Vertical-Transportation Design Planning
What manufacturers and architects should be aware of in the planning stages of a building’s
elevatoring
by Samson Rajan Babu
Elevator contractors are quite familiar with
their specialty tasks – they do sales engineering,
negotiate and sell elevators, produce shop
drawings, procure materials, install elevators and
carry out maintenance. However, the
background information (i.e., how a verticaltransportation solution is selected for a new
building project) and the factors that govern
elevator selection (i.e., how the original elevator
layout and specifications came into existence)
remain somewhat hidden. This article provides
an insight into understanding the essential
design efforts that go behind the verticaltransportation planning of any new construction
project. It also intends to help architects
formulate a scientific method of developing,
integrating and verifying a vertical-transportation
system design within their projects.
It is hoped the information presented in this
article will also help elevator contractors
understand tender specifications and drawings
in a better way and be informed and decisive,
while complying with or deviating from a
project requirement. It is also intended to help
elevator contractors properly estimate their
costs and liabilities on a new project and present
attractive value engineering options to their
clients, while increasing their chances of
winning a project.

Applicable Codes
There are applicable building-design codes
for projects based on their geographical location.
These include (but are not limited to)
international-building, life-safety, fire-protection,
seismic, accessibility and local-municipality/
civil-defense codes. While these are mandatory
requirements, the consultant and/or owner

might choose to exceed the minimum
requirements and provide additional/superior
features, such as evacuation communication
systems, evacuation elevators, etc.

Performance Targets
Any new project has owner requirements,
and most established brand owners have their
own vertical-transportation design and
performance requirements. Design requirements
include average interval, average waiting time,
average time to destination, car capacities, and
car and door sizes. While starting a new design
project, consultants should check with the
owners for their published design guidelines. If
this is not available, the consultant should
propose standards based on the international
best design practices and the project’s brand
positioning at the geographical location. This
becomes the “design criteria” for the project.
Widely Used Building Design
Codes
International Building Code
International Fire Code
National Fire Protection
Association Standards
International Mechanical
Code
International Electrical Code
International Plumbing Code
Life Safety Code
National Fire Alarm Code
Accessible Design Standards
Seismic Design Standards
Local Civil Defense Codes
Local Municipality Codes

Elevator-/EscalatorEquipment Safety
Codes
BS/EN 81
BS/EN 115
ASME A17.1
CSA B44
AS 1735
JIS & BSLJ
GB 7588
GB 16899

Widely used building and elevator-/escalator-equipment
safety codes, which are separate from each other.
Continued

112

www.elevatorworld.com • March 2014
Analyzing Population and Vertical Circulation

Elevator Sizes/Capacities

For each type of building project, the population and vertical
circulation of people and material inside the building must be
elaborately studied. This includes types of users, populations on
each upper floor, parking spaces on parking floors, loading docks,
arrival/exit patterns, access-control concepts, bulk arrival
(including transportation for both the public and staff ) scenarios,
interfloor circulation patterns and peak traffic estimation. Main
lobby floors should be identified for arrival. Exit scenarios and the
volume of peak traffic should be estimated using practical and
working knowledge on each building type. Similarly, high-traffic
floors that are not main lobby floors should be identified, and peak
traffic to/from these floors is to be estimated.

Depending on user space requirements, comfort levels and
various code requirements, the most suitable car sizes/capacities
and door sizes should be identified for each elevator group. Even
though an elevator analysis might minimally require smaller
elevators, an architect might select larger elevators to serve the
above requirements. The option to provide a machine room at the
top of the building should also be discussed with an architect in
reference to machine-room-less (MRL) elevators, which may have
different capacities, speed and range.

Elevator Traffic Analysis

Various traffic patterns and peak traffic identified throughout
the day at the building can now be analyzed via calculations or a
Traffic Segregation
simulation. A typical elevator traffic analysis involves assuming
To realize the elevator systems’ maximum efficiency, it is ideal
various elevator operating parameters (door times, passenger
to have dedicated elevator groups for each user type. It also helps
movement times, acceleration, etc.), and such assumptions must
in improving user comfort, access control of protected areas and
match desired car and door sizes. All such assumptions made at
exclusivity for VIP users. However, it may not be economical or
this stage must be practically achievable by any elevator
viable commercially. With this in mind, the conditions that will
manufacturer for the traffic study results to be valid.
allow combining certain user groups are to be reviewed, and
It is very important not to overestimate or underestimate the
minimum required elevator groups (cores) should be proposed.
peak traffic, because this will ultimately result in more or fewer
Once this is agreed upon, the peak traffic is again verified for the
elevators. It should also be noted that the estimated average
combined user types (if any) for each elevator core.
waiting times are only indicative and cannot be repeated on an
actual site. Hence, practical
Bank No
01
02
03
04
knowledge and an exceptional
Lift No.
PL01
PL02
SL01
SL02
PL03
understanding of simulation
Location
Hospital
Hospital
Hospital
Hospital
Accomm
procedures are necessary for a
Front: G
Front: G
Opening
Front
Front
Front
Rear: 1
Rear: 1
vertical-transportation consultant to
Lift Type
Public/Staff
Public/Staff
Service/Staff
Service/Staff
Public/Service
properly guide the architects/design
No. of Floors Served
2
2
2
2
2
team.
Travel approx.
4.5m
4.5m
4.5m
4.5m
3.5m
Various speed, capacity and
Fireman Lift
Yes
quantity combinations should be
Persons
13
13
33
33
17
verified to check if the performance
Capacity (Kg)
1000
1000
2500
2500
1275
meets the design criteria, while
Speed m/s
1.0
1.0
1.0
1.0
keeping in mind the initial and
1.0
maintenance costs for each
1400X1600X2400
Car Size (W X D X H)
1800X2750X2400 1800X2750X2400
1200X2300X2400
(2 opposite entrances)
combination. Vertical dimension
Shaft Size (W X D)
4650X2200
3000X3300
3000X3300
2100X2800
requirements (e.g., pit depth,
overhead and machine-room height)
Door Opening (W X H)
1000X2100
1000X2100
1400X2200
1400X2200
1100X2200
Structural Opening
should be simultaneously considered,
1200X2200
1200X2200
1600X2300
1600X2300
1300X2300
(W X H)
because the required vertical
Door Type
CO
CO
2S
2S
2S
dimensions cannot be provided due
Headroom
4500
4500
4500
4500
4500
to various architectural reasons and
Pit Depth
1600
1600
1700
1700
1700
height restrictions. After careful
Power-Supply
Capacity
20
20
48
48
20
evaluation, the ideal and acceptable
(kVA)
Elev.
elevator groups are to be selected.
Main
Power

Starting
Power (kVA)

32

93

93

32

Breaker
Capacity (A)
Elev.
Lighting
Power

32
40

40

63

63

40

Power-Supply
Capacity
2
(kVA)

2

2

2

2

Breaker
Capacity (A)

20

20

20

20

20

1211

1211

3966

3966

1211

Heat Emission (Kcal/hr.)

An elevator-specification summary sheet

Firefighters’ Elevator

Core Dimensions
Once the elevator groups are
finalized, elevator core sizes should
be planned in such a way that they
accommodate at least three elevator
manufacturers available in the local
market and per the applicable
equipment safety codes. Special
requirements (to accommodate such
Continued

114

www.elevatorworld.com • March 2014
circumstances as building plumb deviations, seismic designs,
fire-rated entrances, wind-shear noise, piston effects, special safety
features, etc.) should also be considered, and the core sizes
increased as necessary. Type of construction for the elevator core
walls is then finalized, considering the structural and fire-code
requirements.
For quick reference, all the elevator groups should be
consolidated onto a spreadsheet showing all relevant dimensions
and specification data. This spreadsheet could be used as a
cross-reference, while verifying the elevator tender response for
the project. Elevator contractors are required to confirm their
compliance or noncompliance to each item on this summary sheet.

Core Layout
Based on the final core dimensions, the elevator cores should be
laid out on the plan drawings. Structural support requirements for
the guide rails, separator beams, trimmer beams, entrance frames,
machines and controllers should be identified, and suitable
provisions should be made for the size and type of construction.
Door structural openings should be approximately shown on the
plans. It is important to note that the location of door structural
openings and front-wall dimensions are approximate. This must be
finalized and constructed based only on the elevator supplier’s
shop drawings.

floor in order to drop the machine to a floor with elevator service,
then move it to the ground floor for future maintenance/
replacement. For MRL elevators, the location of an emergency
rescue panel outside the hoistway should be identified.

Structural Coordination
The structural loads on the guide-rail support system, impact
loads on the pit buffer, reaction loads at the machine room and
lifting-hook capacities should be reviewed, and the structural
frame (reinforced cement concrete (RCC) beam/column/slab/
wall) should be designed to meet the requirements. The structural
fixing (anchoring) requirements for the guide-rail brackets,
machines and other steel elements should be reviewed, and a
suitable substructure (RCC or similar) should be provided. The
size of structural door openings, trap doors and rope holes are to
be compiled, and their impact on the structural stability of the core
wall system should be reviewed by the structural design engineers.

Mechanical Coordination
The mechanical requirements for efficient functioning of the
elevator equipment should be reviewed, and suitable provisions
should be made by the mechanical designers to remove the heat
generated by the elevator equipment and provide suitable ambient
conditions within the machine room. These provisions can include
heating, ventilation, air-conditioning, ducting, routing and
diffusers. Special requirements, such as air-conditioning for the
elevator car, pressurization, stack effect, smoke mitigation and
noise reduction requirements should also be reviewed, and a
matching mechanical design and additional equipment provided to
prevent any detrimental effect on the elevator systems’
performance. Acoustics and vibration characteristics of the
elevator equipment should be reviewed, and suitable coordination
and adjustments may need to be carried out to reduce such
undesirable effects generated by the elevator system.

Electrical Coordination

An elevator core drawing

The electrical requirements for efficient functioning of elevator
equipment should also be reviewed, and suitable provisions
(suitably rated isolators, fuses, fire protection, and cable sizes,
shields, routing and containment) should be made by the electrical
designers to supply the power required by the elevator equipment.
Standby-power requirements should be identified for specific
elevators and suitable provisions made in this stage through
automatic transfer switches to provide generator power to specific
elevators, as well as other building services. The requirement of a
battery-operated automatic rescue device and regenerative drives
for specific elevators should then be reviewed and finalized.
Equipment sensitive to electromagnetic interference (EMI) at the
site should be identified, and the elevator power-supply circuits
should be suitably designed to prevent EMI with such equipment.

Machine-Room Layout

Lighting Coordination

For each elevator core, the machine-room layout should be
finalized, taking the requirements for easy access and safe working
conditions into consideration. Machine-room heights include joist
beams/lifting hooks for maintenance. For heavy machinery, where
possible, a trap door should be included on the machine-room

Normal lighting requirements for the machine room and
emergency-lighting requirements should be reviewed. Suitable
lighting fixtures can then be provided to achieve desired brightness
inside these spaces. Special elevator-car interior lighting and
lighting effects should be reviewed and incorporated.
Continued

116

www.elevatorworld.com • March 2014
Height
Mtrs.

LEVEL

LEVEL

R

R

2

2

4.5

1

1

4.5

G

G

4.5

B1

6

B

PIT

PIT

PIT

PIT

PIT

PIT

PIT

PIT

-

-

-

-

-

-

PIT

PIT

PIT

PIT

PIT

PIT

PIT

PIT

11

12

13

14

15

16

17

18

19

20

21

7

8

9

10

11

12

13

14

15

16

Lift Group

Staff & public

Staff & public

Public

Staff & public

Staff & public

Usage Type

Public

Lift pit

Lift Number

6

Staff & public

10
5

Staff & public

09

Staff & public

08
4

Training wing

07

Service

Public

Public

Public

06
3

Usage
Public

05

Service

04
2

Service

03

Service

02
1

Service

01

Lift Bank

Service

Lift Number

Service

Key:

Staff/public lift
Public lift
Facilities management service lift
R

Roof of building

A riser diagram

Plumbing Coordination
Sump pits required within the elevator
pits should be reviewed and suitable
provisions made for the sump pits (i.e., a
permanent sump pump, simple floor drain or
dry sump pit). Drainage piping design,
routing and containment should be
reviewed, so they do not cause a code
deviation and damage elevator equipment.
Special floor drains required at each elevator
lobby should be evaluated and adopted if
found necessary.

Low-Voltage-Systems
Coordination
Special features and low-voltage systems
linked to the elevator equipment should be
reviewed and suitable cabling with
containment, power supply, mounting
requirements and location of interface
terminals coordinated with relevant vendors.
The systems in question can include remote
monitoring, remote control, building
management, access-control card readers,
closed-circuit TV cameras, media displays,
external dialing means, fire alarms and
smoke detectors.

Architectural and Interior Design
Coordination
Related elevator spaces (shaft, lobbies
and machine rooms) should be reviewed in
parallel with the interior design concepts
and appropriate alignments carried out.
Suitable lobby widths are necessary to
achieve international standards in user
comfort. Elevator-door handing (which side
they open) is to be reviewed in relation to
the surroundings and elevator approach,
after which the most suitable should be
selected. Depending on the front-wall
cladding thickness and floor-finish thickness,
Continued

118

www.elevatorworld.com • March 2014
suitable adjustments can be made to the architectural positioning
of each door opening.
Special attention should be paid to aligning the elevator-door
openings opposite to each other. Placement of hall-call stations,
lanterns, indicators, firefighters’ switches, emergency control
panels (for MRL elevators only) and related equipment regularly
installed at the landings should be reviewed, adjusted and aligned
to achieve the best-looking lobby possible.

Signalization and Signage Coordination
The following is a list of required signalization/signage that
requires coordination with the elevator-installation procedure:
♦ Car and landing call stations
♦ Lighting color

♦
♦
♦
♦
♦

Faceplate color and material
Visual/audible signals
Automated voice messages
Media display schemes
Accessibility and VIP features (on push buttons and signalization)

Accessibility Design Coordination
Every passenger elevator should be reviewed for compliance
with accessibility codes and features. Elevator car sizes that allow
full rotation of wheelchairs, auxiliary car control panels for the
handicapped, maximum height of push buttons from floor level,
and Braille and tactile features on push buttons are examples.
Special accessibility features such as induction loops for the
hearing impaired, voice announcements in the local language and
tactile pavements in the elevator lobby may
be reviewed on a case-to-case basis and
adopted as deemed necessary.

Tender Documents

Our Mission: To educate the public on the safe and proper
use of elevators, escalators and moving walks
through informational programs.

Traditionally, manufacturers estimate
their tender price based on the elevator
specifications (and elevator drawings, if
any). However, it must be noted that
elevator specifications always crossreference various other specifications within
the master specifications. It is recommended
that elevator manufacturers read all relevant
codes and specifications to understand how
the elevator system is required to coordinate
and work with other project equipment and
design concepts.

Conclusion
Request a Safe-T Rider sample kit from EESF online or contact the
Foundation directly.
Read over the information and ask EESF if you have any questions.
Go to your local school or district and talk with the appropriate decision maker about presenting the program.
Contact the Foundation to have material sent to yourself or directly to
the school.
Use the Teacher’s Guide for step-by-step instructions on how to administer the program.
Safe-T Rider costumes are available for rent or purchase, based on availability.

Elevator Escalator Safety Foundation
356 Morgan Ave – Mobile, AL 36606
(800)949-6442 – www.eesf.org – info@eesf.org

120

www.elevatorworld.com • March 2014

While the information in this article
should help architects to exercise a fair
amount of control on vertical-transportation
system design and integration, a qualified
and knowledgeable vertical-transportation
engineer is the only suitable person to
completely manage and control the process
in the best possible manner. The author and
his firm welcome any query from the readers
of this article on any vertical-transportation
system design and will be pleased to offer
🌐
engineering guidance.
Samson Rajan Babu is
technical director at VTME
Vertical Transportation
Systems Consultants in
Dubai. He is a mechanical
engineer specializing in
vertical-transportation
systems and façade-access equipment. Following
his graduation from Anna University in Chennai,
India, in 1994, he worked on many projects in the
Indian and Persian Gulf markets. He can be
contacted at email: sbabu@vtmeconsulting.com.

Weitere ähnliche Inhalte

Ähnlich wie Vtme dubai samson babu article on vertical transportation planning ELEVATOR WORLD MARCH 2014

Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...
Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...
Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...
Yvo Saanen
 
SridharOmmi_Resume
SridharOmmi_ResumeSridharOmmi_Resume
SridharOmmi_Resume
Sridhar Ommi
 
A practical approach for ship construction cost estimation
A practical approach for ship construction cost estimationA practical approach for ship construction cost estimation
A practical approach for ship construction cost estimation
Gopalakrishnan P
 
16SMCE310 16SCVE310 – Engineering Skills Project Brief .docx
16SMCE310  16SCVE310 – Engineering Skills Project Brief .docx16SMCE310  16SCVE310 – Engineering Skills Project Brief .docx
16SMCE310 16SCVE310 – Engineering Skills Project Brief .docx
felicidaddinwoodie
 

Ähnlich wie Vtme dubai samson babu article on vertical transportation planning ELEVATOR WORLD MARCH 2014 (20)

Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...
Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...
Lean&Mean Terminal Design benefits from advanced modelling (Terminal Operator...
 
ECE elevator.pptx
ECE elevator.pptxECE elevator.pptx
ECE elevator.pptx
 
ECE elevator.pdf
ECE elevator.pdfECE elevator.pdf
ECE elevator.pdf
 
IRJET- Final Modeling and Prototype & Analysis of Hydraulic Scissor Lift
IRJET- Final Modeling and Prototype & Analysis of Hydraulic Scissor LiftIRJET- Final Modeling and Prototype & Analysis of Hydraulic Scissor Lift
IRJET- Final Modeling and Prototype & Analysis of Hydraulic Scissor Lift
 
CV_Vikram
CV_VikramCV_Vikram
CV_Vikram
 
IBS Design recommendation for Efficient DAS
IBS Design recommendation for Efficient DASIBS Design recommendation for Efficient DAS
IBS Design recommendation for Efficient DAS
 
SridharOmmi_Resume
SridharOmmi_ResumeSridharOmmi_Resume
SridharOmmi_Resume
 
Building product suggestions for a BIM model based on rule sets and a semant...
Building product suggestions for a BIM model based on rule sets and a  semant...Building product suggestions for a BIM model based on rule sets and a  semant...
Building product suggestions for a BIM model based on rule sets and a semant...
 
A practical approach for ship construction cost estimation
A practical approach for ship construction cost estimationA practical approach for ship construction cost estimation
A practical approach for ship construction cost estimation
 
Gagnant company limited our operations
Gagnant company limited our operationsGagnant company limited our operations
Gagnant company limited our operations
 
Malaysia Elevators & Escalators Market 2026
Malaysia Elevators & Escalators Market 2026Malaysia Elevators & Escalators Market 2026
Malaysia Elevators & Escalators Market 2026
 
EC8791 Requirement-Specifications-Quality assurance techniques
EC8791 Requirement-Specifications-Quality assurance techniquesEC8791 Requirement-Specifications-Quality assurance techniques
EC8791 Requirement-Specifications-Quality assurance techniques
 
Report_Altair
Report_AltairReport_Altair
Report_Altair
 
Unit iii-Architecture in the lifecycle
Unit iii-Architecture in the lifecycleUnit iii-Architecture in the lifecycle
Unit iii-Architecture in the lifecycle
 
Modelling For Signals
Modelling For SignalsModelling For Signals
Modelling For Signals
 
CL 380_Unit-1 (1).pptx
CL 380_Unit-1 (1).pptxCL 380_Unit-1 (1).pptx
CL 380_Unit-1 (1).pptx
 
Konecranes Overhead Crane Design Life White Paper
Konecranes Overhead Crane Design Life White PaperKonecranes Overhead Crane Design Life White Paper
Konecranes Overhead Crane Design Life White Paper
 
16SMCE310 16SCVE310 – Engineering Skills Project Brief .docx
16SMCE310  16SCVE310 – Engineering Skills Project Brief .docx16SMCE310  16SCVE310 – Engineering Skills Project Brief .docx
16SMCE310 16SCVE310 – Engineering Skills Project Brief .docx
 
Project Planning Organising Tracking Construction
Project Planning Organising Tracking  ConstructionProject Planning Organising Tracking  Construction
Project Planning Organising Tracking Construction
 
Automotive Supply Chain Management-A2Z by Rahul Guhathakurta
Automotive Supply Chain Management-A2Z by Rahul GuhathakurtaAutomotive Supply Chain Management-A2Z by Rahul Guhathakurta
Automotive Supply Chain Management-A2Z by Rahul Guhathakurta
 

Mehr von SAMSON BABU MCIBSE

Mehr von SAMSON BABU MCIBSE (19)

Vertical transport vtme elevator_escalator_safety improvements to escalators_...
Vertical transport vtme elevator_escalator_safety improvements to escalators_...Vertical transport vtme elevator_escalator_safety improvements to escalators_...
Vertical transport vtme elevator_escalator_safety improvements to escalators_...
 
Vtme rajan samson ew_june18_article lift car cab decoration
Vtme rajan samson ew_june18_article lift car cab decorationVtme rajan samson ew_june18_article lift car cab decoration
Vtme rajan samson ew_june18_article lift car cab decoration
 
VTME Elevator Consultant lift consultant UAE DUBAI FIRE CODE
VTME Elevator Consultant lift consultant UAE DUBAI FIRE CODEVTME Elevator Consultant lift consultant UAE DUBAI FIRE CODE
VTME Elevator Consultant lift consultant UAE DUBAI FIRE CODE
 
VTME ELEVATOR CONSULTANTS DUBAI ELEVATOR SIGNAL FIXTURES
VTME ELEVATOR CONSULTANTS DUBAI ELEVATOR SIGNAL FIXTURESVTME ELEVATOR CONSULTANTS DUBAI ELEVATOR SIGNAL FIXTURES
VTME ELEVATOR CONSULTANTS DUBAI ELEVATOR SIGNAL FIXTURES
 
Elevator Signal Fixtures Elevator World June 2016
Elevator Signal Fixtures Elevator World June 2016Elevator Signal Fixtures Elevator World June 2016
Elevator Signal Fixtures Elevator World June 2016
 
Vtme elevator consultant scope of work
Vtme elevator consultant scope of workVtme elevator consultant scope of work
Vtme elevator consultant scope of work
 
BIM Modeling VTME Elevator Consultants
BIM Modeling VTME Elevator ConsultantsBIM Modeling VTME Elevator Consultants
BIM Modeling VTME Elevator Consultants
 
Vertical transportation card
Vertical transportation cardVertical transportation card
Vertical transportation card
 
VTME DUBAI elevator consultants advise for firefighting evacuation
VTME DUBAI elevator consultants advise for firefighting evacuation VTME DUBAI elevator consultants advise for firefighting evacuation
VTME DUBAI elevator consultants advise for firefighting evacuation
 
VERTICAL TRANSPORTATION
VERTICAL TRANSPORTATIONVERTICAL TRANSPORTATION
VERTICAL TRANSPORTATION
 
Www.ctbuh.org desktop modules_digarticle_print
Www.ctbuh.org desktop modules_digarticle_printWww.ctbuh.org desktop modules_digarticle_print
Www.ctbuh.org desktop modules_digarticle_print
 
VTME ELEVATOR CONSULTANTS Emergency operations ew nov14
VTME ELEVATOR CONSULTANTS Emergency operations ew nov14VTME ELEVATOR CONSULTANTS Emergency operations ew nov14
VTME ELEVATOR CONSULTANTS Emergency operations ew nov14
 
Vertical Transportation Consultant BMU Facade Access Cradle Systems consultan...
Vertical Transportation Consultant BMU Facade Access Cradle Systems consultan...Vertical Transportation Consultant BMU Facade Access Cradle Systems consultan...
Vertical Transportation Consultant BMU Facade Access Cradle Systems consultan...
 
vertical transportation consultants dubai VTME dubai escalator safety rajan s...
vertical transportation consultants dubai VTME dubai escalator safety rajan s...vertical transportation consultants dubai VTME dubai escalator safety rajan s...
vertical transportation consultants dubai VTME dubai escalator safety rajan s...
 
VTME dubai Rajan samson coordination of vertical transport systems design for...
VTME dubai Rajan samson coordination of vertical transport systems design for...VTME dubai Rajan samson coordination of vertical transport systems design for...
VTME dubai Rajan samson coordination of vertical transport systems design for...
 
VTME dubai Rajan Samson Facade access equipment bmu design planning by samson...
VTME dubai Rajan Samson Facade access equipment bmu design planning by samson...VTME dubai Rajan Samson Facade access equipment bmu design planning by samson...
VTME dubai Rajan Samson Facade access equipment bmu design planning by samson...
 
VTME dubai Rajan Samson Article on Comparison of dedicated against common ser...
VTME dubai Rajan Samson Article on Comparison of dedicated against common ser...VTME dubai Rajan Samson Article on Comparison of dedicated against common ser...
VTME dubai Rajan Samson Article on Comparison of dedicated against common ser...
 
Vertical Transportation Consultants Dubai VTME Dubai Rajan Samson Article MRL...
Vertical Transportation Consultants Dubai VTME Dubai Rajan Samson Article MRL...Vertical Transportation Consultants Dubai VTME Dubai Rajan Samson Article MRL...
Vertical Transportation Consultants Dubai VTME Dubai Rajan Samson Article MRL...
 
VTME dubai Rajan Samson Article Elevators For Improving Life Safety
VTME dubai Rajan Samson Article Elevators For Improving Life SafetyVTME dubai Rajan Samson Article Elevators For Improving Life Safety
VTME dubai Rajan Samson Article Elevators For Improving Life Safety
 

Kürzlich hochgeladen

Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion pills in Kuwait Cytotec pills in Kuwait
 
Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...
Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...
Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...
instagramfab782445
 
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
gajnagarg
 
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
nirzagarg
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
CristineGraceAcuyan
 
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
nirzagarg
 
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
gajnagarg
 
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
eeanqy
 

Kürzlich hochgeladen (20)

Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
 
Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...
Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...
Abortion pill for sale in Muscat (+918761049707)) Get Cytotec Cash on deliver...
 
Sweety Planet Packaging Design Process Book.pptx
Sweety Planet Packaging Design Process Book.pptxSweety Planet Packaging Design Process Book.pptx
Sweety Planet Packaging Design Process Book.pptx
 
Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...
Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...
Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...
 
Essential UI/UX Design Principles: A Comprehensive Guide
Essential UI/UX Design Principles: A Comprehensive GuideEssential UI/UX Design Principles: A Comprehensive Guide
Essential UI/UX Design Principles: A Comprehensive Guide
 
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
 
Jordan_Amanda_DMBS202404_PB1_2024-04.pdf
Jordan_Amanda_DMBS202404_PB1_2024-04.pdfJordan_Amanda_DMBS202404_PB1_2024-04.pdf
Jordan_Amanda_DMBS202404_PB1_2024-04.pdf
 
Gamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad IbrahimGamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad Ibrahim
 
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
 
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime PondicherryPondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
 
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service AvailableCall Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
 
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
 
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best ServiceHigh Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
 
How to Turn a Picture Into a Line Drawing in Photoshop
How to Turn a Picture Into a Line Drawing in PhotoshopHow to Turn a Picture Into a Line Drawing in Photoshop
How to Turn a Picture Into a Line Drawing in Photoshop
 
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
 
NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...
NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...
NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...
 
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
 
How to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdfHow to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdf
 
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEKLANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
 

Vtme dubai samson babu article on vertical transportation planning ELEVATOR WORLD MARCH 2014

  • 1. Engineering Vertical-Transportation Design Planning What manufacturers and architects should be aware of in the planning stages of a building’s elevatoring by Samson Rajan Babu Elevator contractors are quite familiar with their specialty tasks – they do sales engineering, negotiate and sell elevators, produce shop drawings, procure materials, install elevators and carry out maintenance. However, the background information (i.e., how a verticaltransportation solution is selected for a new building project) and the factors that govern elevator selection (i.e., how the original elevator layout and specifications came into existence) remain somewhat hidden. This article provides an insight into understanding the essential design efforts that go behind the verticaltransportation planning of any new construction project. It also intends to help architects formulate a scientific method of developing, integrating and verifying a vertical-transportation system design within their projects. It is hoped the information presented in this article will also help elevator contractors understand tender specifications and drawings in a better way and be informed and decisive, while complying with or deviating from a project requirement. It is also intended to help elevator contractors properly estimate their costs and liabilities on a new project and present attractive value engineering options to their clients, while increasing their chances of winning a project. Applicable Codes There are applicable building-design codes for projects based on their geographical location. These include (but are not limited to) international-building, life-safety, fire-protection, seismic, accessibility and local-municipality/ civil-defense codes. While these are mandatory requirements, the consultant and/or owner might choose to exceed the minimum requirements and provide additional/superior features, such as evacuation communication systems, evacuation elevators, etc. Performance Targets Any new project has owner requirements, and most established brand owners have their own vertical-transportation design and performance requirements. Design requirements include average interval, average waiting time, average time to destination, car capacities, and car and door sizes. While starting a new design project, consultants should check with the owners for their published design guidelines. If this is not available, the consultant should propose standards based on the international best design practices and the project’s brand positioning at the geographical location. This becomes the “design criteria” for the project. Widely Used Building Design Codes International Building Code International Fire Code National Fire Protection Association Standards International Mechanical Code International Electrical Code International Plumbing Code Life Safety Code National Fire Alarm Code Accessible Design Standards Seismic Design Standards Local Civil Defense Codes Local Municipality Codes Elevator-/EscalatorEquipment Safety Codes BS/EN 81 BS/EN 115 ASME A17.1 CSA B44 AS 1735 JIS & BSLJ GB 7588 GB 16899 Widely used building and elevator-/escalator-equipment safety codes, which are separate from each other. Continued 112 www.elevatorworld.com • March 2014
  • 2. Analyzing Population and Vertical Circulation Elevator Sizes/Capacities For each type of building project, the population and vertical circulation of people and material inside the building must be elaborately studied. This includes types of users, populations on each upper floor, parking spaces on parking floors, loading docks, arrival/exit patterns, access-control concepts, bulk arrival (including transportation for both the public and staff ) scenarios, interfloor circulation patterns and peak traffic estimation. Main lobby floors should be identified for arrival. Exit scenarios and the volume of peak traffic should be estimated using practical and working knowledge on each building type. Similarly, high-traffic floors that are not main lobby floors should be identified, and peak traffic to/from these floors is to be estimated. Depending on user space requirements, comfort levels and various code requirements, the most suitable car sizes/capacities and door sizes should be identified for each elevator group. Even though an elevator analysis might minimally require smaller elevators, an architect might select larger elevators to serve the above requirements. The option to provide a machine room at the top of the building should also be discussed with an architect in reference to machine-room-less (MRL) elevators, which may have different capacities, speed and range. Elevator Traffic Analysis Various traffic patterns and peak traffic identified throughout the day at the building can now be analyzed via calculations or a Traffic Segregation simulation. A typical elevator traffic analysis involves assuming To realize the elevator systems’ maximum efficiency, it is ideal various elevator operating parameters (door times, passenger to have dedicated elevator groups for each user type. It also helps movement times, acceleration, etc.), and such assumptions must in improving user comfort, access control of protected areas and match desired car and door sizes. All such assumptions made at exclusivity for VIP users. However, it may not be economical or this stage must be practically achievable by any elevator viable commercially. With this in mind, the conditions that will manufacturer for the traffic study results to be valid. allow combining certain user groups are to be reviewed, and It is very important not to overestimate or underestimate the minimum required elevator groups (cores) should be proposed. peak traffic, because this will ultimately result in more or fewer Once this is agreed upon, the peak traffic is again verified for the elevators. It should also be noted that the estimated average combined user types (if any) for each elevator core. waiting times are only indicative and cannot be repeated on an actual site. Hence, practical Bank No 01 02 03 04 knowledge and an exceptional Lift No. PL01 PL02 SL01 SL02 PL03 understanding of simulation Location Hospital Hospital Hospital Hospital Accomm procedures are necessary for a Front: G Front: G Opening Front Front Front Rear: 1 Rear: 1 vertical-transportation consultant to Lift Type Public/Staff Public/Staff Service/Staff Service/Staff Public/Service properly guide the architects/design No. of Floors Served 2 2 2 2 2 team. Travel approx. 4.5m 4.5m 4.5m 4.5m 3.5m Various speed, capacity and Fireman Lift Yes quantity combinations should be Persons 13 13 33 33 17 verified to check if the performance Capacity (Kg) 1000 1000 2500 2500 1275 meets the design criteria, while Speed m/s 1.0 1.0 1.0 1.0 keeping in mind the initial and 1.0 maintenance costs for each 1400X1600X2400 Car Size (W X D X H) 1800X2750X2400 1800X2750X2400 1200X2300X2400 (2 opposite entrances) combination. Vertical dimension Shaft Size (W X D) 4650X2200 3000X3300 3000X3300 2100X2800 requirements (e.g., pit depth, overhead and machine-room height) Door Opening (W X H) 1000X2100 1000X2100 1400X2200 1400X2200 1100X2200 Structural Opening should be simultaneously considered, 1200X2200 1200X2200 1600X2300 1600X2300 1300X2300 (W X H) because the required vertical Door Type CO CO 2S 2S 2S dimensions cannot be provided due Headroom 4500 4500 4500 4500 4500 to various architectural reasons and Pit Depth 1600 1600 1700 1700 1700 height restrictions. After careful Power-Supply Capacity 20 20 48 48 20 evaluation, the ideal and acceptable (kVA) Elev. elevator groups are to be selected. Main Power Starting Power (kVA) 32 93 93 32 Breaker Capacity (A) Elev. Lighting Power 32 40 40 63 63 40 Power-Supply Capacity 2 (kVA) 2 2 2 2 Breaker Capacity (A) 20 20 20 20 20 1211 1211 3966 3966 1211 Heat Emission (Kcal/hr.) An elevator-specification summary sheet Firefighters’ Elevator Core Dimensions Once the elevator groups are finalized, elevator core sizes should be planned in such a way that they accommodate at least three elevator manufacturers available in the local market and per the applicable equipment safety codes. Special requirements (to accommodate such Continued 114 www.elevatorworld.com • March 2014
  • 3. circumstances as building plumb deviations, seismic designs, fire-rated entrances, wind-shear noise, piston effects, special safety features, etc.) should also be considered, and the core sizes increased as necessary. Type of construction for the elevator core walls is then finalized, considering the structural and fire-code requirements. For quick reference, all the elevator groups should be consolidated onto a spreadsheet showing all relevant dimensions and specification data. This spreadsheet could be used as a cross-reference, while verifying the elevator tender response for the project. Elevator contractors are required to confirm their compliance or noncompliance to each item on this summary sheet. Core Layout Based on the final core dimensions, the elevator cores should be laid out on the plan drawings. Structural support requirements for the guide rails, separator beams, trimmer beams, entrance frames, machines and controllers should be identified, and suitable provisions should be made for the size and type of construction. Door structural openings should be approximately shown on the plans. It is important to note that the location of door structural openings and front-wall dimensions are approximate. This must be finalized and constructed based only on the elevator supplier’s shop drawings. floor in order to drop the machine to a floor with elevator service, then move it to the ground floor for future maintenance/ replacement. For MRL elevators, the location of an emergency rescue panel outside the hoistway should be identified. Structural Coordination The structural loads on the guide-rail support system, impact loads on the pit buffer, reaction loads at the machine room and lifting-hook capacities should be reviewed, and the structural frame (reinforced cement concrete (RCC) beam/column/slab/ wall) should be designed to meet the requirements. The structural fixing (anchoring) requirements for the guide-rail brackets, machines and other steel elements should be reviewed, and a suitable substructure (RCC or similar) should be provided. The size of structural door openings, trap doors and rope holes are to be compiled, and their impact on the structural stability of the core wall system should be reviewed by the structural design engineers. Mechanical Coordination The mechanical requirements for efficient functioning of the elevator equipment should be reviewed, and suitable provisions should be made by the mechanical designers to remove the heat generated by the elevator equipment and provide suitable ambient conditions within the machine room. These provisions can include heating, ventilation, air-conditioning, ducting, routing and diffusers. Special requirements, such as air-conditioning for the elevator car, pressurization, stack effect, smoke mitigation and noise reduction requirements should also be reviewed, and a matching mechanical design and additional equipment provided to prevent any detrimental effect on the elevator systems’ performance. Acoustics and vibration characteristics of the elevator equipment should be reviewed, and suitable coordination and adjustments may need to be carried out to reduce such undesirable effects generated by the elevator system. Electrical Coordination An elevator core drawing The electrical requirements for efficient functioning of elevator equipment should also be reviewed, and suitable provisions (suitably rated isolators, fuses, fire protection, and cable sizes, shields, routing and containment) should be made by the electrical designers to supply the power required by the elevator equipment. Standby-power requirements should be identified for specific elevators and suitable provisions made in this stage through automatic transfer switches to provide generator power to specific elevators, as well as other building services. The requirement of a battery-operated automatic rescue device and regenerative drives for specific elevators should then be reviewed and finalized. Equipment sensitive to electromagnetic interference (EMI) at the site should be identified, and the elevator power-supply circuits should be suitably designed to prevent EMI with such equipment. Machine-Room Layout Lighting Coordination For each elevator core, the machine-room layout should be finalized, taking the requirements for easy access and safe working conditions into consideration. Machine-room heights include joist beams/lifting hooks for maintenance. For heavy machinery, where possible, a trap door should be included on the machine-room Normal lighting requirements for the machine room and emergency-lighting requirements should be reviewed. Suitable lighting fixtures can then be provided to achieve desired brightness inside these spaces. Special elevator-car interior lighting and lighting effects should be reviewed and incorporated. Continued 116 www.elevatorworld.com • March 2014
  • 4. Height Mtrs. LEVEL LEVEL R R 2 2 4.5 1 1 4.5 G G 4.5 B1 6 B PIT PIT PIT PIT PIT PIT PIT PIT - - - - - - PIT PIT PIT PIT PIT PIT PIT PIT 11 12 13 14 15 16 17 18 19 20 21 7 8 9 10 11 12 13 14 15 16 Lift Group Staff & public Staff & public Public Staff & public Staff & public Usage Type Public Lift pit Lift Number 6 Staff & public 10 5 Staff & public 09 Staff & public 08 4 Training wing 07 Service Public Public Public 06 3 Usage Public 05 Service 04 2 Service 03 Service 02 1 Service 01 Lift Bank Service Lift Number Service Key: Staff/public lift Public lift Facilities management service lift R Roof of building A riser diagram Plumbing Coordination Sump pits required within the elevator pits should be reviewed and suitable provisions made for the sump pits (i.e., a permanent sump pump, simple floor drain or dry sump pit). Drainage piping design, routing and containment should be reviewed, so they do not cause a code deviation and damage elevator equipment. Special floor drains required at each elevator lobby should be evaluated and adopted if found necessary. Low-Voltage-Systems Coordination Special features and low-voltage systems linked to the elevator equipment should be reviewed and suitable cabling with containment, power supply, mounting requirements and location of interface terminals coordinated with relevant vendors. The systems in question can include remote monitoring, remote control, building management, access-control card readers, closed-circuit TV cameras, media displays, external dialing means, fire alarms and smoke detectors. Architectural and Interior Design Coordination Related elevator spaces (shaft, lobbies and machine rooms) should be reviewed in parallel with the interior design concepts and appropriate alignments carried out. Suitable lobby widths are necessary to achieve international standards in user comfort. Elevator-door handing (which side they open) is to be reviewed in relation to the surroundings and elevator approach, after which the most suitable should be selected. Depending on the front-wall cladding thickness and floor-finish thickness, Continued 118 www.elevatorworld.com • March 2014
  • 5. suitable adjustments can be made to the architectural positioning of each door opening. Special attention should be paid to aligning the elevator-door openings opposite to each other. Placement of hall-call stations, lanterns, indicators, firefighters’ switches, emergency control panels (for MRL elevators only) and related equipment regularly installed at the landings should be reviewed, adjusted and aligned to achieve the best-looking lobby possible. Signalization and Signage Coordination The following is a list of required signalization/signage that requires coordination with the elevator-installation procedure: ♦ Car and landing call stations ♦ Lighting color ♦ ♦ ♦ ♦ ♦ Faceplate color and material Visual/audible signals Automated voice messages Media display schemes Accessibility and VIP features (on push buttons and signalization) Accessibility Design Coordination Every passenger elevator should be reviewed for compliance with accessibility codes and features. Elevator car sizes that allow full rotation of wheelchairs, auxiliary car control panels for the handicapped, maximum height of push buttons from floor level, and Braille and tactile features on push buttons are examples. Special accessibility features such as induction loops for the hearing impaired, voice announcements in the local language and tactile pavements in the elevator lobby may be reviewed on a case-to-case basis and adopted as deemed necessary. Tender Documents Our Mission: To educate the public on the safe and proper use of elevators, escalators and moving walks through informational programs. Traditionally, manufacturers estimate their tender price based on the elevator specifications (and elevator drawings, if any). However, it must be noted that elevator specifications always crossreference various other specifications within the master specifications. It is recommended that elevator manufacturers read all relevant codes and specifications to understand how the elevator system is required to coordinate and work with other project equipment and design concepts. Conclusion Request a Safe-T Rider sample kit from EESF online or contact the Foundation directly. Read over the information and ask EESF if you have any questions. Go to your local school or district and talk with the appropriate decision maker about presenting the program. Contact the Foundation to have material sent to yourself or directly to the school. Use the Teacher’s Guide for step-by-step instructions on how to administer the program. Safe-T Rider costumes are available for rent or purchase, based on availability. Elevator Escalator Safety Foundation 356 Morgan Ave – Mobile, AL 36606 (800)949-6442 – www.eesf.org – info@eesf.org 120 www.elevatorworld.com • March 2014 While the information in this article should help architects to exercise a fair amount of control on vertical-transportation system design and integration, a qualified and knowledgeable vertical-transportation engineer is the only suitable person to completely manage and control the process in the best possible manner. The author and his firm welcome any query from the readers of this article on any vertical-transportation system design and will be pleased to offer 🌐 engineering guidance. Samson Rajan Babu is technical director at VTME Vertical Transportation Systems Consultants in Dubai. He is a mechanical engineer specializing in vertical-transportation systems and façade-access equipment. Following his graduation from Anna University in Chennai, India, in 1994, he worked on many projects in the Indian and Persian Gulf markets. He can be contacted at email: sbabu@vtmeconsulting.com.