There can be hardly any other field relevant to safety that has generated so much drafting and redrafting of standards
as Ex (explosion) protection. Every year sees more changes to existing regulations to ensure that only systems which
are truly explosion-proof are placed on the market. This is no simple matter for manufacturers, as the example of cable
glands demonstrates.
Preassembled cables can be fed through and reliably sealed by the UNI Ex-e II with its split sealing insertsCable glands certified
according to the latest Atex requirements
Certainly not explosive
The blueglobe HT Ex-e II with its black silicone sealing insert is approved for use in
potentially explosive atmospheres at ambient temperatures from -55 to +160 °C
Cable glands such as the blueglobe TRI Ex-e II with its surrounding TRI spring provide Ex protection even under EMC conditions: HF
shielding values are achieved right up into the GHz range A hole that is temporarily
not required can be fitted with an Ex cable gland with a blind plug instead of a separate, additional solid plug
Unnoticed but effective: the Ex-e vent connection allows air to circulate in the
housing without reducing the protection class The UNI Dicht 2M for applications
requiring large numbers of cable glands is likewise already certified in accordance with Atex
EU standards are constantly being updated to take new requirements into account. For manufacturers, this means the affected products
have to be recertified time and time again and any necessary modifications implemented.
All devices, protective systems and components for use in potentially explosive atmospheres must comply with the relevant EU directive
(94/9/EC). In technical literature, this directive is sometimes referred to as Atex 95 or the Atex Equipment Directive. The term Atex
(Atmosphères Explosibles) has been adopted in EC type examination certificates, which are issued based on the provisions of this EU
directive. The new EU directive 2014/34/EU has applied since April 2014. EC type examination certificates complying with the directive
have only been issued since this date.
The 94/9/EC directive sets out the requirements for equipment, safety systems and components for use in potentially explosive
atmospheres. It contains the basic safety requirements and applies to the design, construction and production phases of explosion-
protected equipment. This equipment is also subject to special monitoring during manufacturing in accordance with
DIN EN ISO/IEC 80079-34 to ensure "good" and appropriate manufacturing practices. The Atex Directive is mandatory for all member
states of the European Union (EU).
The 94/9/EC directive governs product approv-al and conformity procedures comprised of the EC type examination, quality monitoring,
the manufacturer or supplier's EC declaration of conformity and the CE marking. An EC type examination is required for all equipment
and protective systems intended for use in potentially explosive atmospheres (zones 0 and 1 = explosive due to the presence of gases
as well as zones 20 and 21 = explosive due to the presence of dusts). A manufacturer's declaration is sufficient only for class II 3G and
3D equipment or protective systems for use in Zones 2 and 22.
In order for an EC type examination certificate to be granted, the manufacturer or supplier must have an accredited quality assurance
system, certified in accordance with the ISO 9001 series of standards, in place for the production process. This QA system must include
the performance of an additional audit covering the special requirements relating to Ex equipment. Furthermore, all Pflitsch Ex versions
undergo a special quality assurance process.
No explosion from sparking
Only components certified in accordance with Atex may be used in potentially explosive atmospheres. Gases and dusts are prevented
from entering the housings and systems of such components, so that an explosion cannot occur in potentially explosive atmospheres as
a result of sparking. Cable glands are therefore very important in this situation, because they have to securely "close" the holes in the
housings through which the cables pass. In the lat-est versions of the EN 60079-0, EN 60079-7 and EN 60079-31 standards for cable
glands, Ex versions in the installed state must "prove" that they remain reliably sealed even when they age – i .e. after a long operating
life in a piece of plant or machinery – and that they continue to provide at least an IP 54 standard of seal as well as specific levels of
strain relief. The relevant allowable operating temperature is -20 to +60 °C.
For the manufacturer, this means that all products must undergo the complex certification procedure which the German manufacturer
Pflitsch recently completed for its UNI Dicht and blueglobe series in metal.
Three application-oriented series
Pflitsch cable glands are currently approved in accordance with this procedure for G (gas) and D (dust) applications in equipment class II
as well as in the e (increased safety for zones 1, 2, 21 and 22) and d (flameproof) types of protection. For the Ex e type of protection, the
UNI Dicht system includes metal (brass or stainless steel) Ex cable glands in sizes M10 to M80 or Pg 7 to Pg 48 that achieve IP 68 and
are approved for temperatures from -20 to +60 °C.
The blueglobe series in nickel-plated brass or stainless steel and sizes M12 to M85 is also certified according to Atex: its TPE sealing
insert is likewise approved for temperatures from -20 to +60 °C while the silicone HT insert can cope with anything from -55 to +160 °C.
IP 68 protection is achieved.
The manufacturer offers a series of metal (brass or stainless steel) Ex cable glands for the Ex d type of protection in sizes M16 to M100,
or on request with Pg, imperial or NPT connection threads, for armoured and non-armoured cables and wires. The UNI Dicht 2M series
is designed for applications involving large numbers of cable glands where high standards of seal and strain relief are called for
alongside durability. The main focus during the development of this product was on providing very large sealing ranges, i. e. one cable
gland size seals cables of any thickness. In addition, the materials used for the gland bodies and sealing inserts were optimised. The
resulting combination of shorter installed depths and small wrench sizes with closer hole centres produces highly compact installations.
UNI Dicht 2M in high-quality nickel-plated brass is initially available in four common sizes from M16 to M40 for cable diameters from 4 to
33.5 mm. In response to demand, an M50 size for even larger cable cross-sections is in preparation. The green TPE sealing insert sits in
such a way that it cannot turn in the double nipple and provides a reliable but gentle seal. UNI Dicht 2M has been tested to the latest
version of EN 60079.
In addition to Atex Ex-d and Ex-e, these cable glands are also approved in accordance with IECEx and EAC.
Sealing inserts replace Ex sealing plugs
Ex cable glands with solid sealing inserts are used to effectively seal unoccupied holes in housings with Ex e explosion protection. They
allow users the option of simply replacing the sealing insert if one or more wires or cables have to be fed into the housing at a later date.
A separate Ex sealing plug, which would normally be employed instead of a cable gland, is no longer necessary.
Since the protection demanded of housings is increasing, it is essential today that the air inside them can circulate. Pflitsch's solution for
this is a vent connection for the Ex e type of protection, which can simply be screwed into a hole in the housing.
Optimum safety: Ex and EMC protection
The various Atex-certified EMC cable glands are particularly worthy of mention: they provide explosion protection in combination with
efficient EMC safety. The 360° contact with the cable shielding braid via a surrounding spring allows the UNI Iris, UNI HF, UNI EMC
Dicht with double cone and Iris spring, and blue-globe TRI with triangular spring to achieve very high shielding values, which are higher
than those specified in the standard right up into the GHz range. Electromagnetic interference is effectively kept away from the system
electronics. In addition, these glands could not be simpler to install: the cable sheath only needs to be removed from the spring contact
point. The shielding braid remains intact and complete right up to the terminal in the housing. Certified solutions are also available for
steel-reinforced cables. As with the UNI Dicht modular system, Pflitsch offers a number of application-specific solutions, e. g. with pres-
sure screws for fixed or flexible cable layouts where special strain relief requirements apply, or with expanders or reducers to guide thick
or thin cables securely through a given hole size. Many products can be connected to protective tubing to provide mechanical protection
for the cable.

Weitere ähnliche Inhalte

Was ist angesagt?

Airex Manufacturing Pro System Kit www.airexmfg.com
Airex Manufacturing Pro System Kit   www.airexmfg.comAirex Manufacturing Pro System Kit   www.airexmfg.com
Airex Manufacturing Pro System Kit www.airexmfg.comAirex Manufacturing Inc
 
Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...
Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...
Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...Thorne & Derrick International
 
Sealing solutionsfor building and industrial installation
Sealing solutionsfor building and industrial installationSealing solutionsfor building and industrial installation
Sealing solutionsfor building and industrial installationMartin Franke
 
Cast resin bus duct
Cast resin bus ductCast resin bus duct
Cast resin bus ductAmy Song
 
Information infrared heater mirror infrared heater by celine infrapower infra...
Information infrared heater mirror infrared heater by celine infrapower infra...Information infrared heater mirror infrared heater by celine infrapower infra...
Information infrared heater mirror infrared heater by celine infrapower infra...Marina Infocenter
 
10 heb en_0703
10 heb en_070310 heb en_0703
10 heb en_0703Adit Group
 
Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...
Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...
Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...Thorne & Derrick UK
 
Natural Smoke And Heat Exhaust Systems
Natural Smoke And Heat Exhaust SystemsNatural Smoke And Heat Exhaust Systems
Natural Smoke And Heat Exhaust SystemsMaxpromotion
 
01 verso en_0703
01 verso en_070301 verso en_0703
01 verso en_0703Adit Group
 
Techsil OverTEC 5FR
Techsil OverTEC 5FRTechsil OverTEC 5FR
Techsil OverTEC 5FRTechsil Ltd
 
07 hek en_0703
07 hek en_070307 hek en_0703
07 hek en_0703Adit Group
 
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4Sarah Vanden Broeck
 

Was ist angesagt? (16)

Airex Manufacturing Pro System Kit www.airexmfg.com
Airex Manufacturing Pro System Kit   www.airexmfg.comAirex Manufacturing Pro System Kit   www.airexmfg.com
Airex Manufacturing Pro System Kit www.airexmfg.com
 
Airex Pro System Kit
Airex Pro System KitAirex Pro System Kit
Airex Pro System Kit
 
Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...
Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...
Abtech BPG (GRP) Fire Rated Electrical Enclosures & Junction Boxes For Hazard...
 
Sealing solutionsfor building and industrial installation
Sealing solutionsfor building and industrial installationSealing solutionsfor building and industrial installation
Sealing solutionsfor building and industrial installation
 
Cast resin bus duct
Cast resin bus ductCast resin bus duct
Cast resin bus duct
 
Flyer - Ex Equipment
Flyer - Ex EquipmentFlyer - Ex Equipment
Flyer - Ex Equipment
 
Cat. Solexin_english_4
Cat. Solexin_english_4Cat. Solexin_english_4
Cat. Solexin_english_4
 
Information infrared heater mirror infrared heater by celine infrapower infra...
Information infrared heater mirror infrared heater by celine infrapower infra...Information infrared heater mirror infrared heater by celine infrapower infra...
Information infrared heater mirror infrared heater by celine infrapower infra...
 
Fire Resistant Cable Joints
Fire Resistant Cable JointsFire Resistant Cable Joints
Fire Resistant Cable Joints
 
10 heb en_0703
10 heb en_070310 heb en_0703
10 heb en_0703
 
Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...
Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...
Asco Em WSEM Atex Iec ex Flameproof Explosion Proof Operator Hazardous Area S...
 
Natural Smoke And Heat Exhaust Systems
Natural Smoke And Heat Exhaust SystemsNatural Smoke And Heat Exhaust Systems
Natural Smoke And Heat Exhaust Systems
 
01 verso en_0703
01 verso en_070301 verso en_0703
01 verso en_0703
 
Techsil OverTEC 5FR
Techsil OverTEC 5FRTechsil OverTEC 5FR
Techsil OverTEC 5FR
 
07 hek en_0703
07 hek en_070307 hek en_0703
07 hek en_0703
 
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
 

Ähnlich wie Certainly not explosive (Eng)

Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueFlexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueThorne & Derrick International
 
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Thorne & Derrick International
 
ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016Ran Svarth
 
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...Thorne & Derrick International
 
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction BoxesAbtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction BoxesThorne & Derrick International
 
Bosch - Procter - Guarding1
Bosch - Procter - Guarding1Bosch - Procter - Guarding1
Bosch - Procter - Guarding1Daniel Ruell
 
Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors
Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors
Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors Thorne & Derrick International
 
Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...
Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...
Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...Thorne & Derrick UK
 
BARTEC NASP_Company Profile (2017)
BARTEC NASP_Company Profile (2017)BARTEC NASP_Company Profile (2017)
BARTEC NASP_Company Profile (2017)Davide Baccino
 
Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet
Eltherm ELK-AG-N Heat Trace Cable - Spec SheetEltherm ELK-AG-N Heat Trace Cable - Spec Sheet
Eltherm ELK-AG-N Heat Trace Cable - Spec SheetThorne & Derrick UK
 
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...Thorne & Derrick International
 
UK Plus Brochure
UK Plus Brochure UK Plus Brochure
UK Plus Brochure Schiedel UK
 
Ensto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable TerminationsEnsto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable TerminationsThorne & Derrick International
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Thorne & Derrick International
 
Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...
Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...
Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...Thorne & Derrick International
 
Flexible Liners installation instructions
Flexible Liners installation instructionsFlexible Liners installation instructions
Flexible Liners installation instructionsSchiedel UK
 

Ähnlich wie Certainly not explosive (Eng) (20)

Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueFlexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
 
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
 
Catalogo40 productos gis
Catalogo40 productos gisCatalogo40 productos gis
Catalogo40 productos gis
 
ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016
 
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
 
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction BoxesAbtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
 
Bosch - Procter - Guarding1
Bosch - Procter - Guarding1Bosch - Procter - Guarding1
Bosch - Procter - Guarding1
 
The Elektro Tipp - Cable Entry Systems
The Elektro Tipp - Cable Entry SystemsThe Elektro Tipp - Cable Entry Systems
The Elektro Tipp - Cable Entry Systems
 
Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors
Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors
Cablofil EZ Path Fire Protection Seals for Fire Barrier Walls & Floors
 
Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...
Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...
Bernstein Inductive Proximity Sensors, Capacitive Sensors, Ultrasonic Sensors...
 
BARTEC NASP_Company Profile (2017)
BARTEC NASP_Company Profile (2017)BARTEC NASP_Company Profile (2017)
BARTEC NASP_Company Profile (2017)
 
Ip68
Ip68Ip68
Ip68
 
Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet
Eltherm ELK-AG-N Heat Trace Cable - Spec SheetEltherm ELK-AG-N Heat Trace Cable - Spec Sheet
Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet
 
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
 
Monolite SLA RANGE
Monolite SLA RANGEMonolite SLA RANGE
Monolite SLA RANGE
 
UK Plus Brochure
UK Plus Brochure UK Plus Brochure
UK Plus Brochure
 
Ensto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable TerminationsEnsto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable Terminations
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
 
Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...
Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...
Captrad Cable Systems - GRP Cable Tray, GRP Cable Troughs, Recycled Plastic C...
 
Flexible Liners installation instructions
Flexible Liners installation instructionsFlexible Liners installation instructions
Flexible Liners installation instructions
 

Mehr von ie-net ingenieursvereniging vzw

Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)ie-net ingenieursvereniging vzw
 
Hoe maak ik de omgeving van mijn opslagtank veilig efficient
Hoe maak ik de omgeving van mijn opslagtank veilig  efficientHoe maak ik de omgeving van mijn opslagtank veilig  efficient
Hoe maak ik de omgeving van mijn opslagtank veilig efficientie-net ingenieursvereniging vzw
 
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)ie-net ingenieursvereniging vzw
 
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)ie-net ingenieursvereniging vzw
 

Mehr von ie-net ingenieursvereniging vzw (20)

Ultrasoon_Clamp-on.pdf
Ultrasoon_Clamp-on.pdfUltrasoon_Clamp-on.pdf
Ultrasoon_Clamp-on.pdf
 
Elektromagnetische_debietmeters.pdf
Elektromagnetische_debietmeters.pdfElektromagnetische_debietmeters.pdf
Elektromagnetische_debietmeters.pdf
 
SGS Skybase (NL) .pdf
SGS Skybase (NL) .pdfSGS Skybase (NL) .pdf
SGS Skybase (NL) .pdf
 
VEGA-Radar vs US-26APR2022-NL.pdf
VEGA-Radar vs US-26APR2022-NL.pdfVEGA-Radar vs US-26APR2022-NL.pdf
VEGA-Radar vs US-26APR2022-NL.pdf
 
From process to emission
From process to emissionFrom process to emission
From process to emission
 
Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)
 
Connecting fieldbus power and knowledge
Connecting fieldbus power and knowledgeConnecting fieldbus power and knowledge
Connecting fieldbus power and knowledge
 
Frequentieregelaars
FrequentieregelaarsFrequentieregelaars
Frequentieregelaars
 
Breekplaten beademingsmachines vlamdover (NED.)
Breekplaten beademingsmachines vlamdover (NED.)Breekplaten beademingsmachines vlamdover (NED.)
Breekplaten beademingsmachines vlamdover (NED.)
 
Veiligheden rond de tank
Veiligheden rond de tankVeiligheden rond de tank
Veiligheden rond de tank
 
Veiligheden rond de tank
Veiligheden rond de tankVeiligheden rond de tank
Veiligheden rond de tank
 
Hima cyber security
Hima cyber securityHima cyber security
Hima cyber security
 
Vik g.haekens-atex risico evaluatie
Vik g.haekens-atex risico evaluatieVik g.haekens-atex risico evaluatie
Vik g.haekens-atex risico evaluatie
 
Hoe maak ik de omgeving van mijn opslagtank veilig efficient
Hoe maak ik de omgeving van mijn opslagtank veilig  efficientHoe maak ik de omgeving van mijn opslagtank veilig  efficient
Hoe maak ik de omgeving van mijn opslagtank veilig efficient
 
Checklist tankcontrole 2018 bacd
Checklist tankcontrole 2018 bacdChecklist tankcontrole 2018 bacd
Checklist tankcontrole 2018 bacd
 
Controle en ingebruikname van uw opslagtank
Controle en ingebruikname van uw opslagtankControle en ingebruikname van uw opslagtank
Controle en ingebruikname van uw opslagtank
 
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
 
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
 
Tuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentationTuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentation
 
Pressure Relief Devices
Pressure Relief DevicesPressure Relief Devices
Pressure Relief Devices
 

Kürzlich hochgeladen

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 

Kürzlich hochgeladen (20)

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 

Certainly not explosive (Eng)

  • 1. There can be hardly any other field relevant to safety that has generated so much drafting and redrafting of standards as Ex (explosion) protection. Every year sees more changes to existing regulations to ensure that only systems which are truly explosion-proof are placed on the market. This is no simple matter for manufacturers, as the example of cable glands demonstrates. Preassembled cables can be fed through and reliably sealed by the UNI Ex-e II with its split sealing insertsCable glands certified according to the latest Atex requirements Certainly not explosive The blueglobe HT Ex-e II with its black silicone sealing insert is approved for use in potentially explosive atmospheres at ambient temperatures from -55 to +160 °C Cable glands such as the blueglobe TRI Ex-e II with its surrounding TRI spring provide Ex protection even under EMC conditions: HF
  • 2. shielding values are achieved right up into the GHz range A hole that is temporarily not required can be fitted with an Ex cable gland with a blind plug instead of a separate, additional solid plug Unnoticed but effective: the Ex-e vent connection allows air to circulate in the housing without reducing the protection class The UNI Dicht 2M for applications requiring large numbers of cable glands is likewise already certified in accordance with Atex EU standards are constantly being updated to take new requirements into account. For manufacturers, this means the affected products have to be recertified time and time again and any necessary modifications implemented. All devices, protective systems and components for use in potentially explosive atmospheres must comply with the relevant EU directive (94/9/EC). In technical literature, this directive is sometimes referred to as Atex 95 or the Atex Equipment Directive. The term Atex (Atmosphères Explosibles) has been adopted in EC type examination certificates, which are issued based on the provisions of this EU directive. The new EU directive 2014/34/EU has applied since April 2014. EC type examination certificates complying with the directive have only been issued since this date. The 94/9/EC directive sets out the requirements for equipment, safety systems and components for use in potentially explosive atmospheres. It contains the basic safety requirements and applies to the design, construction and production phases of explosion- protected equipment. This equipment is also subject to special monitoring during manufacturing in accordance with DIN EN ISO/IEC 80079-34 to ensure "good" and appropriate manufacturing practices. The Atex Directive is mandatory for all member states of the European Union (EU).
  • 3. The 94/9/EC directive governs product approv-al and conformity procedures comprised of the EC type examination, quality monitoring, the manufacturer or supplier's EC declaration of conformity and the CE marking. An EC type examination is required for all equipment and protective systems intended for use in potentially explosive atmospheres (zones 0 and 1 = explosive due to the presence of gases as well as zones 20 and 21 = explosive due to the presence of dusts). A manufacturer's declaration is sufficient only for class II 3G and 3D equipment or protective systems for use in Zones 2 and 22. In order for an EC type examination certificate to be granted, the manufacturer or supplier must have an accredited quality assurance system, certified in accordance with the ISO 9001 series of standards, in place for the production process. This QA system must include the performance of an additional audit covering the special requirements relating to Ex equipment. Furthermore, all Pflitsch Ex versions undergo a special quality assurance process. No explosion from sparking Only components certified in accordance with Atex may be used in potentially explosive atmospheres. Gases and dusts are prevented from entering the housings and systems of such components, so that an explosion cannot occur in potentially explosive atmospheres as a result of sparking. Cable glands are therefore very important in this situation, because they have to securely "close" the holes in the housings through which the cables pass. In the lat-est versions of the EN 60079-0, EN 60079-7 and EN 60079-31 standards for cable glands, Ex versions in the installed state must "prove" that they remain reliably sealed even when they age – i .e. after a long operating life in a piece of plant or machinery – and that they continue to provide at least an IP 54 standard of seal as well as specific levels of strain relief. The relevant allowable operating temperature is -20 to +60 °C. For the manufacturer, this means that all products must undergo the complex certification procedure which the German manufacturer Pflitsch recently completed for its UNI Dicht and blueglobe series in metal. Three application-oriented series Pflitsch cable glands are currently approved in accordance with this procedure for G (gas) and D (dust) applications in equipment class II as well as in the e (increased safety for zones 1, 2, 21 and 22) and d (flameproof) types of protection. For the Ex e type of protection, the UNI Dicht system includes metal (brass or stainless steel) Ex cable glands in sizes M10 to M80 or Pg 7 to Pg 48 that achieve IP 68 and are approved for temperatures from -20 to +60 °C. The blueglobe series in nickel-plated brass or stainless steel and sizes M12 to M85 is also certified according to Atex: its TPE sealing insert is likewise approved for temperatures from -20 to +60 °C while the silicone HT insert can cope with anything from -55 to +160 °C. IP 68 protection is achieved. The manufacturer offers a series of metal (brass or stainless steel) Ex cable glands for the Ex d type of protection in sizes M16 to M100, or on request with Pg, imperial or NPT connection threads, for armoured and non-armoured cables and wires. The UNI Dicht 2M series is designed for applications involving large numbers of cable glands where high standards of seal and strain relief are called for
  • 4. alongside durability. The main focus during the development of this product was on providing very large sealing ranges, i. e. one cable gland size seals cables of any thickness. In addition, the materials used for the gland bodies and sealing inserts were optimised. The resulting combination of shorter installed depths and small wrench sizes with closer hole centres produces highly compact installations. UNI Dicht 2M in high-quality nickel-plated brass is initially available in four common sizes from M16 to M40 for cable diameters from 4 to 33.5 mm. In response to demand, an M50 size for even larger cable cross-sections is in preparation. The green TPE sealing insert sits in such a way that it cannot turn in the double nipple and provides a reliable but gentle seal. UNI Dicht 2M has been tested to the latest version of EN 60079. In addition to Atex Ex-d and Ex-e, these cable glands are also approved in accordance with IECEx and EAC. Sealing inserts replace Ex sealing plugs Ex cable glands with solid sealing inserts are used to effectively seal unoccupied holes in housings with Ex e explosion protection. They allow users the option of simply replacing the sealing insert if one or more wires or cables have to be fed into the housing at a later date. A separate Ex sealing plug, which would normally be employed instead of a cable gland, is no longer necessary. Since the protection demanded of housings is increasing, it is essential today that the air inside them can circulate. Pflitsch's solution for this is a vent connection for the Ex e type of protection, which can simply be screwed into a hole in the housing. Optimum safety: Ex and EMC protection The various Atex-certified EMC cable glands are particularly worthy of mention: they provide explosion protection in combination with efficient EMC safety. The 360° contact with the cable shielding braid via a surrounding spring allows the UNI Iris, UNI HF, UNI EMC Dicht with double cone and Iris spring, and blue-globe TRI with triangular spring to achieve very high shielding values, which are higher than those specified in the standard right up into the GHz range. Electromagnetic interference is effectively kept away from the system electronics. In addition, these glands could not be simpler to install: the cable sheath only needs to be removed from the spring contact point. The shielding braid remains intact and complete right up to the terminal in the housing. Certified solutions are also available for steel-reinforced cables. As with the UNI Dicht modular system, Pflitsch offers a number of application-specific solutions, e. g. with pres- sure screws for fixed or flexible cable layouts where special strain relief requirements apply, or with expanders or reducers to guide thick or thin cables securely through a given hole size. Many products can be connected to protective tubing to provide mechanical protection for the cable.