rights Reserved
Generator Pitch and Zero Sequence
Impedance
•  Generator impedances vary with respect to winding
pitch, especially zero sequence impedance
•  Generator zero sequence impedance directly impacts
the amount of circulating neutral current
•  Many claim that a 2/3rd pitch generator is better for 3rd
harmonic, but this is not entirely true
–  it has very low zero sequence impedance which
results in less 3rd harmonic voltage distortion under
non-linear loading, but
–  the low zero sequence impedance presents little
resistance to the flow of circulating currents
© 2015 Mirus International | All Rights Reserved
How Paralleling Dissimilarly Pitched Generators creates
Neutral Circulating Current
•  Generators with different pitch configurations will have slightly
different voltage waveshapes
•  Differences in Phase-Neutral (Ph-N) instantaneous voltages will
appear as triple frequency
•  Can also apply when paralleling alternate energy sources with
the Utility
5/6P Gen1
2/3P Gen2
Generator	
  Pitch	
  &	
  
Harmonics	
  
Circula4ng	
  Currents	
  
problems	
  
Preven4ng	
  Generator	
  
Circula4ng	
  Current	
  
GENLINK	
  DPNL	
   Case	
  Studies	
  
© 2015 Mirus International | All Rights Reserved
How Paralleling Dissimilarly Pitched Generators
creates Neutral Circulating Current (cont.)
•  Difference in instantaneous voltages drives neutral
circulating current
•  Flow is restricted only by zero sequence impedance of
generators and cables which is usually quite low
© 2015 Mirus International | All Rights Reserved
Traditional Methods for limiting
Circulating Currents
•  Ensure that generators are of similar pitch
–  This is not always possible or even preferred when
expanding a site with older, existing generators
–  Can be difficult when sourcing from different suppliers or a
supplier that has changed their pitch design
–  Even identically pitched generators can have slightly
different voltage waveshapes
Generator	
  Pitch	
  &	
  
Harmonics	
  
Circula4ng	
  Currents	
  
problems	
  
Preven4ng	
  Generator	
  
Circula4ng	
  Current	
  
GENLINK	
  DPNL	
   Case	
  Studies	
  
© 2015 Mirus International | All Rights Reserved
Traditional Methods for limiting
Circulating Currents (cont.)
•  Add impedance in the common neutral
–  Neutral Grounding Resistors or Neutral Reactors can be
used but the impedance required to limit circulating current
might reduce 1-ph faults to unacceptable levels
(ie. such that breakers do not trip)
–  These devices must be rated for the residual steady state
circulating current
–  If NGR’s are required for fault limiting, this can be an
effective method but the requirement to handle steady state
current will increase size and cost
© 2015 Mirus International | All Rights Reserved
Traditional Methods for limiting
Circulating Currents (cont.)
•  An ungrounded system can be used where neutrals
are not connected together or grounded
–  Ground fault monitoring is required and no neutral return
path is available for 1-ph loads
–  Sometimes zigzag reactors are used to provide a ground
reference
•  Internal generator faults may be a problem
© 2015 Mirus International | All Rights Reserved
GENLINK Dissimilar Pitch Neutral Limiter
•  Multiple winding reactor installed in the common
neutral of paralleled generators or generators
paralleled with Utility
•  Inserts ~ 48% impedance in
neutral current circulating path
at triple frequency
–  Reduces neutral circulating
current by 70% or more
•  Minimal effect on fault level
–  Adds < 1% saturated
impedance to 1-Ph fault level
–  No impedance to 3-Ph
fault level
•  Designed to meet IEEE Std 32
Requirements for Neutral Grounding Devices
Generator	
  Pitch	
  &	
  
Harmonics	
  
Circula4ng	
  Currents	
  
problems	
  
Preven4ng	
  Generator	
  
Circula4ng	
  Current	
  
GENLINK	
  DPNL	
   Case	
  Studies	
  
© 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International
•  Paralleled generators with dissimilar pitches in stand-
alone or emergency stand-bye operation
•  Generator or other Alternative Energy source that is
paralleled with a Utility transformer that can have its
neutral-ground bond routed through the DPNL
–  Cascaded DPNL’s can be used where there are more
than two connected supplies
•  Examples are alternative
energy generators, standby
generators, islanded supplies
for drilling rigs, production
platforms, pumping stations,
etc.
Applications for GenLink DPNL
© 2015 Mirus International | All Rights Reserved
Application of GENLINK DPNL in 4-Wire
System
•  DPNL is used when 2 or more generators of dissimilar pitch
are paralleled together or a generator is paralleled with an
alternate source, such as the Utility
•  DPNL is inserted in the neutral between the dissimilar groups
•  Neutral should be grounded in only 1 location
–  Preferred location is neutral bus in switchboard
© 2015 Mirus International | All Rights Reserved
Application of GenLink DPNL on 4-Wire
System with Utility Transformer
•  Utility transformer neutral should be grounded through
DPNL
•  Ground at only 1 location
© 2015 Mirus International | All Rights Reserved
Cascaded System for Multiple Generators
•  DPNL’s can be cascaded in applications where there are
more than 2 types of dissimilar pitch generators or dissimilarly
pitched generators are paralleled with Utility
•  Size each DPNL based on the total generator load connected
to it
© 2015 Mirus International | All Rights Reserved
DPNL Fault Current Path
•  Fault current passes through the shoulder of the DPNL
(Z-X or Y-X)
–  Shoulder impedance is typically 4% – 5%
•  During a fault, reactor steel saturates, significantly
reducing the impedance
Fault current path
© 2015 Mirus International | All Rights Reserved
GENLINK Effect on 1-Ph Fault Level
3000A DPNL
•  1-ph impedance
–  Normal Operation ~ 5%
–  Above 8000A (saturated condition) < 1%
© 2015 Mirus International | All Rights Reserved
GENLINK Dissimilar Pitch Neutral Limiter
•  Circulating current inductance (Y-Z) is almost 4x the
shoulder inductance
•  Since the frequency of the circulating current is 3x the
fundamental current (180 Hz vs 60 Hz), circulating current
impedance is 3x greater
•  Net impedance to circulating current is around 48%
© 2015 Mirus International | All Rights Reserved
Application of GENLINK DPNL in 3-Wire
System
•  In a 3-Wire application where there is no return neutral
current from 1-Ph loads, a smaller size DPNL can be used
•  Terminal X may or may not be grounded
–  If ungrounded, Ground Fault monitoring will be required
© 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International
•  Paralleled generators with dissimilar pitches that are tied to a
Utility grid supplied by a transformer or multiple transformers
that cannot have neutral grounded through DPNL
–  DPNL prevents circulating current between the generators
–  NGI helps block circulating current between the generators and
the Utility transformers
–  NGI is not necessary if Neutral-Ground bond on Utility
transformers can be routed through DPNL
•  Examples are Generating Stations with Alternative Energy
sources, Co-generation sites, Peak Shaving generators, etc.
•  Also NGI alone can be
useful in applications
with Alternative Energy
sources and Utility when
neutral is inaccessible
Applications for GenLink DPNL + NGI
© 2015 Mirus International | All Rights Reserved
How to Size GENLINK for a Specific
Application
•  Determine total capacity in
kW or kVA of all generators
connected in parallel
•  Select DPNL that corresponds
to this value in the appropriate
system voltage
column
© 2015 Mirus International | All Rights Reserved
How to Size GENLINK (cont.)
•  This will size the DPNL for a return neutral current that
will be at least 50% of full phase current rating
–  85% for 208V-240V or 380V-440V systems
•  It is the Users responsibility to ensure that actual return
neutral current will not exceed DPNL rating
–  If return neutral current is expected to exceed DPNL
rating then a larger DPNL should be selected
–  A larger DPNL will be slightly less effective in reducing
circulating current
•  For 3-Wire applications or where return neutral current is
known to be very low, smaller DPNLs can be selected
© 2015 Mirus International | All Rights Reserved
Total neutral current = 160A
Case Study: Martin Brower Distribution Facility
Two Dissimilarly Pitched Generators
Generator	
  Pitch	
  &	
  
Harmonics	
  
Circula4ng	
  Currents	
  
problems	
  
Preven4ng	
  Generator	
  
Circula4ng	
  Current	
  
GENLINK	
  DPNL	
   Case	
  Studies	
  
© 2015 Mirus International | All Rights Reserved
Case Study: Martin Brower Distribution Facility
Neutral Grounded at one location only
© 2015 Mirus International | All Rights Reserved
Case Study: Martin Brower Distribution Facility
•  1-Ph load return neutral current = 38.4A
•  Most of the current from generators to DPNL is return
neutral current from 1- ph loads
•  Almost all generator circulating current was eliminated
© 2015 Mirus International | All Rights Reserved
Case Study: Boca Hospital, S. Florida
•  Generator configuration
–  2 x 1375kVA
0.8667 Pitch
–  1 x 1200kVA .
0667 Pitch
•  Calculation of expected
circulating neutral
current provided by
Caterpillar Distributor
•  Circulating 3rd harmonic
current
–  Ga and Gb ~ 97A
–  Gc ~ 194A
© 2015 Mirus International | All Rights Reserved
Case Study: Boca Hospital, S. Florida
“Reading went from 400 amp
to zero on all three generators
and system has functioned
with no problems since then.”
Hassan Entezari,
Pantropic Power Inc.
2500A GenLink DPNL
© 2015 Mirus International | All Rights Reserved
Case Study: 13.8kV System, Waterloo Illinois
- Differently pitched Generators and Multiple Utility Trans.
•  New Generator different
pitch than existing
–  Existing 6600kW (.722P)
–  New 7200kW (.814P)
•  No access to Utility
transformer neutrals but
Mirus was not initially
informed of this
© 2015 Mirus International | All Rights Reserved
Case Study: 13.8kV System, Waterloo Illinois
•  Virtually no neutral circulating current between Generators
•  Residual current to Utility transformers still too high however
© 2015 Mirus International | All Rights Reserved
Case Study: 13.8kV System, Waterloo Illinois
•  Required continuously rated Neutral Grounding Resistor
(NGR) or additional Neutral Grounding Inductor (NGI)
between DPNL and ground
•  NGR recommended for this application:
–  60A continuous duty, Z = 19 Ohms
–  36”W x 36”D x 66”H
–  Residual circulating current estimated to be < 50A
•  NGI recommended for this application:
–  100A continuous duty, Z = 6.6 Ohms at 60Hz
–  44”W x 38”D x 66”H
–  Residual circulating current estimated to be < 25A
•  Advantages of NGI over NGR
–  More effective in reducing circulating current
–  Less effect on fault level
–  Much lower losses
•  NGR power dissipation is entirely kW
–  Lower cost
© 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International
Summary
•  Paralleling of different power sources can cause neutral
circulating current
–  Dissimilarly pitched generators
–  Generator or other alternative energy source with Utility supply
–  Different alternative energy sources
•  Neutral circulating current is predominantly triple frequency
•  Application of GenLink DPNL can reduce triple frequency
circulating current by 70% or more without significantly
affecting fault levels
•  Neutral should be grounded at only one location
–  Recommended grounding at Switchboard
•  If Utility transformer neutrals are not accessible, Neutral
Grounding Inductor will also be needed
© 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International
Questions

Weitere ähnliche Inhalte

Was ist angesagt?

Substation design guideliness
Substation design guidelinessSubstation design guideliness
Substation design guideliness
michaeljmack
 
Commissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptCommissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.ppt
AlemayehuAsmare
 
Power system protection
Power system protectionPower system protection
Power system protection
Anu Priya
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
michaeljmack
 

Was ist angesagt? (20)

Advance Electrical system Design and solar power plant design courses
Advance Electrical system Design and solar power plant design courses Advance Electrical system Design and solar power plant design courses
Advance Electrical system Design and solar power plant design courses
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substation
 
Three phase half wave controlled converter
Three phase half wave controlled converterThree phase half wave controlled converter
Three phase half wave controlled converter
 
Excitation system for alternator
Excitation system for alternatorExcitation system for alternator
Excitation system for alternator
 
Substation and It's Equipment
Substation and It's Equipment Substation and It's Equipment
Substation and It's Equipment
 
Substation design guideliness
Substation design guidelinessSubstation design guideliness
Substation design guideliness
 
Distribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss Calculation
 
Commissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptCommissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.ppt
 
5. Switchyard & Substation
5. Switchyard & Substation5. Switchyard & Substation
5. Switchyard & Substation
 
Generator grounding
Generator groundingGenerator grounding
Generator grounding
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
Load Characteristics
Load CharacteristicsLoad Characteristics
Load Characteristics
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substations
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Base Load Plants and Peak Load Plant
Base Load Plants and Peak Load PlantBase Load Plants and Peak Load Plant
Base Load Plants and Peak Load Plant
 
Transformer testing on sight and off sight
Transformer testing on sight and off sightTransformer testing on sight and off sight
Transformer testing on sight and off sight
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
 

Andere mochten auch

Alternating Current Machines 3
Alternating Current Machines 3Alternating Current Machines 3
Alternating Current Machines 3
Talia Carbis
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
-
 
Earthing Arrangements
Earthing  ArrangementsEarthing  Arrangements
Earthing Arrangements
Paul Holden
 
Autism Spectrum Disorder
Autism Spectrum DisorderAutism Spectrum Disorder
Autism Spectrum Disorder
Amanda Lozano
 
懶人版慕立達
懶人版慕立達懶人版慕立達
懶人版慕立達
千蘊 沈
 
Karmacharya_MS_Thesis_Florida
Karmacharya_MS_Thesis_FloridaKarmacharya_MS_Thesis_Florida
Karmacharya_MS_Thesis_Florida
Binab Karmacharya
 
Sustainable Theatre Report-Laura
Sustainable Theatre Report-LauraSustainable Theatre Report-Laura
Sustainable Theatre Report-Laura
Laura Shultz
 

Andere mochten auch (20)

1.7.4 Example 2
1.7.4 Example 21.7.4 Example 2
1.7.4 Example 2
 
Presentation1
Presentation1Presentation1
Presentation1
 
A Single Phase Induction Generator As Wind Generator – A New Concept and Design
A Single Phase Induction Generator As Wind Generator – A New Concept and DesignA Single Phase Induction Generator As Wind Generator – A New Concept and Design
A Single Phase Induction Generator As Wind Generator – A New Concept and Design
 
Alternating Current Machines 3
Alternating Current Machines 3Alternating Current Machines 3
Alternating Current Machines 3
 
3-Phase AC Motor Model(PSpice Model)
3-Phase AC Motor Model(PSpice Model)3-Phase AC Motor Model(PSpice Model)
3-Phase AC Motor Model(PSpice Model)
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
 
Decentralized Generation In Microgrids
Decentralized Generation In MicrogridsDecentralized Generation In Microgrids
Decentralized Generation In Microgrids
 
Earthing Arrangements
Earthing  ArrangementsEarthing  Arrangements
Earthing Arrangements
 
Autism Spectrum Disorder
Autism Spectrum DisorderAutism Spectrum Disorder
Autism Spectrum Disorder
 
懶人版慕立達
懶人版慕立達懶人版慕立達
懶人版慕立達
 
Blow dry bar gold coast
Blow dry bar gold coastBlow dry bar gold coast
Blow dry bar gold coast
 
Karmacharya_MS_Thesis_Florida
Karmacharya_MS_Thesis_FloridaKarmacharya_MS_Thesis_Florida
Karmacharya_MS_Thesis_Florida
 
Figuras
FigurasFiguras
Figuras
 
Sustainable Theatre Report-Laura
Sustainable Theatre Report-LauraSustainable Theatre Report-Laura
Sustainable Theatre Report-Laura
 
Games quiz
Games quizGames quiz
Games quiz
 
Dynamic DSM Features - Financials
Dynamic DSM Features - FinancialsDynamic DSM Features - Financials
Dynamic DSM Features - Financials
 
RAE
RAERAE
RAE
 
7. ret hans
7. ret hans7. ret hans
7. ret hans
 
Marketing clerk performance appraisal
Marketing clerk performance appraisalMarketing clerk performance appraisal
Marketing clerk performance appraisal
 
RENUGOPAL BABU
RENUGOPAL BABURENUGOPAL BABU
RENUGOPAL BABU
 

Ähnlich wie Preventing circulating current in parallel generator applications

Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)
Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)
Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)
George Sey Jr., PE
 
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Living Online
 
improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...
vinay kumar mali
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 

Ähnlich wie Preventing circulating current in parallel generator applications (20)

GENERATOR PROTECTIONS
GENERATOR PROTECTIONS GENERATOR PROTECTIONS
GENERATOR PROTECTIONS
 
SPARC_Course_IIT_D_DH_WTG_Modeling_March_2021_VV.pptx
SPARC_Course_IIT_D_DH_WTG_Modeling_March_2021_VV.pptxSPARC_Course_IIT_D_DH_WTG_Modeling_March_2021_VV.pptx
SPARC_Course_IIT_D_DH_WTG_Modeling_March_2021_VV.pptx
 
Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)
Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)
Microsoft PowerPoint - Impacts of Distributed Generation (Public Copy)
 
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
 
IRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdfIRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdf
 
Transformers stdm
Transformers stdmTransformers stdm
Transformers stdm
 
Nidec asi electric power solutions for pipeline applications
Nidec asi electric power solutions for pipeline applicationsNidec asi electric power solutions for pipeline applications
Nidec asi electric power solutions for pipeline applications
 
High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Pune
 
Wsu genprotoverview 180305
Wsu genprotoverview 180305Wsu genprotoverview 180305
Wsu genprotoverview 180305
 
The inverter core consists of 3 components
The inverter core consists of 3 componentsThe inverter core consists of 3 components
The inverter core consists of 3 components
 
improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...improved reactive power capability of grid connected doubly fed induction gen...
improved reactive power capability of grid connected doubly fed induction gen...
 
Power
PowerPower
Power
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Electrical Machines
Electrical Machines Electrical Machines
Electrical Machines
 
UNIT2-PQ-PPT.ppt
UNIT2-PQ-PPT.pptUNIT2-PQ-PPT.ppt
UNIT2-PQ-PPT.ppt
 
Generation overview
Generation overviewGeneration overview
Generation overview
 
Inverter
InverterInverter
Inverter
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic concepts
 
63-pq.ppt
63-pq.ppt63-pq.ppt
63-pq.ppt
 
63-pq.ppt
63-pq.ppt63-pq.ppt
63-pq.ppt
 

Kürzlich hochgeladen

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 

Kürzlich hochgeladen (20)

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 

Preventing circulating current in parallel generator applications

  • 1. © 2015 Mirus International | All Rights Reserved Harmonic and Energy Saving Solutions Power Quality You Can Trust | Real World Experience | A History of Innovation
  • 2. © 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International Preventing Circulating Currents in Parallel Generator Applications Today’s Presenter •  Prior to joining Mirus, Tony was the Chief Facilities Electrical Engineer at an IBM manufacturing facility in Toronto •  Tony is a professional engineer •  Tony is also a member of IEEE, and has published multiple research papers on power quality
  • 3. © 2015 Mirus International | All Rights Reserved Preventing Circulating Current in Parallel Generator Applications
  • 4. © 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International Scope of Presentation •  Generator Pitch and Harmonics •  How paralleling dissimilarly pitched generators creates neutral circulating current •  Traditional methods used to prevent generator circulating current •  GENLINK Dissimilar Pitch Neutral Limiter (DPNL) •  Case Studies: –  Martin Brower Distribution Facility •  750kW and 1000kW Generators –  Arkansas University •  2 x 800kW Generators with 1500kVA Utility Transformer –  City of Waterloo Power Plant Expansion •  New 7200kW 13.8kV Turbine Generator •  Summary
  • 5. © 2015 Mirus International | All Rights Reserved Generator Pitch and Harmonics Coil Pitch: The angular distance between the two sides of an individual coil of an AC armature winding Pole Pitch: The angular distance between centers of adjacent field poles Winding Pitch: The ratio of Coil Pitch to Pole Pitch Full Pitch Winding: When Coil Pitch is exactly equal to Pole Pitch Full Pitch Generator Coil Pitch = 90°, Pole Pitch = 90° Generator  Pitch  &   Harmonics   Circula4ng  Currents   problems   Preven4ng  Generator   Circula4ng  Current   GENLINK  DPNL   Case  Studies  
  • 6. © 2015 Mirus International | All Rights Reserved Generator Pitch and Harmonics Fractional Pitch Winding: When Coil Pitch is less than Pole Pitch Advantages of Fractional Pitch Generators: –  Shorter end connections to reduce copper –  More sinusoidal waveform and therefore, less harmonics 2/3 Pitch Generator Coil Pitch = 60°, Pole Pitch = 90°
  • 7. © 2015 Mirus International | All Rights Reserved Generator Pitch and Harmonics •  Voltage waveform produced by a generator will vary slightly with respect to winding pitch •  Harmonic content in voltage will also vary based on winding pitch –  Pitch factors below are used to predict harmonic voltages based on respective harmonic fluxes Reference: ‘Generator Winding Pitch and Harmonics, Engine Data Sheet EDS 70.4, Caterpillar, March 1993 ’ Pitch Fund. 3rd 5th 7th 9th 2/3 0.866 0.0 0.866 0.866 0.866 4/5 0.951 0.588 0.0 0.588 0.951 5/6 0.966 0.707 0.259 0.259 0.966 6/7 0.975 0.782 0.434 0.0 0.782
  • 8. © 2015 Mirus International | All Rights Reserved Generator Pitch and Zero Sequence Impedance •  Generator impedances vary with respect to winding pitch, especially zero sequence impedance •  Generator zero sequence impedance directly impacts the amount of circulating neutral current •  Many claim that a 2/3rd pitch generator is better for 3rd harmonic, but this is not entirely true –  it has very low zero sequence impedance which results in less 3rd harmonic voltage distortion under non-linear loading, but –  the low zero sequence impedance presents little resistance to the flow of circulating currents
  • 9. © 2015 Mirus International | All Rights Reserved How Paralleling Dissimilarly Pitched Generators creates Neutral Circulating Current •  Generators with different pitch configurations will have slightly different voltage waveshapes •  Differences in Phase-Neutral (Ph-N) instantaneous voltages will appear as triple frequency •  Can also apply when paralleling alternate energy sources with the Utility 5/6P Gen1 2/3P Gen2 Generator  Pitch  &   Harmonics   Circula4ng  Currents   problems   Preven4ng  Generator   Circula4ng  Current   GENLINK  DPNL   Case  Studies  
  • 10. © 2015 Mirus International | All Rights Reserved How Paralleling Dissimilarly Pitched Generators creates Neutral Circulating Current (cont.) •  Difference in instantaneous voltages drives neutral circulating current •  Flow is restricted only by zero sequence impedance of generators and cables which is usually quite low
  • 11. © 2015 Mirus International | All Rights Reserved Traditional Methods for limiting Circulating Currents •  Ensure that generators are of similar pitch –  This is not always possible or even preferred when expanding a site with older, existing generators –  Can be difficult when sourcing from different suppliers or a supplier that has changed their pitch design –  Even identically pitched generators can have slightly different voltage waveshapes Generator  Pitch  &   Harmonics   Circula4ng  Currents   problems   Preven4ng  Generator   Circula4ng  Current   GENLINK  DPNL   Case  Studies  
  • 12. © 2015 Mirus International | All Rights Reserved Traditional Methods for limiting Circulating Currents (cont.) •  Add impedance in the common neutral –  Neutral Grounding Resistors or Neutral Reactors can be used but the impedance required to limit circulating current might reduce 1-ph faults to unacceptable levels (ie. such that breakers do not trip) –  These devices must be rated for the residual steady state circulating current –  If NGR’s are required for fault limiting, this can be an effective method but the requirement to handle steady state current will increase size and cost
  • 13. © 2015 Mirus International | All Rights Reserved Traditional Methods for limiting Circulating Currents (cont.) •  An ungrounded system can be used where neutrals are not connected together or grounded –  Ground fault monitoring is required and no neutral return path is available for 1-ph loads –  Sometimes zigzag reactors are used to provide a ground reference •  Internal generator faults may be a problem
  • 14. © 2015 Mirus International | All Rights Reserved GENLINK Dissimilar Pitch Neutral Limiter •  Multiple winding reactor installed in the common neutral of paralleled generators or generators paralleled with Utility •  Inserts ~ 48% impedance in neutral current circulating path at triple frequency –  Reduces neutral circulating current by 70% or more •  Minimal effect on fault level –  Adds < 1% saturated impedance to 1-Ph fault level –  No impedance to 3-Ph fault level •  Designed to meet IEEE Std 32 Requirements for Neutral Grounding Devices Generator  Pitch  &   Harmonics   Circula4ng  Currents   problems   Preven4ng  Generator   Circula4ng  Current   GENLINK  DPNL   Case  Studies  
  • 15. © 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International •  Paralleled generators with dissimilar pitches in stand- alone or emergency stand-bye operation •  Generator or other Alternative Energy source that is paralleled with a Utility transformer that can have its neutral-ground bond routed through the DPNL –  Cascaded DPNL’s can be used where there are more than two connected supplies •  Examples are alternative energy generators, standby generators, islanded supplies for drilling rigs, production platforms, pumping stations, etc. Applications for GenLink DPNL
  • 16. © 2015 Mirus International | All Rights Reserved Application of GENLINK DPNL in 4-Wire System •  DPNL is used when 2 or more generators of dissimilar pitch are paralleled together or a generator is paralleled with an alternate source, such as the Utility •  DPNL is inserted in the neutral between the dissimilar groups •  Neutral should be grounded in only 1 location –  Preferred location is neutral bus in switchboard
  • 17. © 2015 Mirus International | All Rights Reserved Application of GenLink DPNL on 4-Wire System with Utility Transformer •  Utility transformer neutral should be grounded through DPNL •  Ground at only 1 location
  • 18. © 2015 Mirus International | All Rights Reserved Cascaded System for Multiple Generators •  DPNL’s can be cascaded in applications where there are more than 2 types of dissimilar pitch generators or dissimilarly pitched generators are paralleled with Utility •  Size each DPNL based on the total generator load connected to it
  • 19. © 2015 Mirus International | All Rights Reserved DPNL Fault Current Path •  Fault current passes through the shoulder of the DPNL (Z-X or Y-X) –  Shoulder impedance is typically 4% – 5% •  During a fault, reactor steel saturates, significantly reducing the impedance Fault current path
  • 20. © 2015 Mirus International | All Rights Reserved GENLINK Effect on 1-Ph Fault Level 3000A DPNL •  1-ph impedance –  Normal Operation ~ 5% –  Above 8000A (saturated condition) < 1%
  • 21. © 2015 Mirus International | All Rights Reserved GENLINK Dissimilar Pitch Neutral Limiter •  Circulating current inductance (Y-Z) is almost 4x the shoulder inductance •  Since the frequency of the circulating current is 3x the fundamental current (180 Hz vs 60 Hz), circulating current impedance is 3x greater •  Net impedance to circulating current is around 48%
  • 22. © 2015 Mirus International | All Rights Reserved Application of GENLINK DPNL in 3-Wire System •  In a 3-Wire application where there is no return neutral current from 1-Ph loads, a smaller size DPNL can be used •  Terminal X may or may not be grounded –  If ungrounded, Ground Fault monitoring will be required
  • 23. © 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International •  Paralleled generators with dissimilar pitches that are tied to a Utility grid supplied by a transformer or multiple transformers that cannot have neutral grounded through DPNL –  DPNL prevents circulating current between the generators –  NGI helps block circulating current between the generators and the Utility transformers –  NGI is not necessary if Neutral-Ground bond on Utility transformers can be routed through DPNL •  Examples are Generating Stations with Alternative Energy sources, Co-generation sites, Peak Shaving generators, etc. •  Also NGI alone can be useful in applications with Alternative Energy sources and Utility when neutral is inaccessible Applications for GenLink DPNL + NGI
  • 24. © 2015 Mirus International | All Rights Reserved How to Size GENLINK for a Specific Application •  Determine total capacity in kW or kVA of all generators connected in parallel •  Select DPNL that corresponds to this value in the appropriate system voltage column
  • 25. © 2015 Mirus International | All Rights Reserved How to Size GENLINK (cont.) •  This will size the DPNL for a return neutral current that will be at least 50% of full phase current rating –  85% for 208V-240V or 380V-440V systems •  It is the Users responsibility to ensure that actual return neutral current will not exceed DPNL rating –  If return neutral current is expected to exceed DPNL rating then a larger DPNL should be selected –  A larger DPNL will be slightly less effective in reducing circulating current •  For 3-Wire applications or where return neutral current is known to be very low, smaller DPNLs can be selected
  • 26. © 2015 Mirus International | All Rights Reserved Total neutral current = 160A Case Study: Martin Brower Distribution Facility Two Dissimilarly Pitched Generators Generator  Pitch  &   Harmonics   Circula4ng  Currents   problems   Preven4ng  Generator   Circula4ng  Current   GENLINK  DPNL   Case  Studies  
  • 27. © 2015 Mirus International | All Rights Reserved Case Study: Martin Brower Distribution Facility Neutral Grounded at one location only
  • 28. © 2015 Mirus International | All Rights Reserved Case Study: Martin Brower Distribution Facility •  1-Ph load return neutral current = 38.4A •  Most of the current from generators to DPNL is return neutral current from 1- ph loads •  Almost all generator circulating current was eliminated
  • 29. © 2015 Mirus International | All Rights Reserved Case Study: Boca Hospital, S. Florida •  Generator configuration –  2 x 1375kVA 0.8667 Pitch –  1 x 1200kVA . 0667 Pitch •  Calculation of expected circulating neutral current provided by Caterpillar Distributor •  Circulating 3rd harmonic current –  Ga and Gb ~ 97A –  Gc ~ 194A
  • 30. © 2015 Mirus International | All Rights Reserved Case Study: Boca Hospital, S. Florida “Reading went from 400 amp to zero on all three generators and system has functioned with no problems since then.” Hassan Entezari, Pantropic Power Inc. 2500A GenLink DPNL
  • 31. © 2015 Mirus International | All Rights Reserved Case Study: 13.8kV System, Waterloo Illinois - Differently pitched Generators and Multiple Utility Trans. •  New Generator different pitch than existing –  Existing 6600kW (.722P) –  New 7200kW (.814P) •  No access to Utility transformer neutrals but Mirus was not initially informed of this
  • 32. © 2015 Mirus International | All Rights Reserved Case Study: 13.8kV System, Waterloo Illinois •  Virtually no neutral circulating current between Generators •  Residual current to Utility transformers still too high however
  • 33. © 2015 Mirus International | All Rights Reserved Case Study: 13.8kV System, Waterloo Illinois •  Required continuously rated Neutral Grounding Resistor (NGR) or additional Neutral Grounding Inductor (NGI) between DPNL and ground •  NGR recommended for this application: –  60A continuous duty, Z = 19 Ohms –  36”W x 36”D x 66”H –  Residual circulating current estimated to be < 50A •  NGI recommended for this application: –  100A continuous duty, Z = 6.6 Ohms at 60Hz –  44”W x 38”D x 66”H –  Residual circulating current estimated to be < 25A •  Advantages of NGI over NGR –  More effective in reducing circulating current –  Less effect on fault level –  Much lower losses •  NGR power dissipation is entirely kW –  Lower cost
  • 34. © 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International Summary •  Paralleling of different power sources can cause neutral circulating current –  Dissimilarly pitched generators –  Generator or other alternative energy source with Utility supply –  Different alternative energy sources •  Neutral circulating current is predominantly triple frequency •  Application of GenLink DPNL can reduce triple frequency circulating current by 70% or more without significantly affecting fault levels •  Neutral should be grounded at only one location –  Recommended grounding at Switchboard •  If Utility transformer neutrals are not accessible, Neutral Grounding Inductor will also be needed
  • 35. © 2015 Mirus International | All Rights ReservedPrivate and Confidential | Mirus International Questions