Lecture 9
1. EE 369
POWER SYSTEM ANALYSIS
Lecture 9
Transformers, Per Unit Calculations
Tom Overbye and Ross Baldick
1
2. Announcements
• For lectures 8 to 10 read Chapter 3
• Homework 7 is 5.8, 5.15, 5.17, 5.24, 5.27,
5.28, 5.29, 5.34, 5.37, 5.38, 5.43, 5.45; due
10/22.
• Homework 8 is 3.1, 3.3, 3.4, 3.7, 3.8, 3.9, 3.10,
3.12, 3.13, 3.14, 3.16, 3.18; due 10/29.
• Homework 9 is 3.20, 3.23, 3.25, 3.27, 3.28,
3.29, 3.35, 3.38, 3.39, 3.41, 3.44, 3.47; due
11/5.
2
3. Per Unit Change of MVA Base
Parameters for equipment are often given using
power rating of equipment as the MVA base
To analyze a system all per unit data must be on
a common power base
2 2
Hence Z
Z
/base base
OriginalBase NewBase
pu actual pu
OriginalBase NewBase
pu puOriginalBase NewBase
BaseBase
NewBase
OriginalBase NewBaseBase
pu puOriginalBase
Base
Z Z Z
V V
Z
S S
S
Z
S
→ →
× =
× =
3
4. Per Unit Change of Base Example
•A 54 MVA transformer has a leakage
reactance of 3.69% (on its own MVA base).
•What is the reactance on a 100 MVA base?
100
0.0369 0.0683 p.u.
54
eX = × =
4
5. Transformer Reactance
Transformer reactance is often specified as a
percentage, say 10%. This is a per unit value
expressed as a percentage on the power base
of the transformer.
Example: A 350 MVA, 230/20 kV transformer
has leakage reactance of 10%. What is p.u.
value on 100 MVA base? What is value in
ohms (230 kV)?
2
100
0.10 0.0286 p.u.
350
230
0.0286 15.1
100
eX = × =
× = Ω
5
6. Three Phase Transformers
•There are 4 different ways to connect 3φ
transformers
Y-Y ∆-
∆
Usually 3φ transformers are constructed so all windings
share a common core 6
10. Y-Y Connection: Per Phase Model
Per phase analysis of Y-Y connections is exactly the
same as analysis of a single phase transformer.
Y-Y connections are common in transmission systems.
Key advantages are the ability to ground each side
and there is no phase shift is introduced. 10
12. ∆-∆ Connection: 3φ Detailed Model
To use the per phase equivalent we need to use
the delta-wye load transformation
12
13. ∆-∆ Connection: Per Phase Model
Per phase analysis similar to Y-Y except impedances
are decreased by a factor of 3.
Key disadvantage is ∆-∆ connections can not be
grounded; not commonly used.
13
15. ∆-Y Connection V/I Relationships
, also 3 30
3030
Hence 3 and 3
For current we get
1
1
3 30 30
3
1
30
3
AB AB
an ab an
an
AnAB
ab an
AB
a AB
a
A AB AB A
a A
V V
a V V V
V a
VV
V V
a a
I
I a I
I a
I I I I
I a I
= ⇒ = = ∠ °
∠ °∠ °
= =
= ⇒ =
= ∠ − ° ⇒ = ∠ °
∴ = ∠ °
15
16. ∆-Y Connection: Per Phase Model
Note: Connection introduces a 30 degree phase shift!
Common for transmission/distribution step-down since
there is a neutral on the low voltage side.
Even if a = 1 there is a sqrt(3) step-up ratio
16
17. Y-∆ Connection: Per Phase Model
Exact opposite of the ∆-Y connection, now with a
phase shift of -30 degrees.
17