International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015
ISSN: XXXX-XXXX http://www.ijetjournal.org Page 1
Performance Analysis Of Domestic Refrigerator By Using 662 S-
Silicone Grease Coating On The Evaporator
P.Mallikarjuna1
,Dr. B.Uma Maheswar Gowd 2
1. M.Tech scholar, JNTUA University, Anantapur, A.P
2. Professor of Mechanical engineering , Director Of Admissions , JNTUA, Anantapuramu, A.P,INDIA.
---------------------------------------------**************************************************----------------------------------------
Abstract :-
In present days, Refrigerators are cyclic devices working fluid in refrigerator is called Refrigerant. The performance of refrigerators
is expressed in terms of coefficient of Performance. And the cooling capacity of a refrigerating system is expressed in terms of Tonne of
Refrigeration. Frosting is an unavoidable phenomenon either in domestic refrigerator or in industrial installations. Different methods are
available to remove the frost accumulation like water defrost, electric defrost and hot gas defrost methods. Very few techniques are available
to reduce the frost accumulation in the evaporator. The main objective of the present work is to reduce the quantity of frost by using coating
on the evaporator coil. The coating chosen is to be very smooth, sustain the low temperatures and non wettable . so that there is a chance of
forming of frost layers in the evaporator. By doing so, water drips can roll off easily, the dust and other impurities deposited on the surface can
be easily removed. Commercially available 662 S - SILICONE GREASE coating material is chosen as coating material. A domestic
refrigerator of 165litres capacity working with refrigerant 134a was procured and its pull down characteristics was determined to analyse
proper working condition of the refrigerator without coating on the evaporator walls the load was kept inside the refrigerator and the amount
of frost deposited was measured for various time intervals. The above process was repeated for various loads. Then the evaporator was coated
with 662 S-SILICONE GREASE. The amount of frost deposited on evaporator was measured with the same loads used for without coating for
various time intervals. By comparing the experimental results the amount of frost deposited was found to be reduced when 662 S-SILICONE
GREASE coating was used. Due to reduction of frost accumulation the power consumption also was found to be reduced.
Keywords: Refrigerator, evaporator, R134A, frost accumulation, 662 S-SILICONE GREASE coating, COP, power consumption
.
INTRODUCTION:-
“Refrigeration is the science of providing and maintaining
temperature below that of surrounding (ambient) temperature.
Removal of heat from a body at lower temperature is possible
only with the aid of external agency according to the Second
Law of Thermodynamics.
Condensation occurs on any surface exposed to moist
air whenever the temperature of that surface is below the dew
point[2] .The condensate will freeze and a layer of frost will
form on the surface. This process occurs continually on the
evaporator coil of any refrigerator freezer. In evaporators that
consist of a plate fins and tubes, this layer can grow and
decrease the performance of the system .If the growth
becomes large, it will decrease the amount of air flow over the
coil and thus decrease the heat transfer. To keep the flow at a
constant rate, the power delivered by the fan motor must be
increased. due to this evaporator efficiency will be decreased.
Frosting is transient process with properties changing
over time. At lower temperatures, the condition of the frost
will be light and fluffy. At the freezing point, the frost
becomes hard and dense, and eventually forms into solid ice
as freezing occurs. At temperatures below the freezing point
there is usually less moisture present, thus the formation of
frost is slower than at near freezing point conditions.
A review of the articles that pertain to the accumulation
of frost will be discussed in this section. Although these
surfaces do not directly apply to large warehouse evaporators,
the qualitative relationships for frost growth and frost
properties should still apply. An extensive review of studies
on simple geometries, such as flat plates, cylinders and annuli.
As well as finned tube heat exchangers, was done by Heflin.
Another review on finned tube heat exchangers was done by
the review in this paper will be concerned mainly with studies
done on the effects of frost on heat transfer and on the heat
transfer coefficient during the operation of finned tube heat
exchangers.
LITERATURE SURVEY:-
A. Frosting
There is every possibility of formation of ice on the surface of
the cooling coil if the air is used as source on heat either in
primary circuit or in secondary circuit.because the moisture is
the air will come out in the form off dew when the air is
cooled in the cooling coil below its dew pint temperature. The
dew collected on the surface of the cooling coil is breezed and
RESEARCH ARTICLE OPEN ACCESS
International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015
ISSN: XXXX-XXXX http://www.ijetjournal.org Page 2
deposited . Therefore the moisture from the air will not only
condense but also freeze on the coil surface. Hence for such
applications, frost formation on the evaporator coil is
inevitable. Also it obvious that lower the evaporator
temperature, greater will be frost formation. A finned coil
should never be allowed to frost because the accumulation of
frost between the fins reduces the capacity. The frost on the
evaporator coil also acts as insulator and retards the heat
transfer rate between the air and the cooling coil . If the frost
is allowed to accumulate further even liquid flood back to the
compressor can occur due to a substantial reduction of the
evaporator capacity. And thus the bond between the fin and
the evaporator tube gets lost. Once this happens the evaporator
capacity will come down substantially. It has been found that
25mm frost can have the same insulating effect as 12mm cork.
Hence to maintain coil efficiency, it must be defrosted
periodically.
The frosting is unavoidable process either in
domestic refrigerator or in industrial installation. For the
efficient operation of system, the defrosting of cooling coil is
essential. Period of defrosting depends upon the type of
evaporator method used for defrosting. Bare tube evaporators
used in cold storage plants and breweries are defrosted once or
twice in a month on the other hand.
B. Defrosting
For the reasons above frost formed should be defrosted
periodically for efficient operation of the system. The various
methods used for defrosting the evaporators are as follows
1. Manual defrosting method
2. Pressure control defrosting method
3. Temperature control defrosting method
4. Water defrosting method
5. Reverse cycle defrosting method defrosting
method
6. Simple hot gas defrosting method
7. Automatic hot gas defrosting method
8. Thermo bank defrosting method
9. Electric defrosting method
1) Manual defrosting method :
It is the earliest and the simplest method of
defrosting [1]. In this method either the compressor is stopped
or the refrigerant to the evaporator is closed until the
accumulated frost or ice is melted. At that point, the
compressor is started or the refrigerant valve is re-opened.
This method is still employed on large installations. The major
drawback of this system is that it requires along period for
defrosting.
2) Electric defrosting method :
The electric defrosting method is popularly used for
low temperature evaporators. In this system the heating coils
for heating may be installed within the evaporator[3]. Special
evaporators are required for installing this type of system. In
one of the electric defrosting method, the electric heater is
mounted under the evaporator, drain pan and the drain line. In
its operation the compressor is stopped and the liquid line
closed the refrigerant from evaporator is pumped down. A
thermostatic control returns the refrigerating systems to
normal operation.
The length of the defrost period is determined by the degree of
frost accumulation. The length of defrost period depends
upon the method of defrosting used. A particular temperature
in the evaporator is essential to preserve the perishable
products. it is necessary to provide some means for defrosting
as the frosting comes in the way of maintaining the required
temperature.
Humidity and surface temperature influence the frost growth
more than the air velocity and air temperature.There may be
other factors affection conductivity such as plate temperature
and frost surface temperature. There also disagreement on the
role Reynolds number has on frost growth. Schneider showed
Reynolds number to be unimportant whereas O’Neal and tree
found that frost growth increased with increasing Reynolds
number had negligible.
The evaporator in a refrigerator obviously will have to be at
temperatures lower than 00 c .The freezing point of water
therefore it is subjected to the accumulation of the frost.This
frost acts as an insulation that reduces the heat transfer rate
between the air and the cooling coil. causing the compressor
to operate at lower suction pressure which further reduces the
refrigerating capacity and C.O.P of the system. Therefore
removal of frost or defrosting done by manually putting “off”
the refrigerators. In Present days refrigerators are equipped
with push-button defrost thermostats. A push-button is
provided in the centre of the thermostat knob. Defrosting can
be initiated by simply pressing the push button. This causes a
mechanical leverage in thermostat to break and keeps the
electrical constant of the thermostat opened. until the
evaporator temperature rises above freezing point and
defrosting takes place.
662 S- SILICONE GREASE COATING :-
A. Introduction:
The name “silicone” was given in 1901 by Kipping to
describe new compounds of the brut formula R2SiO [7].
These were rapidly identified as being polymeric and actually
corresponding to polydialkylsiloxanes. Among them, the most
common are polydimethylsiloxanes (PDMS),
trimethylsilyloxy terminated with the structure:
Me
MeMeMe
MeMeMe
MeSi SinoSi )( −− − − −−
−
−
−
−
−
−
o
International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015
ISSN: XXXX-XXXX http://www.ijetjournal.org Page 3
or
323 )( SiMeOSiMeSiOMe n
Where n=0,1,……….
The methyl groups along the chain can be substituted by many
other groups (e.g., phenyl,Vinyl or trifluoropropyl). The
simultaneous presence of “organic” groups attached to an
“Inorganic” backbone hence silicones a combination of
unique properties and allows their use in fields as different as
aerospace (low and high temperature performance),
Electronics (electrical insulation), health care (excellent
biocompatibility) or in theBuilding industries (resistance to
weathering).
Figure 1:Picture of 662 s-silicone grease coating material
B. Properties Of 662 S- Silicone Grease Coating
662 s-silicone grease coating as selected to coat on the
evaporator .The selected 662 s-silicone grease coating consist
of all below properties. 662 s-silicone grease coating consist
of the following properties[8].
1) Low thermal conductivity
2) Low chemical reactivity
3) Low toxicity
4) They have high gas permeability.
5) Smooth surface finish.
6) Thermal stability (constancy of properties over a
wide temperature range of −100 to 250 °C).
7) It resist to low temperature.
8) Non wetting in nature.
9) The ability to repel water and form watertight seals,
although silicones are not hydrophobic.
10) Does not stick to many substrates, but adheres very
well to others, e.g. glass.
11) Does not support microbiological growth.
12) Resistance to oxygen, ozone, and ultraviolet (UV)
light.
13) This property has led to widespread use of silicones
in the construction refrigeration industry and
automotive industry.
EXPERIMENTAL SETUP AND PROCEDURE:-
A. Experimental set up
The experimental setup consists of the following apparatus.
1) Refrigerator
2) Energy meter
3) Measuring jar
4) Temperature indicator
1) Refrigerator details:
5) Gross volume=165litres
6) Storage volume=123 litres
7) Voltage applied=220+10%, AC 1Ф,50 HZ
8) Refrigerant used=R134a
Figure 2: Domestic refrigerator
2) Energy meter details:
Name plate details: 240 V, 50Hz, AC single phase 270 C±20
C.
International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015
ISSN: XXXX-XXXX http://www.ijetjournal.org Page 4
Figure 3: Energy meter
3) Measuring Jar details:
250ml standard Measuring jar is used for measuring frost
quantity.
Figure 4: Measuring Jar
B. Experimental procedure
Figure 5: Experimental set up for 20 litres of water without coating
1. The refrigerator is loaded with 20 litres of water without
any coating and run continuously for 25, 50, 75 hours.
2. Temperature is measured at evaporator; power consumption
and frost quantity are tabulated as shown in the table 1.
Table 1: Temperature drop, power consumed and Frost quantity with a load of
20litres of water in a tray in the refrigerator.
3. The refrigerator is loaded with 20 litres of water with 662
s-silicone grease coating and run continuously for 25, 50, 75
hours.
4. Temperature is measured at evaporator, power consumption
and frost quantity are tabulated is shown in table 2.
Table 2: Temperature drop, power consumed and Frost quantity with a load
of 20 litres of water in a tray in the refrigerator with 662 s-silicone grease
coating.
C. The following photographs show the frost development
with and without coating
International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015
ISSN: XXXX-XXXX http://www.ijetjournal.org Page 5
Figure 6 : Formation of ice on chillier without coating in the experiment with
20litres of water load run for 25 hrs.
Figure 7: Frost covering the ice formed in an the experiment with 20 litres of
water load run 25hrs on a coated evaporator.
Fig ure 8: Formation of ice on chillier without coating in the experiment with
20litres of water load run for 50 hrs.
Figure 9: Frost is covering the ice formed in an the experiment with 20litres
of water load run 50hrs on a coated evaporator.
RESULTS AND DISCUSSIONS:-
A. Experiment 1
Time taken by the refrigerator (using R134a as refrigerant) to
reach a evaporator temperature of 70C is observer to be 45
minutes, when the average room temperature is around 320C.
Energy consumed is 0.05kWh the refrigerator pull down
characteristics are very good.
B. Experiment 2
The evaporator with coating and without coating is run
continuously with varying water quantity and time of 20litres
of water with varying time as 25, 50, 75 hours.
1) From the table 1 it can be seen that the frost collected is
420ml without coating in the experiment with water load
as 20litres over time of 25hours
2) The water vapour sources within the refrigerator badly
affect the performance of the refrigerator by causing frost
formation and further accumulation over time.
3) By applying 662 s- silicone grease coating on both sides
of evaporator the frost reduced from 420ml-382ml with
water load as 20litres over time of 25hours as shown in
table 2.
4) The frost collected is 1750ml without coating in the
experiment with water load as 20litres over time as
50hours as shown in table 1.
5) The water vapour sources within the refrigerator badly
affect the performance of the refrigerator by causing frost
formation and further accumulation over time.
6) By applying 662 s- silicone grease coating on both sides
of evaporator the frost reduced from 1750ml-1360ml with
water load as 20litres over time of 50hours as shown in
table 2.
International Journal of Engineering
ISSN: XXXX-XXXX http://www.ije
7) The frost collected is 2036ml without coating in the
experiment with water load as 20litres over time of
75hours as shown in table 1.
8) The water vapour sources within the refrigerator badly
affect the performance of the refrigerator by causing frost
formation and further accumulation over time.
9) By applying 662 s- silicone grease coating
of evaporator the frost reduced from 2036ml
water load as 20litres over time of 75hours
table 2.
10) From the below figures 10 & 11 as the time and water
load increased the frost is greatly reduced by applying
coating on the evaporator.
The result from the data collected is shown in the foregoing
discussion in the form of plots:
Figure 10 : Graph between Time Vs Frost quantity without and with coating
for 20 Litres of Water from table 1 & 2.
Figure 11: comparision of power consumption drop over time with water
quantity as 20litres with and without evoparator coating from table 1 & 2
CONCLUSIONS:-
In this project work the evaporator of a domestic refrigerator
was coated with 662 S - SILICON E GREASE coating. The
experiments were conducted with 662 s -
0
500
1000
1500
2000
2500
25 50 75
420
1750
2036
382
1360
1850
Frostquantity(ml)
Time(Hrs)
Time Vs Frost quantity
without Coating
with Coating
0
2
4
6
8
10
25 50 75
2.95
5.12
9.25
2.29
4.93
8.2
Power
Consumption(kWh)
Time(Hrs)
Time Vs Power consumption
without coating
with coating
Engineering and Techniques – Volume 1 Issue 1, 2015
http://www.ijetjournal.org
The frost collected is 2036ml without coating in the
20litres over time of
The water vapour sources within the refrigerator badly
affect the performance of the refrigerator by causing frost
formation and further accumulation over time.
silicone grease coating on both sides
of evaporator the frost reduced from 2036ml-1850ml with
water load as 20litres over time of 75hours as shown in
as the time and water
load increased the frost is greatly reduced by applying
The result from the data collected is shown in the foregoing
out and with coating
.
comparision of power consumption drop over time with water
ator coating from table 1 & 2.
evaporator of a domestic refrigerator
SILICON E GREASE coating. The
silicone grease
coating on the evaporator with varying water quantity such
10litres, 20litres and time as 25hours, 50hours,
A. For 20litres of water
1) In 25hrs the frost quantity reduced from 420ml to
382ml.
2) In 50hrs the frost quantity reduced from 1750ml to
1360ml.
3) In 75hrs the frost quantity reduced from 2036ml to
1850ml.
B. For 20litres of water
1) In 25hrs the power consumption reduced from 2.95 to
2.29kWh.
2) In 50hrs the power consumption reduced from 5.12 to
4.93kWh.
3) In 75hrs the power consumption reduced from 9.25 to
8.2kWh.
4) The frost quantity reduction as 9.04% to 9.13% for
20litres of water from the figure 10
5) The power consumption reduction as 22.37% to 21.8%
for 20litres of water from the figure
6) Thus, it is concluded that by using 662 s
coating on evaporator .The frost formation is reduced and
also accumulation is lessened with increase in the water
(load) quantity in the refrigerator.
7) At higher loads the power savings are conside
REFERENCES:-
1 Refrigeration and Air Conditioning by ARORA
AND DOKUNDWAR (Dhanapat Rai & Co).
2 Refrigeration and Air Conditioning by C.P.ARORA
3 Basic Refrigeration and Air Conditioning by
P.N.ANANTHANARAYANA, Tata Mc Grew Hill
Publishing Ltd.
4 Refrigeration and Air Conditioning by
R.S.KHURMI, S.Chand & Company Ltd.
5 Silicone coating by V. N. KHABASHESKU.
6 Hans-Heinrich Moretto, Manfred Schulze, Gebhard
Wagner (2005) "Silicones" in
Encyclopedia of Industrial.
7 Greenwood, Norman N.; Earnshaw, Alan
ISBN 0080379419.
8 Silicone properties by V. N. Khabashesku, Z. A.
Kerzina, K. N. Kudin, O. M. Nefedov (1998).
"Matrix isolation infrared and density
functionaltheoretical studies of organic silanones,
(CH3O)2Si=O and (C6H5)2Si=O".
9 W. Witter and R. Leiper (1979). "A Comparison for
the Effects of Various Forms of Silicon
Contamination on Contact.
Time Vs Frost quantity
without Coating
with Coating
Time Vs Power consumption
without coating
with coating
2015
Page 6
coating on the evaporator with varying water quantity such
ime as 25hours, 50hours, 75hours.
5hrs the frost quantity reduced from 420ml to
In 50hrs the frost quantity reduced from 1750ml to
In 75hrs the frost quantity reduced from 2036ml to
In 25hrs the power consumption reduced from 2.95 to
In 50hrs the power consumption reduced from 5.12 to
consumption reduced from 9.25 to
The frost quantity reduction as 9.04% to 9.13% for
10.
The power consumption reduction as 22.37% to 21.8%
ure 11.
Thus, it is concluded that by using 662 s- silicone grease
he frost formation is reduced and
also accumulation is lessened with increase in the water
At higher loads the power savings are considerable.
Refrigeration and Air Conditioning by ARORA
AND DOKUNDWAR (Dhanapat Rai & Co).
Refrigeration and Air Conditioning by C.P.ARORA
Basic Refrigeration and Air Conditioning by
P.N.ANANTHANARAYANA, Tata Mc Grew Hill
on and Air Conditioning by
R.S.KHURMI, S.Chand & Company Ltd.
V. N. KHABASHESKU.
Heinrich Moretto, Manfred Schulze, Gebhard
Wagner (2005) "Silicones" in Ullmann's
Greenwood, Norman N.; Earnshaw, Alan (1997).
V. N. Khabashesku, Z. A.
Kerzina, K. N. Kudin, O. M. Nefedov (1998).
"Matrix isolation infrared and density
functionaltheoretical studies of organic silanones,
(CH3O)2Si=O and (C6H5)2Si=O".
Leiper (1979). "A Comparison for
the Effects of Various Forms of Silicon

Weitere ähnliche Inhalte

Was ist angesagt?

THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...
THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...
THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...
Sayeed Mohammed
 
Fundamentalsof heatpipesii
Fundamentalsof heatpipesiiFundamentalsof heatpipesii
Fundamentalsof heatpipesii
mammukka
 
STUDY_HongKongPoly_pre-cool(1)
STUDY_HongKongPoly_pre-cool(1)STUDY_HongKongPoly_pre-cool(1)
STUDY_HongKongPoly_pre-cool(1)
Blue Energy Europe
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
theijes
 

Was ist angesagt? (19)

Cooling Tower & cooling water treatment
Cooling Tower & cooling water treatment Cooling Tower & cooling water treatment
Cooling Tower & cooling water treatment
 
THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...
THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...
THERMAL ANALYSIS AND DESIGN OF A NATURAL DRAFT COOLING TOWER OF A 1000 MW NUC...
 
Heat pipes by akash saraswat for devna rani
Heat pipes by akash saraswat for devna raniHeat pipes by akash saraswat for devna rani
Heat pipes by akash saraswat for devna rani
 
Fundamentalsof heatpipesii
Fundamentalsof heatpipesiiFundamentalsof heatpipesii
Fundamentalsof heatpipesii
 
Heat transfer
Heat transferHeat transfer
Heat transfer
 
Cooling Tower and Cooling Water Circuit
Cooling Tower and Cooling Water CircuitCooling Tower and Cooling Water Circuit
Cooling Tower and Cooling Water Circuit
 
Heat Pipe
Heat PipeHeat Pipe
Heat Pipe
 
Heat Pipes (Better One)
Heat Pipes (Better One)Heat Pipes (Better One)
Heat Pipes (Better One)
 
Heat Pipe Seminar Presentation PPT
Heat Pipe Seminar Presentation PPTHeat Pipe Seminar Presentation PPT
Heat Pipe Seminar Presentation PPT
 
STUDY_HongKongPoly_pre-cool(1)
STUDY_HongKongPoly_pre-cool(1)STUDY_HongKongPoly_pre-cool(1)
STUDY_HongKongPoly_pre-cool(1)
 
Heat pipes
Heat pipesHeat pipes
Heat pipes
 
Seminar Report on heat pipes
Seminar Report on heat pipesSeminar Report on heat pipes
Seminar Report on heat pipes
 
HEAT PIPE
HEAT PIPEHEAT PIPE
HEAT PIPE
 
Study of Heat Transfer Process using Heat Pipes
Study of Heat Transfer Process using Heat PipesStudy of Heat Transfer Process using Heat Pipes
Study of Heat Transfer Process using Heat Pipes
 
PPT on HEAT PIPES
PPT on HEAT PIPES PPT on HEAT PIPES
PPT on HEAT PIPES
 
S3 Lec 2 (Condenser) Note
S3 Lec 2 (Condenser) NoteS3 Lec 2 (Condenser) Note
S3 Lec 2 (Condenser) Note
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
Design of condenser
Design of condenserDesign of condenser
Design of condenser
 
Seminar Report on Heat Pipes by Sumit Singh
Seminar Report on Heat Pipes by Sumit SinghSeminar Report on Heat Pipes by Sumit Singh
Seminar Report on Heat Pipes by Sumit Singh
 

Andere mochten auch

[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia
[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia
[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia
IJET - International Journal of Engineering and Techniques
 

Andere mochten auch (19)

[IJET-V1I2P11] Authors :Abdul Latif Saleem, Raja Sagar R, Sachin Datta N S, S...
[IJET-V1I2P11] Authors :Abdul Latif Saleem, Raja Sagar R, Sachin Datta N S, S...[IJET-V1I2P11] Authors :Abdul Latif Saleem, Raja Sagar R, Sachin Datta N S, S...
[IJET-V1I2P11] Authors :Abdul Latif Saleem, Raja Sagar R, Sachin Datta N S, S...
 
[IJET-V1I4P9] Author :Su Hlaing Win
[IJET-V1I4P9] Author :Su Hlaing Win[IJET-V1I4P9] Author :Su Hlaing Win
[IJET-V1I4P9] Author :Su Hlaing Win
 
[IJET-V1I4P2] Authors : Doddappa Kandakur; Ashwini B P
[IJET-V1I4P2] Authors : Doddappa Kandakur; Ashwini B P[IJET-V1I4P2] Authors : Doddappa Kandakur; Ashwini B P
[IJET-V1I4P2] Authors : Doddappa Kandakur; Ashwini B P
 
[IJET-V1I3P21] Authors :Mr. D K Kamat, Ms. Pooja S Ganorkar, Mrs. R A Jain
[IJET-V1I3P21] Authors :Mr. D K Kamat, Ms. Pooja S Ganorkar, Mrs. R A Jain[IJET-V1I3P21] Authors :Mr. D K Kamat, Ms. Pooja S Ganorkar, Mrs. R A Jain
[IJET-V1I3P21] Authors :Mr. D K Kamat, Ms. Pooja S Ganorkar, Mrs. R A Jain
 
[IJET-V1I5P6] Authors:M. Newlin Rajkumar, M. Lavanya
[IJET-V1I5P6] Authors:M. Newlin Rajkumar, M. Lavanya[IJET-V1I5P6] Authors:M. Newlin Rajkumar, M. Lavanya
[IJET-V1I5P6] Authors:M. Newlin Rajkumar, M. Lavanya
 
[IJET-V1I6P6] Authors: Ms. Neeta D. Birajdar, Mr. Madhav N. Dhuppe, Ms. Trupt...
[IJET-V1I6P6] Authors: Ms. Neeta D. Birajdar, Mr. Madhav N. Dhuppe, Ms. Trupt...[IJET-V1I6P6] Authors: Ms. Neeta D. Birajdar, Mr. Madhav N. Dhuppe, Ms. Trupt...
[IJET-V1I6P6] Authors: Ms. Neeta D. Birajdar, Mr. Madhav N. Dhuppe, Ms. Trupt...
 
[IJET-V1I5P5] Authors: T.Jalaja, M.Shailaja
[IJET-V1I5P5] Authors: T.Jalaja, M.Shailaja[IJET-V1I5P5] Authors: T.Jalaja, M.Shailaja
[IJET-V1I5P5] Authors: T.Jalaja, M.Shailaja
 
[IJET-V1I4P11] Authors :Wai Mar Myint, Theingi
[IJET-V1I4P11] Authors :Wai Mar Myint, Theingi[IJET-V1I4P11] Authors :Wai Mar Myint, Theingi
[IJET-V1I4P11] Authors :Wai Mar Myint, Theingi
 
[IJET-V1I4P16] Authors : Mr. Pankaj Shende , Syed Tanveer , A. Nagesh
[IJET-V1I4P16] Authors : Mr. Pankaj Shende , Syed Tanveer , A. Nagesh [IJET-V1I4P16] Authors : Mr. Pankaj Shende , Syed Tanveer , A. Nagesh
[IJET-V1I4P16] Authors : Mr. Pankaj Shende , Syed Tanveer , A. Nagesh
 
[IJET-V1I5P11]Authors: Medhavi Malik, Rupika Dureja
[IJET-V1I5P11]Authors: Medhavi Malik, Rupika Dureja[IJET-V1I5P11]Authors: Medhavi Malik, Rupika Dureja
[IJET-V1I5P11]Authors: Medhavi Malik, Rupika Dureja
 
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan [IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
 
[IJET-V1I6P4] Authors: Bhatia Shradha, Doshi Jaina,Jadhav Preeti, Shah Nikita
[IJET-V1I6P4] Authors: Bhatia Shradha, Doshi Jaina,Jadhav Preeti, Shah Nikita[IJET-V1I6P4] Authors: Bhatia Shradha, Doshi Jaina,Jadhav Preeti, Shah Nikita
[IJET-V1I6P4] Authors: Bhatia Shradha, Doshi Jaina,Jadhav Preeti, Shah Nikita
 
[IJET-V1I5P12] Authors: Omkar Dhorge, ShantanuShamraj ,Sumedh Melkunde, Rohit...
[IJET-V1I5P12] Authors: Omkar Dhorge, ShantanuShamraj ,Sumedh Melkunde, Rohit...[IJET-V1I5P12] Authors: Omkar Dhorge, ShantanuShamraj ,Sumedh Melkunde, Rohit...
[IJET-V1I5P12] Authors: Omkar Dhorge, ShantanuShamraj ,Sumedh Melkunde, Rohit...
 
[IJET-V1I4P17] Authors: Fahimuddin. Shaik, Dr.Anil Kumar Sharma, Dr.Syed.Must...
[IJET-V1I4P17] Authors: Fahimuddin. Shaik, Dr.Anil Kumar Sharma, Dr.Syed.Must...[IJET-V1I4P17] Authors: Fahimuddin. Shaik, Dr.Anil Kumar Sharma, Dr.Syed.Must...
[IJET-V1I4P17] Authors: Fahimuddin. Shaik, Dr.Anil Kumar Sharma, Dr.Syed.Must...
 
[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia
[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia
[IJET-V1I6P11] Authors: A.Stenila, M. Kavitha, S.Alonshia
 
[IJET-V1I3P8] Authors :Mrs. Latha A.P.,Pratik Agarwal, Rishabh Rajgarhia,Shas...
[IJET-V1I3P8] Authors :Mrs. Latha A.P.,Pratik Agarwal, Rishabh Rajgarhia,Shas...[IJET-V1I3P8] Authors :Mrs. Latha A.P.,Pratik Agarwal, Rishabh Rajgarhia,Shas...
[IJET-V1I3P8] Authors :Mrs. Latha A.P.,Pratik Agarwal, Rishabh Rajgarhia,Shas...
 
[IJET-V1I6P5] Authors: Tawde Priyanka, Londhe Archana, Nazirkar Sandhya, Khat...
[IJET-V1I6P5] Authors: Tawde Priyanka, Londhe Archana, Nazirkar Sandhya, Khat...[IJET-V1I6P5] Authors: Tawde Priyanka, Londhe Archana, Nazirkar Sandhya, Khat...
[IJET-V1I6P5] Authors: Tawde Priyanka, Londhe Archana, Nazirkar Sandhya, Khat...
 
[IJET-V1I3P7] Authors : Prateek Joshi, Mohammad UmairZaki
[IJET-V1I3P7] Authors : Prateek Joshi, Mohammad UmairZaki[IJET-V1I3P7] Authors : Prateek Joshi, Mohammad UmairZaki
[IJET-V1I3P7] Authors : Prateek Joshi, Mohammad UmairZaki
 
[IJET-V1I3P14] Authors :Kruthika R.
[IJET-V1I3P14] Authors :Kruthika R.[IJET-V1I3P14] Authors :Kruthika R.
[IJET-V1I3P14] Authors :Kruthika R.
 

Ähnlich wie Ijet v1 i1p6

H0502 01 3747
H0502 01 3747H0502 01 3747
H0502 01 3747
IJMER
 
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
IJMER
 
Refrigeration PPT to present.ppt
Refrigeration PPT to present.pptRefrigeration PPT to present.ppt
Refrigeration PPT to present.ppt
BodhiSeal1
 

Ähnlich wie Ijet v1 i1p6 (20)

Design of Ice Manufacturing Plant 2000 lb
Design of Ice Manufacturing Plant 2000 lbDesign of Ice Manufacturing Plant 2000 lb
Design of Ice Manufacturing Plant 2000 lb
 
Mechanism of refrigerator asrafi tonmoy-diu
Mechanism of refrigerator  asrafi tonmoy-diuMechanism of refrigerator  asrafi tonmoy-diu
Mechanism of refrigerator asrafi tonmoy-diu
 
Methods of Refrigeration.pdf
Methods of Refrigeration.pdfMethods of Refrigeration.pdf
Methods of Refrigeration.pdf
 
ref.pdf
ref.pdfref.pdf
ref.pdf
 
DOMESTIC REFRIGERATION USING LPG CYLINDER
DOMESTIC REFRIGERATION USING LPG CYLINDERDOMESTIC REFRIGERATION USING LPG CYLINDER
DOMESTIC REFRIGERATION USING LPG CYLINDER
 
lpg content
lpg contentlpg content
lpg content
 
R&ac lecture 22
R&ac lecture 22R&ac lecture 22
R&ac lecture 22
 
Condensation
CondensationCondensation
Condensation
 
IRJET- Review on Comparative Analysis of COP of Vapour Compression Refrig...
IRJET-  	  Review on Comparative Analysis of COP of Vapour Compression Refrig...IRJET-  	  Review on Comparative Analysis of COP of Vapour Compression Refrig...
IRJET- Review on Comparative Analysis of COP of Vapour Compression Refrig...
 
2 (1)
2 (1)2 (1)
2 (1)
 
Experimental Investigation & Performance of VCRS system by using Air cooled C...
Experimental Investigation & Performance of VCRS system by using Air cooled C...Experimental Investigation & Performance of VCRS system by using Air cooled C...
Experimental Investigation & Performance of VCRS system by using Air cooled C...
 
Kapes project
Kapes projectKapes project
Kapes project
 
Green refrigeration
Green refrigerationGreen refrigeration
Green refrigeration
 
Itnesh kumar freeze drying- report
Itnesh kumar   freeze drying- reportItnesh kumar   freeze drying- report
Itnesh kumar freeze drying- report
 
H0502 01 3747
H0502 01 3747H0502 01 3747
H0502 01 3747
 
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
 
Refrigeration PPT to present.ppt
Refrigeration PPT to present.pptRefrigeration PPT to present.ppt
Refrigeration PPT to present.ppt
 
refrigeration in hvac
refrigeration in hvacrefrigeration in hvac
refrigeration in hvac
 
Solar based industrial refrigeration system
Solar based industrial refrigeration systemSolar based industrial refrigeration system
Solar based industrial refrigeration system
 
Modification of Generator In Electrolux Refrigerator
Modification of Generator In Electrolux RefrigeratorModification of Generator In Electrolux Refrigerator
Modification of Generator In Electrolux Refrigerator
 

Mehr von IJET - International Journal of Engineering and Techniques

healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...
IJET - International Journal of Engineering and Techniques
 
IJET-V3I2P23
IJET-V3I2P23IJET-V3I2P23
IJET-V3I2P21
IJET-V3I2P21IJET-V3I2P21

Mehr von IJET - International Journal of Engineering and Techniques (20)

healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...
 
verifiable and multi-keyword searchable attribute-based encryption scheme for...
verifiable and multi-keyword searchable attribute-based encryption scheme for...verifiable and multi-keyword searchable attribute-based encryption scheme for...
verifiable and multi-keyword searchable attribute-based encryption scheme for...
 
Ijet v5 i6p18
Ijet v5 i6p18Ijet v5 i6p18
Ijet v5 i6p18
 
Ijet v5 i6p17
Ijet v5 i6p17Ijet v5 i6p17
Ijet v5 i6p17
 
Ijet v5 i6p16
Ijet v5 i6p16Ijet v5 i6p16
Ijet v5 i6p16
 
Ijet v5 i6p15
Ijet v5 i6p15Ijet v5 i6p15
Ijet v5 i6p15
 
Ijet v5 i6p14
Ijet v5 i6p14Ijet v5 i6p14
Ijet v5 i6p14
 
Ijet v5 i6p13
Ijet v5 i6p13Ijet v5 i6p13
Ijet v5 i6p13
 
Ijet v5 i6p12
Ijet v5 i6p12Ijet v5 i6p12
Ijet v5 i6p12
 
Ijet v5 i6p11
Ijet v5 i6p11Ijet v5 i6p11
Ijet v5 i6p11
 
Ijet v5 i6p10
Ijet v5 i6p10Ijet v5 i6p10
Ijet v5 i6p10
 
Ijet v5 i6p2
Ijet v5 i6p2Ijet v5 i6p2
Ijet v5 i6p2
 
IJET-V3I2P24
IJET-V3I2P24IJET-V3I2P24
IJET-V3I2P24
 
IJET-V3I2P23
IJET-V3I2P23IJET-V3I2P23
IJET-V3I2P23
 
IJET-V3I2P22
IJET-V3I2P22IJET-V3I2P22
IJET-V3I2P22
 
IJET-V3I2P21
IJET-V3I2P21IJET-V3I2P21
IJET-V3I2P21
 
IJET-V3I2P20
IJET-V3I2P20IJET-V3I2P20
IJET-V3I2P20
 
IJET-V3I2P19
IJET-V3I2P19IJET-V3I2P19
IJET-V3I2P19
 
IJET-V3I2P18
IJET-V3I2P18IJET-V3I2P18
IJET-V3I2P18
 
IJET-V3I2P17
IJET-V3I2P17IJET-V3I2P17
IJET-V3I2P17
 

Ijet v1 i1p6

  • 1. International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015 ISSN: XXXX-XXXX http://www.ijetjournal.org Page 1 Performance Analysis Of Domestic Refrigerator By Using 662 S- Silicone Grease Coating On The Evaporator P.Mallikarjuna1 ,Dr. B.Uma Maheswar Gowd 2 1. M.Tech scholar, JNTUA University, Anantapur, A.P 2. Professor of Mechanical engineering , Director Of Admissions , JNTUA, Anantapuramu, A.P,INDIA. ---------------------------------------------**************************************************---------------------------------------- Abstract :- In present days, Refrigerators are cyclic devices working fluid in refrigerator is called Refrigerant. The performance of refrigerators is expressed in terms of coefficient of Performance. And the cooling capacity of a refrigerating system is expressed in terms of Tonne of Refrigeration. Frosting is an unavoidable phenomenon either in domestic refrigerator or in industrial installations. Different methods are available to remove the frost accumulation like water defrost, electric defrost and hot gas defrost methods. Very few techniques are available to reduce the frost accumulation in the evaporator. The main objective of the present work is to reduce the quantity of frost by using coating on the evaporator coil. The coating chosen is to be very smooth, sustain the low temperatures and non wettable . so that there is a chance of forming of frost layers in the evaporator. By doing so, water drips can roll off easily, the dust and other impurities deposited on the surface can be easily removed. Commercially available 662 S - SILICONE GREASE coating material is chosen as coating material. A domestic refrigerator of 165litres capacity working with refrigerant 134a was procured and its pull down characteristics was determined to analyse proper working condition of the refrigerator without coating on the evaporator walls the load was kept inside the refrigerator and the amount of frost deposited was measured for various time intervals. The above process was repeated for various loads. Then the evaporator was coated with 662 S-SILICONE GREASE. The amount of frost deposited on evaporator was measured with the same loads used for without coating for various time intervals. By comparing the experimental results the amount of frost deposited was found to be reduced when 662 S-SILICONE GREASE coating was used. Due to reduction of frost accumulation the power consumption also was found to be reduced. Keywords: Refrigerator, evaporator, R134A, frost accumulation, 662 S-SILICONE GREASE coating, COP, power consumption . INTRODUCTION:- “Refrigeration is the science of providing and maintaining temperature below that of surrounding (ambient) temperature. Removal of heat from a body at lower temperature is possible only with the aid of external agency according to the Second Law of Thermodynamics. Condensation occurs on any surface exposed to moist air whenever the temperature of that surface is below the dew point[2] .The condensate will freeze and a layer of frost will form on the surface. This process occurs continually on the evaporator coil of any refrigerator freezer. In evaporators that consist of a plate fins and tubes, this layer can grow and decrease the performance of the system .If the growth becomes large, it will decrease the amount of air flow over the coil and thus decrease the heat transfer. To keep the flow at a constant rate, the power delivered by the fan motor must be increased. due to this evaporator efficiency will be decreased. Frosting is transient process with properties changing over time. At lower temperatures, the condition of the frost will be light and fluffy. At the freezing point, the frost becomes hard and dense, and eventually forms into solid ice as freezing occurs. At temperatures below the freezing point there is usually less moisture present, thus the formation of frost is slower than at near freezing point conditions. A review of the articles that pertain to the accumulation of frost will be discussed in this section. Although these surfaces do not directly apply to large warehouse evaporators, the qualitative relationships for frost growth and frost properties should still apply. An extensive review of studies on simple geometries, such as flat plates, cylinders and annuli. As well as finned tube heat exchangers, was done by Heflin. Another review on finned tube heat exchangers was done by the review in this paper will be concerned mainly with studies done on the effects of frost on heat transfer and on the heat transfer coefficient during the operation of finned tube heat exchangers. LITERATURE SURVEY:- A. Frosting There is every possibility of formation of ice on the surface of the cooling coil if the air is used as source on heat either in primary circuit or in secondary circuit.because the moisture is the air will come out in the form off dew when the air is cooled in the cooling coil below its dew pint temperature. The dew collected on the surface of the cooling coil is breezed and RESEARCH ARTICLE OPEN ACCESS
  • 2. International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015 ISSN: XXXX-XXXX http://www.ijetjournal.org Page 2 deposited . Therefore the moisture from the air will not only condense but also freeze on the coil surface. Hence for such applications, frost formation on the evaporator coil is inevitable. Also it obvious that lower the evaporator temperature, greater will be frost formation. A finned coil should never be allowed to frost because the accumulation of frost between the fins reduces the capacity. The frost on the evaporator coil also acts as insulator and retards the heat transfer rate between the air and the cooling coil . If the frost is allowed to accumulate further even liquid flood back to the compressor can occur due to a substantial reduction of the evaporator capacity. And thus the bond between the fin and the evaporator tube gets lost. Once this happens the evaporator capacity will come down substantially. It has been found that 25mm frost can have the same insulating effect as 12mm cork. Hence to maintain coil efficiency, it must be defrosted periodically. The frosting is unavoidable process either in domestic refrigerator or in industrial installation. For the efficient operation of system, the defrosting of cooling coil is essential. Period of defrosting depends upon the type of evaporator method used for defrosting. Bare tube evaporators used in cold storage plants and breweries are defrosted once or twice in a month on the other hand. B. Defrosting For the reasons above frost formed should be defrosted periodically for efficient operation of the system. The various methods used for defrosting the evaporators are as follows 1. Manual defrosting method 2. Pressure control defrosting method 3. Temperature control defrosting method 4. Water defrosting method 5. Reverse cycle defrosting method defrosting method 6. Simple hot gas defrosting method 7. Automatic hot gas defrosting method 8. Thermo bank defrosting method 9. Electric defrosting method 1) Manual defrosting method : It is the earliest and the simplest method of defrosting [1]. In this method either the compressor is stopped or the refrigerant to the evaporator is closed until the accumulated frost or ice is melted. At that point, the compressor is started or the refrigerant valve is re-opened. This method is still employed on large installations. The major drawback of this system is that it requires along period for defrosting. 2) Electric defrosting method : The electric defrosting method is popularly used for low temperature evaporators. In this system the heating coils for heating may be installed within the evaporator[3]. Special evaporators are required for installing this type of system. In one of the electric defrosting method, the electric heater is mounted under the evaporator, drain pan and the drain line. In its operation the compressor is stopped and the liquid line closed the refrigerant from evaporator is pumped down. A thermostatic control returns the refrigerating systems to normal operation. The length of the defrost period is determined by the degree of frost accumulation. The length of defrost period depends upon the method of defrosting used. A particular temperature in the evaporator is essential to preserve the perishable products. it is necessary to provide some means for defrosting as the frosting comes in the way of maintaining the required temperature. Humidity and surface temperature influence the frost growth more than the air velocity and air temperature.There may be other factors affection conductivity such as plate temperature and frost surface temperature. There also disagreement on the role Reynolds number has on frost growth. Schneider showed Reynolds number to be unimportant whereas O’Neal and tree found that frost growth increased with increasing Reynolds number had negligible. The evaporator in a refrigerator obviously will have to be at temperatures lower than 00 c .The freezing point of water therefore it is subjected to the accumulation of the frost.This frost acts as an insulation that reduces the heat transfer rate between the air and the cooling coil. causing the compressor to operate at lower suction pressure which further reduces the refrigerating capacity and C.O.P of the system. Therefore removal of frost or defrosting done by manually putting “off” the refrigerators. In Present days refrigerators are equipped with push-button defrost thermostats. A push-button is provided in the centre of the thermostat knob. Defrosting can be initiated by simply pressing the push button. This causes a mechanical leverage in thermostat to break and keeps the electrical constant of the thermostat opened. until the evaporator temperature rises above freezing point and defrosting takes place. 662 S- SILICONE GREASE COATING :- A. Introduction: The name “silicone” was given in 1901 by Kipping to describe new compounds of the brut formula R2SiO [7]. These were rapidly identified as being polymeric and actually corresponding to polydialkylsiloxanes. Among them, the most common are polydimethylsiloxanes (PDMS), trimethylsilyloxy terminated with the structure: Me MeMeMe MeMeMe MeSi SinoSi )( −− − − −− − − − − − − o
  • 3. International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015 ISSN: XXXX-XXXX http://www.ijetjournal.org Page 3 or 323 )( SiMeOSiMeSiOMe n Where n=0,1,………. The methyl groups along the chain can be substituted by many other groups (e.g., phenyl,Vinyl or trifluoropropyl). The simultaneous presence of “organic” groups attached to an “Inorganic” backbone hence silicones a combination of unique properties and allows their use in fields as different as aerospace (low and high temperature performance), Electronics (electrical insulation), health care (excellent biocompatibility) or in theBuilding industries (resistance to weathering). Figure 1:Picture of 662 s-silicone grease coating material B. Properties Of 662 S- Silicone Grease Coating 662 s-silicone grease coating as selected to coat on the evaporator .The selected 662 s-silicone grease coating consist of all below properties. 662 s-silicone grease coating consist of the following properties[8]. 1) Low thermal conductivity 2) Low chemical reactivity 3) Low toxicity 4) They have high gas permeability. 5) Smooth surface finish. 6) Thermal stability (constancy of properties over a wide temperature range of −100 to 250 °C). 7) It resist to low temperature. 8) Non wetting in nature. 9) The ability to repel water and form watertight seals, although silicones are not hydrophobic. 10) Does not stick to many substrates, but adheres very well to others, e.g. glass. 11) Does not support microbiological growth. 12) Resistance to oxygen, ozone, and ultraviolet (UV) light. 13) This property has led to widespread use of silicones in the construction refrigeration industry and automotive industry. EXPERIMENTAL SETUP AND PROCEDURE:- A. Experimental set up The experimental setup consists of the following apparatus. 1) Refrigerator 2) Energy meter 3) Measuring jar 4) Temperature indicator 1) Refrigerator details: 5) Gross volume=165litres 6) Storage volume=123 litres 7) Voltage applied=220+10%, AC 1Ф,50 HZ 8) Refrigerant used=R134a Figure 2: Domestic refrigerator 2) Energy meter details: Name plate details: 240 V, 50Hz, AC single phase 270 C±20 C.
  • 4. International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015 ISSN: XXXX-XXXX http://www.ijetjournal.org Page 4 Figure 3: Energy meter 3) Measuring Jar details: 250ml standard Measuring jar is used for measuring frost quantity. Figure 4: Measuring Jar B. Experimental procedure Figure 5: Experimental set up for 20 litres of water without coating 1. The refrigerator is loaded with 20 litres of water without any coating and run continuously for 25, 50, 75 hours. 2. Temperature is measured at evaporator; power consumption and frost quantity are tabulated as shown in the table 1. Table 1: Temperature drop, power consumed and Frost quantity with a load of 20litres of water in a tray in the refrigerator. 3. The refrigerator is loaded with 20 litres of water with 662 s-silicone grease coating and run continuously for 25, 50, 75 hours. 4. Temperature is measured at evaporator, power consumption and frost quantity are tabulated is shown in table 2. Table 2: Temperature drop, power consumed and Frost quantity with a load of 20 litres of water in a tray in the refrigerator with 662 s-silicone grease coating. C. The following photographs show the frost development with and without coating
  • 5. International Journal of Engineering and Techniques – Volume 1 Issue 1, 2015 ISSN: XXXX-XXXX http://www.ijetjournal.org Page 5 Figure 6 : Formation of ice on chillier without coating in the experiment with 20litres of water load run for 25 hrs. Figure 7: Frost covering the ice formed in an the experiment with 20 litres of water load run 25hrs on a coated evaporator. Fig ure 8: Formation of ice on chillier without coating in the experiment with 20litres of water load run for 50 hrs. Figure 9: Frost is covering the ice formed in an the experiment with 20litres of water load run 50hrs on a coated evaporator. RESULTS AND DISCUSSIONS:- A. Experiment 1 Time taken by the refrigerator (using R134a as refrigerant) to reach a evaporator temperature of 70C is observer to be 45 minutes, when the average room temperature is around 320C. Energy consumed is 0.05kWh the refrigerator pull down characteristics are very good. B. Experiment 2 The evaporator with coating and without coating is run continuously with varying water quantity and time of 20litres of water with varying time as 25, 50, 75 hours. 1) From the table 1 it can be seen that the frost collected is 420ml without coating in the experiment with water load as 20litres over time of 25hours 2) The water vapour sources within the refrigerator badly affect the performance of the refrigerator by causing frost formation and further accumulation over time. 3) By applying 662 s- silicone grease coating on both sides of evaporator the frost reduced from 420ml-382ml with water load as 20litres over time of 25hours as shown in table 2. 4) The frost collected is 1750ml without coating in the experiment with water load as 20litres over time as 50hours as shown in table 1. 5) The water vapour sources within the refrigerator badly affect the performance of the refrigerator by causing frost formation and further accumulation over time. 6) By applying 662 s- silicone grease coating on both sides of evaporator the frost reduced from 1750ml-1360ml with water load as 20litres over time of 50hours as shown in table 2.
  • 6. International Journal of Engineering ISSN: XXXX-XXXX http://www.ije 7) The frost collected is 2036ml without coating in the experiment with water load as 20litres over time of 75hours as shown in table 1. 8) The water vapour sources within the refrigerator badly affect the performance of the refrigerator by causing frost formation and further accumulation over time. 9) By applying 662 s- silicone grease coating of evaporator the frost reduced from 2036ml water load as 20litres over time of 75hours table 2. 10) From the below figures 10 & 11 as the time and water load increased the frost is greatly reduced by applying coating on the evaporator. The result from the data collected is shown in the foregoing discussion in the form of plots: Figure 10 : Graph between Time Vs Frost quantity without and with coating for 20 Litres of Water from table 1 & 2. Figure 11: comparision of power consumption drop over time with water quantity as 20litres with and without evoparator coating from table 1 & 2 CONCLUSIONS:- In this project work the evaporator of a domestic refrigerator was coated with 662 S - SILICON E GREASE coating. The experiments were conducted with 662 s - 0 500 1000 1500 2000 2500 25 50 75 420 1750 2036 382 1360 1850 Frostquantity(ml) Time(Hrs) Time Vs Frost quantity without Coating with Coating 0 2 4 6 8 10 25 50 75 2.95 5.12 9.25 2.29 4.93 8.2 Power Consumption(kWh) Time(Hrs) Time Vs Power consumption without coating with coating Engineering and Techniques – Volume 1 Issue 1, 2015 http://www.ijetjournal.org The frost collected is 2036ml without coating in the 20litres over time of The water vapour sources within the refrigerator badly affect the performance of the refrigerator by causing frost formation and further accumulation over time. silicone grease coating on both sides of evaporator the frost reduced from 2036ml-1850ml with water load as 20litres over time of 75hours as shown in as the time and water load increased the frost is greatly reduced by applying The result from the data collected is shown in the foregoing out and with coating . comparision of power consumption drop over time with water ator coating from table 1 & 2. evaporator of a domestic refrigerator SILICON E GREASE coating. The silicone grease coating on the evaporator with varying water quantity such 10litres, 20litres and time as 25hours, 50hours, A. For 20litres of water 1) In 25hrs the frost quantity reduced from 420ml to 382ml. 2) In 50hrs the frost quantity reduced from 1750ml to 1360ml. 3) In 75hrs the frost quantity reduced from 2036ml to 1850ml. B. For 20litres of water 1) In 25hrs the power consumption reduced from 2.95 to 2.29kWh. 2) In 50hrs the power consumption reduced from 5.12 to 4.93kWh. 3) In 75hrs the power consumption reduced from 9.25 to 8.2kWh. 4) The frost quantity reduction as 9.04% to 9.13% for 20litres of water from the figure 10 5) The power consumption reduction as 22.37% to 21.8% for 20litres of water from the figure 6) Thus, it is concluded that by using 662 s coating on evaporator .The frost formation is reduced and also accumulation is lessened with increase in the water (load) quantity in the refrigerator. 7) At higher loads the power savings are conside REFERENCES:- 1 Refrigeration and Air Conditioning by ARORA AND DOKUNDWAR (Dhanapat Rai & Co). 2 Refrigeration and Air Conditioning by C.P.ARORA 3 Basic Refrigeration and Air Conditioning by P.N.ANANTHANARAYANA, Tata Mc Grew Hill Publishing Ltd. 4 Refrigeration and Air Conditioning by R.S.KHURMI, S.Chand & Company Ltd. 5 Silicone coating by V. N. KHABASHESKU. 6 Hans-Heinrich Moretto, Manfred Schulze, Gebhard Wagner (2005) "Silicones" in Encyclopedia of Industrial. 7 Greenwood, Norman N.; Earnshaw, Alan ISBN 0080379419. 8 Silicone properties by V. N. Khabashesku, Z. A. Kerzina, K. N. Kudin, O. M. Nefedov (1998). "Matrix isolation infrared and density functionaltheoretical studies of organic silanones, (CH3O)2Si=O and (C6H5)2Si=O". 9 W. Witter and R. Leiper (1979). "A Comparison for the Effects of Various Forms of Silicon Contamination on Contact. Time Vs Frost quantity without Coating with Coating Time Vs Power consumption without coating with coating 2015 Page 6 coating on the evaporator with varying water quantity such ime as 25hours, 50hours, 75hours. 5hrs the frost quantity reduced from 420ml to In 50hrs the frost quantity reduced from 1750ml to In 75hrs the frost quantity reduced from 2036ml to In 25hrs the power consumption reduced from 2.95 to In 50hrs the power consumption reduced from 5.12 to consumption reduced from 9.25 to The frost quantity reduction as 9.04% to 9.13% for 10. The power consumption reduction as 22.37% to 21.8% ure 11. Thus, it is concluded that by using 662 s- silicone grease he frost formation is reduced and also accumulation is lessened with increase in the water At higher loads the power savings are considerable. Refrigeration and Air Conditioning by ARORA AND DOKUNDWAR (Dhanapat Rai & Co). Refrigeration and Air Conditioning by C.P.ARORA Basic Refrigeration and Air Conditioning by P.N.ANANTHANARAYANA, Tata Mc Grew Hill on and Air Conditioning by R.S.KHURMI, S.Chand & Company Ltd. V. N. KHABASHESKU. Heinrich Moretto, Manfred Schulze, Gebhard Wagner (2005) "Silicones" in Ullmann's Greenwood, Norman N.; Earnshaw, Alan (1997). V. N. Khabashesku, Z. A. Kerzina, K. N. Kudin, O. M. Nefedov (1998). "Matrix isolation infrared and density functionaltheoretical studies of organic silanones, (CH3O)2Si=O and (C6H5)2Si=O". Leiper (1979). "A Comparison for the Effects of Various Forms of Silicon