SlideShare ist ein Scribd-Unternehmen logo
1 von 10
TR19
Regulations
Free guide for compliance cleaning

the
Guide to Good Practice Internal Cleanliness of Ventilation
Specific Considerations for Kitchen Extract Systems
7.1 The kitchen extract system presents particular hazards due tothe potential for the
accumulation of grease. Accumulated grease within an extract system forms a hidden
combustion load. Under certain circumstances flame or very high temperature within the duct
can ignite the grease causing fire to spread rapidly through the duct.
Flame and heat within the duct can ignite surrounding materials at
various points along the ductwork path and transfer fire in ways that
are difficult to predict and control by designers, installers and
ultimately fire fighters.
7.2 Kitchen extract ventilation systems are defined here as the extract
systems intended to collect and remove contaminants, heat and
moisture from cooking appliances (See also DW/172). A kitchen extract
system wouldn’t typically comprise of the following components:Canopy
Also referred to as hood, canopy hood, extraction hood, cooking hood, cooker hood, cooking
canopy or extraction canopy. This would most likely include a vertical canopy skirt running
around the perimeter of the canopy. Channel on the bottom edge of the skirt; a canopy roof
sitting horizontally on the top of and joining the skirts; a grease filter housing assembly (with
grease filters and traps) hanging within the boundary of the skirts.
Canopy/Extract plenum
This is typically the area immediately behind the grease filter housing and below where the
ducting commences.
Ducting
Beyond the canopy/extract plenum, extraction ductwork would be connected. This may involve
short transition ducts connected directly to the suction side of an extract fan or could include
many linear metres of horizontal and/or vertical ductwork. Vertical ductwork, also referred to as
riser may pass through many levels of a building.
Contained within the ducting there may be attenuators, flow control dampers, fire dampers, air
turning vanes and sensors.
Extract Fan
To create extraction from the canopy an extract fan would be connected to the ductwork, some
extract fans (roof mounted) discharge directly to atmosphere via a cowl.
Discharge Duct
On the exhaust side of the fan a discharge duct would direct extract air out of the building via
an outlet. This outlet point may include weather louvres and mesh to prevent the ingress of
weather and vermin. Other systems such as ventilated ceilings and directly ducted extraction are
also used. It is important that the person responsible for implementing cleaning regimes clearly
understands the breakdown of the system so that any cleaning regime is compliant with the
terms of buildings insurance relevant to the kitchen extract maintenance.
7.3 Other extraction systems serving the cooking area, such as potwash/dishwash systems,
general extraction etc. may also be affected by grease deposits and similar considerations will
apply.
7.4 Kitchen extract systems are liable to internal fouling by grease and oils. It is usual for the
systems to be protected by grease filters, but these differ widely in terms of efficiency of grease
removal and of barrier to flame. Total grease removal is not normally feasible and therefore
fouling of systems downstream will occur to a greater or lesser degree.
7.5 Grease deposits within systems also pose hygiene, odour, vermin and mechanical efficiency
hazards. Poorly designed and installed or damaged ductwork can leak grease, thus extending the
fire risk, hygiene, odour and vermin hazards. Also, where ductwork distorts under fire conditions,
burning grease can leak out and spread the fire to duct surroundings.
7.6 Supply or make-up ventilation systems should be maintained in hygienic condition as detailed
in this Guide. Due to the accumulated grease within extract systems, the majority of the
duct - work cleaning will be by manual rather than mechanical methods. At the time of system
survey, a detailed schematic should be provided, highlighting any areas which are inaccessible
and therefore, will remain uncleaned. The client must be advised of any inaccessible areas, the
reason for their inaccessibility and, if possible, the likely cost to provide full and free access.
It is the clients responsibility to highlight this to their insurer or other relevant third party, if
required, who must confirm whether an exception to the total cleaning in accordance with TR/19
is acceptable.
7.7 This section of the Guide provides specific advice on how to clean and maintain kitchen
extract systems, but similar consideration will apply to non kitchen areas that might be affected
by grease and/or oil deposits.

Design and access to the Internal Surfaces of the
Kitchen Extract
7.8 Advice is provided in B&ES/HVCA DW/172: Specification for kitchen ventilation system (2005)
7.9 Internal surfaces of kitchen extract systems should be free of irregularities, all of which make
grease accumulation more likely and cleaning more difficult.
7.10 It is essential that a kitchen extract ductwork system, and canopy/extract plenum, is
provided with access panels of sufficient number, quality and size to
enable unrestricted access for regular cleaning and inspection of the
internal surfaces and in-line components.
7.11 Location of access to the internal surfaces of a kitchen extract
system is dependent on a number of design and operational
considerations

•	
•	
•	
•	
•	
•	
•	

Design and location of ductwork
Building design and construction materials
Location of kitchen within the building
Location of extract fan and accessibility for maintenance
Accessibility to physically reach the ductwork
Any building modifications and current uses that may restrict access
Location and number of system components requiring access.

7.12 Access panels should be suitable for the purpose for which they are intended. The panels
and frames should be constructed of the same material as the ductwork. As a minimum they
should incorporate quick release catches, sealing gasket and thermal, acoustic and fire rated
insulation properties equal tothat of the duct to which they are fitted. Particular consideration
must be given to maintaining the fire integrity of fire rated ductwork. The recommendations of
the manufacturer or specialist fire protection adviser should be followed where appropriate.
7.13 Access panels should be as large as the duct size permits to a maximum of 460mm x 610mm
without weakening the structure of the system. Openings should not be obstructed by other
building services, stored equipment or by the fabric of the building. The panel and aperture
should be free of any sharp edges.
7.14 Access panels should be fitted at the side of the duct, a minimum of 10mm above the base to
minimise the risk of grease leakage. Exceptionally, they may be fitted on the top of the duct, but
due consideration should be given to the accessibility of the panel. Where access panels must be
fitted to the underside of a duct, particular care must be taken to ensure a leakfree fit and notice
should be affixed warning of the risk of oil being released on opening the panels. In designing
systems due consideration should be given to providing physical unobstructed access to all
access panels.
7.15 Access panels should be fitted on either side of in-line components, as detailed in Table 8,
to allow physical entry to clean these intricate surfaces. This Table includes components, such as
fire dampers and attenuators, which are not normally recommended to be installed, but are often
found in practice.
This has a significant impact on installations such as ventilation extractions where a significant
risk exists if the installation fails.
Table 8: Location of Access Panels for Cleaning and Inspection Purposes
Volume Control Dampers

Both sides

Fire Dampers

Both sides

Attenuators

Both sides

Changes in Direction

Both sides

Filter Sections

Both sides

Horizontal Ducts

Generally every 3 metres
(see Note 2)

Risers

Top and bottom as a minimum
(see Note 3)

Extract Fans

Both sides (see Note 4)

Discharge grille/mesh

One side

Notes to Table 8
1.	 Additional builders work hatches may need to be fitted in ceilings/walls in existing
installations, or provided for in new constructions. Consideration should also be given to safe
high level access to external ductwork.
2.	 Access openings for cleaning purposes are generally required at a maximum of 3 metre
centres and/or at each change of direction. This distance should be reduced where the size of
the duct prevents adequate cleaning by hand, where there are several changes in direction or
where other external features restrict the positioning of panels.
3.	 Internal kitchen extract risers often require access doors fitted on at least each floor level so
that all internal surfaces can be reached and fire dampers, where fitted, cleaned and checked.
In older buildings this may require additional builders works (e.g. hatches through brickwork)
to reach the riser ducts (see 7.6).
4.	 Extract fan design should allow thorough cleaning of impellor blades and internal surfaces
without the need for dismantling, i.e. ductwork with access panels should be provided
immediately upstream and downstream. Larger fans should be designed with panels in the
casing. Similarly, attenuators or other in-line fittings likely to obscure cleaning activity should
be provided with access on both sides.

System Testing (Inspection/Monitoring)
7.18 The Health & Safety Executive and industry and insurance guidance and regulations (see
Appendices B&ES) stipulate that kitchen extract systems should be kept clean to minimise fire
and other risks.
This Guide now provides a method of measuring and defining cleanliness
and dirtiness as a benchmark for good practice.
7.19 The Cleaning Guys has investigated a variety of methods for
testing ductwork system internal surfaces to measure grease deposits
and recommends the Wet Film Thickness Test (W.F.T.T) measurement
method. This method is described in Appendix D.3.
7.20 The Deposit Thickness Test (D.T.T), as described in Section 5, may also be used and may
be necessary in the case of extremely hardbaked, carbonised, deposits and the funding of
hard-baked deposits would normally indicate a requirement to clean or in the case of cleanliness
verification a requirement to reclean.
7.21 The testing methods provide an objective, repeatable and verifiable measurement of grease
deposits, and over come the subjectivity of visual inspection alone.
7.22 It is recommended that testing be carried out at intervals not exceeding 12 months.
Monitoring of grease deposits may need to be carried out more frequently if it is necessary to
establish a precise definition of required cleaning frequencies. The cleaning frequency required
should be estimated by a specialist service provider and/or client on initial inspection or
assessment and subsequent pre-clean testing will confirm whether the initial predicted frequency
is correct or requires adjustment.
7.23 Measurements should be taken at the following locations where practicable:
•	
•	
•	
•	
•	
•	

Canopy/Extract plenum behind filters
Duct 1 metre from canopy
Duct 3 metres from canopy
Duct midway between canopy and fan
Duct upstream of fan
Discharge duct downstream of fan

7.24 Table 9 sets out guideline maximum levels of grease deposit and actions recommended.
The actual recommended action timing will depend on the rate of accumulation, the risk
vulnerability of the system and site and any particular warranties imposed by the building
insurers.
Table 9: Surface Grease Deposit Limits
Wet Film Thickness Test Measurement

Recommended Action

200μm as a mean across the system

Complete cleaning required

Any single measurement above 500μm

Urgent local cleaning required

Notes to Table 9
1.	 In the abscence of, and the likely theoretical difficulties of an absolute measure of the
flammability of various quantities of grease deposit, the surface grease deposit limits are
given in Table 9 and paragraph 7.42.
2.	 These levels were determined by extensive field testing to measure at what levels good
practice employers, or operators of systems, carry out system cleaning and what levels of
cleanliness are normally achieved by specialist duct cleaners using available cleaning and
measurement technology within reasonable economic bounds.
3.	 The mean measurement is calculated by dividing the total of the test results by the number of
testing locations.
4.	 The second category of any single measurement above 500um is provided to cater for local
“hot spots” which should be cleaned even where the whole system does not require complete
cleaning. Examples might be immediately local to a canopy or at a fan.
5.	 The extent of urgent local cleaning precipitated by the presence of grease deposits above
500um should be subject to reasonable appreciation of the extent of fouling and risk posed.
7.25 The surface grease deposits limits should not be confused with the level set for Post - Clean
verification which is far more stringent and detailed in paragraph 7.42.
7.26 Stand-alone, regular or post-clean testing can usefully be combined with inspection of other
kitchen extract system safety issues. If specifi ed by a client, a service provider should provide
evidence of competence to carry out such inspection. Such inspection should include, but not be
restricted to:
1.	 Adequacy of filters and their regular maintenance
2.	 Adequacy of regular cleaning of canopy, and associated drains and traps
3.	 Existence and visual condition of any fire suppression or detection system
4.	 Damage to fire protection
5.	 Ductwork grease leakage
6.	 Ductwork damage
7.	 Damage to or inappropriate ductwork fixtures
8.	 Visual/audible check of fan operation
9.	 Rubbish/debris adjacent to system
10.	Visual assessment of any special filtration
11.	 Discharge condition, including grease splatter/staining
7.27 Such inspection should not be regarded as a substitute for proper maintenance of plant
such as fans and fire suppression or detection systems.

Cleaning Methods
7.28 This guide is not intended to be definitive in relation to the method of cleaning, as there are
many existing methods that can be applied in tandem, and emergent new
technologies. Examples of cleaning methods are listed in Table 10.
7.29 To conform with the Guide, the actual method or methods must
be capable of achieving the required results, i.e. Post-Clean Verification,
not only on the internal surfaces of the extract duct but also on system
components.
7.30 When choosing the cleaning method, consideration should be given to operative safety and
also to effects on the surrounding environment, particularly where using wet cleaning methods,
since grease/moisture can leak from the ductwork components and damage the surrounding
fabric.
Table 10: Examples of Cleaning Methodology
Generic Name

Energy Source

Removal Method

Hand wipe

Manual

Wiping the surface of the ductwork

Hand scrape

Manual

Removing heavy deposits by hand
scraping

Chemical

Manual

Softens or dissolves deposits making
them suitable for hand scraping

High pressure water
wash (steam)

Electrical or compressed air

Vapour or liquid expelled at
high pressure from lance to
dislodge/ dissolve deposits

Blasting (remote or direct)
using suitable medium as
appropriate

Compressed air

Blasting medium dislodges
contaminant from duct and
component surfaces to be removed
via vacuum techniques or high
volume filtered extraction.

7.31 Steam cleaning and high pressure water washing are not recommended for ductwork that is
situated above false ceilings or in sensitive areas, due to possible leakage of contaminants from
the duct, unless specifically designed for wet cleaning.
7.32 After applying wet cleaning methods care should be taken to ensure that any condensed
vapours and cleaning fluids are removed from all parts of the system.
7.33 The use of chemical cleaning agents should only be considered where a risk/COSHH
assessment has been carried out (See Section 10), the details recorded and the effects of the
applied chemicals have been assessed on the material construction, environment and for hazards
to cleaning personnel.
7.34 It should be noted that it is not normally economically practicable to clean kitchen extract
systems to a “like new” bright metal condition due to substratestaining.
Frequency of Cleaning
7.35 The need for specialist cleaning of extract systems will depend on the level of usage of the
cooking equipment, types and quantity of cooking and other risk factors such as vulnerability of
the system to ignition and of the building and its occupant/users to system fire, hygiene, vermin
and mechanical hazards. Typical cleaning intervals are shown in Table 11:
Table 11: Frequency of Cleaning
Heavily Use

12-16 hours per day

- 3 monthly

Moderately Use

6-12 hours per day

- 6 monthly

Light Use

2-6 hours per day

-12 monthly

Notes to Table 11
The canopy and canopy/extract plenum is an area of higher fire risk and consideration should be
given to more frequent cleaning in accordance with insurance requirements (see 7.39)
7.36 The frequency of cleaning should be adjusted by means of system testing (inspection/
monitoring) - see paragraph 7.23, so that surface grease deposit limits in Table 9 are not
exceeded. The buildings insurance company should be consulted to ensure that the cleaning
regime is compliant with the terms of their specific warranty.
7.37 Any cleaning regime should be justified by a considered risk assessment. (The latest Fire
Precautions Workplace, and Management of Health & Safety at Work Regulations apply).
7.38 Regular cleaning will result in an improved mean standard and reduce the costs of cleaning
as deposits are not allowed to bake and harden.
7.39 Periodic specialist cleaning should be accompanied by daily or weekly cleaning of canopies,
filters and associated drains and traps in accordance with manufacturers’ recommendations,
typically carried out by the kitchen operator.
Post-Clean Verification of Cleanliness
7.40 The primary method of assessment is visual. For cleaned system verification, the surface
should be visibly clean and capable of meeting the level of cleanliness specified.
7.41 Verification of cleanliness should be by means of the Deposit Thickness Test or Wet Film
Thickness Test as detailed in System Testing (Inspection/Monitoring) at paragraph.
7.42 The level of cleanliness is that no single measurement should exceed 50μm.
7.43 On completion a report should be provided containing the following:The system(s) cleaned
•	 Pre-clean measurements (as per System Testing)
•	 Post-clean measurements
•	 Photographic records
•	 Additional works carried out (if any)
•	 COSHH data on any chemicals used
•	 Recommendations for future cleaning requirements
•	 Observations on the condition of the ductwork system
7.44 If specified, additional kitchen extract safety issues should also be reported (as outlined in
paragraph 7.26).
7.45 The Post-Clean Verification of Cleanliness report should assist to serve as evidence of
system status to insurance assessors, Environmental Health Officers, landlord’s agents, etc.
For further information:
Pathway Cleaning Ltd
Lamoc House
7-9 Summer Hill Terrace
Birmingham B1 3RA
Telephone: 0121 236 1448 and 0121 236 4050
www.pathwaycleaning.co.uk • www.thecleaningguys.co.uk

Weitere ähnliche Inhalte

Was ist angesagt?

Quality assurance maintenance of hvac system in pharmaceutical industry
Quality assurance maintenance of hvac system in pharmaceutical industryQuality assurance maintenance of hvac system in pharmaceutical industry
Quality assurance maintenance of hvac system in pharmaceutical industryShahbazNadaf
 
Theatre design and ventilation
Theatre design and ventilationTheatre design and ventilation
Theatre design and ventilationLokesh Sharoff
 
Air circulation maintenance industry for sterile and non sterile area
Air circulation maintenance  industry for sterile and non sterile areaAir circulation maintenance  industry for sterile and non sterile area
Air circulation maintenance industry for sterile and non sterile areaGNIPST
 

Was ist angesagt? (7)

08 cleanroom
08 cleanroom08 cleanroom
08 cleanroom
 
Hvac basics
Hvac basicsHvac basics
Hvac basics
 
Hvac
HvacHvac
Hvac
 
Quality assurance maintenance of hvac system in pharmaceutical industry
Quality assurance maintenance of hvac system in pharmaceutical industryQuality assurance maintenance of hvac system in pharmaceutical industry
Quality assurance maintenance of hvac system in pharmaceutical industry
 
Kitchen Exhaust India
Kitchen Exhaust IndiaKitchen Exhaust India
Kitchen Exhaust India
 
Theatre design and ventilation
Theatre design and ventilationTheatre design and ventilation
Theatre design and ventilation
 
Air circulation maintenance industry for sterile and non sterile area
Air circulation maintenance  industry for sterile and non sterile areaAir circulation maintenance  industry for sterile and non sterile area
Air circulation maintenance industry for sterile and non sterile area
 

Ähnlich wie Pathway Cleaning - TR19 regulations - Ductwork Clean - Extraction Clean

TR19 Regulations - B&ES Guide to Good Practice - London & Midland Cleaning C...
TR19 Regulations - B&ES Guide to Good Practice -  London & Midland Cleaning C...TR19 Regulations - B&ES Guide to Good Practice -  London & Midland Cleaning C...
TR19 Regulations - B&ES Guide to Good Practice - London & Midland Cleaning C...The Pathway Group
 
Chapter 8 duct design and sealing
Chapter 8 duct design and sealingChapter 8 duct design and sealing
Chapter 8 duct design and sealingsahiloct11969
 
Applying design and construction standards to successfully build a cleanroom ...
Applying design and construction standards to successfully build a cleanroom ...Applying design and construction standards to successfully build a cleanroom ...
Applying design and construction standards to successfully build a cleanroom ...alone160162
 
S3 Supply Air Duct System Assignment
S3 Supply Air Duct System AssignmentS3 Supply Air Duct System Assignment
S3 Supply Air Duct System Assignmentno suhaila
 
building services
building servicesbuilding services
building servicesszelun
 
Guidelines for airbone infection isolation room
Guidelines for airbone infection isolation roomGuidelines for airbone infection isolation room
Guidelines for airbone infection isolation roompekka ilmaranta
 
Natural ventilation, Artificial ventilation, Air conditioning
Natural ventilation, Artificial ventilation, Air conditioningNatural ventilation, Artificial ventilation, Air conditioning
Natural ventilation, Artificial ventilation, Air conditioningSusmitaMulayPatil
 
1603104213-hatchery-planning-design-and-construction.pptx
1603104213-hatchery-planning-design-and-construction.pptx1603104213-hatchery-planning-design-and-construction.pptx
1603104213-hatchery-planning-design-and-construction.pptxMkulimaHodari1
 
Hvca presentation ag-revised-dec09 2
Hvca presentation ag-revised-dec09 2Hvca presentation ag-revised-dec09 2
Hvca presentation ag-revised-dec09 2IndepthHygiene
 
298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf
298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf
298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdfAhmadHamouda3
 
Building Services 1 Report
Building Services 1 ReportBuilding Services 1 Report
Building Services 1 ReportMelvin Lim
 
VENTILATION.pdf
VENTILATION.pdfVENTILATION.pdf
VENTILATION.pdfKishAgrwa1
 
HVAC Install - Trust But Verify
HVAC Install  - Trust But VerifyHVAC Install  - Trust But Verify
HVAC Install - Trust But VerifyERH West
 

Ähnlich wie Pathway Cleaning - TR19 regulations - Ductwork Clean - Extraction Clean (20)

TR19 Regulations - B&ES Guide to Good Practice - London & Midland Cleaning C...
TR19 Regulations - B&ES Guide to Good Practice -  London & Midland Cleaning C...TR19 Regulations - B&ES Guide to Good Practice -  London & Midland Cleaning C...
TR19 Regulations - B&ES Guide to Good Practice - London & Midland Cleaning C...
 
DW172
DW172DW172
DW172
 
Chapter 8 duct design and sealing
Chapter 8 duct design and sealingChapter 8 duct design and sealing
Chapter 8 duct design and sealing
 
Applying design and construction standards to successfully build a cleanroom ...
Applying design and construction standards to successfully build a cleanroom ...Applying design and construction standards to successfully build a cleanroom ...
Applying design and construction standards to successfully build a cleanroom ...
 
S3 Supply Air Duct System Assignment
S3 Supply Air Duct System AssignmentS3 Supply Air Duct System Assignment
S3 Supply Air Duct System Assignment
 
Infection Prevention & Control During Constructions and Renovation
Infection Prevention & Control During Constructions and RenovationInfection Prevention & Control During Constructions and Renovation
Infection Prevention & Control During Constructions and Renovation
 
building services
building servicesbuilding services
building services
 
Guidelines for airbone infection isolation room
Guidelines for airbone infection isolation roomGuidelines for airbone infection isolation room
Guidelines for airbone infection isolation room
 
Brookvent part f compliance guide
Brookvent part f compliance guideBrookvent part f compliance guide
Brookvent part f compliance guide
 
Natural ventilation, Artificial ventilation, Air conditioning
Natural ventilation, Artificial ventilation, Air conditioningNatural ventilation, Artificial ventilation, Air conditioning
Natural ventilation, Artificial ventilation, Air conditioning
 
Chap 43
Chap 43Chap 43
Chap 43
 
1603104213-hatchery-planning-design-and-construction.pptx
1603104213-hatchery-planning-design-and-construction.pptx1603104213-hatchery-planning-design-and-construction.pptx
1603104213-hatchery-planning-design-and-construction.pptx
 
Hvca presentation ag-revised-dec09 2
Hvca presentation ag-revised-dec09 2Hvca presentation ag-revised-dec09 2
Hvca presentation ag-revised-dec09 2
 
Hvac System
Hvac SystemHvac System
Hvac System
 
298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf
298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf
298232596-HVAC-Handbook-CARRIER-2-Air-Distributer.pdf
 
layout of buildings
layout of buildingslayout of buildings
layout of buildings
 
Building Services 1 Report
Building Services 1 ReportBuilding Services 1 Report
Building Services 1 Report
 
VENTILATION.pdf
VENTILATION.pdfVENTILATION.pdf
VENTILATION.pdf
 
HVAC Install - Trust But Verify
HVAC Install  - Trust But VerifyHVAC Install  - Trust But Verify
HVAC Install - Trust But Verify
 
Parenteral production
Parenteral   productionParenteral   production
Parenteral production
 

Mehr von The Pathway Group

Responsible Individual Training - F5 Foster Care.pptx
Responsible Individual Training -  F5 Foster Care.pptxResponsible Individual Training -  F5 Foster Care.pptx
Responsible Individual Training - F5 Foster Care.pptxThe Pathway Group
 
Responsible Individual Training fostercare- F5 Foster Care UK
Responsible Individual Training  fostercare-  F5 Foster Care UKResponsible Individual Training  fostercare-  F5 Foster Care UK
Responsible Individual Training fostercare- F5 Foster Care UKThe Pathway Group
 
Pathway Group 2024 by Safaraz Ali.pdf
Pathway Group 2024 by Safaraz Ali.pdfPathway Group 2024 by Safaraz Ali.pdf
Pathway Group 2024 by Safaraz Ali.pdfThe Pathway Group
 
1973 Toyota Production System Handbook
1973 Toyota Production System Handbook1973 Toyota Production System Handbook
1973 Toyota Production System HandbookThe Pathway Group
 
Multicultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdf
Multicultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdfMulticultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdf
Multicultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdfThe Pathway Group
 
Empowering The Nation - White Paper .pdf
Empowering The Nation - White Paper .pdfEmpowering The Nation - White Paper .pdf
Empowering The Nation - White Paper .pdfThe Pathway Group
 
Peer Meetup by Safaraz Ali 13.Oct.2023.pdf
Peer Meetup by Safaraz Ali 13.Oct.2023.pdfPeer Meetup by Safaraz Ali 13.Oct.2023.pdf
Peer Meetup by Safaraz Ali 13.Oct.2023.pdfThe Pathway Group
 
Peer Meetup by Safaraz Ali 13.Oct.2023.ppt
Peer Meetup by Safaraz Ali 13.Oct.2023.pptPeer Meetup by Safaraz Ali 13.Oct.2023.ppt
Peer Meetup by Safaraz Ali 13.Oct.2023.pptThe Pathway Group
 
A Guide to Apprenticeships for the Higher Education Sector.pdf
A Guide to Apprenticeships for the Higher Education Sector.pdfA Guide to Apprenticeships for the Higher Education Sector.pdf
A Guide to Apprenticeships for the Higher Education Sector.pdfThe Pathway Group
 
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdf
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdfAll Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdf
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdfThe Pathway Group
 
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.ppt
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pptAll Matters Regulatory - Apprenticeship Training Material - Pathway Group.ppt
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pptThe Pathway Group
 
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...The Pathway Group
 
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...The Pathway Group
 
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...The Pathway Group
 
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...The Pathway Group
 
The World of Learning - Apprenticeship Training Material - Pathway Group.ppt
The World of Learning - Apprenticeship Training Material - Pathway Group.pptThe World of Learning - Apprenticeship Training Material - Pathway Group.ppt
The World of Learning - Apprenticeship Training Material - Pathway Group.pptThe Pathway Group
 
The World of Learning - Apprenticeship Training Material - Pathway Group.pdf
The World of Learning - Apprenticeship Training Material - Pathway Group.pdfThe World of Learning - Apprenticeship Training Material - Pathway Group.pdf
The World of Learning - Apprenticeship Training Material - Pathway Group.pdfThe Pathway Group
 
How Independent Training Providers (ITPs) can survive and thrive in an inflat...
How Independent Training Providers (ITPs) can survive and thrive in an inflat...How Independent Training Providers (ITPs) can survive and thrive in an inflat...
How Independent Training Providers (ITPs) can survive and thrive in an inflat...The Pathway Group
 
Birmingham Pakistani Report PDF June 2023.pdf
Birmingham Pakistani Report PDF June 2023.pdfBirmingham Pakistani Report PDF June 2023.pdf
Birmingham Pakistani Report PDF June 2023.pdfThe Pathway Group
 
Multicultural Apprenticeship Alliance Launch Slide - Safaraz Ali
Multicultural Apprenticeship Alliance Launch Slide - Safaraz AliMulticultural Apprenticeship Alliance Launch Slide - Safaraz Ali
Multicultural Apprenticeship Alliance Launch Slide - Safaraz AliThe Pathway Group
 

Mehr von The Pathway Group (20)

Responsible Individual Training - F5 Foster Care.pptx
Responsible Individual Training -  F5 Foster Care.pptxResponsible Individual Training -  F5 Foster Care.pptx
Responsible Individual Training - F5 Foster Care.pptx
 
Responsible Individual Training fostercare- F5 Foster Care UK
Responsible Individual Training  fostercare-  F5 Foster Care UKResponsible Individual Training  fostercare-  F5 Foster Care UK
Responsible Individual Training fostercare- F5 Foster Care UK
 
Pathway Group 2024 by Safaraz Ali.pdf
Pathway Group 2024 by Safaraz Ali.pdfPathway Group 2024 by Safaraz Ali.pdf
Pathway Group 2024 by Safaraz Ali.pdf
 
1973 Toyota Production System Handbook
1973 Toyota Production System Handbook1973 Toyota Production System Handbook
1973 Toyota Production System Handbook
 
Multicultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdf
Multicultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdfMulticultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdf
Multicultural-Apprenticeship-Awards-2023-Compressed-Brochure.pdf
 
Empowering The Nation - White Paper .pdf
Empowering The Nation - White Paper .pdfEmpowering The Nation - White Paper .pdf
Empowering The Nation - White Paper .pdf
 
Peer Meetup by Safaraz Ali 13.Oct.2023.pdf
Peer Meetup by Safaraz Ali 13.Oct.2023.pdfPeer Meetup by Safaraz Ali 13.Oct.2023.pdf
Peer Meetup by Safaraz Ali 13.Oct.2023.pdf
 
Peer Meetup by Safaraz Ali 13.Oct.2023.ppt
Peer Meetup by Safaraz Ali 13.Oct.2023.pptPeer Meetup by Safaraz Ali 13.Oct.2023.ppt
Peer Meetup by Safaraz Ali 13.Oct.2023.ppt
 
A Guide to Apprenticeships for the Higher Education Sector.pdf
A Guide to Apprenticeships for the Higher Education Sector.pdfA Guide to Apprenticeships for the Higher Education Sector.pdf
A Guide to Apprenticeships for the Higher Education Sector.pdf
 
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdf
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdfAll Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdf
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pdf
 
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.ppt
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.pptAll Matters Regulatory - Apprenticeship Training Material - Pathway Group.ppt
All Matters Regulatory - Apprenticeship Training Material - Pathway Group.ppt
 
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
 
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
End-Point Assessment Organisations EPAOs - Apprenticeship Training Material -...
 
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
 
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
How Apprenticeships Work & Why They Work - Apprenticeship Training Material -...
 
The World of Learning - Apprenticeship Training Material - Pathway Group.ppt
The World of Learning - Apprenticeship Training Material - Pathway Group.pptThe World of Learning - Apprenticeship Training Material - Pathway Group.ppt
The World of Learning - Apprenticeship Training Material - Pathway Group.ppt
 
The World of Learning - Apprenticeship Training Material - Pathway Group.pdf
The World of Learning - Apprenticeship Training Material - Pathway Group.pdfThe World of Learning - Apprenticeship Training Material - Pathway Group.pdf
The World of Learning - Apprenticeship Training Material - Pathway Group.pdf
 
How Independent Training Providers (ITPs) can survive and thrive in an inflat...
How Independent Training Providers (ITPs) can survive and thrive in an inflat...How Independent Training Providers (ITPs) can survive and thrive in an inflat...
How Independent Training Providers (ITPs) can survive and thrive in an inflat...
 
Birmingham Pakistani Report PDF June 2023.pdf
Birmingham Pakistani Report PDF June 2023.pdfBirmingham Pakistani Report PDF June 2023.pdf
Birmingham Pakistani Report PDF June 2023.pdf
 
Multicultural Apprenticeship Alliance Launch Slide - Safaraz Ali
Multicultural Apprenticeship Alliance Launch Slide - Safaraz AliMulticultural Apprenticeship Alliance Launch Slide - Safaraz Ali
Multicultural Apprenticeship Alliance Launch Slide - Safaraz Ali
 

Kürzlich hochgeladen

call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️soniya singh
 
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial VenturesM3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial Venturessheltercareglobal
 
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...delhimodel235
 
Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...delhimodel235
 
2k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 92055419142k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 9205541914Delhi Call girls
 
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCRGirls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCRasmaqueen5
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | GurgaonFULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaonsoniya singh
 
How to Build Multifamily and Laneway Suites in Toronto!! (feat. Expert Archi...
How to Build Multifamily and Laneway Suites  in Toronto!! (feat. Expert Archi...How to Build Multifamily and Laneway Suites  in Toronto!! (feat. Expert Archi...
How to Build Multifamily and Laneway Suites in Toronto!! (feat. Expert Archi...Volition Properties
 
Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...delhimodel235
 
Sankla East World Hadapsar Pune E-Brochure.pdf
Sankla East World Hadapsar Pune  E-Brochure.pdfSankla East World Hadapsar Pune  E-Brochure.pdf
Sankla East World Hadapsar Pune E-Brochure.pdfManishSaxena95
 
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdfKohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdfManishSaxena95
 
Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...
Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...
Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...asmaqueen5
 
Aparna Greenscapes Kompally Hyderabad E - Brochure.pdf
Aparna Greenscapes Kompally Hyderabad E - Brochure.pdfAparna Greenscapes Kompally Hyderabad E - Brochure.pdf
Aparna Greenscapes Kompally Hyderabad E - Brochure.pdffaheemali990101
 
3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGI3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGIPanoram CGI
 
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|AkshayJoshi575980
 
Raquel Thompson: Combining Creativity with Practicality in Architecture
Raquel Thompson: Combining  Creativity with Practicality in ArchitectureRaquel Thompson: Combining  Creativity with Practicality in Architecture
Raquel Thompson: Combining Creativity with Practicality in ArchitectureRaquel Thompson Barbados
 
Puravankara Mundhwa Pune E-Brochure.pdf
Puravankara Mundhwa Pune  E-Brochure.pdfPuravankara Mundhwa Pune  E-Brochure.pdf
Puravankara Mundhwa Pune E-Brochure.pdfManishSaxena95
 
9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhidelhimodel235
 
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...delhimodel235
 
Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024VickyAulakh1
 

Kürzlich hochgeladen (20)

call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
call girls in ganesh nagar Delhi 8264348440 ✅ call girls ❤️
 
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial VenturesM3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
 
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
Call Girls in laxmi Nagar Delhi 💯Call Us 🔝 9582086666🔝 South Delhi Escorts Se...
 
Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 12 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
 
2k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 92055419142k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 9205541914
 
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCRGirls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
Girls in Kalyanpuri }Delhi↫8447779280↬Escort Service. In Delhi NCR
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | GurgaonFULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
FULL ENJOY 🔝 8264348440 🔝 Call Girls in DLF phase 3 | Gurgaon
 
How to Build Multifamily and Laneway Suites in Toronto!! (feat. Expert Archi...
How to Build Multifamily and Laneway Suites  in Toronto!! (feat. Expert Archi...How to Build Multifamily and Laneway Suites  in Toronto!! (feat. Expert Archi...
How to Build Multifamily and Laneway Suites in Toronto!! (feat. Expert Archi...
 
Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 13 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
 
Sankla East World Hadapsar Pune E-Brochure.pdf
Sankla East World Hadapsar Pune  E-Brochure.pdfSankla East World Hadapsar Pune  E-Brochure.pdf
Sankla East World Hadapsar Pune E-Brochure.pdf
 
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdfKohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
 
Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...
Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...
Call Girls In Hari Nagar Dadb Block {8447779280}Hari Nagar {West Delhi Escort...
 
Aparna Greenscapes Kompally Hyderabad E - Brochure.pdf
Aparna Greenscapes Kompally Hyderabad E - Brochure.pdfAparna Greenscapes Kompally Hyderabad E - Brochure.pdf
Aparna Greenscapes Kompally Hyderabad E - Brochure.pdf
 
3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGI3D Architectural Rendering Company by Panoram CGI
3D Architectural Rendering Company by Panoram CGI
 
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
Maha Mauka Squarefeet Brochure |Maha Mauka Squarefeet PDF Brochure|
 
Raquel Thompson: Combining Creativity with Practicality in Architecture
Raquel Thompson: Combining  Creativity with Practicality in ArchitectureRaquel Thompson: Combining  Creativity with Practicality in Architecture
Raquel Thompson: Combining Creativity with Practicality in Architecture
 
Puravankara Mundhwa Pune E-Brochure.pdf
Puravankara Mundhwa Pune  E-Brochure.pdfPuravankara Mundhwa Pune  E-Brochure.pdf
Puravankara Mundhwa Pune E-Brochure.pdf
 
9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 6 Delhi (Call Girls) Delhi
 
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
Call Girls in Noida Sector 11 Noida 💯Call Us 🔝 9582086666 🔝 South Delhi Escor...
 
Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024
 

Pathway Cleaning - TR19 regulations - Ductwork Clean - Extraction Clean

  • 1. TR19 Regulations Free guide for compliance cleaning the
  • 2. Guide to Good Practice Internal Cleanliness of Ventilation Specific Considerations for Kitchen Extract Systems 7.1 The kitchen extract system presents particular hazards due tothe potential for the accumulation of grease. Accumulated grease within an extract system forms a hidden combustion load. Under certain circumstances flame or very high temperature within the duct can ignite the grease causing fire to spread rapidly through the duct. Flame and heat within the duct can ignite surrounding materials at various points along the ductwork path and transfer fire in ways that are difficult to predict and control by designers, installers and ultimately fire fighters. 7.2 Kitchen extract ventilation systems are defined here as the extract systems intended to collect and remove contaminants, heat and moisture from cooking appliances (See also DW/172). A kitchen extract system wouldn’t typically comprise of the following components:Canopy Also referred to as hood, canopy hood, extraction hood, cooking hood, cooker hood, cooking canopy or extraction canopy. This would most likely include a vertical canopy skirt running around the perimeter of the canopy. Channel on the bottom edge of the skirt; a canopy roof sitting horizontally on the top of and joining the skirts; a grease filter housing assembly (with grease filters and traps) hanging within the boundary of the skirts. Canopy/Extract plenum This is typically the area immediately behind the grease filter housing and below where the ducting commences. Ducting Beyond the canopy/extract plenum, extraction ductwork would be connected. This may involve short transition ducts connected directly to the suction side of an extract fan or could include many linear metres of horizontal and/or vertical ductwork. Vertical ductwork, also referred to as riser may pass through many levels of a building. Contained within the ducting there may be attenuators, flow control dampers, fire dampers, air turning vanes and sensors. Extract Fan To create extraction from the canopy an extract fan would be connected to the ductwork, some extract fans (roof mounted) discharge directly to atmosphere via a cowl. Discharge Duct On the exhaust side of the fan a discharge duct would direct extract air out of the building via an outlet. This outlet point may include weather louvres and mesh to prevent the ingress of weather and vermin. Other systems such as ventilated ceilings and directly ducted extraction are also used. It is important that the person responsible for implementing cleaning regimes clearly understands the breakdown of the system so that any cleaning regime is compliant with the terms of buildings insurance relevant to the kitchen extract maintenance. 7.3 Other extraction systems serving the cooking area, such as potwash/dishwash systems, general extraction etc. may also be affected by grease deposits and similar considerations will apply.
  • 3. 7.4 Kitchen extract systems are liable to internal fouling by grease and oils. It is usual for the systems to be protected by grease filters, but these differ widely in terms of efficiency of grease removal and of barrier to flame. Total grease removal is not normally feasible and therefore fouling of systems downstream will occur to a greater or lesser degree. 7.5 Grease deposits within systems also pose hygiene, odour, vermin and mechanical efficiency hazards. Poorly designed and installed or damaged ductwork can leak grease, thus extending the fire risk, hygiene, odour and vermin hazards. Also, where ductwork distorts under fire conditions, burning grease can leak out and spread the fire to duct surroundings. 7.6 Supply or make-up ventilation systems should be maintained in hygienic condition as detailed in this Guide. Due to the accumulated grease within extract systems, the majority of the duct - work cleaning will be by manual rather than mechanical methods. At the time of system survey, a detailed schematic should be provided, highlighting any areas which are inaccessible and therefore, will remain uncleaned. The client must be advised of any inaccessible areas, the reason for their inaccessibility and, if possible, the likely cost to provide full and free access. It is the clients responsibility to highlight this to their insurer or other relevant third party, if required, who must confirm whether an exception to the total cleaning in accordance with TR/19 is acceptable. 7.7 This section of the Guide provides specific advice on how to clean and maintain kitchen extract systems, but similar consideration will apply to non kitchen areas that might be affected by grease and/or oil deposits. Design and access to the Internal Surfaces of the Kitchen Extract 7.8 Advice is provided in B&ES/HVCA DW/172: Specification for kitchen ventilation system (2005) 7.9 Internal surfaces of kitchen extract systems should be free of irregularities, all of which make grease accumulation more likely and cleaning more difficult. 7.10 It is essential that a kitchen extract ductwork system, and canopy/extract plenum, is provided with access panels of sufficient number, quality and size to enable unrestricted access for regular cleaning and inspection of the internal surfaces and in-line components. 7.11 Location of access to the internal surfaces of a kitchen extract system is dependent on a number of design and operational considerations • • • • • • • Design and location of ductwork Building design and construction materials Location of kitchen within the building Location of extract fan and accessibility for maintenance Accessibility to physically reach the ductwork Any building modifications and current uses that may restrict access Location and number of system components requiring access. 7.12 Access panels should be suitable for the purpose for which they are intended. The panels
  • 4. and frames should be constructed of the same material as the ductwork. As a minimum they should incorporate quick release catches, sealing gasket and thermal, acoustic and fire rated insulation properties equal tothat of the duct to which they are fitted. Particular consideration must be given to maintaining the fire integrity of fire rated ductwork. The recommendations of the manufacturer or specialist fire protection adviser should be followed where appropriate. 7.13 Access panels should be as large as the duct size permits to a maximum of 460mm x 610mm without weakening the structure of the system. Openings should not be obstructed by other building services, stored equipment or by the fabric of the building. The panel and aperture should be free of any sharp edges. 7.14 Access panels should be fitted at the side of the duct, a minimum of 10mm above the base to minimise the risk of grease leakage. Exceptionally, they may be fitted on the top of the duct, but due consideration should be given to the accessibility of the panel. Where access panels must be fitted to the underside of a duct, particular care must be taken to ensure a leakfree fit and notice should be affixed warning of the risk of oil being released on opening the panels. In designing systems due consideration should be given to providing physical unobstructed access to all access panels. 7.15 Access panels should be fitted on either side of in-line components, as detailed in Table 8, to allow physical entry to clean these intricate surfaces. This Table includes components, such as fire dampers and attenuators, which are not normally recommended to be installed, but are often found in practice. This has a significant impact on installations such as ventilation extractions where a significant risk exists if the installation fails. Table 8: Location of Access Panels for Cleaning and Inspection Purposes Volume Control Dampers Both sides Fire Dampers Both sides Attenuators Both sides Changes in Direction Both sides Filter Sections Both sides Horizontal Ducts Generally every 3 metres (see Note 2) Risers Top and bottom as a minimum (see Note 3) Extract Fans Both sides (see Note 4) Discharge grille/mesh One side Notes to Table 8 1. Additional builders work hatches may need to be fitted in ceilings/walls in existing installations, or provided for in new constructions. Consideration should also be given to safe high level access to external ductwork. 2. Access openings for cleaning purposes are generally required at a maximum of 3 metre centres and/or at each change of direction. This distance should be reduced where the size of the duct prevents adequate cleaning by hand, where there are several changes in direction or where other external features restrict the positioning of panels.
  • 5. 3. Internal kitchen extract risers often require access doors fitted on at least each floor level so that all internal surfaces can be reached and fire dampers, where fitted, cleaned and checked. In older buildings this may require additional builders works (e.g. hatches through brickwork) to reach the riser ducts (see 7.6). 4. Extract fan design should allow thorough cleaning of impellor blades and internal surfaces without the need for dismantling, i.e. ductwork with access panels should be provided immediately upstream and downstream. Larger fans should be designed with panels in the casing. Similarly, attenuators or other in-line fittings likely to obscure cleaning activity should be provided with access on both sides. System Testing (Inspection/Monitoring) 7.18 The Health & Safety Executive and industry and insurance guidance and regulations (see Appendices B&ES) stipulate that kitchen extract systems should be kept clean to minimise fire and other risks. This Guide now provides a method of measuring and defining cleanliness and dirtiness as a benchmark for good practice. 7.19 The Cleaning Guys has investigated a variety of methods for testing ductwork system internal surfaces to measure grease deposits and recommends the Wet Film Thickness Test (W.F.T.T) measurement method. This method is described in Appendix D.3. 7.20 The Deposit Thickness Test (D.T.T), as described in Section 5, may also be used and may be necessary in the case of extremely hardbaked, carbonised, deposits and the funding of hard-baked deposits would normally indicate a requirement to clean or in the case of cleanliness verification a requirement to reclean. 7.21 The testing methods provide an objective, repeatable and verifiable measurement of grease deposits, and over come the subjectivity of visual inspection alone. 7.22 It is recommended that testing be carried out at intervals not exceeding 12 months. Monitoring of grease deposits may need to be carried out more frequently if it is necessary to establish a precise definition of required cleaning frequencies. The cleaning frequency required should be estimated by a specialist service provider and/or client on initial inspection or assessment and subsequent pre-clean testing will confirm whether the initial predicted frequency is correct or requires adjustment. 7.23 Measurements should be taken at the following locations where practicable: • • • • • • Canopy/Extract plenum behind filters Duct 1 metre from canopy Duct 3 metres from canopy Duct midway between canopy and fan Duct upstream of fan Discharge duct downstream of fan 7.24 Table 9 sets out guideline maximum levels of grease deposit and actions recommended. The actual recommended action timing will depend on the rate of accumulation, the risk vulnerability of the system and site and any particular warranties imposed by the building insurers.
  • 6. Table 9: Surface Grease Deposit Limits Wet Film Thickness Test Measurement Recommended Action 200μm as a mean across the system Complete cleaning required Any single measurement above 500μm Urgent local cleaning required Notes to Table 9 1. In the abscence of, and the likely theoretical difficulties of an absolute measure of the flammability of various quantities of grease deposit, the surface grease deposit limits are given in Table 9 and paragraph 7.42. 2. These levels were determined by extensive field testing to measure at what levels good practice employers, or operators of systems, carry out system cleaning and what levels of cleanliness are normally achieved by specialist duct cleaners using available cleaning and measurement technology within reasonable economic bounds. 3. The mean measurement is calculated by dividing the total of the test results by the number of testing locations. 4. The second category of any single measurement above 500um is provided to cater for local “hot spots” which should be cleaned even where the whole system does not require complete cleaning. Examples might be immediately local to a canopy or at a fan. 5. The extent of urgent local cleaning precipitated by the presence of grease deposits above 500um should be subject to reasonable appreciation of the extent of fouling and risk posed. 7.25 The surface grease deposits limits should not be confused with the level set for Post - Clean verification which is far more stringent and detailed in paragraph 7.42. 7.26 Stand-alone, regular or post-clean testing can usefully be combined with inspection of other kitchen extract system safety issues. If specifi ed by a client, a service provider should provide evidence of competence to carry out such inspection. Such inspection should include, but not be restricted to: 1. Adequacy of filters and their regular maintenance 2. Adequacy of regular cleaning of canopy, and associated drains and traps 3. Existence and visual condition of any fire suppression or detection system 4. Damage to fire protection 5. Ductwork grease leakage 6. Ductwork damage 7. Damage to or inappropriate ductwork fixtures 8. Visual/audible check of fan operation 9. Rubbish/debris adjacent to system
  • 7. 10. Visual assessment of any special filtration 11. Discharge condition, including grease splatter/staining 7.27 Such inspection should not be regarded as a substitute for proper maintenance of plant such as fans and fire suppression or detection systems. Cleaning Methods 7.28 This guide is not intended to be definitive in relation to the method of cleaning, as there are many existing methods that can be applied in tandem, and emergent new technologies. Examples of cleaning methods are listed in Table 10. 7.29 To conform with the Guide, the actual method or methods must be capable of achieving the required results, i.e. Post-Clean Verification, not only on the internal surfaces of the extract duct but also on system components. 7.30 When choosing the cleaning method, consideration should be given to operative safety and also to effects on the surrounding environment, particularly where using wet cleaning methods, since grease/moisture can leak from the ductwork components and damage the surrounding fabric. Table 10: Examples of Cleaning Methodology Generic Name Energy Source Removal Method Hand wipe Manual Wiping the surface of the ductwork Hand scrape Manual Removing heavy deposits by hand scraping Chemical Manual Softens or dissolves deposits making them suitable for hand scraping High pressure water wash (steam) Electrical or compressed air Vapour or liquid expelled at high pressure from lance to dislodge/ dissolve deposits Blasting (remote or direct) using suitable medium as appropriate Compressed air Blasting medium dislodges contaminant from duct and component surfaces to be removed via vacuum techniques or high volume filtered extraction. 7.31 Steam cleaning and high pressure water washing are not recommended for ductwork that is situated above false ceilings or in sensitive areas, due to possible leakage of contaminants from the duct, unless specifically designed for wet cleaning. 7.32 After applying wet cleaning methods care should be taken to ensure that any condensed vapours and cleaning fluids are removed from all parts of the system.
  • 8. 7.33 The use of chemical cleaning agents should only be considered where a risk/COSHH assessment has been carried out (See Section 10), the details recorded and the effects of the applied chemicals have been assessed on the material construction, environment and for hazards to cleaning personnel. 7.34 It should be noted that it is not normally economically practicable to clean kitchen extract systems to a “like new” bright metal condition due to substratestaining. Frequency of Cleaning 7.35 The need for specialist cleaning of extract systems will depend on the level of usage of the cooking equipment, types and quantity of cooking and other risk factors such as vulnerability of the system to ignition and of the building and its occupant/users to system fire, hygiene, vermin and mechanical hazards. Typical cleaning intervals are shown in Table 11: Table 11: Frequency of Cleaning Heavily Use 12-16 hours per day - 3 monthly Moderately Use 6-12 hours per day - 6 monthly Light Use 2-6 hours per day -12 monthly Notes to Table 11 The canopy and canopy/extract plenum is an area of higher fire risk and consideration should be given to more frequent cleaning in accordance with insurance requirements (see 7.39) 7.36 The frequency of cleaning should be adjusted by means of system testing (inspection/ monitoring) - see paragraph 7.23, so that surface grease deposit limits in Table 9 are not exceeded. The buildings insurance company should be consulted to ensure that the cleaning regime is compliant with the terms of their specific warranty. 7.37 Any cleaning regime should be justified by a considered risk assessment. (The latest Fire Precautions Workplace, and Management of Health & Safety at Work Regulations apply). 7.38 Regular cleaning will result in an improved mean standard and reduce the costs of cleaning as deposits are not allowed to bake and harden. 7.39 Periodic specialist cleaning should be accompanied by daily or weekly cleaning of canopies, filters and associated drains and traps in accordance with manufacturers’ recommendations, typically carried out by the kitchen operator. Post-Clean Verification of Cleanliness 7.40 The primary method of assessment is visual. For cleaned system verification, the surface should be visibly clean and capable of meeting the level of cleanliness specified. 7.41 Verification of cleanliness should be by means of the Deposit Thickness Test or Wet Film Thickness Test as detailed in System Testing (Inspection/Monitoring) at paragraph. 7.42 The level of cleanliness is that no single measurement should exceed 50μm.
  • 9. 7.43 On completion a report should be provided containing the following:The system(s) cleaned • Pre-clean measurements (as per System Testing) • Post-clean measurements • Photographic records • Additional works carried out (if any) • COSHH data on any chemicals used • Recommendations for future cleaning requirements • Observations on the condition of the ductwork system 7.44 If specified, additional kitchen extract safety issues should also be reported (as outlined in paragraph 7.26). 7.45 The Post-Clean Verification of Cleanliness report should assist to serve as evidence of system status to insurance assessors, Environmental Health Officers, landlord’s agents, etc.
  • 10. For further information: Pathway Cleaning Ltd Lamoc House 7-9 Summer Hill Terrace Birmingham B1 3RA Telephone: 0121 236 1448 and 0121 236 4050 www.pathwaycleaning.co.uk • www.thecleaningguys.co.uk