Application of Capacitors to Distribution System and Voltage Regulation

Ameen San
Ameen Sanلسا ما اشتغلت
Chapter V
Application of Capacitors to
Distribution System and Voltage
Regulation
POWER FACTOR IMPROVEMENT
Introduction:
• The electrical energy is almost exclusively generated, transmitted and
distributed in the form of alternating current. Therefore, the question of
power factor immediately comes into picture. M
• Most of the loads (e.g. induction motors , arc lamps) are inductive in
nature and hence have low lagging power factor. The low power factor is
highly undesirable as it causes an increase in current, resulting in an
additional losses of active power in all the elements of power system from
power station generator down to the utilization device.
• In order to ensure most favourable conditions for a supply system from
engineering and economical standpoint , it is important to have power
factor as close to unity as possible.
The cosine of angle between voltage and currentin an a.c. circuit is
known as power factor.
Power Triangle
Application of Capacitors to Distribution System and Voltage Regulation
Disadvantages of Low Power Factor
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
Power Factor Improvement
Power Factor Improvement Equipment
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
Calculations of Power Factor correction
Application of Capacitors to Distribution System and Voltage Regulation
Nomogram for calculating Multiplication factor
Problem
A single phase motor connected to 400 V, 50 Hz supply takes 31·7A at a power
factor of 0·7 lagging. Calculate the capacitance required in parallel with the motor
to raise the power factor to 0·9 lagging.
A 3-phase, 5 kW induction motor has a p.f. of 0·75 lagging. A bank of capacitors
is connected in delta across the supply terminals and p.f. raised to 0·9 lagging.
Determine the kVAR rating of the capacitors connected in each phase.
Problem:
The load on an installation is 800 kW, 0·8 lagging p.f. which works for 3000
hours per annum. The tariff is Rs 100 per kVA plus 20 paise per kWh. If the power
factor is improved to 0·9 lagging by means of loss-free capacitors costing Rs 60 per
kVAR, calculate the annual saving effected. Allow 10% per annum for interest and
depreciation on capacitors.
Application of Capacitors to Distribution System and Voltage Regulation
The operating power from distribution system is composed of both active and
reactive elements. The typical daily load curves (reactive and active power) for
a 66kV feeder is given in Fig.
Real and Reactive Power Demand
The reactive power is consumed by overhead lines, transformers
and loads. Its proper generation and control is important for
maintaining the network voltage under normal and abnormal
power system operation and to reduce system losses.
The system voltage collapse due to lack of global control of
reactive power flow during crucial grid has collapsed many times
during the past few years due to lack of reactive power in the
region.
Cost per kVAr of reactive power generation varies between 2 per
cent and 4 per cent of per kW installed regulating controls. The
system should be planned for carrying out suitable proportion of
reactive energy.
Reactive Power Consumption by lines:
•The distribution lines consume reactive power (I2X) depending upon
the series reactance (X) and load current (I). The series reactance of
line is proportional to the conductor self – inductance, which decreases
as the spacing between conductors decreases.
•The minimum spacing is kept such as to prevent flash- over in foul
weather conditions. According to a study of rural area , the average
reactive power consumed by primary HT (11kV) and LT lines for each
transformer at full-load is almost 1 per cent of transformer rating. The
underground cable (11 kV and above) generate reactive power (Ic
2Xc)
depending upon the capacitive reactance (Xc) and charging current (Ic)
at rated voltage.
Reactive Power Consumption by lines:
•Increasing the line voltage at transformer and motors above the rated
voltage will increase the consumption of reactive energy, the extent of
which depends upon their designs. Generally, increase of 10% of the
rated voltage will result in about 20% reduction of power factor.
Reactive Power Consumption by Distribution
Transformers
The reactive power consumption takes place in the series leakage and the
shunt magnetizing reactances. The second component is voltage
dependent, while the first component is proportional to the square of the
transformer current. A completely unloaded transformer would be very
inductive and has a very low power factor. The reactive power used by a
transformer (up to 100 kVA capacity) at full load and at rated voltage is
approximately 7-9 % of the rated power of the transformer. When
unloaded, the amount of reactive power remains between 3 and 4 % of
the rated power.
Reactive Power Consumption by Loads
Loads have varying reactive power requirement. The low power
factor can be a result of the equipment as in case of welders, or it
can result from the operating conditions under which equipment is
used as lightly loaded transformers and lightly loaded induction
motors.
Reactive Power Compensation and Voltage
control
Mainly capacitors are used to develop reactive power near the point of
consumption. For capacitor compensation at load, the user reaps the same
advantage as the power utility for higher power factor on small scale.
Also, if each load is compensated, the power factor remains
relatively constant since in plants, loads are switched on and off and the
dangers of over – compensation do not exist.
Suitable capacitor banks at grid or main sub- station are
desirable to feed reactive requirement of lines, transformers and domestic
consumers, etc., who have no capacitors at terminals.
Over Compensation
At the point of capacitors over-compensation, the voltage
rises and capacitive kVAr will export, i.e. it will flow to
reverse side of the load. Under certain conditions,
dangerously high transient voltage may prevail on the
power lines.
Also, torque surges of over 20 times the motor
rating can be transmitted to the motor shaft under rapid
restart conditions. Over-compensation at consumer
premises is not generally desirable.
Typical capacitor connection at Transformer
The minimum capacitor size can be connected permanently
on secondary terminals, irrespective of load. This is the value
of capacitance required to compensate the no-load
magnetizing kV A of the transformer.
Transformer KVA * % Impedance
Minimum Capacitor in KVAr = _______________________________
200
Typical scheme for automatic control of LT capacitors at
distribution transformers
The minimum number of units required to limit the voltage increase to 10% can
be calculated from the following equation for the grounded star bank.
Where N = Minimum number of parallel units in one series section
S = Number of series sections in each phase.
System Harmonics
With the increasing use of rectifiers, thyristor control
shunt capacitors, etc. the harmonic generation can create
problems with sensitive electronic equipment which can lead
to errors in the protective gear, metering and control systems
and also overload the capacitor banks besides causing
resonance.
Reactors are sometimes needed to reduce the total current
drawn by the capacitor banks if unduly large harmonics are
present in the system voltage.
The causes of harmonics in the power system
• Over-excited
transformers
• Mercury rectifiers and
thyristors
• Arc furnaces
• Slot harmonics of rotary
machine
• Corona loss
• Large motors running at
low slip, fluorescent
lighting , T.V. and radio
equipment
• System switching and
load chocking
Inrush Currents
When the capacitor banks are connected parallel to the
supply, the initial charging current is said be inrush current. The
inrush current can be reduced by connecting the series damping
reacors.
In the case of single capacitor bank, the damping reactor
is not normally required from the consideration of inrush currents
at the time of switching.
The system reactance including the transformer to
which the capacitor bank is installed is adequate enough to bring
down the value of inrush currents with in safe limit of the capacitor
or switchgear.
Even otherwise the duration of inrush current is so small
, of the order of few cycles only, that their effect can be ignored.
When a number of capacitor banks are used in parallel, it may
become necessary to use series reactors for limiting the inrush
currents.
Assuming the severest condition of switching , the value of damping reactors in
henries is given by
The maximum peak inrush current can be approximately given by the
formula
Where,
Ic1 = capacitor’s rated current (fundamental wave) rms
Xc1 = capacitor reactance (fundamental wave)
Xl1 = total inductive reactance of the system including capacitor bank
(fundamental wave)
Application of Capacitors to Distribution System and Voltage Regulation
In case of parallel banks, which are already energized, the
inrush current is predominantly governed by the
momentary discharge from the energized banks and since
the impedance between the energized capacitor bank and
the capacitor bank to be energized may be small, it may
result in high peak inrush current. The maximum peak
current is given by the expression
C= equivalent capacitance of the circuit in H
L= equivalent series inductance between the
energized banks and bank to be energized in H
En1 = line to neutral voltage
Example
Two 11 kV capacitors banks, each of 2.5 MVAr, are installed in
parallel at a 132/11 kV sub-station. Calculate the value of the series
damping reactor with each capacitor bank
Solution
Load Utilized Voltage
10 kW 230 V
10-50 kW 415/230 V
50 kW-5 MW 11 kV
5 MW-30 MW 33-66 kV
30 MW-50MW 132 kV
Above 50 MW 220 kV
Different Consumers Voltage Standards
Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
Methods of Voltage Control
Importance Of Voltage Control
When the load on the supply system changes, the
voltage at the consumers' terminals also changes.
The variations of voltage at the consumer's
terminals are undesirable and must be kept within
prescribed limits for the following reasons :
(i) In case of lighting load, the lamp characteristics are very
sensitive to changes of voltage. For instance, if the supply voltagip
to an incandescent lamp decreases by 6% of rated value, then
illuminating power may decrease by 20%. On the other hand, if
the supply voltage is 6% above the rated value, the life of the
lamp may be reduced by 50% due to the rapid deterioration of
the filament.
(ii) In case of power load consisting of induction motors,
the voltage variations may cause erratic operation. If the supply
voltage is above the normal, the motor may operate with a
saturated magnetic circuit, with consequent large magnetising
current, heating and low power factor. On the other hand, if the
voltage is too low, it will reduce the starting torque of the motor
considerably.
(iii) Too wide variations of voltage cause excessive heating of
distribution transformers. This may reduce their ratings to a
considerable extent.
It is clear from the above discussion that voltage variations in a
power system must be kept to minimum level in order to deliver
good service to the consumers. With the trend towards larger
and larger interconnected system, it has become necessary to
employ appropriate methods of voltage control.
Methods Of Voltage Control
There are several methods of voltage control. In each method,
the system voltage is changed in accordance with the load to
obtain a fairly constant voltage at the consumer's end of the
system. The following are the methods of voltage control in an
a.c. power system:
(i) By excitation control
(ii) By using tap changing transformers
(iii) Auto-transformer tap changing
(iv) Booster Transformers
(v) Induction Regulators
(vi) By Synchronous Condensors
Method (i) is used at the generating station only whereas methods
(ii) to (v) can be used for transmission as well as primary
distribution systems. However, method
Tap-Changing Transformers
Off load tap-changing transformer
Application of Capacitors to Distribution System and Voltage Regulation
Figure shows the arrangement where a number of tappings
have been provided on the secondary. As the position of the
tap is varied, the effective number of secondary turns is varied
and hence the output voltage of the secondary can he
changed.
Thus referring to Fig. when the movable arm makes contact
with stud 1, the secondary voltage is minimum and when
with stud 5, it is maximum. During the period of light load,
the voltage across the primary is not much below the
alternator voltage and the movable arm is placed on stud 1.
When the load increases,
the voltage across the primary drops, but the secondary
voltage can be kept at the previous value by placing the
movable arm on to a higher stud. Whenever a tapping is to be
changed in this type of transformer, the load is kept off and
hence the name off load tap. changing transformer
Application of Capacitors to Distribution System and Voltage Regulation
ON load tap-changing transformer
1 von 58

Recomendados

Ppt of ehv ac transmission von
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmissionSumit Kumar
68.4K views15 Folien
Unit 03 Protective relays von
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
13.8K views73 Folien
Load flow study von
Load flow studyLoad flow study
Load flow studyHozefa Jinya
22.6K views18 Folien
Power quality von
Power qualityPower quality
Power qualityBadar Aaqili
939 views51 Folien
Transient in Power system von
Transient in Power systemTransient in Power system
Transient in Power systemPreet_patel
10.4K views54 Folien
Loading Capability Limits of Transmission Lines von
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesRaja Adapa
4.1K views10 Folien

Más contenido relacionado

Was ist angesagt?

Economic operation of Power systems by Unit commitment von
Economic operation of Power systems by Unit commitment Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment Pritesh Priyadarshi
15.5K views15 Folien
Firing angle control von
Firing angle controlFiring angle control
Firing angle controljawaharramaya
8.9K views12 Folien
Power System Control And Line Compensation von
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line CompensationAnakin Akshat Assal
6.4K views31 Folien
Power flow analysis von
Power flow analysisPower flow analysis
Power flow analysisRevathi Subramaniam
6.2K views18 Folien
Instrument transformer CT & PT von
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PTChandan Singh
16.6K views19 Folien
power flow and optimal power flow von
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flowAhmed M. Elkholy
4.7K views15 Folien

Was ist angesagt?(20)

Economic operation of Power systems by Unit commitment von Pritesh Priyadarshi
Economic operation of Power systems by Unit commitment Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment
Pritesh Priyadarshi15.5K views
Instrument transformer CT & PT von Chandan Singh
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
Chandan Singh16.6K views
Extra high voltage long ac transmission lines von Shivagee Raj
Extra high voltage long ac transmission linesExtra high voltage long ac transmission lines
Extra high voltage long ac transmission lines
Shivagee Raj12.1K views
POWER QUALITY IMPROVEMENT von Uday Wankar
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENT
Uday Wankar33.5K views
Facts controller von Debayon Saha
Facts controllerFacts controller
Facts controller
Debayon Saha13.9K views
Tcsc ppt von Prabhu R
Tcsc pptTcsc ppt
Tcsc ppt
Prabhu R22.4K views
Voltage and Frequency Control of the Grid von Leonardo ENERGY
Voltage and Frequency Control of the GridVoltage and Frequency Control of the Grid
Voltage and Frequency Control of the Grid
Leonardo ENERGY9K views
Differential Protection Relay von kishore kish
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
kishore kish8.3K views

Destacado

capacitors von
capacitorscapacitors
capacitorsVincent Wedelich, PE MBA
7.2K views168 Folien
Distribution System Voltage Drop and Power Loss Calculation von
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss CalculationAmeen San
45.3K views53 Folien
ELECTRICAL DISTRIBUTION TECHNOLOGY von
ELECTRICAL DISTRIBUTION TECHNOLOGYELECTRICAL DISTRIBUTION TECHNOLOGY
ELECTRICAL DISTRIBUTION TECHNOLOGYAmeen San
6.4K views26 Folien
Automation of capacitor banks based on MVAR Requirement von
Automation of capacitor banks based on MVAR RequirementAutomation of capacitor banks based on MVAR Requirement
Automation of capacitor banks based on MVAR RequirementAhmed Aslam
7.9K views67 Folien
Load Characteristics von
Load CharacteristicsLoad Characteristics
Load CharacteristicsAmeen San
21.2K views38 Folien
automatic power factor controller von
automatic power factor controllerautomatic power factor controller
automatic power factor controllersingh1515
34.7K views37 Folien

Destacado(20)

Distribution System Voltage Drop and Power Loss Calculation von Ameen San
Distribution System Voltage Drop and Power Loss CalculationDistribution System Voltage Drop and Power Loss Calculation
Distribution System Voltage Drop and Power Loss Calculation
Ameen San45.3K views
ELECTRICAL DISTRIBUTION TECHNOLOGY von Ameen San
ELECTRICAL DISTRIBUTION TECHNOLOGYELECTRICAL DISTRIBUTION TECHNOLOGY
ELECTRICAL DISTRIBUTION TECHNOLOGY
Ameen San6.4K views
Automation of capacitor banks based on MVAR Requirement von Ahmed Aslam
Automation of capacitor banks based on MVAR RequirementAutomation of capacitor banks based on MVAR Requirement
Automation of capacitor banks based on MVAR Requirement
Ahmed Aslam7.9K views
Load Characteristics von Ameen San
Load CharacteristicsLoad Characteristics
Load Characteristics
Ameen San21.2K views
automatic power factor controller von singh1515
automatic power factor controllerautomatic power factor controller
automatic power factor controller
singh151534.7K views
Distribution systems von SURAJ PRASAD
Distribution systemsDistribution systems
Distribution systems
SURAJ PRASAD59.5K views
Stepper motor von Ameen San
Stepper motor Stepper motor
Stepper motor
Ameen San1K views
PLC arithmatic functions von Ameen San
PLC arithmatic functionsPLC arithmatic functions
PLC arithmatic functions
Ameen San5.2K views
PLC application von Ameen San
PLC applicationPLC application
PLC application
Ameen San1.1K views
PLC data types and addressing von Ameen San
PLC data types and addressingPLC data types and addressing
PLC data types and addressing
Ameen San37.4K views
Plc analog input output programming von Engr Alam
Plc analog input output programmingPlc analog input output programming
Plc analog input output programming
Engr Alam9.5K views
Capacitor bank and improvement of power factor von Ahshan Kabir
Capacitor bank and improvement of power factorCapacitor bank and improvement of power factor
Capacitor bank and improvement of power factor
Ahshan Kabir7.5K views
PLC Traffic Light Control von Ameen San
PLC Traffic Light ControlPLC Traffic Light Control
PLC Traffic Light Control
Ameen San17.5K views
Engineering Economy von Ameen San
Engineering EconomyEngineering Economy
Engineering Economy
Ameen San58.1K views
PLC input and output devices von Ameen San
PLC input and output devices PLC input and output devices
PLC input and output devices
Ameen San31.9K views
Electricity distribution system in india von Jasgt Singh
Electricity distribution system in indiaElectricity distribution system in india
Electricity distribution system in india
Jasgt Singh50.7K views
Accounting & financial decisions von Ameen San
Accounting & financial decisionsAccounting & financial decisions
Accounting & financial decisions
Ameen San722 views

Similar a Application of Capacitors to Distribution System and Voltage Regulation

Reactive power consumption in modern power system von
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power systemRahuldey1991
35.5K views30 Folien
Power factor improvement von
Power factor improvementPower factor improvement
Power factor improvementharshal567
4K views17 Folien
Synchronous condensers von
Synchronous condensersSynchronous condensers
Synchronous condensersujvnl
7.3K views15 Folien
power-factor-correction.pptx von
power-factor-correction.pptxpower-factor-correction.pptx
power-factor-correction.pptxBabySweet5
17 views29 Folien
STATCOM von
STATCOMSTATCOM
STATCOMTribhuvan University
677 views29 Folien

Similar a Application of Capacitors to Distribution System and Voltage Regulation(20)

Reactive power consumption in modern power system von Rahuldey1991
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power system
Rahuldey199135.5K views
Power factor improvement von harshal567
Power factor improvementPower factor improvement
Power factor improvement
harshal5674K views
Synchronous condensers von ujvnl
Synchronous condensersSynchronous condensers
Synchronous condensers
ujvnl7.3K views
power-factor-correction.pptx von BabySweet5
power-factor-correction.pptxpower-factor-correction.pptx
power-factor-correction.pptx
BabySweet517 views
power factor correction soham+niraj von soham patel
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
soham patel1.3K views
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact... von IRJET Journal
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET Journal259 views
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area von ijceronline
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
ijceronline34 views
COMPENSATION OF REACTIVE POWER von ST Chowhury
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWER
ST Chowhury233 views
Reactive power management and voltage control by using statcom von Hussain Ali
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
Hussain Ali3.6K views
Power Factor von Tim Cohen
Power FactorPower Factor
Power Factor
Tim Cohen18.8K views
Reactivepowercompensation 140401183847-phpapp01 (6) von REVANTH CHINTU
Reactivepowercompensation 140401183847-phpapp01 (6)Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)
REVANTH CHINTU346 views

Más de Ameen San

PLC Timers von
PLC TimersPLC Timers
PLC TimersAmeen San
1.5K views13 Folien
PLC Internal Relays von
PLC Internal RelaysPLC Internal Relays
PLC Internal RelaysAmeen San
6.6K views4 Folien
PLC Intro to programming von
PLC Intro to programmingPLC Intro to programming
PLC Intro to programmingAmeen San
804 views8 Folien
PLC Logic Circuits von
PLC Logic CircuitsPLC Logic Circuits
PLC Logic CircuitsAmeen San
3.9K views13 Folien
PLC Applications von
PLC ApplicationsPLC Applications
PLC ApplicationsAmeen San
728 views5 Folien
Protection Devices and the Lightning von
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
8K views54 Folien

Más de Ameen San(18)

PLC Timers von Ameen San
PLC TimersPLC Timers
PLC Timers
Ameen San1.5K views
PLC Internal Relays von Ameen San
PLC Internal RelaysPLC Internal Relays
PLC Internal Relays
Ameen San6.6K views
PLC Intro to programming von Ameen San
PLC Intro to programmingPLC Intro to programming
PLC Intro to programming
Ameen San804 views
PLC Logic Circuits von Ameen San
PLC Logic CircuitsPLC Logic Circuits
PLC Logic Circuits
Ameen San3.9K views
PLC Applications von Ameen San
PLC ApplicationsPLC Applications
PLC Applications
Ameen San728 views
Protection Devices and the Lightning von Ameen San
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
Ameen San8K views
Protection von Ameen San
ProtectionProtection
Protection
Ameen San1.3K views
Relays von Ameen San
RelaysRelays
Relays
Ameen San20.6K views
Circuit Breakers von Ameen San
Circuit BreakersCircuit Breakers
Circuit Breakers
Ameen San5.5K views
Ratio analysis von Ameen San
Ratio  analysisRatio  analysis
Ratio analysis
Ameen San1.4K views
Depreciation methods von Ameen San
Depreciation methodsDepreciation methods
Depreciation methods
Ameen San7.6K views
Income statement von Ameen San
Income statementIncome statement
Income statement
Ameen San531 views
Capital budgeting von Ameen San
Capital budgetingCapital budgeting
Capital budgeting
Ameen San1.2K views
Time value of money von Ameen San
Time value of moneyTime value of money
Time value of money
Ameen San2.6K views
Cash flow statement von Ameen San
Cash flow statementCash flow statement
Cash flow statement
Ameen San1.5K views
Forms of business organizations von Ameen San
Forms of business organizationsForms of business organizations
Forms of business organizations
Ameen San2.3K views
مهارات الحوار والاقناع von Ameen San
مهارات الحوار والاقناعمهارات الحوار والاقناع
مهارات الحوار والاقناع
Ameen San9.2K views
Matlab solving rlc circuit von Ameen San
Matlab solving rlc circuitMatlab solving rlc circuit
Matlab solving rlc circuit
Ameen San26.3K views

Último

Créativité dans le design mécanique à l’aide de l’optimisation topologique von
Créativité dans le design mécanique à l’aide de l’optimisation topologiqueCréativité dans le design mécanique à l’aide de l’optimisation topologique
Créativité dans le design mécanique à l’aide de l’optimisation topologiqueLIEGE CREATIVE
8 views84 Folien
Integrating Sustainable Development Goals (SDGs) in School Education von
Integrating Sustainable Development Goals (SDGs) in School EducationIntegrating Sustainable Development Goals (SDGs) in School Education
Integrating Sustainable Development Goals (SDGs) in School EducationSheetalTank1
11 views29 Folien
Plant Design Report-Oil Refinery.pdf von
Plant Design Report-Oil Refinery.pdfPlant Design Report-Oil Refinery.pdf
Plant Design Report-Oil Refinery.pdfSafeen Yaseen Ja'far
9 views10 Folien
Proposal Presentation.pptx von
Proposal Presentation.pptxProposal Presentation.pptx
Proposal Presentation.pptxkeytonallamon
76 views36 Folien
Unlocking Research Visibility.pdf von
Unlocking Research Visibility.pdfUnlocking Research Visibility.pdf
Unlocking Research Visibility.pdfKhatirNaima
11 views19 Folien
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx von
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptxlwang78
188 views19 Folien

Último(20)

Créativité dans le design mécanique à l’aide de l’optimisation topologique von LIEGE CREATIVE
Créativité dans le design mécanique à l’aide de l’optimisation topologiqueCréativité dans le design mécanique à l’aide de l’optimisation topologique
Créativité dans le design mécanique à l’aide de l’optimisation topologique
LIEGE CREATIVE8 views
Integrating Sustainable Development Goals (SDGs) in School Education von SheetalTank1
Integrating Sustainable Development Goals (SDGs) in School EducationIntegrating Sustainable Development Goals (SDGs) in School Education
Integrating Sustainable Development Goals (SDGs) in School Education
SheetalTank111 views
Unlocking Research Visibility.pdf von KhatirNaima
Unlocking Research Visibility.pdfUnlocking Research Visibility.pdf
Unlocking Research Visibility.pdf
KhatirNaima11 views
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx von lwang78
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx
2023Dec ASU Wang NETR Group Research Focus and Facility Overview.pptx
lwang78188 views
GDSC Mikroskil Members Onboarding 2023.pdf von gdscmikroskil
GDSC Mikroskil Members Onboarding 2023.pdfGDSC Mikroskil Members Onboarding 2023.pdf
GDSC Mikroskil Members Onboarding 2023.pdf
gdscmikroskil68 views
MongoDB.pdf von ArthyR3
MongoDB.pdfMongoDB.pdf
MongoDB.pdf
ArthyR351 views
REACTJS.pdf von ArthyR3
REACTJS.pdfREACTJS.pdf
REACTJS.pdf
ArthyR337 views
Design of machine elements-UNIT 3.pptx von gopinathcreddy
Design of machine elements-UNIT 3.pptxDesign of machine elements-UNIT 3.pptx
Design of machine elements-UNIT 3.pptx
gopinathcreddy38 views
Ansari: Practical experiences with an LLM-based Islamic Assistant von M Waleed Kadous
Ansari: Practical experiences with an LLM-based Islamic AssistantAnsari: Practical experiences with an LLM-based Islamic Assistant
Ansari: Practical experiences with an LLM-based Islamic Assistant
M Waleed Kadous11 views
Design_Discover_Develop_Campaign.pptx von ShivanshSeth6
Design_Discover_Develop_Campaign.pptxDesign_Discover_Develop_Campaign.pptx
Design_Discover_Develop_Campaign.pptx
ShivanshSeth655 views
Web Dev Session 1.pptx von VedVekhande
Web Dev Session 1.pptxWeb Dev Session 1.pptx
Web Dev Session 1.pptx
VedVekhande20 views
Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc... von csegroupvn
Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc...Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc...
Design of Structures and Foundations for Vibrating Machines, Arya-ONeill-Pinc...
csegroupvn13 views

Application of Capacitors to Distribution System and Voltage Regulation

  • 1. Chapter V Application of Capacitors to Distribution System and Voltage Regulation
  • 2. POWER FACTOR IMPROVEMENT Introduction: • The electrical energy is almost exclusively generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor immediately comes into picture. M • Most of the loads (e.g. induction motors , arc lamps) are inductive in nature and hence have low lagging power factor. The low power factor is highly undesirable as it causes an increase in current, resulting in an additional losses of active power in all the elements of power system from power station generator down to the utilization device. • In order to ensure most favourable conditions for a supply system from engineering and economical standpoint , it is important to have power factor as close to unity as possible.
  • 3. The cosine of angle between voltage and currentin an a.c. circuit is known as power factor.
  • 6. Disadvantages of Low Power Factor
  • 13. Calculations of Power Factor correction
  • 15. Nomogram for calculating Multiplication factor
  • 16. Problem A single phase motor connected to 400 V, 50 Hz supply takes 31·7A at a power factor of 0·7 lagging. Calculate the capacitance required in parallel with the motor to raise the power factor to 0·9 lagging.
  • 17. A 3-phase, 5 kW induction motor has a p.f. of 0·75 lagging. A bank of capacitors is connected in delta across the supply terminals and p.f. raised to 0·9 lagging. Determine the kVAR rating of the capacitors connected in each phase.
  • 18. Problem: The load on an installation is 800 kW, 0·8 lagging p.f. which works for 3000 hours per annum. The tariff is Rs 100 per kVA plus 20 paise per kWh. If the power factor is improved to 0·9 lagging by means of loss-free capacitors costing Rs 60 per kVAR, calculate the annual saving effected. Allow 10% per annum for interest and depreciation on capacitors.
  • 20. The operating power from distribution system is composed of both active and reactive elements. The typical daily load curves (reactive and active power) for a 66kV feeder is given in Fig. Real and Reactive Power Demand
  • 21. The reactive power is consumed by overhead lines, transformers and loads. Its proper generation and control is important for maintaining the network voltage under normal and abnormal power system operation and to reduce system losses. The system voltage collapse due to lack of global control of reactive power flow during crucial grid has collapsed many times during the past few years due to lack of reactive power in the region. Cost per kVAr of reactive power generation varies between 2 per cent and 4 per cent of per kW installed regulating controls. The system should be planned for carrying out suitable proportion of reactive energy.
  • 22. Reactive Power Consumption by lines: •The distribution lines consume reactive power (I2X) depending upon the series reactance (X) and load current (I). The series reactance of line is proportional to the conductor self – inductance, which decreases as the spacing between conductors decreases. •The minimum spacing is kept such as to prevent flash- over in foul weather conditions. According to a study of rural area , the average reactive power consumed by primary HT (11kV) and LT lines for each transformer at full-load is almost 1 per cent of transformer rating. The underground cable (11 kV and above) generate reactive power (Ic 2Xc) depending upon the capacitive reactance (Xc) and charging current (Ic) at rated voltage.
  • 23. Reactive Power Consumption by lines: •Increasing the line voltage at transformer and motors above the rated voltage will increase the consumption of reactive energy, the extent of which depends upon their designs. Generally, increase of 10% of the rated voltage will result in about 20% reduction of power factor.
  • 24. Reactive Power Consumption by Distribution Transformers The reactive power consumption takes place in the series leakage and the shunt magnetizing reactances. The second component is voltage dependent, while the first component is proportional to the square of the transformer current. A completely unloaded transformer would be very inductive and has a very low power factor. The reactive power used by a transformer (up to 100 kVA capacity) at full load and at rated voltage is approximately 7-9 % of the rated power of the transformer. When unloaded, the amount of reactive power remains between 3 and 4 % of the rated power.
  • 25. Reactive Power Consumption by Loads Loads have varying reactive power requirement. The low power factor can be a result of the equipment as in case of welders, or it can result from the operating conditions under which equipment is used as lightly loaded transformers and lightly loaded induction motors.
  • 26. Reactive Power Compensation and Voltage control Mainly capacitors are used to develop reactive power near the point of consumption. For capacitor compensation at load, the user reaps the same advantage as the power utility for higher power factor on small scale. Also, if each load is compensated, the power factor remains relatively constant since in plants, loads are switched on and off and the dangers of over – compensation do not exist. Suitable capacitor banks at grid or main sub- station are desirable to feed reactive requirement of lines, transformers and domestic consumers, etc., who have no capacitors at terminals.
  • 27. Over Compensation At the point of capacitors over-compensation, the voltage rises and capacitive kVAr will export, i.e. it will flow to reverse side of the load. Under certain conditions, dangerously high transient voltage may prevail on the power lines. Also, torque surges of over 20 times the motor rating can be transmitted to the motor shaft under rapid restart conditions. Over-compensation at consumer premises is not generally desirable.
  • 29. The minimum capacitor size can be connected permanently on secondary terminals, irrespective of load. This is the value of capacitance required to compensate the no-load magnetizing kV A of the transformer. Transformer KVA * % Impedance Minimum Capacitor in KVAr = _______________________________ 200
  • 30. Typical scheme for automatic control of LT capacitors at distribution transformers
  • 31. The minimum number of units required to limit the voltage increase to 10% can be calculated from the following equation for the grounded star bank. Where N = Minimum number of parallel units in one series section S = Number of series sections in each phase.
  • 32. System Harmonics With the increasing use of rectifiers, thyristor control shunt capacitors, etc. the harmonic generation can create problems with sensitive electronic equipment which can lead to errors in the protective gear, metering and control systems and also overload the capacitor banks besides causing resonance. Reactors are sometimes needed to reduce the total current drawn by the capacitor banks if unduly large harmonics are present in the system voltage.
  • 33. The causes of harmonics in the power system • Over-excited transformers • Mercury rectifiers and thyristors • Arc furnaces • Slot harmonics of rotary machine • Corona loss • Large motors running at low slip, fluorescent lighting , T.V. and radio equipment • System switching and load chocking
  • 34. Inrush Currents When the capacitor banks are connected parallel to the supply, the initial charging current is said be inrush current. The inrush current can be reduced by connecting the series damping reacors. In the case of single capacitor bank, the damping reactor is not normally required from the consideration of inrush currents at the time of switching. The system reactance including the transformer to which the capacitor bank is installed is adequate enough to bring down the value of inrush currents with in safe limit of the capacitor or switchgear. Even otherwise the duration of inrush current is so small , of the order of few cycles only, that their effect can be ignored. When a number of capacitor banks are used in parallel, it may become necessary to use series reactors for limiting the inrush currents.
  • 35. Assuming the severest condition of switching , the value of damping reactors in henries is given by
  • 36. The maximum peak inrush current can be approximately given by the formula Where, Ic1 = capacitor’s rated current (fundamental wave) rms Xc1 = capacitor reactance (fundamental wave) Xl1 = total inductive reactance of the system including capacitor bank (fundamental wave)
  • 38. In case of parallel banks, which are already energized, the inrush current is predominantly governed by the momentary discharge from the energized banks and since the impedance between the energized capacitor bank and the capacitor bank to be energized may be small, it may result in high peak inrush current. The maximum peak current is given by the expression C= equivalent capacitance of the circuit in H L= equivalent series inductance between the energized banks and bank to be energized in H En1 = line to neutral voltage
  • 39. Example Two 11 kV capacitors banks, each of 2.5 MVAr, are installed in parallel at a 132/11 kV sub-station. Calculate the value of the series damping reactor with each capacitor bank
  • 41. Load Utilized Voltage 10 kW 230 V 10-50 kW 415/230 V 50 kW-5 MW 11 kV 5 MW-30 MW 33-66 kV 30 MW-50MW 132 kV Above 50 MW 220 kV Different Consumers Voltage Standards
  • 45. Importance Of Voltage Control When the load on the supply system changes, the voltage at the consumers' terminals also changes. The variations of voltage at the consumer's terminals are undesirable and must be kept within prescribed limits for the following reasons :
  • 46. (i) In case of lighting load, the lamp characteristics are very sensitive to changes of voltage. For instance, if the supply voltagip to an incandescent lamp decreases by 6% of rated value, then illuminating power may decrease by 20%. On the other hand, if the supply voltage is 6% above the rated value, the life of the lamp may be reduced by 50% due to the rapid deterioration of the filament.
  • 47. (ii) In case of power load consisting of induction motors, the voltage variations may cause erratic operation. If the supply voltage is above the normal, the motor may operate with a saturated magnetic circuit, with consequent large magnetising current, heating and low power factor. On the other hand, if the voltage is too low, it will reduce the starting torque of the motor considerably.
  • 48. (iii) Too wide variations of voltage cause excessive heating of distribution transformers. This may reduce their ratings to a considerable extent.
  • 49. It is clear from the above discussion that voltage variations in a power system must be kept to minimum level in order to deliver good service to the consumers. With the trend towards larger and larger interconnected system, it has become necessary to employ appropriate methods of voltage control.
  • 50. Methods Of Voltage Control There are several methods of voltage control. In each method, the system voltage is changed in accordance with the load to obtain a fairly constant voltage at the consumer's end of the system. The following are the methods of voltage control in an a.c. power system: (i) By excitation control (ii) By using tap changing transformers (iii) Auto-transformer tap changing (iv) Booster Transformers (v) Induction Regulators (vi) By Synchronous Condensors
  • 51. Method (i) is used at the generating station only whereas methods (ii) to (v) can be used for transmission as well as primary distribution systems. However, method
  • 52. Tap-Changing Transformers Off load tap-changing transformer
  • 54. Figure shows the arrangement where a number of tappings have been provided on the secondary. As the position of the tap is varied, the effective number of secondary turns is varied and hence the output voltage of the secondary can he changed.
  • 55. Thus referring to Fig. when the movable arm makes contact with stud 1, the secondary voltage is minimum and when with stud 5, it is maximum. During the period of light load, the voltage across the primary is not much below the alternator voltage and the movable arm is placed on stud 1. When the load increases,
  • 56. the voltage across the primary drops, but the secondary voltage can be kept at the previous value by placing the movable arm on to a higher stud. Whenever a tapping is to be changed in this type of transformer, the load is kept off and hence the name off load tap. changing transformer
  • 58. ON load tap-changing transformer