Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
1
Layer-Type Power Transformer Thermal Analysis
Considering Effective Parameters On The
Temperature Rise
M.Ghanbaria
, M.A.Taghikhanib
a
Department of Electrical and Computer Engineering, Saveh Branch, Islamic Azad
University, Saveh, Iran
b
Department of Engineering, Imam Khomeini International University, Qazvin, Iran
ABSTRACT
Since large power transformers belong to the most valuable assets in electrical power networks it is
suitable to pay higher attention to these operating resources. Thermal impact leads not only to long-term
oil/paper-insulation degradation; it is also a limiting factor for the transformer operation. Therefore, the
knowledge of the temperature, especially the hottest spot (HST) temperature, is of high interest. This paper
presents steady state temperature distribution of a power transformer layer-type winding using conjugated
heat transfer analysis, therefore energy and Navier-Stokes equations are solved using finite difference
method. Meanwhile, the effects of load conditions and type of oil on HST are investigated using the model.
Oil in the transformer is assumed nearly incompressible and oil parameters such as thermal conductivity,
special heat, viscosity, and density vary with temperature. Comparing the results with those obtained from
finite integral transform checks the validity and accuracy of the proposed method.
KEYWORDS
Power transformer; Layer-Type Winding; Thermal Analysis; Conjugated Heat Transfer; Finite difference
method.
1. INTRODUCTION
In a power transformer a part of the electrical energy is converted into the heat. Although this part
is quite small comparing to total electric power transferred through a transformer, it causes
significant temperature rise, which represents the limiting criteria for possible power transfer
through a transformer. That is why the precise calculation of temperatures in critical points (top
oil and the hottest solid insulation spot) is of practical interest. Thermal impact leads not only to
long-term oil/paper-insulation degradation; it is also a limiting factor for the transformer
operation [1], [2]. Therefore, the knowledge of the temperature, especially the hottest spot
temperature, is of high interest. If the temperature rise goes beyond the permissible value, the
load of transformer must be reduced or an auxiliary transformer is used in order to preserve the
insulation from deterioration. For an oil-immersed transformer, the oil surrounds the transformer
body. Oil is a nearly incompressible fluid and density changes due to temperature rise, therefore
oil moves in the transformer. The heat transferred by convection is the most important method of
heat transfer.
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
2
Hottest spot temperature must not exceed the prescribed value in order to avoid insulation faults.
Furthermore, an accurate computation of the HST helps in a realistic estimation of the reliability
and remaining life of the transformer winding insulation. The classical approach has been to
consider the hottest-spot temperature as the sum of the ambient temperature, the top-oil
temperature rise, and the hottest-spot-to-top-oil temperature gradient. A hottest spot temperature
calculation is given in the International Standards [3]-[5]. The algorithm for calculating the
hottest spot temperature of a directly loaded transformer using data obtained in a short circuit
heating test is given in [6]. Heat transfer theory results from winding to oil are exposed in [7], [8].
The structure of a transformer winding is complex and does not conform to any known geometry
in the strict sense. Under general conditions, the transformer windings can be assumed
cylindrical; hence, a layer or a disc winding is a finite annular cylinder. The thermal and physical
properties of the system would be equivalent to a composite system of insulation and conductor.
In this paper, author has proposed a procedure for obtaining the temperature distribution in the
power transformer and the effects of load conditions and type of oil are investigated using the
model. For this reason energy and Navier-Stokes equations are solved using finite difference
method. Therefore, a code has been provided under MATLAB software. The model can be used
for temperature calculation on the arbitrary change of current and outside air temperature. In the
paper, thermal model, energy, and Navier-Stokes equations are given in section 2. Results and
discussion of the proposed work have been provided in section 3.
2. THERMAL MODEL
Energy equation for Newtonian incompressible fluid (or nearly incompressible fluid) such as oil
in two dimensions is [9]
)
(
)
(
)
)
(
)
(
(
y
T
k
y
x
T
k
x
y
T
C
V
x
T
C
V
p
y
p
x
∂
∂
⋅
∂
∂
+
∂
∂
⋅
∂
∂
=
∂
⋅
∂
+
∂
⋅
∂
⋅
 (1)
Where T is temperature, Vx is velocity in x direction, Vy is velocity in y direction, k is thermal
conductivity,  is density and Cp is special heat of the oil in the transformer. In equation (1), oil
properties vary with temperature [1], [10], [11]. The temperature dependence of oil properties are
given as follows:
)
273
exp( 2
1
+
⋅
=
T
a
a
 (2)
T
a
a
C
p ⋅
+
= 4
3 (3)
T
a
a ⋅
+
= 6
5
 (4)
T
a
a
k ⋅
+
= 8
7 (5)
9
a
=
 (6)
Where : is viscosity and  is volumetric expansion coefficient. The nine constants for
transformer oil and silicon oil have been listed in Table 1 [3, 4]. It is generally valid for all types
of transformer oil that the variation of the oil viscosity with temperature is much higher than the
variation of other oil properties [11]. Thus, all oil physical properties except the viscosity can be
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
3
replaced by a constant. However, the variations of all oil properties with temperature have been
considered in this paper.
Table1. Oil constants
Oil constant Transformer oil Silicon oil
a1 0.0000013573 0.00012127
a2 2797.3 1782.3
a3 1960 1424
a4 4.005 2.513
a5 887 989
a6 -0.659 -0.870
a7 0.124 0.138
a8 -0.0001525 -0.00009621
a9 0.00086 0.00095
In (1) velocity is unknown, and then we must solve Navier-Stokes equations. Navier-Stokes
equations in two dimensions for Newtonian incompressible fluid are [9]
Continuity Equation:
0
=
∂
∂
+
∂
∂
y
V
x
V y
x
(7)
Momentum Equations:
))
(
)
2
(
(
)
.(
x
V
y
V
y
x
V
x
x
P
y
V
V
x
V
V
y
x
x
x
y
x
x
∂
∂
⋅
+
∂
∂
⋅
∂
∂
+
∂
∂
⋅
⋅
∂
∂
+
∂
∂
−
=
∂
∂
+
∂
∂



 (8)
)
(
))
2
(
)
(
(
)
.(
0 ref
y
y
x
x
y
x
x
T
T
g
y
V
y
x
V
y
V
x
y
P
y
V
V
x
V
V
−
⋅
⋅
⋅
+
∂
∂
⋅
⋅
∂
∂
+
∂
∂
⋅
+
∂
∂
⋅
∂
∂
+
∂
∂
−
=
∂
∂
+
∂
∂






(9)
Where P is pressure and g is gravitational acceleration .The heat conduction equation for core and
windings is written [10], [11]
0
2
2
2
2
=
+
∂
∂
⋅
+
∂
∂
⋅ Q
y
T
k
x
T
k y
x (10)
Where kx and ky are thermal conductivity in x and y directions respectively. The term Q is the
volumetric heat source function and has been modified here to take care of variation of electrical
resistance of copper with temperature. The heat source term Q can be of the form
)]
(
1
[
0 ref
c T
T
Q
Q −
⋅
+
⋅
=  (11)
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
4
Where c is the temperature coefficient of electrical resistance of copper wire. With this
representation, the function Q becomes temperature dependent, distributed heat source. Thermal
conductivities are unequal in different directions. Thermal conductivity has been treated as a
vector quantity, having components in both radial and axial direction. Resultant thermal
conductivity of the system is [10]
2
2
y
x k
k
K +
= (12)
Where
)
log
...
log
log
(
log
1
2
2
3
1
1
2
1
n
n
n
n
x
k
r
r
k
r
r
k
r
r
r
r
k
−
+
+
+
=
in
cu
cu
in
in
cu
in
cu
y
k
t
k
t
t
t
k
k
k
⋅
+
⋅
+
⋅
⋅
=
)
(
Term K represents resultant thermal conductivity of insulation and conductor system. In this
paper, the bottom oil temperature rise over ambient temperature has been calculated as
n
l
l
r
fl
u
R
R
I
)
1
1
(
2
+
+
⋅
= 
 (13)
Where u is the bottom oil temperature rise over ambient temperature, fl is the full load bottom
oil temperature rise over ambient temperature obtained from an off-line test, Rl is the ratio of load
loss at rated load to no-load loss. The variable Ir is the ratio of the specified load to rated load.
rated
r
I
I
I = (14)
The exponent n depends upon the cooling state. The loading guide recommends the use of n=0.8
for natural convection and n=0.9-1.0 for forced cooling.
3. RESULTS AND DISCUSSION
A code has been provided for finite difference solution of energy and Navier-Stokes equations
using MATLAB 7.1. Figure 1 shows cross section of a 50KVA, 20KV/400V power transformer
in two dimensions. Dimensions and specifications of the power transformer have been
summarized in Table 2. Table 3 shows the power transformer losses.
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
5
Figure1. Three phase power transformer in two dimensions
Table2. Dimensions and specifications of the proposed power transformer
Core diameter (cm) 10
Width of each window (cm) 12
Height of window (cm) 28
Thickness of LV winding (cm) 1.2
Thickness of HV winding (cm) 2
Rated power 50KVA
HV voltage 20kV
LV voltage 400V
HV current 1.44A
LV current 72A
Table3. Power transformer losses
Losses (w) Value
Core 158
DC of LV windings 384
DC of HV windings 534
Eddy currents of LV windings 64
Eddy currents of HV windings -
We assume that inlet oil temperature is the temperature base. Therefore, we have
(15)
100
,
,
×
−
=
∆
oil
b
oil
b
T
T
T
T
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
6
Where Tb,oil is the bottom oil temperature. Figure 2 shows temperature distribution from LV
winding (axis symmetry in height direction) in one per unit (p.u.) load with oil natural cooling
(ON). It can be pointed out that for LV winding, maximum temperature location is around 80%
of winding height from the bottom and at about 50% of radial thickness of the layer. Temperature
distribution from HV winding has been shown in figure 3. It can be observed that the maximum
temperature occurs in the neighborhood of 55% of the axial and 50% of the radial thickness of the
layer.
0 0.05 0.1 0.15 0.2
32
34
36
38
40
42
Height of LV winding(m)
HST
rise
over
bottom
oil
temperature(%)
Figure2. Temperature distribution in height direction of LV winding with transformer oil natural cooling
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
7
0 0.05 0.1 0.15 0.2
44
46
48
50
52
54
56
58
60
62
64
Height of HV winding(m)
HST
rise
over
bottom
oil
temperature(%)
Figure3. Temperature distribution in height direction of HV winding with transformer oil natural cooling
Figure 4 shows HST rise over bottom oil temperature versus load for two types of oils and
figure 5 shows HST versus load at Tamb=25(°C).
0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5
40
50
60
70
80
90
100
110
120
Load(p.u.)
HST
rise
over
bottom
oil
temperature(%)
Transformer oil
Silicon oil
Figure4. HST rise over bottom oil temperature versus load at Tamb=25(°C) with oil natural cooling
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
8
0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5
60
70
80
90
100
110
120
130
140
150
Load(p.u.)
HST(°C) Transformer oil
Silicon oil
Figure5. HST versus load at Tamb=25(°C) with oil natural cooling
It can be pointed out from figures 4 and 5 that the HST value is low when the transformer oil is
used for cooling, therefore the transformer oil is better than silicon oil in the cooling of the power
transformer when load changes. Table 4 shows comparison of the proposed method with finite
integral transform used in [10] for power transformer oil. HST locations at different loading are
given in Table 5.
Table4. HST (°C) magnitudes at Tamb=25(°C)
Load (p.u.) Proposed Analytical [10]
0.6 51.72 53
0.7 58.35 56
0.8 65.71 66
0.9 73.78 75
1.0 82.54 80
1.1 91.99 93
1.2 102.15 101
1.3 113.01 115
1.4 124.59 125
1.5 136.91 139
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
9
Table5. HST locations at Tamb=25(°C)
Load (p.u.)
Proposed (radial thickness%-
height%)
Analytical [10] (radial thickness%-
height%)
0.6 50 / 54.17 44 / 52
0.7 50 / 54.17 45 / 53.5
0.8 50 / 54.58 46 / 54
0.9 50 / 54.58 48 / 54.5
1.0 50 / 55 50 / 55
1.1 50 / 55 50 / 55
1.2 50 / 55.42 50 / 55
1.3 50 / 55.42 50 / 55
1.4 50 / 55.42 50 / 55.5
1.5 50 / 55.42 50 / 55.5
Reference [10] has proposed an analytical method based on boundary value problem of heat
conduction in power transformer winding using finite integral transform techniques. This
technique uses Fourier transform and Hankel transform and finds temperature based on
polynomials with infinite order (sequential series) of space variables and time, and then
approximates temperature with finite order. Analytical method in [10] is suitable for cylindrical
winding with rectangle cross-section, but this limitation is not for finite difference method. In the
other hand, if we assume that we can increase order of polynomial, solution time will rise and
analytical method will not differ with numerical method.
4. CONCLUSION
A numerical study was conducted to investigate temperature distribution in layer-type power
transformer for a variety of load conditions and type of oil. On the other hand, an attempt has
been made to suggest a method to improve the accuracy of prediction of the temperature of the
hottest spot in power transformer. Heat transfer partial differential equations were solved
numerically with finite difference method. The heat source function has been taken as
temperature dependent and has been directly incorporated in the heat conduction equation for
core and windings. The purely numerical approach followed in this paper seems to correspond
reasonably well with results of analytical calculations [10]. In addition, it can be pointed out that
transformer oil is better than silicon oil in cooling of the power transformer when load changes.
NOMENCLATURE
Cp : specific heat of oil (J.kg-1
.K-1
)
g: gravitational acceleration (m.s-2
)
Ir: ratio of the specified load to rated load
k: thermal conductivity of oil (W.m-1
.K-1
)
K: equivalent thermal conductivity (W.m-1
.K-1
)
kcu : thermal conductivity of copper (W.m-1
.K-1
)
kin : thermal conductivity of insulation (W.m-1
.K-1
)
kx : thermal conductivity in x direction (W.m-1
.K-1
)
ky : thermal conductivity in y direction (W.m-1
.K-1
)
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
10
n : temperature rise exponent due to bottom oil
P: pressure (N.m-2
)
Q : volumetric heat source function (W.m-3
)
Q0: reference volumetric heat source (W.m-3
)
ri’s : radius of insulation and conductor layers (m)
Rl : loss ratio = load loss/no load loss
T: temperature (K)
Tref : reference temperature (K)
Tb,oi : bottom oil temperature (K)
tcu: thickness of conductor (m)
tin : thickness of insulation (m)
Vx: velocity in x direction (m.s-1
)
Vy: velocity in y direction (m.s-1
)
Abbreviations
HST: hottest spot temperature
HV: high voltage
LV: low voltage
ON: oil natural cooling
p.u.: per unit
Greek symbols
 : coefficient of volumetric expansion of oil (K-1
)
u : bottom oil temperature rise over ambient temperature (K)
fl: bottom oil temperature rise over ambient temperature at rated load (K)
 : density of oil (kg.m-3
)
0: reference density of oil (kg.m-3
)
c : temperature coefficient of electrical resistance (K-1
)
 : viscosity of oil (kg.m-1
.s-1
)
REFERENCES
[1] L. W. Pierce, (1992) “An investigation of the thermal performance of an oil filled transformer
winding,” IEEE Transactions on Power Delivery, 7(3), pp. 1347-1358.
[2] L. W. Pierce, (1994) “Predicting liquid filled transformer loading capability,” IEEE Transactions on
Industry Applications, 30(1), pp. 170–178.
[3] IEC Standard, IEC60076-7 (2006) "Loading guide for oil immersed transformers".
[4] IEEE Standard, C57.91-1995 (1996) "IEEE guide for loading mineral oil immersed transformer".
[5] IEEE Standard, 1538-2000 (2000) "IEEE guide for determination of maximum winding temperature
rise in liquid-filled transformers".
[6] Z. Radakovic, K. Feser, (2003) “A new method for the calculation of the hot-spot temperature in
power transformers with ONAN cooling”, IEEE Transactions on Power Delivery, 18(4), pp. 1–9.
[7] G. Swift, T. Molinski, W. Lehn, R. Bray, (2001) “A fundamental approach to transformer thermal
modeling—Part I: Theory and equivalent circuit”, IEEE Transactions on Power Delivery, 16(2), pp.
171-175.
[8] W. H. Tang, O. H. Wu ,Z. J. Richardson, (2002) “Equivalent heat circuit based power transformer
thermal model”, IEE Electric Power Application, 149(2), pp. 87-92.
Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014
11
[9] F. P. Incropera, D. P. DeWitt, (1996) “Fundamentals of heat and mass transfer”, 4th edition, New
York/USA: J. Wiley & Sons.
[10] M. K. Pradhan, T. S. Ramu, (2003) “Prediction of hottest spot temperature (HST) in power and
station transformers”, IEEE Transactions on Power Delivery, 18(4), pp. 1275–1283.
[11] M. A. Taghikhani, A. Gholami, (2008) “Temperature Distribution in Power Transformer Windings
with NDOF and DOF Cooling”, PES General Meeting, Pittsburgh, PA, USA, 20-24 July .

Weitere ähnliche Inhalte

Ähnlich wie Layer-Type Power Transformer Thermal Analysis Considering Effective Parameters On The Temperature Rise

Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...
Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...
Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...Nate Werner
 
IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...
IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...
IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...IRJET Journal
 
Optimization of a Shell and Tube Condenser using Numerical Method
Optimization of a Shell and Tube Condenser using Numerical MethodOptimization of a Shell and Tube Condenser using Numerical Method
Optimization of a Shell and Tube Condenser using Numerical MethodIJERA Editor
 
JIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperJIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperAhmed Sohail Izhar
 
Study of the Thermal Behavior of a Synchronous Motor With Permanent Magnets
Study of the Thermal Behavior of a Synchronous Motor With Permanent MagnetsStudy of the Thermal Behavior of a Synchronous Motor With Permanent Magnets
Study of the Thermal Behavior of a Synchronous Motor With Permanent MagnetsCSCJournals
 
Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...
Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...
Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...IJAEMSJORNAL
 
A simplified thermal model for the three way catalytic converter (1)
A simplified thermal model for the three way catalytic converter (1)A simplified thermal model for the three way catalytic converter (1)
A simplified thermal model for the three way catalytic converter (1)Varun Pandey
 
IRJET - Review of Entropy Generation Minimization in Heat Exchanger
IRJET - Review of Entropy Generation Minimization in Heat ExchangerIRJET - Review of Entropy Generation Minimization in Heat Exchanger
IRJET - Review of Entropy Generation Minimization in Heat ExchangerIRJET Journal
 
Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...
Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...
Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...IRJET Journal
 
types of heat exchangers.pdf
types of heat exchangers.pdftypes of heat exchangers.pdf
types of heat exchangers.pdfhassanzain10
 
Stirling Engine Report
Stirling Engine ReportStirling Engine Report
Stirling Engine ReportRobert Harding
 
High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...
High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...
High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...IAES-IJPEDS
 
Heat integration of_crude_organic_distil
Heat integration of_crude_organic_distilHeat integration of_crude_organic_distil
Heat integration of_crude_organic_distilMayurkumarpatil1
 
FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...
FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...
FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...Bishal Bhandari
 
1 s2.0-s1876610209000757-main
1 s2.0-s1876610209000757-main1 s2.0-s1876610209000757-main
1 s2.0-s1876610209000757-mainmanojg1990
 

Ähnlich wie Layer-Type Power Transformer Thermal Analysis Considering Effective Parameters On The Temperature Rise (20)

Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...
Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...
Numerical_Analysis_of_Turbulent_Momentum_and_Heat_Transfer_in_a_Rectangular_H...
 
IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...
IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...
IRJET- Calculating BLDC Stator Temperature and Relationships with Other Param...
 
Optimization of a Shell and Tube Condenser using Numerical Method
Optimization of a Shell and Tube Condenser using Numerical MethodOptimization of a Shell and Tube Condenser using Numerical Method
Optimization of a Shell and Tube Condenser using Numerical Method
 
C341518
C341518C341518
C341518
 
JIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperJIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference Paper
 
Study of the Thermal Behavior of a Synchronous Motor With Permanent Magnets
Study of the Thermal Behavior of a Synchronous Motor With Permanent MagnetsStudy of the Thermal Behavior of a Synchronous Motor With Permanent Magnets
Study of the Thermal Behavior of a Synchronous Motor With Permanent Magnets
 
Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...
Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...
Simulation and Optimization of Cooling Tubes of Transformer for Efficient Hea...
 
A simplified thermal model for the three way catalytic converter (1)
A simplified thermal model for the three way catalytic converter (1)A simplified thermal model for the three way catalytic converter (1)
A simplified thermal model for the three way catalytic converter (1)
 
J010337176
J010337176J010337176
J010337176
 
Module 2.pptx
Module 2.pptxModule 2.pptx
Module 2.pptx
 
IRJET - Review of Entropy Generation Minimization in Heat Exchanger
IRJET - Review of Entropy Generation Minimization in Heat ExchangerIRJET - Review of Entropy Generation Minimization in Heat Exchanger
IRJET - Review of Entropy Generation Minimization in Heat Exchanger
 
Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...
Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...
Experimental Studies on Pool Boiling Heat Transfer Using Alumina and Graphene...
 
types of heat exchangers.pdf
types of heat exchangers.pdftypes of heat exchangers.pdf
types of heat exchangers.pdf
 
Stirling Engine Report
Stirling Engine ReportStirling Engine Report
Stirling Engine Report
 
High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...
High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...
High Power Density Multi-Mosfet-Based Series Resonant Inverter for Induction ...
 
Heat integration of_crude_organic_distil
Heat integration of_crude_organic_distilHeat integration of_crude_organic_distil
Heat integration of_crude_organic_distil
 
slides
slidesslides
slides
 
C1303071722
C1303071722C1303071722
C1303071722
 
FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...
FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...
FABRICATION OF EXPERIMENTAL SETUP TO EVALUATE CONVECTIVE HEAT TRANSFER COEFFI...
 
1 s2.0-s1876610209000757-main
1 s2.0-s1876610209000757-main1 s2.0-s1876610209000757-main
1 s2.0-s1876610209000757-main
 

Mehr von AEIJjournal2

DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...
DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...
DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...AEIJjournal2
 
Direct Alcohol Alkaline Fuel Cell as Future Prospectus
Direct Alcohol Alkaline Fuel Cell as Future ProspectusDirect Alcohol Alkaline Fuel Cell as Future Prospectus
Direct Alcohol Alkaline Fuel Cell as Future ProspectusAEIJjournal2
 
COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...
COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...
COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...AEIJjournal2
 
FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...
FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...
FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...AEIJjournal2
 
GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...
GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...
GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...AEIJjournal2
 
ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS
ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS
ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS AEIJjournal2
 
STUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLS
STUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLSSTUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLS
STUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLSAEIJjournal2
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...AEIJjournal2
 
A Review on RDB to RDF Mapping for Semantic Web
A Review on RDB to RDF Mapping for Semantic WebA Review on RDB to RDF Mapping for Semantic Web
A Review on RDB to RDF Mapping for Semantic WebAEIJjournal2
 
Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...
Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...
Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...AEIJjournal2
 
SIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICON
SIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICONSIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICON
SIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICONAEIJjournal2
 
DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...
DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...
DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...AEIJjournal2
 
EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...
EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...
EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...AEIJjournal2
 
Co integration Relationship Between Economic Growth, Export and Electricity C...
Co integration Relationship Between Economic Growth, Export and Electricity C...Co integration Relationship Between Economic Growth, Export and Electricity C...
Co integration Relationship Between Economic Growth, Export and Electricity C...AEIJjournal2
 
Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...
Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...
Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...AEIJjournal2
 
Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...
Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...
Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...AEIJjournal2
 
The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...
The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...
The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...AEIJjournal2
 
A MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEM
A MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEMA MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEM
A MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEMAEIJjournal2
 
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...AEIJjournal2
 
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...AEIJjournal2
 

Mehr von AEIJjournal2 (20)

DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...
DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...
DYNAMICS IN THE HISTORY AND ECONOMIC DEVELOPMENT OF MAN: REFOCUSING ON ECOLOG...
 
Direct Alcohol Alkaline Fuel Cell as Future Prospectus
Direct Alcohol Alkaline Fuel Cell as Future ProspectusDirect Alcohol Alkaline Fuel Cell as Future Prospectus
Direct Alcohol Alkaline Fuel Cell as Future Prospectus
 
COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...
COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...
COMPARING ECONOMIC FEASIBILITY OF DOMESTIC SOLAR WATER HEATER INSTALLATION IN...
 
FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...
FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...
FREE CONVECTION HEAT TRANSFER OF NANOFLUIDS FROM A HORIZONTAL PLATE EMBEDDED ...
 
GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...
GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...
GDQ SIMULATION FOR FLOW AND HEAT TRANSFER OF A NANOFLUID OVER A NONLINEARLY S...
 
ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS
ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS
ASSESSING PERCEPTUAL VIDEO QUALITY IN WIMAX NETWORKS
 
STUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLS
STUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLSSTUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLS
STUDY OF THE EQUIVALENT CIRCUIT OF A DYESENSITIZED SOLAR CELLS
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
 
A Review on RDB to RDF Mapping for Semantic Web
A Review on RDB to RDF Mapping for Semantic WebA Review on RDB to RDF Mapping for Semantic Web
A Review on RDB to RDF Mapping for Semantic Web
 
Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...
Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...
Dynamics in the History and Economic Development of Man: Refocusing on Ecolog...
 
SIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICON
SIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICONSIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICON
SIMULATION OF THE SOLAR CELLS WITH PC1D, APPLICATION TO CELLS BASED ON SILICON
 
DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...
DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...
DESIGN AND DEVELOPMENT OF WIND TURBINE EMULATOR TO OPERATE WITH 1.5KW INDUCTI...
 
EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...
EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...
EVALUATING MATHEMATICAL HEAT TRANSFER EFFECTIVENESS EQUATIONS USING CFD TECHN...
 
Co integration Relationship Between Economic Growth, Export and Electricity C...
Co integration Relationship Between Economic Growth, Export and Electricity C...Co integration Relationship Between Economic Growth, Export and Electricity C...
Co integration Relationship Between Economic Growth, Export and Electricity C...
 
Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...
Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...
Effect of Zn Concentration On Structural and Optical Proprieties Of ZNO Thin ...
 
Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...
Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...
Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet...
 
The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...
The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...
The Force Convection Heat Transfer of A Nanofluid Over A Flat Plate: Using Th...
 
A MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEM
A MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEMA MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEM
A MODIFIED ANT COLONY ALGORITHM FOR SOLVING THE UNIT COMMITMENT PROBLEM
 
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
 
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
Impedance Spectroscopy Analysis of a Liquid Tin Anode Fuel Cell in Voltage Re...
 

Kürzlich hochgeladen

❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.
❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.
❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.Nitya salvi
 
Zoology 4th semester series (krishna).pdf
Zoology 4th semester series (krishna).pdfZoology 4th semester series (krishna).pdf
Zoology 4th semester series (krishna).pdfSumit Kumar yadav
 
Botany 4th semester series (krishna).pdf
Botany 4th semester series (krishna).pdfBotany 4th semester series (krishna).pdf
Botany 4th semester series (krishna).pdfSumit Kumar yadav
 
Bacterial Identification and Classifications
Bacterial Identification and ClassificationsBacterial Identification and Classifications
Bacterial Identification and ClassificationsAreesha Ahmad
 
Pests of cotton_Sucking_Pests_Dr.UPR.pdf
Pests of cotton_Sucking_Pests_Dr.UPR.pdfPests of cotton_Sucking_Pests_Dr.UPR.pdf
Pests of cotton_Sucking_Pests_Dr.UPR.pdfPirithiRaju
 
GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...
GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...
GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...Lokesh Kothari
 
High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...
High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...
High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...chandars293
 
Pests of mustard_Identification_Management_Dr.UPR.pdf
Pests of mustard_Identification_Management_Dr.UPR.pdfPests of mustard_Identification_Management_Dr.UPR.pdf
Pests of mustard_Identification_Management_Dr.UPR.pdfPirithiRaju
 
COST ESTIMATION FOR A RESEARCH PROJECT.pptx
COST ESTIMATION FOR A RESEARCH PROJECT.pptxCOST ESTIMATION FOR A RESEARCH PROJECT.pptx
COST ESTIMATION FOR A RESEARCH PROJECT.pptxFarihaAbdulRasheed
 
Pulmonary drug delivery system M.pharm -2nd sem P'ceutics
Pulmonary drug delivery system M.pharm -2nd sem P'ceuticsPulmonary drug delivery system M.pharm -2nd sem P'ceutics
Pulmonary drug delivery system M.pharm -2nd sem P'ceuticssakshisoni2385
 
GBSN - Microbiology (Unit 1)
GBSN - Microbiology (Unit 1)GBSN - Microbiology (Unit 1)
GBSN - Microbiology (Unit 1)Areesha Ahmad
 
Animal Communication- Auditory and Visual.pptx
Animal Communication- Auditory and Visual.pptxAnimal Communication- Auditory and Visual.pptx
Animal Communication- Auditory and Visual.pptxUmerFayaz5
 
Biopesticide (2).pptx .This slides helps to know the different types of biop...
Biopesticide (2).pptx  .This slides helps to know the different types of biop...Biopesticide (2).pptx  .This slides helps to know the different types of biop...
Biopesticide (2).pptx .This slides helps to know the different types of biop...RohitNehra6
 
Hire 💕 9907093804 Hooghly Call Girls Service Call Girls Agency
Hire 💕 9907093804 Hooghly Call Girls Service Call Girls AgencyHire 💕 9907093804 Hooghly Call Girls Service Call Girls Agency
Hire 💕 9907093804 Hooghly Call Girls Service Call Girls AgencySheetal Arora
 
Chemical Tests; flame test, positive and negative ions test Edexcel Internati...
Chemical Tests; flame test, positive and negative ions test Edexcel Internati...Chemical Tests; flame test, positive and negative ions test Edexcel Internati...
Chemical Tests; flame test, positive and negative ions test Edexcel Internati...ssuser79fe74
 
Nanoparticles synthesis and characterization​ ​
Nanoparticles synthesis and characterization​  ​Nanoparticles synthesis and characterization​  ​
Nanoparticles synthesis and characterization​ ​kaibalyasahoo82800
 
Recombinant DNA technology (Immunological screening)
Recombinant DNA technology (Immunological screening)Recombinant DNA technology (Immunological screening)
Recombinant DNA technology (Immunological screening)PraveenaKalaiselvan1
 
Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...
Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...
Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...Monika Rani
 
Recombination DNA Technology (Nucleic Acid Hybridization )
Recombination DNA Technology (Nucleic Acid Hybridization )Recombination DNA Technology (Nucleic Acid Hybridization )
Recombination DNA Technology (Nucleic Acid Hybridization )aarthirajkumar25
 

Kürzlich hochgeladen (20)

❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.
❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.
❤Jammu Kashmir Call Girls 8617697112 Personal Whatsapp Number 💦✅.
 
Zoology 4th semester series (krishna).pdf
Zoology 4th semester series (krishna).pdfZoology 4th semester series (krishna).pdf
Zoology 4th semester series (krishna).pdf
 
Botany 4th semester series (krishna).pdf
Botany 4th semester series (krishna).pdfBotany 4th semester series (krishna).pdf
Botany 4th semester series (krishna).pdf
 
Bacterial Identification and Classifications
Bacterial Identification and ClassificationsBacterial Identification and Classifications
Bacterial Identification and Classifications
 
Pests of cotton_Sucking_Pests_Dr.UPR.pdf
Pests of cotton_Sucking_Pests_Dr.UPR.pdfPests of cotton_Sucking_Pests_Dr.UPR.pdf
Pests of cotton_Sucking_Pests_Dr.UPR.pdf
 
GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...
GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...
GUIDELINES ON SIMILAR BIOLOGICS Regulatory Requirements for Marketing Authori...
 
High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...
High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...
High Class Escorts in Hyderabad ₹7.5k Pick Up & Drop With Cash Payment 969456...
 
Pests of mustard_Identification_Management_Dr.UPR.pdf
Pests of mustard_Identification_Management_Dr.UPR.pdfPests of mustard_Identification_Management_Dr.UPR.pdf
Pests of mustard_Identification_Management_Dr.UPR.pdf
 
COST ESTIMATION FOR A RESEARCH PROJECT.pptx
COST ESTIMATION FOR A RESEARCH PROJECT.pptxCOST ESTIMATION FOR A RESEARCH PROJECT.pptx
COST ESTIMATION FOR A RESEARCH PROJECT.pptx
 
Pulmonary drug delivery system M.pharm -2nd sem P'ceutics
Pulmonary drug delivery system M.pharm -2nd sem P'ceuticsPulmonary drug delivery system M.pharm -2nd sem P'ceutics
Pulmonary drug delivery system M.pharm -2nd sem P'ceutics
 
GBSN - Microbiology (Unit 1)
GBSN - Microbiology (Unit 1)GBSN - Microbiology (Unit 1)
GBSN - Microbiology (Unit 1)
 
Animal Communication- Auditory and Visual.pptx
Animal Communication- Auditory and Visual.pptxAnimal Communication- Auditory and Visual.pptx
Animal Communication- Auditory and Visual.pptx
 
Biopesticide (2).pptx .This slides helps to know the different types of biop...
Biopesticide (2).pptx  .This slides helps to know the different types of biop...Biopesticide (2).pptx  .This slides helps to know the different types of biop...
Biopesticide (2).pptx .This slides helps to know the different types of biop...
 
Hire 💕 9907093804 Hooghly Call Girls Service Call Girls Agency
Hire 💕 9907093804 Hooghly Call Girls Service Call Girls AgencyHire 💕 9907093804 Hooghly Call Girls Service Call Girls Agency
Hire 💕 9907093804 Hooghly Call Girls Service Call Girls Agency
 
Chemical Tests; flame test, positive and negative ions test Edexcel Internati...
Chemical Tests; flame test, positive and negative ions test Edexcel Internati...Chemical Tests; flame test, positive and negative ions test Edexcel Internati...
Chemical Tests; flame test, positive and negative ions test Edexcel Internati...
 
Nanoparticles synthesis and characterization​ ​
Nanoparticles synthesis and characterization​  ​Nanoparticles synthesis and characterization​  ​
Nanoparticles synthesis and characterization​ ​
 
Recombinant DNA technology (Immunological screening)
Recombinant DNA technology (Immunological screening)Recombinant DNA technology (Immunological screening)
Recombinant DNA technology (Immunological screening)
 
Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...
Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...
Vip profile Call Girls In Lonavala 9748763073 For Genuine Sex Service At Just...
 
CELL -Structural and Functional unit of life.pdf
CELL -Structural and Functional unit of life.pdfCELL -Structural and Functional unit of life.pdf
CELL -Structural and Functional unit of life.pdf
 
Recombination DNA Technology (Nucleic Acid Hybridization )
Recombination DNA Technology (Nucleic Acid Hybridization )Recombination DNA Technology (Nucleic Acid Hybridization )
Recombination DNA Technology (Nucleic Acid Hybridization )
 

Layer-Type Power Transformer Thermal Analysis Considering Effective Parameters On The Temperature Rise

  • 1. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 1 Layer-Type Power Transformer Thermal Analysis Considering Effective Parameters On The Temperature Rise M.Ghanbaria , M.A.Taghikhanib a Department of Electrical and Computer Engineering, Saveh Branch, Islamic Azad University, Saveh, Iran b Department of Engineering, Imam Khomeini International University, Qazvin, Iran ABSTRACT Since large power transformers belong to the most valuable assets in electrical power networks it is suitable to pay higher attention to these operating resources. Thermal impact leads not only to long-term oil/paper-insulation degradation; it is also a limiting factor for the transformer operation. Therefore, the knowledge of the temperature, especially the hottest spot (HST) temperature, is of high interest. This paper presents steady state temperature distribution of a power transformer layer-type winding using conjugated heat transfer analysis, therefore energy and Navier-Stokes equations are solved using finite difference method. Meanwhile, the effects of load conditions and type of oil on HST are investigated using the model. Oil in the transformer is assumed nearly incompressible and oil parameters such as thermal conductivity, special heat, viscosity, and density vary with temperature. Comparing the results with those obtained from finite integral transform checks the validity and accuracy of the proposed method. KEYWORDS Power transformer; Layer-Type Winding; Thermal Analysis; Conjugated Heat Transfer; Finite difference method. 1. INTRODUCTION In a power transformer a part of the electrical energy is converted into the heat. Although this part is quite small comparing to total electric power transferred through a transformer, it causes significant temperature rise, which represents the limiting criteria for possible power transfer through a transformer. That is why the precise calculation of temperatures in critical points (top oil and the hottest solid insulation spot) is of practical interest. Thermal impact leads not only to long-term oil/paper-insulation degradation; it is also a limiting factor for the transformer operation [1], [2]. Therefore, the knowledge of the temperature, especially the hottest spot temperature, is of high interest. If the temperature rise goes beyond the permissible value, the load of transformer must be reduced or an auxiliary transformer is used in order to preserve the insulation from deterioration. For an oil-immersed transformer, the oil surrounds the transformer body. Oil is a nearly incompressible fluid and density changes due to temperature rise, therefore oil moves in the transformer. The heat transferred by convection is the most important method of heat transfer.
  • 2. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 2 Hottest spot temperature must not exceed the prescribed value in order to avoid insulation faults. Furthermore, an accurate computation of the HST helps in a realistic estimation of the reliability and remaining life of the transformer winding insulation. The classical approach has been to consider the hottest-spot temperature as the sum of the ambient temperature, the top-oil temperature rise, and the hottest-spot-to-top-oil temperature gradient. A hottest spot temperature calculation is given in the International Standards [3]-[5]. The algorithm for calculating the hottest spot temperature of a directly loaded transformer using data obtained in a short circuit heating test is given in [6]. Heat transfer theory results from winding to oil are exposed in [7], [8]. The structure of a transformer winding is complex and does not conform to any known geometry in the strict sense. Under general conditions, the transformer windings can be assumed cylindrical; hence, a layer or a disc winding is a finite annular cylinder. The thermal and physical properties of the system would be equivalent to a composite system of insulation and conductor. In this paper, author has proposed a procedure for obtaining the temperature distribution in the power transformer and the effects of load conditions and type of oil are investigated using the model. For this reason energy and Navier-Stokes equations are solved using finite difference method. Therefore, a code has been provided under MATLAB software. The model can be used for temperature calculation on the arbitrary change of current and outside air temperature. In the paper, thermal model, energy, and Navier-Stokes equations are given in section 2. Results and discussion of the proposed work have been provided in section 3. 2. THERMAL MODEL Energy equation for Newtonian incompressible fluid (or nearly incompressible fluid) such as oil in two dimensions is [9] ) ( ) ( ) ) ( ) ( ( y T k y x T k x y T C V x T C V p y p x ∂ ∂ ⋅ ∂ ∂ + ∂ ∂ ⋅ ∂ ∂ = ∂ ⋅ ∂ + ∂ ⋅ ∂ ⋅  (1) Where T is temperature, Vx is velocity in x direction, Vy is velocity in y direction, k is thermal conductivity,  is density and Cp is special heat of the oil in the transformer. In equation (1), oil properties vary with temperature [1], [10], [11]. The temperature dependence of oil properties are given as follows: ) 273 exp( 2 1 + ⋅ = T a a  (2) T a a C p ⋅ + = 4 3 (3) T a a ⋅ + = 6 5  (4) T a a k ⋅ + = 8 7 (5) 9 a =  (6) Where : is viscosity and  is volumetric expansion coefficient. The nine constants for transformer oil and silicon oil have been listed in Table 1 [3, 4]. It is generally valid for all types of transformer oil that the variation of the oil viscosity with temperature is much higher than the variation of other oil properties [11]. Thus, all oil physical properties except the viscosity can be
  • 3. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 3 replaced by a constant. However, the variations of all oil properties with temperature have been considered in this paper. Table1. Oil constants Oil constant Transformer oil Silicon oil a1 0.0000013573 0.00012127 a2 2797.3 1782.3 a3 1960 1424 a4 4.005 2.513 a5 887 989 a6 -0.659 -0.870 a7 0.124 0.138 a8 -0.0001525 -0.00009621 a9 0.00086 0.00095 In (1) velocity is unknown, and then we must solve Navier-Stokes equations. Navier-Stokes equations in two dimensions for Newtonian incompressible fluid are [9] Continuity Equation: 0 = ∂ ∂ + ∂ ∂ y V x V y x (7) Momentum Equations: )) ( ) 2 ( ( ) .( x V y V y x V x x P y V V x V V y x x x y x x ∂ ∂ ⋅ + ∂ ∂ ⋅ ∂ ∂ + ∂ ∂ ⋅ ⋅ ∂ ∂ + ∂ ∂ − = ∂ ∂ + ∂ ∂     (8) ) ( )) 2 ( ) ( ( ) .( 0 ref y y x x y x x T T g y V y x V y V x y P y V V x V V − ⋅ ⋅ ⋅ + ∂ ∂ ⋅ ⋅ ∂ ∂ + ∂ ∂ ⋅ + ∂ ∂ ⋅ ∂ ∂ + ∂ ∂ − = ∂ ∂ + ∂ ∂       (9) Where P is pressure and g is gravitational acceleration .The heat conduction equation for core and windings is written [10], [11] 0 2 2 2 2 = + ∂ ∂ ⋅ + ∂ ∂ ⋅ Q y T k x T k y x (10) Where kx and ky are thermal conductivity in x and y directions respectively. The term Q is the volumetric heat source function and has been modified here to take care of variation of electrical resistance of copper with temperature. The heat source term Q can be of the form )] ( 1 [ 0 ref c T T Q Q − ⋅ + ⋅ =  (11)
  • 4. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 4 Where c is the temperature coefficient of electrical resistance of copper wire. With this representation, the function Q becomes temperature dependent, distributed heat source. Thermal conductivities are unequal in different directions. Thermal conductivity has been treated as a vector quantity, having components in both radial and axial direction. Resultant thermal conductivity of the system is [10] 2 2 y x k k K + = (12) Where ) log ... log log ( log 1 2 2 3 1 1 2 1 n n n n x k r r k r r k r r r r k − + + + = in cu cu in in cu in cu y k t k t t t k k k ⋅ + ⋅ + ⋅ ⋅ = ) ( Term K represents resultant thermal conductivity of insulation and conductor system. In this paper, the bottom oil temperature rise over ambient temperature has been calculated as n l l r fl u R R I ) 1 1 ( 2 + + ⋅ =   (13) Where u is the bottom oil temperature rise over ambient temperature, fl is the full load bottom oil temperature rise over ambient temperature obtained from an off-line test, Rl is the ratio of load loss at rated load to no-load loss. The variable Ir is the ratio of the specified load to rated load. rated r I I I = (14) The exponent n depends upon the cooling state. The loading guide recommends the use of n=0.8 for natural convection and n=0.9-1.0 for forced cooling. 3. RESULTS AND DISCUSSION A code has been provided for finite difference solution of energy and Navier-Stokes equations using MATLAB 7.1. Figure 1 shows cross section of a 50KVA, 20KV/400V power transformer in two dimensions. Dimensions and specifications of the power transformer have been summarized in Table 2. Table 3 shows the power transformer losses.
  • 5. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 5 Figure1. Three phase power transformer in two dimensions Table2. Dimensions and specifications of the proposed power transformer Core diameter (cm) 10 Width of each window (cm) 12 Height of window (cm) 28 Thickness of LV winding (cm) 1.2 Thickness of HV winding (cm) 2 Rated power 50KVA HV voltage 20kV LV voltage 400V HV current 1.44A LV current 72A Table3. Power transformer losses Losses (w) Value Core 158 DC of LV windings 384 DC of HV windings 534 Eddy currents of LV windings 64 Eddy currents of HV windings - We assume that inlet oil temperature is the temperature base. Therefore, we have (15) 100 , , × − = ∆ oil b oil b T T T T
  • 6. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 6 Where Tb,oil is the bottom oil temperature. Figure 2 shows temperature distribution from LV winding (axis symmetry in height direction) in one per unit (p.u.) load with oil natural cooling (ON). It can be pointed out that for LV winding, maximum temperature location is around 80% of winding height from the bottom and at about 50% of radial thickness of the layer. Temperature distribution from HV winding has been shown in figure 3. It can be observed that the maximum temperature occurs in the neighborhood of 55% of the axial and 50% of the radial thickness of the layer. 0 0.05 0.1 0.15 0.2 32 34 36 38 40 42 Height of LV winding(m) HST rise over bottom oil temperature(%) Figure2. Temperature distribution in height direction of LV winding with transformer oil natural cooling
  • 7. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 7 0 0.05 0.1 0.15 0.2 44 46 48 50 52 54 56 58 60 62 64 Height of HV winding(m) HST rise over bottom oil temperature(%) Figure3. Temperature distribution in height direction of HV winding with transformer oil natural cooling Figure 4 shows HST rise over bottom oil temperature versus load for two types of oils and figure 5 shows HST versus load at Tamb=25(°C). 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 40 50 60 70 80 90 100 110 120 Load(p.u.) HST rise over bottom oil temperature(%) Transformer oil Silicon oil Figure4. HST rise over bottom oil temperature versus load at Tamb=25(°C) with oil natural cooling
  • 8. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 8 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 60 70 80 90 100 110 120 130 140 150 Load(p.u.) HST(°C) Transformer oil Silicon oil Figure5. HST versus load at Tamb=25(°C) with oil natural cooling It can be pointed out from figures 4 and 5 that the HST value is low when the transformer oil is used for cooling, therefore the transformer oil is better than silicon oil in the cooling of the power transformer when load changes. Table 4 shows comparison of the proposed method with finite integral transform used in [10] for power transformer oil. HST locations at different loading are given in Table 5. Table4. HST (°C) magnitudes at Tamb=25(°C) Load (p.u.) Proposed Analytical [10] 0.6 51.72 53 0.7 58.35 56 0.8 65.71 66 0.9 73.78 75 1.0 82.54 80 1.1 91.99 93 1.2 102.15 101 1.3 113.01 115 1.4 124.59 125 1.5 136.91 139
  • 9. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 9 Table5. HST locations at Tamb=25(°C) Load (p.u.) Proposed (radial thickness%- height%) Analytical [10] (radial thickness%- height%) 0.6 50 / 54.17 44 / 52 0.7 50 / 54.17 45 / 53.5 0.8 50 / 54.58 46 / 54 0.9 50 / 54.58 48 / 54.5 1.0 50 / 55 50 / 55 1.1 50 / 55 50 / 55 1.2 50 / 55.42 50 / 55 1.3 50 / 55.42 50 / 55 1.4 50 / 55.42 50 / 55.5 1.5 50 / 55.42 50 / 55.5 Reference [10] has proposed an analytical method based on boundary value problem of heat conduction in power transformer winding using finite integral transform techniques. This technique uses Fourier transform and Hankel transform and finds temperature based on polynomials with infinite order (sequential series) of space variables and time, and then approximates temperature with finite order. Analytical method in [10] is suitable for cylindrical winding with rectangle cross-section, but this limitation is not for finite difference method. In the other hand, if we assume that we can increase order of polynomial, solution time will rise and analytical method will not differ with numerical method. 4. CONCLUSION A numerical study was conducted to investigate temperature distribution in layer-type power transformer for a variety of load conditions and type of oil. On the other hand, an attempt has been made to suggest a method to improve the accuracy of prediction of the temperature of the hottest spot in power transformer. Heat transfer partial differential equations were solved numerically with finite difference method. The heat source function has been taken as temperature dependent and has been directly incorporated in the heat conduction equation for core and windings. The purely numerical approach followed in this paper seems to correspond reasonably well with results of analytical calculations [10]. In addition, it can be pointed out that transformer oil is better than silicon oil in cooling of the power transformer when load changes. NOMENCLATURE Cp : specific heat of oil (J.kg-1 .K-1 ) g: gravitational acceleration (m.s-2 ) Ir: ratio of the specified load to rated load k: thermal conductivity of oil (W.m-1 .K-1 ) K: equivalent thermal conductivity (W.m-1 .K-1 ) kcu : thermal conductivity of copper (W.m-1 .K-1 ) kin : thermal conductivity of insulation (W.m-1 .K-1 ) kx : thermal conductivity in x direction (W.m-1 .K-1 ) ky : thermal conductivity in y direction (W.m-1 .K-1 )
  • 10. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 10 n : temperature rise exponent due to bottom oil P: pressure (N.m-2 ) Q : volumetric heat source function (W.m-3 ) Q0: reference volumetric heat source (W.m-3 ) ri’s : radius of insulation and conductor layers (m) Rl : loss ratio = load loss/no load loss T: temperature (K) Tref : reference temperature (K) Tb,oi : bottom oil temperature (K) tcu: thickness of conductor (m) tin : thickness of insulation (m) Vx: velocity in x direction (m.s-1 ) Vy: velocity in y direction (m.s-1 ) Abbreviations HST: hottest spot temperature HV: high voltage LV: low voltage ON: oil natural cooling p.u.: per unit Greek symbols  : coefficient of volumetric expansion of oil (K-1 ) u : bottom oil temperature rise over ambient temperature (K) fl: bottom oil temperature rise over ambient temperature at rated load (K)  : density of oil (kg.m-3 ) 0: reference density of oil (kg.m-3 ) c : temperature coefficient of electrical resistance (K-1 )  : viscosity of oil (kg.m-1 .s-1 ) REFERENCES [1] L. W. Pierce, (1992) “An investigation of the thermal performance of an oil filled transformer winding,” IEEE Transactions on Power Delivery, 7(3), pp. 1347-1358. [2] L. W. Pierce, (1994) “Predicting liquid filled transformer loading capability,” IEEE Transactions on Industry Applications, 30(1), pp. 170–178. [3] IEC Standard, IEC60076-7 (2006) "Loading guide for oil immersed transformers". [4] IEEE Standard, C57.91-1995 (1996) "IEEE guide for loading mineral oil immersed transformer". [5] IEEE Standard, 1538-2000 (2000) "IEEE guide for determination of maximum winding temperature rise in liquid-filled transformers". [6] Z. Radakovic, K. Feser, (2003) “A new method for the calculation of the hot-spot temperature in power transformers with ONAN cooling”, IEEE Transactions on Power Delivery, 18(4), pp. 1–9. [7] G. Swift, T. Molinski, W. Lehn, R. Bray, (2001) “A fundamental approach to transformer thermal modeling—Part I: Theory and equivalent circuit”, IEEE Transactions on Power Delivery, 16(2), pp. 171-175. [8] W. H. Tang, O. H. Wu ,Z. J. Richardson, (2002) “Equivalent heat circuit based power transformer thermal model”, IEE Electric Power Application, 149(2), pp. 87-92.
  • 11. Advanced Energy: An International Journal (AEIJ), Vol. 1, No. 1, January 2014 11 [9] F. P. Incropera, D. P. DeWitt, (1996) “Fundamentals of heat and mass transfer”, 4th edition, New York/USA: J. Wiley & Sons. [10] M. K. Pradhan, T. S. Ramu, (2003) “Prediction of hottest spot temperature (HST) in power and station transformers”, IEEE Transactions on Power Delivery, 18(4), pp. 1275–1283. [11] M. A. Taghikhani, A. Gholami, (2008) “Temperature Distribution in Power Transformer Windings with NDOF and DOF Cooling”, PES General Meeting, Pittsburgh, PA, USA, 20-24 July .