Wayne T. Bates
Cleaning Your RO
Eventually the day comes when your RO system will require cleaning. Cleaning is
recommended when your RO shows evidence of fouling, just prior to a long term
shutdown, or as a matter of scheduled routine maintenance. Fouling characteristics
that signal you need to clean are a 10-15% decrease in normalized permeate flow, a
10-15% decrease in normalized permeate quality, or a 10-15% increase in
normalized pressure drop as measured between the feed and concentrate headers.
RO cleaning frequency due to fouling will vary by site. A rough rule of thumb as to an
acceptable cleaning frequency is once every 3 to 12 months. If you have to clean
more than once a month, you should be able to justify further capital expenditures for
improved RO pretreatment or a re-design of the RO operation. If cleaning frequency is
every one to three months, you may want to focus on improving the operation of your
existing equipment but further capital expenditure may be harder to justify.
One RO design feature that is commonly over-looked in reducing RO cleaning
frequency is the use of RO permeate water for flushing foulants from the system.
Soaking the RO elements during standby with permeate can help dissolve scale and
loosen precipitates, reducing the frequency of chemical cleaning.
What you clean for can vary site by site depending on the foulant. Complicating the
situation frequently is that one more than one fulant can be present. Typical foulants
are:
• Calcium carbonate scale
• Sulfate scale of calcium, barium or strontium
• Metal oxides of iron, manganese, aluminum, etc.
• Silica scale
• Colloidal deposits (inorganic or mixed inorganic/organic)
• Organic material of natural origin or man-made origin
• Biological (bioslime, mold, or fungi)
There are a number of factors involved in the selection of a suitable cleaning chemical
(or chemicals) and proper cleaning protocol. The first time you have to perform a
cleaning, it is recommended to contact the manufacturer of the equipment, the RO
element manufacturer, or a RO specialty chemical supplier. Once the suspected
foulant(s) are identified, one or more cleaning chemicals will be recommended.
These chemical(s) can be generic and available from a number of suppliers or can
be private-labeled proprietary cleaning solutions. The proprietary solutions can be
more expensive but may be easier to use and you cannot rule out the advantage of the
intellectual knowledge supplied by these companies. An invaluable service offered by
some service companies is that they will determine the proper cleaning chemicals
and protocol by testing at their facility an element pulled from your system.
It is not unusual to have to use a number of different cleaning chemicals in a specific
sequence to achieve the optimum cleaning. There are times that a low pH cleaning is
used first to remove foulants like mineral scale, followed by a high pH cleaning to
remove organic material. However, there are times that a high pH cleaning is used
first to remove foulants like oil followed by a low pH cleaning. Some cleaning
solutions have detergents added to aid in the removal of heavy biological and organic
debris, while others have a chelating agent like EDTA added to aid in the removal of
colloidal material, organic and biological material, and sulfate scale. An important
thing to remember is that the improper selection of a cleaning chemical or the
sequence of chemical introduction can make the foulant worse.
There are a number of precautions in cleaning chemical selection and usage for a
composite polyamide membrane:
• Follow the manufacturer s recommended chemical list, dosage, pH, temperature
and contact time guidelines.
• Use the leash harshest chemical cleaning to get the job done. This will optimize
the useful life of the membrane.
• Be prudent in the adjustment of pH at the low and high pH range to extend the
useful life of the membrane. A gentle pH range is 4 to 10, while the harshest is 2
to 12.
• Don t mix acids with caustics. Thoroughly rinse the 1st cleaning solution from the
system before introducing the next solution.
• Flush out detergents with high pH permeate
• Verify that proper disposal requirements for the cleaning solution are followed.
If your system has been fouled biologically, you may want to consider the extra step of
introducing a sanitizing biocide chemical after a successful cleaning. Biocides can
be introduced immediately after cleaning, periodically (e.g. once a week), or
continuously during service. You must be sure however that the biocide is compatible
with the membrane, does not create any health risks, is effective in controlling
biological activity, and is not cost prohibitive.
The successful cleaning of an RO on-site requires a well designed RO cleaning skid.
Normally this skid is not hard piped to the RO skid and uses temporary hosing for
connections. It is recommended to clean a multi-stage RO one stage at a time to
optimize crossflow cleaning velocity. The source water for chemical solution make up
and rinsing should be RO permeate, DI water or at least soft water. Components
must be corrosion proof. Major cleaning system components are:
• RO Cleaning Tank: This tank needs to be sized properly to accommodate the
displacement of water in the hose, piping, and pressure vessels. The tank should
be designed to allow 100 % drainage, easy access for chemical introduction and
mixing, a recirculation line from the RO Cleaning Pump, proper venting, overflow,
and a return line located near the bottom to minimize foam formation when using a
surfactant.
• RO Cleaning Pump: This pump needs to be sized to develop the proper crossflow
velocity to scrub the membrane clean. The cleaning rate for a 8-inch diameter
vessel is 30 to 40 gpm and for a 4-inch diameter vessel is 8 to 10 gpm. The
maximum recommended pressure is 60 psi to minimize the production of
permeate during cleaning and reduce the convective redeposition of foulant back
on to the membrane surface.
• RO Cleaning Cartridge Filter: Normally 5 to 10-micron and is designed to remove
foulants that have been displaced from the cleaning process.
• RO Tank Heater or Cooler: The optimal temperature for cleaning is 35 to 45
o
C.
One cannot forget that heat is generated and imparted by the RO Cleaning Pump
during recirculation.
• RO Tank Mixer: This is recommended to get optimal mixing of chemical, though
some designers rely solely on the slow introduction of chemical while maintaining
a recirculation through the RO Cleaning Pump back to the tank.
• Instrumentation: Cleaning system instrumentation should be included to monitor
flow, temperature, pressure, and tank level.
• Sample Points: Sample valves should be located to allow pH and TDS
measurements off the RO Cleaning Pump discharge and the concentrate side
recirculation return line.
• Permeate Return Line: A small amount of the cleaning solution can permeate
through the membranes and so a permeate side return line is recommended.
RO cleaning procedures may vary dependent on the situation. The time required to
clean a stage can take from 4 to 8 hours., The basic steps of cleaning are:
1. Perform a low pressure flush with feed or permeate water to remove service
concentrate and foulants.
2. Make up the cleaning solution per the manufacturer s instructions.
3. Introduce the cleaning solution to the first stage for 60 minutes. You may want to
throttle the flow up slowly to minimize the plugging of the feed path with dislodged
foulant. Send the displaced water and up to 20% of the fouled cleaning solution to
drain before returning the cleaning solution back to the RO Cleaning Tank.
Readjust the pH to the target when it changes more than 0.5 pH units.
4. An optional soak and recirculation sequence can be used. The soak time can be
from 1 hour to overnight depending on the manufacturer s recommendations, but
be cautious that the proper temperature and pH be maintained and that this does
increase the chemical exposure time of the membrane.
5. A low pressure Cleaning Rinse with permeate water is required to remove all
traces of chemical from the Cleaning Skid and the RO Skid.
6. Once all the stages of a train are cleaned, the RO can be placed back into service.
It is not unusual for it to take from a few hours to a few days for the RO permeate
quality to stabilize, especially after high pH cleanings.
It is exciting to have a successful cleaning and watch your pressures and permeate
quality improve. On the flip side it is frustrating to have an unsuccessful cleaning,
though its no reason to become suicidal. If the cleaning did not provide the results
you were hoping for, you may want to consider talking to those suppliers who offer off-
site services rather than proceed with a trial-and-error approach on site. Pull one or
two elements from the front or back end and ship them to a service company. A
service company can determine the optimal cleaning procedure and also report how
effective the cleaning was in restoring flow and salt rejection.

Weitere ähnliche Inhalte

Was ist angesagt?

03 Conventional Biological Treatments
03 Conventional Biological Treatments03 Conventional Biological Treatments
03 Conventional Biological Treatmentsakashpadole
 
AIChE Final Design Report Excerpt
AIChE Final Design Report ExcerptAIChE Final Design Report Excerpt
AIChE Final Design Report Excerptaarittha
 
Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...
Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...
Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...MilliporeSigma
 
Bottled water filtration selection guide for products and applications rev 1 d
Bottled water filtration selection guide for products and applications rev 1 dBottled water filtration selection guide for products and applications rev 1 d
Bottled water filtration selection guide for products and applications rev 1 dAna Saray Ayala Chirinos
 
{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...
{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...
{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...MODI20077
 
Clean in-place-cip-buying-guide
Clean in-place-cip-buying-guideClean in-place-cip-buying-guide
Clean in-place-cip-buying-guideChevronelle
 
IRJET- A Review on Utilization of Sequence Batch Reactor Technology (SBR)...
IRJET-  	  A Review on Utilization of Sequence Batch Reactor Technology (SBR)...IRJET-  	  A Review on Utilization of Sequence Batch Reactor Technology (SBR)...
IRJET- A Review on Utilization of Sequence Batch Reactor Technology (SBR)...IRJET Journal
 
Performance Evaluation of Dairy Wastewater Treatment Plant
Performance Evaluation of Dairy Wastewater Treatment PlantPerformance Evaluation of Dairy Wastewater Treatment Plant
Performance Evaluation of Dairy Wastewater Treatment PlantIRJET Journal
 
Laboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality StandardsLaboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality StandardsPurite
 
C22 3 cleaning-in-place_final-web
C22 3 cleaning-in-place_final-webC22 3 cleaning-in-place_final-web
C22 3 cleaning-in-place_final-webDir Jan
 
Industrialwastewatertreatment
IndustrialwastewatertreatmentIndustrialwastewatertreatment
Industrialwastewatertreatmentgayatri VISHWA
 
BIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSISBIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSISalenashik
 
20_SS_disinfection_pacificozone_0411WQP
20_SS_disinfection_pacificozone_0411WQP20_SS_disinfection_pacificozone_0411WQP
20_SS_disinfection_pacificozone_0411WQPChris Rombach
 
Ecofriendly Sugar Polymer based Toilet Cleaners
Ecofriendly Sugar Polymer based Toilet CleanersEcofriendly Sugar Polymer based Toilet Cleaners
Ecofriendly Sugar Polymer based Toilet CleanersIRJET Journal
 
Oil Technics Ltd: Decommissioning solutions brochure.
Oil Technics Ltd: Decommissioning solutions brochure.Oil Technics Ltd: Decommissioning solutions brochure.
Oil Technics Ltd: Decommissioning solutions brochure.David Holmes
 

Was ist angesagt? (20)

03 Conventional Biological Treatments
03 Conventional Biological Treatments03 Conventional Biological Treatments
03 Conventional Biological Treatments
 
AIChE Final Design Report Excerpt
AIChE Final Design Report ExcerptAIChE Final Design Report Excerpt
AIChE Final Design Report Excerpt
 
Cleaning In Place- Principle, Parameter, Procedure
Cleaning In Place-  Principle, Parameter, ProcedureCleaning In Place-  Principle, Parameter, Procedure
Cleaning In Place- Principle, Parameter, Procedure
 
Etp Final Report
Etp Final ReportEtp Final Report
Etp Final Report
 
Water systems
Water systemsWater systems
Water systems
 
MBBR PRESENTATION
MBBR PRESENTATIONMBBR PRESENTATION
MBBR PRESENTATION
 
Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...
Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...
Redesigned Filter Capsule Improves Final Filtration Assembly Design and Opera...
 
Bottled water filtration selection guide for products and applications rev 1 d
Bottled water filtration selection guide for products and applications rev 1 dBottled water filtration selection guide for products and applications rev 1 d
Bottled water filtration selection guide for products and applications rev 1 d
 
{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...
{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...
{Ed1b3845 4477-45f9-80bd-807c64b69168} 201509-dw_ps_global_wr_wa_advanced_ro_...
 
Clean in-place-cip-buying-guide
Clean in-place-cip-buying-guideClean in-place-cip-buying-guide
Clean in-place-cip-buying-guide
 
IRJET- A Review on Utilization of Sequence Batch Reactor Technology (SBR)...
IRJET-  	  A Review on Utilization of Sequence Batch Reactor Technology (SBR)...IRJET-  	  A Review on Utilization of Sequence Batch Reactor Technology (SBR)...
IRJET- A Review on Utilization of Sequence Batch Reactor Technology (SBR)...
 
Performance Evaluation of Dairy Wastewater Treatment Plant
Performance Evaluation of Dairy Wastewater Treatment PlantPerformance Evaluation of Dairy Wastewater Treatment Plant
Performance Evaluation of Dairy Wastewater Treatment Plant
 
Laboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality StandardsLaboratory Water Purification Technology, Products and Water Quality Standards
Laboratory Water Purification Technology, Products and Water Quality Standards
 
C22 3 cleaning-in-place_final-web
C22 3 cleaning-in-place_final-webC22 3 cleaning-in-place_final-web
C22 3 cleaning-in-place_final-web
 
Industrialwastewatertreatment
IndustrialwastewatertreatmentIndustrialwastewatertreatment
Industrialwastewatertreatment
 
BIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSISBIOLOGY-REVERSE OSMOSIS
BIOLOGY-REVERSE OSMOSIS
 
20_SS_disinfection_pacificozone_0411WQP
20_SS_disinfection_pacificozone_0411WQP20_SS_disinfection_pacificozone_0411WQP
20_SS_disinfection_pacificozone_0411WQP
 
Noh reverse osmosis
Noh reverse osmosisNoh reverse osmosis
Noh reverse osmosis
 
Ecofriendly Sugar Polymer based Toilet Cleaners
Ecofriendly Sugar Polymer based Toilet CleanersEcofriendly Sugar Polymer based Toilet Cleaners
Ecofriendly Sugar Polymer based Toilet Cleaners
 
Oil Technics Ltd: Decommissioning solutions brochure.
Oil Technics Ltd: Decommissioning solutions brochure.Oil Technics Ltd: Decommissioning solutions brochure.
Oil Technics Ltd: Decommissioning solutions brochure.
 

Ähnlich wie Cleaning your ro

Sequencing Batch Reactor (SBR) presentation1.pptx
Sequencing Batch Reactor (SBR) presentation1.pptxSequencing Batch Reactor (SBR) presentation1.pptx
Sequencing Batch Reactor (SBR) presentation1.pptxJohnReymerSaplan1
 
Dipti cleaning ppt
Dipti cleaning pptDipti cleaning ppt
Dipti cleaning pptNeha Suresh
 
CIP presentation - ensure safety and sanitation.pdf
CIP presentation - ensure safety and sanitation.pdfCIP presentation - ensure safety and sanitation.pdf
CIP presentation - ensure safety and sanitation.pdfnguyenlekhanhx02
 
Bs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finalsBs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finalsDaphne Tan
 
Bs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finalsBs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finalsDaphne Tan
 
Reverse osmosis troubleshooting
Reverse osmosis troubleshootingReverse osmosis troubleshooting
Reverse osmosis troubleshootingAhmed Adel
 
Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!
Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!
Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!William Shorter
 
Current cleaning techniques in dairy processing industry
Current cleaning techniques in dairy processing industryCurrent cleaning techniques in dairy processing industry
Current cleaning techniques in dairy processing industrySelvaprakashnavaneethan
 
Wastewater treatment for engineering.pdf
Wastewater treatment for engineering.pdfWastewater treatment for engineering.pdf
Wastewater treatment for engineering.pdfmstrkhnz
 
Stirred tank bioreactor
Stirred tank bioreactorStirred tank bioreactor
Stirred tank bioreactorNizam Ashraf
 
Effluent water treatment plant in an industry
Effluent water treatment plant in an industryEffluent water treatment plant in an industry
Effluent water treatment plant in an industryHGASSAMARASINGHE
 
Water Consumption of Industrial Steam Cleaners: What to Know
Water Consumption of Industrial Steam Cleaners: What to KnowWater Consumption of Industrial Steam Cleaners: What to Know
Water Consumption of Industrial Steam Cleaners: What to KnowPure Steam Cleaners
 
dokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptx
dokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptxdokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptx
dokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptxabdo badr
 
Recycling Earths Rapidly Shrinking Resources_Published
Recycling Earths Rapidly Shrinking Resources_PublishedRecycling Earths Rapidly Shrinking Resources_Published
Recycling Earths Rapidly Shrinking Resources_PublishedNate Maguire
 
Dairy and meat processing plants cleaning by Geeta Chauhan
Dairy and meat processing plants cleaning by Geeta ChauhanDairy and meat processing plants cleaning by Geeta Chauhan
Dairy and meat processing plants cleaning by Geeta ChauhanGeeta12344
 

Ähnlich wie Cleaning your ro (20)

Sequencing Batch Reactor (SBR) presentation1.pptx
Sequencing Batch Reactor (SBR) presentation1.pptxSequencing Batch Reactor (SBR) presentation1.pptx
Sequencing Batch Reactor (SBR) presentation1.pptx
 
Dipti cleaning ppt
Dipti cleaning pptDipti cleaning ppt
Dipti cleaning ppt
 
CIP presentation - ensure safety and sanitation.pdf
CIP presentation - ensure safety and sanitation.pdfCIP presentation - ensure safety and sanitation.pdf
CIP presentation - ensure safety and sanitation.pdf
 
ETP Operation.pdf
ETP Operation.pdfETP Operation.pdf
ETP Operation.pdf
 
Bs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finalsBs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finals
 
Bs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finalsBs water-treatment-presentation-1-1 finals
Bs water-treatment-presentation-1-1 finals
 
Reverse osmosis troubleshooting
Reverse osmosis troubleshootingReverse osmosis troubleshooting
Reverse osmosis troubleshooting
 
Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!
Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!
Drain Safe Products: They’re Waste Water Compliant, Right? Wrong!
 
Dialysis Water Treatment
 Dialysis Water Treatment  Dialysis Water Treatment
Dialysis Water Treatment
 
Current cleaning techniques in dairy processing industry
Current cleaning techniques in dairy processing industryCurrent cleaning techniques in dairy processing industry
Current cleaning techniques in dairy processing industry
 
Wastewater treatment for engineering.pdf
Wastewater treatment for engineering.pdfWastewater treatment for engineering.pdf
Wastewater treatment for engineering.pdf
 
How to maintain ro
How to maintain roHow to maintain ro
How to maintain ro
 
Stirred tank bioreactor
Stirred tank bioreactorStirred tank bioreactor
Stirred tank bioreactor
 
Effluent water treatment plant in an industry
Effluent water treatment plant in an industryEffluent water treatment plant in an industry
Effluent water treatment plant in an industry
 
BIO102: 5 Keys
BIO102: 5 KeysBIO102: 5 Keys
BIO102: 5 Keys
 
Water Consumption of Industrial Steam Cleaners: What to Know
Water Consumption of Industrial Steam Cleaners: What to KnowWater Consumption of Industrial Steam Cleaners: What to Know
Water Consumption of Industrial Steam Cleaners: What to Know
 
Pickling & Passivation
Pickling & PassivationPickling & Passivation
Pickling & Passivation
 
dokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptx
dokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptxdokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptx
dokumen.tips_validation-of-water-system-for-pharmaceutical-use.pptx
 
Recycling Earths Rapidly Shrinking Resources_Published
Recycling Earths Rapidly Shrinking Resources_PublishedRecycling Earths Rapidly Shrinking Resources_Published
Recycling Earths Rapidly Shrinking Resources_Published
 
Dairy and meat processing plants cleaning by Geeta Chauhan
Dairy and meat processing plants cleaning by Geeta ChauhanDairy and meat processing plants cleaning by Geeta Chauhan
Dairy and meat processing plants cleaning by Geeta Chauhan
 

Mehr von Christian Alberto Chiroque Ruiz (8)

563062 fundamentos de_la_tecnica_de_automatizacion
563062 fundamentos de_la_tecnica_de_automatizacion563062 fundamentos de_la_tecnica_de_automatizacion
563062 fundamentos de_la_tecnica_de_automatizacion
 
Bmfcir789g
Bmfcir789gBmfcir789g
Bmfcir789g
 
Design guidline for_small_waste_water_treatment_works
Design guidline for_small_waste_water_treatment_worksDesign guidline for_small_waste_water_treatment_works
Design guidline for_small_waste_water_treatment_works
 
Ggc q orgánica_i__20101
Ggc q orgánica_i__20101Ggc q orgánica_i__20101
Ggc q orgánica_i__20101
 
Lumbreras lenguaje
Lumbreras   lenguajeLumbreras   lenguaje
Lumbreras lenguaje
 
Lumbreras geografia
Lumbreras   geografiaLumbreras   geografia
Lumbreras geografia
 
Compe física trilce
Compe física trilceCompe física trilce
Compe física trilce
 
1 membranas y_su_uso
1 membranas y_su_uso1 membranas y_su_uso
1 membranas y_su_uso
 

Kürzlich hochgeladen

Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 

Kürzlich hochgeladen (20)

Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 

Cleaning your ro

  • 1. Wayne T. Bates Cleaning Your RO Eventually the day comes when your RO system will require cleaning. Cleaning is recommended when your RO shows evidence of fouling, just prior to a long term shutdown, or as a matter of scheduled routine maintenance. Fouling characteristics that signal you need to clean are a 10-15% decrease in normalized permeate flow, a 10-15% decrease in normalized permeate quality, or a 10-15% increase in normalized pressure drop as measured between the feed and concentrate headers. RO cleaning frequency due to fouling will vary by site. A rough rule of thumb as to an acceptable cleaning frequency is once every 3 to 12 months. If you have to clean more than once a month, you should be able to justify further capital expenditures for improved RO pretreatment or a re-design of the RO operation. If cleaning frequency is every one to three months, you may want to focus on improving the operation of your existing equipment but further capital expenditure may be harder to justify. One RO design feature that is commonly over-looked in reducing RO cleaning frequency is the use of RO permeate water for flushing foulants from the system. Soaking the RO elements during standby with permeate can help dissolve scale and loosen precipitates, reducing the frequency of chemical cleaning. What you clean for can vary site by site depending on the foulant. Complicating the situation frequently is that one more than one fulant can be present. Typical foulants are: • Calcium carbonate scale • Sulfate scale of calcium, barium or strontium • Metal oxides of iron, manganese, aluminum, etc. • Silica scale • Colloidal deposits (inorganic or mixed inorganic/organic) • Organic material of natural origin or man-made origin • Biological (bioslime, mold, or fungi) There are a number of factors involved in the selection of a suitable cleaning chemical (or chemicals) and proper cleaning protocol. The first time you have to perform a cleaning, it is recommended to contact the manufacturer of the equipment, the RO
  • 2. element manufacturer, or a RO specialty chemical supplier. Once the suspected foulant(s) are identified, one or more cleaning chemicals will be recommended. These chemical(s) can be generic and available from a number of suppliers or can be private-labeled proprietary cleaning solutions. The proprietary solutions can be more expensive but may be easier to use and you cannot rule out the advantage of the intellectual knowledge supplied by these companies. An invaluable service offered by some service companies is that they will determine the proper cleaning chemicals and protocol by testing at their facility an element pulled from your system. It is not unusual to have to use a number of different cleaning chemicals in a specific sequence to achieve the optimum cleaning. There are times that a low pH cleaning is used first to remove foulants like mineral scale, followed by a high pH cleaning to remove organic material. However, there are times that a high pH cleaning is used first to remove foulants like oil followed by a low pH cleaning. Some cleaning solutions have detergents added to aid in the removal of heavy biological and organic debris, while others have a chelating agent like EDTA added to aid in the removal of colloidal material, organic and biological material, and sulfate scale. An important thing to remember is that the improper selection of a cleaning chemical or the sequence of chemical introduction can make the foulant worse. There are a number of precautions in cleaning chemical selection and usage for a composite polyamide membrane: • Follow the manufacturer s recommended chemical list, dosage, pH, temperature and contact time guidelines. • Use the leash harshest chemical cleaning to get the job done. This will optimize the useful life of the membrane. • Be prudent in the adjustment of pH at the low and high pH range to extend the useful life of the membrane. A gentle pH range is 4 to 10, while the harshest is 2 to 12. • Don t mix acids with caustics. Thoroughly rinse the 1st cleaning solution from the system before introducing the next solution. • Flush out detergents with high pH permeate • Verify that proper disposal requirements for the cleaning solution are followed. If your system has been fouled biologically, you may want to consider the extra step of introducing a sanitizing biocide chemical after a successful cleaning. Biocides can be introduced immediately after cleaning, periodically (e.g. once a week), or continuously during service. You must be sure however that the biocide is compatible with the membrane, does not create any health risks, is effective in controlling biological activity, and is not cost prohibitive. The successful cleaning of an RO on-site requires a well designed RO cleaning skid. Normally this skid is not hard piped to the RO skid and uses temporary hosing for connections. It is recommended to clean a multi-stage RO one stage at a time to optimize crossflow cleaning velocity. The source water for chemical solution make up
  • 3. and rinsing should be RO permeate, DI water or at least soft water. Components must be corrosion proof. Major cleaning system components are: • RO Cleaning Tank: This tank needs to be sized properly to accommodate the displacement of water in the hose, piping, and pressure vessels. The tank should be designed to allow 100 % drainage, easy access for chemical introduction and mixing, a recirculation line from the RO Cleaning Pump, proper venting, overflow, and a return line located near the bottom to minimize foam formation when using a surfactant. • RO Cleaning Pump: This pump needs to be sized to develop the proper crossflow velocity to scrub the membrane clean. The cleaning rate for a 8-inch diameter vessel is 30 to 40 gpm and for a 4-inch diameter vessel is 8 to 10 gpm. The maximum recommended pressure is 60 psi to minimize the production of permeate during cleaning and reduce the convective redeposition of foulant back on to the membrane surface. • RO Cleaning Cartridge Filter: Normally 5 to 10-micron and is designed to remove foulants that have been displaced from the cleaning process. • RO Tank Heater or Cooler: The optimal temperature for cleaning is 35 to 45 o C. One cannot forget that heat is generated and imparted by the RO Cleaning Pump during recirculation. • RO Tank Mixer: This is recommended to get optimal mixing of chemical, though some designers rely solely on the slow introduction of chemical while maintaining a recirculation through the RO Cleaning Pump back to the tank. • Instrumentation: Cleaning system instrumentation should be included to monitor flow, temperature, pressure, and tank level. • Sample Points: Sample valves should be located to allow pH and TDS measurements off the RO Cleaning Pump discharge and the concentrate side recirculation return line. • Permeate Return Line: A small amount of the cleaning solution can permeate through the membranes and so a permeate side return line is recommended. RO cleaning procedures may vary dependent on the situation. The time required to clean a stage can take from 4 to 8 hours., The basic steps of cleaning are: 1. Perform a low pressure flush with feed or permeate water to remove service concentrate and foulants. 2. Make up the cleaning solution per the manufacturer s instructions. 3. Introduce the cleaning solution to the first stage for 60 minutes. You may want to throttle the flow up slowly to minimize the plugging of the feed path with dislodged foulant. Send the displaced water and up to 20% of the fouled cleaning solution to drain before returning the cleaning solution back to the RO Cleaning Tank. Readjust the pH to the target when it changes more than 0.5 pH units. 4. An optional soak and recirculation sequence can be used. The soak time can be from 1 hour to overnight depending on the manufacturer s recommendations, but be cautious that the proper temperature and pH be maintained and that this does increase the chemical exposure time of the membrane. 5. A low pressure Cleaning Rinse with permeate water is required to remove all traces of chemical from the Cleaning Skid and the RO Skid.
  • 4. 6. Once all the stages of a train are cleaned, the RO can be placed back into service. It is not unusual for it to take from a few hours to a few days for the RO permeate quality to stabilize, especially after high pH cleanings. It is exciting to have a successful cleaning and watch your pressures and permeate quality improve. On the flip side it is frustrating to have an unsuccessful cleaning, though its no reason to become suicidal. If the cleaning did not provide the results you were hoping for, you may want to consider talking to those suppliers who offer off- site services rather than proceed with a trial-and-error approach on site. Pull one or two elements from the front or back end and ship them to a service company. A service company can determine the optimal cleaning procedure and also report how effective the cleaning was in restoring flow and salt rejection.