SlideShare ist ein Scribd-Unternehmen logo
1 von 4
AIR-CONDITIONING SYSTEMS DUCT – EQUAL-FRICTION METHOD

An industrial air-conditioning system requires 36000 cfm of air. This low-velocity system will be fitted with enough air outlets to distribute the
air uniformly throughout the conditioned space. The required operating pressure for each duct is 0.20 in wg. Determine the duct sizes
required for this system by using the equal-friction method of design. What is the required fan static discharge pressure?

    1.   Sketch the duct system

The required air quantity, 3600 ft3/min, must be distributed in approximately equal quantities to the various areas in the building. Sketch the
proposed duct layout.




Determine the required capacity of each air outlet from air quantity required, ft3/min.

                                            ft 3
                                     36000                3
         air quantity per outlet =          min = 2000 ft   per outlet
                                         18            min

This is within the usual range of many commercially available outlets.
Where the required capacity outlet is extremely large, say 10000 ft3/min, or extremely small, say 5 ft3/min, change the number of outlets
shown on the duct sketch to obtain an air quantity within the usual range of commercially available outlets. Relocate each outlet in the so it
serves approximately the same amount of floor area as each of the other outlets in the system. Thus, the duct sketch serves as a trial-and-
error analysis of the outlet location and capacity.

    2.   Determine the required outlet operating pressure

Consult the manufacturer’s engineering data for the required operating pressure of each outlet. Where possible, try to use the same type of
outlets throughout the system. This will reduce the investment.

Assume that the required outlet operating pressure is 0.20-in wg for each outlet in this system.

    3.   Choose the air velocity for the main duct

Use Table 7 – Recommended Maximum Duct Velocities for Low Velocity Systems (FPM) by Dr. Carriers Handbook, to determine a suitable air
velocity for the main duct of this system.

Table shows that 2500 ft/min can be used for main ducts where noise is the controlling factor; 3000 ft/min where duct friction is the
controlling factor.

A velocity of 2500 ft/min will be used for the main duct in this installation.
4.   Determine the dimensions of the duct

The require duct area:

               ft 3 / min 36000 ft 3 / min
         A =             =                 = 14.4 ft 2
                ft / min   2500 ft / min

                   A nearly square duct: 46 x 45-in has an area of 14.38 ft2 and is a good first choice for this system because it is closely
                   approximates the outlet size of a standard centrifugal fan.

                   Where possible, use a square main duct to simplify fan connections.

                   Thus a 46 x 46-in duct might be the final choice for this system.

    5.   Determine the main-duct friction loss
                                                                                                0.50                            0.50
                                                                                    ⎛ 144 A ⎞             ⎛ 144 * 14.4 ft 3 ⎞
Convert the required duct area to the equivalent diameter in inches d, using: d = 2 ⎜
                                                                                    ⎜ π ⎟
                                                                                            ⎟          =2 ⎜
                                                                                                          ⎜
                                                                                                                            ⎟
                                                                                                                            ⎟          = 51.5 in .
                                                                                    ⎝       ⎠             ⎝       π         ⎠

Enter Chart 7 – Friction Loss for Round Duct by Dr. Carrier Handbook at 36000 ft3/min and project horizontally to a round duct diameter of
                                                                           in wg
51.5-in. At the top of the chart read the friction loss as 0.13                             .
                                                                100 ft of equivalent length

    6.   Size the branch ducts

For many common air-conditioning systems the equal-friction method is used to size the ducts. In this method the supply, exhaust, and
return-air ducts are sized so they have the same friction loss per foot of length for the entire system.

The usual procedure in the equal-friction method is to select an initial air velocity in the main duct near the fan, using the sound level as the
limiting factor.

Compute the duct areas, using Table 13 – Percent Section Area in Branches for Maintaining Equal Friction by Dr. Carriers Handbook. Tabulate
the results, using the duct run having the highest resistance. The friction loss through all elbows and fittings in the section must be included.
The total friction loss in the duct having the highest resistance is the loss the fan must overcome.

By inspection of the duct layout, shows that the duct run from the fan to the outlet 18 has the highest resistance because it is the longest
run.




Column 1 lists the longest duct run in the system.

Column 2, the air leaving the outlets in branch A, (6 outlets)(2000 ft3/min) = 12000 ft3/min, is subtracted from the quantity of air, 36000
ft3/min, discharge by the fan to give the air quantity flowing from A-B. A similar procedure is followed for each successive duct and air
quantity.

Column 3, is found by dividing the air quantity in each branch listed in columns 1 and 2 by 36000 ft3/min, and multiplying the result by 100.
                       12000 ft3 / min
Thus for column B-13:                  * 100% = 33%
                       36000 ft3 / min

Column 4 values are found from Table 13 - Percent Section Area in Branches for Maintaining Equal Friction by Dr. Carriers Handbook. Enter
that table with ft3/min capacity from column 3 and read the duct area, percent.
Thus for column 13-14, with 28% cfm capacity, the % duct area is 35.3%.

Column 5 values show the area of the duct, in sqm.
                                     (        )
Thus for column 13-14, ductarea = 14.4 ft2 (0.355) = 5.1 ft2
Convert the duct area to nearly square, or a square, duct by finding two dimensions that will produce the desired area.

Column 6 values shows the nearly square dimensions of the duct. Table 6 – Duct dimensions, Section Area, Circular Equivalent Diameter, and
Duct Class by Dr. Carrier Handbook is used to select the rectangular duct sizes.

Duct sections A through 6 and B through 12 have the same dimensions as the corresponding duct sections B through 18.
7.   Find the total duct friction loss

Examination of the duct sketch indicates that the duct run from the fan to outlet 18 has the highest resistance. Compute the total duct run
length and the equivalent of the two elbows in the run as shown.




Column 3, duct length, is determined from the sketch

Column 4, are the equivalent length of the duct elbows can be found in Table 12 – Friction of Rectangular Elbows by Dr. Carriers Handbook.

         The total equivalent length = (column 1) + (column 2) = 255 ft.


    8.   Compute the duct friction loss

Use the general relation: hL = L f
                  Where: hL = total friction loss in duct, in wg
                         L = total equivalent duct length, ft
                         f = friction loss for the system, in wg per 100 ft.
Hence;

              (      )
                     ⎛
         hL = 255 ft ⎜ 0.13
                     ⎜
                                       in wg            ⎞
                                                        ⎟ = 0.3315 − in wg
                            100 ft of equivalent length ⎟
                     ⎝                                  ⎠

    9.   Determine the required fan static discharge pressure

Total static pressure required at the fan discharge = outlet operating pressure + duct loss – velocity regain between first and last duct section


The velocity for duct section A:
                       ft 3
               36000
         vA =         min = 2500 ft
                 14.4 ft 2       min


The velocity for duct last section:
                      ft 3
                2000
         v 18 =      min = 1333.33 ft
                 1.5 ft 2           min

When the fan discharge velocity is higher than the duct velocity in an air-conditioning system, compute for Static Pressure Regain, R by:

                  ⎡⎛ v ⎞ 2 ⎛ v ⎞ 2 ⎤
         R = 0.75 ⎢⎜   f
                          ⎟ −⎜ ⎜ 4000 ⎟ ⎥
                                   d

                  ⎢⎜ 4000 ⎟
                   ⎝      ⎠    ⎝
                                       ⎟ ⎥
                                       ⎠ ⎦
                  ⎣
                 Where: vf = fan outlet velocity, ft/min
                            vd = duct velocity, ft/min
                  ⎡⎛                 2
                                                          ⎞ ⎤
                                                           2
                     2500 ft / min ⎞     ⎛
                                   ⎟ − ⎜ 1333.33 ft / min ⎟ ⎥ = 0.21 − in wg
         R = 0.75 ⎢⎜
                  ⎢⎜     4000      ⎟     ⎜     4000       ⎟ ⎥
                  ⎣⎝               ⎠     ⎝                ⎠ ⎦

Hence;

Total static pressure required at the fan discharge = (0.20 + 0.3315 – 0.21) – in wg

Total static pressure required at the fan discharge = 0.3215-in wg
Figure below shows the detail of duct hanger for ducts of various dimensions.




Figure below shows the details of rectangular duct takeoffs for air supply to specific rooms or areas.




NOTE: The equal-friction method of air-conditioning system duct design are applicable only to low-velocity systems in which the maximum air
velocity is 3000 ft/min, or less.

Weitere ähnliche Inhalte

Was ist angesagt?

Was ist angesagt? (20)

HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
 
AIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGINGAIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGING
 
Ventilation system
Ventilation systemVentilation system
Ventilation system
 
PRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGNPRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGN
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
Air distribution Product
Air distribution ProductAir distribution Product
Air distribution Product
 
Hvac how to size and design ducts r1
Hvac   how to size and design ducts r1Hvac   how to size and design ducts r1
Hvac how to size and design ducts r1
 
Blowers and fans Analysis
Blowers and fans AnalysisBlowers and fans Analysis
Blowers and fans Analysis
 
Duct system
Duct systemDuct system
Duct system
 
HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & Components
 
ASHRAE62.1-2019.pdf
ASHRAE62.1-2019.pdfASHRAE62.1-2019.pdf
ASHRAE62.1-2019.pdf
 
Hvac systems
Hvac systemsHvac systems
Hvac systems
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
 
HVAC Air distribution fundamentals
HVAC Air distribution fundamentalsHVAC Air distribution fundamentals
HVAC Air distribution fundamentals
 
Airchanges hvac
Airchanges hvacAirchanges hvac
Airchanges hvac
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculations
 
chilled water pipe sizer chart
chilled water pipe sizer chartchilled water pipe sizer chart
chilled water pipe sizer chart
 
Duct design .ppt
Duct design .pptDuct design .ppt
Duct design .ppt
 
Important parts of a centrifugal fan
Important parts of a centrifugal fanImportant parts of a centrifugal fan
Important parts of a centrifugal fan
 
9. DUCT DESIGN.pdf
9. DUCT DESIGN.pdf9. DUCT DESIGN.pdf
9. DUCT DESIGN.pdf
 

Ähnlich wie Duct design

DUCT FORMULA Design-2006.pptx
DUCT FORMULA Design-2006.pptxDUCT FORMULA Design-2006.pptx
DUCT FORMULA Design-2006.pptx
PraveenMGowdru
 
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
IJERA Editor
 
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
IJERA Editor
 
391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf
BlentBulut5
 
ME449_OConnor_Presentation
ME449_OConnor_PresentationME449_OConnor_Presentation
ME449_OConnor_Presentation
Dillon O'Connor
 
fanmodule-230428052900-38a217b0.pdf
fanmodule-230428052900-38a217b0.pdffanmodule-230428052900-38a217b0.pdf
fanmodule-230428052900-38a217b0.pdf
BlentBulut5
 
Hooman_Rezaei_asme_paper2
Hooman_Rezaei_asme_paper2Hooman_Rezaei_asme_paper2
Hooman_Rezaei_asme_paper2
rezaeiho
 
Eurovent 4.21 calculation method for the energy use 14186506522
Eurovent 4.21 calculation method for the energy use 14186506522Eurovent 4.21 calculation method for the energy use 14186506522
Eurovent 4.21 calculation method for the energy use 14186506522
Januário Esteves
 

Ähnlich wie Duct design (20)

008
008008
008
 
HVAC
HVACHVAC
HVAC
 
DUCT FORMULA Design-2006.pptx
DUCT FORMULA Design-2006.pptxDUCT FORMULA Design-2006.pptx
DUCT FORMULA Design-2006.pptx
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptx
 
duct.pptx
duct.pptxduct.pptx
duct.pptx
 
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
 
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of ...
 
Thermo 5th chap05_p001
Thermo 5th chap05_p001Thermo 5th chap05_p001
Thermo 5th chap05_p001
 
391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf
 
M01312106112
M01312106112M01312106112
M01312106112
 
Aircraft propulsion combustor diffusor
Aircraft propulsion   combustor diffusorAircraft propulsion   combustor diffusor
Aircraft propulsion combustor diffusor
 
3.1 hydraulics
3.1  hydraulics3.1  hydraulics
3.1 hydraulics
 
Ac ducts
Ac ductsAc ducts
Ac ducts
 
ME449_OConnor_Presentation
ME449_OConnor_PresentationME449_OConnor_Presentation
ME449_OConnor_Presentation
 
fanmodule-230428052900-38a217b0.pdf
fanmodule-230428052900-38a217b0.pdffanmodule-230428052900-38a217b0.pdf
fanmodule-230428052900-38a217b0.pdf
 
FAN MODULE.pdf
FAN MODULE.pdfFAN MODULE.pdf
FAN MODULE.pdf
 
Hooman_Rezaei_asme_paper2
Hooman_Rezaei_asme_paper2Hooman_Rezaei_asme_paper2
Hooman_Rezaei_asme_paper2
 
friction loss along a pipe
friction loss along a pipefriction loss along a pipe
friction loss along a pipe
 
Fluid_Mechanics_Lab_IVSem (1).pdf
Fluid_Mechanics_Lab_IVSem (1).pdfFluid_Mechanics_Lab_IVSem (1).pdf
Fluid_Mechanics_Lab_IVSem (1).pdf
 
Eurovent 4.21 calculation method for the energy use 14186506522
Eurovent 4.21 calculation method for the energy use 14186506522Eurovent 4.21 calculation method for the energy use 14186506522
Eurovent 4.21 calculation method for the energy use 14186506522
 

Mehr von physics101

Bm 10 mr and e-marketing
Bm 10 mr and e-marketingBm 10 mr and e-marketing
Bm 10 mr and e-marketing
physics101
 
Bm 9 marketing element for be and csr
Bm 9 marketing element for be and csrBm 9 marketing element for be and csr
Bm 9 marketing element for be and csr
physics101
 
Bm 8 brand equity & management
Bm 8 brand equity & managementBm 8 brand equity & management
Bm 8 brand equity & management
physics101
 
Bernoulli's equation
Bernoulli's equationBernoulli's equation
Bernoulli's equation
physics101
 
Fundamental law of gearing
Fundamental law of gearingFundamental law of gearing
Fundamental law of gearing
physics101
 
Centrifugal pumps in series and parallel
Centrifugal pumps in series and parallelCentrifugal pumps in series and parallel
Centrifugal pumps in series and parallel
physics101
 
Laminar and turbulent f low
Laminar and turbulent f lowLaminar and turbulent f low
Laminar and turbulent f low
physics101
 
Engine systems
Engine systemsEngine systems
Engine systems
physics101
 
Bomb calorimeter experiment
Bomb calorimeter experimentBomb calorimeter experiment
Bomb calorimeter experiment
physics101
 
Flash and fire point
Flash and fire pointFlash and fire point
Flash and fire point
physics101
 
Calibration of pressure gauges
Calibration of pressure gaugesCalibration of pressure gauges
Calibration of pressure gauges
physics101
 
Hazardous substances 01
Hazardous substances 01Hazardous substances 01
Hazardous substances 01
physics101
 
Hazard communication lect 1
Hazard communication lect 1Hazard communication lect 1
Hazard communication lect 1
physics101
 
Scientific methods
Scientific methodsScientific methods
Scientific methods
physics101
 

Mehr von physics101 (20)

Bm 10 mr and e-marketing
Bm 10 mr and e-marketingBm 10 mr and e-marketing
Bm 10 mr and e-marketing
 
Bm 9 marketing element for be and csr
Bm 9 marketing element for be and csrBm 9 marketing element for be and csr
Bm 9 marketing element for be and csr
 
Bm 8 brand equity & management
Bm 8 brand equity & managementBm 8 brand equity & management
Bm 8 brand equity & management
 
Manuala hw
Manuala hwManuala hw
Manuala hw
 
F1
F1F1
F1
 
F6
F6F6
F6
 
Fire safety
Fire safetyFire safety
Fire safety
 
Bernoulli's equation
Bernoulli's equationBernoulli's equation
Bernoulli's equation
 
Gear trains
Gear trainsGear trains
Gear trains
 
Fundamental law of gearing
Fundamental law of gearingFundamental law of gearing
Fundamental law of gearing
 
Gears
GearsGears
Gears
 
Centrifugal pumps in series and parallel
Centrifugal pumps in series and parallelCentrifugal pumps in series and parallel
Centrifugal pumps in series and parallel
 
Laminar and turbulent f low
Laminar and turbulent f lowLaminar and turbulent f low
Laminar and turbulent f low
 
Engine systems
Engine systemsEngine systems
Engine systems
 
Bomb calorimeter experiment
Bomb calorimeter experimentBomb calorimeter experiment
Bomb calorimeter experiment
 
Flash and fire point
Flash and fire pointFlash and fire point
Flash and fire point
 
Calibration of pressure gauges
Calibration of pressure gaugesCalibration of pressure gauges
Calibration of pressure gauges
 
Hazardous substances 01
Hazardous substances 01Hazardous substances 01
Hazardous substances 01
 
Hazard communication lect 1
Hazard communication lect 1Hazard communication lect 1
Hazard communication lect 1
 
Scientific methods
Scientific methodsScientific methods
Scientific methods
 

Duct design

  • 1. AIR-CONDITIONING SYSTEMS DUCT – EQUAL-FRICTION METHOD An industrial air-conditioning system requires 36000 cfm of air. This low-velocity system will be fitted with enough air outlets to distribute the air uniformly throughout the conditioned space. The required operating pressure for each duct is 0.20 in wg. Determine the duct sizes required for this system by using the equal-friction method of design. What is the required fan static discharge pressure? 1. Sketch the duct system The required air quantity, 3600 ft3/min, must be distributed in approximately equal quantities to the various areas in the building. Sketch the proposed duct layout. Determine the required capacity of each air outlet from air quantity required, ft3/min. ft 3 36000 3 air quantity per outlet = min = 2000 ft per outlet 18 min This is within the usual range of many commercially available outlets. Where the required capacity outlet is extremely large, say 10000 ft3/min, or extremely small, say 5 ft3/min, change the number of outlets shown on the duct sketch to obtain an air quantity within the usual range of commercially available outlets. Relocate each outlet in the so it serves approximately the same amount of floor area as each of the other outlets in the system. Thus, the duct sketch serves as a trial-and- error analysis of the outlet location and capacity. 2. Determine the required outlet operating pressure Consult the manufacturer’s engineering data for the required operating pressure of each outlet. Where possible, try to use the same type of outlets throughout the system. This will reduce the investment. Assume that the required outlet operating pressure is 0.20-in wg for each outlet in this system. 3. Choose the air velocity for the main duct Use Table 7 – Recommended Maximum Duct Velocities for Low Velocity Systems (FPM) by Dr. Carriers Handbook, to determine a suitable air velocity for the main duct of this system. Table shows that 2500 ft/min can be used for main ducts where noise is the controlling factor; 3000 ft/min where duct friction is the controlling factor. A velocity of 2500 ft/min will be used for the main duct in this installation.
  • 2. 4. Determine the dimensions of the duct The require duct area: ft 3 / min 36000 ft 3 / min A = = = 14.4 ft 2 ft / min 2500 ft / min A nearly square duct: 46 x 45-in has an area of 14.38 ft2 and is a good first choice for this system because it is closely approximates the outlet size of a standard centrifugal fan. Where possible, use a square main duct to simplify fan connections. Thus a 46 x 46-in duct might be the final choice for this system. 5. Determine the main-duct friction loss 0.50 0.50 ⎛ 144 A ⎞ ⎛ 144 * 14.4 ft 3 ⎞ Convert the required duct area to the equivalent diameter in inches d, using: d = 2 ⎜ ⎜ π ⎟ ⎟ =2 ⎜ ⎜ ⎟ ⎟ = 51.5 in . ⎝ ⎠ ⎝ π ⎠ Enter Chart 7 – Friction Loss for Round Duct by Dr. Carrier Handbook at 36000 ft3/min and project horizontally to a round duct diameter of in wg 51.5-in. At the top of the chart read the friction loss as 0.13 . 100 ft of equivalent length 6. Size the branch ducts For many common air-conditioning systems the equal-friction method is used to size the ducts. In this method the supply, exhaust, and return-air ducts are sized so they have the same friction loss per foot of length for the entire system. The usual procedure in the equal-friction method is to select an initial air velocity in the main duct near the fan, using the sound level as the limiting factor. Compute the duct areas, using Table 13 – Percent Section Area in Branches for Maintaining Equal Friction by Dr. Carriers Handbook. Tabulate the results, using the duct run having the highest resistance. The friction loss through all elbows and fittings in the section must be included. The total friction loss in the duct having the highest resistance is the loss the fan must overcome. By inspection of the duct layout, shows that the duct run from the fan to the outlet 18 has the highest resistance because it is the longest run. Column 1 lists the longest duct run in the system. Column 2, the air leaving the outlets in branch A, (6 outlets)(2000 ft3/min) = 12000 ft3/min, is subtracted from the quantity of air, 36000 ft3/min, discharge by the fan to give the air quantity flowing from A-B. A similar procedure is followed for each successive duct and air quantity. Column 3, is found by dividing the air quantity in each branch listed in columns 1 and 2 by 36000 ft3/min, and multiplying the result by 100. 12000 ft3 / min Thus for column B-13: * 100% = 33% 36000 ft3 / min Column 4 values are found from Table 13 - Percent Section Area in Branches for Maintaining Equal Friction by Dr. Carriers Handbook. Enter that table with ft3/min capacity from column 3 and read the duct area, percent. Thus for column 13-14, with 28% cfm capacity, the % duct area is 35.3%. Column 5 values show the area of the duct, in sqm. ( ) Thus for column 13-14, ductarea = 14.4 ft2 (0.355) = 5.1 ft2 Convert the duct area to nearly square, or a square, duct by finding two dimensions that will produce the desired area. Column 6 values shows the nearly square dimensions of the duct. Table 6 – Duct dimensions, Section Area, Circular Equivalent Diameter, and Duct Class by Dr. Carrier Handbook is used to select the rectangular duct sizes. Duct sections A through 6 and B through 12 have the same dimensions as the corresponding duct sections B through 18.
  • 3. 7. Find the total duct friction loss Examination of the duct sketch indicates that the duct run from the fan to outlet 18 has the highest resistance. Compute the total duct run length and the equivalent of the two elbows in the run as shown. Column 3, duct length, is determined from the sketch Column 4, are the equivalent length of the duct elbows can be found in Table 12 – Friction of Rectangular Elbows by Dr. Carriers Handbook. The total equivalent length = (column 1) + (column 2) = 255 ft. 8. Compute the duct friction loss Use the general relation: hL = L f Where: hL = total friction loss in duct, in wg L = total equivalent duct length, ft f = friction loss for the system, in wg per 100 ft. Hence; ( ) ⎛ hL = 255 ft ⎜ 0.13 ⎜ in wg ⎞ ⎟ = 0.3315 − in wg 100 ft of equivalent length ⎟ ⎝ ⎠ 9. Determine the required fan static discharge pressure Total static pressure required at the fan discharge = outlet operating pressure + duct loss – velocity regain between first and last duct section The velocity for duct section A: ft 3 36000 vA = min = 2500 ft 14.4 ft 2 min The velocity for duct last section: ft 3 2000 v 18 = min = 1333.33 ft 1.5 ft 2 min When the fan discharge velocity is higher than the duct velocity in an air-conditioning system, compute for Static Pressure Regain, R by: ⎡⎛ v ⎞ 2 ⎛ v ⎞ 2 ⎤ R = 0.75 ⎢⎜ f ⎟ −⎜ ⎜ 4000 ⎟ ⎥ d ⎢⎜ 4000 ⎟ ⎝ ⎠ ⎝ ⎟ ⎥ ⎠ ⎦ ⎣ Where: vf = fan outlet velocity, ft/min vd = duct velocity, ft/min ⎡⎛ 2 ⎞ ⎤ 2 2500 ft / min ⎞ ⎛ ⎟ − ⎜ 1333.33 ft / min ⎟ ⎥ = 0.21 − in wg R = 0.75 ⎢⎜ ⎢⎜ 4000 ⎟ ⎜ 4000 ⎟ ⎥ ⎣⎝ ⎠ ⎝ ⎠ ⎦ Hence; Total static pressure required at the fan discharge = (0.20 + 0.3315 – 0.21) – in wg Total static pressure required at the fan discharge = 0.3215-in wg
  • 4. Figure below shows the detail of duct hanger for ducts of various dimensions. Figure below shows the details of rectangular duct takeoffs for air supply to specific rooms or areas. NOTE: The equal-friction method of air-conditioning system duct design are applicable only to low-velocity systems in which the maximum air velocity is 3000 ft/min, or less.