SlideShare ist ein Scribd-Unternehmen logo
1 von 57
Unit-III
Apparatus Protection:
Md Irshad Ahmad
Irshad.ahmad@jit.edu.in
Electrical Engineering Department
Subject: NEE –602: SWITCHGEAR AND PROTECTION
Unit-III
Protection of Transmission Line:
 Over current protection
 Distance protection,
 Pilot wire protection
 Carrier current protection
 Protection of bus
 Auto re-closing,
 As the fault impedance is less than load impedance,
the fault current is more than load current. If a short
circuit occurs the circuit impedance is reduced to a
low value and therefore a fault is accompanied by
large current.
 Over-current protection is that protection in which
the relay picks up when the magnitude of current
exceeds the pickup level.
 The Over-current relays are connected to the system,
normally by means of CT's
Over current protection
 1. High speed Over-current protection.
 2. Definite time Over-current protection.
 3. Inverse minimum time Over-current protection.
 4. Directional Over-current protection
(of above types).
Over-current relaying has following
types:
 Construction and working principle of instantaneous over current
relay quite simple.
 Magnetic core is wound by current coil. A piece of iron is so fitted by
hinge support and restraining spring in the relay, that when there is
not sufficient current in the coil, the NO contacts remain open. When
current in the coil crosses a present value, the attractive force
becomes sufficient to pull the iron piece towards the magnetic core
and consequently the no contacts are closed.
Instantaneous Over Current Relay
 Definite Time Over Current Relay
 This relay is created by applying intentional time delay after crossing
pick up value of the current. A definite time over current relay can
be adjusted to issue a trip output at definite amount of time after it
picks up. Thus, it has a time setting adjustment and pick up
adjustment.
 Inverse Time Over Current Relay
 Inverse time is a natural character of any induction type rotating
device. This means the speed of rotation of rotating art of the device
is faster if input current is increased.
 Inverse Definite Minimum Time Over Current Relay or IDMT O/C
Relay
 Inverse time characteristics can not be achieved, in an over current
relay. As the current in the system increases, the secondary current
of the current transformer is increased proportionally. The secondary
current is fed to the relay current coil. But when the CT becomes
saturated
Classification of Transmission Lines
Short Lines Length < = 80kM
Medium Lines Length < = 240kM
Long Lines Length > 240kM
Types of faults in the transmission
system
Short circuit faults Frequency
Phase – Ground faults 85%
Phase- Phase faults 8%
Phase – Phase –Ground faults 5%
3 Ph faults 2%
Open circuit faults
Broken conductor
Open jumper
Protection Scheme
Protection Scheme for Transmission lines as per CBIP guidelines
• Should have two independent high speed main protection schemes
• Two stage over voltage protection
• Sensitive IDMT directional E/F relays
• Auto reclose relay suitable for 1 ph/3ph (with deadline charging and
synchro check) reclosure.
Types of main Protections:
• Over Current Protection.
• Differential or Phase Comparison or Unit Protection.
• Distance Protection.
• Shall have min. of three independent zones with directional characteristics.
• Shall be non switched type with separate measurement for both earth faults
and phase faults
• Capable of 1phase and 3 phase tripping.
• Capable of operation for close up faults and switch on to faults
• Accuracy of better than 5% of reach setting for Zone 1, 10% for Zone-2 &3.
• Shall have variable residual compensation.
• Shall include power swing detection feature for selectively blocking.
• Shall include fuse failure feature to monitor all types of fuse failures and block
distance protection.
Requirements of distance protection:
If = E/(ZS+ZL)
The reach of over current relay is function of Source
Impedance which varies considerably, making it difficult
to get fast and Selective tripping .
E ZS ZL
If
XXXXX
Over Current Protection
Phase Comparison Protection
 Current Phase comparison type
 Suitable for operation with PLCC
 High sensitivity and selectivity for all types of faults
 Capable of single and three pole tripping.
 Un effected By:
 Heavy load transfer
 Power swings
 CT saturation
 CT Phase errors

Distance Protection
Type of distance relays
Reactance
 Suitable for short lines
 Not effected by fault resistance
 Effected by power swings
 Non directional
Impedance
 Suitable for medium lines
 Non directional
 Effected by fault resistance
Mho
 Directional
 Least effected by power swings
 Less effected by fault resistance
Impedance Relay Characteristics
Load
Area
X
R
Z1
Z2
Z3
MHO relay characteristic
The characteristic of a mho impedance element , when plotted
on a R/X diagram, is a circle whose circumference pass through
the origin .
Y
Y = relay characteristic angle
R
X
OFF set MHO characteristic
Under close up faults, when the voltage is near to zero then MHO will
not operate. The mho characteristic can be shifted towards origin for
operation of close up faults. This is know as OFF set MHO.
Y
Y = relay characteristic angle
R
X
Lenticular characteristics
The characteristic of lenticular mho will be useful to provide
maximum load transfer condition with maximum fault
resistance coverage.
Y
Y = relay characteristic angle
Z-1
Z-2
Z-3
Z-3
R
Quadrilateral characteristic
It is a basically a reactance relay superseded with
controlled resistive reach.
Y
Y = relay characteristic angle
Z-1&2
Z-1
Z-2
Z-3
Z-3
Zones of Distance Protection:
Z1
Z2
Z3
BASIC SETTING PHILOSOPHY
ZONE –1 : 80 % of protected line
ZONE –2 : 100 % of protected line + 20 % of shortest adj. line
section or 100% + 50% of transformer impedance
ZONE –3 : 100% of protected line + 100 % of longest adj. line
or 100 % + 100% of transformer impedance.
ZONE -4 : To cover close up back-up non-directional faults generally
reverse reach will be provided in relays (10%).
X X X X X X
Parallel Compensation
Necessity of parallel compensation:
For the fault on the parallel line, fault current also fed from healthy line and
 this current pass through ground. This current changes the mutual
 inductance and in turn causes relay measuring impedance to increase and
 is more than actual fault impedance.
This effect will be compensated by connecting neutral current of the line to
 parallel line.
This compensation will not work, if the parallel line neutral current is more
 than line neutral current.
ZONE-II CHARACTERISTICS
Delayed tripping and non selective phase tripping.
Provide back up protection for part of adjacent line.
Trip the faulty line instantaneously using carrier aided tripping.
Time delay is normally 500ms
ZONE-III CHARACTERISTICS
This provides back up protection for the adjacent lines or
transformer
Time delay is normally 1500ms
ZONE –IV CHARACTERISTICS
This provides back up protection for the station faults
It is normally in the reverse direction
Time delay is normally 1500ms
Distance Schemes:
1 . P . U . R -- Permissive under reach scheme
2. P . O . R -- Permissive Over Reach scheme
3. BLOCKING SCHEME
4. WEAK END FEED
AUTORECLOSE – PHILOSOPHY
NEED FOR AUTO RECLOSE
1. REDUCING OUTAGE TIME
2. IMPROVED RELIABILITY
3. RESTORATION OF NETWORK STABILITY AND
SYNCHRONISM
TYPES OF FAULTS
1. TRANSIENT FAULTS
2. SEMI PERMANENT FAULTS
3. PERMANENT FAULTS
TRANSIENT FAULTS -CHARACTERISTIC
Chracterised by disappearnance after Short dead time and are
disapper without any action being taken.
TYPES OF TRANSIENT FAULTS
1. Lightning strokes resulting in fashovers
2. Conductor swinging due to high winds
3. Bird fault
4. Temporary contact with foreign objects like tree etc.
About 85 % of faults on transmission lines are transient in nature
DEAD TIME :
The time between the autoreclose scheme being energised
and the operation of the contacts which energise the CB closing
Circuit.
RECLAIM TIME :
The time following a successful closing operation measured
from the instant the A/R relay closing contacts make, which
must elapse before the autoreclose relay will initiate reclosing
sequence in the event of a further fault.
CHOICE OF RECLAIM TIME
The reclaim time must not be set to such a low value that
the intended operating cycle of the breaker is exceeded
when two fault incidents occurs close together.
for example the reclaim time for a air blast circuit breakers
must allow time for air pressure to recover to its normal
value.
CHOICE OF DEAD TIME
Dead time for EHV system lower limit is decided by
de-ionising time, upper limit is decided by transient stability
and synchronism
Power Swing
Power Swings are disturbances in system due to various reasons
such as sudden load throw, bad synchronization etc
Power swings are characterized by slow power flow oscillations,
resulting in swinging of voltages and currents, resulting in
operating point movement into distance relay characteristics,
in turn can cause tripping of distance relays.
Tripping during power swings is undesirable since no actual fault
is present and moreover a line outage during power swing may
cause further deterioration to system stability.
Detection of power swing will block the distance protection
Zones 2,3,4. Normally tripping in Zone-I is not blocked even after
detection of power swing.
X
R
Z1
Z2
Z3
Power
swing
detection
zones
Power Swing detection
Time taken by fault locus to cross the power swing
detection zones is more than 40-50ms, then it is called
power swing.
Fuse Failure Function
Asymmetrical measuring voltage failure:
Substantial asymmetry of measured voltage, while the measured
 currents are in symmetry indicates fuse fail
Asymmetry of voltage detected by 3Uo or U2 > threshold
Symmetry in current detected by 3Io or I2 < threshold
During blocking of distance protection by fuse fail, the distance
 protection switched to emergency over current function automatically.
 If the asymmetry in measured current is detected during blocking by FF
 function, then FF block will released.
Switch on to fault
This feature provide protection against energisation of the tr.
line with fault or dead short.
Distance protection will not provide protection in
this case as voltage is not available for distance measurement.
It can be activated by TNC switch or CB aux. binary input or
internal detection of current rise.
It provides instantaneous 3Ph trip and blocks auto reclose.
One and Half Breaker Scheme
Ckt-1 Ckt-2
Bus-1
Bus-2
21
Stub Protection
DEF Protection
It provides back up protection for tr. line.
It provides reliable protection for high resistance earth
faults.
It uses cross polarized voltage for directional
discrimination.
 Carrier current protection scheme is mainly used for the
protection of the long transmission line.
 In the carrier, current protection schemes, the phase angle of
the current at the two phases of the line are compared instead
of the actual current.
 Phase angle of the line decides whether the fault is internal
and external.
 The main elements of the carrier channel are a transmitter,
receiver, coupling equipment, and line trap
Carrier Current Protection of
Transmission Lines
 In Absence Of BUSBAR Protection,
Fault Clearance takes place
in Zone II of Distance Relay by
Remote End Tripping
 This Means Slow & Unselective Tripping
and wide spread blackout
NEED FOR BUS BAR PROTECTION
 Minimizing damage at fault location
 Maintaining system stability
 Localizing isolation to avoid wide
spread disruption
 Delayed clearance create shock to inter
connected equipment like Generator shaft
and windings of Transformer
NEED FOR BUS BAR PROTECTION
 High speed operation
 Selectivity – shall isolate the faulty bus bar only
 Stability – stable for through faults upto 40 KA
fault level
 Reliability – Check feature
 Applicable for any type of bus bar protection
 Shall provide zone indication
REQUIREMENT OF BUS BAR
PROTECTION
 Continuous supervision for CT Secondaries
against any possible Open Ckt.
 In case of detection of any Open Circuiting of CT
secondary, after a time delay, the affected zone
of protection shall be rendered(provide) in-
operative and an alarm initiated.
REQUIREMENT OF BUS BAR PROTECTION
 Bus bar protection must be provided in all new 400kV and
220kV Substations as well as Generation Switch Yards
 For existing substations, provision of bus bar protection is
considered a must at 400kV level and for 220kV level it is
essential at substations having multiple feed.
 In case of radially fed 220kv substations, having more
than one bus it is desirable to have bus bar protection but
is not a must
RECOMMENDATIONS FOR PROVIDING BUS BAR
PROTECTION
NEED FOR BUSBAR PROTECTION
In Its Absence Fault Clearing Takes Place In Zone-2 Of Distance Relay By Remote
End Tripping. this means slow and unselective tripping and wide spread blackout.
EFFECT OF DELAYED CLEARENCE
 Greater damage at fault point.
 Indirect shock to connected equipment like shafts of generator and windings of
transformer.
BASIC THEORY
Kirchoff’s current law states that the sum of the currents entering a given node must
be equal to the currents leaving at that node.
BASICS OF BUSBAR PROTECTION
TYPES OF BUS BAR PROTECTION
 Low Impedance
 High Impedance
Both use Circulating Current Differential
Principle - To isolate the entire bus bar section
by disconnecting all the feeders connected to
the bus.
HIGH SPEED DIFFERENTIAL PROTECTION
Simple Current Differential Circuit:
Simple Current Differential Circuit with Bus Fault
Simple Current Differential Circuit with Close in Line Fault
AUTO-RECLOSING
 It is placed on over head transmission line and nearer to
the CB .
 It is also one of the protective relay.
44
What is
Auto – Reclosing ?
45
Introduction to auto-reclosing
scheme
46
Types Of Faults
• Transient Faults
• Semi Permanent faults
• Permanent Faults
Utility Substation Customers
47
48
STEPS TO BE FOLLOWED IN AUTORECLOSING
Visual Check
Check of the
Power Supply
Test of the
Auto-re-closure settings
Functional Testing
(involving operation of
Protective Relays
& Circuit Breaker(s)
INSTALLATION
OPERATION
Scheme Of Operation
• Live bus Dead Line Charging
• Other end closing under synchronism check relay
• Live bus Live line charging
49
Types of Auto Reclosing
1. Medium voltage auto-reclose
• Aim of continuity of supply
• the obvious advantages are continuous supply except for short
duration when tripping and re-closure operations are being performed.
• high speed protection decreases the amount of damage incurred and
thus increases the probability of auto reclosure.
2. High voltage auto-reclose
• main considerations are of stability and synchronizing.
• the fault levels associated are extremely high.
• High speed re-closure in high voltage circuits improves the stability
to a considerable extent on single-circuit ties.
FACTORS TO BE CONSIDERED FOR
AUTO RECLOSING SYSTEM
• Protection Characteristics
• De- Ionization of Fault Arc
• Circuit Breaker Characteristics
• Reclaim Time
• Number of Shots
51
SINGLE PHASE AUTO – RECLOSING
ADVANTAGES:-
•Maintenance of System Integrity
• Reduced switching overvoltage due to reclosing
• Reduced shock to generators.
• Sudden changes in mechanical output are less
• Longer De – ionization time
DISADVANTAGE:-
52
1. Densely interconnected systems.

Where the Loss of a single line is unlikely to
cause loss of synchronism between two ends
2. Dead Time is allowed to be long enough for any
power swings due to fault and tripping allowed
to decay before reclosing

a) Less shock to system than with high speed
A/R
b) Problems of arc de – ionization times, and
circuit breaker operating characterstics are
eliminated.
Delayed Auto-Reclose Application
53
Operating feature of Auto reclosing
schemes
• Dead Timer
• Anti Pumping Devices
• Reclaim timer
• CB Lockout
• Manual Closing
• Multi Shot Scheme
54
Auto - Reclose Blocking
• Receipt of transfer Trip
• Manual Trip
• Breaker failure
• Three phase Fault
• Faults On Buses
• Under frequency/ Under voltage load shedding trips
55
Benefits Of Auto - Reclosing
• Minimizing the interruption of supply.
• Maintenance of system stability and Synchronism.
• Minimum Outage and least expenditure of manpower.
• Ability to run substation unattended.
56
Switchgear and protection 3

Weitere ähnliche Inhalte

Was ist angesagt?

Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Rohini Haridas
 
Tripping and control of impulse generators
Tripping and control of impulse generatorsTripping and control of impulse generators
Tripping and control of impulse generatorsFariza Zahari
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.pptSalim Palayi
 
Switchgear and protection 2
Switchgear and protection 2Switchgear and protection 2
Switchgear and protection 2Md Irshad Ahmad
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zonesSlides Hub
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage ControlYashvi Mehta
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relayCS V
 
Planning and modern trends in hvdc
Planning and modern trends in hvdcPlanning and modern trends in hvdc
Planning and modern trends in hvdcjawaharramaya
 
Power system protection
Power system protectionPower system protection
Power system protectionAnu Priya
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
electrical machines
electrical machineselectrical machines
electrical machinesmahesh babu
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 

Was ist angesagt? (20)

Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
 
Tripping and control of impulse generators
Tripping and control of impulse generatorsTripping and control of impulse generators
Tripping and control of impulse generators
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
Switchgear and protection 2
Switchgear and protection 2Switchgear and protection 2
Switchgear and protection 2
 
Static relay
Static relayStatic relay
Static relay
 
Per unit system
Per unit systemPer unit system
Per unit system
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage Control
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Planning and modern trends in hvdc
Planning and modern trends in hvdcPlanning and modern trends in hvdc
Planning and modern trends in hvdc
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
electrical machines
electrical machineselectrical machines
electrical machines
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Relays
RelaysRelays
Relays
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 

Andere mochten auch

Switchgear and protection 4
Switchgear and protection 4Switchgear and protection 4
Switchgear and protection 4Md Irshad Ahmad
 
Switchgear and protection 5
Switchgear and protection 5Switchgear and protection 5
Switchgear and protection 5Md Irshad Ahmad
 
switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamleshKamlesh Vala
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protectionBinit Das
 
20120504 LISAT slides Dube
20120504 LISAT slides Dube20120504 LISAT slides Dube
20120504 LISAT slides Dubemosesnbklyn
 
Irshad hygiene &amp; cleaning committee
Irshad hygiene &amp; cleaning committeeIrshad hygiene &amp; cleaning committee
Irshad hygiene &amp; cleaning committeeMd Irshad Ahmad
 
Study of generator and switchgear Vizag steel plant report
Study of generator and switchgear Vizag steel plant reportStudy of generator and switchgear Vizag steel plant report
Study of generator and switchgear Vizag steel plant reportsushi roy
 
Irshad Caring mother earth day 22nd of April 2016
Irshad Caring mother earth day 22nd of April 2016Irshad Caring mother earth day 22nd of April 2016
Irshad Caring mother earth day 22nd of April 2016Md Irshad Ahmad
 
Switchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsSwitchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsNicola Cochrane
 
Commissioning Testing And Maintenance (M'sia) - Arifin
Commissioning Testing And Maintenance (M'sia) - ArifinCommissioning Testing And Maintenance (M'sia) - Arifin
Commissioning Testing And Maintenance (M'sia) - ArifinMd Arifin
 

Andere mochten auch (20)

Switchgear and protection 4
Switchgear and protection 4Switchgear and protection 4
Switchgear and protection 4
 
Switchgear and protection 5
Switchgear and protection 5Switchgear and protection 5
Switchgear and protection 5
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamlesh
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
 
EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013
 
distance relay
distance relaydistance relay
distance relay
 
20120504 LISAT slides Dube
20120504 LISAT slides Dube20120504 LISAT slides Dube
20120504 LISAT slides Dube
 
Irshad hygiene &amp; cleaning committee
Irshad hygiene &amp; cleaning committeeIrshad hygiene &amp; cleaning committee
Irshad hygiene &amp; cleaning committee
 
Unit 5
Unit 5Unit 5
Unit 5
 
Power quality 3
Power quality 3Power quality 3
Power quality 3
 
Power quality 4
Power quality 4Power quality 4
Power quality 4
 
Unit ii-2 -
Unit ii-2 -Unit ii-2 -
Unit ii-2 -
 
Study of generator and switchgear Vizag steel plant report
Study of generator and switchgear Vizag steel plant reportStudy of generator and switchgear Vizag steel plant report
Study of generator and switchgear Vizag steel plant report
 
Irshad Caring mother earth day 22nd of April 2016
Irshad Caring mother earth day 22nd of April 2016Irshad Caring mother earth day 22nd of April 2016
Irshad Caring mother earth day 22nd of April 2016
 
Power quality 2
Power quality 2Power quality 2
Power quality 2
 
Switchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsSwitchgear and Protection of HV Systems
Switchgear and Protection of HV Systems
 
Khao lam
Khao lamKhao lam
Khao lam
 
Commissioning process for writing *new*
Commissioning process for writing *new*Commissioning process for writing *new*
Commissioning process for writing *new*
 
Commissioning Testing And Maintenance (M'sia) - Arifin
Commissioning Testing And Maintenance (M'sia) - ArifinCommissioning Testing And Maintenance (M'sia) - Arifin
Commissioning Testing And Maintenance (M'sia) - Arifin
 

Ähnlich wie Switchgear and protection 3

os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).pptos-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).pptThien Phan Bản
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]moiz89
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)Adarsh Verma
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdfThien Phan Bản
 
Presentation1.pptx power system
Presentation1.pptx power systemPresentation1.pptx power system
Presentation1.pptx power systemArvind Nathan
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars PremanandDesai
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detailSlides Hub
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protectionDinesh Sharma
 
Introduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basicsIntroduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basicsMd. Rashedul Islam
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONDr. Rohit Babu
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
presentation.pptx
presentation.pptxpresentation.pptx
presentation.pptxHasan21747
 
Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...IDES Editor
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.pptThien Phan Bản
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSHIVANICHAUUHAN1
 
Generator Protection
Generator ProtectionGenerator Protection
Generator ProtectionPriten Vasa
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSatish Pydimarla
 

Ähnlich wie Switchgear and protection 3 (20)

os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).pptos-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf
 
Presentation1.pptx power system
Presentation1.pptx power systemPresentation1.pptx power system
Presentation1.pptx power system
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
Introduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basicsIntroduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basics
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
presentation.pptx
presentation.pptxpresentation.pptx
presentation.pptx
 
Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
PPT.pptx
PPT.pptxPPT.pptx
PPT.pptx
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 

Mehr von Md Irshad Ahmad

Academic Council Meet PPT- 19
Academic Council Meet PPT- 19Academic Council Meet PPT- 19
Academic Council Meet PPT- 19Md Irshad Ahmad
 
Power station practice (NEE-702) unit-5
Power station practice (NEE-702) unit-5Power station practice (NEE-702) unit-5
Power station practice (NEE-702) unit-5Md Irshad Ahmad
 
Power station practice (NEE-702) unit-4
Power station practice (NEE-702) unit-4Power station practice (NEE-702) unit-4
Power station practice (NEE-702) unit-4Md Irshad Ahmad
 
Power station practice (NEE-702) unit-3
Power station practice (NEE-702) unit-3Power station practice (NEE-702) unit-3
Power station practice (NEE-702) unit-3Md Irshad Ahmad
 
Power station practice (NEE-702) unit-2
Power station practice (NEE-702) unit-2Power station practice (NEE-702) unit-2
Power station practice (NEE-702) unit-2Md Irshad Ahmad
 
Power station practice (NEE- 702) unit-1
Power station practice (NEE- 702) unit-1Power station practice (NEE- 702) unit-1
Power station practice (NEE- 702) unit-1Md Irshad Ahmad
 
Electrical measurement & measuring instruments [emmi (nee-302) -unit-5]
Electrical measurement & measuring instruments [emmi  (nee-302) -unit-5]Electrical measurement & measuring instruments [emmi  (nee-302) -unit-5]
Electrical measurement & measuring instruments [emmi (nee-302) -unit-5]Md Irshad Ahmad
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-4]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-4]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-4]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-4]Md Irshad Ahmad
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-3]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-3]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-3]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-3]Md Irshad Ahmad
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]Md Irshad Ahmad
 
ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]
ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]
ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]Md Irshad Ahmad
 

Mehr von Md Irshad Ahmad (14)

Academic Council Meet PPT- 19
Academic Council Meet PPT- 19Academic Council Meet PPT- 19
Academic Council Meet PPT- 19
 
Power station practice (NEE-702) unit-5
Power station practice (NEE-702) unit-5Power station practice (NEE-702) unit-5
Power station practice (NEE-702) unit-5
 
Power station practice (NEE-702) unit-4
Power station practice (NEE-702) unit-4Power station practice (NEE-702) unit-4
Power station practice (NEE-702) unit-4
 
Power station practice (NEE-702) unit-3
Power station practice (NEE-702) unit-3Power station practice (NEE-702) unit-3
Power station practice (NEE-702) unit-3
 
Power station practice (NEE-702) unit-2
Power station practice (NEE-702) unit-2Power station practice (NEE-702) unit-2
Power station practice (NEE-702) unit-2
 
Power station practice (NEE- 702) unit-1
Power station practice (NEE- 702) unit-1Power station practice (NEE- 702) unit-1
Power station practice (NEE- 702) unit-1
 
Electrical measurement & measuring instruments [emmi (nee-302) -unit-5]
Electrical measurement & measuring instruments [emmi  (nee-302) -unit-5]Electrical measurement & measuring instruments [emmi  (nee-302) -unit-5]
Electrical measurement & measuring instruments [emmi (nee-302) -unit-5]
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-4]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-4]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-4]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-4]
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-3]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-3]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-3]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-3]
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
 
ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]
ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]
ELECTRICAL MEASUREMENT & MEASURING INSTRUMENTS [Emmi- (NEE-302) -unit-1]
 
Power quality 5
Power quality 5Power quality 5
Power quality 5
 
Power quality 1
Power quality 1Power quality 1
Power quality 1
 
Electromagnetic Theory
Electromagnetic Theory Electromagnetic Theory
Electromagnetic Theory
 

Kürzlich hochgeladen

University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spaintimesproduction05
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Christo Ananth
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLManishPatel169454
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01KreezheaRecto
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 

Kürzlich hochgeladen (20)

University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 

Switchgear and protection 3

  • 1. Unit-III Apparatus Protection: Md Irshad Ahmad Irshad.ahmad@jit.edu.in Electrical Engineering Department Subject: NEE –602: SWITCHGEAR AND PROTECTION
  • 2. Unit-III Protection of Transmission Line:  Over current protection  Distance protection,  Pilot wire protection  Carrier current protection  Protection of bus  Auto re-closing,
  • 3.  As the fault impedance is less than load impedance, the fault current is more than load current. If a short circuit occurs the circuit impedance is reduced to a low value and therefore a fault is accompanied by large current.  Over-current protection is that protection in which the relay picks up when the magnitude of current exceeds the pickup level.  The Over-current relays are connected to the system, normally by means of CT's Over current protection
  • 4.  1. High speed Over-current protection.  2. Definite time Over-current protection.  3. Inverse minimum time Over-current protection.  4. Directional Over-current protection (of above types). Over-current relaying has following types:
  • 5.  Construction and working principle of instantaneous over current relay quite simple.  Magnetic core is wound by current coil. A piece of iron is so fitted by hinge support and restraining spring in the relay, that when there is not sufficient current in the coil, the NO contacts remain open. When current in the coil crosses a present value, the attractive force becomes sufficient to pull the iron piece towards the magnetic core and consequently the no contacts are closed. Instantaneous Over Current Relay
  • 6.  Definite Time Over Current Relay  This relay is created by applying intentional time delay after crossing pick up value of the current. A definite time over current relay can be adjusted to issue a trip output at definite amount of time after it picks up. Thus, it has a time setting adjustment and pick up adjustment.  Inverse Time Over Current Relay  Inverse time is a natural character of any induction type rotating device. This means the speed of rotation of rotating art of the device is faster if input current is increased.  Inverse Definite Minimum Time Over Current Relay or IDMT O/C Relay  Inverse time characteristics can not be achieved, in an over current relay. As the current in the system increases, the secondary current of the current transformer is increased proportionally. The secondary current is fed to the relay current coil. But when the CT becomes saturated
  • 7. Classification of Transmission Lines Short Lines Length < = 80kM Medium Lines Length < = 240kM Long Lines Length > 240kM
  • 8. Types of faults in the transmission system Short circuit faults Frequency Phase – Ground faults 85% Phase- Phase faults 8% Phase – Phase –Ground faults 5% 3 Ph faults 2% Open circuit faults Broken conductor Open jumper
  • 9. Protection Scheme Protection Scheme for Transmission lines as per CBIP guidelines • Should have two independent high speed main protection schemes • Two stage over voltage protection • Sensitive IDMT directional E/F relays • Auto reclose relay suitable for 1 ph/3ph (with deadline charging and synchro check) reclosure. Types of main Protections: • Over Current Protection. • Differential or Phase Comparison or Unit Protection. • Distance Protection.
  • 10. • Shall have min. of three independent zones with directional characteristics. • Shall be non switched type with separate measurement for both earth faults and phase faults • Capable of 1phase and 3 phase tripping. • Capable of operation for close up faults and switch on to faults • Accuracy of better than 5% of reach setting for Zone 1, 10% for Zone-2 &3. • Shall have variable residual compensation. • Shall include power swing detection feature for selectively blocking. • Shall include fuse failure feature to monitor all types of fuse failures and block distance protection. Requirements of distance protection:
  • 11. If = E/(ZS+ZL) The reach of over current relay is function of Source Impedance which varies considerably, making it difficult to get fast and Selective tripping . E ZS ZL If XXXXX Over Current Protection
  • 12. Phase Comparison Protection  Current Phase comparison type  Suitable for operation with PLCC  High sensitivity and selectivity for all types of faults  Capable of single and three pole tripping.  Un effected By:  Heavy load transfer  Power swings  CT saturation  CT Phase errors 
  • 13. Distance Protection Type of distance relays Reactance  Suitable for short lines  Not effected by fault resistance  Effected by power swings  Non directional Impedance  Suitable for medium lines  Non directional  Effected by fault resistance Mho  Directional  Least effected by power swings  Less effected by fault resistance
  • 15. MHO relay characteristic The characteristic of a mho impedance element , when plotted on a R/X diagram, is a circle whose circumference pass through the origin . Y Y = relay characteristic angle R X
  • 16. OFF set MHO characteristic Under close up faults, when the voltage is near to zero then MHO will not operate. The mho characteristic can be shifted towards origin for operation of close up faults. This is know as OFF set MHO. Y Y = relay characteristic angle R X
  • 17. Lenticular characteristics The characteristic of lenticular mho will be useful to provide maximum load transfer condition with maximum fault resistance coverage. Y Y = relay characteristic angle Z-1 Z-2 Z-3 Z-3 R
  • 18. Quadrilateral characteristic It is a basically a reactance relay superseded with controlled resistive reach. Y Y = relay characteristic angle Z-1&2 Z-1 Z-2 Z-3 Z-3
  • 19. Zones of Distance Protection: Z1 Z2 Z3 BASIC SETTING PHILOSOPHY ZONE –1 : 80 % of protected line ZONE –2 : 100 % of protected line + 20 % of shortest adj. line section or 100% + 50% of transformer impedance ZONE –3 : 100% of protected line + 100 % of longest adj. line or 100 % + 100% of transformer impedance. ZONE -4 : To cover close up back-up non-directional faults generally reverse reach will be provided in relays (10%). X X X X X X
  • 20. Parallel Compensation Necessity of parallel compensation: For the fault on the parallel line, fault current also fed from healthy line and  this current pass through ground. This current changes the mutual  inductance and in turn causes relay measuring impedance to increase and  is more than actual fault impedance. This effect will be compensated by connecting neutral current of the line to  parallel line. This compensation will not work, if the parallel line neutral current is more  than line neutral current.
  • 21. ZONE-II CHARACTERISTICS Delayed tripping and non selective phase tripping. Provide back up protection for part of adjacent line. Trip the faulty line instantaneously using carrier aided tripping. Time delay is normally 500ms ZONE-III CHARACTERISTICS This provides back up protection for the adjacent lines or transformer Time delay is normally 1500ms ZONE –IV CHARACTERISTICS This provides back up protection for the station faults It is normally in the reverse direction Time delay is normally 1500ms
  • 22. Distance Schemes: 1 . P . U . R -- Permissive under reach scheme 2. P . O . R -- Permissive Over Reach scheme 3. BLOCKING SCHEME 4. WEAK END FEED
  • 23. AUTORECLOSE – PHILOSOPHY NEED FOR AUTO RECLOSE 1. REDUCING OUTAGE TIME 2. IMPROVED RELIABILITY 3. RESTORATION OF NETWORK STABILITY AND SYNCHRONISM TYPES OF FAULTS 1. TRANSIENT FAULTS 2. SEMI PERMANENT FAULTS 3. PERMANENT FAULTS
  • 24. TRANSIENT FAULTS -CHARACTERISTIC Chracterised by disappearnance after Short dead time and are disapper without any action being taken. TYPES OF TRANSIENT FAULTS 1. Lightning strokes resulting in fashovers 2. Conductor swinging due to high winds 3. Bird fault 4. Temporary contact with foreign objects like tree etc. About 85 % of faults on transmission lines are transient in nature
  • 25. DEAD TIME : The time between the autoreclose scheme being energised and the operation of the contacts which energise the CB closing Circuit. RECLAIM TIME : The time following a successful closing operation measured from the instant the A/R relay closing contacts make, which must elapse before the autoreclose relay will initiate reclosing sequence in the event of a further fault.
  • 26. CHOICE OF RECLAIM TIME The reclaim time must not be set to such a low value that the intended operating cycle of the breaker is exceeded when two fault incidents occurs close together. for example the reclaim time for a air blast circuit breakers must allow time for air pressure to recover to its normal value. CHOICE OF DEAD TIME Dead time for EHV system lower limit is decided by de-ionising time, upper limit is decided by transient stability and synchronism
  • 27. Power Swing Power Swings are disturbances in system due to various reasons such as sudden load throw, bad synchronization etc Power swings are characterized by slow power flow oscillations, resulting in swinging of voltages and currents, resulting in operating point movement into distance relay characteristics, in turn can cause tripping of distance relays. Tripping during power swings is undesirable since no actual fault is present and moreover a line outage during power swing may cause further deterioration to system stability. Detection of power swing will block the distance protection Zones 2,3,4. Normally tripping in Zone-I is not blocked even after detection of power swing.
  • 28. X R Z1 Z2 Z3 Power swing detection zones Power Swing detection Time taken by fault locus to cross the power swing detection zones is more than 40-50ms, then it is called power swing.
  • 29. Fuse Failure Function Asymmetrical measuring voltage failure: Substantial asymmetry of measured voltage, while the measured  currents are in symmetry indicates fuse fail Asymmetry of voltage detected by 3Uo or U2 > threshold Symmetry in current detected by 3Io or I2 < threshold During blocking of distance protection by fuse fail, the distance  protection switched to emergency over current function automatically.  If the asymmetry in measured current is detected during blocking by FF  function, then FF block will released.
  • 30. Switch on to fault This feature provide protection against energisation of the tr. line with fault or dead short. Distance protection will not provide protection in this case as voltage is not available for distance measurement. It can be activated by TNC switch or CB aux. binary input or internal detection of current rise. It provides instantaneous 3Ph trip and blocks auto reclose.
  • 31. One and Half Breaker Scheme Ckt-1 Ckt-2 Bus-1 Bus-2 21 Stub Protection
  • 32. DEF Protection It provides back up protection for tr. line. It provides reliable protection for high resistance earth faults. It uses cross polarized voltage for directional discrimination.
  • 33.  Carrier current protection scheme is mainly used for the protection of the long transmission line.  In the carrier, current protection schemes, the phase angle of the current at the two phases of the line are compared instead of the actual current.  Phase angle of the line decides whether the fault is internal and external.  The main elements of the carrier channel are a transmitter, receiver, coupling equipment, and line trap Carrier Current Protection of Transmission Lines
  • 34.  In Absence Of BUSBAR Protection, Fault Clearance takes place in Zone II of Distance Relay by Remote End Tripping  This Means Slow & Unselective Tripping and wide spread blackout NEED FOR BUS BAR PROTECTION
  • 35.  Minimizing damage at fault location  Maintaining system stability  Localizing isolation to avoid wide spread disruption  Delayed clearance create shock to inter connected equipment like Generator shaft and windings of Transformer NEED FOR BUS BAR PROTECTION
  • 36.  High speed operation  Selectivity – shall isolate the faulty bus bar only  Stability – stable for through faults upto 40 KA fault level  Reliability – Check feature  Applicable for any type of bus bar protection  Shall provide zone indication REQUIREMENT OF BUS BAR PROTECTION
  • 37.  Continuous supervision for CT Secondaries against any possible Open Ckt.  In case of detection of any Open Circuiting of CT secondary, after a time delay, the affected zone of protection shall be rendered(provide) in- operative and an alarm initiated. REQUIREMENT OF BUS BAR PROTECTION
  • 38.  Bus bar protection must be provided in all new 400kV and 220kV Substations as well as Generation Switch Yards  For existing substations, provision of bus bar protection is considered a must at 400kV level and for 220kV level it is essential at substations having multiple feed.  In case of radially fed 220kv substations, having more than one bus it is desirable to have bus bar protection but is not a must RECOMMENDATIONS FOR PROVIDING BUS BAR PROTECTION
  • 39. NEED FOR BUSBAR PROTECTION In Its Absence Fault Clearing Takes Place In Zone-2 Of Distance Relay By Remote End Tripping. this means slow and unselective tripping and wide spread blackout. EFFECT OF DELAYED CLEARENCE  Greater damage at fault point.  Indirect shock to connected equipment like shafts of generator and windings of transformer. BASIC THEORY Kirchoff’s current law states that the sum of the currents entering a given node must be equal to the currents leaving at that node. BASICS OF BUSBAR PROTECTION
  • 40. TYPES OF BUS BAR PROTECTION  Low Impedance  High Impedance Both use Circulating Current Differential Principle - To isolate the entire bus bar section by disconnecting all the feeders connected to the bus.
  • 41. HIGH SPEED DIFFERENTIAL PROTECTION Simple Current Differential Circuit:
  • 42. Simple Current Differential Circuit with Bus Fault
  • 43. Simple Current Differential Circuit with Close in Line Fault
  • 44. AUTO-RECLOSING  It is placed on over head transmission line and nearer to the CB .  It is also one of the protective relay. 44
  • 45. What is Auto – Reclosing ? 45
  • 47. Types Of Faults • Transient Faults • Semi Permanent faults • Permanent Faults Utility Substation Customers 47
  • 48. 48 STEPS TO BE FOLLOWED IN AUTORECLOSING Visual Check Check of the Power Supply Test of the Auto-re-closure settings Functional Testing (involving operation of Protective Relays & Circuit Breaker(s) INSTALLATION OPERATION
  • 49. Scheme Of Operation • Live bus Dead Line Charging • Other end closing under synchronism check relay • Live bus Live line charging 49
  • 50. Types of Auto Reclosing 1. Medium voltage auto-reclose • Aim of continuity of supply • the obvious advantages are continuous supply except for short duration when tripping and re-closure operations are being performed. • high speed protection decreases the amount of damage incurred and thus increases the probability of auto reclosure. 2. High voltage auto-reclose • main considerations are of stability and synchronizing. • the fault levels associated are extremely high. • High speed re-closure in high voltage circuits improves the stability to a considerable extent on single-circuit ties.
  • 51. FACTORS TO BE CONSIDERED FOR AUTO RECLOSING SYSTEM • Protection Characteristics • De- Ionization of Fault Arc • Circuit Breaker Characteristics • Reclaim Time • Number of Shots 51
  • 52. SINGLE PHASE AUTO – RECLOSING ADVANTAGES:- •Maintenance of System Integrity • Reduced switching overvoltage due to reclosing • Reduced shock to generators. • Sudden changes in mechanical output are less • Longer De – ionization time DISADVANTAGE:- 52
  • 53. 1. Densely interconnected systems.  Where the Loss of a single line is unlikely to cause loss of synchronism between two ends 2. Dead Time is allowed to be long enough for any power swings due to fault and tripping allowed to decay before reclosing  a) Less shock to system than with high speed A/R b) Problems of arc de – ionization times, and circuit breaker operating characterstics are eliminated. Delayed Auto-Reclose Application 53
  • 54. Operating feature of Auto reclosing schemes • Dead Timer • Anti Pumping Devices • Reclaim timer • CB Lockout • Manual Closing • Multi Shot Scheme 54
  • 55. Auto - Reclose Blocking • Receipt of transfer Trip • Manual Trip • Breaker failure • Three phase Fault • Faults On Buses • Under frequency/ Under voltage load shedding trips 55
  • 56. Benefits Of Auto - Reclosing • Minimizing the interruption of supply. • Maintenance of system stability and Synchronism. • Minimum Outage and least expenditure of manpower. • Ability to run substation unattended. 56