1.General Description
The power factor regulator combines comprehensive operation with
user-friendly control setting. It uses numerical techniques in
computing the phase difference between the fundamentals of
current and voltage, thus precise power factor measurement is
achieved even in presence of harmonics.
The power factor regulator is designed to optimize the control of
reactive power compensation. Reactive power compensation is
achieved by measuring continuously the reactive power of the
system and then compensated by the switching of capacitor banks.
The sensitivity setting optimizes the switching speed.With the built-
in intelligent automatic switching program, the power factor
regulator further improves the switching efficiency by reducing the
number of switching operations required to achieve the desired
power factor.
Usage of the capacitor bank is evenly distributed by the intelligent
switching algorithm. This ensures uniform ageing of the capacitors
and the contactors used.
The four-quadrant operation feature allows the power factor
regulator to operate correctly in the case of active power feed back
to the mains where regenerative power sources are used.
Harmonic current in the system can be harmful to the capacitor
bank. This power factor regulator is capable of measuring the total
harmonic distortion (THD) in the system and produce an alarm if the
THD level is higher than the pre-set value. Other alarms include
under/over compensate alarm, under/over current alarm and
under/over voltage alarm.
Current transformer (CT) polarity is important in determining the
correct phase angle different between the current and voltage
hence the power factor. This power factor regulator will
automatically correct the CT polarity internally in the event that the
polarity is reversed.
2.Light indication
The regulator has a 3-digit numeric display and several light
indicators of which can be functionally divided into 3 categories:-
AUTO
MANUAL
CURRENT
THD
SET Cos
C/K
SENSITIVITY
RECON TIME
RATED STEPS
SWITCH PROG
THD LIMIT
ALARM
IND CAP
1 2 3 4 5 6 7
PROGRAM MODE/
SCROLL
8 9 10 11 12 13 14
POWER FACTOR REGULATOR
a
b
c
d
e
f
g
h
i
Power Factor Regulator User's Guide
A BRIEF OVERVIEW
i. Metering functions - power factor,current & THD for current.
ii. Control parameters functions - power factor, C/K, sensitivity,
reconnection time, rated step, switching program & THD Limit.
iii. Alarm messages function.
To access the above functions, press the "MODE/SCROLL" key until
the light indicator is indicating the desired function. The 3-digit
numeric display will show the value of the selected function. If there
are sub-functions on the selected function such as the function for
"rated step" & "alarm messages",press the "UP" or "DOWN" arrow key
to access these sub-functions.
3.Metering function
3.1 Power Factor
Upon powered up, the numeric display indicates the measured
power factor of the system. If the "IND" LED lights up, it mean the
system is having inductive power factor. On the other hand, if the
"CAP" LED lights up, it means the system is having capacitive power
factor.
If the power factor regulator detects a re-generative condition where
the energy flow is reversed, the power factor display will shown a
minus sign in front of the power factor reading.
When the load current is below the operating range and the power
factor cannot be measured accurately, the numeric display will
shows "---".
If the power factor regulator has been previously set to other display
function, it will automatically return to this power factor display
function if no key is pressed for more than 3 minutes.
3.2 Current
This function display mode is indicated by the "CURRENT" light
indicator. The numeric display shows the true-rms value of the
secondary current measured by the 5A current transformer (CT).
Power Factor
Measurement
Current
Measurement
THD
Measurement
Power Factor
Setting
C/K
Setting
Sensitivity
Setting
Reconnection
Time Setting
Rated Steps
Stepping
Switching
Pragram Setting
THD Limit
Setting
Alarm
Step 1
Coefficient
Step 5
Coefficient
Step 4
Coefficient
Step 3
Coefficient
Step 2
Coefficient
Step 6
Coefficient
Step 7
Coefficient
Step 14
Coefficient
Alarm Message 1
Alarm Message 2
Alarm Message 9
Figure 1: Display Structure
Press "MODE/SCROLL" Press "UP" or "DOWN"
1
a - 3-digit numeric display
b - "CAP " and"IND " indicators(CAP = Capacitive, IND = Inductive)
c - Step indicator
d - "UP" button
e - "MODE /SCROLL " button
f - "DOWN " button
g - "PROGRAM " button
h - "AUTO " and"MANUAL " indicators
i - Mode indicator
PHUONGLAI.COM
www.dienhathe.xyz
www.dienhathe.vn
2
1
2
n
2
i
i∑
∝
=n
in = n
th
order harmonic current rms
i1 = Fundamental current rms
Smallest Capacitor in ( kvar )
C/K - Value for 415V
2.5 5 10 15 20 25 30 40 50 60 100 150
0.35
0.29
0.23
0.17
0.23
0.12
0.14
0.07
0.04
0.03
1.16
0.93
0.70
0.46
0.35
0.28
0.23
0.17
0.14
0.12
0.09
0.07
0.05
0.03
0.93
0.70
0.56
0.46
0.35
0.28
0.23
0.17
0.14
0.09
0.07
1.04
0.70
0.52
0.42
0.35
0.26
0.21
0.17
0.13
0.10
0.07
0.05
1.16
0.87
0.70
0.58
0.43
0.35
0.29
0.22
0.17
0.12
0.09
1.04
0.83
0.70
0.52
0.42
0.35
0.26
0.21
0.14
0.10
1.11
0.93
0.70
0.56
0.46
0.35
0.28
0.19
0.14
1.16
0.87
0.70
0.58
0.43
0.35
0.23
0.17
1.04
0.83
0.70
0.52
0.42
0.28
0.21
1.16
0.87
0.70
0.46
0.35
1.04
0.70
0.52
50
60
75
100
150
200
250
300
400
500
600
800
1000
1500
2000
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
: 5
C.T.
Table 1:C/K Table for 415V
Example:
If a 1000/5A CT is used and the display shows "2.50", the primary
measured current is 500A.
3.3 Current Total Harmonic Distortion(THD)
This mode is indicated by a "THD" light indicator.The numeric display
shows the total harmonic distortion of the current as according to
the formula below.
THD =
This measurement is possible only if the total load is at least 10% of
the rated load. If the THD could not be displayed, the 3 -digit
numeric display will show "---".
4.Control Parameters
4.1 Target Power Factor (SET Cos )
This set the targeted power factor required when the system is
under automatic mode. The power factor regulator will switch the
capacitors in or out in order to achieve this set value.
4.2 C/K
This setting is used to set the switching hysteresis and it is calculated
based on the smallest size capacitor used.
With automatic C/K selection(C/K set to AtC), the reactive power
compensation is achieved without C/K setting.The PFR will measure
and evaluate all steps available when necessary and C/K value is then
computed.
The C/K value can also be obtained manually from table 1 or
calculated with the following formula :-
C/K =
where Q = smallest capacitor step (var)
V = nominal primary system voltage (V)
I = primary rating of the current transformer (A)
Example:-
If Q= 15kvar; V= 415V; I= 800A
=> C/K = (2.88 x15000)/ (415 x 800) = 0.13
4.3 Sensitivity
This parameter set the speed of the switching. A larger sensitivity
value will result in slower switching speed and conversely, a smaller
sensitivity value will result in a faster switching speed.This sensitivity
applies to both switching on and switching off of the capacitor.
Example:- If smallest step, Q1st
= 15 kvar; Sensitivity= 60 s/step
Scenario 1:
Reactive power required to achieve set power factor, Qrq
= 15 kvar
Step required to achieve target power factor = Qrq / Q1st
= 15kvar/15kvar
= 1 step
Reaction time = 60/1 = 60 sec
Scenario 2:
Reactive power required to achieve set power factor, Qrq
= 45 kvar
Step required to achieve target power factor = Qrq
/ Q1st
= 45kvar/15kvar
= 3 steps
Reaction time = 60/3 = 20 sec
IV ××
×
3
5Q
IV ×
×
≈
Q2.88
4.4 Reconnection Time
This is the safety lockout time which is used to prohibit the
reconnection of the same capacitor step before it is fully discharged.
This parameter is usually set larger than the discharge time of the
largest capacitor size in used.
4.5 Rated Step
Every step in the power factor regulator is programmable except
Step 1.Step 1 is fixed as "1" and it is the smallest capacitor step used.
All other steps were programmed as multiple of Step 1.
Example:
If the configuration of capacitors used, starting from Step 1, is 10kvar,
10kvar, 20kvar, 20kvar, 30kvar, 30kvar, 60kvar & 60kvar, then the rated
steps are 1,1,2,2,3,3,6,6.
Unless all steps are fully used, the unused steps should be set as
"000". The last step can be programmed as alarm/fan output by
setting the step to "ALA" /"FAn". When the last output is
programmed as alarm output, second last output can be
programmed as fan output.
During the programming of the "Step", the corresponding light
indicator for that selected step will light up. Example, number "1"
light indicator indicates rated step for contact output number 1.
If the automatic C/K mode is enabled, the PFR will carry out the
automatic rated step measurement. Therefore, all steps are not
programmable except alarm/fan output.
4.6 Switching Program
This setting allows the selection of one of the four available
switching algorithms.
a) Manual switching (n-A):
b) Rotational switching (rot):
c) Automatic switching (Aut):
d) Four-quadrant switching (Fqr):
The "Manual" light indicator on the power factor regulator lights up
if the switching program is set to Manual switching (n-A). For
Rotational (rot), Automatic (Aut) and Four-quadrant (Fqr) switching
programs,the "Auto" light indicator on the regulator lights up.
Under normal operating condition, the step indicators indicate the
ON/OFF status of every step. A steady ON light indicates the
particular step is switched in. A blinking light indicates that the
particular step is required to switch in but unable to do so
temporary due to reconnection time lockout.
When this switching program is selected, the capacitor steps are
controlled manually by the "UP" or "DOWN" keys.The "UP" key will
connect the capacitor step and "DOWN" key will disconnect the
capacitor step. Steps are switched in a rotational manner based on
first-in-first-out basis.
This switching program is similar to the manual switching method
and it is based on rotational first-in-first-out sequence. Unlike the
manual switching program, this option will automatically switch in
and out the capacitors according to the targeted power factor,
sensitivity setting and the reconnection time setting.
This automatic switching program uses intelligent switching
sequence. The step switching sequence is not fixed and the
program automatically select the most appropriate steps to switch
in or out in order to achieve shortest reaction time with minimum
number of steps. For equal ageing of the capacitor and contactors,
the program will select the least used step to be switched in if
there are two equally rated steps.
Under this switching program, the power factor regulator
automatically detects the CT polarity during power up. Once this
polarity reference is fixed, any subsequent re-generative power
condition detected will cause all the capacitor steps to be
This switching program is similar to the automatic switching
program (Aut) except that this switching program allows the
power factor regulator to operate correctly under both import
power and export power (re-generative) conditions. Under export
power condition, the active power is fed back to the supply mains
by other energy sources such as solar power etc. If this option is
selected, the installer must ensure that the CT polarity is correctly
wired because the automatic CT polarity correction detection
feature is disabled.
2
Note:(i) During automatic C/k measurement(C/K set to AtC),any step with C/K value lower than
0.03 may not be detected and will be excluded from the controlling process.
(ii) The user may encounter non-optimized regulating during the initial stage before the C/K
value is determined.
0.70
0.58
0.46
0.35
0.23
0.18
0.14
0.12
0.09
0.07
0.06
0.04
0.03
PHUONGLAI.COM
www.dienhathe.xyz
www.dienhathe.vn
Select the required item by stepping through all the items
using "MODE/SCOLL" key.The corresponding indicator of the
selected item will be lit. For "Rated step" setting, the
individual output can be selected via the "UP" or "DOWN"
keys,the step indicator corresponds to the step number.
Press the "PROGRAM" key once, the indicator of the selected
item will blink to indicate that the system is now in
programming mode.
Alarm
Message
thd
Lol
Hil
LoU
HiU
UCo
OCo
ESt
ECt
Description
Current THD exceed set
THD Limit
Current lower than 3%
rated value
Current exceed 110% of
rated value
voltage lower than 85% of
rated value
Voltage exceed 110% of
rated value
All capacitors are
connected and the
power factor lower than
set power factor
All capacitors are
disconnected and the
power factor higher than
set power factor
Auto C/K or rated step
measurement error.
Manual setting required
Automatic CT polarity
detection error
Delay time
Activate Deactivate
5 min 2.5 min
10 s 5 s
2 min 1 min
100 ms 5 s
15 min 7.5 min
15 min 7.5 min
15 min 7.5 min
- -
- -
Action
*5
All steps
disconnected
-
* 5
All steps
disconnected
-
-
-
-
-
*5- Automatic switching of steps are prohibited when this alarm occurred.
Table 3:Alarm table
7.Automatic CT polarity detection
During the power on start-up process, the power factor regulator, if
programmed under Rotational or Automatic switching program,
detects the CT polarity and correct it internally if the CT polarity is
reversed. If the power factor regulator is set for Four-quadrant
switching program,this feature is disabled.
8.Programming Lock
The power factor regulator is equipped with a programming lock to
prevent inadvertent changes to the control parameters. If locked, all
the control parameters can only be viewed at and cannot be
changed without unlocking it first.
To lock or unlock, first ensure that the display is on the power factor
display function mode, then press "PROGRAM" key once followed by
"DOWN" key immediately. Hold the "DOWN" key until the numeric
display flashes "LOC" or "CLr". "LOC" indicates the power factor
regulator is locked and "CLr" indicates the regulator is unlocked.
9.Technical Data
9.1 Auxiliary Supply
Supply voltage : 220VAC / 415VAC
Operating Limits : -15% + 10%
Consumption : 10VA max
Frequency : 50Hz or 60Hz
9.2 Current Input
Rated current ,ln : 5A
Operatings Limits : 0.15A - 6.5A
Rated Frequency : 50Hz or 60Hz
9.3 Relay Output
Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 / PFR80 / PFR120/ PFR140)
Contact arrangment : NO contact type
Rated capacity : 5A 250VAC (Cos ϕ = 1)
Max current for the : 12A continuous
common terminals
9.4 Control Range
Power factor setting : 0.8 inductive - 0.8 capacitive
C/K setting : 0.03 - 1.00
Switching sensitivity : 5 - 600 s/step
Reconnection time : 5 - 240 s
for same step
THD threshold : 0.20 - 3.00 (20% - 300%) / OFF
Switching Program : Automatic / Automatic Rotate / Manual/
Four- quadrant
Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 6 / 8 / 12 /16
9.5 Mechanical
Mounting : Panel mounting
Dimension ( h X w X d) : 144mm X 144mm X 91mm
Approximate weight : 1kg
Control
Paramenter
Target power Factor
C/K
Sensitivity
Reconnection Time
Rated Step*2
:Step 1
Step 2
Step 14
Switching Program
THD Limit
Indication
LED
SET Cos
C/K
SENSITIVITY
RECON TIME
RATED STEPS
SWITCH PROG
THD LIMIT
STEP
LED*1
1
2
14
Setting
Range
0.80 Ind - 0.80 Cap
0.03 - 1.20/AtC
5 - 300 s/step
5 - 240s
001- 002 - 003 - 004 -
005 - 006 - 008 - 012 -
016
000 - disable
ALA*3
- alarm ouput
FAn*4
- fan output
n-A - rot - Aut - Fqr
0.20 - 3.00/ oFF
Default
Factory
Setting
0.98 Ind
AtC
45 s/step
30s
001
Aut
0.50
*1- Under normal operation except for rated step display,the step indicator indicate step
ON/OFF status
*2- Number of steps depend on model
*3- Only last output can be configured as alarm output
*4- Last output can be configured as fan output,or second last output can be configured
as fan output only when last output is configured as alarm output.
Table 2:Parameters setting
Please note that all the steps will be disconnected if the power factor
regulator detects a re-generative condition under Rotational (rot) or
Automatic (Aut) switching program.
4.7 THD Limit
This parameter specifies the limit of total harmonic distortion level
before an alarm is activated (More information on section 6). This
function can be disabled by setting the parameter to "oFF".
4.8 Procedure for Setting the Control Parameters
Step 1:
Step 2:
Step 3:Use the "UP" or "DOWN" keys to select the desired value.
Step 4:
To abort without saving the selected setting, press the
"MODE/SCROLL" key.
4.9 Reset To Factory Default Setting
To reset all programmable parameters to factory default, first power
off the power factor regulator. Press the "UP" & "DOWN" keys
simultaneously while turning on the power and holds it for more
than 5 sec until the display flashes "dEF" for 3 sec. Now the power
factor regulator is restored to factory default setting.
5.Fan Output
When the fan output is selected, the output will be energized with
any capacitor bank switched ON.
6.Alarm
Alarm conditions detected by the power factor regulator are
indicated by the flashing "ALARM" light indicator.The last step of the
regulator, if required, can also be selectively programmed as alarm
contact in addition to the "ALARM" indicator. This additional alarm
contact is normally open and it closes when alarm is activated.
To view the alarm message, press the "MODE/SCROLL" key until the
"ALARM" function is selected. The numeric display will show the
alarm message as according to Table 3 below.If more than one alarm
messages are recorded, press the "UP" or "DOWN" keys to view the
others. The alarm indications are automatically reset to normal once
the alarm conditions are restored.
To save the selected value, press the "PROGRAM" key once,
the indicator stop blinking and the setting is saved.
3
Alarm outputs
LED Relay
Blinks On
Blinks -
Blinks On
Blinks On
Blinks On
Blinks On
Blinks On
Blinks -
Blinks -
PHUONGLAI.COM
www.dienhathe.xyz
www.dienhathe.vn
1
4
2
3
5
8
6
7
9
10
PowerFactorRegulator
K13K14 K1K2
L1N L2L3
MAIN
FUSE
LOAD
P1
P2
VOLTAGE
240VAC
CURRENT
/5A
24
13
16
14
15
17
20
18
19
21
22
23
1
4
2
3
5
8
6
7
9
10
11
12
11
14
12
13
1
4
2
3
5
8
6
7
9
10
PowerFactorRegulator
K13K14 K1K2
L1N L2L3
MAIN
FUSE
LOAD
P1
P2
CURRENT
24
13
16
14
15
17
20
18
19
21
22
23
1
4
2
3
5
8
6
7
9
10
11
12
11
14
12
13
External
resistor
11. Case Dimensions
91mm
77mm144mm
144mm
136mm
136mm
10.Typical Application Diagram
10.1 Diagram 1 -Without external discharge resistors
10.2 Diagram 2 -With external discharge resistor
*Industri Teknologi Mikro Sdn Bhd reserves the right to make changes without futher notice to any products herein to improve reliability,function or design.The figures shown are without obligation.
4
VOLTAGE
415AC
VOLTAGE
240VAC
VOLTAGE
415AC
PHUONGLAI.COM
www.dienhathe.xyz
www.dienhathe.vn

Weitere ähnliche Inhalte

Was ist angesagt?

Level Control of Tank System Using PID Controller-A Review
Level Control of Tank System Using PID Controller-A ReviewLevel Control of Tank System Using PID Controller-A Review
Level Control of Tank System Using PID Controller-A ReviewIJSRD
 
Pid control by Adarsh singh
Pid control  by Adarsh singhPid control  by Adarsh singh
Pid control by Adarsh singhAdarsh Singh
 
Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysismichaeljmack
 
Final Project Paper
Final Project PaperFinal Project Paper
Final Project PaperAhmed Hashem
 
NF Frequency Response Analyzer FRA tecknical guide
NF Frequency Response Analyzer FRA  tecknical guide NF Frequency Response Analyzer FRA  tecknical guide
NF Frequency Response Analyzer FRA tecknical guide NIHON DENKEI SINGAPORE
 
PID Controllers
PID Controllers PID Controllers
PID Controllers Hussain K
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-HoneywellEUR ING Gorka Akarregi
 
Week 14 pid may 24 2016 pe 3032
Week  14 pid  may 24 2016 pe 3032Week  14 pid  may 24 2016 pe 3032
Week 14 pid may 24 2016 pe 3032Charlton Inao
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation ControlMINAL RADE
 
Cascade control system
Cascade control systemCascade control system
Cascade control systemVedant Patel
 
Control configuration in digital control
Control configuration in digital controlControl configuration in digital control
Control configuration in digital controlAshvani Shukla
 

Was ist angesagt? (20)

Level Control of Tank System Using PID Controller-A Review
Level Control of Tank System Using PID Controller-A ReviewLevel Control of Tank System Using PID Controller-A Review
Level Control of Tank System Using PID Controller-A Review
 
Pid control by Adarsh singh
Pid control  by Adarsh singhPid control  by Adarsh singh
Pid control by Adarsh singh
 
Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysis
 
Control actions
Control actionsControl actions
Control actions
 
PID Temperature Controller
PID Temperature ControllerPID Temperature Controller
PID Temperature Controller
 
Final Project Paper
Final Project PaperFinal Project Paper
Final Project Paper
 
Pi dcontroller
Pi dcontrollerPi dcontroller
Pi dcontroller
 
Cs
CsCs
Cs
 
NF Frequency Response Analyzer FRA tecknical guide
NF Frequency Response Analyzer FRA  tecknical guide NF Frequency Response Analyzer FRA  tecknical guide
NF Frequency Response Analyzer FRA tecknical guide
 
PID Controllers
PID Controllers PID Controllers
PID Controllers
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
CONTROL OF ACTIVE POWER & FREQUENCY
CONTROL OF ACTIVE POWER & FREQUENCYCONTROL OF ACTIVE POWER & FREQUENCY
CONTROL OF ACTIVE POWER & FREQUENCY
 
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
 
Week 14 pid may 24 2016 pe 3032
Week  14 pid  may 24 2016 pe 3032Week  14 pid  may 24 2016 pe 3032
Week 14 pid may 24 2016 pe 3032
 
Anees ppt on hcc
Anees ppt on hccAnees ppt on hcc
Anees ppt on hcc
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
Cascade control system
Cascade control systemCascade control system
Cascade control system
 
Design of a discrete PID controller based on identification data for a simsca...
Design of a discrete PID controller based on identification data for a simsca...Design of a discrete PID controller based on identification data for a simsca...
Design of a discrete PID controller based on identification data for a simsca...
 
E1803033337
E1803033337E1803033337
E1803033337
 
Control configuration in digital control
Control configuration in digital controlControl configuration in digital control
Control configuration in digital control
 

Ähnlich wie Catalog mikro mikro pfr140-user_manual

Gsm based transformer fault detection system
Gsm based transformer fault detection systemGsm based transformer fault detection system
Gsm based transformer fault detection systemKabilesh K
 
Development of Digital Controller for DC-DC Buck Converter
Development of Digital Controller for DC-DC Buck ConverterDevelopment of Digital Controller for DC-DC Buck Converter
Development of Digital Controller for DC-DC Buck ConverterIJPEDS-IAES
 
Neo coolcam - smart-plug user guide v2 - Zwave
Neo coolcam  - smart-plug user guide v2 - ZwaveNeo coolcam  - smart-plug user guide v2 - Zwave
Neo coolcam - smart-plug user guide v2 - ZwaveThierry Zoller
 
ANALOG TO DIGITALCONVERTOR FOR BLOOD-GLUCOSE MONITORING
ANALOG TO DIGITALCONVERTOR FOR  BLOOD-GLUCOSE MONITORING  ANALOG TO DIGITALCONVERTOR FOR  BLOOD-GLUCOSE MONITORING
ANALOG TO DIGITALCONVERTOR FOR BLOOD-GLUCOSE MONITORING csijjournal
 
Analog to Digitalconvertor for Blood-Glucose Monitoring
Analog to Digitalconvertor for Blood-Glucose MonitoringAnalog to Digitalconvertor for Blood-Glucose Monitoring
Analog to Digitalconvertor for Blood-Glucose Monitoringcsijjournal
 
18 OBDG04 ECM Summary Tables
18 OBDG04 ECM Summary Tables18 OBDG04 ECM Summary Tables
18 OBDG04 ECM Summary TablesOBD Codex
 
dtsd1352-manual.pdf
dtsd1352-manual.pdfdtsd1352-manual.pdf
dtsd1352-manual.pdfacrelenergy
 
MAX8819 - A Complete Power Solution for Handheld Applications
MAX8819 - A Complete Power Solution for Handheld ApplicationsMAX8819 - A Complete Power Solution for Handheld Applications
MAX8819 - A Complete Power Solution for Handheld ApplicationsPremier Farnell
 
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...IAEME Publication
 
Monitoring and data logging system for a generator
Monitoring and data logging system for a generatorMonitoring and data logging system for a generator
Monitoring and data logging system for a generatorMoon Shahzad
 
Distribution and Load Sharing of Transformer Automatically by using Microcont...
Distribution and Load Sharing of Transformer Automatically by using Microcont...Distribution and Load Sharing of Transformer Automatically by using Microcont...
Distribution and Load Sharing of Transformer Automatically by using Microcont...IRJET Journal
 
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET Journal
 
Speed Control Of DC motor By Using PWM Technique
Speed Control Of DC motor By Using PWM TechniqueSpeed Control Of DC motor By Using PWM Technique
Speed Control Of DC motor By Using PWM TechniqueRITESH D. PATIL
 
Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)anattaembe
 
Bt0064 logic design2
Bt0064 logic design2Bt0064 logic design2
Bt0064 logic design2Techglyphs
 
Fundamentals on Measurement and uncertainty
Fundamentals on Measurement  and  uncertaintyFundamentals on Measurement  and  uncertainty
Fundamentals on Measurement and uncertaintyBerkefede
 
Introduction to control system 2
Introduction to control system 2Introduction to control system 2
Introduction to control system 2turna67
 
KLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONIC
KLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONICKLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONIC
KLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONICdanto .
 

Ähnlich wie Catalog mikro mikro pfr140-user_manual (20)

Gsm based transformer fault detection system
Gsm based transformer fault detection systemGsm based transformer fault detection system
Gsm based transformer fault detection system
 
Development of Digital Controller for DC-DC Buck Converter
Development of Digital Controller for DC-DC Buck ConverterDevelopment of Digital Controller for DC-DC Buck Converter
Development of Digital Controller for DC-DC Buck Converter
 
Neo coolcam - smart-plug user guide v2 - Zwave
Neo coolcam  - smart-plug user guide v2 - ZwaveNeo coolcam  - smart-plug user guide v2 - Zwave
Neo coolcam - smart-plug user guide v2 - Zwave
 
ANALOG TO DIGITALCONVERTOR FOR BLOOD-GLUCOSE MONITORING
ANALOG TO DIGITALCONVERTOR FOR  BLOOD-GLUCOSE MONITORING  ANALOG TO DIGITALCONVERTOR FOR  BLOOD-GLUCOSE MONITORING
ANALOG TO DIGITALCONVERTOR FOR BLOOD-GLUCOSE MONITORING
 
Analog to Digitalconvertor for Blood-Glucose Monitoring
Analog to Digitalconvertor for Blood-Glucose MonitoringAnalog to Digitalconvertor for Blood-Glucose Monitoring
Analog to Digitalconvertor for Blood-Glucose Monitoring
 
18 OBDG04 ECM Summary Tables
18 OBDG04 ECM Summary Tables18 OBDG04 ECM Summary Tables
18 OBDG04 ECM Summary Tables
 
Control
ControlControl
Control
 
dtsd1352-manual.pdf
dtsd1352-manual.pdfdtsd1352-manual.pdf
dtsd1352-manual.pdf
 
MAX8819 - A Complete Power Solution for Handheld Applications
MAX8819 - A Complete Power Solution for Handheld ApplicationsMAX8819 - A Complete Power Solution for Handheld Applications
MAX8819 - A Complete Power Solution for Handheld Applications
 
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
 
Monitoring and data logging system for a generator
Monitoring and data logging system for a generatorMonitoring and data logging system for a generator
Monitoring and data logging system for a generator
 
Distribution and Load Sharing of Transformer Automatically by using Microcont...
Distribution and Load Sharing of Transformer Automatically by using Microcont...Distribution and Load Sharing of Transformer Automatically by using Microcont...
Distribution and Load Sharing of Transformer Automatically by using Microcont...
 
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
 
Speed Control Of DC motor By Using PWM Technique
Speed Control Of DC motor By Using PWM TechniqueSpeed Control Of DC motor By Using PWM Technique
Speed Control Of DC motor By Using PWM Technique
 
Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)
 
Bt0064 logic design2
Bt0064 logic design2Bt0064 logic design2
Bt0064 logic design2
 
Fundamentals on Measurement and uncertainty
Fundamentals on Measurement  and  uncertaintyFundamentals on Measurement  and  uncertainty
Fundamentals on Measurement and uncertainty
 
Introduction to control system 2
Introduction to control system 2Introduction to control system 2
Introduction to control system 2
 
PLC.pdf
PLC.pdfPLC.pdf
PLC.pdf
 
KLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONIC
KLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONICKLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONIC
KLEA( ENERGY ANALYZER ) & ECRAS ( MULTIMETER ) -KLEMSAN ELECTRIC ELECTRONIC
 

Mehr von Dien Ha The

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Dien Ha The
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookDien Ha The
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseDien Ha The
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Dien Ha The
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalogDien Ha The
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbDien Ha The
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Dien Ha The
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsDien Ha The
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter familyDien Ha The
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesDien Ha The
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesDien Ha The
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuDien Ha The
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesDien Ha The
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Dien Ha The
 

Mehr von Dien Ha The (20)

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.com
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library book
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalog
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcb
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new models
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter family
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din series
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 series
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj series
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
 

Kürzlich hochgeladen

KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoordharasingh5698
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfrs7054576148
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 

Kürzlich hochgeladen (20)

KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdf
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 

Catalog mikro mikro pfr140-user_manual

  • 1. 1.General Description The power factor regulator combines comprehensive operation with user-friendly control setting. It uses numerical techniques in computing the phase difference between the fundamentals of current and voltage, thus precise power factor measurement is achieved even in presence of harmonics. The power factor regulator is designed to optimize the control of reactive power compensation. Reactive power compensation is achieved by measuring continuously the reactive power of the system and then compensated by the switching of capacitor banks. The sensitivity setting optimizes the switching speed.With the built- in intelligent automatic switching program, the power factor regulator further improves the switching efficiency by reducing the number of switching operations required to achieve the desired power factor. Usage of the capacitor bank is evenly distributed by the intelligent switching algorithm. This ensures uniform ageing of the capacitors and the contactors used. The four-quadrant operation feature allows the power factor regulator to operate correctly in the case of active power feed back to the mains where regenerative power sources are used. Harmonic current in the system can be harmful to the capacitor bank. This power factor regulator is capable of measuring the total harmonic distortion (THD) in the system and produce an alarm if the THD level is higher than the pre-set value. Other alarms include under/over compensate alarm, under/over current alarm and under/over voltage alarm. Current transformer (CT) polarity is important in determining the correct phase angle different between the current and voltage hence the power factor. This power factor regulator will automatically correct the CT polarity internally in the event that the polarity is reversed. 2.Light indication The regulator has a 3-digit numeric display and several light indicators of which can be functionally divided into 3 categories:- AUTO MANUAL CURRENT THD SET Cos C/K SENSITIVITY RECON TIME RATED STEPS SWITCH PROG THD LIMIT ALARM IND CAP 1 2 3 4 5 6 7 PROGRAM MODE/ SCROLL 8 9 10 11 12 13 14 POWER FACTOR REGULATOR a b c d e f g h i Power Factor Regulator User's Guide A BRIEF OVERVIEW i. Metering functions - power factor,current & THD for current. ii. Control parameters functions - power factor, C/K, sensitivity, reconnection time, rated step, switching program & THD Limit. iii. Alarm messages function. To access the above functions, press the "MODE/SCROLL" key until the light indicator is indicating the desired function. The 3-digit numeric display will show the value of the selected function. If there are sub-functions on the selected function such as the function for "rated step" & "alarm messages",press the "UP" or "DOWN" arrow key to access these sub-functions. 3.Metering function 3.1 Power Factor Upon powered up, the numeric display indicates the measured power factor of the system. If the "IND" LED lights up, it mean the system is having inductive power factor. On the other hand, if the "CAP" LED lights up, it means the system is having capacitive power factor. If the power factor regulator detects a re-generative condition where the energy flow is reversed, the power factor display will shown a minus sign in front of the power factor reading. When the load current is below the operating range and the power factor cannot be measured accurately, the numeric display will shows "---". If the power factor regulator has been previously set to other display function, it will automatically return to this power factor display function if no key is pressed for more than 3 minutes. 3.2 Current This function display mode is indicated by the "CURRENT" light indicator. The numeric display shows the true-rms value of the secondary current measured by the 5A current transformer (CT). Power Factor Measurement Current Measurement THD Measurement Power Factor Setting C/K Setting Sensitivity Setting Reconnection Time Setting Rated Steps Stepping Switching Pragram Setting THD Limit Setting Alarm Step 1 Coefficient Step 5 Coefficient Step 4 Coefficient Step 3 Coefficient Step 2 Coefficient Step 6 Coefficient Step 7 Coefficient Step 14 Coefficient Alarm Message 1 Alarm Message 2 Alarm Message 9 Figure 1: Display Structure Press "MODE/SCROLL" Press "UP" or "DOWN" 1 a - 3-digit numeric display b - "CAP " and"IND " indicators(CAP = Capacitive, IND = Inductive) c - Step indicator d - "UP" button e - "MODE /SCROLL " button f - "DOWN " button g - "PROGRAM " button h - "AUTO " and"MANUAL " indicators i - Mode indicator PHUONGLAI.COM www.dienhathe.xyz www.dienhathe.vn
  • 2. 2 1 2 n 2 i i∑ ∝ =n in = n th order harmonic current rms i1 = Fundamental current rms Smallest Capacitor in ( kvar ) C/K - Value for 415V 2.5 5 10 15 20 25 30 40 50 60 100 150 0.35 0.29 0.23 0.17 0.23 0.12 0.14 0.07 0.04 0.03 1.16 0.93 0.70 0.46 0.35 0.28 0.23 0.17 0.14 0.12 0.09 0.07 0.05 0.03 0.93 0.70 0.56 0.46 0.35 0.28 0.23 0.17 0.14 0.09 0.07 1.04 0.70 0.52 0.42 0.35 0.26 0.21 0.17 0.13 0.10 0.07 0.05 1.16 0.87 0.70 0.58 0.43 0.35 0.29 0.22 0.17 0.12 0.09 1.04 0.83 0.70 0.52 0.42 0.35 0.26 0.21 0.14 0.10 1.11 0.93 0.70 0.56 0.46 0.35 0.28 0.19 0.14 1.16 0.87 0.70 0.58 0.43 0.35 0.23 0.17 1.04 0.83 0.70 0.52 0.42 0.28 0.21 1.16 0.87 0.70 0.46 0.35 1.04 0.70 0.52 50 60 75 100 150 200 250 300 400 500 600 800 1000 1500 2000 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 : 5 C.T. Table 1:C/K Table for 415V Example: If a 1000/5A CT is used and the display shows "2.50", the primary measured current is 500A. 3.3 Current Total Harmonic Distortion(THD) This mode is indicated by a "THD" light indicator.The numeric display shows the total harmonic distortion of the current as according to the formula below. THD = This measurement is possible only if the total load is at least 10% of the rated load. If the THD could not be displayed, the 3 -digit numeric display will show "---". 4.Control Parameters 4.1 Target Power Factor (SET Cos ) This set the targeted power factor required when the system is under automatic mode. The power factor regulator will switch the capacitors in or out in order to achieve this set value. 4.2 C/K This setting is used to set the switching hysteresis and it is calculated based on the smallest size capacitor used. With automatic C/K selection(C/K set to AtC), the reactive power compensation is achieved without C/K setting.The PFR will measure and evaluate all steps available when necessary and C/K value is then computed. The C/K value can also be obtained manually from table 1 or calculated with the following formula :- C/K = where Q = smallest capacitor step (var) V = nominal primary system voltage (V) I = primary rating of the current transformer (A) Example:- If Q= 15kvar; V= 415V; I= 800A => C/K = (2.88 x15000)/ (415 x 800) = 0.13 4.3 Sensitivity This parameter set the speed of the switching. A larger sensitivity value will result in slower switching speed and conversely, a smaller sensitivity value will result in a faster switching speed.This sensitivity applies to both switching on and switching off of the capacitor. Example:- If smallest step, Q1st = 15 kvar; Sensitivity= 60 s/step Scenario 1: Reactive power required to achieve set power factor, Qrq = 15 kvar Step required to achieve target power factor = Qrq / Q1st = 15kvar/15kvar = 1 step Reaction time = 60/1 = 60 sec Scenario 2: Reactive power required to achieve set power factor, Qrq = 45 kvar Step required to achieve target power factor = Qrq / Q1st = 45kvar/15kvar = 3 steps Reaction time = 60/3 = 20 sec IV ×× × 3 5Q IV × × ≈ Q2.88 4.4 Reconnection Time This is the safety lockout time which is used to prohibit the reconnection of the same capacitor step before it is fully discharged. This parameter is usually set larger than the discharge time of the largest capacitor size in used. 4.5 Rated Step Every step in the power factor regulator is programmable except Step 1.Step 1 is fixed as "1" and it is the smallest capacitor step used. All other steps were programmed as multiple of Step 1. Example: If the configuration of capacitors used, starting from Step 1, is 10kvar, 10kvar, 20kvar, 20kvar, 30kvar, 30kvar, 60kvar & 60kvar, then the rated steps are 1,1,2,2,3,3,6,6. Unless all steps are fully used, the unused steps should be set as "000". The last step can be programmed as alarm/fan output by setting the step to "ALA" /"FAn". When the last output is programmed as alarm output, second last output can be programmed as fan output. During the programming of the "Step", the corresponding light indicator for that selected step will light up. Example, number "1" light indicator indicates rated step for contact output number 1. If the automatic C/K mode is enabled, the PFR will carry out the automatic rated step measurement. Therefore, all steps are not programmable except alarm/fan output. 4.6 Switching Program This setting allows the selection of one of the four available switching algorithms. a) Manual switching (n-A): b) Rotational switching (rot): c) Automatic switching (Aut): d) Four-quadrant switching (Fqr): The "Manual" light indicator on the power factor regulator lights up if the switching program is set to Manual switching (n-A). For Rotational (rot), Automatic (Aut) and Four-quadrant (Fqr) switching programs,the "Auto" light indicator on the regulator lights up. Under normal operating condition, the step indicators indicate the ON/OFF status of every step. A steady ON light indicates the particular step is switched in. A blinking light indicates that the particular step is required to switch in but unable to do so temporary due to reconnection time lockout. When this switching program is selected, the capacitor steps are controlled manually by the "UP" or "DOWN" keys.The "UP" key will connect the capacitor step and "DOWN" key will disconnect the capacitor step. Steps are switched in a rotational manner based on first-in-first-out basis. This switching program is similar to the manual switching method and it is based on rotational first-in-first-out sequence. Unlike the manual switching program, this option will automatically switch in and out the capacitors according to the targeted power factor, sensitivity setting and the reconnection time setting. This automatic switching program uses intelligent switching sequence. The step switching sequence is not fixed and the program automatically select the most appropriate steps to switch in or out in order to achieve shortest reaction time with minimum number of steps. For equal ageing of the capacitor and contactors, the program will select the least used step to be switched in if there are two equally rated steps. Under this switching program, the power factor regulator automatically detects the CT polarity during power up. Once this polarity reference is fixed, any subsequent re-generative power condition detected will cause all the capacitor steps to be This switching program is similar to the automatic switching program (Aut) except that this switching program allows the power factor regulator to operate correctly under both import power and export power (re-generative) conditions. Under export power condition, the active power is fed back to the supply mains by other energy sources such as solar power etc. If this option is selected, the installer must ensure that the CT polarity is correctly wired because the automatic CT polarity correction detection feature is disabled. 2 Note:(i) During automatic C/k measurement(C/K set to AtC),any step with C/K value lower than 0.03 may not be detected and will be excluded from the controlling process. (ii) The user may encounter non-optimized regulating during the initial stage before the C/K value is determined. 0.70 0.58 0.46 0.35 0.23 0.18 0.14 0.12 0.09 0.07 0.06 0.04 0.03 PHUONGLAI.COM www.dienhathe.xyz www.dienhathe.vn
  • 3. Select the required item by stepping through all the items using "MODE/SCOLL" key.The corresponding indicator of the selected item will be lit. For "Rated step" setting, the individual output can be selected via the "UP" or "DOWN" keys,the step indicator corresponds to the step number. Press the "PROGRAM" key once, the indicator of the selected item will blink to indicate that the system is now in programming mode. Alarm Message thd Lol Hil LoU HiU UCo OCo ESt ECt Description Current THD exceed set THD Limit Current lower than 3% rated value Current exceed 110% of rated value voltage lower than 85% of rated value Voltage exceed 110% of rated value All capacitors are connected and the power factor lower than set power factor All capacitors are disconnected and the power factor higher than set power factor Auto C/K or rated step measurement error. Manual setting required Automatic CT polarity detection error Delay time Activate Deactivate 5 min 2.5 min 10 s 5 s 2 min 1 min 100 ms 5 s 15 min 7.5 min 15 min 7.5 min 15 min 7.5 min - - - - Action *5 All steps disconnected - * 5 All steps disconnected - - - - - *5- Automatic switching of steps are prohibited when this alarm occurred. Table 3:Alarm table 7.Automatic CT polarity detection During the power on start-up process, the power factor regulator, if programmed under Rotational or Automatic switching program, detects the CT polarity and correct it internally if the CT polarity is reversed. If the power factor regulator is set for Four-quadrant switching program,this feature is disabled. 8.Programming Lock The power factor regulator is equipped with a programming lock to prevent inadvertent changes to the control parameters. If locked, all the control parameters can only be viewed at and cannot be changed without unlocking it first. To lock or unlock, first ensure that the display is on the power factor display function mode, then press "PROGRAM" key once followed by "DOWN" key immediately. Hold the "DOWN" key until the numeric display flashes "LOC" or "CLr". "LOC" indicates the power factor regulator is locked and "CLr" indicates the regulator is unlocked. 9.Technical Data 9.1 Auxiliary Supply Supply voltage : 220VAC / 415VAC Operating Limits : -15% + 10% Consumption : 10VA max Frequency : 50Hz or 60Hz 9.2 Current Input Rated current ,ln : 5A Operatings Limits : 0.15A - 6.5A Rated Frequency : 50Hz or 60Hz 9.3 Relay Output Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 / PFR80 / PFR120/ PFR140) Contact arrangment : NO contact type Rated capacity : 5A 250VAC (Cos ϕ = 1) Max current for the : 12A continuous common terminals 9.4 Control Range Power factor setting : 0.8 inductive - 0.8 capacitive C/K setting : 0.03 - 1.00 Switching sensitivity : 5 - 600 s/step Reconnection time : 5 - 240 s for same step THD threshold : 0.20 - 3.00 (20% - 300%) / OFF Switching Program : Automatic / Automatic Rotate / Manual/ Four- quadrant Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 6 / 8 / 12 /16 9.5 Mechanical Mounting : Panel mounting Dimension ( h X w X d) : 144mm X 144mm X 91mm Approximate weight : 1kg Control Paramenter Target power Factor C/K Sensitivity Reconnection Time Rated Step*2 :Step 1 Step 2 Step 14 Switching Program THD Limit Indication LED SET Cos C/K SENSITIVITY RECON TIME RATED STEPS SWITCH PROG THD LIMIT STEP LED*1 1 2 14 Setting Range 0.80 Ind - 0.80 Cap 0.03 - 1.20/AtC 5 - 300 s/step 5 - 240s 001- 002 - 003 - 004 - 005 - 006 - 008 - 012 - 016 000 - disable ALA*3 - alarm ouput FAn*4 - fan output n-A - rot - Aut - Fqr 0.20 - 3.00/ oFF Default Factory Setting 0.98 Ind AtC 45 s/step 30s 001 Aut 0.50 *1- Under normal operation except for rated step display,the step indicator indicate step ON/OFF status *2- Number of steps depend on model *3- Only last output can be configured as alarm output *4- Last output can be configured as fan output,or second last output can be configured as fan output only when last output is configured as alarm output. Table 2:Parameters setting Please note that all the steps will be disconnected if the power factor regulator detects a re-generative condition under Rotational (rot) or Automatic (Aut) switching program. 4.7 THD Limit This parameter specifies the limit of total harmonic distortion level before an alarm is activated (More information on section 6). This function can be disabled by setting the parameter to "oFF". 4.8 Procedure for Setting the Control Parameters Step 1: Step 2: Step 3:Use the "UP" or "DOWN" keys to select the desired value. Step 4: To abort without saving the selected setting, press the "MODE/SCROLL" key. 4.9 Reset To Factory Default Setting To reset all programmable parameters to factory default, first power off the power factor regulator. Press the "UP" & "DOWN" keys simultaneously while turning on the power and holds it for more than 5 sec until the display flashes "dEF" for 3 sec. Now the power factor regulator is restored to factory default setting. 5.Fan Output When the fan output is selected, the output will be energized with any capacitor bank switched ON. 6.Alarm Alarm conditions detected by the power factor regulator are indicated by the flashing "ALARM" light indicator.The last step of the regulator, if required, can also be selectively programmed as alarm contact in addition to the "ALARM" indicator. This additional alarm contact is normally open and it closes when alarm is activated. To view the alarm message, press the "MODE/SCROLL" key until the "ALARM" function is selected. The numeric display will show the alarm message as according to Table 3 below.If more than one alarm messages are recorded, press the "UP" or "DOWN" keys to view the others. The alarm indications are automatically reset to normal once the alarm conditions are restored. To save the selected value, press the "PROGRAM" key once, the indicator stop blinking and the setting is saved. 3 Alarm outputs LED Relay Blinks On Blinks - Blinks On Blinks On Blinks On Blinks On Blinks On Blinks - Blinks - PHUONGLAI.COM www.dienhathe.xyz www.dienhathe.vn
  • 4. 1 4 2 3 5 8 6 7 9 10 PowerFactorRegulator K13K14 K1K2 L1N L2L3 MAIN FUSE LOAD P1 P2 VOLTAGE 240VAC CURRENT /5A 24 13 16 14 15 17 20 18 19 21 22 23 1 4 2 3 5 8 6 7 9 10 11 12 11 14 12 13 1 4 2 3 5 8 6 7 9 10 PowerFactorRegulator K13K14 K1K2 L1N L2L3 MAIN FUSE LOAD P1 P2 CURRENT 24 13 16 14 15 17 20 18 19 21 22 23 1 4 2 3 5 8 6 7 9 10 11 12 11 14 12 13 External resistor 11. Case Dimensions 91mm 77mm144mm 144mm 136mm 136mm 10.Typical Application Diagram 10.1 Diagram 1 -Without external discharge resistors 10.2 Diagram 2 -With external discharge resistor *Industri Teknologi Mikro Sdn Bhd reserves the right to make changes without futher notice to any products herein to improve reliability,function or design.The figures shown are without obligation. 4 VOLTAGE 415AC VOLTAGE 240VAC VOLTAGE 415AC PHUONGLAI.COM www.dienhathe.xyz www.dienhathe.vn