VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
HVAC SYSTEM
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-00
A.S A.S A.I
HVAC SET
PROJECT: ABU FETRA VILLA
CLIENT: ABU FETRA
LOCATION: KUWAIT CITY, KUWAIT
00 28/04/2020 DESIGN - INTENT - 01
CEILING MOUNTED F.C.U
CUT OFF &
COMBINED METERING
RETURN
CHILED WATER
SUPPLY
CHILLED WATER
AUXILIARY
CONTROL 2-WAY VALVE
CUT OFF VALVE
COLLAR
DIELECTRIC
FILTER
BALANCING VALVE
CONNECTION
CONNECTION
ELECTRICAL
INLET
DRAIN PAN
STRAINER
FLOW DIRECTION
FLOW DIRECTION
AIR DIRECTION
AIR DIRECTION
FAN & MOTOR
FAN & MOTOR
COIL
FLOW METER
REF.
NAME
SUPPORTING
ANGLE SIZE
MAX. DUCT
(mm)
HANGING ROD SIZE
SIZE. (mm) (mm) SPACING (mm)
TABLE
THIS TABLE IS BASED ON DW/144 FOR FIGURE-68
CONCRETE SLAB
32
32 25
25 DUCT SIZE
DUCT SIZE
DUCT
SIZE
DUCT SUPPORTING DETAILS
SCALE N.T.S.
G.I. THREADED ROD
(REFER TO SCHEDULE)
WASHER (TYP.)
DOUBLE LOCKNUT W/
EXPANSION SHIELD
(TYPICAL)
MS ANGLE
(REFER TO SCHEDULE)
LOCKNUT W/ WASHER
GA6
GA5
GA4
GA3
GA2
GA1
3000 60x60x6 2500mm 12mm
2000 50x50x5 2500mm 10mm
1500 40x40x3 2500mm 10mm
1000 30x30x3 3000mm 8mm
600 25x25x3 3000mm 8mm
400 25x25x1.6 3000mm 8mm
LEGEND :
APPLICATION :
NOTE :
8
2a
6
7
3
4
1
2
4A
5
5A
3
1
2
2a
4 OR 5
7
3
-
2
1
-
2a
4 7
6
-
6
8
3
2
1
2a
5 7
6 8
-
3
2
1
2a
4A 7
6 8
3
2
1
2a
5A 7
6 8
**
**
**
**
**
*
ADHESIVE FOR LINEAR INSULATION
SELF ADHESIVE PIN
ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE
50x50x0.6mm G.I CORNER ANGLE
ALUMINUM CLADDING (0.7mm THICKNESS)
ACOUSTIC DUCT LINER
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1
G.I DUCTING
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1
ELASTOMERIC FOAM
TYPE
DI-2
DI-1
SCHEDULE OF INSULATION
INSULATION TYPE THICKNESS
(mm)
25
25
DENSITY
(Kg/m )
64
64
3
THERMAL
CONDUCTIVITY
(W/M°K)
0.037
0.037
MAXIMUM
TEMP. RATING
(°C)
85
85
APPLICATION
CONCEALED SUPPLY/RETURN IN CONDITIONED AREA
INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY
& RETURN DUCT .
IN SHAFT, TUNNELS & NON CONDITIONED SPACE.
APLICABLE ONLY FROM THE FAN OUTLET,
ACOUSTIC DUCT LINER @3 METER LENGTH,
GRILLE & PLENUM BOX OR TO FIRST BRANCH.
INDOOR A/C SUPPLY & RETURN DUCT
IN CONDENSING SPACE.
REFER TO DUCT LINEAR INSULATION DETAILS
INDOOR A/C SUPPLY & RETURN DUCT
IN MECHANICAL ROOMS & CONDITIONED SPACE.
REFER TO NOTE:
REFER TO DUCT LINEAR INSULATION DETAILS
INSULATION
ELASTOMERIC FOAM
INSULATION
FINISH
F1
F2
TYPE
FINISH TYPE
FACTORY APPLIED
ALUMINUM FOIL
ALUMINUM CLADING
0.7mm THICKNESS
DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED
ELASTOMERIC FOAM
INSULATION
F2
ALUMINUM CLADING
0.7mm THICKNESS
DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH
ELASTOMERIC FOAM
INSULATION
F1+F2 ALUMINUM CLADING
85
85 ALUMINUM FOIL
CONDITIONED AREA IN MECHANICAL ROOMS
AREAS (TUNNELS & SHAFTS)
* AT MEAN TEMPERATURE OF 20°C
REFER TO SPECIFICATION SECTION 15341
REFER TO MECHANICAL SUBMITTAL
REFERENCE 11- MA-004-A
TYPICAL DUCT INSULATION AND LAGGING DETAIL
SCALE N.T.S.
CAPACITY
AIR FLOW
L/S
DIA.
FLEX. DUCT
(mm)
-
TYPICAL FLEXIBLE DUCT HANGER DETAILS
(AS PER SPECIFICATION)
INSULATION
FIBERGLASS
SPACING
(41.7mm PER m) OF SUPPORT
MAX. SAG 12.7mm PER 300mm
NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED,
25.4 x 0.85mm
DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A
CONNECTION BEFORE BENDING.
FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm.
G.I. ROD 2.75
@1500mm O.C.
(MAXIMUM)
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
G.I. STRAP
ALUMINUM
FLEXIBLE DUCT
-
UP TO 30
100 160
61 TO 90
200
91 TO 135
250
136 TO 200
300
201 TO 300 301 TO 380
350
381 TO 500
400
125
31 TO 60
SCALE N.T.S.
TYPICAL SPLITTER DETAIL
06
013 NTS
ECCENTRIC TRANSITION
DIVERGING MAX. 30°
x W
W1 x D1
=
A
MAIN
DUCT
AIR FLOW
W2 x D2
=
B
R = 0.75W
R1 = A + R
MAIN
DUCT
R
R1
BRANCH
DUCT
(W1 x D1) + (W2 x D2)
(W1 x D1) + (W2 x D2)
x W
V.D
V.D
"B"
W
x
D
"A"
1000mm
min.
W1 x D1
W2
x
D2
40mm
4
0
m
m
1
5
m
m
DUCT DETAILS FLESIBLE CONNECTION
08
013 NTS
8mm FLANGE
SEALING COMPOUND APPLIED BETWEEN FABRIC,
BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY*
* REQUIRED ON HIGH PRESSURE SYSTEMS ONLY
BOLT ON 100mm
CENTERS
ROUND (FAN INLET)
SEALING COMPOUND
APPLIED BETWEEN
FLEXIBLE
CONNECTION AND
CASING BEFORE
ASSEMBLY *
RECTANGULAR (FAN OUTLET)
RUBBER
IMPREGNATED
FABRIC
CASING
DUCT
40mm POCKET
SLIP
ALTERNATE POSITION
OF BOLT
25mm x 3mm
BAND IRON
BOLT ON
100mm CENTERS
25mm FLANGE
AND HEM
20 U.S. GAUGE
STEEL
25mm x 3mm
BAND IRON
SHEET METAL SCREWS
ON 300mm CENTERS
25mm x 3mm
DRAW BAND
RUBBER
IMPREGNATED
FABRIC
RIVET ON 100mm
CENTERS
8mm
FLANGE
18 U.S. GAGE
STEEL
DUCT THRU WALL MOUNTING DETAIL
01
013 NTS
DUCTWORK
DUCT INSULATION (SEE
SPECS. FOR DETAILS)
NON-HARDENING
MASTIC SEALANT ALL
AROUND (TYPICAL)
#20 G.I. SHEET DUCT
SLEEVE ALL AROUND
REINFORCED DUCT TAPE
MASONRY WALL
50mm MAX. 50mm MAX.
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
2 3 4 5 6
B
C
D
E
F
G
H
7
1
A
I
60
60
60
60
7.28
0.48
5.82
1.50
1.50
1.34 1.34
0.23
0.23
0.23
0.23
0.16
0.23
0.23
0.25
0.25
0.25
0.25
0.25
5.06
0.51
0.56
1.63
2.98
0.33
0.55
0.23
0.23
2.31
2.47
0.23
0.23
0.99
0.41
1.19
1.63
1.87
0.31
1.35
2.50
3.00
0.33
1.83
3.00
4.87
1.08
0.78
1.73
0.48
0.94
0.97
0.90 1.10
0.60
0.68
0.62
0.84
0.19
1.35
0.97
1.00
0.47
0.72
0.46
0.56
0.53
0.63
1.00
0.89
1.25
0.83
1.58
0.38
0.33
2.00
0.50
1.25 0.75 1.25
0.69
0.55
1.15
3.25
0.50
2.00
1.58
0.94
0.97
0.96
0.93
0.62 1.03 0.57
0.82
0.78
0.52
1.04
0.57
0.32
1.00 1.00 1.00
0.90 1.42 1.43
1.75 0.17 1.51
1.55
0.22
1.73
1.97
1.13
0.25
4.00
4.00
1.00
1.00
1.00
0.56
0.31
0.68
0.75
1.64
1.50
0.48
0.74
0.44
1.13
1.13
1.13
2.10
0.20
1.60
1.43
0.68
1.12
1.20
1.00
1.60
0.45
0.48
1.60
2.61
1.28
0.16
1.90
0.66
1.50
1.14
0.56
1.00
1.00
0.90
0.38
4.00
4.50
3.75
4.00
0.42
1.67
0.46
0.51
1.50
0.45
1.03
0.23
1.56 0.16 0.53
1.30 0.76
1.00
0.61
0.36
0.80
0.18
1.56
1.50
1.53
0.75
0.56
0.31
1.92
0.83
0.53
1.00 1.00 1.00 1.00 1.00
0.94 1.48 1.38 1.82
1.78 0.20 1.82 0.19 1.58
0.38
4.07
4.07
1.92
1.00 1.00 1.00 1.00 1.00
0.83
0.53
1.86
0.21
1.78
0.20
1.53
0.92
1.50
1.27
1.98
0.38
6.00
6.00
FCU-BF.02.1 / 3.0 TR
FCU-BF.03.3 / 2.5 TR
FCU-BF.03.2 / 2.5 TR
FCU-BF.04.2 / 2.0 TR
FCU-BF.01.1 / 3.5 TR
FCU-BF.03.1
/
2.5
TR
FCU-BF.04.1
/
2.0
TR
W.SU-BF.02.1 / 1.5 TR
W.SU-BF.01.1
/
2.0
TR
Size: 250x250
BOD: 4.15m
Size: 350x350
BOD: 4.10m
Size: 450x350
BOD: 4.10m
Size: 450x350
BOD: 4.10m
Size: 350x350
BOD: 4.10m
Size: 250x250
BOD: 4.15m
Size: 250x200
BOD: 3.31m
Size: 350x300
BOD: 3.26m
Size: 200x200
BOD: 3.31m
Size: 300x300
BOD: 3.26m
Size: 500x300
BOD: 3.26m
Size: 500x300
BOD: 3.26m
Size: 250x250
BOD: 3.55m
Size: 250x250
BOD: 3.55m
Size: 400x250
BOD: 3.55m
Size: 450x300
BOD: 3.52m
Size: 350x300
BOD: 3.52m
Size: 250x250
BOD: 3.55m
Size: 200x200
BOD: 3.57m
Size: 250x250
BOD: 3.69m
Size: 350x300
BOD: 3.66m
Size: 500x350
BOD: 3.64m
Size: 350x300
BOD: 3.66m
Size: 250x250
BOD: 3.69m
Size: 250x200
BOD: 3.50m
Size: 300x250
BOD: 3.48m
Size: 200x200
BOD: 3.50m
Size: 400x250
BOD: 3.47m
Size: 400x250
BOD: 3.48m
125 Ф 125 Ф
125 Ф
200 Ф
200 Ф
200 Ф
200 Ф
125 Ф
125 Ф
125 Ф
125 Ф
125 Ф
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
8.50 m
1200 CFM
7.58 m
1200 CFM
1 1
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
12.00 m
1000 CFM
12 m
1000 CFM
3 3
6.00
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
6.00 m
800 CFM
10.05 m
800 CFM
1
2.00
2.50
0.73
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
8.50 m
1400 CFM
7.75 m
1400 CFM
2 2
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
8.00 m
1000 CFM
10.04 m
1000 CFM
1
2.88
1.63
0.98
0.50
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
6.50 m
800 CFM
5 m
800 CFM
1 1
A
AC-14
B
AC-15
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
BASEMENT FLOOR HVAC DUCTING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-01
A.S A.S A.I
SCALE 1 : 65
BASEMENT FLOOR HVAC DUCTING PLAN
01
AC
00 28/04/2020 DESIGN - INTENT - 01
CEILING MOUNTED F.C.U
CUT OFF &
COMBINED METERING
RETURN
CHILED WATER
SUPPLY
CHILLED WATER
AUXILIARY
CONTROL 2-WAY VALVE
CUT OFF VALVE
COLLAR
DIELECTRIC
FILTER
BALANCING VALVE
CONNECTION
CONNECTION
ELECTRICAL
INLET
DRAIN PAN
STRAINER
FLOW DIRECTION
FLOW DIRECTION
AIR DIRECTION
AIR DIRECTION
FAN & MOTOR
FAN & MOTOR
COIL
FLOW METER
REF.
NAME
SUPPORTING
ANGLE SIZE
MAX. DUCT
(mm)
HANGING ROD SIZE
SIZE. (mm) (mm) SPACING (mm)
TABLE
THIS TABLE IS BASED ON DW/144 FOR FIGURE-68
CONCRETE SLAB
32
32 25
25 DUCT SIZE
DUCT SIZE
DUCT
SIZE
DUCT SUPPORTING DETAILS
SCALE N.T.S.
G.I. THREADED ROD
(REFER TO SCHEDULE)
WASHER (TYP.)
DOUBLE LOCKNUT W/
EXPANSION SHIELD
(TYPICAL)
MS ANGLE
(REFER TO SCHEDULE)
LOCKNUT W/ WASHER
GA6
GA5
GA4
GA3
GA2
GA1
3000 60x60x6 2500mm 12mm
2000 50x50x5 2500mm 10mm
1500 40x40x3 2500mm 10mm
1000 30x30x3 3000mm 8mm
600 25x25x3 3000mm 8mm
400 25x25x1.6 3000mm 8mm
LEGEND :
APPLICATION :
NOTE :
8
2a
6
7
3
4
1
2
4A
5
5A
3
1
2
2a
4 OR 5
7
3
-
2
1
-
2a
4 7
6
-
6
8
3
2
1
2a
5 7
6 8
-
3
2
1
2a
4A 7
6 8
3
2
1
2a
5A 7
6 8
**
**
**
**
**
*
ADHESIVE FOR LINEAR INSULATION
SELF ADHESIVE PIN
ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE
50x50x0.6mm G.I CORNER ANGLE
ALUMINUM CLADDING (0.7mm THICKNESS)
ACOUSTIC DUCT LINER
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1
G.I DUCTING
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1
ELASTOMERIC FOAM
TYPE
DI-2
DI-1
SCHEDULE OF INSULATION
INSULATION TYPE THICKNESS
(mm)
25
25
DENSITY
(Kg/m )
64
64
3
THERMAL
CONDUCTIVITY
(W/M°K)
0.037
0.037
MAXIMUM
TEMP. RATING
(°C)
85
85
APPLICATION
CONCEALED SUPPLY/RETURN IN CONDITIONED AREA
INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY
& RETURN DUCT .
IN SHAFT, TUNNELS & NON CONDITIONED SPACE.
APLICABLE ONLY FROM THE FAN OUTLET,
ACOUSTIC DUCT LINER @3 METER LENGTH,
GRILLE & PLENUM BOX OR TO FIRST BRANCH.
INDOOR A/C SUPPLY & RETURN DUCT
IN CONDENSING SPACE.
REFER TO DUCT LINEAR INSULATION DETAILS
INDOOR A/C SUPPLY & RETURN DUCT
IN MECHANICAL ROOMS & CONDITIONED SPACE.
REFER TO NOTE:
REFER TO DUCT LINEAR INSULATION DETAILS
INSULATION
ELASTOMERIC FOAM
INSULATION
FINISH
F1
F2
TYPE
FINISH TYPE
FACTORY APPLIED
ALUMINUM FOIL
ALUMINUM CLADING
0.7mm THICKNESS
DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED
ELASTOMERIC FOAM
INSULATION
F2
ALUMINUM CLADING
0.7mm THICKNESS
DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH
ELASTOMERIC FOAM
INSULATION
F1+F2 ALUMINUM CLADING
85
85 ALUMINUM FOIL
CONDITIONED AREA IN MECHANICAL ROOMS
AREAS (TUNNELS & SHAFTS)
* AT MEAN TEMPERATURE OF 20°C
REFER TO SPECIFICATION SECTION 15341
REFER TO MECHANICAL SUBMITTAL
REFERENCE 11- MA-004-A
TYPICAL DUCT INSULATION AND LAGGING DETAIL
SCALE N.T.S.
CAPACITY
AIR FLOW
L/S
DIA.
FLEX. DUCT
(mm)
-
TYPICAL FLEXIBLE DUCT HANGER DETAILS
(AS PER SPECIFICATION)
INSULATION
FIBERGLASS
SPACING
(41.7mm PER m) OF SUPPORT
MAX. SAG 12.7mm PER 300mm
NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED,
25.4 x 0.85mm
DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A
CONNECTION BEFORE BENDING.
FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm.
G.I. ROD 2.75
@1500mm O.C.
(MAXIMUM)
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
G.I. STRAP
ALUMINUM
FLEXIBLE DUCT
-
UP TO 30
100 160
61 TO 90
200
91 TO 135
250
136 TO 200
300
201 TO 300 301 TO 380
350
381 TO 500
400
125
31 TO 60
SCALE N.T.S.
TYPICAL SPLITTER DETAIL
06
013 NTS
ECCENTRIC TRANSITION
DIVERGING MAX. 30°
x W
W1 x D1
=
A
MAIN
DUCT
AIR FLOW
W2 x D2
=
B
R = 0.75W
R1 = A + R
MAIN
DUCT
R
R1
BRANCH
DUCT
(W1 x D1) + (W2 x D2)
(W1 x D1) + (W2 x D2)
x W
V.D
V.D
"B"
W
x
D
"A"
1000mm
min.
W1 x D1
W2
x
D2
40mm
4
0
m
m
1
5
m
m
DUCT DETAILS FLESIBLE CONNECTION
08
013 NTS
8mm FLANGE
SEALING COMPOUND APPLIED BETWEEN FABRIC,
BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY*
* REQUIRED ON HIGH PRESSURE SYSTEMS ONLY
BOLT ON 100mm
CENTERS
ROUND (FAN INLET)
SEALING COMPOUND
APPLIED BETWEEN
FLEXIBLE
CONNECTION AND
CASING BEFORE
ASSEMBLY *
RECTANGULAR (FAN OUTLET)
RUBBER
IMPREGNATED
FABRIC
CASING
DUCT
40mm POCKET
SLIP
ALTERNATE POSITION
OF BOLT
25mm x 3mm
BAND IRON
BOLT ON
100mm CENTERS
25mm FLANGE
AND HEM
20 U.S. GAUGE
STEEL
25mm x 3mm
BAND IRON
SHEET METAL SCREWS
ON 300mm CENTERS
25mm x 3mm
DRAW BAND
RUBBER
IMPREGNATED
FABRIC
RIVET ON 100mm
CENTERS
8mm
FLANGE
18 U.S. GAGE
STEEL
DUCT THRU WALL MOUNTING DETAIL
01
013 NTS
DUCTWORK
DUCT INSULATION (SEE
SPECS. FOR DETAILS)
NON-HARDENING
MASTIC SEALANT ALL
AROUND (TYPICAL)
#20 G.I. SHEET DUCT
SLEEVE ALL AROUND
REINFORCED DUCT TAPE
MASONRY WALL
50mm MAX. 50mm MAX.
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
2 3 4 5 6
B
C
D
E
F
G
H
7
1
A
I
0.26
0.26
0.27
0.26
0.25
0.25
0.25
3.15
1.22
1.38
1.19
0.61
0.31
0.83
0.83
1.42
1.10
0.51
1.26
1.16
1.00
1.40
1.19
1.42
0.83
0.83
0.70
0.40
0.21
1.25
1.86
0.24
1.76
0.20
1.77
0.28
1.62
1.50
1.36
1.87
2.08
1.80
1.84
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.72
0.42
8.00
6.00
2.39
1.86
0.20
1.80
0.22
1.80
0.22
1.68
1.56
1.28
1.92
2.02
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.72
0.42
0.40 2.36
2.50
3.15
0.60
2.50
1.65
0.17
1.81
0.21
0.88
0.71
0.79
1.70
1.98
1.00
1.00
1.00
1.00
0.62
0.32
1.60 1.89
2.59
4.52
0.75
5.00
1.93
0.17
1.88
0.18
0.88
0.71
0.83
1.62
2.00
1.00
1.00
1.00
1.00
0.53
0.83
1.54
0.83
1.96
0.28
5.00
2.00
2.25
FCU-GF.03.1
/
2.5
TR
Size: 300x250
BOD: 3.87m
Size: 400x350
BOD: 3.82m
Size: 450x400
BOD: 3.80m
Size: 550x400
BOD: 3.80m
Size: 550x400
BOD: 3.80m
Size: 450x400
BOD: 3.80m
Size: 400x350
BOD: 3.82m
Size: 300x250
BOD: 3.87m
Size: 200x200
BOD: 4.30m
Size: 300x300
BOD: 4.25m
Size: 350x350
BOD: 4.22m
Size: 600x350
BOD: 4.22m
Size: 200x200
BOD: 4.30m
Size: 300x300
BOD: 4.25m
Size: 350x350
BOD: 4.22m
Size: 600x350
BOD: -0.89m
Size: 300x300
BOD: 4.24m
Size: 300x300
BOD: 4.24m
Size: 300x300
BOD: 4.24m
Size: 500x300
BOD: 4.24m
FCU-BF.03.1
/
2.5
TR
FCU-GF.03.2 / 2.5 TR
FCU-GF.01.1 / 3.0 TR
W.SU-BF.01.1 / 2.0 TR
W.SU-BF.01.2 / 2.0 TR
Size: 550x400
BOD: 4.19m
200 Ф
200 Ф
200 Ф
200 Ф
200 Ф 200 Ф
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
10.00 m
1200 CFM
10.54 m
1200 CFM
2 2
4.52
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
5.00 m
1000 CFM
7.5 m
1000 CFM
2 2
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
16.00 m
2000 CFM
12 m
2000 CFM
3 3
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
GROUND FLOOR HVAC DUCTING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-02
A.S A.S A.I
SCALE 1 : 65
GROUND FLOOR HVAC DUCTING PLAN
02
AC
00 28/04/2020 DESIGN - INTENT - 01
CEILING MOUNTED F.C.U
CUT OFF &
COMBINED METERING
RETURN
CHILED WATER
SUPPLY
CHILLED WATER
AUXILIARY
CONTROL 2-WAY VALVE
CUT OFF VALVE
COLLAR
DIELECTRIC
FILTER
BALANCING VALVE
CONNECTION
CONNECTION
ELECTRICAL
INLET
DRAIN PAN
STRAINER
FLOW DIRECTION
FLOW DIRECTION
AIR DIRECTION
AIR DIRECTION
FAN & MOTOR
FAN & MOTOR
COIL
FLOW METER
REF.
NAME
SUPPORTING
ANGLE SIZE
MAX. DUCT
(mm)
HANGING ROD SIZE
SIZE. (mm) (mm) SPACING (mm)
TABLE
THIS TABLE IS BASED ON DW/144 FOR FIGURE-68
CONCRETE SLAB
32
32 25
25 DUCT SIZE
DUCT SIZE
DUCT
SIZE
DUCT SUPPORTING DETAILS
SCALE N.T.S.
G.I. THREADED ROD
(REFER TO SCHEDULE)
WASHER (TYP.)
DOUBLE LOCKNUT W/
EXPANSION SHIELD
(TYPICAL)
MS ANGLE
(REFER TO SCHEDULE)
LOCKNUT W/ WASHER
GA6
GA5
GA4
GA3
GA2
GA1
3000 60x60x6 2500mm 12mm
2000 50x50x5 2500mm 10mm
1500 40x40x3 2500mm 10mm
1000 30x30x3 3000mm 8mm
600 25x25x3 3000mm 8mm
400 25x25x1.6 3000mm 8mm
LEGEND :
APPLICATION :
NOTE :
8
2a
6
7
3
4
1
2
4A
5
5A
3
1
2
2a
4 OR 5
7
3
-
2
1
-
2a
4 7
6
-
6
8
3
2
1
2a
5 7
6 8
-
3
2
1
2a
4A 7
6 8
3
2
1
2a
5A 7
6 8
**
**
**
**
**
*
ADHESIVE FOR LINEAR INSULATION
SELF ADHESIVE PIN
ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE
50x50x0.6mm G.I CORNER ANGLE
ALUMINUM CLADDING (0.7mm THICKNESS)
ACOUSTIC DUCT LINER
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1
G.I DUCTING
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1
ELASTOMERIC FOAM
TYPE
DI-2
DI-1
SCHEDULE OF INSULATION
INSULATION TYPE THICKNESS
(mm)
25
25
DENSITY
(Kg/m )
64
64
3
THERMAL
CONDUCTIVITY
(W/M°K)
0.037
0.037
MAXIMUM
TEMP. RATING
(°C)
85
85
APPLICATION
CONCEALED SUPPLY/RETURN IN CONDITIONED AREA
INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY
& RETURN DUCT .
IN SHAFT, TUNNELS & NON CONDITIONED SPACE.
APLICABLE ONLY FROM THE FAN OUTLET,
ACOUSTIC DUCT LINER @3 METER LENGTH,
GRILLE & PLENUM BOX OR TO FIRST BRANCH.
INDOOR A/C SUPPLY & RETURN DUCT
IN CONDENSING SPACE.
REFER TO DUCT LINEAR INSULATION DETAILS
INDOOR A/C SUPPLY & RETURN DUCT
IN MECHANICAL ROOMS & CONDITIONED SPACE.
REFER TO NOTE:
REFER TO DUCT LINEAR INSULATION DETAILS
INSULATION
ELASTOMERIC FOAM
INSULATION
FINISH
F1
F2
TYPE
FINISH TYPE
FACTORY APPLIED
ALUMINUM FOIL
ALUMINUM CLADING
0.7mm THICKNESS
DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED
ELASTOMERIC FOAM
INSULATION
F2
ALUMINUM CLADING
0.7mm THICKNESS
DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH
ELASTOMERIC FOAM
INSULATION
F1+F2 ALUMINUM CLADING
85
85 ALUMINUM FOIL
CONDITIONED AREA IN MECHANICAL ROOMS
AREAS (TUNNELS & SHAFTS)
* AT MEAN TEMPERATURE OF 20°C
REFER TO SPECIFICATION SECTION 15341
REFER TO MECHANICAL SUBMITTAL
REFERENCE 11- MA-004-A
TYPICAL DUCT INSULATION AND LAGGING DETAIL
SCALE N.T.S.
CAPACITY
AIR FLOW
L/S
DIA.
FLEX. DUCT
(mm)
-
TYPICAL FLEXIBLE DUCT HANGER DETAILS
(AS PER SPECIFICATION)
INSULATION
FIBERGLASS
SPACING
(41.7mm PER m) OF SUPPORT
MAX. SAG 12.7mm PER 300mm
NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED,
25.4 x 0.85mm
DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A
CONNECTION BEFORE BENDING.
FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm.
G.I. ROD 2.75
@1500mm O.C.
(MAXIMUM)
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
G.I. STRAP
ALUMINUM
FLEXIBLE DUCT
-
UP TO 30
100 160
61 TO 90
200
91 TO 135
250
136 TO 200
300
201 TO 300 301 TO 380
350
381 TO 500
400
125
31 TO 60
SCALE N.T.S.
TYPICAL SPLITTER DETAIL
06
013 NTS
ECCENTRIC TRANSITION
DIVERGING MAX. 30°
x W
W1 x D1
=
A
MAIN
DUCT
AIR FLOW
W2 x D2
=
B
R = 0.75W
R1 = A + R
MAIN
DUCT
R
R1
BRANCH
DUCT
(W1 x D1) + (W2 x D2)
(W1 x D1) + (W2 x D2)
x W
V.D
V.D
"B"
W
x
D
"A"
1000mm
min.
W1 x D1
W2
x
D2
40mm
4
0
m
m
1
5
m
m
DUCT DETAILS FLESIBLE CONNECTION
08
013 NTS
8mm FLANGE
SEALING COMPOUND APPLIED BETWEEN FABRIC,
BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY*
* REQUIRED ON HIGH PRESSURE SYSTEMS ONLY
BOLT ON 100mm
CENTERS
ROUND (FAN INLET)
SEALING COMPOUND
APPLIED BETWEEN
FLEXIBLE
CONNECTION AND
CASING BEFORE
ASSEMBLY *
RECTANGULAR (FAN OUTLET)
RUBBER
IMPREGNATED
FABRIC
CASING
DUCT
40mm POCKET
SLIP
ALTERNATE POSITION
OF BOLT
25mm x 3mm
BAND IRON
BOLT ON
100mm CENTERS
25mm FLANGE
AND HEM
20 U.S. GAUGE
STEEL
25mm x 3mm
BAND IRON
SHEET METAL SCREWS
ON 300mm CENTERS
25mm x 3mm
DRAW BAND
RUBBER
IMPREGNATED
FABRIC
RIVET ON 100mm
CENTERS
8mm
FLANGE
18 U.S. GAGE
STEEL
DUCT THRU WALL MOUNTING DETAIL
01
013 NTS
DUCTWORK
DUCT INSULATION (SEE
SPECS. FOR DETAILS)
NON-HARDENING
MASTIC SEALANT ALL
AROUND (TYPICAL)
#20 G.I. SHEET DUCT
SLEEVE ALL AROUND
REINFORCED DUCT TAPE
MASONRY WALL
50mm MAX. 50mm MAX.
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
2 3 4 5 6
C
D
E
F
G
0.26
0.26
0.26
0.26
0.54 0.70 0.21 0.83 0.20 0.79 0.22 1.50
0.60 1.52 0.98 1.34
2.39
0.81
4.00
4.00
1.00 1.00 1.00
1.01
0.79 1.48 1.45 1.06 1.40 1.14
1.49 1.18 1.80 1.20 1.20
1.04 1.04 1.04 1.04 1.04
0.62
0.32
6.25
1.04
6.25
1.15
0.72
1.82 0.78 0.18 0.89 0.22 1.83 0.20 1.58 1.40
1.92 1.57 1.31 1.90 1.60
5.00
4.00
1.00 1.00 1.00 1.00
0.76
0.46
0.25
1.26
2.56
0.90
0.78 0.22 0.85 0.22 1.83 0.20 1.58 1.40
1.55
1.65
1.82
1.00 1.00 1.00 1.00
0.76
0.46
1.90 1.55 1.23 2.02 1.60
0.41
0.34
1.68 0.87 0.22 0.85 0.79
1.20 1.56 0.87
1.00 1.00
0.69
0.39
0.66
1.47
0.42
1.21
0.96
1.10 1.40 0.77
0.49 1.30 1.10
0.86
0.19
0.75
0.24
0.80
0.23
0.66
1.40
1.35
1.20
0.89
1.06
1.06
1.44
4.00
0.66
0.71
0.41
1.00
1.00
1.00
4.00
Size: 250x200
BOD: 3.15m
Size: 300x300
BOD: 3.10m
Size: 350x350
BOD: 3.07m
Size: 450x350
BOD: 3.07m
Size: 450x300
BOD: 3.10m
Size: 200x200
BOD: 3.40m
Size: 200x200
BOD: 3.40m
Size: 300x250
BOD: 3.37m
Size: 300x250
BOD: 3.37m
Size: 250x200
BOD: 3.15m
Size: 450x300
BOD: 3.10m
Size: 550x300
BOD: 3.10m
Size: 250x250
BOD: 3.13m
Size: 350x300
BOD: 3.10m
Size: 350x300
BOD: 3.10m
Size: 350x300
BOD: 3.10m
Size: 500x300
BOD: 3.10m
Size: 500x300
BOD: 3.10m
Size: 500x300
BOD: 3.10m
Size: 500x300
BOD: 3.10m
Size: 400x300
BOD: 3.10m
Size: 300x300
BOD: 3.10m
Size: 250x250
BOD: 3.12m
FCU-1F.02.2
/
3.0
TR
FCU-1F.04.1
/
1.5
TR
FCU-1F.02.2
/
3.0
TR
FCU-1F.03.1
/
2.0
TR
FCU-1F.01.2
/
2.5
TR
FCU-1F.01.1
/
3.25
TR
125 Ф
200 Ф
0.61
0.31
200 Ф
200 Ф
200 Ф
200 Ф
0.95
0.41
0.97
0.66
0.31
0.37
0.33
0.36
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
4.00 m
1200 CFM
4 m
1200 CFM
3 3
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
3.00 m
800 CFM
3 m
800 CFM
3 3
3.00
3.00
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
10.00 m
2600 CFM
8 m
2600 CFM
3 3
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
6.25 m
600 CFM
8.33 m
600 CFM
1 1
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
4.00 m
1200 CFM
4 m
1200 CFM
3 3
C
AC-17
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
FIRST FLOOR HVAC DUCTING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-03
A.S A.S A.I
SCALE 1 : 65
FIRST FLOOR HVAC DUCTING PLAN
03
AC
00 28/04/2020 DESIGN - INTENT - 01
CEILING MOUNTED F.C.U
CUT OFF &
COMBINED METERING
RETURN
CHILED WATER
SUPPLY
CHILLED WATER
AUXILIARY
CONTROL 2-WAY VALVE
CUT OFF VALVE
COLLAR
DIELECTRIC
FILTER
BALANCING VALVE
CONNECTION
CONNECTION
ELECTRICAL
INLET
DRAIN PAN
STRAINER
FLOW DIRECTION
FLOW DIRECTION
AIR DIRECTION
AIR DIRECTION
FAN & MOTOR
FAN & MOTOR
COIL
FLOW METER
REF.
NAME
SUPPORTING
ANGLE SIZE
MAX. DUCT
(mm)
HANGING ROD SIZE
SIZE. (mm) (mm) SPACING (mm)
TABLE
THIS TABLE IS BASED ON DW/144 FOR FIGURE-68
CONCRETE SLAB
32
32 25
25 DUCT SIZE
DUCT SIZE
DUCT
SIZE
DUCT SUPPORTING DETAILS
SCALE N.T.S.
G.I. THREADED ROD
(REFER TO SCHEDULE)
WASHER (TYP.)
DOUBLE LOCKNUT W/
EXPANSION SHIELD
(TYPICAL)
MS ANGLE
(REFER TO SCHEDULE)
LOCKNUT W/ WASHER
GA6
GA5
GA4
GA3
GA2
GA1
3000 60x60x6 2500mm 12mm
2000 50x50x5 2500mm 10mm
1500 40x40x3 2500mm 10mm
1000 30x30x3 3000mm 8mm
600 25x25x3 3000mm 8mm
400 25x25x1.6 3000mm 8mm
LEGEND :
APPLICATION :
NOTE :
8
2a
6
7
3
4
1
2
4A
5
5A
3
1
2
2a
4 OR 5
7
3
-
2
1
-
2a
4 7
6
-
6
8
3
2
1
2a
5 7
6 8
-
3
2
1
2a
4A 7
6 8
3
2
1
2a
5A 7
6 8
**
**
**
**
**
*
ADHESIVE FOR LINEAR INSULATION
SELF ADHESIVE PIN
ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE
50x50x0.6mm G.I CORNER ANGLE
ALUMINUM CLADDING (0.7mm THICKNESS)
ACOUSTIC DUCT LINER
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1
G.I DUCTING
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1
ELASTOMERIC FOAM
TYPE
DI-2
DI-1
SCHEDULE OF INSULATION
INSULATION TYPE THICKNESS
(mm)
25
25
DENSITY
(Kg/m )
64
64
3
THERMAL
CONDUCTIVITY
(W/M°K)
0.037
0.037
MAXIMUM
TEMP. RATING
(°C)
85
85
APPLICATION
CONCEALED SUPPLY/RETURN IN CONDITIONED AREA
INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY
& RETURN DUCT .
IN SHAFT, TUNNELS & NON CONDITIONED SPACE.
APLICABLE ONLY FROM THE FAN OUTLET,
ACOUSTIC DUCT LINER @3 METER LENGTH,
GRILLE & PLENUM BOX OR TO FIRST BRANCH.
INDOOR A/C SUPPLY & RETURN DUCT
IN CONDENSING SPACE.
REFER TO DUCT LINEAR INSULATION DETAILS
INDOOR A/C SUPPLY & RETURN DUCT
IN MECHANICAL ROOMS & CONDITIONED SPACE.
REFER TO NOTE:
REFER TO DUCT LINEAR INSULATION DETAILS
INSULATION
ELASTOMERIC FOAM
INSULATION
FINISH
F1
F2
TYPE
FINISH TYPE
FACTORY APPLIED
ALUMINUM FOIL
ALUMINUM CLADING
0.7mm THICKNESS
DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED
ELASTOMERIC FOAM
INSULATION
F2
ALUMINUM CLADING
0.7mm THICKNESS
DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH
ELASTOMERIC FOAM
INSULATION
F1+F2 ALUMINUM CLADING
85
85 ALUMINUM FOIL
CONDITIONED AREA IN MECHANICAL ROOMS
AREAS (TUNNELS & SHAFTS)
* AT MEAN TEMPERATURE OF 20°C
REFER TO SPECIFICATION SECTION 15341
REFER TO MECHANICAL SUBMITTAL
REFERENCE 11- MA-004-A
TYPICAL DUCT INSULATION AND LAGGING DETAIL
SCALE N.T.S.
CAPACITY
AIR FLOW
L/S
DIA.
FLEX. DUCT
(mm)
-
TYPICAL FLEXIBLE DUCT HANGER DETAILS
(AS PER SPECIFICATION)
INSULATION
FIBERGLASS
SPACING
(41.7mm PER m) OF SUPPORT
MAX. SAG 12.7mm PER 300mm
NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED,
25.4 x 0.85mm
DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A
CONNECTION BEFORE BENDING.
FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm.
G.I. ROD 2.75
@1500mm O.C.
(MAXIMUM)
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
G.I. STRAP
ALUMINUM
FLEXIBLE DUCT
-
UP TO 30
100 160
61 TO 90
200
91 TO 135
250
136 TO 200
300
201 TO 300 301 TO 380
350
381 TO 500
400
125
31 TO 60
SCALE N.T.S.
TYPICAL SPLITTER DETAIL
06
013 NTS
ECCENTRIC TRANSITION
DIVERGING MAX. 30°
x W
W1 x D1
=
A
MAIN
DUCT
AIR FLOW
W2 x D2
=
B
R = 0.75W
R1 = A + R
MAIN
DUCT
R
R1
BRANCH
DUCT
(W1 x D1) + (W2 x D2)
(W1 x D1) + (W2 x D2)
x W
V.D
V.D
"B"
W
x
D
"A"
1000mm
min.
W1 x D1
W2
x
D2
40mm
4
0
m
m
1
5
m
m
DUCT DETAILS FLESIBLE CONNECTION
08
013 NTS
8mm FLANGE
SEALING COMPOUND APPLIED BETWEEN FABRIC,
BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY*
* REQUIRED ON HIGH PRESSURE SYSTEMS ONLY
BOLT ON 100mm
CENTERS
ROUND (FAN INLET)
SEALING COMPOUND
APPLIED BETWEEN
FLEXIBLE
CONNECTION AND
CASING BEFORE
ASSEMBLY *
RECTANGULAR (FAN OUTLET)
RUBBER
IMPREGNATED
FABRIC
CASING
DUCT
40mm POCKET
SLIP
ALTERNATE POSITION
OF BOLT
25mm x 3mm
BAND IRON
BOLT ON
100mm CENTERS
25mm FLANGE
AND HEM
20 U.S. GAUGE
STEEL
25mm x 3mm
BAND IRON
SHEET METAL SCREWS
ON 300mm CENTERS
25mm x 3mm
DRAW BAND
RUBBER
IMPREGNATED
FABRIC
RIVET ON 100mm
CENTERS
8mm
FLANGE
18 U.S. GAGE
STEEL
DUCT THRU WALL MOUNTING DETAIL
01
013 NTS
DUCTWORK
DUCT INSULATION (SEE
SPECS. FOR DETAILS)
NON-HARDENING
MASTIC SEALANT ALL
AROUND (TYPICAL)
#20 G.I. SHEET DUCT
SLEEVE ALL AROUND
REINFORCED DUCT TAPE
MASONRY WALL
50mm MAX. 50mm MAX.
2 3 4 5 6
B
C
D
E
F
G
EQ EQ
EQ
EQ
EQ
EQ
EQ EQ
EQ EQ
EQ
EQ
EQ EQ
EQ
EQ
0.37
0.37
EQ EQ
EQ
EQ
3.17
2.41
2.41
EQ EQ
EQ
EQ
2.62
2.62
EQ EQ
6.74
0.85
0.94
0.17
1.73
0.99
1.40
1.10
0.65
1.00
1.00
0.57
0.37
0.80
1.10
1.40
0.97
1.60
0.16
0.96
0.85
0.59
0.39
3.17
1.02
0.26
0.45
1.17
0.26
0.27
1.23 0.18 2.75
1.18
1.28
1.51
0.80
0.27
3.00
0.35
1.00 1.00
0.61
0.31
1.23 0.88 0.20 0.77 0.21 0.77 0.69 0.45
1.10
1.02
1.55
0.94
2.16
0.50
3.00
1.17
0.85
0.94
0.15
1.96
0.85
0.96 1.25
0.34
0.25
1.49
0.23
1.70
0.24
1.78
0.51
2.03
1.92
1.31
0.96
0.96
0.96
0.96
0.96
0.86
0.61
5.75
0.81
2.22
1.00
1.00
1.00
1.01
1.00
0.91
0.66
1.90
0.19
1.70
0.24
2.08
1.36
1.99
1.84
1.26
1.59
6.00
4.09
4.37
2.74
FCU-2F.01.1
/
3.25
TR
FCU-2F.04.2
/
2.0
TR
FCU-2F.05.1
/
1.5
TR
FCU-1F.03.1
/
2.5
TR
FCU-2F.01.2
/
3.25
TR
FCU-2F.02.1 / 3.0 TR
FCU-2F.04.1 / 2.0 TR
3.57
0.26
125 Ф 125 Ф
200 Ф
200 Ф
200 Ф
125 Ф
Size: 250x250
BOD: 3.03m
Size: 300x250
BOD: 3.03m
Size: 250x250
BOD: 2.67m
Size: 300x300
BOD: 2.65m
Size: 350x350
BOD: 2.62m
Size: 350x350
BOD: 2.92m
Size: 350x350
BOD: 3.10m
Size: 500x350
BOD: 3.12m
Size: 350x350
BOD: 3.12m
Size: 300x250
BOD: 3.17m
Size: 350x350
BOD: 3.12m
Size: 500x350
BOD: 3.12m
Size: 200x200
BOD: 3.10m
Size: 200x200
BOD: 3.10m
Size: 250x250
BOD: 3.08m
Size: 250x250
BOD: 3.08m
Size: 250x250
BOD: 3.08m
Size: 250x250
BOD: 3.08m
Size: 200x200
BOD: 3.10m
Size: 200x200
BOD: 3.10m
Size: 400x250
BOD: 3.08m
Size: 400x250
BOD: 3.08m
Size: 350x350
BOD: 2.92m
Size: 400x250
BOD: 3.08m
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
6.34 m
800 CFM
4.82 m
800 CFM
1 1
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
6.34 m
800 CFM
5.24 m
800 CFM
1 1
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
11.75 m
2600 CFM
14.94 m
2600 CFM
3 3
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
3.00 m
1200 CFM
3 m
1200 CFM
3 3
1.00
2.74
E
AC-18
F
AC-19
D
AC-16
QTY.
FLOW
DIM. (mm)
DIF. TYPE SSD SRD
400x400 400x400
1
1000 CFM 1000 CFM
1
QTY.
FLOW
DIM. (mm)
DIF. TYPE SSD SRD
225x225 225x225
1.40
1.75
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
SECOND FLOOR HVAC DUCTING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-04
A.S A.S A.I
SCALE 1 : 65
SECOND FLOOR HVAC DUCTING PLAN
04
AC
00 28/04/2020 DESIGN - INTENT - 01
CEILING MOUNTED F.C.U
CUT OFF &
COMBINED METERING
RETURN
CHILED WATER
SUPPLY
CHILLED WATER
AUXILIARY
CONTROL 2-WAY VALVE
CUT OFF VALVE
COLLAR
DIELECTRIC
FILTER
BALANCING VALVE
CONNECTION
CONNECTION
ELECTRICAL
INLET
DRAIN PAN
STRAINER
FLOW DIRECTION
FLOW DIRECTION
AIR DIRECTION
AIR DIRECTION
FAN & MOTOR
FAN & MOTOR
COIL
FLOW METER
REF.
NAME
SUPPORTING
ANGLE SIZE
MAX. DUCT
(mm)
HANGING ROD SIZE
SIZE. (mm) (mm) SPACING (mm)
TABLE
THIS TABLE IS BASED ON DW/144 FOR FIGURE-68
CONCRETE SLAB
32
32 25
25 DUCT SIZE
DUCT SIZE
DUCT
SIZE
DUCT SUPPORTING DETAILS
SCALE N.T.S.
G.I. THREADED ROD
(REFER TO SCHEDULE)
WASHER (TYP.)
DOUBLE LOCKNUT W/
EXPANSION SHIELD
(TYPICAL)
MS ANGLE
(REFER TO SCHEDULE)
LOCKNUT W/ WASHER
GA6
GA5
GA4
GA3
GA2
GA1
3000 60x60x6 2500mm 12mm
2000 50x50x5 2500mm 10mm
1500 40x40x3 2500mm 10mm
1000 30x30x3 3000mm 8mm
600 25x25x3 3000mm 8mm
400 25x25x1.6 3000mm 8mm
LEGEND :
APPLICATION :
NOTE :
8
2a
6
7
3
4
1
2
4A
5
5A
3
1
2
2a
4 OR 5
7
3
-
2
1
-
2a
4 7
6
-
6
8
3
2
1
2a
5 7
6 8
-
3
2
1
2a
4A 7
6 8
3
2
1
2a
5A 7
6 8
**
**
**
**
**
*
ADHESIVE FOR LINEAR INSULATION
SELF ADHESIVE PIN
ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE
50x50x0.6mm G.I CORNER ANGLE
ALUMINUM CLADDING (0.7mm THICKNESS)
ACOUSTIC DUCT LINER
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1
G.I DUCTING
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3)
CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1
ELASTOMERIC FOAM
TYPE
DI-2
DI-1
SCHEDULE OF INSULATION
INSULATION TYPE THICKNESS
(mm)
25
25
DENSITY
(Kg/m )
64
64
3
THERMAL
CONDUCTIVITY
(W/M°K)
0.037
0.037
MAXIMUM
TEMP. RATING
(°C)
85
85
APPLICATION
CONCEALED SUPPLY/RETURN IN CONDITIONED AREA
INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY
& RETURN DUCT .
IN SHAFT, TUNNELS & NON CONDITIONED SPACE.
APLICABLE ONLY FROM THE FAN OUTLET,
ACOUSTIC DUCT LINER @3 METER LENGTH,
GRILLE & PLENUM BOX OR TO FIRST BRANCH.
INDOOR A/C SUPPLY & RETURN DUCT
IN CONDENSING SPACE.
REFER TO DUCT LINEAR INSULATION DETAILS
INDOOR A/C SUPPLY & RETURN DUCT
IN MECHANICAL ROOMS & CONDITIONED SPACE.
REFER TO NOTE:
REFER TO DUCT LINEAR INSULATION DETAILS
INSULATION
ELASTOMERIC FOAM
INSULATION
FINISH
F1
F2
TYPE
FINISH TYPE
FACTORY APPLIED
ALUMINUM FOIL
ALUMINUM CLADING
0.7mm THICKNESS
DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED
ELASTOMERIC FOAM
INSULATION
F2
ALUMINUM CLADING
0.7mm THICKNESS
DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH
ELASTOMERIC FOAM
INSULATION
F1+F2 ALUMINUM CLADING
85
85 ALUMINUM FOIL
CONDITIONED AREA IN MECHANICAL ROOMS
AREAS (TUNNELS & SHAFTS)
* AT MEAN TEMPERATURE OF 20°C
REFER TO SPECIFICATION SECTION 15341
REFER TO MECHANICAL SUBMITTAL
REFERENCE 11- MA-004-A
TYPICAL DUCT INSULATION AND LAGGING DETAIL
SCALE N.T.S.
CAPACITY
AIR FLOW
L/S
DIA.
FLEX. DUCT
(mm)
-
TYPICAL FLEXIBLE DUCT HANGER DETAILS
(AS PER SPECIFICATION)
INSULATION
FIBERGLASS
SPACING
(41.7mm PER m) OF SUPPORT
MAX. SAG 12.7mm PER 300mm
NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED,
25.4 x 0.85mm
DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A
CONNECTION BEFORE BENDING.
FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm.
G.I. ROD 2.75
@1500mm O.C.
(MAXIMUM)
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
G.I. STRAP
ALUMINUM
FLEXIBLE DUCT
-
UP TO 30
100 160
61 TO 90
200
91 TO 135
250
136 TO 200
300
201 TO 300 301 TO 380
350
381 TO 500
400
125
31 TO 60
SCALE N.T.S.
TYPICAL SPLITTER DETAIL
06
013 NTS
ECCENTRIC TRANSITION
DIVERGING MAX. 30°
x W
W1 x D1
=
A
MAIN
DUCT
AIR FLOW
W2 x D2
=
B
R = 0.75W
R1 = A + R
MAIN
DUCT
R
R1
BRANCH
DUCT
(W1 x D1) + (W2 x D2)
(W1 x D1) + (W2 x D2)
x W
V.D
V.D
"B"
W
x
D
"A"
1000mm
min.
W1 x D1
W2
x
D2
40mm
4
0
m
m
1
5
m
m
DUCT DETAILS FLESIBLE CONNECTION
08
013 NTS
8mm FLANGE
SEALING COMPOUND APPLIED BETWEEN FABRIC,
BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY*
* REQUIRED ON HIGH PRESSURE SYSTEMS ONLY
BOLT ON 100mm
CENTERS
ROUND (FAN INLET)
SEALING COMPOUND
APPLIED BETWEEN
FLEXIBLE
CONNECTION AND
CASING BEFORE
ASSEMBLY *
RECTANGULAR (FAN OUTLET)
RUBBER
IMPREGNATED
FABRIC
CASING
DUCT
40mm POCKET
SLIP
ALTERNATE POSITION
OF BOLT
25mm x 3mm
BAND IRON
BOLT ON
100mm CENTERS
25mm FLANGE
AND HEM
20 U.S. GAUGE
STEEL
25mm x 3mm
BAND IRON
SHEET METAL SCREWS
ON 300mm CENTERS
25mm x 3mm
DRAW BAND
RUBBER
IMPREGNATED
FABRIC
RIVET ON 100mm
CENTERS
8mm
FLANGE
18 U.S. GAGE
STEEL
DUCT THRU WALL MOUNTING DETAIL
01
013 NTS
DUCTWORK
DUCT INSULATION (SEE
SPECS. FOR DETAILS)
NON-HARDENING
MASTIC SEALANT ALL
AROUND (TYPICAL)
#20 G.I. SHEET DUCT
SLEEVE ALL AROUND
REINFORCED DUCT TAPE
MASONRY WALL
50mm MAX. 50mm MAX.
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
2 3 4 5 6
C
D
E
F
G
0.25
0.25
0.25
3.03
0.26
0.10
0.65
1.35
0.61
1.07
0.23
0.75
0.20
0.79
0.15
0.86
1.00
1.00
1.00
1.00
0.69
0.39
1.48
0.97
1.02
0.95
1.16
0.32
0.99
0.66
2.06
3.33
0.48
0.50
0.50
5.00
5.00
3.33
0.24
1.03
0.89
0.16
0.75
0.23
0.72
0.23
0.78
0.24
0.48
0.56
0.94
1.50
0.99
1.01
0.51
1.00
1.00
1.00
1.00
0.69
0.39
1.34
0.25
0.73
0.22
0.85
0.20
0.78
0.16
0.86
2.48
1.50
1.04
0.97
1.33
1.00
1.00
1.00
1.00
0.69
0.39
4.40
5.00
1.60
0.23
0.63
1.18
0.52
1.11
3.45
1.40
0.97
0.15
0.88
0.77
1.10
1.10
1.37
3.45
1.00
1.00
0.58
0.33
0.28
0.74
1.40
1.14
0.15
0.94
0.71
1.20
1.04
1.31
1.00
1.00
0.62
0.37
0.46
0.35
0.41
3.03
FCU-RF.01.1
/
3.0
TR
FCU-RF.01.2
/
3.0
TR
FCU-RF.02.1 / 2.0 TR
FCU-RF.01.3 / 3.0 TR
0.35
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
15.00 m
3600 CFM
13.66 m
3600 CFM
3 3
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
6.06 m
800 CFM
6.9 m
800 CFM
1 1
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
ROOF FLOOR HVAC PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-05
A.S A.S A.I
SCALE 1 : 65
ROOF FLOOR HVAC PLAN
05
AC
00 28/04/2020 DESIGN - INTENT - 01
FINISHING TAPE
PIPE INSULATION
INSULATION OF BOTH
LIQUID AND GAS PIPES
ELECTRIC CABLE
LIQUID PIPE
GAS PIPE
CUT
OFF
UNUSED
RODS
FOR
PIPES
200∅ AND
OVER
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
2000
20∅ RODS
FOR CHILLED WATER
AND CONDENSER WATER
PIPES 65∅ AND LARGER
FOR STEAM SUPPLY, CONDENSATE RETURN
VENT RELIEF, BOILER FEED BLOW-DOWN, HOT
WATER, AND EXHAUST PIPING
INSULATION WHERE
SPECIFIED.
PIPE SADDLE
WELDED TO PIPE
16 GAUGE STEEL
SADDLE BY 300 LONG.
INSULATION AT BEARING
POINT SHALL BE 8 Lbs.
MINIMUM DENSITY.
FOR ALL PIPES 50∅ AND
SMALLER
HANGERS IN DIRECT CONTACT WITH COPPER TUBING
OR PIPING SHALL BE COPPER PLATED OR PLASTIC
COATED.
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
3000
65∅-80∅
3600
100∅-150∅
4000
200∅-300∅
4500
350∅ &
ABOVE
5000
ROD SIZE
(∅MM) 8 10 12 16 20 22
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
1800
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
2400
65∅-80∅
3000
ROD SIZE
(∅MM) 8 10 10
HARVARD ROLLER
BAND
NOTE
CLEVIS
ADJ. ROLL SUPPORT
MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING
MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING
PIPE HANGERS DETAILS
SCALE N.T.S REFRIGERANT PIPING CONNECTIONS
FOR D-X AIR CONDITIONING UNIT
2.
1.
NOTES:-
CIRCUIT SYSTEMS.
DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE
THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION
WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS.
13
8
7
6
12
7
9
CHARGING CONNECTION
EXPANSION VALVE
7
9
8
ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD
SIGHT GLASS
CONDENSER
STOP VALVE
DX-COIL
COMPRESSOR
AIR COOLED CONDENSING UNIT.
1
3
5
6
4
2
Y- STRAINER
LIQUID LINE
SOLENOID VALVE
THERMAL BULB
10
12
13
11
SUCTION LINE (DOUBLE RISER)
14
4
11
10
1
3
2
5
14
2 3 4 5 6
B
C
D
E
F
G
H
7
1
A
I
2.64
2.71
0.55
0.62
0.90
0.97
2.68
2.76
1.58
1.65
1.10
1.17
0.40
0.48
1.23
1.30
0.44
0.51
1.04
1.11
1.91
1.98
1.75
1.83
0.78
0.85
0.51
0.58
0.41
0.48
0.85
0.92
0.91
0.99
FCU-BF.02.1 / 3.0 TR
FCU-BF.03.3 / 2.5 TR
FCU-BF.03.2 / 2.5 TR
FCU-BF.04.2 / 2.0 TR
FCU-BF.01.1 / 3.5 TR
FCU-BF.03.1
/
2.5
TR
FCU-BF.04.1
/
2.0
TR
W.SU-BF.02.1 / 1.5 TR
W.SU-BF.01.1
/
2.0
TR
4.26
4.33
1.79
1.86
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
BASEMENT FLOOR HVAC PIPING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-06
A.S A.S A.I
SCALE 1 : 65
BASEMENT FLOOR HVAC PIPING PLAN
06
AC
00 28/04/2020 DESIGN - INTENT - 01
FINISHING TAPE
PIPE INSULATION
INSULATION OF BOTH
LIQUID AND GAS PIPES
ELECTRIC CABLE
LIQUID PIPE
GAS PIPE
CUT
OFF
UNUSED
RODS
FOR
PIPES
200∅ AND
OVER
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
2000
20∅ RODS
FOR CHILLED WATER
AND CONDENSER WATER
PIPES 65∅ AND LARGER
FOR STEAM SUPPLY, CONDENSATE RETURN
VENT RELIEF, BOILER FEED BLOW-DOWN, HOT
WATER, AND EXHAUST PIPING
INSULATION WHERE
SPECIFIED.
PIPE SADDLE
WELDED TO PIPE
16 GAUGE STEEL
SADDLE BY 300 LONG.
INSULATION AT BEARING
POINT SHALL BE 8 Lbs.
MINIMUM DENSITY.
FOR ALL PIPES 50∅ AND
SMALLER
HANGERS IN DIRECT CONTACT WITH COPPER TUBING
OR PIPING SHALL BE COPPER PLATED OR PLASTIC
COATED.
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
3000
65∅-80∅
3600
100∅-150∅
4000
200∅-300∅
4500
350∅ &
ABOVE
5000
ROD SIZE
(∅MM) 8 10 12 16 20 22
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
1800
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
2400
65∅-80∅
3000
ROD SIZE
(∅MM) 8 10 10
HARVARD ROLLER
BAND
NOTE
CLEVIS
ADJ. ROLL SUPPORT
MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING
MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING
PIPE HANGERS DETAILS
SCALE N.T.S REFRIGERANT PIPING CONNECTIONS
FOR D-X AIR CONDITIONING UNIT
2.
1.
NOTES:-
CIRCUIT SYSTEMS.
DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE
THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION
WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS.
13
8
7
6
12
7
9
CHARGING CONNECTION
EXPANSION VALVE
7
9
8
ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD
SIGHT GLASS
CONDENSER
STOP VALVE
DX-COIL
COMPRESSOR
AIR COOLED CONDENSING UNIT.
1
3
5
6
4
2
Y- STRAINER
LIQUID LINE
SOLENOID VALVE
THERMAL BULB
10
12
13
11
SUCTION LINE (DOUBLE RISER)
14
4
11
10
1
3
2
5
14
2 3 4 5 6
B
C
D
E
F
G
H
7
1
A
I
1.71
1.79
1.96
2.04
0.44
0.51
0.84
4.56
4.63
0.36
0.43
0.30
0.37
FCU-GF.03.1
/
2.5
TR
FCU-GF.03.1
/
2.5
TR
FCU-GF.03.2 / 2.5 TR
FCU-GF.01.1 / 3.0 TR
W.SU-GF.01.1 / 2.0 TR
W.SU-GF.01.2 / 2.0 TR
W.SU-BF.02.1
W.SU-GF.01.2
W.SU-GF.01.1
W.SU-BF.01.1
1.99 0.97 1.30 2.20
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
GROUND FLOOR HVAC PIPING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-07
A.S A.S A.I
SCALE 1 : 65
GROUND FLOOR HVAC PIPING PLAN
07
AC
00 28/04/2020 DESIGN - INTENT - 01
FINISHING TAPE
PIPE INSULATION
INSULATION OF BOTH
LIQUID AND GAS PIPES
ELECTRIC CABLE
LIQUID PIPE
GAS PIPE
CUT
OFF
UNUSED
RODS
FOR
PIPES
200∅ AND
OVER
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
2000
20∅ RODS
FOR CHILLED WATER
AND CONDENSER WATER
PIPES 65∅ AND LARGER
FOR STEAM SUPPLY, CONDENSATE RETURN
VENT RELIEF, BOILER FEED BLOW-DOWN, HOT
WATER, AND EXHAUST PIPING
INSULATION WHERE
SPECIFIED.
PIPE SADDLE
WELDED TO PIPE
16 GAUGE STEEL
SADDLE BY 300 LONG.
INSULATION AT BEARING
POINT SHALL BE 8 Lbs.
MINIMUM DENSITY.
FOR ALL PIPES 50∅ AND
SMALLER
HANGERS IN DIRECT CONTACT WITH COPPER TUBING
OR PIPING SHALL BE COPPER PLATED OR PLASTIC
COATED.
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
3000
65∅-80∅
3600
100∅-150∅
4000
200∅-300∅
4500
350∅ &
ABOVE
5000
ROD SIZE
(∅MM) 8 10 12 16 20 22
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
1800
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
2400
65∅-80∅
3000
ROD SIZE
(∅MM) 8 10 10
HARVARD ROLLER
BAND
NOTE
CLEVIS
ADJ. ROLL SUPPORT
MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING
MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING
PIPE HANGERS DETAILS
SCALE N.T.S REFRIGERANT PIPING CONNECTIONS
FOR D-X AIR CONDITIONING UNIT
2.
1.
NOTES:-
CIRCUIT SYSTEMS.
DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE
THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION
WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS.
13
8
7
6
12
7
9
CHARGING CONNECTION
EXPANSION VALVE
7
9
8
ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD
SIGHT GLASS
CONDENSER
STOP VALVE
DX-COIL
COMPRESSOR
AIR COOLED CONDENSING UNIT.
1
3
5
6
4
2
Y- STRAINER
LIQUID LINE
SOLENOID VALVE
THERMAL BULB
10
12
13
11
SUCTION LINE (DOUBLE RISER)
14
4
11
10
1
3
2
5
14
2 3 4 5
B
C
D
E
F
G
A
1.13
1.20
0.31
0.38
0.93
1.01
0.98
1.06
1.19
1.27
0.16
0.23
0.39
0.46
0.51
0.59
0.60
0.67
FCU-1F.02.2
/
3.0
TR
FCU-1F.04.1
/
1.5
TR
FCU-1F.02.2
/
3.0
TR
FCU-1F.03.1
/
2.0
TR
FCU-1F.01.2
/
2.5
TR
FCU-1F.01.1
/
3.25
TR
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
FIRST FLOOR HVAC PIPING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-08
A.S A.S A.I
SCALE 1 : 65
FIRST FLOOR HVAC PIPING PLAN
08
AC
00 28/04/2020 DESIGN - INTENT - 01
FINISHING TAPE
PIPE INSULATION
INSULATION OF BOTH
LIQUID AND GAS PIPES
ELECTRIC CABLE
LIQUID PIPE
GAS PIPE
CUT
OFF
UNUSED
RODS
FOR
PIPES
200∅ AND
OVER
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
2000
20∅ RODS
FOR CHILLED WATER
AND CONDENSER WATER
PIPES 65∅ AND LARGER
FOR STEAM SUPPLY, CONDENSATE RETURN
VENT RELIEF, BOILER FEED BLOW-DOWN, HOT
WATER, AND EXHAUST PIPING
INSULATION WHERE
SPECIFIED.
PIPE SADDLE
WELDED TO PIPE
16 GAUGE STEEL
SADDLE BY 300 LONG.
INSULATION AT BEARING
POINT SHALL BE 8 Lbs.
MINIMUM DENSITY.
FOR ALL PIPES 50∅ AND
SMALLER
HANGERS IN DIRECT CONTACT WITH COPPER TUBING
OR PIPING SHALL BE COPPER PLATED OR PLASTIC
COATED.
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
3000
65∅-80∅
3600
100∅-150∅
4000
200∅-300∅
4500
350∅ &
ABOVE
5000
ROD SIZE
(∅MM) 8 10 12 16 20 22
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
1800
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
2400
65∅-80∅
3000
ROD SIZE
(∅MM) 8 10 10
HARVARD ROLLER
BAND
NOTE
CLEVIS
ADJ. ROLL SUPPORT
MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING
MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING
PIPE HANGERS DETAILS
SCALE N.T.S REFRIGERANT PIPING CONNECTIONS
FOR D-X AIR CONDITIONING UNIT
2.
1.
NOTES:-
CIRCUIT SYSTEMS.
DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE
THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION
WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS.
13
8
7
6
12
7
9
CHARGING CONNECTION
EXPANSION VALVE
7
9
8
ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD
SIGHT GLASS
CONDENSER
STOP VALVE
DX-COIL
COMPRESSOR
AIR COOLED CONDENSING UNIT.
1
3
5
6
4
2
Y- STRAINER
LIQUID LINE
SOLENOID VALVE
THERMAL BULB
10
12
13
11
SUCTION LINE (DOUBLE RISER)
14
4
11
10
1
3
2
5
14
2 3 4 5 6
B
C
D
E
F
G
0.30
0.38
0.56
0.63
0.83
0.91
1.55
1.62
0.14
0.21
3.91
3.91
0.15
0.22
FCU-2F.01.1
/
3.25
TR
FCU-2F.04.2
/
2.0
TR
FCU-2F.05.1
/
1.5
TR
FCU-1F.03.1
/
2.5
TR
FCU-2F.01.2
/
3.25
TR
FCU-2F.02.1 / 3.0 TR
FCU-2F.04.1 / 2.0 TR
1.11
1.18
1.28
1.35
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
SECOND FLOOR HVAC PIPING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-09
A.S A.S A.I
SCALE 1 : 65
SECOND FLOOR HVAC PIPING PLAN
09
AC
00 28/04/2020 DESIGN - INTENT - 01
FINISHING TAPE
PIPE INSULATION
INSULATION OF BOTH
LIQUID AND GAS PIPES
ELECTRIC CABLE
LIQUID PIPE
GAS PIPE
CUT
OFF
UNUSED
RODS
FOR
PIPES
200∅ AND
OVER
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
2000
20∅ RODS
FOR CHILLED WATER
AND CONDENSER WATER
PIPES 65∅ AND LARGER
FOR STEAM SUPPLY, CONDENSATE RETURN
VENT RELIEF, BOILER FEED BLOW-DOWN, HOT
WATER, AND EXHAUST PIPING
INSULATION WHERE
SPECIFIED.
PIPE SADDLE
WELDED TO PIPE
16 GAUGE STEEL
SADDLE BY 300 LONG.
INSULATION AT BEARING
POINT SHALL BE 8 Lbs.
MINIMUM DENSITY.
FOR ALL PIPES 50∅ AND
SMALLER
HANGERS IN DIRECT CONTACT WITH COPPER TUBING
OR PIPING SHALL BE COPPER PLATED OR PLASTIC
COATED.
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
3000
65∅-80∅
3600
100∅-150∅
4000
200∅-300∅
4500
350∅ &
ABOVE
5000
ROD SIZE
(∅MM) 8 10 12 16 20 22
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
1800
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
2400
65∅-80∅
3000
ROD SIZE
(∅MM) 8 10 10
HARVARD ROLLER
BAND
NOTE
CLEVIS
ADJ. ROLL SUPPORT
MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING
MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING
PIPE HANGERS DETAILS
SCALE N.T.S REFRIGERANT PIPING CONNECTIONS
FOR D-X AIR CONDITIONING UNIT
2.
1.
NOTES:-
CIRCUIT SYSTEMS.
DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE
THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION
WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS.
13
8
7
6
12
7
9
CHARGING CONNECTION
EXPANSION VALVE
7
9
8
ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD
SIGHT GLASS
CONDENSER
STOP VALVE
DX-COIL
COMPRESSOR
AIR COOLED CONDENSING UNIT.
1
3
5
6
4
2
Y- STRAINER
LIQUID LINE
SOLENOID VALVE
THERMAL BULB
10
12
13
11
SUCTION LINE (DOUBLE RISER)
14
4
11
10
1
3
2
5
14
TYPICAL UNIT FOUNDATION DETAIL
(NOT TO SCALE)
F.F.L
250mm HIGH R.C.C FOUNDATION
(BY OTHERS)
ABOVE FINISHED ROOF LEVEL
WATER PROOFING
MEMBRANE
ROOF SLAB
BETWEEN ROOF SLAB & PLINTH
50mmTHICK POLYURETHANE SHEET
2
5
0
2 3 4 5 6
B
C
D
E
F
G
H
0.41
1.46
1.49
1.90
0.54
1.74
1.81
0.33
0.41
2.11
2.17
0.32
FCU-GF.01.1 FCU-BF.02.1
FCU-RF.01.1
/
3.0
TR
FCU-RF.01.2
/
3.0
TR
FCU-RF.02.1 / 2.0 TR
FCU-RF.01.3 / 3.0 TR
0.29
0.37
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
ROOF FLOOR HVAC PIPING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-10
A.S A.S A.I
SCALE 1 : 65
ROOF FLOOR HVAC PIPING PLAN
10
AC
00 28/04/2020 DESIGN - INTENT - 01
FINISHING TAPE
PIPE INSULATION
INSULATION OF BOTH
LIQUID AND GAS PIPES
ELECTRIC CABLE
LIQUID PIPE
GAS PIPE
CUT
OFF
UNUSED
RODS
FOR
PIPES
200∅ AND
OVER
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
2000
20∅ RODS
FOR CHILLED WATER
AND CONDENSER WATER
PIPES 65∅ AND LARGER
FOR STEAM SUPPLY, CONDENSATE RETURN
VENT RELIEF, BOILER FEED BLOW-DOWN, HOT
WATER, AND EXHAUST PIPING
INSULATION WHERE
SPECIFIED.
PIPE SADDLE
WELDED TO PIPE
16 GAUGE STEEL
SADDLE BY 300 LONG.
INSULATION AT BEARING
POINT SHALL BE 8 Lbs.
MINIMUM DENSITY.
FOR ALL PIPES 50∅ AND
SMALLER
HANGERS IN DIRECT CONTACT WITH COPPER TUBING
OR PIPING SHALL BE COPPER PLATED OR PLASTIC
COATED.
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
3000
65∅-80∅
3600
100∅-150∅
4000
200∅-300∅
4500
350∅ &
ABOVE
5000
ROD SIZE
(∅MM) 8 10 12 16 20 22
SIZE,
MM
NOMINAL
PIPE UP TO
25∅
1800
DISTANCE
BETWEEN
SUPPORTS
32∅-50∅
2400
65∅-80∅
3000
ROD SIZE
(∅MM) 8 10 10
HARVARD ROLLER
BAND
NOTE
CLEVIS
ADJ. ROLL SUPPORT
MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING
MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING
PIPE HANGERS DETAILS
SCALE N.T.S REFRIGERANT PIPING CONNECTIONS
FOR D-X AIR CONDITIONING UNIT
2.
1.
NOTES:-
CIRCUIT SYSTEMS.
DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE
THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION
WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS.
13
8
7
6
12
7
9
CHARGING CONNECTION
EXPANSION VALVE
7
9
8
ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD
SIGHT GLASS
CONDENSER
STOP VALVE
DX-COIL
COMPRESSOR
AIR COOLED CONDENSING UNIT.
1
3
5
6
4
2
Y- STRAINER
LIQUID LINE
SOLENOID VALVE
THERMAL BULB
10
12
13
11
SUCTION LINE (DOUBLE RISER)
14
4
11
10
1
3
2
5
14
TYPICAL UNIT FOUNDATION DETAIL
(NOT TO SCALE)
F.F.L
250mm HIGH R.C.C FOUNDATION
(BY OTHERS)
ABOVE FINISHED ROOF LEVEL
WATER PROOFING
MEMBRANE
ROOF SLAB
BETWEEN ROOF SLAB & PLINTH
50mmTHICK POLYURETHANE SHEET
2
5
0
3 4 5
C
D
E
F
G
FCU-RF.01.2
FCU-1F.02.2
FCU-2F.04.2
FCU-BF.04.1
FCU-1F.02.2
FCU-2F.01.1
FCU-RF.01.1
FCU-1F.04.1
FCU-BF.03.1
FCU-2F.05.1
FCU-1F.01.2
FCU-1F.01.1
FCU-BF.03.2
FCU-RF.01.3
FCU-2F.02.1
EQ EQ EQ EQ
FCU-2F.01.2
FCU-BF.03.3
FCU-1F.03.1
FCU-GF.03.2
FCU-BF.04.2
FCU-GF.03.1 FCU-1F.03.1
FCU-RF.02.1
0.40
0.40
0.40
FCU-2F.04.1
FCU-GF.03.1
0.85
FCU-BF.01.1
0.48
0.65
0.72
0.40
0.70
0.70
0.40
0.57
0.85
0.63
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
TOP ROOF HVAC PIPING PLAN
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-11
A.S A.S A.I
SCALE 1 : 65
TOP ROOF HVAC PIPING PLAN
11
AC
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
1 : 125 @ A1
00
HVAC 3D VIEW A
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-12
A.S A.S A.I
SCALE
HVAC 3D VIEW A
12
AC
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
1 : 125 @ A1
00
HVAC 3D VIEW B
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-13
A.S A.S A.I
SCALE
HVAC 3D VIEW B
13
AC
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
3
F
G
H
I
0.25
0.25
0.25
0.25
0.25
5.06
0.51
0.56
1.63
2.98
1.04
0.57
0.32
1.00 1.00 1.00
0.90 1.42 1.43
1.75 0.17 1.51
1.55
0.22
1.73
1.97
1.13
0.25
4.00
4.00
1.00
1.00
1.00
0.56
0.31
0.68
0.75
1.64
FCU-BF.03.1
/
2.5
TR
Size: 450x300
BOD: 3.52m
Size: 350x300
BOD: 3.52m
Size: 250x250
BOD: 3.55m
Size: 200x200
BOD: 3.57m
125 Ф
2.88
1.63
0.98
0.50
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
CALLOUT A
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-14
A.S A.S A.I
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
2 3
B
C
D
E
1
A
FCU-BF.01.1 / 3.5 TR
Size: 250x250
BOD: 3.69m
Size: 350x300
BOD: 3.66m
Size: 500x350
BOD: 3.64m
Size: 350x300
BOD: 3.66m
Size: 250x250
BOD: 3.69m
200 Ф
200 Ф
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
8.50 m
1400 CFM
7.75 m
1400 CFM
2 2
0.48
5.82
1.50
0.48
0.74
0.44
1.13
1.13
1.13
2.10
0.20
1.60
1.43
1.12
1.20
1.00
1.60
0.45
0.48
1.60
2.61
1.28
0.16
1.90
0.66
1.50
1.14
0.56
1.00
1.00
0.90
0.38
4.00
4.50
3.75
4.00
0.42
0.46
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
CALLOUT B
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-15
A.S A.S A.I
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
3
C
D
3.00
0.35
1.00 1.00
0.61
0.31
1.23 0.88 0.20 0.77 0.21 0.77 0.69 0.45
1.10
1.02
1.55
2.16
3.00
FCU-2F.02.1 / 3.0 TR
200 Ф
Size: 250x250
BOD: 2.67m
Size: 300x300
BOD: 2.65m
Size: 350x350
BOD: 2.62m
Size: 350x350
BOD: 2.92m
Size: 350x350
BOD: 2.92m
FLOW
LIN.
DIF. TYPE LSD LRD
SLOT WIDTH
NO. OF SLOT
25 mm 25 mm
3.00 m
1200 CFM
3 m
1200 CFM
3 3
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
CALLOUT D
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-16
A.S A.S A.I
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
3
E
0.26
0.26
0.26
0.26
1.01
0.79 1.48 1.45 1.06 1.40 1.14
1.49 1.18 1.80 1.20 1.20
1.04 1.04 1.04 1.04 1.04
0.62
0.32
6.25
1.04
6.25
Size: 200x200
BOD: 3.40m
Size: 200x200
BOD: 3.40m
Size: 300x250
BOD: 3.37m
Size: 300x250
BOD: 3.37m
FCU-1F.04.1
/
1.5
TR
125 Ф
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
CALLOUT C
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-17
A.S A.S A.I
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
4
E
F
G
EQ EQ
EQ
EQ
2.62
2.62
EQ EQ
0.26
0.27
1.17
0.85
0.94
0.15
1.96
FCU-2F.04.2
/
2.0
TR
3.57
125 Ф 125 Ф
Size: 200x200
BOD: 3.10m
Size: 200x200
BOD: 3.10m
Size: 250x250
BOD: 3.08m
Size: 250x250
BOD: 3.08m
0.56
0.63
1.10
1.47
1.10
1.46
0.96
0.15
1.83
0.67
0.47
1.01
1.00
1.00
1.00
0.43
3.17
1.09
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
CALLOUT E
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-18
A.S A.S A.I
00 28/04/2020 DESIGN - INTENT - 01
VRV COPPER PIPING Y JUNCTION
25mm INSULATED COPPER PIPE SUPPLY
FAN COIL UNIT (FCU)
RECTANGULAR SYPPLY DUCT
DUCT HANGER
FLEXIBLE DUCT
VOLUME CONTROL DAMPER (VCD)
SUPPLY LINEAR DIFFUSER WITH
PLENUM (SLD)
RETURN LINEAR DIFFUSER (RLD)
RECTANGULAR RETURN DUCT
CODE DESCRIPTION.
25mm INSULATED COPPER PIPE RETURN
4
C
D
0.85
0.96 1.25
FCU-1F.03.1
/
2.5
TR
Size: 350x350
BOD: 3.10m
QTY.
FLOW
DIM. (mm)
DIF. TYPE SSD SRD
400x400 400x400
1
1000 CFM 1000 CFM
1
1.40
1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED
OTHERWISE.
2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS
SHOULD
BE FOLLOW.
3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF
CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD
IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE.
DETAILED DESIGN DRAWING
PROJECT
TITLE:
SCALE:
CLIENT:
LOCATION:
DESIGNED BY:
DRAWING NO.:
CHECKED BY:
REVISION SIGNATURE SIGNATURE
ARCHITECH:
DRAWN BY:
ISSUE FOR APPROVAL
NOTE:
LEGEND:
MEP DESIGNER :
DESCRIPTION
REV. DATE BY
‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬
‫ﺍﻟﺗﺎﺭﻳﺦ‬
‫ﺗﻌﺩﻳﻝ‬
As indicated @ A1
00
CALLOUT F
VILLA
ABU FETRA
KUWAIT CITY, KUWAIT
AC-19
A.S A.S A.I
00 28/04/2020 DESIGN - INTENT - 01

Weitere ähnliche Inhalte

Ähnlich wie HVAC SET.pdf

Loadlock NGP-B Presentation EXTRACT
Loadlock NGP-B Presentation EXTRACTLoadlock NGP-B Presentation EXTRACT
Loadlock NGP-B Presentation EXTRACT
IAN HASKINS
 
Drawings of Revit project for D type qtr.
Drawings of Revit project for  D type qtr.Drawings of Revit project for  D type qtr.
Drawings of Revit project for D type qtr.
mahfooz alam khan
 
LDavis_work_examples
LDavis_work_examplesLDavis_work_examples
LDavis_work_examples
Loren Davis
 
many projects shoring
many projects shoringmany projects shoring
many projects shoring
Samir Salman
 
section and detail sheet1
section and detail sheet1section and detail sheet1
section and detail sheet1
Jacob Dobson
 

Ähnlich wie HVAC SET.pdf (20)

Modelo 1
Modelo 1Modelo 1
Modelo 1
 
Loadlock NGP-B Presentation EXTRACT
Loadlock NGP-B Presentation EXTRACTLoadlock NGP-B Presentation EXTRACT
Loadlock NGP-B Presentation EXTRACT
 
Flow and connection Palamatic Process
Flow and connection Palamatic ProcessFlow and connection Palamatic Process
Flow and connection Palamatic Process
 
Drawings of Revit project for D type qtr.
Drawings of Revit project for  D type qtr.Drawings of Revit project for  D type qtr.
Drawings of Revit project for D type qtr.
 
M2 cv-rc-d-005(anchor bolt details)
M2 cv-rc-d-005(anchor bolt details)M2 cv-rc-d-005(anchor bolt details)
M2 cv-rc-d-005(anchor bolt details)
 
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
 
Kammer Severe Service Valves For Industry
Kammer Severe Service Valves For IndustryKammer Severe Service Valves For Industry
Kammer Severe Service Valves For Industry
 
diffusox.pdf
diffusox.pdfdiffusox.pdf
diffusox.pdf
 
LDavis_work_examples
LDavis_work_examplesLDavis_work_examples
LDavis_work_examples
 
ICS 5000 UK version
ICS 5000 UK version ICS 5000 UK version
ICS 5000 UK version
 
Raccordi per alte pressioni - Fitok serie 60
Raccordi per alte pressioni - Fitok serie 60Raccordi per alte pressioni - Fitok serie 60
Raccordi per alte pressioni - Fitok serie 60
 
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAILAbb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
 
many projects shoring
many projects shoringmany projects shoring
many projects shoring
 
Thông số kỹ thuật băng tải Optibelt - Catalogue Optibelt
Thông số kỹ thuật băng tải Optibelt - Catalogue OptibeltThông số kỹ thuật băng tải Optibelt - Catalogue Optibelt
Thông số kỹ thuật băng tải Optibelt - Catalogue Optibelt
 
section and detail sheet1
section and detail sheet1section and detail sheet1
section and detail sheet1
 
2EFFE INOX -REPAIR CLAMP CATALOG 2015
2EFFE INOX -REPAIR CLAMP CATALOG 20152EFFE INOX -REPAIR CLAMP CATALOG 2015
2EFFE INOX -REPAIR CLAMP CATALOG 2015
 
Schiedel Metaloterm US flue system
Schiedel Metaloterm US flue systemSchiedel Metaloterm US flue system
Schiedel Metaloterm US flue system
 
Ceiling Fans And Room Heaters By Vilo Industries India
Ceiling Fans And Room Heaters By Vilo Industries IndiaCeiling Fans And Room Heaters By Vilo Industries India
Ceiling Fans And Room Heaters By Vilo Industries India
 
Siemens Sitrans F VA 250
Siemens Sitrans F VA 250 Siemens Sitrans F VA 250
Siemens Sitrans F VA 250
 
Slot Gratings
Slot Gratings Slot Gratings
Slot Gratings
 

Kürzlich hochgeladen

Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
CristineGraceAcuyan
 
一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证
一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证
一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证
wpkuukw
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
mark11275
 
怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证
怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证
怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证
ehyxf
 
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
nirzagarg
 
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
eeanqy
 
Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...
Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...
Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...
gajnagarg
 

Kürzlich hochgeladen (20)

Jordan_Amanda_DMBS202404_PB1_2024-04.pdf
Jordan_Amanda_DMBS202404_PB1_2024-04.pdfJordan_Amanda_DMBS202404_PB1_2024-04.pdf
Jordan_Amanda_DMBS202404_PB1_2024-04.pdf
 
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service AvailableCall Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
 
Q4-W4-SCIENCE-5 power point presentation
Q4-W4-SCIENCE-5 power point presentationQ4-W4-SCIENCE-5 power point presentation
Q4-W4-SCIENCE-5 power point presentation
 
Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...
Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...
Abortion pills in Riyadh +966572737505 <> buy cytotec <> unwanted kit Saudi A...
 
The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
 
一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证
一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证
一比一定(购)卡尔顿大学毕业证(CU毕业证)成绩单学位证
 
NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...
NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...
NO1 Top Pakistani Amil Baba Real Amil baba In Pakistan Najoomi Baba in Pakist...
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
 
How to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdfHow to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdf
 
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best ServiceHigh Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
 
怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证
怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证
怎样办理莫纳什大学毕业证(Monash毕业证书)成绩单留信认证
 
Independent Escorts Goregaon WhatsApp +91-9930687706, Best Service
Independent Escorts Goregaon WhatsApp +91-9930687706, Best ServiceIndependent Escorts Goregaon WhatsApp +91-9930687706, Best Service
Independent Escorts Goregaon WhatsApp +91-9930687706, Best Service
 
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
 
TRose UXPA Experience Design Concord .pptx
TRose UXPA Experience Design Concord .pptxTRose UXPA Experience Design Concord .pptx
TRose UXPA Experience Design Concord .pptx
 
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEKLANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
 
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
 
Raebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for Friendship
Raebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for FriendshipRaebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for Friendship
Raebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for Friendship
 
Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...
Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...
Top profile Call Girls In eluru [ 7014168258 ] Call Me For Genuine Models We ...
 
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime PondicherryPondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
 

HVAC SET.pdf

  • 1. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 HVAC SYSTEM VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-00 A.S A.S A.I HVAC SET PROJECT: ABU FETRA VILLA CLIENT: ABU FETRA LOCATION: KUWAIT CITY, KUWAIT 00 28/04/2020 DESIGN - INTENT - 01
  • 2. CEILING MOUNTED F.C.U CUT OFF & COMBINED METERING RETURN CHILED WATER SUPPLY CHILLED WATER AUXILIARY CONTROL 2-WAY VALVE CUT OFF VALVE COLLAR DIELECTRIC FILTER BALANCING VALVE CONNECTION CONNECTION ELECTRICAL INLET DRAIN PAN STRAINER FLOW DIRECTION FLOW DIRECTION AIR DIRECTION AIR DIRECTION FAN & MOTOR FAN & MOTOR COIL FLOW METER REF. NAME SUPPORTING ANGLE SIZE MAX. DUCT (mm) HANGING ROD SIZE SIZE. (mm) (mm) SPACING (mm) TABLE THIS TABLE IS BASED ON DW/144 FOR FIGURE-68 CONCRETE SLAB 32 32 25 25 DUCT SIZE DUCT SIZE DUCT SIZE DUCT SUPPORTING DETAILS SCALE N.T.S. G.I. THREADED ROD (REFER TO SCHEDULE) WASHER (TYP.) DOUBLE LOCKNUT W/ EXPANSION SHIELD (TYPICAL) MS ANGLE (REFER TO SCHEDULE) LOCKNUT W/ WASHER GA6 GA5 GA4 GA3 GA2 GA1 3000 60x60x6 2500mm 12mm 2000 50x50x5 2500mm 10mm 1500 40x40x3 2500mm 10mm 1000 30x30x3 3000mm 8mm 600 25x25x3 3000mm 8mm 400 25x25x1.6 3000mm 8mm LEGEND : APPLICATION : NOTE : 8 2a 6 7 3 4 1 2 4A 5 5A 3 1 2 2a 4 OR 5 7 3 - 2 1 - 2a 4 7 6 - 6 8 3 2 1 2a 5 7 6 8 - 3 2 1 2a 4A 7 6 8 3 2 1 2a 5A 7 6 8 ** ** ** ** ** * ADHESIVE FOR LINEAR INSULATION SELF ADHESIVE PIN ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE 50x50x0.6mm G.I CORNER ANGLE ALUMINUM CLADDING (0.7mm THICKNESS) ACOUSTIC DUCT LINER CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1 G.I DUCTING CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1 ELASTOMERIC FOAM TYPE DI-2 DI-1 SCHEDULE OF INSULATION INSULATION TYPE THICKNESS (mm) 25 25 DENSITY (Kg/m ) 64 64 3 THERMAL CONDUCTIVITY (W/M°K) 0.037 0.037 MAXIMUM TEMP. RATING (°C) 85 85 APPLICATION CONCEALED SUPPLY/RETURN IN CONDITIONED AREA INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY & RETURN DUCT . IN SHAFT, TUNNELS & NON CONDITIONED SPACE. APLICABLE ONLY FROM THE FAN OUTLET, ACOUSTIC DUCT LINER @3 METER LENGTH, GRILLE & PLENUM BOX OR TO FIRST BRANCH. INDOOR A/C SUPPLY & RETURN DUCT IN CONDENSING SPACE. REFER TO DUCT LINEAR INSULATION DETAILS INDOOR A/C SUPPLY & RETURN DUCT IN MECHANICAL ROOMS & CONDITIONED SPACE. REFER TO NOTE: REFER TO DUCT LINEAR INSULATION DETAILS INSULATION ELASTOMERIC FOAM INSULATION FINISH F1 F2 TYPE FINISH TYPE FACTORY APPLIED ALUMINUM FOIL ALUMINUM CLADING 0.7mm THICKNESS DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED ELASTOMERIC FOAM INSULATION F2 ALUMINUM CLADING 0.7mm THICKNESS DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH ELASTOMERIC FOAM INSULATION F1+F2 ALUMINUM CLADING 85 85 ALUMINUM FOIL CONDITIONED AREA IN MECHANICAL ROOMS AREAS (TUNNELS & SHAFTS) * AT MEAN TEMPERATURE OF 20°C REFER TO SPECIFICATION SECTION 15341 REFER TO MECHANICAL SUBMITTAL REFERENCE 11- MA-004-A TYPICAL DUCT INSULATION AND LAGGING DETAIL SCALE N.T.S. CAPACITY AIR FLOW L/S DIA. FLEX. DUCT (mm) - TYPICAL FLEXIBLE DUCT HANGER DETAILS (AS PER SPECIFICATION) INSULATION FIBERGLASS SPACING (41.7mm PER m) OF SUPPORT MAX. SAG 12.7mm PER 300mm NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED, 25.4 x 0.85mm DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm. G.I. ROD 2.75 @1500mm O.C. (MAXIMUM) BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES. G.I. STRAP ALUMINUM FLEXIBLE DUCT - UP TO 30 100 160 61 TO 90 200 91 TO 135 250 136 TO 200 300 201 TO 300 301 TO 380 350 381 TO 500 400 125 31 TO 60 SCALE N.T.S. TYPICAL SPLITTER DETAIL 06 013 NTS ECCENTRIC TRANSITION DIVERGING MAX. 30° x W W1 x D1 = A MAIN DUCT AIR FLOW W2 x D2 = B R = 0.75W R1 = A + R MAIN DUCT R R1 BRANCH DUCT (W1 x D1) + (W2 x D2) (W1 x D1) + (W2 x D2) x W V.D V.D "B" W x D "A" 1000mm min. W1 x D1 W2 x D2 40mm 4 0 m m 1 5 m m DUCT DETAILS FLESIBLE CONNECTION 08 013 NTS 8mm FLANGE SEALING COMPOUND APPLIED BETWEEN FABRIC, BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY* * REQUIRED ON HIGH PRESSURE SYSTEMS ONLY BOLT ON 100mm CENTERS ROUND (FAN INLET) SEALING COMPOUND APPLIED BETWEEN FLEXIBLE CONNECTION AND CASING BEFORE ASSEMBLY * RECTANGULAR (FAN OUTLET) RUBBER IMPREGNATED FABRIC CASING DUCT 40mm POCKET SLIP ALTERNATE POSITION OF BOLT 25mm x 3mm BAND IRON BOLT ON 100mm CENTERS 25mm FLANGE AND HEM 20 U.S. GAUGE STEEL 25mm x 3mm BAND IRON SHEET METAL SCREWS ON 300mm CENTERS 25mm x 3mm DRAW BAND RUBBER IMPREGNATED FABRIC RIVET ON 100mm CENTERS 8mm FLANGE 18 U.S. GAGE STEEL DUCT THRU WALL MOUNTING DETAIL 01 013 NTS DUCTWORK DUCT INSULATION (SEE SPECS. FOR DETAILS) NON-HARDENING MASTIC SEALANT ALL AROUND (TYPICAL) #20 G.I. SHEET DUCT SLEEVE ALL AROUND REINFORCED DUCT TAPE MASONRY WALL 50mm MAX. 50mm MAX. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 2 3 4 5 6 B C D E F G H 7 1 A I 60 60 60 60 7.28 0.48 5.82 1.50 1.50 1.34 1.34 0.23 0.23 0.23 0.23 0.16 0.23 0.23 0.25 0.25 0.25 0.25 0.25 5.06 0.51 0.56 1.63 2.98 0.33 0.55 0.23 0.23 2.31 2.47 0.23 0.23 0.99 0.41 1.19 1.63 1.87 0.31 1.35 2.50 3.00 0.33 1.83 3.00 4.87 1.08 0.78 1.73 0.48 0.94 0.97 0.90 1.10 0.60 0.68 0.62 0.84 0.19 1.35 0.97 1.00 0.47 0.72 0.46 0.56 0.53 0.63 1.00 0.89 1.25 0.83 1.58 0.38 0.33 2.00 0.50 1.25 0.75 1.25 0.69 0.55 1.15 3.25 0.50 2.00 1.58 0.94 0.97 0.96 0.93 0.62 1.03 0.57 0.82 0.78 0.52 1.04 0.57 0.32 1.00 1.00 1.00 0.90 1.42 1.43 1.75 0.17 1.51 1.55 0.22 1.73 1.97 1.13 0.25 4.00 4.00 1.00 1.00 1.00 0.56 0.31 0.68 0.75 1.64 1.50 0.48 0.74 0.44 1.13 1.13 1.13 2.10 0.20 1.60 1.43 0.68 1.12 1.20 1.00 1.60 0.45 0.48 1.60 2.61 1.28 0.16 1.90 0.66 1.50 1.14 0.56 1.00 1.00 0.90 0.38 4.00 4.50 3.75 4.00 0.42 1.67 0.46 0.51 1.50 0.45 1.03 0.23 1.56 0.16 0.53 1.30 0.76 1.00 0.61 0.36 0.80 0.18 1.56 1.50 1.53 0.75 0.56 0.31 1.92 0.83 0.53 1.00 1.00 1.00 1.00 1.00 0.94 1.48 1.38 1.82 1.78 0.20 1.82 0.19 1.58 0.38 4.07 4.07 1.92 1.00 1.00 1.00 1.00 1.00 0.83 0.53 1.86 0.21 1.78 0.20 1.53 0.92 1.50 1.27 1.98 0.38 6.00 6.00 FCU-BF.02.1 / 3.0 TR FCU-BF.03.3 / 2.5 TR FCU-BF.03.2 / 2.5 TR FCU-BF.04.2 / 2.0 TR FCU-BF.01.1 / 3.5 TR FCU-BF.03.1 / 2.5 TR FCU-BF.04.1 / 2.0 TR W.SU-BF.02.1 / 1.5 TR W.SU-BF.01.1 / 2.0 TR Size: 250x250 BOD: 4.15m Size: 350x350 BOD: 4.10m Size: 450x350 BOD: 4.10m Size: 450x350 BOD: 4.10m Size: 350x350 BOD: 4.10m Size: 250x250 BOD: 4.15m Size: 250x200 BOD: 3.31m Size: 350x300 BOD: 3.26m Size: 200x200 BOD: 3.31m Size: 300x300 BOD: 3.26m Size: 500x300 BOD: 3.26m Size: 500x300 BOD: 3.26m Size: 250x250 BOD: 3.55m Size: 250x250 BOD: 3.55m Size: 400x250 BOD: 3.55m Size: 450x300 BOD: 3.52m Size: 350x300 BOD: 3.52m Size: 250x250 BOD: 3.55m Size: 200x200 BOD: 3.57m Size: 250x250 BOD: 3.69m Size: 350x300 BOD: 3.66m Size: 500x350 BOD: 3.64m Size: 350x300 BOD: 3.66m Size: 250x250 BOD: 3.69m Size: 250x200 BOD: 3.50m Size: 300x250 BOD: 3.48m Size: 200x200 BOD: 3.50m Size: 400x250 BOD: 3.47m Size: 400x250 BOD: 3.48m 125 Ф 125 Ф 125 Ф 200 Ф 200 Ф 200 Ф 200 Ф 125 Ф 125 Ф 125 Ф 125 Ф 125 Ф FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 8.50 m 1200 CFM 7.58 m 1200 CFM 1 1 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 12.00 m 1000 CFM 12 m 1000 CFM 3 3 6.00 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 6.00 m 800 CFM 10.05 m 800 CFM 1 2.00 2.50 0.73 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 8.50 m 1400 CFM 7.75 m 1400 CFM 2 2 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 8.00 m 1000 CFM 10.04 m 1000 CFM 1 2.88 1.63 0.98 0.50 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 6.50 m 800 CFM 5 m 800 CFM 1 1 A AC-14 B AC-15 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 BASEMENT FLOOR HVAC DUCTING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-01 A.S A.S A.I SCALE 1 : 65 BASEMENT FLOOR HVAC DUCTING PLAN 01 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 3. CEILING MOUNTED F.C.U CUT OFF & COMBINED METERING RETURN CHILED WATER SUPPLY CHILLED WATER AUXILIARY CONTROL 2-WAY VALVE CUT OFF VALVE COLLAR DIELECTRIC FILTER BALANCING VALVE CONNECTION CONNECTION ELECTRICAL INLET DRAIN PAN STRAINER FLOW DIRECTION FLOW DIRECTION AIR DIRECTION AIR DIRECTION FAN & MOTOR FAN & MOTOR COIL FLOW METER REF. NAME SUPPORTING ANGLE SIZE MAX. DUCT (mm) HANGING ROD SIZE SIZE. (mm) (mm) SPACING (mm) TABLE THIS TABLE IS BASED ON DW/144 FOR FIGURE-68 CONCRETE SLAB 32 32 25 25 DUCT SIZE DUCT SIZE DUCT SIZE DUCT SUPPORTING DETAILS SCALE N.T.S. G.I. THREADED ROD (REFER TO SCHEDULE) WASHER (TYP.) DOUBLE LOCKNUT W/ EXPANSION SHIELD (TYPICAL) MS ANGLE (REFER TO SCHEDULE) LOCKNUT W/ WASHER GA6 GA5 GA4 GA3 GA2 GA1 3000 60x60x6 2500mm 12mm 2000 50x50x5 2500mm 10mm 1500 40x40x3 2500mm 10mm 1000 30x30x3 3000mm 8mm 600 25x25x3 3000mm 8mm 400 25x25x1.6 3000mm 8mm LEGEND : APPLICATION : NOTE : 8 2a 6 7 3 4 1 2 4A 5 5A 3 1 2 2a 4 OR 5 7 3 - 2 1 - 2a 4 7 6 - 6 8 3 2 1 2a 5 7 6 8 - 3 2 1 2a 4A 7 6 8 3 2 1 2a 5A 7 6 8 ** ** ** ** ** * ADHESIVE FOR LINEAR INSULATION SELF ADHESIVE PIN ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE 50x50x0.6mm G.I CORNER ANGLE ALUMINUM CLADDING (0.7mm THICKNESS) ACOUSTIC DUCT LINER CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1 G.I DUCTING CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1 ELASTOMERIC FOAM TYPE DI-2 DI-1 SCHEDULE OF INSULATION INSULATION TYPE THICKNESS (mm) 25 25 DENSITY (Kg/m ) 64 64 3 THERMAL CONDUCTIVITY (W/M°K) 0.037 0.037 MAXIMUM TEMP. RATING (°C) 85 85 APPLICATION CONCEALED SUPPLY/RETURN IN CONDITIONED AREA INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY & RETURN DUCT . IN SHAFT, TUNNELS & NON CONDITIONED SPACE. APLICABLE ONLY FROM THE FAN OUTLET, ACOUSTIC DUCT LINER @3 METER LENGTH, GRILLE & PLENUM BOX OR TO FIRST BRANCH. INDOOR A/C SUPPLY & RETURN DUCT IN CONDENSING SPACE. REFER TO DUCT LINEAR INSULATION DETAILS INDOOR A/C SUPPLY & RETURN DUCT IN MECHANICAL ROOMS & CONDITIONED SPACE. REFER TO NOTE: REFER TO DUCT LINEAR INSULATION DETAILS INSULATION ELASTOMERIC FOAM INSULATION FINISH F1 F2 TYPE FINISH TYPE FACTORY APPLIED ALUMINUM FOIL ALUMINUM CLADING 0.7mm THICKNESS DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED ELASTOMERIC FOAM INSULATION F2 ALUMINUM CLADING 0.7mm THICKNESS DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH ELASTOMERIC FOAM INSULATION F1+F2 ALUMINUM CLADING 85 85 ALUMINUM FOIL CONDITIONED AREA IN MECHANICAL ROOMS AREAS (TUNNELS & SHAFTS) * AT MEAN TEMPERATURE OF 20°C REFER TO SPECIFICATION SECTION 15341 REFER TO MECHANICAL SUBMITTAL REFERENCE 11- MA-004-A TYPICAL DUCT INSULATION AND LAGGING DETAIL SCALE N.T.S. CAPACITY AIR FLOW L/S DIA. FLEX. DUCT (mm) - TYPICAL FLEXIBLE DUCT HANGER DETAILS (AS PER SPECIFICATION) INSULATION FIBERGLASS SPACING (41.7mm PER m) OF SUPPORT MAX. SAG 12.7mm PER 300mm NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED, 25.4 x 0.85mm DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm. G.I. ROD 2.75 @1500mm O.C. (MAXIMUM) BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES. G.I. STRAP ALUMINUM FLEXIBLE DUCT - UP TO 30 100 160 61 TO 90 200 91 TO 135 250 136 TO 200 300 201 TO 300 301 TO 380 350 381 TO 500 400 125 31 TO 60 SCALE N.T.S. TYPICAL SPLITTER DETAIL 06 013 NTS ECCENTRIC TRANSITION DIVERGING MAX. 30° x W W1 x D1 = A MAIN DUCT AIR FLOW W2 x D2 = B R = 0.75W R1 = A + R MAIN DUCT R R1 BRANCH DUCT (W1 x D1) + (W2 x D2) (W1 x D1) + (W2 x D2) x W V.D V.D "B" W x D "A" 1000mm min. W1 x D1 W2 x D2 40mm 4 0 m m 1 5 m m DUCT DETAILS FLESIBLE CONNECTION 08 013 NTS 8mm FLANGE SEALING COMPOUND APPLIED BETWEEN FABRIC, BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY* * REQUIRED ON HIGH PRESSURE SYSTEMS ONLY BOLT ON 100mm CENTERS ROUND (FAN INLET) SEALING COMPOUND APPLIED BETWEEN FLEXIBLE CONNECTION AND CASING BEFORE ASSEMBLY * RECTANGULAR (FAN OUTLET) RUBBER IMPREGNATED FABRIC CASING DUCT 40mm POCKET SLIP ALTERNATE POSITION OF BOLT 25mm x 3mm BAND IRON BOLT ON 100mm CENTERS 25mm FLANGE AND HEM 20 U.S. GAUGE STEEL 25mm x 3mm BAND IRON SHEET METAL SCREWS ON 300mm CENTERS 25mm x 3mm DRAW BAND RUBBER IMPREGNATED FABRIC RIVET ON 100mm CENTERS 8mm FLANGE 18 U.S. GAGE STEEL DUCT THRU WALL MOUNTING DETAIL 01 013 NTS DUCTWORK DUCT INSULATION (SEE SPECS. FOR DETAILS) NON-HARDENING MASTIC SEALANT ALL AROUND (TYPICAL) #20 G.I. SHEET DUCT SLEEVE ALL AROUND REINFORCED DUCT TAPE MASONRY WALL 50mm MAX. 50mm MAX. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 2 3 4 5 6 B C D E F G H 7 1 A I 0.26 0.26 0.27 0.26 0.25 0.25 0.25 3.15 1.22 1.38 1.19 0.61 0.31 0.83 0.83 1.42 1.10 0.51 1.26 1.16 1.00 1.40 1.19 1.42 0.83 0.83 0.70 0.40 0.21 1.25 1.86 0.24 1.76 0.20 1.77 0.28 1.62 1.50 1.36 1.87 2.08 1.80 1.84 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.72 0.42 8.00 6.00 2.39 1.86 0.20 1.80 0.22 1.80 0.22 1.68 1.56 1.28 1.92 2.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.72 0.42 0.40 2.36 2.50 3.15 0.60 2.50 1.65 0.17 1.81 0.21 0.88 0.71 0.79 1.70 1.98 1.00 1.00 1.00 1.00 0.62 0.32 1.60 1.89 2.59 4.52 0.75 5.00 1.93 0.17 1.88 0.18 0.88 0.71 0.83 1.62 2.00 1.00 1.00 1.00 1.00 0.53 0.83 1.54 0.83 1.96 0.28 5.00 2.00 2.25 FCU-GF.03.1 / 2.5 TR Size: 300x250 BOD: 3.87m Size: 400x350 BOD: 3.82m Size: 450x400 BOD: 3.80m Size: 550x400 BOD: 3.80m Size: 550x400 BOD: 3.80m Size: 450x400 BOD: 3.80m Size: 400x350 BOD: 3.82m Size: 300x250 BOD: 3.87m Size: 200x200 BOD: 4.30m Size: 300x300 BOD: 4.25m Size: 350x350 BOD: 4.22m Size: 600x350 BOD: 4.22m Size: 200x200 BOD: 4.30m Size: 300x300 BOD: 4.25m Size: 350x350 BOD: 4.22m Size: 600x350 BOD: -0.89m Size: 300x300 BOD: 4.24m Size: 300x300 BOD: 4.24m Size: 300x300 BOD: 4.24m Size: 500x300 BOD: 4.24m FCU-BF.03.1 / 2.5 TR FCU-GF.03.2 / 2.5 TR FCU-GF.01.1 / 3.0 TR W.SU-BF.01.1 / 2.0 TR W.SU-BF.01.2 / 2.0 TR Size: 550x400 BOD: 4.19m 200 Ф 200 Ф 200 Ф 200 Ф 200 Ф 200 Ф FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 10.00 m 1200 CFM 10.54 m 1200 CFM 2 2 4.52 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 5.00 m 1000 CFM 7.5 m 1000 CFM 2 2 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 16.00 m 2000 CFM 12 m 2000 CFM 3 3 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 GROUND FLOOR HVAC DUCTING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-02 A.S A.S A.I SCALE 1 : 65 GROUND FLOOR HVAC DUCTING PLAN 02 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 4. CEILING MOUNTED F.C.U CUT OFF & COMBINED METERING RETURN CHILED WATER SUPPLY CHILLED WATER AUXILIARY CONTROL 2-WAY VALVE CUT OFF VALVE COLLAR DIELECTRIC FILTER BALANCING VALVE CONNECTION CONNECTION ELECTRICAL INLET DRAIN PAN STRAINER FLOW DIRECTION FLOW DIRECTION AIR DIRECTION AIR DIRECTION FAN & MOTOR FAN & MOTOR COIL FLOW METER REF. NAME SUPPORTING ANGLE SIZE MAX. DUCT (mm) HANGING ROD SIZE SIZE. (mm) (mm) SPACING (mm) TABLE THIS TABLE IS BASED ON DW/144 FOR FIGURE-68 CONCRETE SLAB 32 32 25 25 DUCT SIZE DUCT SIZE DUCT SIZE DUCT SUPPORTING DETAILS SCALE N.T.S. G.I. THREADED ROD (REFER TO SCHEDULE) WASHER (TYP.) DOUBLE LOCKNUT W/ EXPANSION SHIELD (TYPICAL) MS ANGLE (REFER TO SCHEDULE) LOCKNUT W/ WASHER GA6 GA5 GA4 GA3 GA2 GA1 3000 60x60x6 2500mm 12mm 2000 50x50x5 2500mm 10mm 1500 40x40x3 2500mm 10mm 1000 30x30x3 3000mm 8mm 600 25x25x3 3000mm 8mm 400 25x25x1.6 3000mm 8mm LEGEND : APPLICATION : NOTE : 8 2a 6 7 3 4 1 2 4A 5 5A 3 1 2 2a 4 OR 5 7 3 - 2 1 - 2a 4 7 6 - 6 8 3 2 1 2a 5 7 6 8 - 3 2 1 2a 4A 7 6 8 3 2 1 2a 5A 7 6 8 ** ** ** ** ** * ADHESIVE FOR LINEAR INSULATION SELF ADHESIVE PIN ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE 50x50x0.6mm G.I CORNER ANGLE ALUMINUM CLADDING (0.7mm THICKNESS) ACOUSTIC DUCT LINER CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1 G.I DUCTING CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1 ELASTOMERIC FOAM TYPE DI-2 DI-1 SCHEDULE OF INSULATION INSULATION TYPE THICKNESS (mm) 25 25 DENSITY (Kg/m ) 64 64 3 THERMAL CONDUCTIVITY (W/M°K) 0.037 0.037 MAXIMUM TEMP. RATING (°C) 85 85 APPLICATION CONCEALED SUPPLY/RETURN IN CONDITIONED AREA INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY & RETURN DUCT . IN SHAFT, TUNNELS & NON CONDITIONED SPACE. APLICABLE ONLY FROM THE FAN OUTLET, ACOUSTIC DUCT LINER @3 METER LENGTH, GRILLE & PLENUM BOX OR TO FIRST BRANCH. INDOOR A/C SUPPLY & RETURN DUCT IN CONDENSING SPACE. REFER TO DUCT LINEAR INSULATION DETAILS INDOOR A/C SUPPLY & RETURN DUCT IN MECHANICAL ROOMS & CONDITIONED SPACE. REFER TO NOTE: REFER TO DUCT LINEAR INSULATION DETAILS INSULATION ELASTOMERIC FOAM INSULATION FINISH F1 F2 TYPE FINISH TYPE FACTORY APPLIED ALUMINUM FOIL ALUMINUM CLADING 0.7mm THICKNESS DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED ELASTOMERIC FOAM INSULATION F2 ALUMINUM CLADING 0.7mm THICKNESS DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH ELASTOMERIC FOAM INSULATION F1+F2 ALUMINUM CLADING 85 85 ALUMINUM FOIL CONDITIONED AREA IN MECHANICAL ROOMS AREAS (TUNNELS & SHAFTS) * AT MEAN TEMPERATURE OF 20°C REFER TO SPECIFICATION SECTION 15341 REFER TO MECHANICAL SUBMITTAL REFERENCE 11- MA-004-A TYPICAL DUCT INSULATION AND LAGGING DETAIL SCALE N.T.S. CAPACITY AIR FLOW L/S DIA. FLEX. DUCT (mm) - TYPICAL FLEXIBLE DUCT HANGER DETAILS (AS PER SPECIFICATION) INSULATION FIBERGLASS SPACING (41.7mm PER m) OF SUPPORT MAX. SAG 12.7mm PER 300mm NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED, 25.4 x 0.85mm DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm. G.I. ROD 2.75 @1500mm O.C. (MAXIMUM) BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES. G.I. STRAP ALUMINUM FLEXIBLE DUCT - UP TO 30 100 160 61 TO 90 200 91 TO 135 250 136 TO 200 300 201 TO 300 301 TO 380 350 381 TO 500 400 125 31 TO 60 SCALE N.T.S. TYPICAL SPLITTER DETAIL 06 013 NTS ECCENTRIC TRANSITION DIVERGING MAX. 30° x W W1 x D1 = A MAIN DUCT AIR FLOW W2 x D2 = B R = 0.75W R1 = A + R MAIN DUCT R R1 BRANCH DUCT (W1 x D1) + (W2 x D2) (W1 x D1) + (W2 x D2) x W V.D V.D "B" W x D "A" 1000mm min. W1 x D1 W2 x D2 40mm 4 0 m m 1 5 m m DUCT DETAILS FLESIBLE CONNECTION 08 013 NTS 8mm FLANGE SEALING COMPOUND APPLIED BETWEEN FABRIC, BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY* * REQUIRED ON HIGH PRESSURE SYSTEMS ONLY BOLT ON 100mm CENTERS ROUND (FAN INLET) SEALING COMPOUND APPLIED BETWEEN FLEXIBLE CONNECTION AND CASING BEFORE ASSEMBLY * RECTANGULAR (FAN OUTLET) RUBBER IMPREGNATED FABRIC CASING DUCT 40mm POCKET SLIP ALTERNATE POSITION OF BOLT 25mm x 3mm BAND IRON BOLT ON 100mm CENTERS 25mm FLANGE AND HEM 20 U.S. GAUGE STEEL 25mm x 3mm BAND IRON SHEET METAL SCREWS ON 300mm CENTERS 25mm x 3mm DRAW BAND RUBBER IMPREGNATED FABRIC RIVET ON 100mm CENTERS 8mm FLANGE 18 U.S. GAGE STEEL DUCT THRU WALL MOUNTING DETAIL 01 013 NTS DUCTWORK DUCT INSULATION (SEE SPECS. FOR DETAILS) NON-HARDENING MASTIC SEALANT ALL AROUND (TYPICAL) #20 G.I. SHEET DUCT SLEEVE ALL AROUND REINFORCED DUCT TAPE MASONRY WALL 50mm MAX. 50mm MAX. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 2 3 4 5 6 C D E F G 0.26 0.26 0.26 0.26 0.54 0.70 0.21 0.83 0.20 0.79 0.22 1.50 0.60 1.52 0.98 1.34 2.39 0.81 4.00 4.00 1.00 1.00 1.00 1.01 0.79 1.48 1.45 1.06 1.40 1.14 1.49 1.18 1.80 1.20 1.20 1.04 1.04 1.04 1.04 1.04 0.62 0.32 6.25 1.04 6.25 1.15 0.72 1.82 0.78 0.18 0.89 0.22 1.83 0.20 1.58 1.40 1.92 1.57 1.31 1.90 1.60 5.00 4.00 1.00 1.00 1.00 1.00 0.76 0.46 0.25 1.26 2.56 0.90 0.78 0.22 0.85 0.22 1.83 0.20 1.58 1.40 1.55 1.65 1.82 1.00 1.00 1.00 1.00 0.76 0.46 1.90 1.55 1.23 2.02 1.60 0.41 0.34 1.68 0.87 0.22 0.85 0.79 1.20 1.56 0.87 1.00 1.00 0.69 0.39 0.66 1.47 0.42 1.21 0.96 1.10 1.40 0.77 0.49 1.30 1.10 0.86 0.19 0.75 0.24 0.80 0.23 0.66 1.40 1.35 1.20 0.89 1.06 1.06 1.44 4.00 0.66 0.71 0.41 1.00 1.00 1.00 4.00 Size: 250x200 BOD: 3.15m Size: 300x300 BOD: 3.10m Size: 350x350 BOD: 3.07m Size: 450x350 BOD: 3.07m Size: 450x300 BOD: 3.10m Size: 200x200 BOD: 3.40m Size: 200x200 BOD: 3.40m Size: 300x250 BOD: 3.37m Size: 300x250 BOD: 3.37m Size: 250x200 BOD: 3.15m Size: 450x300 BOD: 3.10m Size: 550x300 BOD: 3.10m Size: 250x250 BOD: 3.13m Size: 350x300 BOD: 3.10m Size: 350x300 BOD: 3.10m Size: 350x300 BOD: 3.10m Size: 500x300 BOD: 3.10m Size: 500x300 BOD: 3.10m Size: 500x300 BOD: 3.10m Size: 500x300 BOD: 3.10m Size: 400x300 BOD: 3.10m Size: 300x300 BOD: 3.10m Size: 250x250 BOD: 3.12m FCU-1F.02.2 / 3.0 TR FCU-1F.04.1 / 1.5 TR FCU-1F.02.2 / 3.0 TR FCU-1F.03.1 / 2.0 TR FCU-1F.01.2 / 2.5 TR FCU-1F.01.1 / 3.25 TR 125 Ф 200 Ф 0.61 0.31 200 Ф 200 Ф 200 Ф 200 Ф 0.95 0.41 0.97 0.66 0.31 0.37 0.33 0.36 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 4.00 m 1200 CFM 4 m 1200 CFM 3 3 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 3.00 m 800 CFM 3 m 800 CFM 3 3 3.00 3.00 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 10.00 m 2600 CFM 8 m 2600 CFM 3 3 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 6.25 m 600 CFM 8.33 m 600 CFM 1 1 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 4.00 m 1200 CFM 4 m 1200 CFM 3 3 C AC-17 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 FIRST FLOOR HVAC DUCTING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-03 A.S A.S A.I SCALE 1 : 65 FIRST FLOOR HVAC DUCTING PLAN 03 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 5. CEILING MOUNTED F.C.U CUT OFF & COMBINED METERING RETURN CHILED WATER SUPPLY CHILLED WATER AUXILIARY CONTROL 2-WAY VALVE CUT OFF VALVE COLLAR DIELECTRIC FILTER BALANCING VALVE CONNECTION CONNECTION ELECTRICAL INLET DRAIN PAN STRAINER FLOW DIRECTION FLOW DIRECTION AIR DIRECTION AIR DIRECTION FAN & MOTOR FAN & MOTOR COIL FLOW METER REF. NAME SUPPORTING ANGLE SIZE MAX. DUCT (mm) HANGING ROD SIZE SIZE. (mm) (mm) SPACING (mm) TABLE THIS TABLE IS BASED ON DW/144 FOR FIGURE-68 CONCRETE SLAB 32 32 25 25 DUCT SIZE DUCT SIZE DUCT SIZE DUCT SUPPORTING DETAILS SCALE N.T.S. G.I. THREADED ROD (REFER TO SCHEDULE) WASHER (TYP.) DOUBLE LOCKNUT W/ EXPANSION SHIELD (TYPICAL) MS ANGLE (REFER TO SCHEDULE) LOCKNUT W/ WASHER GA6 GA5 GA4 GA3 GA2 GA1 3000 60x60x6 2500mm 12mm 2000 50x50x5 2500mm 10mm 1500 40x40x3 2500mm 10mm 1000 30x30x3 3000mm 8mm 600 25x25x3 3000mm 8mm 400 25x25x1.6 3000mm 8mm LEGEND : APPLICATION : NOTE : 8 2a 6 7 3 4 1 2 4A 5 5A 3 1 2 2a 4 OR 5 7 3 - 2 1 - 2a 4 7 6 - 6 8 3 2 1 2a 5 7 6 8 - 3 2 1 2a 4A 7 6 8 3 2 1 2a 5A 7 6 8 ** ** ** ** ** * ADHESIVE FOR LINEAR INSULATION SELF ADHESIVE PIN ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE 50x50x0.6mm G.I CORNER ANGLE ALUMINUM CLADDING (0.7mm THICKNESS) ACOUSTIC DUCT LINER CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1 G.I DUCTING CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1 ELASTOMERIC FOAM TYPE DI-2 DI-1 SCHEDULE OF INSULATION INSULATION TYPE THICKNESS (mm) 25 25 DENSITY (Kg/m ) 64 64 3 THERMAL CONDUCTIVITY (W/M°K) 0.037 0.037 MAXIMUM TEMP. RATING (°C) 85 85 APPLICATION CONCEALED SUPPLY/RETURN IN CONDITIONED AREA INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY & RETURN DUCT . IN SHAFT, TUNNELS & NON CONDITIONED SPACE. APLICABLE ONLY FROM THE FAN OUTLET, ACOUSTIC DUCT LINER @3 METER LENGTH, GRILLE & PLENUM BOX OR TO FIRST BRANCH. INDOOR A/C SUPPLY & RETURN DUCT IN CONDENSING SPACE. REFER TO DUCT LINEAR INSULATION DETAILS INDOOR A/C SUPPLY & RETURN DUCT IN MECHANICAL ROOMS & CONDITIONED SPACE. REFER TO NOTE: REFER TO DUCT LINEAR INSULATION DETAILS INSULATION ELASTOMERIC FOAM INSULATION FINISH F1 F2 TYPE FINISH TYPE FACTORY APPLIED ALUMINUM FOIL ALUMINUM CLADING 0.7mm THICKNESS DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED ELASTOMERIC FOAM INSULATION F2 ALUMINUM CLADING 0.7mm THICKNESS DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH ELASTOMERIC FOAM INSULATION F1+F2 ALUMINUM CLADING 85 85 ALUMINUM FOIL CONDITIONED AREA IN MECHANICAL ROOMS AREAS (TUNNELS & SHAFTS) * AT MEAN TEMPERATURE OF 20°C REFER TO SPECIFICATION SECTION 15341 REFER TO MECHANICAL SUBMITTAL REFERENCE 11- MA-004-A TYPICAL DUCT INSULATION AND LAGGING DETAIL SCALE N.T.S. CAPACITY AIR FLOW L/S DIA. FLEX. DUCT (mm) - TYPICAL FLEXIBLE DUCT HANGER DETAILS (AS PER SPECIFICATION) INSULATION FIBERGLASS SPACING (41.7mm PER m) OF SUPPORT MAX. SAG 12.7mm PER 300mm NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED, 25.4 x 0.85mm DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm. G.I. ROD 2.75 @1500mm O.C. (MAXIMUM) BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES. G.I. STRAP ALUMINUM FLEXIBLE DUCT - UP TO 30 100 160 61 TO 90 200 91 TO 135 250 136 TO 200 300 201 TO 300 301 TO 380 350 381 TO 500 400 125 31 TO 60 SCALE N.T.S. TYPICAL SPLITTER DETAIL 06 013 NTS ECCENTRIC TRANSITION DIVERGING MAX. 30° x W W1 x D1 = A MAIN DUCT AIR FLOW W2 x D2 = B R = 0.75W R1 = A + R MAIN DUCT R R1 BRANCH DUCT (W1 x D1) + (W2 x D2) (W1 x D1) + (W2 x D2) x W V.D V.D "B" W x D "A" 1000mm min. W1 x D1 W2 x D2 40mm 4 0 m m 1 5 m m DUCT DETAILS FLESIBLE CONNECTION 08 013 NTS 8mm FLANGE SEALING COMPOUND APPLIED BETWEEN FABRIC, BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY* * REQUIRED ON HIGH PRESSURE SYSTEMS ONLY BOLT ON 100mm CENTERS ROUND (FAN INLET) SEALING COMPOUND APPLIED BETWEEN FLEXIBLE CONNECTION AND CASING BEFORE ASSEMBLY * RECTANGULAR (FAN OUTLET) RUBBER IMPREGNATED FABRIC CASING DUCT 40mm POCKET SLIP ALTERNATE POSITION OF BOLT 25mm x 3mm BAND IRON BOLT ON 100mm CENTERS 25mm FLANGE AND HEM 20 U.S. GAUGE STEEL 25mm x 3mm BAND IRON SHEET METAL SCREWS ON 300mm CENTERS 25mm x 3mm DRAW BAND RUBBER IMPREGNATED FABRIC RIVET ON 100mm CENTERS 8mm FLANGE 18 U.S. GAGE STEEL DUCT THRU WALL MOUNTING DETAIL 01 013 NTS DUCTWORK DUCT INSULATION (SEE SPECS. FOR DETAILS) NON-HARDENING MASTIC SEALANT ALL AROUND (TYPICAL) #20 G.I. SHEET DUCT SLEEVE ALL AROUND REINFORCED DUCT TAPE MASONRY WALL 50mm MAX. 50mm MAX. 2 3 4 5 6 B C D E F G EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ 0.37 0.37 EQ EQ EQ EQ 3.17 2.41 2.41 EQ EQ EQ EQ 2.62 2.62 EQ EQ 6.74 0.85 0.94 0.17 1.73 0.99 1.40 1.10 0.65 1.00 1.00 0.57 0.37 0.80 1.10 1.40 0.97 1.60 0.16 0.96 0.85 0.59 0.39 3.17 1.02 0.26 0.45 1.17 0.26 0.27 1.23 0.18 2.75 1.18 1.28 1.51 0.80 0.27 3.00 0.35 1.00 1.00 0.61 0.31 1.23 0.88 0.20 0.77 0.21 0.77 0.69 0.45 1.10 1.02 1.55 0.94 2.16 0.50 3.00 1.17 0.85 0.94 0.15 1.96 0.85 0.96 1.25 0.34 0.25 1.49 0.23 1.70 0.24 1.78 0.51 2.03 1.92 1.31 0.96 0.96 0.96 0.96 0.96 0.86 0.61 5.75 0.81 2.22 1.00 1.00 1.00 1.01 1.00 0.91 0.66 1.90 0.19 1.70 0.24 2.08 1.36 1.99 1.84 1.26 1.59 6.00 4.09 4.37 2.74 FCU-2F.01.1 / 3.25 TR FCU-2F.04.2 / 2.0 TR FCU-2F.05.1 / 1.5 TR FCU-1F.03.1 / 2.5 TR FCU-2F.01.2 / 3.25 TR FCU-2F.02.1 / 3.0 TR FCU-2F.04.1 / 2.0 TR 3.57 0.26 125 Ф 125 Ф 200 Ф 200 Ф 200 Ф 125 Ф Size: 250x250 BOD: 3.03m Size: 300x250 BOD: 3.03m Size: 250x250 BOD: 2.67m Size: 300x300 BOD: 2.65m Size: 350x350 BOD: 2.62m Size: 350x350 BOD: 2.92m Size: 350x350 BOD: 3.10m Size: 500x350 BOD: 3.12m Size: 350x350 BOD: 3.12m Size: 300x250 BOD: 3.17m Size: 350x350 BOD: 3.12m Size: 500x350 BOD: 3.12m Size: 200x200 BOD: 3.10m Size: 200x200 BOD: 3.10m Size: 250x250 BOD: 3.08m Size: 250x250 BOD: 3.08m Size: 250x250 BOD: 3.08m Size: 250x250 BOD: 3.08m Size: 200x200 BOD: 3.10m Size: 200x200 BOD: 3.10m Size: 400x250 BOD: 3.08m Size: 400x250 BOD: 3.08m Size: 350x350 BOD: 2.92m Size: 400x250 BOD: 3.08m FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 6.34 m 800 CFM 4.82 m 800 CFM 1 1 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 6.34 m 800 CFM 5.24 m 800 CFM 1 1 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 11.75 m 2600 CFM 14.94 m 2600 CFM 3 3 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 3.00 m 1200 CFM 3 m 1200 CFM 3 3 1.00 2.74 E AC-18 F AC-19 D AC-16 QTY. FLOW DIM. (mm) DIF. TYPE SSD SRD 400x400 400x400 1 1000 CFM 1000 CFM 1 QTY. FLOW DIM. (mm) DIF. TYPE SSD SRD 225x225 225x225 1.40 1.75 VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 SECOND FLOOR HVAC DUCTING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-04 A.S A.S A.I SCALE 1 : 65 SECOND FLOOR HVAC DUCTING PLAN 04 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 6. CEILING MOUNTED F.C.U CUT OFF & COMBINED METERING RETURN CHILED WATER SUPPLY CHILLED WATER AUXILIARY CONTROL 2-WAY VALVE CUT OFF VALVE COLLAR DIELECTRIC FILTER BALANCING VALVE CONNECTION CONNECTION ELECTRICAL INLET DRAIN PAN STRAINER FLOW DIRECTION FLOW DIRECTION AIR DIRECTION AIR DIRECTION FAN & MOTOR FAN & MOTOR COIL FLOW METER REF. NAME SUPPORTING ANGLE SIZE MAX. DUCT (mm) HANGING ROD SIZE SIZE. (mm) (mm) SPACING (mm) TABLE THIS TABLE IS BASED ON DW/144 FOR FIGURE-68 CONCRETE SLAB 32 32 25 25 DUCT SIZE DUCT SIZE DUCT SIZE DUCT SUPPORTING DETAILS SCALE N.T.S. G.I. THREADED ROD (REFER TO SCHEDULE) WASHER (TYP.) DOUBLE LOCKNUT W/ EXPANSION SHIELD (TYPICAL) MS ANGLE (REFER TO SCHEDULE) LOCKNUT W/ WASHER GA6 GA5 GA4 GA3 GA2 GA1 3000 60x60x6 2500mm 12mm 2000 50x50x5 2500mm 10mm 1500 40x40x3 2500mm 10mm 1000 30x30x3 3000mm 8mm 600 25x25x3 3000mm 8mm 400 25x25x1.6 3000mm 8mm LEGEND : APPLICATION : NOTE : 8 2a 6 7 3 4 1 2 4A 5 5A 3 1 2 2a 4 OR 5 7 3 - 2 1 - 2a 4 7 6 - 6 8 3 2 1 2a 5 7 6 8 - 3 2 1 2a 4A 7 6 8 3 2 1 2a 5A 7 6 8 ** ** ** ** ** * ADHESIVE FOR LINEAR INSULATION SELF ADHESIVE PIN ALUMINUM PLAIN FSK FINISH SELF ADHESIVE TAPE 50x50x0.6mm G.I CORNER ANGLE ALUMINUM CLADDING (0.7mm THICKNESS) ACOUSTIC DUCT LINER CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-1)+F1 G.I DUCTING CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-2) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-3) CLOSED CELL ELASTOMERIC FOAM INSULATION (DI-4)+F1 ELASTOMERIC FOAM TYPE DI-2 DI-1 SCHEDULE OF INSULATION INSULATION TYPE THICKNESS (mm) 25 25 DENSITY (Kg/m ) 64 64 3 THERMAL CONDUCTIVITY (W/M°K) 0.037 0.037 MAXIMUM TEMP. RATING (°C) 85 85 APPLICATION CONCEALED SUPPLY/RETURN IN CONDITIONED AREA INDOOR A/C SUPPLY & RETURN DUCT ROOF EXPOSED A/C SUPPLY & RETURN DUCT . IN SHAFT, TUNNELS & NON CONDITIONED SPACE. APLICABLE ONLY FROM THE FAN OUTLET, ACOUSTIC DUCT LINER @3 METER LENGTH, GRILLE & PLENUM BOX OR TO FIRST BRANCH. INDOOR A/C SUPPLY & RETURN DUCT IN CONDENSING SPACE. REFER TO DUCT LINEAR INSULATION DETAILS INDOOR A/C SUPPLY & RETURN DUCT IN MECHANICAL ROOMS & CONDITIONED SPACE. REFER TO NOTE: REFER TO DUCT LINEAR INSULATION DETAILS INSULATION ELASTOMERIC FOAM INSULATION FINISH F1 F2 TYPE FINISH TYPE FACTORY APPLIED ALUMINUM FOIL ALUMINUM CLADING 0.7mm THICKNESS DI-3 50 64 0.037 CONCEALED DUCTS IN UNCONDITIONED ELASTOMERIC FOAM INSULATION F2 ALUMINUM CLADING 0.7mm THICKNESS DI-4 50 64 0.037 OUTDOOR/ EXPOSED DUCT DIRECT TO SUNLIGTH ELASTOMERIC FOAM INSULATION F1+F2 ALUMINUM CLADING 85 85 ALUMINUM FOIL CONDITIONED AREA IN MECHANICAL ROOMS AREAS (TUNNELS & SHAFTS) * AT MEAN TEMPERATURE OF 20°C REFER TO SPECIFICATION SECTION 15341 REFER TO MECHANICAL SUBMITTAL REFERENCE 11- MA-004-A TYPICAL DUCT INSULATION AND LAGGING DETAIL SCALE N.T.S. CAPACITY AIR FLOW L/S DIA. FLEX. DUCT (mm) - TYPICAL FLEXIBLE DUCT HANGER DETAILS (AS PER SPECIFICATION) INSULATION FIBERGLASS SPACING (41.7mm PER m) OF SUPPORT MAX. SAG 12.7mm PER 300mm NOTES: STRAPS ARE GALVANIZED STEEL; WIRE IS BLACK ANNEALED, 25.4 x 0.85mm DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. FLEXIBLE DUCT MAXIMUM LENGTH NOT EXCEED 1500mm. G.I. ROD 2.75 @1500mm O.C. (MAXIMUM) BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES. G.I. STRAP ALUMINUM FLEXIBLE DUCT - UP TO 30 100 160 61 TO 90 200 91 TO 135 250 136 TO 200 300 201 TO 300 301 TO 380 350 381 TO 500 400 125 31 TO 60 SCALE N.T.S. TYPICAL SPLITTER DETAIL 06 013 NTS ECCENTRIC TRANSITION DIVERGING MAX. 30° x W W1 x D1 = A MAIN DUCT AIR FLOW W2 x D2 = B R = 0.75W R1 = A + R MAIN DUCT R R1 BRANCH DUCT (W1 x D1) + (W2 x D2) (W1 x D1) + (W2 x D2) x W V.D V.D "B" W x D "A" 1000mm min. W1 x D1 W2 x D2 40mm 4 0 m m 1 5 m m DUCT DETAILS FLESIBLE CONNECTION 08 013 NTS 8mm FLANGE SEALING COMPOUND APPLIED BETWEEN FABRIC, BAND AND 18 U.S. GAUGE STEEL, BEFORE ASSEMBLY* * REQUIRED ON HIGH PRESSURE SYSTEMS ONLY BOLT ON 100mm CENTERS ROUND (FAN INLET) SEALING COMPOUND APPLIED BETWEEN FLEXIBLE CONNECTION AND CASING BEFORE ASSEMBLY * RECTANGULAR (FAN OUTLET) RUBBER IMPREGNATED FABRIC CASING DUCT 40mm POCKET SLIP ALTERNATE POSITION OF BOLT 25mm x 3mm BAND IRON BOLT ON 100mm CENTERS 25mm FLANGE AND HEM 20 U.S. GAUGE STEEL 25mm x 3mm BAND IRON SHEET METAL SCREWS ON 300mm CENTERS 25mm x 3mm DRAW BAND RUBBER IMPREGNATED FABRIC RIVET ON 100mm CENTERS 8mm FLANGE 18 U.S. GAGE STEEL DUCT THRU WALL MOUNTING DETAIL 01 013 NTS DUCTWORK DUCT INSULATION (SEE SPECS. FOR DETAILS) NON-HARDENING MASTIC SEALANT ALL AROUND (TYPICAL) #20 G.I. SHEET DUCT SLEEVE ALL AROUND REINFORCED DUCT TAPE MASONRY WALL 50mm MAX. 50mm MAX. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 2 3 4 5 6 C D E F G 0.25 0.25 0.25 3.03 0.26 0.10 0.65 1.35 0.61 1.07 0.23 0.75 0.20 0.79 0.15 0.86 1.00 1.00 1.00 1.00 0.69 0.39 1.48 0.97 1.02 0.95 1.16 0.32 0.99 0.66 2.06 3.33 0.48 0.50 0.50 5.00 5.00 3.33 0.24 1.03 0.89 0.16 0.75 0.23 0.72 0.23 0.78 0.24 0.48 0.56 0.94 1.50 0.99 1.01 0.51 1.00 1.00 1.00 1.00 0.69 0.39 1.34 0.25 0.73 0.22 0.85 0.20 0.78 0.16 0.86 2.48 1.50 1.04 0.97 1.33 1.00 1.00 1.00 1.00 0.69 0.39 4.40 5.00 1.60 0.23 0.63 1.18 0.52 1.11 3.45 1.40 0.97 0.15 0.88 0.77 1.10 1.10 1.37 3.45 1.00 1.00 0.58 0.33 0.28 0.74 1.40 1.14 0.15 0.94 0.71 1.20 1.04 1.31 1.00 1.00 0.62 0.37 0.46 0.35 0.41 3.03 FCU-RF.01.1 / 3.0 TR FCU-RF.01.2 / 3.0 TR FCU-RF.02.1 / 2.0 TR FCU-RF.01.3 / 3.0 TR 0.35 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 15.00 m 3600 CFM 13.66 m 3600 CFM 3 3 FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 6.06 m 800 CFM 6.9 m 800 CFM 1 1 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 ROOF FLOOR HVAC PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-05 A.S A.S A.I SCALE 1 : 65 ROOF FLOOR HVAC PLAN 05 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 7. FINISHING TAPE PIPE INSULATION INSULATION OF BOTH LIQUID AND GAS PIPES ELECTRIC CABLE LIQUID PIPE GAS PIPE CUT OFF UNUSED RODS FOR PIPES 200∅ AND OVER SIZE, MM NOMINAL PIPE UP TO 25∅ 2000 20∅ RODS FOR CHILLED WATER AND CONDENSER WATER PIPES 65∅ AND LARGER FOR STEAM SUPPLY, CONDENSATE RETURN VENT RELIEF, BOILER FEED BLOW-DOWN, HOT WATER, AND EXHAUST PIPING INSULATION WHERE SPECIFIED. PIPE SADDLE WELDED TO PIPE 16 GAUGE STEEL SADDLE BY 300 LONG. INSULATION AT BEARING POINT SHALL BE 8 Lbs. MINIMUM DENSITY. FOR ALL PIPES 50∅ AND SMALLER HANGERS IN DIRECT CONTACT WITH COPPER TUBING OR PIPING SHALL BE COPPER PLATED OR PLASTIC COATED. DISTANCE BETWEEN SUPPORTS 32∅-50∅ 3000 65∅-80∅ 3600 100∅-150∅ 4000 200∅-300∅ 4500 350∅ & ABOVE 5000 ROD SIZE (∅MM) 8 10 12 16 20 22 SIZE, MM NOMINAL PIPE UP TO 25∅ 1800 DISTANCE BETWEEN SUPPORTS 32∅-50∅ 2400 65∅-80∅ 3000 ROD SIZE (∅MM) 8 10 10 HARVARD ROLLER BAND NOTE CLEVIS ADJ. ROLL SUPPORT MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING PIPE HANGERS DETAILS SCALE N.T.S REFRIGERANT PIPING CONNECTIONS FOR D-X AIR CONDITIONING UNIT 2. 1. NOTES:- CIRCUIT SYSTEMS. DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR. 3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS. 13 8 7 6 12 7 9 CHARGING CONNECTION EXPANSION VALVE 7 9 8 ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD SIGHT GLASS CONDENSER STOP VALVE DX-COIL COMPRESSOR AIR COOLED CONDENSING UNIT. 1 3 5 6 4 2 Y- STRAINER LIQUID LINE SOLENOID VALVE THERMAL BULB 10 12 13 11 SUCTION LINE (DOUBLE RISER) 14 4 11 10 1 3 2 5 14 2 3 4 5 6 B C D E F G H 7 1 A I 2.64 2.71 0.55 0.62 0.90 0.97 2.68 2.76 1.58 1.65 1.10 1.17 0.40 0.48 1.23 1.30 0.44 0.51 1.04 1.11 1.91 1.98 1.75 1.83 0.78 0.85 0.51 0.58 0.41 0.48 0.85 0.92 0.91 0.99 FCU-BF.02.1 / 3.0 TR FCU-BF.03.3 / 2.5 TR FCU-BF.03.2 / 2.5 TR FCU-BF.04.2 / 2.0 TR FCU-BF.01.1 / 3.5 TR FCU-BF.03.1 / 2.5 TR FCU-BF.04.1 / 2.0 TR W.SU-BF.02.1 / 1.5 TR W.SU-BF.01.1 / 2.0 TR 4.26 4.33 1.79 1.86 VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 BASEMENT FLOOR HVAC PIPING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-06 A.S A.S A.I SCALE 1 : 65 BASEMENT FLOOR HVAC PIPING PLAN 06 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 8. FINISHING TAPE PIPE INSULATION INSULATION OF BOTH LIQUID AND GAS PIPES ELECTRIC CABLE LIQUID PIPE GAS PIPE CUT OFF UNUSED RODS FOR PIPES 200∅ AND OVER SIZE, MM NOMINAL PIPE UP TO 25∅ 2000 20∅ RODS FOR CHILLED WATER AND CONDENSER WATER PIPES 65∅ AND LARGER FOR STEAM SUPPLY, CONDENSATE RETURN VENT RELIEF, BOILER FEED BLOW-DOWN, HOT WATER, AND EXHAUST PIPING INSULATION WHERE SPECIFIED. PIPE SADDLE WELDED TO PIPE 16 GAUGE STEEL SADDLE BY 300 LONG. INSULATION AT BEARING POINT SHALL BE 8 Lbs. MINIMUM DENSITY. FOR ALL PIPES 50∅ AND SMALLER HANGERS IN DIRECT CONTACT WITH COPPER TUBING OR PIPING SHALL BE COPPER PLATED OR PLASTIC COATED. DISTANCE BETWEEN SUPPORTS 32∅-50∅ 3000 65∅-80∅ 3600 100∅-150∅ 4000 200∅-300∅ 4500 350∅ & ABOVE 5000 ROD SIZE (∅MM) 8 10 12 16 20 22 SIZE, MM NOMINAL PIPE UP TO 25∅ 1800 DISTANCE BETWEEN SUPPORTS 32∅-50∅ 2400 65∅-80∅ 3000 ROD SIZE (∅MM) 8 10 10 HARVARD ROLLER BAND NOTE CLEVIS ADJ. ROLL SUPPORT MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING PIPE HANGERS DETAILS SCALE N.T.S REFRIGERANT PIPING CONNECTIONS FOR D-X AIR CONDITIONING UNIT 2. 1. NOTES:- CIRCUIT SYSTEMS. DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR. 3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS. 13 8 7 6 12 7 9 CHARGING CONNECTION EXPANSION VALVE 7 9 8 ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD SIGHT GLASS CONDENSER STOP VALVE DX-COIL COMPRESSOR AIR COOLED CONDENSING UNIT. 1 3 5 6 4 2 Y- STRAINER LIQUID LINE SOLENOID VALVE THERMAL BULB 10 12 13 11 SUCTION LINE (DOUBLE RISER) 14 4 11 10 1 3 2 5 14 2 3 4 5 6 B C D E F G H 7 1 A I 1.71 1.79 1.96 2.04 0.44 0.51 0.84 4.56 4.63 0.36 0.43 0.30 0.37 FCU-GF.03.1 / 2.5 TR FCU-GF.03.1 / 2.5 TR FCU-GF.03.2 / 2.5 TR FCU-GF.01.1 / 3.0 TR W.SU-GF.01.1 / 2.0 TR W.SU-GF.01.2 / 2.0 TR W.SU-BF.02.1 W.SU-GF.01.2 W.SU-GF.01.1 W.SU-BF.01.1 1.99 0.97 1.30 2.20 VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 GROUND FLOOR HVAC PIPING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-07 A.S A.S A.I SCALE 1 : 65 GROUND FLOOR HVAC PIPING PLAN 07 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 9. FINISHING TAPE PIPE INSULATION INSULATION OF BOTH LIQUID AND GAS PIPES ELECTRIC CABLE LIQUID PIPE GAS PIPE CUT OFF UNUSED RODS FOR PIPES 200∅ AND OVER SIZE, MM NOMINAL PIPE UP TO 25∅ 2000 20∅ RODS FOR CHILLED WATER AND CONDENSER WATER PIPES 65∅ AND LARGER FOR STEAM SUPPLY, CONDENSATE RETURN VENT RELIEF, BOILER FEED BLOW-DOWN, HOT WATER, AND EXHAUST PIPING INSULATION WHERE SPECIFIED. PIPE SADDLE WELDED TO PIPE 16 GAUGE STEEL SADDLE BY 300 LONG. INSULATION AT BEARING POINT SHALL BE 8 Lbs. MINIMUM DENSITY. FOR ALL PIPES 50∅ AND SMALLER HANGERS IN DIRECT CONTACT WITH COPPER TUBING OR PIPING SHALL BE COPPER PLATED OR PLASTIC COATED. DISTANCE BETWEEN SUPPORTS 32∅-50∅ 3000 65∅-80∅ 3600 100∅-150∅ 4000 200∅-300∅ 4500 350∅ & ABOVE 5000 ROD SIZE (∅MM) 8 10 12 16 20 22 SIZE, MM NOMINAL PIPE UP TO 25∅ 1800 DISTANCE BETWEEN SUPPORTS 32∅-50∅ 2400 65∅-80∅ 3000 ROD SIZE (∅MM) 8 10 10 HARVARD ROLLER BAND NOTE CLEVIS ADJ. ROLL SUPPORT MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING PIPE HANGERS DETAILS SCALE N.T.S REFRIGERANT PIPING CONNECTIONS FOR D-X AIR CONDITIONING UNIT 2. 1. NOTES:- CIRCUIT SYSTEMS. DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR. 3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS. 13 8 7 6 12 7 9 CHARGING CONNECTION EXPANSION VALVE 7 9 8 ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD SIGHT GLASS CONDENSER STOP VALVE DX-COIL COMPRESSOR AIR COOLED CONDENSING UNIT. 1 3 5 6 4 2 Y- STRAINER LIQUID LINE SOLENOID VALVE THERMAL BULB 10 12 13 11 SUCTION LINE (DOUBLE RISER) 14 4 11 10 1 3 2 5 14 2 3 4 5 B C D E F G A 1.13 1.20 0.31 0.38 0.93 1.01 0.98 1.06 1.19 1.27 0.16 0.23 0.39 0.46 0.51 0.59 0.60 0.67 FCU-1F.02.2 / 3.0 TR FCU-1F.04.1 / 1.5 TR FCU-1F.02.2 / 3.0 TR FCU-1F.03.1 / 2.0 TR FCU-1F.01.2 / 2.5 TR FCU-1F.01.1 / 3.25 TR VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 FIRST FLOOR HVAC PIPING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-08 A.S A.S A.I SCALE 1 : 65 FIRST FLOOR HVAC PIPING PLAN 08 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 10. FINISHING TAPE PIPE INSULATION INSULATION OF BOTH LIQUID AND GAS PIPES ELECTRIC CABLE LIQUID PIPE GAS PIPE CUT OFF UNUSED RODS FOR PIPES 200∅ AND OVER SIZE, MM NOMINAL PIPE UP TO 25∅ 2000 20∅ RODS FOR CHILLED WATER AND CONDENSER WATER PIPES 65∅ AND LARGER FOR STEAM SUPPLY, CONDENSATE RETURN VENT RELIEF, BOILER FEED BLOW-DOWN, HOT WATER, AND EXHAUST PIPING INSULATION WHERE SPECIFIED. PIPE SADDLE WELDED TO PIPE 16 GAUGE STEEL SADDLE BY 300 LONG. INSULATION AT BEARING POINT SHALL BE 8 Lbs. MINIMUM DENSITY. FOR ALL PIPES 50∅ AND SMALLER HANGERS IN DIRECT CONTACT WITH COPPER TUBING OR PIPING SHALL BE COPPER PLATED OR PLASTIC COATED. DISTANCE BETWEEN SUPPORTS 32∅-50∅ 3000 65∅-80∅ 3600 100∅-150∅ 4000 200∅-300∅ 4500 350∅ & ABOVE 5000 ROD SIZE (∅MM) 8 10 12 16 20 22 SIZE, MM NOMINAL PIPE UP TO 25∅ 1800 DISTANCE BETWEEN SUPPORTS 32∅-50∅ 2400 65∅-80∅ 3000 ROD SIZE (∅MM) 8 10 10 HARVARD ROLLER BAND NOTE CLEVIS ADJ. ROLL SUPPORT MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING PIPE HANGERS DETAILS SCALE N.T.S REFRIGERANT PIPING CONNECTIONS FOR D-X AIR CONDITIONING UNIT 2. 1. NOTES:- CIRCUIT SYSTEMS. DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR. 3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS. 13 8 7 6 12 7 9 CHARGING CONNECTION EXPANSION VALVE 7 9 8 ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD SIGHT GLASS CONDENSER STOP VALVE DX-COIL COMPRESSOR AIR COOLED CONDENSING UNIT. 1 3 5 6 4 2 Y- STRAINER LIQUID LINE SOLENOID VALVE THERMAL BULB 10 12 13 11 SUCTION LINE (DOUBLE RISER) 14 4 11 10 1 3 2 5 14 2 3 4 5 6 B C D E F G 0.30 0.38 0.56 0.63 0.83 0.91 1.55 1.62 0.14 0.21 3.91 3.91 0.15 0.22 FCU-2F.01.1 / 3.25 TR FCU-2F.04.2 / 2.0 TR FCU-2F.05.1 / 1.5 TR FCU-1F.03.1 / 2.5 TR FCU-2F.01.2 / 3.25 TR FCU-2F.02.1 / 3.0 TR FCU-2F.04.1 / 2.0 TR 1.11 1.18 1.28 1.35 VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 SECOND FLOOR HVAC PIPING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-09 A.S A.S A.I SCALE 1 : 65 SECOND FLOOR HVAC PIPING PLAN 09 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 11. FINISHING TAPE PIPE INSULATION INSULATION OF BOTH LIQUID AND GAS PIPES ELECTRIC CABLE LIQUID PIPE GAS PIPE CUT OFF UNUSED RODS FOR PIPES 200∅ AND OVER SIZE, MM NOMINAL PIPE UP TO 25∅ 2000 20∅ RODS FOR CHILLED WATER AND CONDENSER WATER PIPES 65∅ AND LARGER FOR STEAM SUPPLY, CONDENSATE RETURN VENT RELIEF, BOILER FEED BLOW-DOWN, HOT WATER, AND EXHAUST PIPING INSULATION WHERE SPECIFIED. PIPE SADDLE WELDED TO PIPE 16 GAUGE STEEL SADDLE BY 300 LONG. INSULATION AT BEARING POINT SHALL BE 8 Lbs. MINIMUM DENSITY. FOR ALL PIPES 50∅ AND SMALLER HANGERS IN DIRECT CONTACT WITH COPPER TUBING OR PIPING SHALL BE COPPER PLATED OR PLASTIC COATED. DISTANCE BETWEEN SUPPORTS 32∅-50∅ 3000 65∅-80∅ 3600 100∅-150∅ 4000 200∅-300∅ 4500 350∅ & ABOVE 5000 ROD SIZE (∅MM) 8 10 12 16 20 22 SIZE, MM NOMINAL PIPE UP TO 25∅ 1800 DISTANCE BETWEEN SUPPORTS 32∅-50∅ 2400 65∅-80∅ 3000 ROD SIZE (∅MM) 8 10 10 HARVARD ROLLER BAND NOTE CLEVIS ADJ. ROLL SUPPORT MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING PIPE HANGERS DETAILS SCALE N.T.S REFRIGERANT PIPING CONNECTIONS FOR D-X AIR CONDITIONING UNIT 2. 1. NOTES:- CIRCUIT SYSTEMS. DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR. 3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS. 13 8 7 6 12 7 9 CHARGING CONNECTION EXPANSION VALVE 7 9 8 ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD SIGHT GLASS CONDENSER STOP VALVE DX-COIL COMPRESSOR AIR COOLED CONDENSING UNIT. 1 3 5 6 4 2 Y- STRAINER LIQUID LINE SOLENOID VALVE THERMAL BULB 10 12 13 11 SUCTION LINE (DOUBLE RISER) 14 4 11 10 1 3 2 5 14 TYPICAL UNIT FOUNDATION DETAIL (NOT TO SCALE) F.F.L 250mm HIGH R.C.C FOUNDATION (BY OTHERS) ABOVE FINISHED ROOF LEVEL WATER PROOFING MEMBRANE ROOF SLAB BETWEEN ROOF SLAB & PLINTH 50mmTHICK POLYURETHANE SHEET 2 5 0 2 3 4 5 6 B C D E F G H 0.41 1.46 1.49 1.90 0.54 1.74 1.81 0.33 0.41 2.11 2.17 0.32 FCU-GF.01.1 FCU-BF.02.1 FCU-RF.01.1 / 3.0 TR FCU-RF.01.2 / 3.0 TR FCU-RF.02.1 / 2.0 TR FCU-RF.01.3 / 3.0 TR 0.29 0.37 VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 ROOF FLOOR HVAC PIPING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-10 A.S A.S A.I SCALE 1 : 65 ROOF FLOOR HVAC PIPING PLAN 10 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 12. FINISHING TAPE PIPE INSULATION INSULATION OF BOTH LIQUID AND GAS PIPES ELECTRIC CABLE LIQUID PIPE GAS PIPE CUT OFF UNUSED RODS FOR PIPES 200∅ AND OVER SIZE, MM NOMINAL PIPE UP TO 25∅ 2000 20∅ RODS FOR CHILLED WATER AND CONDENSER WATER PIPES 65∅ AND LARGER FOR STEAM SUPPLY, CONDENSATE RETURN VENT RELIEF, BOILER FEED BLOW-DOWN, HOT WATER, AND EXHAUST PIPING INSULATION WHERE SPECIFIED. PIPE SADDLE WELDED TO PIPE 16 GAUGE STEEL SADDLE BY 300 LONG. INSULATION AT BEARING POINT SHALL BE 8 Lbs. MINIMUM DENSITY. FOR ALL PIPES 50∅ AND SMALLER HANGERS IN DIRECT CONTACT WITH COPPER TUBING OR PIPING SHALL BE COPPER PLATED OR PLASTIC COATED. DISTANCE BETWEEN SUPPORTS 32∅-50∅ 3000 65∅-80∅ 3600 100∅-150∅ 4000 200∅-300∅ 4500 350∅ & ABOVE 5000 ROD SIZE (∅MM) 8 10 12 16 20 22 SIZE, MM NOMINAL PIPE UP TO 25∅ 1800 DISTANCE BETWEEN SUPPORTS 32∅-50∅ 2400 65∅-80∅ 3000 ROD SIZE (∅MM) 8 10 10 HARVARD ROLLER BAND NOTE CLEVIS ADJ. ROLL SUPPORT MAX. HANGER & SUPPORT SPACING FOR CHILLED WATER PIPING MAX. HANGER & SUPPORT SPACING FOR COPPER PIPING PIPE HANGERS DETAILS SCALE N.T.S REFRIGERANT PIPING CONNECTIONS FOR D-X AIR CONDITIONING UNIT 2. 1. NOTES:- CIRCUIT SYSTEMS. DETAIL SHOWS SINGLE CIRCUIT REFRIGERANT PIPING. DUPLICATE REFRIGERANT PIPING REQUIRED FOR DOUBLE THIS DETAIL ONLY WHEN EVAPORATOR (DX-COIL) IS LOCATED LOWER OR AT SAME LEVEL AS COMPRESSOR. 3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FINALIZING THIS DETAILS IN COORDINATION WITH EQUIPMENT MANUFACTURER RECOMMENDATIONS. 13 8 7 6 12 7 9 CHARGING CONNECTION EXPANSION VALVE 7 9 8 ANGLE TYPE FILTER-DRIER WITH REMOVABLE HEAD SIGHT GLASS CONDENSER STOP VALVE DX-COIL COMPRESSOR AIR COOLED CONDENSING UNIT. 1 3 5 6 4 2 Y- STRAINER LIQUID LINE SOLENOID VALVE THERMAL BULB 10 12 13 11 SUCTION LINE (DOUBLE RISER) 14 4 11 10 1 3 2 5 14 TYPICAL UNIT FOUNDATION DETAIL (NOT TO SCALE) F.F.L 250mm HIGH R.C.C FOUNDATION (BY OTHERS) ABOVE FINISHED ROOF LEVEL WATER PROOFING MEMBRANE ROOF SLAB BETWEEN ROOF SLAB & PLINTH 50mmTHICK POLYURETHANE SHEET 2 5 0 3 4 5 C D E F G FCU-RF.01.2 FCU-1F.02.2 FCU-2F.04.2 FCU-BF.04.1 FCU-1F.02.2 FCU-2F.01.1 FCU-RF.01.1 FCU-1F.04.1 FCU-BF.03.1 FCU-2F.05.1 FCU-1F.01.2 FCU-1F.01.1 FCU-BF.03.2 FCU-RF.01.3 FCU-2F.02.1 EQ EQ EQ EQ FCU-2F.01.2 FCU-BF.03.3 FCU-1F.03.1 FCU-GF.03.2 FCU-BF.04.2 FCU-GF.03.1 FCU-1F.03.1 FCU-RF.02.1 0.40 0.40 0.40 FCU-2F.04.1 FCU-GF.03.1 0.85 FCU-BF.01.1 0.48 0.65 0.72 0.40 0.70 0.70 0.40 0.57 0.85 0.63 VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 TOP ROOF HVAC PIPING PLAN VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-11 A.S A.S A.I SCALE 1 : 65 TOP ROOF HVAC PIPING PLAN 11 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 13. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ 1 : 125 @ A1 00 HVAC 3D VIEW A VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-12 A.S A.S A.I SCALE HVAC 3D VIEW A 12 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 14. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ 1 : 125 @ A1 00 HVAC 3D VIEW B VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-13 A.S A.S A.I SCALE HVAC 3D VIEW B 13 AC 00 28/04/2020 DESIGN - INTENT - 01
  • 15. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 3 F G H I 0.25 0.25 0.25 0.25 0.25 5.06 0.51 0.56 1.63 2.98 1.04 0.57 0.32 1.00 1.00 1.00 0.90 1.42 1.43 1.75 0.17 1.51 1.55 0.22 1.73 1.97 1.13 0.25 4.00 4.00 1.00 1.00 1.00 0.56 0.31 0.68 0.75 1.64 FCU-BF.03.1 / 2.5 TR Size: 450x300 BOD: 3.52m Size: 350x300 BOD: 3.52m Size: 250x250 BOD: 3.55m Size: 200x200 BOD: 3.57m 125 Ф 2.88 1.63 0.98 0.50 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 CALLOUT A VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-14 A.S A.S A.I 00 28/04/2020 DESIGN - INTENT - 01
  • 16. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 2 3 B C D E 1 A FCU-BF.01.1 / 3.5 TR Size: 250x250 BOD: 3.69m Size: 350x300 BOD: 3.66m Size: 500x350 BOD: 3.64m Size: 350x300 BOD: 3.66m Size: 250x250 BOD: 3.69m 200 Ф 200 Ф FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 8.50 m 1400 CFM 7.75 m 1400 CFM 2 2 0.48 5.82 1.50 0.48 0.74 0.44 1.13 1.13 1.13 2.10 0.20 1.60 1.43 1.12 1.20 1.00 1.60 0.45 0.48 1.60 2.61 1.28 0.16 1.90 0.66 1.50 1.14 0.56 1.00 1.00 0.90 0.38 4.00 4.50 3.75 4.00 0.42 0.46 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 CALLOUT B VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-15 A.S A.S A.I 00 28/04/2020 DESIGN - INTENT - 01
  • 17. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 3 C D 3.00 0.35 1.00 1.00 0.61 0.31 1.23 0.88 0.20 0.77 0.21 0.77 0.69 0.45 1.10 1.02 1.55 2.16 3.00 FCU-2F.02.1 / 3.0 TR 200 Ф Size: 250x250 BOD: 2.67m Size: 300x300 BOD: 2.65m Size: 350x350 BOD: 2.62m Size: 350x350 BOD: 2.92m Size: 350x350 BOD: 2.92m FLOW LIN. DIF. TYPE LSD LRD SLOT WIDTH NO. OF SLOT 25 mm 25 mm 3.00 m 1200 CFM 3 m 1200 CFM 3 3 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 CALLOUT D VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-16 A.S A.S A.I 00 28/04/2020 DESIGN - INTENT - 01
  • 18. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 3 E 0.26 0.26 0.26 0.26 1.01 0.79 1.48 1.45 1.06 1.40 1.14 1.49 1.18 1.80 1.20 1.20 1.04 1.04 1.04 1.04 1.04 0.62 0.32 6.25 1.04 6.25 Size: 200x200 BOD: 3.40m Size: 200x200 BOD: 3.40m Size: 300x250 BOD: 3.37m Size: 300x250 BOD: 3.37m FCU-1F.04.1 / 1.5 TR 125 Ф 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 CALLOUT C VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-17 A.S A.S A.I 00 28/04/2020 DESIGN - INTENT - 01
  • 19. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 4 E F G EQ EQ EQ EQ 2.62 2.62 EQ EQ 0.26 0.27 1.17 0.85 0.94 0.15 1.96 FCU-2F.04.2 / 2.0 TR 3.57 125 Ф 125 Ф Size: 200x200 BOD: 3.10m Size: 200x200 BOD: 3.10m Size: 250x250 BOD: 3.08m Size: 250x250 BOD: 3.08m 0.56 0.63 1.10 1.47 1.10 1.46 0.96 0.15 1.83 0.67 0.47 1.01 1.00 1.00 1.00 0.43 3.17 1.09 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 CALLOUT E VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-18 A.S A.S A.I 00 28/04/2020 DESIGN - INTENT - 01
  • 20. VRV COPPER PIPING Y JUNCTION 25mm INSULATED COPPER PIPE SUPPLY FAN COIL UNIT (FCU) RECTANGULAR SYPPLY DUCT DUCT HANGER FLEXIBLE DUCT VOLUME CONTROL DAMPER (VCD) SUPPLY LINEAR DIFFUSER WITH PLENUM (SLD) RETURN LINEAR DIFFUSER (RLD) RECTANGULAR RETURN DUCT CODE DESCRIPTION. 25mm INSULATED COPPER PIPE RETURN 4 C D 0.85 0.96 1.25 FCU-1F.03.1 / 2.5 TR Size: 350x350 BOD: 3.10m QTY. FLOW DIM. (mm) DIF. TYPE SSD SRD 400x400 400x400 1 1000 CFM 1000 CFM 1 1.40 1- ALL DIMENSION ARE IN MILLIMETERS AND LEVELS ARE IN METERS; UNLESS STATED OTHERWISE. 2- NO DIMENSIONS ARE TO BE SCALED OUT FROM THE DRAWING, FIGURED DIMENSIONS SHOULD BE FOLLOW. 3- ALL DIMENSIONS AND LEVELS SHOULD BE CHECKED BEFORE COMMENCEMENT OF CONSTRUCTION WORK AND ANY DISCREPANCY NOTED IN THE DRAWINGS SHOULD IMMEDIATELY BE BROUGHT TO THE ARCHITECT'S NOTICE. DETAILED DESIGN DRAWING PROJECT TITLE: SCALE: CLIENT: LOCATION: DESIGNED BY: DRAWING NO.: CHECKED BY: REVISION SIGNATURE SIGNATURE ARCHITECH: DRAWN BY: ISSUE FOR APPROVAL NOTE: LEGEND: MEP DESIGNER : DESCRIPTION REV. DATE BY ‫ﺍﻟﻭﺻﻑ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬ ‫ﺗﻌﺩﻳﻝ‬ As indicated @ A1 00 CALLOUT F VILLA ABU FETRA KUWAIT CITY, KUWAIT AC-19 A.S A.S A.I 00 28/04/2020 DESIGN - INTENT - 01