2. What is Portal Plus?
A networkable access control system based on a 2 door controller
What type of readers may be used?
Proximity, Biometric and Keypad
What protocol is used for connection of the readers?
Wiegand 26 bit
How many users and events does the system support?
A maximum of 15,000 users and 30,000 events per controller
4. Controller Specification
Reader inputs 2
Door relays 2
Door sensor inputs 2
Door egress inputs 2
Users 1,000 – 15,000 per controller
Events 2,500 – 30,000 per controller
Programmable outputs 2 ( relays )
Programmable inputs 2 ( optocouplers )
Wiegand interface W26, W34 or customized 8 - 128 bit
Tamper protection external
Wiring Pluggable terminals
Communication interface RS485 Network and TCP/IP
Diagnostic Buzzer and 16 LED’s
5. Controller Specification
Supply voltage 11 - 15 VDC
Consumption 250 mA ( without readers )
Reader supply 500 mA max
Door relays 250 VAC, 10 A
Programmable outputs relays 250 VAC, 10 A
Programmable inputs 5 - 30 VDC, 3 mA - 28 mA
Environment temperature 0 - 45 C
Housing Metal
6. Control cabinets
Prewired control cabinets contain a 2 door
Portal Plus controller and 12Vdc 3.5A PSU
with battery back up facility
2 types of controller are available:
EWS – RS485 connectivity
EWSi – RS485 or TCP/IP connectivity
PPCU1 PPCU2 PPCU3 PPCU4
EWS: EWSi: EWS: EWSi:
RS485 RS485 & TCP/IP RS485 RS485 & TCP/IP
UBPSU3.5: UBPSU3.5: UBPSU3.5: UBPSU3.5:
12vDC 3.5A PSU 12vDC 3.5A PSU 12vDC 3.5A PSU 12vDC 3.5A PSU
CAB2: CAB2: ST3315: st3315:
Power coated Power coated Ip55 Power coated Ip55 Power coated
lockable control lockable control lockable control lockable control
cabinet cabinet cabinet cabinet
265hx360wx75d 265hx360wx75d 300hx300wx150d 300hx300wx150d
8. Connection Methods TCP/IP
Maximum distance between controller and switch, or switch and
pc = 100 meters
Unlimited amount of controllers may be used
Software may be used to monitor system locally on site, or off
site via the internet
Create a new TCP/IP network or make use of an existing network
Creating wireless networks may overcome issues where cable
cannot be laid
9. Connection Methods RS485
If a connection method of RS485 only is to be used then an ART.481 must be
used to convert USB at the PC end to RS485.
11. Connection Methods RS485
Maximum distance between Art.481 and furthest controller is 1km
Up 25 devices on a 1km BUS (controllers / BIOC readers and
Art.481 are all classed as devices)
A low capacitance 2 pair RS485 cable is recommended, such as
Beldon 9842 or equivalent
RS485 start and end of BUS must be terminated, and screen
must be connected to GND at one end only
RS485 hubs or repeaters may be used for larger distances or
additional controllers
13. Proximity Readers
51mm Resin potted zinc die cast proximity reader
Available in various colours
IP65 rated
92mm
Reads all EM4002 fobs (125Khz)
Wiegand 26 bit
Read range 3-5cm
MTPX-M
Audible and visual feedback
MTPXS-M - Silver
MTPXC-M - Charcoal
MTPXG-M - Green
MTPXR-M - Red
MTPXB-M - Blue
MTPXW-M - White
Standby Accepted Denied
14. Proximity Readers
Resin potted zinc die cast proximity reader
85mm
Vandal resistant
IP67 rated
115mm
Reads all EM4002 fobs (125Khz)
Wiegand 26 bit
Read range 3-5cm
VPROX2-M
Audible and visual feedback
Standby Accepted Denied
15. Panel Mount Proximity Readers
Xprox unit is a standard size panel mount reader –
resin potted (40mm x 40mm cut out)
Reads all EM4002 fobs (125Khz)
XPROX
Wiegand 26 bit
Read range 3-5cm
Audible and visual feedback
4849PP 4849PP and VR4KPPM allow integration of Portal Plus with
Videx 4000 Series equipment
VR4KPPM
16. Mifare Proximity Reader
51mm
Resin potted Mifare proximity reader
Capable of reading Mifare Classic,
Ultralight and Desfire (13.56 MHz)
90mm
IP67 rated
Wiegand 26 bit
Read range 1-6cm
Audible and visual feedback
MINI-MF-W26
Requires PROXE desktop reader for enrolment of fobs
17. Metal Backlit Keypad
51mm
Resin potted zinc die cast keypad complete with backlit
keys
Keys may be illuminated always or upon a
key press
90mm
IP65 rated
Selectable PIN code length (1 – 8 digits)
Wiegand 26 bit
MTPAD-M Audible and visual feedback
MTPADS-M - Silver
MTPADC-M - Charcoal
MTPADG-M - Green
MTPADR-M - Red
MTPADB-M - Blue
MTPADW-M - White
18. Proximity and keypad reader wiring
6 core alarm cable 6 core alarm cable
Maximum distance between readers and controller = 50 meters
19. Biometric Readers
51mm Resin potted zinc die cast biometric reader
place finger on to reader surface
IP54 rated
90mm
9999 finger template capacity (store up to 10 finger
templates per user)
BIOC Wiegand 26 bit
Audible and visual feedback
Seperate bio manager software available for ease of
integration on to third party controllers
BIOCS - Silver
BIOCC - Charcoal Fingers may be enrolled locally at reader or using BIOE
BIOCG - Green usb desktop reader
BIOCR - Red
BIOCB - Blue
BIOCW - White
20. Biometric Readers
51mm Resin potted zinc die cast biometric reader
‘Swipe’ finger down reader surface
IP65 rated
90mm
9999 finger template capacity (store up to 10 finger
templates per user)
BIOC-SW Wiegand 26 bit
Audible and visual feedback
Seperate bio manager software available for ease
of integration on to third party controllers
BIOCS-SW - Silver
BIOCC-SW - Charcoal Fingers may be enrolled locally at reader or using
BIOCG-SW - Green BIOE usb desktop reader
BIOCR-SW - Red
BIOCB-SW - Blue
BIOCW-SW - White
21. Biometric reader wiring
4 core alarm cable 2 pair screened RS485 4 core alarm cable
Maximum distance between readers and controller = 50 meters
RS485 must be wired in a series setup (in / out each device)
Unless a reader is within 3 meters of controller where it can be star wired
(common ground assumed between controllers)
22. Desktop Proximity Reader
zinc die cast desktop enrolment reader
Reads EM type fobs (125KHz)
Reads Mifare (13.56MHz)
(Classic, Ultralight and Desfire)
USB powered
No installation drivers required
(plug and play)
PROXE
Required on systems using Portal Plus Mifare readers
23. Desktop Biometric Reader
desktop optical fingerprint
enrolment reader
USB powered
Enables easy transfer of
fingerprint templates from a pc
to bioc readers
BIOE
24. Key Fobs / Cards
All fobs / cards are EM4002 type (125Khz):
Fobs / cards may be entered by their site code / user code
directly in the software, or by using the desktop enrolment reader.
PBX-1E
PBX-2
Site Code User Code
PBX-2C
25. Touch sensitive press to exit
51mm
Resin potted zinc die cast Press to exit
Available in various colours
92mm
IP66 rated
touch sensitive
Audible and visual feedback
MTT-EXIT
MTTS-EXIT - Silver
MTTC-EXIT - Charcoal
MTTG-EXIT - Green
MTTR-EXIT - Red
MTTB-EXIT - Blue
MTTW-EXIT - White
Standby Active
27. PC software
A copy of the Portal Plus software is supplied with each controller. The software
contains both the Lite and Pro versions, and is free of charge. A comparison of both
is shown below:
LITE PRO
Number of users Max. 15,000 Max. 15,000
Number if events logged Max. 30,000 per controller Max 30,000 per
controller
Number of time zones 24 24 per controller
Number of reader groups Unlimited Unlimited
Number of public holidays 32 32
Number of doors Unlimited Unlimited
Number of sites 1 Unlimited
Supported reader types Prox, Bio, Coded Prox, Bio, coded
Time & attendance no yes
Fire alarm role call no yes