NREL’s Research Support Facility:
Plug Load Efficiency Strategies in
Meeting Net Zero Energy Goals
Shanti Pless, LEED AP
Senior Research Engineer
NREL Commercial Buildings
Research Group
January 29, 2013
Innovation for Our Energy Future
Innovation for Our Energy Future
http://www.nrel.gov/docs/fy11osti/51199.pdf
2
Innovation for Our Energy Future3
NREL: 2006
Used with Permission from Haselden
Innovation for Our Energy Future4
Research Support Facility Vision
• A showcase for sustainable, high-performance design
o Incorporates the best in energy efficiency, environmental performance,
and advanced controls using a “whole-building” integrated design
process
• Serves as a model for cost-competitive, high-performance
commercial buildings for the nation’s design construction,
operation, and financing communities
Credit: RNL
Innovation for Our Energy Future5
NREL: Today
Used with Permission from Haselden
Innovation for Our Energy Future
• More than 800 people in DOE office space on NREL’s campus
• 220,000 ft2
• Design/build process with
required energy goals
• 25 kBtu/ft2
• 50% energy savings
• LEED Platinum
• Replicable
• Process
• Technologies
• Cost
• Site, source, carbon, cost ZEB:B
• Includes plugs loads and datacenter
• Firm fixed price of ~$64 million
• $259/ft2 construction cost (not including $27/ft2 for PV from PPA/ARRA)
• Open first phase June 10, 2010
DOE/NREL Research Support Facility:
Project Goals
Credit:HaseldenConstruction
Innovation for Our Energy Future
Energy Efficiency Design Requirements
7
• 25 kBtu/ft2/yr for standard office space occupant density and data center
loads
• Demand side energy use goal, not including renewables
• Normalized up to 35.1 kBtu/ft2/yr for better space efficiency and to account for full data
center load
• On site renewables sized to offset site energy use to reach net zero annual
use
Credit:ChadLobato/NREL
0
20
40
60
80
100
120
140
Old NREL/DOE
Leased Office
Building
Typical Denver
Office Building
ENERGY STAR 75
Office Building
Average LEED
Office Building
ENERGY STAR 90
Office Building
EPA Region 8
Office
Denver, CO
RSF RSF Renewable
Production
AnnualEUI(kBtu/ft2)
Site Mounted PV
Roof Mounted PV
Data Center
Whole Building
References:
https://www.energystar.gov/index.cfm?c=new_bldg_design.bus_target_finder
http://eere.buildinggreen.com/mtxview.cfm?CFID=46438782&CFTOKEN=31996638
http://femp.buildinggreen.com/overview.cfm?ProjectID=864
Innovation for Our Energy Future8
Key Design Strategies
• Optimal orientation and office space layout
• Fully daylit office wings with high-
performance electrical lighting
• Continuous insulation precast wall panels
with thermal mass
• Operable windows for natural ventilation
• Radiant heating and cooling
• Outdoor air preheating
o Transpired solar collector
o Data Center waste heat
o Exhaust air heat recovery
o Crawl space thermal storage
• Aggressive plug load control strategies
• Data Center outdoor air economizer with
hot aisle containment
• Roof top- and parking lot-based PV
Innovation for Our Energy Future9
•100% of the workstations
are daylit
•No employee more than 30
feet from a window
Daylighting
Innovation for Our Energy Future
Daylighting: Glare Control
A light redirecting
device reflects
sunlight to the
ceiling, creating an
indirect lighting
effect.
Fixed sunshades
limit excess light and
glare.
Credit: RNL
Innovation for Our Energy Future11
Reclaimed natural
gas piping serves
as support for the
building.
The lobby and other
common areas feature
beetle-kill pine from
Western forests.
Daylighting reduces
the need for the use of
electrical lighting.
LEED Platinum
rating, version
2.2 – 59 points.
Innovation for Our Energy Future
Energy Modeling
End Use kBtu/ft2
Space Heating 8.58
Space Cooling 0.85
Pumps 0.48
Ventilation Fans 1.88
Domestic Hot Water 0.90
Exterior Lights 0.12
Lights 2.07
Office Plug Loads 7.87
Task Lights 0.10
Data Center 12.11
Data Center Cooling 0.02
Data Center Fans 0.20
Credit: Stantec
Credit: Chad Lobato/NREL
Space Heating
24%
Space Cooling
3%
Pumps
1%
Ventilation Fans
5%
Domestic Hot
Water
3%
Exterior Lights
0%
Lights
6%
Office Plug Loads
22%
Task Lights
0%
Data Center
35%
Data Center
Cooling
0%
Data Center Fans
1%
NREL RSF Energy Use Breakdown
Innovation for Our Energy Future
Living in a ZEB: Every Watt Counts
•Whole building energy use = 283 Watts
continuous per occupant
• 4-5 incandescent light bulbs per occupant continuous
• $8500 of PV per occupant
•For every 1 watt continuous we save,
we avoid $33 of PV needed
to offset this 1 watt
•Every watt counts!
Innovation for Our Energy Future
Day vs. Night Plug and Process Loads
Annual Plug Load Energy Use Intensity (kBtu/ft2)
Unoccupied Hours Power Density (W/ft2)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
OccupiedHoursPower
Density(W/ft2)
0.10 3.0 5.2 7.4 9.7 11.9 14.1 16.3 18.6 20.8 23.0 25.2 27.4 29.7 31.9 34.1
0.20 3.8 6.0 8.2 10.4 12.7 14.9 17.1 19.3 21.5 23.8 26.0 28.2 30.4 32.7 34.9
0.30 4.5 6.8 9.0 11.2 13.4 15.6 17.9 20.1 22.3 24.5 26.8 29.0 31.2 33.4 35.6
0.40 5.3 7.5 9.7 12.0 14.2 16.4 18.6 20.9 23.1 25.3 27.5 29.7 32.0 34.2 36.4
0.50 6.1 8.3 10.5 12.7 15.0 17.2 19.4 21.6 23.8 26.1 28.3 30.5 32.7 35.0 37.2
0.60 6.8 9.1 11.3 13.5 15.7 17.9 20.2 22.4 24.6 26.8 29.1 31.3 33.5 35.7 38.0
0.70 7.6 9.8 12.0 14.3 16.5 18.7 20.9 23.2 25.4 27.6 29.8 32.1 34.3 36.5 38.7
0.80 8.4 10.6 12.8 15.0 17.3 19.5 21.7 23.9 26.2 28.4 30.6 32.8 35.0 37.3 39.5
0.90 9.1 11.4 13.6 15.8 18.0 20.3 22.5 24.7 26.9 29.1 31.4 33.6 35.8 38.0 40.3
1.00 9.9 12.1 14.4 16.6 18.8 21.0 23.2 25.5 27.7 29.9 32.1 34.4 36.6 38.8 41.0
1.10 10.7 12.9 15.1 17.3 19.6 21.8 24.0 26.2 28.5 30.7 32.9 35.1 37.3 39.6 41.8
1.20 11.4 13.7 15.9 18.1 20.3 22.6 24.8 27.0 29.2 31.4 33.7 35.9 38.1 40.3 42.6
1.30 12.2 14.4 16.7 18.9 21.1 23.3 25.5 27.8 30.0 32.2 34.4 36.7 38.9 41.1 43.3
1.40 13.0 15.2 17.4 19.6 21.9 24.1 26.3 28.5 30.8 33.0 35.2 37.4 39.7 41.9 44.1
1.50 13.7 16.0 18.2 20.4 22.6 24.9 27.1 29.3 31.5 33.8 36.0 38.2 40.4 42.6 44.9
Only occupied about ⅓ of the time
-Nights Unoccupied
-Weekends Unoccupied
-Holidays Unoccupied
Innovation for Our Energy Future
66%
7%
27%
Nights, Weekends, Holidays
Unoccupied workstations
during the day
Annual Occupied Hours
15
• Nights, weekends, and holidays account for 66% of the year
• A typical office building is unoccupied during this time
• During a typical work day, building occupants are only at their desk less than 30% of the time
• Workstations are vacant and should be powered down during more than 70% of business hours
• Workstations should only be powered 7% of the year!
Credit: Chad Lobato/NREL
0
10
20
30
40
50
60
70
80
90
100
0 3 6 9 12 15 18 21
Occupancy(%)
Time of Day
At work, and away
from desk
At work, and at
desk
References:
http://www.gsa.gov/graphics/pbs/WorkPlace_Matters_FINAL508_lowres.pdf
Innovation for Our Energy Future
•How can space efficiency reduce office equipment?
• Maximize use of commons spaces
• Copy rooms
• Break rooms
• Design to use stairs
• Regenerative elevators
• Slower is ok
•Minimize distribution transformers
•Exhaust transfer air for cooling of network/switch rooms
•Opportunities to turn off parasitic office equipment
• Occupancy sensor power strips
• Scheduled outlets
•Integrated datacenter cooling
• Air side economizer
• Evaporative cooling
• Waste heat recovery
Plug and Process Load Opportunities:
Design Team Opportunities
Innovation for Our Energy Future
Elevators
Regenerative Traction Elevators
– Machine Room Less Elevator
– Space Savings
– Recovers breaking energy and
converts it to AC electricity
Change elevator lighting to
energy efficient fluorescent
lighting or LEDs
Turn off lighting and fans when
the elevator is unoccupied
Credit: Jürg Nipkow, Swiss Agency for Efficient Energy Use
Innovation for Our Energy Future
•Document current space efficiency and plug load profiles
•Multifunction Devices
• 75% less printers
•Workstation
• Laptops, VOIP 2 W phones, 6 W LED task lights
•Efficiency datacenter operations
• Blade servers with virtualization
• ASHRAE temperature Guidelines
• Fully contained hot aisle
•All the other “STUFF”
• EnergyStar only a starting point
• Hand operated compact shelving
• Minimize individual stuff
• Question all operations!
Plug and Process Load Opportunities:
Owner Opportunities
Workstation Type Power Savings
Standard PC 400w 0%
Energy Star PC 300w 25%
Laptop 60w 85%
Thin Client 35w 91%
Innovation for Our Energy Future
Energy Efficient Workspace
Typical 19”-24” Monitors
30-50 Watts
24” LCD Energy Efficient
Monitors
18 Watts
Removing personal space heater
saves 1500 Watts
VOIP phones 2 Watts
Power Strip on the desktop
Easy to access power button
Workstation load – 55W
0.4 W/ft2 whole building plug
load intensity
Multi-function Devices
100 Watts (continuous)
Removing desktop printers
saves
~460 Watts/Printer
Fluorescent task lights 35 Watts
LED task lights
6 Watts
Desktop Computer (Energy Star)
300 Watts
Laptop
30 Watts
19
Innovation for Our Energy Future
Multifunction Devices
• Multifunction energy-star 4.0 compliant
devices
• Lower Maintenance
• Higher performance
• Reduce number of network printers by
75%
• Strong justification will be required for
personal printers
• Do not use banner pages
• Default to duplex printing
• Business processes are becoming
increasing paperless
• Use recycled materials
Functions?
 Printing
 Copying
 Scan to mailbox
 Standard fax
 Fax from desktop
Innovation for Our Energy Future
NREL Cyber-Security Policy
Evaluate policies and operations
to ensure effectiveness
– NREL currently used a
screensaver to lock unused
computers
• The screensaver consumes
on average 5W more than an
idle computer
– Instead of a screensaver, if
the monitors and computers
went into standby there would
be a savings of 70W per
person
– ~$500,000 of PV saved
– Anything multiplied by 800 is
a lot!
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
100.0
11:25 11:40 11:55 12:10 12:25 12:40
Power(W)
Time
Computer Power Consumption
Monitor and Computer Screensaver On (W)
Monitor Standby (W)
Monitor and Computer Standby (W)
Innovation for Our Energy Future
0.0
1000.0
2000.0
3000.0
4000.0
5000.0
6000.0
PowerConsumption(W)
Time of Day
NREL Old Coffee Car Daily Load Profile
Wells Food Warmer
Island Oasis Ice Shaver Blender
Amana Microwave
Bunn Omatic Coffee Maker
CMA Grinder
Curtis Grinder
Arctic Air Refrigerator
Haier Refrigerator (Empty)
Haier Refrigerator (Full)
TRUE Refrigerator
Whirlpool Freezer
Ariston Hot Water Heater
Bunn Hot Water System
Black and Decker Toaster
Boston Acoustics Radio
Royal Cash Register
VeriFone Credit Card Machine
GE Phone
Astoria Espresso Machine (EST)
$15,000 of PV to run
nighttime loads
Innovation for Our Energy Future
RSF Data Center
Moving towards high-density blade servers
– Highly efficient power supplies
– Variable speed fans
– Wake-on-LAN
Server virtualization
– Ratio: 4-8 to 1
Dynamic Workload management
– Server resources go from “always on” to “always available”
– Resources are powered up or down as resources are needed
Hot aisle containment with airside economizer and evaporative cooling
Target PUE of 1.1 vs. legacy PUE of 2.5
Expected reduction of 65% in total data
center power consumption
Innovation for Our Energy Future
RSF Plug Load Reduction Strategies
Elevators
– Use energy efficient traction elevators
– Change elevator lighting to energy efficient
fluorescent lighting
– Turn off elevator lighting when the elevator is
unoccupied
Break Rooms
– Increase the number of people that use each
break room from approximately 40 to 60
– Eliminate the cooler on the drinking fountain
Task Lights
– Move from 35W fluorescent task lights to 6W LED
task lights
Phones
– Go from 1000 standard phones to 1000 VOIP
phone that consumes 2W each
Copiers, Printers, Fax Machines
– Decrease the number people that use individual
copiers, printers and fax machines
– Increase the number of people that use common,
or group, copiers, printers and fax machines from
15 to 20
– Increase the use of all-in-one machines
Computers
– Go from approximately 260 laptops, 33% of staff,
to 720, 90% of staff, ensure standby mode works
for all workstations
Data Center
– Blade Servers with Virtualization
– High efficiency UPS
– 65W/employee current to 48W/employee in RSF
The result of these strategies is a 47% reduction in plug
loads
0.00
5.00
10.00
15.00
20.00
Baseline RSF
EUI(kBtu/ft2)
Baseline vs RSF Plug Load EUI
Coffee Kiosk
Elevator Lighting
Elevators
Drinking Fountains
Vending Machines
Microwaves
Coffee Pots
Refrigerators
Task Lights
Phones
Fax Machines
Copiers
Printers
Computers
Data Center
Conference Room
Equipment
Telecom Room
Equipment
Misc
Innovation for Our Energy Future
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Average
October 2010
November 2010
December 2010
January 2011
February 2011
March 2011
April 2011
May 2011
June 2011
July 2011
August 2011
October 2010 – August 2011 Plug Load Power Density
Note: The elevators are included in the plug loads
Credit:MarjorieSchott/NREL
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
Operations Lessons – Plug loads
26
• Daytime loads lower than predicted
• Model did not account for actual occupancy
• Only ~75% of occupants actually at their desk any given
day
•Nighttime loads still difficult
• Programmable outlets added after the fact
• Automatic Laptop standby/hibernate functionality
deployed system-wide
• Monitors go to sleep well
• Laptops have insomnia (except Macs)
• Need a forced standby function and not rely on integrated
windows standby
• Ensure Wake-On-LAN functionality
• Staff have not fully utilized desktop based power strip
controls
•Continued staff educational programs
•Need to develop an optimal workstation plug load control
system
• Programmable power strips to disconnect all plugs at
night?
• Easy to use office plug load disconnect switch?
Innovation for Our Energy Future
Operations Lessons – Plug loads Cont..
27
• 2 Refrigerators per break room sometimes excessive
– Some groups unplug and don’t use second refrigerator
• Utilize more switched outlets or controllable outlets
• Or allow for programmable plugs
• Energy Monitoring Displays on all night…
Innovation for Our Energy Future
Ice Machine Timed Outlet
28
• The devil is in the details…
• Saved 52% energy use on an ENERGY STAR® ice
machine with a $15 programmable outlet
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
0
200
400
600
800
1000
1200
1400
12:00
AM
12:00
PM
12:00
AM
12:00
PM
12:00
AM
12:00
PM
12:00
AM
12:00
PM
12:00
AM
12:00
PM
12:00
AM
12:00
PM
12:00
AM
12:00
PM
Power(W)
Time of Day
Uncontrolled Ice Machine
Timer Controlled Ice Machine
Weekly Energy Savings: 28.6 kWh
Weekly Energy Savings: 52%
Ice Machine Timed Outlet
29
Credit:ChadLobato/NREL
Innovation for Our Energy Future
October 2010 Plug Load Power Density
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
November 2010 Plug Load Power Density
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
December 2010 Plug Load Power Density
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
January 2011 Plug Load Power Density
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
February 2011 Plug Load Power Density
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Credit: Chad Lobato/NREL
Innovation for Our Energy Future
March 2011 Plug Load Power Density
Credit: Chad Lobato/NREL
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Innovation for Our Energy Future
April 2011 Plug Load Power Density
Credit: Chad Lobato/NREL
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Innovation for Our Energy Future
May 2011 Plug Load Power Density
Credit: Chad Lobato/NREL
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Innovation for Our Energy Future
June 2011 Plug Load Power Density
Credit: Chad Lobato/NREL
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Innovation for Our Energy Future
July 2011 Plug Load Power Density
Credit: Chad Lobato/NREL
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Innovation for Our Energy Future
August 2011 Plug Load Power Density
Credit: Chad Lobato/NREL
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0 2 4 6 8 10 12 14 16 18 20 22 24
PowerDensity(W/ft2)
Time of Day
Model Weekday Plug Loads
Model Weekend Plug Loads
RSF Hourly Weekday Plug Loads
RSF Average Weekday Plug Loads
RSF Hourly Weekend Plug Loads
RSF Average Weekend Plug Loads
Innovation for Our Energy Future
Operational Lessons- Datacenter
41
•Fully containing hot aisle difficult
• Custom aisle floor and door seals
• Ensure equipment designed for cold
aisle containment
• And installed to pull cold air
– Not hot air…
•Have run ~1.1-1.15 PUE
•A few hot spots were driving up PUE…
•Summer time PUE of 1.20 because of
increased cooling
•Starting to control hot aisle based on
return temperature of ~80F
•65 Watts/person to 38 Watts/person
• But NREL has doubled in size
• Modeled 65 watts/person for 1200
people
• Using 38 watts/person for 2300 people
NREL/PIX17897
Credit:MarjorieSchott/NREL
Innovation for Our Energy Future42
Innovation for Our Energy Future
-20
-5
10
25
40
55
70
85
100
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
10/1/10 11/30/10 1/29/11 3/30/11 5/29/11 7/28/11
OutdoorTemperature(°F)
PUE
RSF Data Center PUE
Outdoor Temperature
Data Center PUE
Innovation for Our Energy Future
Monthly Average PUE
44
1.04
1.06
1.08
1.10
1.12
1.14
1.16
1.18
1.20
1.22
1.24
1.26
October
2010
November
2010
December
2010
January
2011
February
2011
March
2011
April
2011
May
2011
June
2011
July
2011
August
2011
PUE
Innovation for Our Energy Future
10 Steps to Address PPLs
45
1.
Establish a
PPL
Champion
2.
Develop a
Business
Case
3.
Benchmark
Conventional
Equipment
and
Operations
4.
Identify
Occupant’s
Needs
5.
Meet Needs
as Efficiently
as Possible
6.
Turn It Off at
Night
7.
Design Team:
Identify
Applicable
Strategies
8.
Procurement
Decisions
and Policy
9.
Address
Unique PPLs
10.
Occupant
Awareness
Innovation for Our Energy Future
Step 1: Establish a PPL Champion
Purpose:
To initiate and help implement PPL strategies.
Skills needed:
• Understanding of:
• technical energy efficiency
opportunities
• design strategies
• Ability to:
• apply business model
• question operations, institutional
policies, and procurement processes
46
Innovation for Our Energy Future
Step 2: Develop a business case for
addressing PPLs
Avoided Cost of Renewables (ACR):
Equates the cost of PPL efficiency measures to
avoided renewable costs.
Gives all parties a financial incentive to
investigate PPLs.
ACR for the RSF:
Used to justify demand-side efficiency measures.
1 Watt continuous saved = $33 worth of PV was
avoided. Additional loads must be offset with
renewables.
The PV cost avoided by PPL reductions
exceeded $4 million.
47Photo Credit: Dennis Schroeder PIX 17842
Innovation for Our Energy Future
Step 3: Benchmark your conventional
equipment and operations
Methods:
• Submeter panels (if properly organized)
• PPL power meters
• Combination of submetering and equip.
spec. sheets can be used
Data:
• Understand when equipment is used
• Highlight opportunities to turn off
• Basis of comparison for financial
calculations
48Figure Credit: Microsoft Clip Art
Innovation for Our Energy Future
Step 4: Be willing to identify occupants’ true
needs
True need:
Equipment or procedure required to achieve a
given business goal or an assigned task.
Understand:
What do occupants produce as part of their
jobs and what tools do they require?
Every occupant, including those working in
sensitive operations must be accounted for.
Nonessential equipment:
•A business case must be made for continued
use.
49
Innovation for Our Energy Future
Step 5: Meet needs as efficiently as possible
Search energy efficient equipment databases.
Nonrated equipment:
•Investigate the most efficient model
•Turn off when not in use (if possible)
Pay attention to parasitic loads.
50Photo Credit: Chad Lobato
Innovation for Our Energy Future
Step 6: Turning it all off
Office buildings are typically unoccupied 66% of year.
KEY: Reduce power density during nonbusiness hours.
51Photo Credit: Jennifer Schieb
Innovation for Our Energy Future
Step 7: Encourage the design team to identify
all applicable PPL strategies
Question standard specifications, operations,
and design standards.
Maximize space efficiency.
Integrate PPL control strategies into the
building’s electrical system:
•Switches
•Vacancy sensors
•Timed disconnects for outlets
•Controlling outlets through the Building
Management System (BMS)
Other loads:
•Elevators
•Transformers
•Process cooling systems
•Data centers
52
Innovation for Our Energy Future
Step 8: Institutionalize procurement decisions
and policy programs
Day-to-day energy efficiency: Depends on
the decisions of occupants, facility managers,
and owners.
Identify decision makers who can:
• Institutionalize PPL measures through procurement
decisions and policy programs.
• Promote buy-in.
• Identify unbreakable and unchangeable policies.
53
Innovation for Our Energy Future
Step 9: Address unique miscellaneous PPLs
EXAMPLE: Contractors and food service areas.
Building owner can contractually require or provide the most
efficient equipment available.
Case-by-case evaluation:
• Energy-efficient equipment may not be available and may
be restricted from being turned off (e.g. ATM)
• Manufacturers may be able to recommend alternatives.
54Photo Credit: Chad Lobato
Innovation for Our Energy Future
Step 10: Occupant awareness
Encourage and allow to “do good”.
PPL strategies should counteract “bad users.”
Emphasize importance of turning off personal
electronics when leaving a workspace.
55Photo Credit: Jennifer Scheib
Innovation for Our Energy Future
DOE Commercial Buildings Resource Database:
Additional Plug Load Guidance
Search for:
• Plug or Miscellaneous
Electric Load
• Datacenter
56
http://apps1.eere.energy.gov/buildings/commercial/resource_database/
Innovation for Our Energy Future
Thanks and Questions
Shanti Pless
Shanti.pless@nrel.gov
www.nrel.gov/rsf
57

Weitere ähnliche Inhalte

Was ist angesagt?

Achieving net zero energy at scale gb12 111512
Achieving net zero energy at scale gb12 111512Achieving net zero energy at scale gb12 111512
Achieving net zero energy at scale gb12 111512Tom Hootman
 
MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...
MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...
MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...Midwest Energy Efficiency Alliance
 
NZEB Office Building by David Walshe
NZEB Office Building by  David WalsheNZEB Office Building by  David Walshe
NZEB Office Building by David WalsheSustainableEnergyAut
 
Building A Zero Carbon Internet
Building A Zero Carbon InternetBuilding A Zero Carbon Internet
Building A Zero Carbon InternetBill St. Arnaud
 
Case Study: Zero Net Energy and the Changing Shape of Architecture
Case Study: Zero Net Energy and the Changing Shape of ArchitectureCase Study: Zero Net Energy and the Changing Shape of Architecture
Case Study: Zero Net Energy and the Changing Shape of ArchitectureSustainable Performance Institute
 
3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_trainingmelanie_bissonnette
 
NZEB Interm Specification by Sean Armstrong
NZEB Interm Specification by Sean ArmstrongNZEB Interm Specification by Sean Armstrong
NZEB Interm Specification by Sean ArmstrongSustainableEnergyAut
 
Energy Modeling 2009 Presentation
Energy Modeling 2009 PresentationEnergy Modeling 2009 Presentation
Energy Modeling 2009 PresentationMatt Macko
 
NZEB Office Building including renewable energy ratio calculation orla coyle
NZEB Office Building including renewable energy ratio calculation  orla coyleNZEB Office Building including renewable energy ratio calculation  orla coyle
NZEB Office Building including renewable energy ratio calculation orla coyleSustainableEnergyAut
 
Building the Future: Net Zero and Net Zero Ready
Building the Future: Net Zero and Net Zero ReadyBuilding the Future: Net Zero and Net Zero Ready
Building the Future: Net Zero and Net Zero ReadyRDH Building Science
 
Information about zero energy building and green buiding
Information about zero energy building and green buidingInformation about zero energy building and green buiding
Information about zero energy building and green buidingNikhil NG
 
Examples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John FurlongExamples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John FurlongSustainableEnergyAut
 
Sustainability and Energy Efficiency by Ciaran O'Connor
Sustainability and Energy Efficiency by Ciaran O'ConnorSustainability and Energy Efficiency by Ciaran O'Connor
Sustainability and Energy Efficiency by Ciaran O'ConnorSustainableEnergyAut
 
Case Study: CBT Architects - Building Performance Modeling
Case Study: CBT Architects - Building Performance ModelingCase Study: CBT Architects - Building Performance Modeling
Case Study: CBT Architects - Building Performance ModelingIES VE
 
NREL case study 010512
NREL case study 010512NREL case study 010512
NREL case study 010512Tom Hootman
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...energytrustor
 

Was ist angesagt? (20)

Achieving net zero energy at scale gb12 111512
Achieving net zero energy at scale gb12 111512Achieving net zero energy at scale gb12 111512
Achieving net zero energy at scale gb12 111512
 
MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...
MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...
MEEA Industrial Webinar: Industrial Load Reduction: The Role of Intelligent L...
 
NZEB Office Building by David Walshe
NZEB Office Building by  David WalsheNZEB Office Building by  David Walshe
NZEB Office Building by David Walshe
 
Building A Zero Carbon Internet
Building A Zero Carbon InternetBuilding A Zero Carbon Internet
Building A Zero Carbon Internet
 
Case Study: Zero Net Energy and the Changing Shape of Architecture
Case Study: Zero Net Energy and the Changing Shape of ArchitectureCase Study: Zero Net Energy and the Changing Shape of Architecture
Case Study: Zero Net Energy and the Changing Shape of Architecture
 
3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training
 
Nzeb case study esb
Nzeb case study   esbNzeb case study   esb
Nzeb case study esb
 
Energy in Schools by John Dolan
Energy in Schools by John DolanEnergy in Schools by John Dolan
Energy in Schools by John Dolan
 
NZEB Interm Specification by Sean Armstrong
NZEB Interm Specification by Sean ArmstrongNZEB Interm Specification by Sean Armstrong
NZEB Interm Specification by Sean Armstrong
 
Energy Modeling 2009 Presentation
Energy Modeling 2009 PresentationEnergy Modeling 2009 Presentation
Energy Modeling 2009 Presentation
 
NZEB Office Building including renewable energy ratio calculation orla coyle
NZEB Office Building including renewable energy ratio calculation  orla coyleNZEB Office Building including renewable energy ratio calculation  orla coyle
NZEB Office Building including renewable energy ratio calculation orla coyle
 
Building the Future: Net Zero and Net Zero Ready
Building the Future: Net Zero and Net Zero ReadyBuilding the Future: Net Zero and Net Zero Ready
Building the Future: Net Zero and Net Zero Ready
 
Information about zero energy building and green buiding
Information about zero energy building and green buidingInformation about zero energy building and green buiding
Information about zero energy building and green buiding
 
Examples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John FurlongExamples of NZEB in the Public Sector by John Furlong
Examples of NZEB in the Public Sector by John Furlong
 
Sustainability and Energy Efficiency by Ciaran O'Connor
Sustainability and Energy Efficiency by Ciaran O'ConnorSustainability and Energy Efficiency by Ciaran O'Connor
Sustainability and Energy Efficiency by Ciaran O'Connor
 
Energy Modeling
Energy ModelingEnergy Modeling
Energy Modeling
 
Case Study: CBT Architects - Building Performance Modeling
Case Study: CBT Architects - Building Performance ModelingCase Study: CBT Architects - Building Performance Modeling
Case Study: CBT Architects - Building Performance Modeling
 
NREL case study 010512
NREL case study 010512NREL case study 010512
NREL case study 010512
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...
 
IGBC2014 - Stephen Selkowitz, Lawrence Berkeley National Laboratory
IGBC2014 - Stephen Selkowitz, Lawrence Berkeley National LaboratoryIGBC2014 - Stephen Selkowitz, Lawrence Berkeley National Laboratory
IGBC2014 - Stephen Selkowitz, Lawrence Berkeley National Laboratory
 

Ähnlich wie Plug Load Efficiency for Zero Energy Buildings Webinar 1 29 2013

The Next Network: Lighting, Controls, and the Internet of Things
The Next Network: Lighting, Controls, and the Internet of ThingsThe Next Network: Lighting, Controls, and the Internet of Things
The Next Network: Lighting, Controls, and the Internet of ThingsSUDHAKARA RAO PARVATANENI
 
Benchmarking/Performance Measuring
Benchmarking/Performance MeasuringBenchmarking/Performance Measuring
Benchmarking/Performance MeasuringASHRAE Region VI
 
Maximizing Power Production for Small Commercial Projects
Maximizing Power Production for Small Commercial ProjectsMaximizing Power Production for Small Commercial Projects
Maximizing Power Production for Small Commercial Projectsallearthrenewables
 
Nbi e source_emr_plug_loads_april_2013_higgins_final
Nbi e source_emr_plug_loads_april_2013_higgins_finalNbi e source_emr_plug_loads_april_2013_higgins_final
Nbi e source_emr_plug_loads_april_2013_higgins_finalCathy_Higgins
 
RSF Net zero operations 2020
RSF Net zero operations 2020RSF Net zero operations 2020
RSF Net zero operations 2020Shanti Pless
 
Holistic approaches to green it gregynog colloquium - june 2011
Holistic approaches to green it   gregynog colloquium - june 2011Holistic approaches to green it   gregynog colloquium - june 2011
Holistic approaches to green it gregynog colloquium - june 2011gregynog
 
eea desktop case study.pdf
eea desktop case study.pdfeea desktop case study.pdf
eea desktop case study.pdfDarshanReddy49
 
2015 - Building Simulation Best of 2015-03-23.pptx
2015 - Building Simulation Best of 2015-03-23.pptx2015 - Building Simulation Best of 2015-03-23.pptx
2015 - Building Simulation Best of 2015-03-23.pptxRed Car Analytics
 
US Trends in Data Centre Design with NREL Examples of Large Energy Savings
US Trends in Data Centre Design with NREL Examples of Large Energy Savings US Trends in Data Centre Design with NREL Examples of Large Energy Savings
US Trends in Data Centre Design with NREL Examples of Large Energy Savings JISC's Green ICT Programme
 
Controlling capital costs using a performance based design build process
Controlling capital costs using a performance based design build processControlling capital costs using a performance based design build process
Controlling capital costs using a performance based design build processShanti Pless
 
Practical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & AuditingPractical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & AuditingLiving Online
 
Cost Estimation in Project Management - Case of Solar Assisted Water Pump
Cost Estimation in Project Management - Case of Solar Assisted Water PumpCost Estimation in Project Management - Case of Solar Assisted Water Pump
Cost Estimation in Project Management - Case of Solar Assisted Water PumpNitesh Bhatia
 
Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015
Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015
Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015buildpulse
 

Ähnlich wie Plug Load Efficiency for Zero Energy Buildings Webinar 1 29 2013 (20)

The Next Network: Lighting, Controls, and the Internet of Things
The Next Network: Lighting, Controls, and the Internet of ThingsThe Next Network: Lighting, Controls, and the Internet of Things
The Next Network: Lighting, Controls, and the Internet of Things
 
Benchmarking/Performance Measuring
Benchmarking/Performance MeasuringBenchmarking/Performance Measuring
Benchmarking/Performance Measuring
 
Maximizing Power Production for Small Commercial Projects
Maximizing Power Production for Small Commercial ProjectsMaximizing Power Production for Small Commercial Projects
Maximizing Power Production for Small Commercial Projects
 
Nbi e source_emr_plug_loads_april_2013_higgins_final
Nbi e source_emr_plug_loads_april_2013_higgins_finalNbi e source_emr_plug_loads_april_2013_higgins_final
Nbi e source_emr_plug_loads_april_2013_higgins_final
 
RSF Net zero operations 2020
RSF Net zero operations 2020RSF Net zero operations 2020
RSF Net zero operations 2020
 
1.1 integrating renewables srm
1.1 integrating renewables   srm1.1 integrating renewables   srm
1.1 integrating renewables srm
 
Holistic approaches to green it gregynog colloquium - june 2011
Holistic approaches to green it   gregynog colloquium - june 2011Holistic approaches to green it   gregynog colloquium - june 2011
Holistic approaches to green it gregynog colloquium - june 2011
 
eea desktop case study.pdf
eea desktop case study.pdfeea desktop case study.pdf
eea desktop case study.pdf
 
2015 - Building Simulation Best of 2015-03-23.pptx
2015 - Building Simulation Best of 2015-03-23.pptx2015 - Building Simulation Best of 2015-03-23.pptx
2015 - Building Simulation Best of 2015-03-23.pptx
 
Server room presentation 16th january 2014
Server room presentation 16th january 2014Server room presentation 16th january 2014
Server room presentation 16th january 2014
 
US Trends in Data Centre Design with NREL Examples of Large Energy Savings
US Trends in Data Centre Design with NREL Examples of Large Energy Savings US Trends in Data Centre Design with NREL Examples of Large Energy Savings
US Trends in Data Centre Design with NREL Examples of Large Energy Savings
 
Solaric at ACEF 2014
Solaric at ACEF 2014Solaric at ACEF 2014
Solaric at ACEF 2014
 
RENEWABLE ENERGY SOLUTIONS
RENEWABLE ENERGY SOLUTIONSRENEWABLE ENERGY SOLUTIONS
RENEWABLE ENERGY SOLUTIONS
 
CaseStudy_TP
CaseStudy_TPCaseStudy_TP
CaseStudy_TP
 
Controlling capital costs using a performance based design build process
Controlling capital costs using a performance based design build processControlling capital costs using a performance based design build process
Controlling capital costs using a performance based design build process
 
54 paul gibbs_helioscope
54 paul gibbs_helioscope54 paul gibbs_helioscope
54 paul gibbs_helioscope
 
Gc going green step by step
Gc going green step by stepGc going green step by step
Gc going green step by step
 
Practical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & AuditingPractical Energy Efficiency, Design, Engineering & Auditing
Practical Energy Efficiency, Design, Engineering & Auditing
 
Cost Estimation in Project Management - Case of Solar Assisted Water Pump
Cost Estimation in Project Management - Case of Solar Assisted Water PumpCost Estimation in Project Management - Case of Solar Assisted Water Pump
Cost Estimation in Project Management - Case of Solar Assisted Water Pump
 
Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015
Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015
Utilizing Analytics to Drive Change in Buildings - Apem Sept 18 2015
 

Mehr von Shanti Pless

Innovative Capabilities to Integrate Energy Efficiency Strategies through Ad...
Innovative Capabilities to Integrate Energy Efficiency Strategies through  Ad...Innovative Capabilities to Integrate Energy Efficiency Strategies through  Ad...
Innovative Capabilities to Integrate Energy Efficiency Strategies through Ad...Shanti Pless
 
Getting to Zero Forum 2019 - Buildings and the Grid
Getting to Zero Forum 2019 - Buildings and the GridGetting to Zero Forum 2019 - Buildings and the Grid
Getting to Zero Forum 2019 - Buildings and the GridShanti Pless
 
Energy Efficiency in Permanent Modular Construction NREL Research Project Poster
Energy Efficiency in Permanent Modular Construction NREL Research Project PosterEnergy Efficiency in Permanent Modular Construction NREL Research Project Poster
Energy Efficiency in Permanent Modular Construction NREL Research Project PosterShanti Pless
 
Integrating Energy Efficiency into Advanced Manufacturing of Buildings
Integrating Energy Efficiency into Advanced Manufacturing of BuildingsIntegrating Energy Efficiency into Advanced Manufacturing of Buildings
Integrating Energy Efficiency into Advanced Manufacturing of BuildingsShanti Pless
 
Integrating Energy Efficiency into the Emerging Off-site modular Construction...
Integrating Energy Efficiency into the Emerging Off-site modular Construction...Integrating Energy Efficiency into the Emerging Off-site modular Construction...
Integrating Energy Efficiency into the Emerging Off-site modular Construction...Shanti Pless
 
Next Generation Net Zero Vision
Next Generation Net Zero VisionNext Generation Net Zero Vision
Next Generation Net Zero VisionShanti Pless
 
Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...
Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...
Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...Shanti Pless
 
Human Side Of Net Zero - Rocky Mountain Green
Human Side Of Net Zero - Rocky Mountain GreenHuman Side Of Net Zero - Rocky Mountain Green
Human Side Of Net Zero - Rocky Mountain GreenShanti Pless
 
Occupant Engaged - A ZEB control concept for engaging occupants
Occupant Engaged -  A ZEB control concept for engaging occupantsOccupant Engaged -  A ZEB control concept for engaging occupants
Occupant Engaged - A ZEB control concept for engaging occupantsShanti Pless
 
50% Savings Advanced Energy Design Guides, ACEEE Summer Study, 2012
50% Savings Advanced Energy Design Guides, ACEEE Summer Study, 201250% Savings Advanced Energy Design Guides, ACEEE Summer Study, 2012
50% Savings Advanced Energy Design Guides, ACEEE Summer Study, 2012Shanti Pless
 
Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...
Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...
Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...Shanti Pless
 
Rebuilding Greensburg to be a Zero Energy City
Rebuilding Greensburg to be a Zero Energy CityRebuilding Greensburg to be a Zero Energy City
Rebuilding Greensburg to be a Zero Energy CityShanti Pless
 
NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...
NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...
NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...Shanti Pless
 
AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...
AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...
AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...Shanti Pless
 

Mehr von Shanti Pless (14)

Innovative Capabilities to Integrate Energy Efficiency Strategies through Ad...
Innovative Capabilities to Integrate Energy Efficiency Strategies through  Ad...Innovative Capabilities to Integrate Energy Efficiency Strategies through  Ad...
Innovative Capabilities to Integrate Energy Efficiency Strategies through Ad...
 
Getting to Zero Forum 2019 - Buildings and the Grid
Getting to Zero Forum 2019 - Buildings and the GridGetting to Zero Forum 2019 - Buildings and the Grid
Getting to Zero Forum 2019 - Buildings and the Grid
 
Energy Efficiency in Permanent Modular Construction NREL Research Project Poster
Energy Efficiency in Permanent Modular Construction NREL Research Project PosterEnergy Efficiency in Permanent Modular Construction NREL Research Project Poster
Energy Efficiency in Permanent Modular Construction NREL Research Project Poster
 
Integrating Energy Efficiency into Advanced Manufacturing of Buildings
Integrating Energy Efficiency into Advanced Manufacturing of BuildingsIntegrating Energy Efficiency into Advanced Manufacturing of Buildings
Integrating Energy Efficiency into Advanced Manufacturing of Buildings
 
Integrating Energy Efficiency into the Emerging Off-site modular Construction...
Integrating Energy Efficiency into the Emerging Off-site modular Construction...Integrating Energy Efficiency into the Emerging Off-site modular Construction...
Integrating Energy Efficiency into the Emerging Off-site modular Construction...
 
Next Generation Net Zero Vision
Next Generation Net Zero VisionNext Generation Net Zero Vision
Next Generation Net Zero Vision
 
Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...
Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...
Energy Exchange 2015: Track 7 session 5: Energy Performance Based Design Buil...
 
Human Side Of Net Zero - Rocky Mountain Green
Human Side Of Net Zero - Rocky Mountain GreenHuman Side Of Net Zero - Rocky Mountain Green
Human Side Of Net Zero - Rocky Mountain Green
 
Occupant Engaged - A ZEB control concept for engaging occupants
Occupant Engaged -  A ZEB control concept for engaging occupantsOccupant Engaged -  A ZEB control concept for engaging occupants
Occupant Engaged - A ZEB control concept for engaging occupants
 
50% Savings Advanced Energy Design Guides, ACEEE Summer Study, 2012
50% Savings Advanced Energy Design Guides, ACEEE Summer Study, 201250% Savings Advanced Energy Design Guides, ACEEE Summer Study, 2012
50% Savings Advanced Energy Design Guides, ACEEE Summer Study, 2012
 
Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...
Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...
Advanced Energy Design and Retrofit Guides Summary from the 2013 DOE BTO Peer...
 
Rebuilding Greensburg to be a Zero Energy City
Rebuilding Greensburg to be a Zero Energy CityRebuilding Greensburg to be a Zero Energy City
Rebuilding Greensburg to be a Zero Energy City
 
NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...
NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...
NASA Net Zero Roadmap: Federal Utilities Partnership Working Group, November ...
 
AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...
AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...
AIA 2013: Facts on the Ground: Testing the Performance of Ft. Carson's Green ...
 

Kürzlich hochgeladen

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 

Kürzlich hochgeladen (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 

Plug Load Efficiency for Zero Energy Buildings Webinar 1 29 2013

  • 1. NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the Alliance for Sustainable Energy, LLC. NREL’s Research Support Facility: Plug Load Efficiency Strategies in Meeting Net Zero Energy Goals Shanti Pless, LEED AP Senior Research Engineer NREL Commercial Buildings Research Group January 29, 2013 Innovation for Our Energy Future
  • 2. Innovation for Our Energy Future http://www.nrel.gov/docs/fy11osti/51199.pdf 2
  • 3. Innovation for Our Energy Future3 NREL: 2006 Used with Permission from Haselden
  • 4. Innovation for Our Energy Future4 Research Support Facility Vision • A showcase for sustainable, high-performance design o Incorporates the best in energy efficiency, environmental performance, and advanced controls using a “whole-building” integrated design process • Serves as a model for cost-competitive, high-performance commercial buildings for the nation’s design construction, operation, and financing communities Credit: RNL
  • 5. Innovation for Our Energy Future5 NREL: Today Used with Permission from Haselden
  • 6. Innovation for Our Energy Future • More than 800 people in DOE office space on NREL’s campus • 220,000 ft2 • Design/build process with required energy goals • 25 kBtu/ft2 • 50% energy savings • LEED Platinum • Replicable • Process • Technologies • Cost • Site, source, carbon, cost ZEB:B • Includes plugs loads and datacenter • Firm fixed price of ~$64 million • $259/ft2 construction cost (not including $27/ft2 for PV from PPA/ARRA) • Open first phase June 10, 2010 DOE/NREL Research Support Facility: Project Goals Credit:HaseldenConstruction
  • 7. Innovation for Our Energy Future Energy Efficiency Design Requirements 7 • 25 kBtu/ft2/yr for standard office space occupant density and data center loads • Demand side energy use goal, not including renewables • Normalized up to 35.1 kBtu/ft2/yr for better space efficiency and to account for full data center load • On site renewables sized to offset site energy use to reach net zero annual use Credit:ChadLobato/NREL 0 20 40 60 80 100 120 140 Old NREL/DOE Leased Office Building Typical Denver Office Building ENERGY STAR 75 Office Building Average LEED Office Building ENERGY STAR 90 Office Building EPA Region 8 Office Denver, CO RSF RSF Renewable Production AnnualEUI(kBtu/ft2) Site Mounted PV Roof Mounted PV Data Center Whole Building References: https://www.energystar.gov/index.cfm?c=new_bldg_design.bus_target_finder http://eere.buildinggreen.com/mtxview.cfm?CFID=46438782&CFTOKEN=31996638 http://femp.buildinggreen.com/overview.cfm?ProjectID=864
  • 8. Innovation for Our Energy Future8 Key Design Strategies • Optimal orientation and office space layout • Fully daylit office wings with high- performance electrical lighting • Continuous insulation precast wall panels with thermal mass • Operable windows for natural ventilation • Radiant heating and cooling • Outdoor air preheating o Transpired solar collector o Data Center waste heat o Exhaust air heat recovery o Crawl space thermal storage • Aggressive plug load control strategies • Data Center outdoor air economizer with hot aisle containment • Roof top- and parking lot-based PV
  • 9. Innovation for Our Energy Future9 •100% of the workstations are daylit •No employee more than 30 feet from a window Daylighting
  • 10. Innovation for Our Energy Future Daylighting: Glare Control A light redirecting device reflects sunlight to the ceiling, creating an indirect lighting effect. Fixed sunshades limit excess light and glare. Credit: RNL
  • 11. Innovation for Our Energy Future11 Reclaimed natural gas piping serves as support for the building. The lobby and other common areas feature beetle-kill pine from Western forests. Daylighting reduces the need for the use of electrical lighting. LEED Platinum rating, version 2.2 – 59 points.
  • 12. Innovation for Our Energy Future Energy Modeling End Use kBtu/ft2 Space Heating 8.58 Space Cooling 0.85 Pumps 0.48 Ventilation Fans 1.88 Domestic Hot Water 0.90 Exterior Lights 0.12 Lights 2.07 Office Plug Loads 7.87 Task Lights 0.10 Data Center 12.11 Data Center Cooling 0.02 Data Center Fans 0.20 Credit: Stantec Credit: Chad Lobato/NREL Space Heating 24% Space Cooling 3% Pumps 1% Ventilation Fans 5% Domestic Hot Water 3% Exterior Lights 0% Lights 6% Office Plug Loads 22% Task Lights 0% Data Center 35% Data Center Cooling 0% Data Center Fans 1% NREL RSF Energy Use Breakdown
  • 13. Innovation for Our Energy Future Living in a ZEB: Every Watt Counts •Whole building energy use = 283 Watts continuous per occupant • 4-5 incandescent light bulbs per occupant continuous • $8500 of PV per occupant •For every 1 watt continuous we save, we avoid $33 of PV needed to offset this 1 watt •Every watt counts!
  • 14. Innovation for Our Energy Future Day vs. Night Plug and Process Loads Annual Plug Load Energy Use Intensity (kBtu/ft2) Unoccupied Hours Power Density (W/ft2) 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 OccupiedHoursPower Density(W/ft2) 0.10 3.0 5.2 7.4 9.7 11.9 14.1 16.3 18.6 20.8 23.0 25.2 27.4 29.7 31.9 34.1 0.20 3.8 6.0 8.2 10.4 12.7 14.9 17.1 19.3 21.5 23.8 26.0 28.2 30.4 32.7 34.9 0.30 4.5 6.8 9.0 11.2 13.4 15.6 17.9 20.1 22.3 24.5 26.8 29.0 31.2 33.4 35.6 0.40 5.3 7.5 9.7 12.0 14.2 16.4 18.6 20.9 23.1 25.3 27.5 29.7 32.0 34.2 36.4 0.50 6.1 8.3 10.5 12.7 15.0 17.2 19.4 21.6 23.8 26.1 28.3 30.5 32.7 35.0 37.2 0.60 6.8 9.1 11.3 13.5 15.7 17.9 20.2 22.4 24.6 26.8 29.1 31.3 33.5 35.7 38.0 0.70 7.6 9.8 12.0 14.3 16.5 18.7 20.9 23.2 25.4 27.6 29.8 32.1 34.3 36.5 38.7 0.80 8.4 10.6 12.8 15.0 17.3 19.5 21.7 23.9 26.2 28.4 30.6 32.8 35.0 37.3 39.5 0.90 9.1 11.4 13.6 15.8 18.0 20.3 22.5 24.7 26.9 29.1 31.4 33.6 35.8 38.0 40.3 1.00 9.9 12.1 14.4 16.6 18.8 21.0 23.2 25.5 27.7 29.9 32.1 34.4 36.6 38.8 41.0 1.10 10.7 12.9 15.1 17.3 19.6 21.8 24.0 26.2 28.5 30.7 32.9 35.1 37.3 39.6 41.8 1.20 11.4 13.7 15.9 18.1 20.3 22.6 24.8 27.0 29.2 31.4 33.7 35.9 38.1 40.3 42.6 1.30 12.2 14.4 16.7 18.9 21.1 23.3 25.5 27.8 30.0 32.2 34.4 36.7 38.9 41.1 43.3 1.40 13.0 15.2 17.4 19.6 21.9 24.1 26.3 28.5 30.8 33.0 35.2 37.4 39.7 41.9 44.1 1.50 13.7 16.0 18.2 20.4 22.6 24.9 27.1 29.3 31.5 33.8 36.0 38.2 40.4 42.6 44.9 Only occupied about ⅓ of the time -Nights Unoccupied -Weekends Unoccupied -Holidays Unoccupied
  • 15. Innovation for Our Energy Future 66% 7% 27% Nights, Weekends, Holidays Unoccupied workstations during the day Annual Occupied Hours 15 • Nights, weekends, and holidays account for 66% of the year • A typical office building is unoccupied during this time • During a typical work day, building occupants are only at their desk less than 30% of the time • Workstations are vacant and should be powered down during more than 70% of business hours • Workstations should only be powered 7% of the year! Credit: Chad Lobato/NREL 0 10 20 30 40 50 60 70 80 90 100 0 3 6 9 12 15 18 21 Occupancy(%) Time of Day At work, and away from desk At work, and at desk References: http://www.gsa.gov/graphics/pbs/WorkPlace_Matters_FINAL508_lowres.pdf
  • 16. Innovation for Our Energy Future •How can space efficiency reduce office equipment? • Maximize use of commons spaces • Copy rooms • Break rooms • Design to use stairs • Regenerative elevators • Slower is ok •Minimize distribution transformers •Exhaust transfer air for cooling of network/switch rooms •Opportunities to turn off parasitic office equipment • Occupancy sensor power strips • Scheduled outlets •Integrated datacenter cooling • Air side economizer • Evaporative cooling • Waste heat recovery Plug and Process Load Opportunities: Design Team Opportunities
  • 17. Innovation for Our Energy Future Elevators Regenerative Traction Elevators – Machine Room Less Elevator – Space Savings – Recovers breaking energy and converts it to AC electricity Change elevator lighting to energy efficient fluorescent lighting or LEDs Turn off lighting and fans when the elevator is unoccupied Credit: Jürg Nipkow, Swiss Agency for Efficient Energy Use
  • 18. Innovation for Our Energy Future •Document current space efficiency and plug load profiles •Multifunction Devices • 75% less printers •Workstation • Laptops, VOIP 2 W phones, 6 W LED task lights •Efficiency datacenter operations • Blade servers with virtualization • ASHRAE temperature Guidelines • Fully contained hot aisle •All the other “STUFF” • EnergyStar only a starting point • Hand operated compact shelving • Minimize individual stuff • Question all operations! Plug and Process Load Opportunities: Owner Opportunities Workstation Type Power Savings Standard PC 400w 0% Energy Star PC 300w 25% Laptop 60w 85% Thin Client 35w 91%
  • 19. Innovation for Our Energy Future Energy Efficient Workspace Typical 19”-24” Monitors 30-50 Watts 24” LCD Energy Efficient Monitors 18 Watts Removing personal space heater saves 1500 Watts VOIP phones 2 Watts Power Strip on the desktop Easy to access power button Workstation load – 55W 0.4 W/ft2 whole building plug load intensity Multi-function Devices 100 Watts (continuous) Removing desktop printers saves ~460 Watts/Printer Fluorescent task lights 35 Watts LED task lights 6 Watts Desktop Computer (Energy Star) 300 Watts Laptop 30 Watts 19
  • 20. Innovation for Our Energy Future Multifunction Devices • Multifunction energy-star 4.0 compliant devices • Lower Maintenance • Higher performance • Reduce number of network printers by 75% • Strong justification will be required for personal printers • Do not use banner pages • Default to duplex printing • Business processes are becoming increasing paperless • Use recycled materials Functions?  Printing  Copying  Scan to mailbox  Standard fax  Fax from desktop
  • 21. Innovation for Our Energy Future NREL Cyber-Security Policy Evaluate policies and operations to ensure effectiveness – NREL currently used a screensaver to lock unused computers • The screensaver consumes on average 5W more than an idle computer – Instead of a screensaver, if the monitors and computers went into standby there would be a savings of 70W per person – ~$500,000 of PV saved – Anything multiplied by 800 is a lot! 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0 11:25 11:40 11:55 12:10 12:25 12:40 Power(W) Time Computer Power Consumption Monitor and Computer Screensaver On (W) Monitor Standby (W) Monitor and Computer Standby (W)
  • 22. Innovation for Our Energy Future 0.0 1000.0 2000.0 3000.0 4000.0 5000.0 6000.0 PowerConsumption(W) Time of Day NREL Old Coffee Car Daily Load Profile Wells Food Warmer Island Oasis Ice Shaver Blender Amana Microwave Bunn Omatic Coffee Maker CMA Grinder Curtis Grinder Arctic Air Refrigerator Haier Refrigerator (Empty) Haier Refrigerator (Full) TRUE Refrigerator Whirlpool Freezer Ariston Hot Water Heater Bunn Hot Water System Black and Decker Toaster Boston Acoustics Radio Royal Cash Register VeriFone Credit Card Machine GE Phone Astoria Espresso Machine (EST) $15,000 of PV to run nighttime loads
  • 23. Innovation for Our Energy Future RSF Data Center Moving towards high-density blade servers – Highly efficient power supplies – Variable speed fans – Wake-on-LAN Server virtualization – Ratio: 4-8 to 1 Dynamic Workload management – Server resources go from “always on” to “always available” – Resources are powered up or down as resources are needed Hot aisle containment with airside economizer and evaporative cooling Target PUE of 1.1 vs. legacy PUE of 2.5 Expected reduction of 65% in total data center power consumption
  • 24. Innovation for Our Energy Future RSF Plug Load Reduction Strategies Elevators – Use energy efficient traction elevators – Change elevator lighting to energy efficient fluorescent lighting – Turn off elevator lighting when the elevator is unoccupied Break Rooms – Increase the number of people that use each break room from approximately 40 to 60 – Eliminate the cooler on the drinking fountain Task Lights – Move from 35W fluorescent task lights to 6W LED task lights Phones – Go from 1000 standard phones to 1000 VOIP phone that consumes 2W each Copiers, Printers, Fax Machines – Decrease the number people that use individual copiers, printers and fax machines – Increase the number of people that use common, or group, copiers, printers and fax machines from 15 to 20 – Increase the use of all-in-one machines Computers – Go from approximately 260 laptops, 33% of staff, to 720, 90% of staff, ensure standby mode works for all workstations Data Center – Blade Servers with Virtualization – High efficiency UPS – 65W/employee current to 48W/employee in RSF The result of these strategies is a 47% reduction in plug loads 0.00 5.00 10.00 15.00 20.00 Baseline RSF EUI(kBtu/ft2) Baseline vs RSF Plug Load EUI Coffee Kiosk Elevator Lighting Elevators Drinking Fountains Vending Machines Microwaves Coffee Pots Refrigerators Task Lights Phones Fax Machines Copiers Printers Computers Data Center Conference Room Equipment Telecom Room Equipment Misc
  • 25. Innovation for Our Energy Future 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Average October 2010 November 2010 December 2010 January 2011 February 2011 March 2011 April 2011 May 2011 June 2011 July 2011 August 2011 October 2010 – August 2011 Plug Load Power Density Note: The elevators are included in the plug loads Credit:MarjorieSchott/NREL Credit: Chad Lobato/NREL
  • 26. Innovation for Our Energy Future Operations Lessons – Plug loads 26 • Daytime loads lower than predicted • Model did not account for actual occupancy • Only ~75% of occupants actually at their desk any given day •Nighttime loads still difficult • Programmable outlets added after the fact • Automatic Laptop standby/hibernate functionality deployed system-wide • Monitors go to sleep well • Laptops have insomnia (except Macs) • Need a forced standby function and not rely on integrated windows standby • Ensure Wake-On-LAN functionality • Staff have not fully utilized desktop based power strip controls •Continued staff educational programs •Need to develop an optimal workstation plug load control system • Programmable power strips to disconnect all plugs at night? • Easy to use office plug load disconnect switch?
  • 27. Innovation for Our Energy Future Operations Lessons – Plug loads Cont.. 27 • 2 Refrigerators per break room sometimes excessive – Some groups unplug and don’t use second refrigerator • Utilize more switched outlets or controllable outlets • Or allow for programmable plugs • Energy Monitoring Displays on all night…
  • 28. Innovation for Our Energy Future Ice Machine Timed Outlet 28 • The devil is in the details… • Saved 52% energy use on an ENERGY STAR® ice machine with a $15 programmable outlet Credit: Chad Lobato/NREL
  • 29. Innovation for Our Energy Future 0 200 400 600 800 1000 1200 1400 12:00 AM 12:00 PM 12:00 AM 12:00 PM 12:00 AM 12:00 PM 12:00 AM 12:00 PM 12:00 AM 12:00 PM 12:00 AM 12:00 PM 12:00 AM 12:00 PM Power(W) Time of Day Uncontrolled Ice Machine Timer Controlled Ice Machine Weekly Energy Savings: 28.6 kWh Weekly Energy Savings: 52% Ice Machine Timed Outlet 29 Credit:ChadLobato/NREL
  • 30. Innovation for Our Energy Future October 2010 Plug Load Power Density 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads Credit: Chad Lobato/NREL
  • 31. Innovation for Our Energy Future November 2010 Plug Load Power Density 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads Credit: Chad Lobato/NREL
  • 32. Innovation for Our Energy Future December 2010 Plug Load Power Density 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads Credit: Chad Lobato/NREL
  • 33. Innovation for Our Energy Future January 2011 Plug Load Power Density 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads Credit: Chad Lobato/NREL
  • 34. Innovation for Our Energy Future February 2011 Plug Load Power Density 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads Credit: Chad Lobato/NREL
  • 35. Innovation for Our Energy Future March 2011 Plug Load Power Density Credit: Chad Lobato/NREL 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads
  • 36. Innovation for Our Energy Future April 2011 Plug Load Power Density Credit: Chad Lobato/NREL 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads
  • 37. Innovation for Our Energy Future May 2011 Plug Load Power Density Credit: Chad Lobato/NREL 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads
  • 38. Innovation for Our Energy Future June 2011 Plug Load Power Density Credit: Chad Lobato/NREL 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads
  • 39. Innovation for Our Energy Future July 2011 Plug Load Power Density Credit: Chad Lobato/NREL 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads
  • 40. Innovation for Our Energy Future August 2011 Plug Load Power Density Credit: Chad Lobato/NREL 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0 2 4 6 8 10 12 14 16 18 20 22 24 PowerDensity(W/ft2) Time of Day Model Weekday Plug Loads Model Weekend Plug Loads RSF Hourly Weekday Plug Loads RSF Average Weekday Plug Loads RSF Hourly Weekend Plug Loads RSF Average Weekend Plug Loads
  • 41. Innovation for Our Energy Future Operational Lessons- Datacenter 41 •Fully containing hot aisle difficult • Custom aisle floor and door seals • Ensure equipment designed for cold aisle containment • And installed to pull cold air – Not hot air… •Have run ~1.1-1.15 PUE •A few hot spots were driving up PUE… •Summer time PUE of 1.20 because of increased cooling •Starting to control hot aisle based on return temperature of ~80F •65 Watts/person to 38 Watts/person • But NREL has doubled in size • Modeled 65 watts/person for 1200 people • Using 38 watts/person for 2300 people NREL/PIX17897 Credit:MarjorieSchott/NREL
  • 42. Innovation for Our Energy Future42
  • 43. Innovation for Our Energy Future -20 -5 10 25 40 55 70 85 100 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 10/1/10 11/30/10 1/29/11 3/30/11 5/29/11 7/28/11 OutdoorTemperature(°F) PUE RSF Data Center PUE Outdoor Temperature Data Center PUE
  • 44. Innovation for Our Energy Future Monthly Average PUE 44 1.04 1.06 1.08 1.10 1.12 1.14 1.16 1.18 1.20 1.22 1.24 1.26 October 2010 November 2010 December 2010 January 2011 February 2011 March 2011 April 2011 May 2011 June 2011 July 2011 August 2011 PUE
  • 45. Innovation for Our Energy Future 10 Steps to Address PPLs 45 1. Establish a PPL Champion 2. Develop a Business Case 3. Benchmark Conventional Equipment and Operations 4. Identify Occupant’s Needs 5. Meet Needs as Efficiently as Possible 6. Turn It Off at Night 7. Design Team: Identify Applicable Strategies 8. Procurement Decisions and Policy 9. Address Unique PPLs 10. Occupant Awareness
  • 46. Innovation for Our Energy Future Step 1: Establish a PPL Champion Purpose: To initiate and help implement PPL strategies. Skills needed: • Understanding of: • technical energy efficiency opportunities • design strategies • Ability to: • apply business model • question operations, institutional policies, and procurement processes 46
  • 47. Innovation for Our Energy Future Step 2: Develop a business case for addressing PPLs Avoided Cost of Renewables (ACR): Equates the cost of PPL efficiency measures to avoided renewable costs. Gives all parties a financial incentive to investigate PPLs. ACR for the RSF: Used to justify demand-side efficiency measures. 1 Watt continuous saved = $33 worth of PV was avoided. Additional loads must be offset with renewables. The PV cost avoided by PPL reductions exceeded $4 million. 47Photo Credit: Dennis Schroeder PIX 17842
  • 48. Innovation for Our Energy Future Step 3: Benchmark your conventional equipment and operations Methods: • Submeter panels (if properly organized) • PPL power meters • Combination of submetering and equip. spec. sheets can be used Data: • Understand when equipment is used • Highlight opportunities to turn off • Basis of comparison for financial calculations 48Figure Credit: Microsoft Clip Art
  • 49. Innovation for Our Energy Future Step 4: Be willing to identify occupants’ true needs True need: Equipment or procedure required to achieve a given business goal or an assigned task. Understand: What do occupants produce as part of their jobs and what tools do they require? Every occupant, including those working in sensitive operations must be accounted for. Nonessential equipment: •A business case must be made for continued use. 49
  • 50. Innovation for Our Energy Future Step 5: Meet needs as efficiently as possible Search energy efficient equipment databases. Nonrated equipment: •Investigate the most efficient model •Turn off when not in use (if possible) Pay attention to parasitic loads. 50Photo Credit: Chad Lobato
  • 51. Innovation for Our Energy Future Step 6: Turning it all off Office buildings are typically unoccupied 66% of year. KEY: Reduce power density during nonbusiness hours. 51Photo Credit: Jennifer Schieb
  • 52. Innovation for Our Energy Future Step 7: Encourage the design team to identify all applicable PPL strategies Question standard specifications, operations, and design standards. Maximize space efficiency. Integrate PPL control strategies into the building’s electrical system: •Switches •Vacancy sensors •Timed disconnects for outlets •Controlling outlets through the Building Management System (BMS) Other loads: •Elevators •Transformers •Process cooling systems •Data centers 52
  • 53. Innovation for Our Energy Future Step 8: Institutionalize procurement decisions and policy programs Day-to-day energy efficiency: Depends on the decisions of occupants, facility managers, and owners. Identify decision makers who can: • Institutionalize PPL measures through procurement decisions and policy programs. • Promote buy-in. • Identify unbreakable and unchangeable policies. 53
  • 54. Innovation for Our Energy Future Step 9: Address unique miscellaneous PPLs EXAMPLE: Contractors and food service areas. Building owner can contractually require or provide the most efficient equipment available. Case-by-case evaluation: • Energy-efficient equipment may not be available and may be restricted from being turned off (e.g. ATM) • Manufacturers may be able to recommend alternatives. 54Photo Credit: Chad Lobato
  • 55. Innovation for Our Energy Future Step 10: Occupant awareness Encourage and allow to “do good”. PPL strategies should counteract “bad users.” Emphasize importance of turning off personal electronics when leaving a workspace. 55Photo Credit: Jennifer Scheib
  • 56. Innovation for Our Energy Future DOE Commercial Buildings Resource Database: Additional Plug Load Guidance Search for: • Plug or Miscellaneous Electric Load • Datacenter 56 http://apps1.eere.energy.gov/buildings/commercial/resource_database/
  • 57. Innovation for Our Energy Future Thanks and Questions Shanti Pless Shanti.pless@nrel.gov www.nrel.gov/rsf 57