PRESENTATION ON
Calculations of a.c distributions methods & 3 phase
unbalanced loads & 4 wire star connected loads & ground
detector
Outline
• Calculations of a.c distribution methods
• 3 phase unbalanced loads
• Four wire star-connected unbalanced loads
• Ground detectors
• Mcqs
Calculations of A.C. distribution
• The following two methods are used for making
calculation of a.c Distribution
1. When the power factor of all loads are with reference
to the receiving end voltage.
2. When the load power factor are with reference to their
load voltage.
1. Power factors referred to receiving end voltage.
Consider an a.c distributor AB with concentrated
loads of I1 and I2 tapped off at points C and
B as shown in Fig.Taking the receiving end
voltage VB as the reference vector, let lagging power factors
at C and B be cos φ1 and cos φ2 write VB. Let R1, X1 and
R2, X2 be the resistance and reactance of sections AC and
CB of the distributor.
• Impedance of section AC, ZAC = R1 + j X1
Impedance of section CB, ZCB = R2 + j X2
Load current at point C, I1 = I1 (cos φ1 − j sin φ1)
Load current at point B, I2 = I2 (cos φ2 − j sin φ2)
Current in section CB, ICB = I2 = I2 (cos φ2 − j sin φ2)
Current in section AC, IAC = I1 I2 +
= I1 (cos φ1 − j sin φ1) + I2 (cos φ2 − j sin φ2)
Voltage drop in section CB, VCB = ICB ZCB = I2 (cos φ2 − j sin φ2) (R2 + j X2)
Voltage drop in section AC, VAC = ( ) I AC ZAC = I1 + I2 ZAC
= [I1(cos φ1 − j sin φ1) + I2 (cos φ2 − j sin φ2)] [R1 + jX1]
Sending end voltage, VA = VB VCB VAC + +
Sending end current, IA = I I 1 2
The vector diagram of the a.c. distributor under these conditions is shown in Fig.
Here, the
receiving end voltage VB is taken as the reference vector. As power factors of
loads are given write
VB, therefore, I1 and I2 lag behind VB by φ1 and φ2 respectively.
2. Power factors referred to respective load voltages.
Suppose the power factors of loads in.
• The previous Fig. are referred to their respective load
voltages. Then φ1 is the phase angle between VC and I1
and φ2 is the phase angle between VB and I2. The vector
diagram under these conditions is shown in Fig.
• Voltage drop in section CB = I2 ZCB = I2 (cos φ2 − j sin φ2)
(R2 + j X2)
Voltage at point C = VB + Drop in section CB = VC ∠ α (say)
Now I1 = I1 ∠ − φ1 write voltage VC
∴ I1 = I1 ∠ − (φ1 − α) write voltage VB
i.e. I1 = I1 [cos (φ1 − α) − j sin (φ1 − α)]
Now IAC = I I 1 2 += I1 [cos (φ1 − α) − j sin (φ1 − α)] + I2
(cos φ2 − j sin φ2)
Voltage drop in section AC = IAC ZAC
∴ Voltage at point A = VB + Drop in CB + Drop in AC
• Example 1. A single phase a.c. distributor AB 300
meters long is fed from end A and is
loaded as under :
(i) 100 A at 0·707 p.f. lagging 200 m from point A
(ii) 200 A at 0·8 p.f. lagging 300 m from point A
The load resistance and reactance of the distributor is
0·2 Ω and 0·1 Ω per kilometer. Calculate
the total voltage drop in the distributor. The load power
factors refer to the voltage at the far end.
• Solution. Fig. shows the single line diagram of the distributor.
Impedance of distributor/km = (0·2 + j 0·1) Ω
Impedance of section AC, ZAC = (0·2 + j 0·1) × 200/1000 = (0·04 + j 0·02) Ω
Impedance of section CB, ZCB = (0·2 + j 0·1) × 100/1000 = (0·02 + j 0·01) Ω
Taking voltage at the far end B as the reference vector, we have,
Load current at point B, I2 = I2 (cos φ2 − j sin φ2) = 200 (0·8 − j 0·6)
= (160 − j 120) A
Load current at point C, I1 = I1 (cos φ1 − j sin φ1) = 100 (0·707 − j 0·707)
= (70·7− j 70·7) A
Current in section CB, ICB = I2 = (160 − j 120) A
Current in section AC, IAC = I1 + I2 = (70·7 − j 70·7) + (160 − j 120)
= (230·7 − j 190·7) A
Voltage drop in section CB, VCB = ICB ZCB = (160 − j 120) (0·02 + j 0·01)
= (4·4 − j 0·8) volts
Voltage drop in section AC, VAC = IAC ZAC = (230·7 − j 190·7) (0·04 + j 0·02)
= (13·04 − j 3·01) volts
Voltage drop in the distributor = VAC + VCB = (13·04 − j 3·01) + (4·4 − j 0·8)
= (17·44 − j 3·81) volts
Magnitude of drop = 17 44 3 81 a ⋅ f2 + a ⋅ f2 = 17·85 V
3-Phase Unbalanced Loads
• The 3-phase loads that have the same impedance and
power factor in each phase are called balanced
loads. The problems on balanced loads can be solved by
considering one phase only
• The conditions in the other two phases being similar.
However, we may come across a situation when loads
are unbalanced i.e. each load phase has different
impedance and/or power factor.
• In that case, current and power in each phase will be
different. In practice, we may come across the following
unbalanced loads:
(i) Four-wire star-connected unbalanced load
(ii) Unbalanced Δ-connected load
(iii) Unbalanced 3-wire, Y-connected load
Four-Wire Star-Connected Unbalanced Loads
• We can obtain this type of load in two ways. First, we may
connect a 3-phase, 4-wire unbalanced load to a 3-phase,
4-wire supply as shown in Fig. Note that star point N of the
supply is connected to the load star point N′. Secondly, we
may connect single phase loads between any line and the
neutral wire as shown in Fig.
• This will also result in a 3-phase, 4-wire **unbalanced load
because it is rarely possible that single phase loads on all
the three phases have the same magnitude and power
factor. Since the load is unbalanced, the line currents will
be different in magnitude and displaced from one another
by unequal angles. The current in the neutral wire will be
the phasor sum of the three line currents i.e.
Current in neutral wire, IN = IR + IY + IB ... phasor sum
The following points may be noted carefully :
(i) Since the neutral wire has negligible resistance,
supply neutral N and load neutral N′ will be
at the same potential. It means that voltage across
each impedance is equal to the phase
voltage of the supply. However, current in each phase
(or line) will be different due to
unequal impedances.
(ii) The amount of current flowing in the neutral wire
will depend upon the magnitudes of line
• Currents and their phasor relations. In most circuits encountered in
practice, the neutral current is equal to or smaller than one of the line
currents. The exceptions are those circuits having severe unbalance.
• No doubt 3-phase loads (e.g. 3-phase motors) connected to this
supply are balanced but when we add single phase loads the balance
is lost.
• It is because it is rarely possible that single phase loads on all the
three phases have the same magnitude and power factor.
•actual practice, we never have an unbalanced 3-phase, 4-wire load.
Most of the 3-phase loads are 3-phase, 3-wire and are balanced loads.
• In fact, these are the single phase loads on the 3-phase, 4-wire
supply which constitute unbalanced, 4-wire Y-connected load.
Ground Detectors
•Ground detectors are the devices that are used to detect the
ground fault for ungrounded a.c. systems.
•When a ground fault occurs on such a system, immediate
steps should be taken to clear it.
• If this is not done and a second ground fault happens, a
short circuit occurs.
Fig. shows how lamps are connected to an ungrounded 3-
phase system for the detection of ground fault.
• If ground fault occurs on any wire, the lamp connected to
that wire will be dim and the lamps connected to healthy
(ungrounded) wire will become brighter.
MCQs
Answers
i. Unbalanced
ii. 230∟120 °
iii. Vector ally
iv. Half
v. Single phase 2-wire
Calculations of a.c distributions methods & 3 phase unbalanced loads & 4 wire star connected loads & ground detector

Weitere ähnliche Inhalte

Was ist angesagt?

l4-ac-ac converters.ppt
l4-ac-ac converters.pptl4-ac-ac converters.ppt
l4-ac-ac converters.ppt
antexnebyu
 

Was ist angesagt? (20)

Moving iron (MI) instruments
Moving iron (MI) instrumentsMoving iron (MI) instruments
Moving iron (MI) instruments
 
Topic 2 - Switch Realization.pptx
Topic 2 - Switch Realization.pptxTopic 2 - Switch Realization.pptx
Topic 2 - Switch Realization.pptx
 
Diode circuits
Diode circuitsDiode circuits
Diode circuits
 
Solved problems on rectifiers
Solved problems  on rectifiersSolved problems  on rectifiers
Solved problems on rectifiers
 
Waves on Transmission Lines (2).pptx
Waves on Transmission Lines (2).pptxWaves on Transmission Lines (2).pptx
Waves on Transmission Lines (2).pptx
 
Dot convention in coupled circuits
Dot convention in coupled circuitsDot convention in coupled circuits
Dot convention in coupled circuits
 
Reflection and Transmission coefficients in transmission line
Reflection and Transmission coefficients in transmission lineReflection and Transmission coefficients in transmission line
Reflection and Transmission coefficients in transmission line
 
Electric and magnetic circuits
Electric and magnetic circuitsElectric and magnetic circuits
Electric and magnetic circuits
 
Boost converter
Boost converterBoost converter
Boost converter
 
current&current density
current&current densitycurrent&current density
current&current density
 
ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)
 
Superposition theorem
Superposition theoremSuperposition theorem
Superposition theorem
 
2b.pptx
2b.pptx2b.pptx
2b.pptx
 
Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter
 
transmission-lines
transmission-linestransmission-lines
transmission-lines
 
Buck-Boost Converter
Buck-Boost ConverterBuck-Boost Converter
Buck-Boost Converter
 
Inductance and capacitance
Inductance and capacitanceInductance and capacitance
Inductance and capacitance
 
Est 130 passive components inductors
Est 130 passive components inductorsEst 130 passive components inductors
Est 130 passive components inductors
 
l4-ac-ac converters.ppt
l4-ac-ac converters.pptl4-ac-ac converters.ppt
l4-ac-ac converters.ppt
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulators
 

Ähnlich wie Calculations of a.c distributions methods & 3 phase unbalanced loads & 4 wire star connected loads & ground detector

Distribution System-2 in power system Engin
Distribution System-2 in power system EnginDistribution System-2 in power system Engin
Distribution System-2 in power system Engin
Vatsalkumarpatel
 
Multisim_simulation_project_3_^0_4[1]-2.pptx
Multisim_simulation_project_3_^0_4[1]-2.pptxMultisim_simulation_project_3_^0_4[1]-2.pptx
Multisim_simulation_project_3_^0_4[1]-2.pptx
wencove9
 

Ähnlich wie Calculations of a.c distributions methods & 3 phase unbalanced loads & 4 wire star connected loads & ground detector (20)

Cureent, Resistance & Kirchhoff’s Rules.pptx
Cureent, Resistance & Kirchhoff’s Rules.pptxCureent, Resistance & Kirchhoff’s Rules.pptx
Cureent, Resistance & Kirchhoff’s Rules.pptx
 
Distribution System-2 in power system Engin
Distribution System-2 in power system EnginDistribution System-2 in power system Engin
Distribution System-2 in power system Engin
 
BEF 23803 - Polyphase Circuit Analysis - Lecture 2.pptx
BEF 23803 - Polyphase Circuit Analysis - Lecture 2.pptxBEF 23803 - Polyphase Circuit Analysis - Lecture 2.pptx
BEF 23803 - Polyphase Circuit Analysis - Lecture 2.pptx
 
BEF 23803 - Lesson 3 - Balanced Delta Load Thre-Phase Systems.ppt
BEF 23803 - Lesson 3 - Balanced Delta Load Thre-Phase Systems.pptBEF 23803 - Lesson 3 - Balanced Delta Load Thre-Phase Systems.ppt
BEF 23803 - Lesson 3 - Balanced Delta Load Thre-Phase Systems.ppt
 
207137236 ee2207-lm
207137236 ee2207-lm207137236 ee2207-lm
207137236 ee2207-lm
 
TIPLER CAP r25
TIPLER CAP r25TIPLER CAP r25
TIPLER CAP r25
 
10 three phase system.ppt
10 three phase system.ppt10 three phase system.ppt
10 three phase system.ppt
 
Ce configuration
Ce configurationCe configuration
Ce configuration
 
Diode Applications & Transistor Basics
Diode Applications & Transistor BasicsDiode Applications & Transistor Basics
Diode Applications & Transistor Basics
 
Intro electronics laboratory
Intro electronics laboratoryIntro electronics laboratory
Intro electronics laboratory
 
Power amplifiers analog electronics.pptx
Power amplifiers analog electronics.pptxPower amplifiers analog electronics.pptx
Power amplifiers analog electronics.pptx
 
1.2 interconnection of windings
1.2 interconnection of windings1.2 interconnection of windings
1.2 interconnection of windings
 
ELECTRONICS
ELECTRONICSELECTRONICS
ELECTRONICS
 
analyze the current and voltage distr along distribution line.pptx
analyze the current and voltage  distr along distribution line.pptxanalyze the current and voltage  distr along distribution line.pptx
analyze the current and voltage distr along distribution line.pptx
 
Practice questions for unit ii
Practice questions for unit iiPractice questions for unit ii
Practice questions for unit ii
 
Multisim_simulation_project_3_^0_4[1]-2.pptx
Multisim_simulation_project_3_^0_4[1]-2.pptxMultisim_simulation_project_3_^0_4[1]-2.pptx
Multisim_simulation_project_3_^0_4[1]-2.pptx
 
BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
BEF 23803 - Lecture 8 - Conservation of Complex Power.pptBEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
 
BEEE-UNIT 1.pptx
BEEE-UNIT 1.pptxBEEE-UNIT 1.pptx
BEEE-UNIT 1.pptx
 
Short notes on digital electronics for specialist officer it exam by das sir,...
Short notes on digital electronics for specialist officer it exam by das sir,...Short notes on digital electronics for specialist officer it exam by das sir,...
Short notes on digital electronics for specialist officer it exam by das sir,...
 
Lab 8 bipolar junction transistor characterstics
Lab 8  bipolar junction transistor charactersticsLab 8  bipolar junction transistor characterstics
Lab 8 bipolar junction transistor characterstics
 

Mehr von vishalgohel12195

Mehr von vishalgohel12195 (20)

Variable frequency drive and variable frequency control
Variable frequency drive and variable frequency controlVariable frequency drive and variable frequency control
Variable frequency drive and variable frequency control
 
Self control of synchronous motor drives
Self control of synchronous motor drivesSelf control of synchronous motor drives
Self control of synchronous motor drives
 
Owen’s bridge and measurement of increment inductance
Owen’s bridge and measurement of increment inductanceOwen’s bridge and measurement of increment inductance
Owen’s bridge and measurement of increment inductance
 
Initial and final condition for circuit
Initial and final condition for circuitInitial and final condition for circuit
Initial and final condition for circuit
 
FSK , FM DEMODULATOR & VOLTAGE REGULATOR ICS
FSK , FM DEMODULATOR & VOLTAGE REGULATOR ICS  FSK , FM DEMODULATOR & VOLTAGE REGULATOR ICS
FSK , FM DEMODULATOR & VOLTAGE REGULATOR ICS
 
Differential equations of first order
Differential equations of first orderDifferential equations of first order
Differential equations of first order
 
Cost for production including breaking analysis
Cost for production including breaking  analysisCost for production including breaking  analysis
Cost for production including breaking analysis
 
Concept of general terms pertaining to rotating machines
Concept of general terms pertaining to rotating machinesConcept of general terms pertaining to rotating machines
Concept of general terms pertaining to rotating machines
 
Transfer function and mathematical modeling
Transfer  function  and  mathematical  modelingTransfer  function  and  mathematical  modeling
Transfer function and mathematical modeling
 
armature Winding
armature Windingarmature Winding
armature Winding
 
Switching regulators
Switching regulatorsSwitching regulators
Switching regulators
 
Sag in overhead transmission line, sag calculation & string chart
Sag in overhead transmission line, sag   calculation & string chartSag in overhead transmission line, sag   calculation & string chart
Sag in overhead transmission line, sag calculation & string chart
 
Rectifier
RectifierRectifier
Rectifier
 
Protection against overvoltage
Protection against overvoltageProtection against overvoltage
Protection against overvoltage
 
Pantograph,catenary wire,smothing reactor
Pantograph,catenary wire,smothing reactorPantograph,catenary wire,smothing reactor
Pantograph,catenary wire,smothing reactor
 
On load tap changer in a.c. locomotive transformer & air blast circuit b...
On load tap changer in a.c. locomotive transformer  & air blast circuit b...On load tap changer in a.c. locomotive transformer  & air blast circuit b...
On load tap changer in a.c. locomotive transformer & air blast circuit b...
 
Logical instruction of 8085
Logical instruction of 8085Logical instruction of 8085
Logical instruction of 8085
 
Effect of non sinusoidal waveform of a.c. machine performance
Effect of non sinusoidal waveform of a.c. machine performanceEffect of non sinusoidal waveform of a.c. machine performance
Effect of non sinusoidal waveform of a.c. machine performance
 
Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...
 
Design, Planning and Layout of high voltage laboratory
Design, Planning and Layout of high voltage laboratory Design, Planning and Layout of high voltage laboratory
Design, Planning and Layout of high voltage laboratory
 

Kürzlich hochgeladen

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 

Kürzlich hochgeladen (20)

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 

Calculations of a.c distributions methods & 3 phase unbalanced loads & 4 wire star connected loads & ground detector

  • 1. PRESENTATION ON Calculations of a.c distributions methods & 3 phase unbalanced loads & 4 wire star connected loads & ground detector
  • 2. Outline • Calculations of a.c distribution methods • 3 phase unbalanced loads • Four wire star-connected unbalanced loads • Ground detectors • Mcqs
  • 3. Calculations of A.C. distribution • The following two methods are used for making calculation of a.c Distribution 1. When the power factor of all loads are with reference to the receiving end voltage. 2. When the load power factor are with reference to their load voltage.
  • 4. 1. Power factors referred to receiving end voltage. Consider an a.c distributor AB with concentrated loads of I1 and I2 tapped off at points C and B as shown in Fig.Taking the receiving end voltage VB as the reference vector, let lagging power factors at C and B be cos φ1 and cos φ2 write VB. Let R1, X1 and R2, X2 be the resistance and reactance of sections AC and CB of the distributor.
  • 5. • Impedance of section AC, ZAC = R1 + j X1 Impedance of section CB, ZCB = R2 + j X2 Load current at point C, I1 = I1 (cos φ1 − j sin φ1) Load current at point B, I2 = I2 (cos φ2 − j sin φ2) Current in section CB, ICB = I2 = I2 (cos φ2 − j sin φ2) Current in section AC, IAC = I1 I2 + = I1 (cos φ1 − j sin φ1) + I2 (cos φ2 − j sin φ2) Voltage drop in section CB, VCB = ICB ZCB = I2 (cos φ2 − j sin φ2) (R2 + j X2) Voltage drop in section AC, VAC = ( ) I AC ZAC = I1 + I2 ZAC = [I1(cos φ1 − j sin φ1) + I2 (cos φ2 − j sin φ2)] [R1 + jX1] Sending end voltage, VA = VB VCB VAC + + Sending end current, IA = I I 1 2 The vector diagram of the a.c. distributor under these conditions is shown in Fig. Here, the receiving end voltage VB is taken as the reference vector. As power factors of loads are given write VB, therefore, I1 and I2 lag behind VB by φ1 and φ2 respectively.
  • 6. 2. Power factors referred to respective load voltages. Suppose the power factors of loads in. • The previous Fig. are referred to their respective load voltages. Then φ1 is the phase angle between VC and I1 and φ2 is the phase angle between VB and I2. The vector diagram under these conditions is shown in Fig. • Voltage drop in section CB = I2 ZCB = I2 (cos φ2 − j sin φ2) (R2 + j X2) Voltage at point C = VB + Drop in section CB = VC ∠ α (say) Now I1 = I1 ∠ − φ1 write voltage VC ∴ I1 = I1 ∠ − (φ1 − α) write voltage VB i.e. I1 = I1 [cos (φ1 − α) − j sin (φ1 − α)] Now IAC = I I 1 2 += I1 [cos (φ1 − α) − j sin (φ1 − α)] + I2 (cos φ2 − j sin φ2) Voltage drop in section AC = IAC ZAC ∴ Voltage at point A = VB + Drop in CB + Drop in AC
  • 7. • Example 1. A single phase a.c. distributor AB 300 meters long is fed from end A and is loaded as under : (i) 100 A at 0·707 p.f. lagging 200 m from point A (ii) 200 A at 0·8 p.f. lagging 300 m from point A The load resistance and reactance of the distributor is 0·2 Ω and 0·1 Ω per kilometer. Calculate the total voltage drop in the distributor. The load power factors refer to the voltage at the far end.
  • 8. • Solution. Fig. shows the single line diagram of the distributor. Impedance of distributor/km = (0·2 + j 0·1) Ω Impedance of section AC, ZAC = (0·2 + j 0·1) × 200/1000 = (0·04 + j 0·02) Ω Impedance of section CB, ZCB = (0·2 + j 0·1) × 100/1000 = (0·02 + j 0·01) Ω Taking voltage at the far end B as the reference vector, we have, Load current at point B, I2 = I2 (cos φ2 − j sin φ2) = 200 (0·8 − j 0·6) = (160 − j 120) A Load current at point C, I1 = I1 (cos φ1 − j sin φ1) = 100 (0·707 − j 0·707) = (70·7− j 70·7) A Current in section CB, ICB = I2 = (160 − j 120) A Current in section AC, IAC = I1 + I2 = (70·7 − j 70·7) + (160 − j 120) = (230·7 − j 190·7) A Voltage drop in section CB, VCB = ICB ZCB = (160 − j 120) (0·02 + j 0·01) = (4·4 − j 0·8) volts Voltage drop in section AC, VAC = IAC ZAC = (230·7 − j 190·7) (0·04 + j 0·02) = (13·04 − j 3·01) volts Voltage drop in the distributor = VAC + VCB = (13·04 − j 3·01) + (4·4 − j 0·8) = (17·44 − j 3·81) volts Magnitude of drop = 17 44 3 81 a ⋅ f2 + a ⋅ f2 = 17·85 V
  • 9. 3-Phase Unbalanced Loads • The 3-phase loads that have the same impedance and power factor in each phase are called balanced loads. The problems on balanced loads can be solved by considering one phase only • The conditions in the other two phases being similar. However, we may come across a situation when loads are unbalanced i.e. each load phase has different impedance and/or power factor. • In that case, current and power in each phase will be different. In practice, we may come across the following unbalanced loads: (i) Four-wire star-connected unbalanced load (ii) Unbalanced Δ-connected load (iii) Unbalanced 3-wire, Y-connected load
  • 10. Four-Wire Star-Connected Unbalanced Loads • We can obtain this type of load in two ways. First, we may connect a 3-phase, 4-wire unbalanced load to a 3-phase, 4-wire supply as shown in Fig. Note that star point N of the supply is connected to the load star point N′. Secondly, we may connect single phase loads between any line and the neutral wire as shown in Fig. • This will also result in a 3-phase, 4-wire **unbalanced load because it is rarely possible that single phase loads on all the three phases have the same magnitude and power factor. Since the load is unbalanced, the line currents will be different in magnitude and displaced from one another by unequal angles. The current in the neutral wire will be the phasor sum of the three line currents i.e. Current in neutral wire, IN = IR + IY + IB ... phasor sum
  • 11. The following points may be noted carefully : (i) Since the neutral wire has negligible resistance, supply neutral N and load neutral N′ will be at the same potential. It means that voltage across each impedance is equal to the phase voltage of the supply. However, current in each phase (or line) will be different due to unequal impedances.
  • 12. (ii) The amount of current flowing in the neutral wire will depend upon the magnitudes of line • Currents and their phasor relations. In most circuits encountered in practice, the neutral current is equal to or smaller than one of the line currents. The exceptions are those circuits having severe unbalance. • No doubt 3-phase loads (e.g. 3-phase motors) connected to this supply are balanced but when we add single phase loads the balance is lost. • It is because it is rarely possible that single phase loads on all the three phases have the same magnitude and power factor. •actual practice, we never have an unbalanced 3-phase, 4-wire load. Most of the 3-phase loads are 3-phase, 3-wire and are balanced loads. • In fact, these are the single phase loads on the 3-phase, 4-wire supply which constitute unbalanced, 4-wire Y-connected load.
  • 13. Ground Detectors •Ground detectors are the devices that are used to detect the ground fault for ungrounded a.c. systems. •When a ground fault occurs on such a system, immediate steps should be taken to clear it. • If this is not done and a second ground fault happens, a short circuit occurs. Fig. shows how lamps are connected to an ungrounded 3- phase system for the detection of ground fault. • If ground fault occurs on any wire, the lamp connected to that wire will be dim and the lamps connected to healthy (ungrounded) wire will become brighter.
  • 14.
  • 15. MCQs
  • 16. Answers i. Unbalanced ii. 230∟120 ° iii. Vector ally iv. Half v. Single phase 2-wire