Overcurrent Protection
Presented by
Mohammad Zishan
3/14/2019 1
Introduction : Overcurrent its cause
and effects
Overcurrent :
• In an electrical power system overcurrent or excess current is a
situation where a larger than intended electric current exists
through a conductor, leading to excessive generation of heat, and
the risk of fire or damage to equipment.
Cause :
• Short Circuit
• Excessive Loading
• Incorrect Design
• Ground fault
Effects
• Equipment overloading and Equipment damage
2
Overcurrent Relay
Overcurrent Relay :
• A protective relay which operates when the load current exceeds
a preset value, is called an Overcurrent relay.
• The value of the preset current above which relay operate is
know as pickup value.
• Overcurrent relay offer a cheapest and simplest form of
protection.
• These relays are used for the protection of distribution lines,
large motor , Power equipments and industrial system.
3
Working Principle
• In an over current relay , there would be essentially a current coil.
When normal current flows through this coil, the magnetic effect
generated by the coil is not sufficient to move the moving element of
the relay, as in this condition the restraining force is grater than
deflecting force.
• When the current through the coil increased, the magnetic effect
increases and after certain level of current the deflecting force
generated by the magnetic effect of the coil, crosses the restraining
force, as a result the moving element starts moving to change the
contact position in the relay.
4
Overcurrent Protection
• Overcurrent Relay are fed from
Current transformer.
• Whenever the current through the
relay exceeds the preset value the
relay operate and actuates the trip coil
of the circuit breaker and isolate the
faulty network .
5
Types of Overcurrent relay
Depending upon the operating time of the overcurrent relay
• Instantaneous Overcurrent Relay
• Definite time Overcurrent Relay
• Inverse time Overcurrent Relay
6
Instantaneous Overcurrent Relay
• Instantaneous over current relay
operate as soon as the current in the
coil gets higher than the per set
value(Ip).
• There is no internal time delay set.
• There is always an inherent time delay
in order of a few millisecond (ms). (A)Current
Time
(sec)
No Trip
Trip
Ip
7
Definite Time Over Current Relay
• Definite time over current relay is
created by applying intentional time delay
after crossing pick up value of the
current.
• A definite time over current relay can be
adjusted to issue a trip time after its picks
up.Thus , it has a time setting adjustment
and pick up adjustment.
I(A)
Time
Sec
t1
t
8
Ip
Inverse Time Over Current Relay
• Inverse Time is a natural character of
any inductive type rotating device. This
means that , the time of relay operation
inversely varies with input current .
• This characteristic of electromechanical
induction disc relay is very suitable for
over current protection.
• In this relay if the fault is more severe,
it would be cleared more faster.
Time
Sec
I(A)
Inverse Time
9
Classification of Inverse Time Relay
Inverse time over current Relay
(IDMT) again classified in
• Standard or Normal inverse over
current relay
• Very Inverse time over current
relay
• Extremely Inverse time over
current relay
10
Standard IDMT Relay
The current/time tripping
characteristics of IDMT relays
may need to be varied according
to the tripping time required and
the characteristics of other
protective device used in
network. For this purpose, IEC
60255 defines the number of
standard characteristics as
follows :
• Standard Inverse (SI)
• Very Inverse (VI)
• Extremely Inverse (EI)
• Definite Time (DT) 11
Application of Overcurrent Relay
Overcurrent relay are used for protection of electrical equipments
such as :
• Transformer
• Generator
• HT & LT breaker Failure Protection
• Motors
• HT Lines
• EHT Lines (Directional Overcurrent & E/F relay )
• Capacitor Bank
• Natural Displacement relay in capacitor banks
12
Thank You
3/14/2019 13

Weitere ähnliche Inhalte

Was ist angesagt?

Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
Ayyarao T S L V
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
 
Introduction to power system protection
Introduction to power system protectionIntroduction to power system protection
Introduction to power system protection
SaifUrrehman183
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
moiz89
 

Was ist angesagt? (20)

Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
 
Protective relay
Protective relay Protective relay
Protective relay
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
Introduction to power system protection
Introduction to power system protectionIntroduction to power system protection
Introduction to power system protection
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Thyristor turn on methods
Thyristor turn on methodsThyristor turn on methods
Thyristor turn on methods
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Power Quality
Power QualityPower Quality
Power Quality
 
Power Quality Measurement Devices & Monotoring
Power Quality Measurement Devices & MonotoringPower Quality Measurement Devices & Monotoring
Power Quality Measurement Devices & Monotoring
 
Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...
 
surge diverters
surge diverterssurge diverters
surge diverters
 
measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
Power system stability
Power system stabilityPower system stability
Power system stability
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission Lines
 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer Presentation
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Protection against overvoltage
Protection against overvoltageProtection against overvoltage
Protection against overvoltage
 
Resonant Converter
Resonant ConverterResonant Converter
Resonant Converter
 

Ähnlich wie Overcurrent Protection

Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relays
michaeljmack
 
14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt
ssuser157f0e1
 
switchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptxswitchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptx
SaishDalvi
 

Ähnlich wie Overcurrent Protection (20)

Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Relays
RelaysRelays
Relays
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)
 
Fundamentals of Microprocessor-based Relaying
Fundamentals of Microprocessor-based RelayingFundamentals of Microprocessor-based Relaying
Fundamentals of Microprocessor-based Relaying
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relays
 
Protective relay.pptx
Protective relay.pptxProtective relay.pptx
Protective relay.pptx
 
14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt14362648-Chapter 7 System Protection.ppt
14362648-Chapter 7 System Protection.ppt
 
Power_System_Protection Lecture-1.pdf
Power_System_Protection Lecture-1.pdfPower_System_Protection Lecture-1.pdf
Power_System_Protection Lecture-1.pdf
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester ppt
 
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdferrahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
 
Relay Generation and history
Relay Generation and historyRelay Generation and history
Relay Generation and history
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptx
 
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxOhiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
 
Fusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity CircuitsFusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity Circuits
 
switchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptxswitchgear%20%20&%20protection%20introduction.pptx
switchgear%20%20&%20protection%20introduction.pptx
 
Pacemakers
PacemakersPacemakers
Pacemakers
 

Kürzlich hochgeladen

Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Kürzlich hochgeladen (20)

chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 

Overcurrent Protection

  • 2. Introduction : Overcurrent its cause and effects Overcurrent : • In an electrical power system overcurrent or excess current is a situation where a larger than intended electric current exists through a conductor, leading to excessive generation of heat, and the risk of fire or damage to equipment. Cause : • Short Circuit • Excessive Loading • Incorrect Design • Ground fault Effects • Equipment overloading and Equipment damage 2
  • 3. Overcurrent Relay Overcurrent Relay : • A protective relay which operates when the load current exceeds a preset value, is called an Overcurrent relay. • The value of the preset current above which relay operate is know as pickup value. • Overcurrent relay offer a cheapest and simplest form of protection. • These relays are used for the protection of distribution lines, large motor , Power equipments and industrial system. 3
  • 4. Working Principle • In an over current relay , there would be essentially a current coil. When normal current flows through this coil, the magnetic effect generated by the coil is not sufficient to move the moving element of the relay, as in this condition the restraining force is grater than deflecting force. • When the current through the coil increased, the magnetic effect increases and after certain level of current the deflecting force generated by the magnetic effect of the coil, crosses the restraining force, as a result the moving element starts moving to change the contact position in the relay. 4
  • 5. Overcurrent Protection • Overcurrent Relay are fed from Current transformer. • Whenever the current through the relay exceeds the preset value the relay operate and actuates the trip coil of the circuit breaker and isolate the faulty network . 5
  • 6. Types of Overcurrent relay Depending upon the operating time of the overcurrent relay • Instantaneous Overcurrent Relay • Definite time Overcurrent Relay • Inverse time Overcurrent Relay 6
  • 7. Instantaneous Overcurrent Relay • Instantaneous over current relay operate as soon as the current in the coil gets higher than the per set value(Ip). • There is no internal time delay set. • There is always an inherent time delay in order of a few millisecond (ms). (A)Current Time (sec) No Trip Trip Ip 7
  • 8. Definite Time Over Current Relay • Definite time over current relay is created by applying intentional time delay after crossing pick up value of the current. • A definite time over current relay can be adjusted to issue a trip time after its picks up.Thus , it has a time setting adjustment and pick up adjustment. I(A) Time Sec t1 t 8 Ip
  • 9. Inverse Time Over Current Relay • Inverse Time is a natural character of any inductive type rotating device. This means that , the time of relay operation inversely varies with input current . • This characteristic of electromechanical induction disc relay is very suitable for over current protection. • In this relay if the fault is more severe, it would be cleared more faster. Time Sec I(A) Inverse Time 9
  • 10. Classification of Inverse Time Relay Inverse time over current Relay (IDMT) again classified in • Standard or Normal inverse over current relay • Very Inverse time over current relay • Extremely Inverse time over current relay 10
  • 11. Standard IDMT Relay The current/time tripping characteristics of IDMT relays may need to be varied according to the tripping time required and the characteristics of other protective device used in network. For this purpose, IEC 60255 defines the number of standard characteristics as follows : • Standard Inverse (SI) • Very Inverse (VI) • Extremely Inverse (EI) • Definite Time (DT) 11
  • 12. Application of Overcurrent Relay Overcurrent relay are used for protection of electrical equipments such as : • Transformer • Generator • HT & LT breaker Failure Protection • Motors • HT Lines • EHT Lines (Directional Overcurrent & E/F relay ) • Capacitor Bank • Natural Displacement relay in capacitor banks 12