Conductor Size
Considerations for
Station Class Arresters
Prepared by
Jonathan Woodworth
Consulting Engineer
ArresterWorks
February 2012
ArresterFacts 034
ArresterWorks
ArresterFacts 034 Conductor Size Considerations for Station Class Arresters
Copyright 2012 Visit ArresterWorks ArresterFacts Library for other Resources Page 2
ArresterFacts 034
Conductor Size Considerations for Station Class Arresters
By Jonathan Woodworth, ArresterWorks
The Basic Question
“Does the arrester line lead as shown in Figure
1 need to be the same diameter as the down
conductor to the transformer?”
Answer
The diameter of a line lead connected to an
arrester has a negligible effect on the
protection offered by that arrester. In other
words, the diameter of the conductor carrying a
surge does not change the total discharge
voltage or clamping voltage of the arrester.
What is important is the length of the lead in
series with the arrester and electrically in
parallel with the protected insulation, as this is
what determines the inductance of the lead.
Whereas the lead diameter has little effect on
the inductance. A lead that is sized longer than
required will result in a higher inductance which
will have a negative effect on the protection
provided by the arrester.
Other Related Considerations for the Line
Connector
Therefore, when selecting the arrester lead on a
station class arrester, there are several factors
that need to be taken into consideration to
ensure the arrester protection capabilities are
not affected.
Fault Current: When an arrester fails, the fault
current through the arrester can be quite
substantial. If it is important that the lead not
burn through or fail mechanically, the lead
should be selected to meet these criteria,
keeping in mind that the diameter of the
lead will have an effect on the corona.
Corona: For higher voltage systems the
conductor diameter can determine the level
of corona that it will be emitted. Therefore
this may be the limiting factor in
determining the conductor size.
Figure 1 Transformer showing arrester leads
Arrester LeadDown Conductor
ArresterFacts 034 Conductor Size Considerations for Station Class Arresters
Copyright 2012 Visit ArresterWorks ArresterFacts Library for other Resources Page 3
Voltage Reflections: Voltage
reflections that will occur
because the bushing and
arrester are separated by a
finite distance are also
affected by the conductor
length but not the diameter.
Mechanical Considerations:
The mechanical strength of
the lead is a primary
consideration when sizing any
arrester lead in a substation.
The mechanical stress
generally dominates the
decision after the electrical
considerations have been
made.
Ground Conductor
Considerations
The size of the ground
conductor (and the material) has little effect
on the protection the arrester provides to
the transformer. Again, the length has more
effect and shorter is always better. If a neutral
bushing is exposed externally, a conductor
directly to that bushing from the arrester is
always better than running both the arrester
and the bushing down to the earth mat
separately. Also as in the line lead, the
conductor should be large enough to survive
the rigors of a fault event otherwise; it might
burn thorough or fail from stress. Sharp bends
in leads also have no significant effect in the
protection of the transformer.
Summary
The optimum size of an arrester conductor
that is mounted to a transformer in a
substation is determined by the mechanical
requirements. Fault current response
needs to be considered; mechanical stress
from wind and the configuration, and
corona are the major factors in this
consideration.
Figure 2 Arresters’ with large diameter leads due to
mechanical strength requirements

Weitere ähnliche Inhalte

Was ist angesagt?

Power system slide notes
Power system slide notesPower system slide notes
Power system slide notes
michaeljmack
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
Sumit Kumar
 

Was ist angesagt? (20)

Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission lines
 
Dampers used in electrical transmission lines
Dampers used in electrical transmission linesDampers used in electrical transmission lines
Dampers used in electrical transmission lines
 
Tl book
Tl bookTl book
Tl book
 
Deicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesDeicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc losses
 
Equipments of power transmission
Equipments of power transmissionEquipments of power transmission
Equipments of power transmission
 
Lec transmission line
Lec transmission lineLec transmission line
Lec transmission line
 
Transmission Line
Transmission LineTransmission Line
Transmission Line
 
Akt tl design01
Akt tl design01Akt tl design01
Akt tl design01
 
Ehv line design
Ehv line designEhv line design
Ehv line design
 
Power system slide notes
Power system slide notesPower system slide notes
Power system slide notes
 
TDU - Unit 01 Transmission system
TDU - Unit  01 Transmission system TDU - Unit  01 Transmission system
TDU - Unit 01 Transmission system
 
transmission-lines
transmission-linestransmission-lines
transmission-lines
 
Le.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentLe.h insulation coordination - Digsilent
Le.h insulation coordination - Digsilent
 
Ce31533536
Ce31533536Ce31533536
Ce31533536
 
Overvoltages 1
Overvoltages 1Overvoltages 1
Overvoltages 1
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission line
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordination
 
Electrical power transmission system
Electrical power transmission systemElectrical power transmission system
Electrical power transmission system
 

Andere mochten auch

Atp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs programAtp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs program
Gilberto Mejía
 

Andere mochten auch (20)

Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
 
Cyme equipment reference manual
Cyme equipment reference manualCyme equipment reference manual
Cyme equipment reference manual
 
Estudio de seleccion de ruta de la linea
Estudio de seleccion de ruta de la lineaEstudio de seleccion de ruta de la linea
Estudio de seleccion de ruta de la linea
 
Transitorios electromagneticos por maniobras
Transitorios electromagneticos por maniobrasTransitorios electromagneticos por maniobras
Transitorios electromagneticos por maniobras
 
Bentley substation civil instruction manual-v2.3
Bentley substation civil instruction manual-v2.3Bentley substation civil instruction manual-v2.3
Bentley substation civil instruction manual-v2.3
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
 
Libro coordinación aislamiento unal
Libro coordinación aislamiento unalLibro coordinación aislamiento unal
Libro coordinación aislamiento unal
 
Modelacion de redes aereas
Modelacion de redes aereasModelacion de redes aereas
Modelacion de redes aereas
 
00 programa de la asignatura
00 programa de la asignatura00 programa de la asignatura
00 programa de la asignatura
 
Seminario de investigación
Seminario de investigaciónSeminario de investigación
Seminario de investigación
 
5220 l11
5220 l115220 l11
5220 l11
 
Capitulo 6.1
Capitulo 6.1Capitulo 6.1
Capitulo 6.1
 
7839 10179-1-pb
7839 10179-1-pb7839 10179-1-pb
7839 10179-1-pb
 
3 4-energizacion-de-condensadores
3 4-energizacion-de-condensadores3 4-energizacion-de-condensadores
3 4-energizacion-de-condensadores
 
Tutorial de instalacion del programa atp draw pdf
Tutorial de instalacion del programa atp draw pdfTutorial de instalacion del programa atp draw pdf
Tutorial de instalacion del programa atp draw pdf
 
Comparison of conductor material
Comparison of conductor materialComparison of conductor material
Comparison of conductor material
 
Atp AtpDraw Guia Basica de uso
Atp AtpDraw Guia Basica de usoAtp AtpDraw Guia Basica de uso
Atp AtpDraw Guia Basica de uso
 
Guía de prácticas fenómenos transitorios electromagnéticos
Guía de prácticas fenómenos transitorios electromagnéticosGuía de prácticas fenómenos transitorios electromagnéticos
Guía de prácticas fenómenos transitorios electromagnéticos
 
Atp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs programAtp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs program
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 

Ähnlich wie Conductor size considerations_for_station_class_arresters

Chapter6 electronic-components
Chapter6 electronic-componentsChapter6 electronic-components
Chapter6 electronic-components
Vin Voro
 
technology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHH
technology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHHtechnology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHH
technology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHH
mhosn627
 
Chapter 35
Chapter 35Chapter 35
Chapter 35
mcfalltj
 

Ähnlich wie Conductor size considerations_for_station_class_arresters (20)

Chapter#5
Chapter#5Chapter#5
Chapter#5
 
Chapter6 electronic-components
Chapter6 electronic-componentsChapter6 electronic-components
Chapter6 electronic-components
 
1. Resistors .pptx
1. Resistors .pptx1. Resistors .pptx
1. Resistors .pptx
 
technology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHH
technology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHHtechnology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHH
technology.pptxFFFFFFFFFFFGGGGGGGGGGGGGHHHHH
 
Proximity effect
Proximity effectProximity effect
Proximity effect
 
ESA Module 1 Part-B ME832. by Dr. Mohammed Imran
ESA Module 1 Part-B ME832. by Dr. Mohammed ImranESA Module 1 Part-B ME832. by Dr. Mohammed Imran
ESA Module 1 Part-B ME832. by Dr. Mohammed Imran
 
Busbar Presentation2.pdf
Busbar Presentation2.pdfBusbar Presentation2.pdf
Busbar Presentation2.pdf
 
Experimental stress analysis BE notes by mohammed imran
Experimental stress analysis BE notes by mohammed imranExperimental stress analysis BE notes by mohammed imran
Experimental stress analysis BE notes by mohammed imran
 
Lightening Arrester.pptx
Lightening Arrester.pptxLightening Arrester.pptx
Lightening Arrester.pptx
 
STARIN GAUGE.pdf
STARIN GAUGE.pdfSTARIN GAUGE.pdf
STARIN GAUGE.pdf
 
Passive circuit elements
Passive circuit elementsPassive circuit elements
Passive circuit elements
 
Experiments manual
Experiments manual Experiments manual
Experiments manual
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
 
Transmission & distribution of electrical power
Transmission & distribution of electrical powerTransmission & distribution of electrical power
Transmission & distribution of electrical power
 
Proposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorProposal Technique for an Static Var Compensator
Proposal Technique for an Static Var Compensator
 
INTRODUCTION TO STRAIN GAUGES
INTRODUCTION TO STRAIN GAUGESINTRODUCTION TO STRAIN GAUGES
INTRODUCTION TO STRAIN GAUGES
 
Distribution system 2
Distribution system  2Distribution system  2
Distribution system 2
 
Chapter 35
Chapter 35Chapter 35
Chapter 35
 
Surge arrester
Surge arresterSurge arrester
Surge arrester
 
IR Drop Analysis and Its Reduction Techniques in Deep Submicron Technology
IR Drop Analysis and Its Reduction Techniques in Deep Submicron TechnologyIR Drop Analysis and Its Reduction Techniques in Deep Submicron Technology
IR Drop Analysis and Its Reduction Techniques in Deep Submicron Technology
 

Mehr von Gilberto Mejía (10)

Analisis de-falla-sistema-de-transmision-26-enero-2011
Analisis de-falla-sistema-de-transmision-26-enero-2011Analisis de-falla-sistema-de-transmision-26-enero-2011
Analisis de-falla-sistema-de-transmision-26-enero-2011
 
2. operacion de sistemas de transmision de 500k v rep
2. operacion de sistemas de transmision de 500k v rep2. operacion de sistemas de transmision de 500k v rep
2. operacion de sistemas de transmision de 500k v rep
 
Atp draw-tutorial
Atp draw-tutorialAtp draw-tutorial
Atp draw-tutorial
 
Transients in-power-systems-wiley
Transients in-power-systems-wileyTransients in-power-systems-wiley
Transients in-power-systems-wiley
 
Transients in-power-systems
Transients in-power-systemsTransients in-power-systems
Transients in-power-systems
 
Taller evaluacion descargas_ atmosfericas
Taller evaluacion descargas_ atmosfericasTaller evaluacion descargas_ atmosfericas
Taller evaluacion descargas_ atmosfericas
 
Resumen de teoria de atp
Resumen de teoria de atpResumen de teoria de atp
Resumen de teoria de atp
 
Aislamiento lineas transmision_energia
Aislamiento lineas transmision_energiaAislamiento lineas transmision_energia
Aislamiento lineas transmision_energia
 
Taller entregable calculo_parametros_2013_01
Taller entregable calculo_parametros_2013_01Taller entregable calculo_parametros_2013_01
Taller entregable calculo_parametros_2013_01
 
Guia trabajo seleccion de ruta
Guia trabajo seleccion de rutaGuia trabajo seleccion de ruta
Guia trabajo seleccion de ruta
 

Kürzlich hochgeladen

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 

Kürzlich hochgeladen (20)

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 

Conductor size considerations_for_station_class_arresters

  • 1. Conductor Size Considerations for Station Class Arresters Prepared by Jonathan Woodworth Consulting Engineer ArresterWorks February 2012 ArresterFacts 034 ArresterWorks
  • 2. ArresterFacts 034 Conductor Size Considerations for Station Class Arresters Copyright 2012 Visit ArresterWorks ArresterFacts Library for other Resources Page 2 ArresterFacts 034 Conductor Size Considerations for Station Class Arresters By Jonathan Woodworth, ArresterWorks The Basic Question “Does the arrester line lead as shown in Figure 1 need to be the same diameter as the down conductor to the transformer?” Answer The diameter of a line lead connected to an arrester has a negligible effect on the protection offered by that arrester. In other words, the diameter of the conductor carrying a surge does not change the total discharge voltage or clamping voltage of the arrester. What is important is the length of the lead in series with the arrester and electrically in parallel with the protected insulation, as this is what determines the inductance of the lead. Whereas the lead diameter has little effect on the inductance. A lead that is sized longer than required will result in a higher inductance which will have a negative effect on the protection provided by the arrester. Other Related Considerations for the Line Connector Therefore, when selecting the arrester lead on a station class arrester, there are several factors that need to be taken into consideration to ensure the arrester protection capabilities are not affected. Fault Current: When an arrester fails, the fault current through the arrester can be quite substantial. If it is important that the lead not burn through or fail mechanically, the lead should be selected to meet these criteria, keeping in mind that the diameter of the lead will have an effect on the corona. Corona: For higher voltage systems the conductor diameter can determine the level of corona that it will be emitted. Therefore this may be the limiting factor in determining the conductor size. Figure 1 Transformer showing arrester leads Arrester LeadDown Conductor
  • 3. ArresterFacts 034 Conductor Size Considerations for Station Class Arresters Copyright 2012 Visit ArresterWorks ArresterFacts Library for other Resources Page 3 Voltage Reflections: Voltage reflections that will occur because the bushing and arrester are separated by a finite distance are also affected by the conductor length but not the diameter. Mechanical Considerations: The mechanical strength of the lead is a primary consideration when sizing any arrester lead in a substation. The mechanical stress generally dominates the decision after the electrical considerations have been made. Ground Conductor Considerations The size of the ground conductor (and the material) has little effect on the protection the arrester provides to the transformer. Again, the length has more effect and shorter is always better. If a neutral bushing is exposed externally, a conductor directly to that bushing from the arrester is always better than running both the arrester and the bushing down to the earth mat separately. Also as in the line lead, the conductor should be large enough to survive the rigors of a fault event otherwise; it might burn thorough or fail from stress. Sharp bends in leads also have no significant effect in the protection of the transformer. Summary The optimum size of an arrester conductor that is mounted to a transformer in a substation is determined by the mechanical requirements. Fault current response needs to be considered; mechanical stress from wind and the configuration, and corona are the major factors in this consideration. Figure 2 Arresters’ with large diameter leads due to mechanical strength requirements