                   Fire Risk Assessment
                           Review
                               For
                        59 Castillon Road
                             Catford
                             London
                            SE6 1QD




Date of Review
                        31/07/2009
Reviewer
                        Neil Tilley mbifm Tech IOSH (Neil Tilley Company)
On site person
responsible for Fire
Safety
nt – fra 59 Castillon Road Catford London




Contents:
Executive Summary

1.    Recommended Remedial Action Plan

2.    Review Summary
2.1   Original Recommended Corrective Action Plan
2.2   Review of building details/occupancy profile and history
2.3   Review of any Occupants at Special Risk
2.4   Review of Hazards
2.5   Review of the Maintenance of Existing Measures

3. Other Observations

Photo Library (if applicable)




Executive Summary

Neil Tilley 59 Castillon Road Catford London SE6 1QD                                                     2
Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
nt – fra 59 Castillon Road Catford London

This document is a review of the existing comprehensive Fire Risk Assessment as completed on the 7th November 2008 and
reviewed and up-dated on 25th March 2009

The review consisted of an audit of the existing Fire Risk Assessment with particularly reference to those significant defects
noted at the time of the original assessment and to measure the amount of corrective actions taken plus an audit of the
maintenance of existing preventive and protective measures.

A comprehensive building inspection was not completed but a sample number of key fire safety elements were checked.

Any new issues have also been highlighted

As a result of this review the significant defects noted are:
    • That a number of issues raised on the original assessment and subsequent reviews have not been actioned.
    • A number of these means that the responsible person as defined in the Regulatory Reform (Fire Safety) Order 2005
         could be in breech of that order.




Neil Tilley 59 Castillon Road Catford London SE6 1QD                                                                         2
Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
nt – fra 59 Castillon Road Catford London


Level of Risk
As a result of the Fire Risk Assessment review I would assess the residual risk to:

     •    All staff as being medium.

     •    The public as being medium.

     •    The continuity of the business as moderate.

  All ratings would drop to low upon confirmation that the sprinkler system is fully operational
             and is being tested, serviced and maintained to its installation standard.

These assessments are made on the assumption that all or the greater part of the
recommendations will be implemented within the given timeframes.

Where recommendations are not implemented it is suggested that the Fire Risk Assessment
is noted as to the reasons for not taking any action or what alternative actions were taken
instead.

It is recommended that the Fire Risk Assessment is comprehensively reviewed every year. It
will also require to be reviewed if:

     a) There are alterations to the building including any internal layout changes.
     b) Substantial changes to furniture and fittings.
     c) Changes to work activities or the way that you organise them, including the introduction
        of new equipment.
     d) The introduction, change of use or increase in the storage of hazardous materials.
     e) The failure of fire precautions e.g. fire detection systems and alarm system, life safety
        sprinklers systems or smoke ventilation systems.
     f) Significant changes to displays or quantities of stock or similar materials.
     g) Significant increase in the numbers of people present.
     h) The presence of people with some form of disability and who would require assistance
        to evacuate.
     i) If a fire or a “near-miss” incident occurs.




Neil Tilley 59 Castillon Road Catford London SE6 1QD                                                     2
Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
nt – fra 59 Castillon Road Catford London




                                                         Priority Rating Table
       Priority Ratings                                             Description
                              Urgent - Needs to be completed urgently as the hazard represents a high risk to all
                 A            occupants and represents a significant threat to the continuity of the business.
                              Medium - The risk is less than that of “A” but still a risk to occupants and a threat to the
                 B            continuity of the business. Action is required in the short to medium term.
                 C            Low - Work that is desirable or work that would be part of a servicing regime.




                                                                                                                              Date
Priority             Recommended Actions                              Comments                   Person Responsible
                                                                                                                           Completed

           Ensure that there are procedures in place   Vulnerable persons PEEP register policy                            12/06/2009
           that make provision for the evacuation of   in place. All staff should be aware.
   A       any disabled persons that doesn’t rely on   Usually the Fire Warden is the BUDDY.
           fire service intervention
                                                       Due to build fire lifts are DDA ready
nt – fra 59 Castillon Road Catford London

                                                                                                                                                   Date
       Priority                   Recommended Actions                               Comments                        Person Responsible
                                                                                                                                                Completed

                    Have a competent sprinkler system                Maintenance logs are up to date. A full    N TILLEY – Follow-up actions   12/06/2009
                    engineer carry out an audit on the sprinkler     programme of works is in place under       in green
                    system to ensure that the recessed heads         the current contract regime
                    are correctly aligned to the ceiling levels,
                    and that any painted caps have been
                    replaced.

                                                                     All logs with Bill Neeves
           A
                    Ensure that there is an integrity test carried
                    out on all gas flood rooms.


                                                                     Offending core 1 stationery stores now
                    Ensure that in all areas no goods are stored
                                                                     compliant
                    within half a metre of the sprinkler heads.



                    Replace the AFFF foam extinguisher inside        The AFFF extinguisher is a 9 L. The                                       12/06/2009
                    the third floor kitchen with a wet chemical      concern is weight. Chef assures his team
           A        extinguisher                                     are competent and the extinguisher is
                                                                     fit for purpose




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                        2
nt – fra 59 Castillon Road Catford London

                                                                                                                                            Date
       Priority                   Recommended Actions                             Comments                     Person Responsible
                                                                                                                                         Completed

                    Atrium Exit Doors: Change the door             These glass doors are historically left                              12/06/2009
                    hardware to allow for the doors to open in     locked open for that very reason.
                    the direction of escape                        Common practice


           A        As the final exit doors are electronically     This is the case
                    alarmed/control it is important that these
                    are tested regularly (monthly) to ensure
                    there correct operation



                    Have a competent person check all fires        tba                                                                  12/06/2009
                    door to ensure they are fully compliant.


           B        Fit an approved fire door hold open device
                    to the kitchen area fire door that is
                    persistently being wedged open.
                                                                   Retraining and advice to staff


                    Ensure there is a suitable testing regime in   PAT testing on a three year rolling plan.                            12/06/2009
                    place for electrical equipment. Particular     Home and external electricals are
                    attention should be paid to the kitchen        prohibited. Bespoke new work
           B        equipment that are thermostatically            equipment should be assessed by PME
                    controlled such as deep fat fryers.




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                  2
nt – fra 59 Castillon Road Catford London

                                                                                                                                        Date
       Priority                   Recommended Actions                             Comments                 Person Responsible
                                                                                                                                     Completed

                    Check the smoke detector in core 3 9th         Addressed                                                        12/06/2009
                    floor photocopying area where the unit
           B        dopes not appear to be sitting in its
                    bracket.



                    Ensure that within the back of house           Advice given to staff                                            12/06/2009
                    area of the third floor kitchen that
           B
                    escape routes should clearly
                    identified and routes kept clear

                    Check the smoke detector in core 3 Addressed                                                                    12/06/2009
                    9th floor photocopying area where
           B
                    the unit does not appear to be sitting
                    in its bracket.

                    Service the CO2 extinguishers in the Costa     On schedule. Staff spoken to. Compass                            12/06/2009
                    coffee bars and instruct staff on there safe   asked to join in on the Fire Officer
           B        handling to prevent this being a continuous    training
                    problem.


                    I would recommend that a periodic              NT as competent person                                           31/03/2009
           B        (monthly) visual check is scheduled
                    to be made of all extinguishers




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                              2
nt – fra 59 Castillon Road Catford London

                                                                                                                               Date
       Priority                   Recommended Actions                            Comments         Person Responsible
                                                                                                                            Completed

                    Ensure all staff receive appropriate fire      Company Policy sets the pace                            12/06/2009
                    safety training as outlined within the
                    Regulatory Reform (Fire Safety) Order
                    2005.

           B

                    Ensure kitchen staff receive adequate fire
                                                                   Chef assures staff competent
                    safety training including the practical use
                    of fire extinguishers.




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                     2
nt – fra 59 Castillon Road Catford London



                                                 2.2 REVIEW SUMMARY OF BUILDING DETAILS/OCCUPANCY PROFILE AND HISTORY




                  Item                                             Findings                                       Comments



                                      The only significant changes have been to floor layouts and
        Building Details              this principally means the removal of internal glass
                                      partitions.



                                      Staff occupancy numbers have been reduced
        Staff Occupancy
                                      .


                                      As per the previous FRA access to the building is strictly
        Public Use                    controlled.



                                      The buildings is in good condition and appears well
        Summary of                    maintained
        Building
        Observations


        History                       Since the previous FRA there have been no significant
                                      incidents




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                              2
nt – fra 59 Castillon Road Catford London




                                                                   2.3. REVIEW OF ANY OCCUPANTS AT SPECIAL RISK




                        Item                                            Findings                                                  Comments



        Sleeping                                  No provision for sleeping on site

        Disabled/others who    As per previous FRA there lacks formalised                               This lack is a management failing. A full plan is in place but
        may require            procedures for the evacuation of disable persons                         is either mis-understood or not known. N Tilley to redress
        assistance to evacuate although the building has good provision for this in                     this balance
                                                  the form of evacuation lifts. This procedure must
                                                  be able to be carried out by staff and not rely on
                                                  fire service intervention.



        Working in remote                         Given the fixed and active fire protection measures
        areas                                     within the building along with access controls then
                                                  working in remote areas is not a significant risk.



        Young persons                             There would normally be young persons employed        Compliance is via N Tilley, M Dumbura, BU involved & HR
                                                  within the building. Where this may occur such as
                                                  for work experience then a separate and suitable
                                                  risk assessment is carried out.

        Contractors (non-                         There are contractor controls in place by the
        employees)                                building management.




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                              2
nt – fra 59 Castillon Road Catford London



                                                                             2.4. REVIEW OF HAZARDS




                        Item                                           Findings                                                 Comments



        Control of Ignition Sources               The site management team responsible for the 250     Ensure there is a suitable testing regime in place for
                                                  Bishopsgate appear to take all reasonable steps to   electrical equipment. Particular attention should be paid to
                                                  ensure the control of ignition sources.              the kitchen equipment that are thermostatically controlled
                                                                                                       such as deep fat fryers.
                                                  An audit of electrical equipment noted that whilst
                                                  some electrical had been subjected to recent
                                                  testing this was not all inclusive. Particular
                                                  attention should be paid to the kitchen equipment
                                                  that are thermostatically controlled such as deep
                                                  fat fryers.




        Control of Fuels                          The site management team appear to take all
                                                  reasonable steps to control flammable materials
                                                  within the building.




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                            2
nt – fra 59 Castillon Road Catford London



                                                                   2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES




                        Item                                              Findings                                                   Comments



        Fire-fighting Equipment                   There are fire extinguishers located through out         Service the CO2 extinguishers in the Costa coffee bars and
                                                  the floor areas. Recently installed extinguishers in     instruct staff on there safe handling to prevent this being a
                                                  the Costa coffee bars were found to have damaged         continuous problem.
                                                  anti-tamper tags and/or pins partly removed.
                                                  These units require urgent servicing

                                                  The Foam extinguisher is still in the kitchen. If this    I would recommend that a periodic (monthly) visual check
                                                  extinguisher was to be operated in and around the        is scheduled to be made of all extinguishers
                                                  deep fat fryers or other hot oil this could present a
                                                  significant threat to the user or other staff and
                                                  could spread the fire. The extinguisher should be
                                                  replaced with a wet chemical extinguisher.

                                                  Given the number of extinguishers missing anti-
                                                  tamper tag and pins removed or partly removed I
                                                  would recommend that a periodic (monthly) visual
                                                  check is scheduled to be made of all extinguishers.



        Fire Suppression, Detection               As per previous risk assessment concerns have            Check the smoke detector in core 3 / 9th floor photocopying
        and Evacuation Alarms                     been expressed regarding the recessed sprinkler          area where the unit dopes not appear to be sitting in its
        Systems                                   heads. There was not evidence on hand to show            bracket.
                                                  the system has been checked and in fact in the
                                                  kitchen area on the third floor a head was missing
                                                  a cover-plate and the head was poorly aligned to
                                                  the ceiling. It was not possible to determine that


Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                                 2
nt – fra 59 Castillon Road Catford London



                                                                   2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES




                        Item                                              Findings                                                  Comments



                                                  this was a”drop-down” head.

                                                  The site representative did inform me that a large
                                                  number of the existing glass walls were to be
                                                  removed, this should help with the both the
                                                  location of the smoke detectors as well as the
                                                  spray pattern o f the sprinkler heads.

                                                  Within the photocopying area on the 9th floor core
                                                  3 the existing smoke detector is not sitting
                                                  correctly in its bracket

                                                  As per previous fire risk assessment goods are still
                                                  being stored within 0.5m of sprinkler heads. (L5)



        Means of Escape                           At the time of the review all exits from the floors     Atrium Exit Doors: Change the door hardware to allow for
                                                  were found to be in good order. Again my concern        the doors to open in the direction of escape
                                                  is that there are a number of doors leading to exits
                                                  which have key locks. Again I reiterate that any exit
                                                  door (including doors access the exit route) should
                                                                                                          As the final exit doors are electronically alarmed/control it
                                                  be able to be opened without the use of a key.
                                                                                                          is important that these are tested regularly (monthly) to
                                                  With proposed works being planed on some floors         ensure there correct operation
                                                  the design should be such not to restrict access to
                                                                                                          These door locks definitely have no key available.
                                                  the exit routes. In some case access ways are less
                                                  than 800mm.

Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                                2
nt – fra 59 Castillon Road Catford London



                                                                   2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES




                        Item                                              Findings                                                Comments



                                                  The area at the rear of the main client kitchens was
                                                  again found to have a trolleys and other
                                                  equipment blocking the exit ways

                                                  Within the atrium the exit doors, which would be
                                                  the escape route for large numbers of people open
                                                  inwards. I believe it would be a simple operation to
                                                  change these to double swung doors therefore
                                                  allowing the doors to open in the direction of the
                                                  escape route.

                                                  As the final exit doors are electronically
                                                  alarmed/control it is important that these are
                                                  tested regularly (monthly) to ensure there correct
                                                  operation. This could be done by security officer
                                                  after hours and during regular building checks

        Fire Separation                           As per the previous fire risk assessment some key      N Tilley has suitable ROSPA signage and is to reiterate
                                                  fire doors were found to be wedged open.               instruction



        Signage                                   Signage is as found on previous FRAs.



        Emergency Escape Lighting                 The emergency lighting appears to be adequate
                                                  throughout, although this was based on a visual


Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                              2
nt – fra 59 Castillon Road Catford London



                                                                   2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES




                        Item                                              Findings                                      Comments



                                                  inspection at the time of the visit and no test was
                                                  carried out on the luminance level or the
                                                  verification of compliance with British Standards.



        Housekeeping                              At the time of the review apart from the client
                                                  kitchen area, housekeeping was better



        Equipment/Information                     As per the Fire Risk assessment.
        Provided for Fire Brigade
                                                  Limited information is held for Fire-fighters but
                                                  there is security on site 24/7



        Records                                   Records showing the maintenance of all safety
                                                  systems were limited




        Co-operation and Co-                      This is basically a single occupied building but a
        ordination                                number of the services are contracted out




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                    2
nt – fra 59 Castillon Road Catford London



                                                                   2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES




                        Item                                              Findings                                                 Comments



        Emergency Planning                        There is a basic emergency plan in place but no        Formal plans for DDA compliance is not visible. N Tilley to
                                                  formal arrangements for the evacuation of any          address this 12/06/2009
                                                  disabled persons. Whilst the building has good
                                                  safety features a formalized plan is need to ensure
                                                  the safe evacuation of all persons without fire
                                                  service intervention.. This may require the
                                                  assistance of the security staff



        Staff Training                            Key staff continue to be trained but general staff     Ensure all staff receive appropriate fire safety training as
                                                  training appears to be limited.                        outlined within the Regulatory Reform (Fire Safety) Order
                                                                                                         2005.
                                                  It should also be noted that as the operation of the
                                                  kitchen is outsourced it is important that these       Ensure kitchen staff receive adequate fire safety training
                                                  staff members receive adequate fire safety training    including the practical use of fire extinguishers.
                                                  including the practical use of fire extinguishers.




Neil Tilley 59 Castillon Road Catford London SE6 1QD

Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com                                                               2
nt – fra 59 Castillon Road Catford London



3. OTHER OBERSERVATIONS
Records

Records should be kept to demonstrate compliance with Fire Safety law particularly records showing the maintenance of all
fire-protection equipment and training.

I suggest that a Fire Safety log book be introduced and within this should be:

    a) A copy of the FRA.

    b) A copy of the emergency plan plus identification of key staff and their roles.

    c) Records showing the maintenance of all fire safety systems within the building.

    d) Details of staff training.

    e) Incident reposts showing details of any fire, false alarms or near miss incidents.

It is recommended that within the Fire Safety log book is kept a line drawing covering each floor detailing general fire
precautions measures for that floor. This could include:-

    •    Fire Warden Evacuation zones.

    •    Break glass call points.

    •    Emergency lighting units.

    •    Fire extinguishers (including types).

    •    Emergency exits.

    •    Fire doors with self closures.

    •    Fire resistant constructions such as protected escape routes.
nt – fra 59 Castillon Road Catford London



9) Photo Library:
Sprinkler head with the kitchen area ceiling. Not the large build up of dust and other material on the head. The head is also
not centred on the ceiling hole. There are some obvious electrical faults. Overloaded adaptors, multiple extension ganging.
Obstructions to fire corridor.




Neil Tilley 59 Castillon Road Catford London SE6 1QD                                                                            2
Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
nt – fra 59 Castillon Road Catford London




Neil Tilley 59 Castillon Road Catford London SE6 1QD                                                     2
Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com

Weitere ähnliche Inhalte

Was ist angesagt?

Basic Fire & Fire Extinguisher Training.ppt
Basic Fire & Fire Extinguisher Training.pptBasic Fire & Fire Extinguisher Training.ppt
Basic Fire & Fire Extinguisher Training.pptRonald Aranha
 
Armazenagem de Produtos Quimicos
Armazenagem de Produtos QuimicosArmazenagem de Produtos Quimicos
Armazenagem de Produtos Quimicosrhtdesenvolvimento
 
Epi para trabalho em altura NR 35
Epi para trabalho em altura NR 35Epi para trabalho em altura NR 35
Epi para trabalho em altura NR 35DiegoAugusto86
 
Prevenzione incendi
Prevenzione incendiPrevenzione incendi
Prevenzione incendii6dxa
 
Ar comprimido - Segurança na operação (oficial)
Ar comprimido - Segurança na operação (oficial)Ar comprimido - Segurança na operação (oficial)
Ar comprimido - Segurança na operação (oficial)Claudio Cesar Pontes ن
 
Plano de Segurança do Trabalho em Oficinas Mecânicas de Veículos Pesados
Plano de Segurança do Trabalho em Oficinas Mecânicas de Veículos PesadosPlano de Segurança do Trabalho em Oficinas Mecânicas de Veículos Pesados
Plano de Segurança do Trabalho em Oficinas Mecânicas de Veículos PesadosJonas Abilio Sestrem Jr
 
Emergency drills: A Problem with Effectiveness
Emergency drills: A Problem with EffectivenessEmergency drills: A Problem with Effectiveness
Emergency drills: A Problem with Effectivenessavoelzke
 
Working Alone Safely: Controlling the Risks of Solitary Work
Working Alone Safely: Controlling the Risks of Solitary WorkWorking Alone Safely: Controlling the Risks of Solitary Work
Working Alone Safely: Controlling the Risks of Solitary WorkSafety+Health magazine
 
Safety presentation isolation and tagging
Safety presentation isolation and taggingSafety presentation isolation and tagging
Safety presentation isolation and taggingWarwick Bursey
 
Health and safety committe roles and operations
Health and safety committe roles and operationsHealth and safety committe roles and operations
Health and safety committe roles and operationsEaneida
 
Apresentação NR26
Apresentação NR26Apresentação NR26
Apresentação NR26André Tobo
 
Hazard Control Safety Training
Hazard Control Safety TrainingHazard Control Safety Training
Hazard Control Safety Trainingsafety113
 
TLV History
TLV HistoryTLV History
TLV HistoryDIv CHAS
 
Accident reporting procedure
Accident reporting procedureAccident reporting procedure
Accident reporting procedureJasabir Arora
 
HIERARCHY OF CONTROL
HIERARCHY OF CONTROLHIERARCHY OF CONTROL
HIERARCHY OF CONTROLIzam Lukman
 

Was ist angesagt? (20)

Basic Fire & Fire Extinguisher Training.ppt
Basic Fire & Fire Extinguisher Training.pptBasic Fire & Fire Extinguisher Training.ppt
Basic Fire & Fire Extinguisher Training.ppt
 
Safety Briefing Trc
Safety Briefing  TrcSafety Briefing  Trc
Safety Briefing Trc
 
Nfpa 10 extintores portatiles
Nfpa 10 extintores portatilesNfpa 10 extintores portatiles
Nfpa 10 extintores portatiles
 
Armazenagem de Produtos Quimicos
Armazenagem de Produtos QuimicosArmazenagem de Produtos Quimicos
Armazenagem de Produtos Quimicos
 
Epi para trabalho em altura NR 35
Epi para trabalho em altura NR 35Epi para trabalho em altura NR 35
Epi para trabalho em altura NR 35
 
Prevenzione incendi
Prevenzione incendiPrevenzione incendi
Prevenzione incendi
 
Ar comprimido - Segurança na operação (oficial)
Ar comprimido - Segurança na operação (oficial)Ar comprimido - Segurança na operação (oficial)
Ar comprimido - Segurança na operação (oficial)
 
Programa de proteção respiratória
Programa de proteção respiratóriaPrograma de proteção respiratória
Programa de proteção respiratória
 
Plano de Segurança do Trabalho em Oficinas Mecânicas de Veículos Pesados
Plano de Segurança do Trabalho em Oficinas Mecânicas de Veículos PesadosPlano de Segurança do Trabalho em Oficinas Mecânicas de Veículos Pesados
Plano de Segurança do Trabalho em Oficinas Mecânicas de Veículos Pesados
 
Emergency drills: A Problem with Effectiveness
Emergency drills: A Problem with EffectivenessEmergency drills: A Problem with Effectiveness
Emergency drills: A Problem with Effectiveness
 
Chemical industry & its safety training
Chemical industry & its safety trainingChemical industry & its safety training
Chemical industry & its safety training
 
Working Alone Safely: Controlling the Risks of Solitary Work
Working Alone Safely: Controlling the Risks of Solitary WorkWorking Alone Safely: Controlling the Risks of Solitary Work
Working Alone Safely: Controlling the Risks of Solitary Work
 
Safety presentation isolation and tagging
Safety presentation isolation and taggingSafety presentation isolation and tagging
Safety presentation isolation and tagging
 
SHUTDOWN
SHUTDOWNSHUTDOWN
SHUTDOWN
 
Health and safety committe roles and operations
Health and safety committe roles and operationsHealth and safety committe roles and operations
Health and safety committe roles and operations
 
Apresentação NR26
Apresentação NR26Apresentação NR26
Apresentação NR26
 
Hazard Control Safety Training
Hazard Control Safety TrainingHazard Control Safety Training
Hazard Control Safety Training
 
TLV History
TLV HistoryTLV History
TLV History
 
Accident reporting procedure
Accident reporting procedureAccident reporting procedure
Accident reporting procedure
 
HIERARCHY OF CONTROL
HIERARCHY OF CONTROLHIERARCHY OF CONTROL
HIERARCHY OF CONTROL
 

Andere mochten auch

How to carry out fire risk assessments
How to carry out fire risk assessmentsHow to carry out fire risk assessments
How to carry out fire risk assessmentsQuick-Test
 
Film production risk assessment form
Film production risk assessment formFilm production risk assessment form
Film production risk assessment formcembitmead
 
Fire Risk Assessment Presentation
Fire Risk Assessment PresentationFire Risk Assessment Presentation
Fire Risk Assessment PresentationDavid Cant - CMIOSH
 
Risk assessment template
Risk assessment templateRisk assessment template
Risk assessment templatetamz486
 
Bizsafe Risk Assessment
Bizsafe Risk AssessmentBizsafe Risk Assessment
Bizsafe Risk Assessmentsearchgeeksg
 
Risk assessment
Risk assessmentRisk assessment
Risk assessmentchamahan
 
J McGinty_NEBOSH Certificate in Occupational Health & Safety
J McGinty_NEBOSH Certificate in Occupational Health & SafetyJ McGinty_NEBOSH Certificate in Occupational Health & Safety
J McGinty_NEBOSH Certificate in Occupational Health & SafetyJames McGinty
 
Risk assessment template media
Risk assessment template mediaRisk assessment template media
Risk assessment template mediaKhem Slawson
 
Risk factors and risk assessment of periodontal disease.
Risk factors and risk assessment of periodontal disease.Risk factors and risk assessment of periodontal disease.
Risk factors and risk assessment of periodontal disease.Gururam MDS
 
Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...
Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...
Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...Evan Goldsmith
 
Risk assessment principles and guidelines
Risk assessment principles and guidelinesRisk assessment principles and guidelines
Risk assessment principles and guidelinesHaris Tahir
 

Andere mochten auch (17)

How to carry out fire risk assessments
How to carry out fire risk assessmentsHow to carry out fire risk assessments
How to carry out fire risk assessments
 
Film production risk assessment form
Film production risk assessment formFilm production risk assessment form
Film production risk assessment form
 
Fire Risk Assessment Presentation
Fire Risk Assessment PresentationFire Risk Assessment Presentation
Fire Risk Assessment Presentation
 
Risk assessment template
Risk assessment templateRisk assessment template
Risk assessment template
 
Risk assessment c19
Risk assessment c19Risk assessment c19
Risk assessment c19
 
Bizsafe Risk Assessment
Bizsafe Risk AssessmentBizsafe Risk Assessment
Bizsafe Risk Assessment
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 
Designers Risk Assessment
Designers Risk AssessmentDesigners Risk Assessment
Designers Risk Assessment
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 
J McGinty_NEBOSH Certificate in Occupational Health & Safety
J McGinty_NEBOSH Certificate in Occupational Health & SafetyJ McGinty_NEBOSH Certificate in Occupational Health & Safety
J McGinty_NEBOSH Certificate in Occupational Health & Safety
 
Risk assessment template media
Risk assessment template mediaRisk assessment template media
Risk assessment template media
 
Risk factors and risk assessment of periodontal disease.
Risk factors and risk assessment of periodontal disease.Risk factors and risk assessment of periodontal disease.
Risk factors and risk assessment of periodontal disease.
 
risk assessment
risk assessmentrisk assessment
risk assessment
 
Risk Assessment and Reduction
Risk Assessment and ReductionRisk Assessment and Reduction
Risk Assessment and Reduction
 
Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...
Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...
Fire Hazard Risk and Response Capacity Assessment in Aftermath of Kathmandu V...
 
Risk assessment principles and guidelines
Risk assessment principles and guidelinesRisk assessment principles and guidelines
Risk assessment principles and guidelines
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 

Ähnlich wie My Fire Risk Assessment Template

Minimax Fire Fighting Systems - Joerg Lindner
Minimax Fire Fighting Systems - Joerg Lindner Minimax Fire Fighting Systems - Joerg Lindner
Minimax Fire Fighting Systems - Joerg Lindner Jenna Cali
 
2 eliminate hidden riskof cui
2 eliminate hidden riskof cui2 eliminate hidden riskof cui
2 eliminate hidden riskof cuiJithu John
 
KOM Presentation STN-N Conductor_rev 2
KOM Presentation STN-N Conductor_rev 2KOM Presentation STN-N Conductor_rev 2
KOM Presentation STN-N Conductor_rev 2Brian Quan (Minh)
 
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainDefender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainlyndaflintof
 
Unit 104 sample questions
Unit 104 sample questionsUnit 104 sample questions
Unit 104 sample questionswirethehouse
 

Ähnlich wie My Fire Risk Assessment Template (6)

Minimax Fire Fighting Systems - Joerg Lindner
Minimax Fire Fighting Systems - Joerg Lindner Minimax Fire Fighting Systems - Joerg Lindner
Minimax Fire Fighting Systems - Joerg Lindner
 
2 eliminate hidden riskof cui
2 eliminate hidden riskof cui2 eliminate hidden riskof cui
2 eliminate hidden riskof cui
 
KOM Presentation STN-N Conductor_rev 2
KOM Presentation STN-N Conductor_rev 2KOM Presentation STN-N Conductor_rev 2
KOM Presentation STN-N Conductor_rev 2
 
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainDefender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
 
Unit 104 sample questions
Unit 104 sample questionsUnit 104 sample questions
Unit 104 sample questions
 
Warmer Homes Workshop - WHS Team
Warmer Homes Workshop - WHS TeamWarmer Homes Workshop - WHS Team
Warmer Homes Workshop - WHS Team
 

My Fire Risk Assessment Template

  • 1. nt – fra 59 Castillon Road Catford London Fire Risk Assessment Review For 59 Castillon Road Catford London SE6 1QD Date of Review 31/07/2009 Reviewer Neil Tilley mbifm Tech IOSH (Neil Tilley Company) On site person responsible for Fire Safety
  • 2. nt – fra 59 Castillon Road Catford London Contents: Executive Summary 1. Recommended Remedial Action Plan 2. Review Summary 2.1 Original Recommended Corrective Action Plan 2.2 Review of building details/occupancy profile and history 2.3 Review of any Occupants at Special Risk 2.4 Review of Hazards 2.5 Review of the Maintenance of Existing Measures 3. Other Observations Photo Library (if applicable) Executive Summary Neil Tilley 59 Castillon Road Catford London SE6 1QD 2 Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
  • 3. nt – fra 59 Castillon Road Catford London This document is a review of the existing comprehensive Fire Risk Assessment as completed on the 7th November 2008 and reviewed and up-dated on 25th March 2009 The review consisted of an audit of the existing Fire Risk Assessment with particularly reference to those significant defects noted at the time of the original assessment and to measure the amount of corrective actions taken plus an audit of the maintenance of existing preventive and protective measures. A comprehensive building inspection was not completed but a sample number of key fire safety elements were checked. Any new issues have also been highlighted As a result of this review the significant defects noted are: • That a number of issues raised on the original assessment and subsequent reviews have not been actioned. • A number of these means that the responsible person as defined in the Regulatory Reform (Fire Safety) Order 2005 could be in breech of that order. Neil Tilley 59 Castillon Road Catford London SE6 1QD 2 Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
  • 4. nt – fra 59 Castillon Road Catford London Level of Risk As a result of the Fire Risk Assessment review I would assess the residual risk to: • All staff as being medium. • The public as being medium. • The continuity of the business as moderate. All ratings would drop to low upon confirmation that the sprinkler system is fully operational and is being tested, serviced and maintained to its installation standard. These assessments are made on the assumption that all or the greater part of the recommendations will be implemented within the given timeframes. Where recommendations are not implemented it is suggested that the Fire Risk Assessment is noted as to the reasons for not taking any action or what alternative actions were taken instead. It is recommended that the Fire Risk Assessment is comprehensively reviewed every year. It will also require to be reviewed if: a) There are alterations to the building including any internal layout changes. b) Substantial changes to furniture and fittings. c) Changes to work activities or the way that you organise them, including the introduction of new equipment. d) The introduction, change of use or increase in the storage of hazardous materials. e) The failure of fire precautions e.g. fire detection systems and alarm system, life safety sprinklers systems or smoke ventilation systems. f) Significant changes to displays or quantities of stock or similar materials. g) Significant increase in the numbers of people present. h) The presence of people with some form of disability and who would require assistance to evacuate. i) If a fire or a “near-miss” incident occurs. Neil Tilley 59 Castillon Road Catford London SE6 1QD 2 Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com
  • 5. nt – fra 59 Castillon Road Catford London Priority Rating Table Priority Ratings Description Urgent - Needs to be completed urgently as the hazard represents a high risk to all A occupants and represents a significant threat to the continuity of the business. Medium - The risk is less than that of “A” but still a risk to occupants and a threat to the B continuity of the business. Action is required in the short to medium term. C Low - Work that is desirable or work that would be part of a servicing regime. Date Priority Recommended Actions Comments Person Responsible Completed Ensure that there are procedures in place Vulnerable persons PEEP register policy 12/06/2009 that make provision for the evacuation of in place. All staff should be aware. A any disabled persons that doesn’t rely on Usually the Fire Warden is the BUDDY. fire service intervention Due to build fire lifts are DDA ready
  • 6. nt – fra 59 Castillon Road Catford London Date Priority Recommended Actions Comments Person Responsible Completed Have a competent sprinkler system Maintenance logs are up to date. A full N TILLEY – Follow-up actions 12/06/2009 engineer carry out an audit on the sprinkler programme of works is in place under in green system to ensure that the recessed heads the current contract regime are correctly aligned to the ceiling levels, and that any painted caps have been replaced. All logs with Bill Neeves A Ensure that there is an integrity test carried out on all gas flood rooms. Offending core 1 stationery stores now Ensure that in all areas no goods are stored compliant within half a metre of the sprinkler heads. Replace the AFFF foam extinguisher inside The AFFF extinguisher is a 9 L. The 12/06/2009 the third floor kitchen with a wet chemical concern is weight. Chef assures his team A extinguisher are competent and the extinguisher is fit for purpose Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 7. nt – fra 59 Castillon Road Catford London Date Priority Recommended Actions Comments Person Responsible Completed Atrium Exit Doors: Change the door These glass doors are historically left 12/06/2009 hardware to allow for the doors to open in locked open for that very reason. the direction of escape Common practice A As the final exit doors are electronically This is the case alarmed/control it is important that these are tested regularly (monthly) to ensure there correct operation Have a competent person check all fires tba 12/06/2009 door to ensure they are fully compliant. B Fit an approved fire door hold open device to the kitchen area fire door that is persistently being wedged open. Retraining and advice to staff Ensure there is a suitable testing regime in PAT testing on a three year rolling plan. 12/06/2009 place for electrical equipment. Particular Home and external electricals are attention should be paid to the kitchen prohibited. Bespoke new work B equipment that are thermostatically equipment should be assessed by PME controlled such as deep fat fryers. Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 8. nt – fra 59 Castillon Road Catford London Date Priority Recommended Actions Comments Person Responsible Completed Check the smoke detector in core 3 9th Addressed 12/06/2009 floor photocopying area where the unit B dopes not appear to be sitting in its bracket. Ensure that within the back of house Advice given to staff 12/06/2009 area of the third floor kitchen that B escape routes should clearly identified and routes kept clear Check the smoke detector in core 3 Addressed 12/06/2009 9th floor photocopying area where B the unit does not appear to be sitting in its bracket. Service the CO2 extinguishers in the Costa On schedule. Staff spoken to. Compass 12/06/2009 coffee bars and instruct staff on there safe asked to join in on the Fire Officer B handling to prevent this being a continuous training problem. I would recommend that a periodic NT as competent person 31/03/2009 B (monthly) visual check is scheduled to be made of all extinguishers Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 9. nt – fra 59 Castillon Road Catford London Date Priority Recommended Actions Comments Person Responsible Completed Ensure all staff receive appropriate fire Company Policy sets the pace 12/06/2009 safety training as outlined within the Regulatory Reform (Fire Safety) Order 2005. B Ensure kitchen staff receive adequate fire Chef assures staff competent safety training including the practical use of fire extinguishers. Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 10. nt – fra 59 Castillon Road Catford London 2.2 REVIEW SUMMARY OF BUILDING DETAILS/OCCUPANCY PROFILE AND HISTORY Item Findings Comments The only significant changes have been to floor layouts and Building Details this principally means the removal of internal glass partitions. Staff occupancy numbers have been reduced Staff Occupancy . As per the previous FRA access to the building is strictly Public Use controlled. The buildings is in good condition and appears well Summary of maintained Building Observations History Since the previous FRA there have been no significant incidents Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 11. nt – fra 59 Castillon Road Catford London 2.3. REVIEW OF ANY OCCUPANTS AT SPECIAL RISK Item Findings Comments Sleeping No provision for sleeping on site Disabled/others who As per previous FRA there lacks formalised This lack is a management failing. A full plan is in place but may require procedures for the evacuation of disable persons is either mis-understood or not known. N Tilley to redress assistance to evacuate although the building has good provision for this in this balance the form of evacuation lifts. This procedure must be able to be carried out by staff and not rely on fire service intervention. Working in remote Given the fixed and active fire protection measures areas within the building along with access controls then working in remote areas is not a significant risk. Young persons There would normally be young persons employed Compliance is via N Tilley, M Dumbura, BU involved & HR within the building. Where this may occur such as for work experience then a separate and suitable risk assessment is carried out. Contractors (non- There are contractor controls in place by the employees) building management. Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 12. nt – fra 59 Castillon Road Catford London 2.4. REVIEW OF HAZARDS Item Findings Comments Control of Ignition Sources The site management team responsible for the 250 Ensure there is a suitable testing regime in place for Bishopsgate appear to take all reasonable steps to electrical equipment. Particular attention should be paid to ensure the control of ignition sources. the kitchen equipment that are thermostatically controlled such as deep fat fryers. An audit of electrical equipment noted that whilst some electrical had been subjected to recent testing this was not all inclusive. Particular attention should be paid to the kitchen equipment that are thermostatically controlled such as deep fat fryers. Control of Fuels The site management team appear to take all reasonable steps to control flammable materials within the building. Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 13. nt – fra 59 Castillon Road Catford London 2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES Item Findings Comments Fire-fighting Equipment There are fire extinguishers located through out Service the CO2 extinguishers in the Costa coffee bars and the floor areas. Recently installed extinguishers in instruct staff on there safe handling to prevent this being a the Costa coffee bars were found to have damaged continuous problem. anti-tamper tags and/or pins partly removed. These units require urgent servicing The Foam extinguisher is still in the kitchen. If this I would recommend that a periodic (monthly) visual check extinguisher was to be operated in and around the is scheduled to be made of all extinguishers deep fat fryers or other hot oil this could present a significant threat to the user or other staff and could spread the fire. The extinguisher should be replaced with a wet chemical extinguisher. Given the number of extinguishers missing anti- tamper tag and pins removed or partly removed I would recommend that a periodic (monthly) visual check is scheduled to be made of all extinguishers. Fire Suppression, Detection As per previous risk assessment concerns have Check the smoke detector in core 3 / 9th floor photocopying and Evacuation Alarms been expressed regarding the recessed sprinkler area where the unit dopes not appear to be sitting in its Systems heads. There was not evidence on hand to show bracket. the system has been checked and in fact in the kitchen area on the third floor a head was missing a cover-plate and the head was poorly aligned to the ceiling. It was not possible to determine that Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 14. nt – fra 59 Castillon Road Catford London 2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES Item Findings Comments this was a”drop-down” head. The site representative did inform me that a large number of the existing glass walls were to be removed, this should help with the both the location of the smoke detectors as well as the spray pattern o f the sprinkler heads. Within the photocopying area on the 9th floor core 3 the existing smoke detector is not sitting correctly in its bracket As per previous fire risk assessment goods are still being stored within 0.5m of sprinkler heads. (L5) Means of Escape At the time of the review all exits from the floors Atrium Exit Doors: Change the door hardware to allow for were found to be in good order. Again my concern the doors to open in the direction of escape is that there are a number of doors leading to exits which have key locks. Again I reiterate that any exit door (including doors access the exit route) should As the final exit doors are electronically alarmed/control it be able to be opened without the use of a key. is important that these are tested regularly (monthly) to With proposed works being planed on some floors ensure there correct operation the design should be such not to restrict access to These door locks definitely have no key available. the exit routes. In some case access ways are less than 800mm. Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 15. nt – fra 59 Castillon Road Catford London 2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES Item Findings Comments The area at the rear of the main client kitchens was again found to have a trolleys and other equipment blocking the exit ways Within the atrium the exit doors, which would be the escape route for large numbers of people open inwards. I believe it would be a simple operation to change these to double swung doors therefore allowing the doors to open in the direction of the escape route. As the final exit doors are electronically alarmed/control it is important that these are tested regularly (monthly) to ensure there correct operation. This could be done by security officer after hours and during regular building checks Fire Separation As per the previous fire risk assessment some key N Tilley has suitable ROSPA signage and is to reiterate fire doors were found to be wedged open. instruction Signage Signage is as found on previous FRAs. Emergency Escape Lighting The emergency lighting appears to be adequate throughout, although this was based on a visual Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 16. nt – fra 59 Castillon Road Catford London 2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES Item Findings Comments inspection at the time of the visit and no test was carried out on the luminance level or the verification of compliance with British Standards. Housekeeping At the time of the review apart from the client kitchen area, housekeeping was better Equipment/Information As per the Fire Risk assessment. Provided for Fire Brigade Limited information is held for Fire-fighters but there is security on site 24/7 Records Records showing the maintenance of all safety systems were limited Co-operation and Co- This is basically a single occupied building but a ordination number of the services are contracted out Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 17. nt – fra 59 Castillon Road Catford London 2.5 REVIEW OF MAINTENANCE OF EXISTING MEASURES Item Findings Comments Emergency Planning There is a basic emergency plan in place but no Formal plans for DDA compliance is not visible. N Tilley to formal arrangements for the evacuation of any address this 12/06/2009 disabled persons. Whilst the building has good safety features a formalized plan is need to ensure the safe evacuation of all persons without fire service intervention.. This may require the assistance of the security staff Staff Training Key staff continue to be trained but general staff Ensure all staff receive appropriate fire safety training as training appears to be limited. outlined within the Regulatory Reform (Fire Safety) Order 2005. It should also be noted that as the operation of the kitchen is outsourced it is important that these Ensure kitchen staff receive adequate fire safety training staff members receive adequate fire safety training including the practical use of fire extinguishers. including the practical use of fire extinguishers. Neil Tilley 59 Castillon Road Catford London SE6 1QD Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com 2
  • 18. nt – fra 59 Castillon Road Catford London 3. OTHER OBERSERVATIONS Records Records should be kept to demonstrate compliance with Fire Safety law particularly records showing the maintenance of all fire-protection equipment and training. I suggest that a Fire Safety log book be introduced and within this should be: a) A copy of the FRA. b) A copy of the emergency plan plus identification of key staff and their roles. c) Records showing the maintenance of all fire safety systems within the building. d) Details of staff training. e) Incident reposts showing details of any fire, false alarms or near miss incidents. It is recommended that within the Fire Safety log book is kept a line drawing covering each floor detailing general fire precautions measures for that floor. This could include:- • Fire Warden Evacuation zones. • Break glass call points. • Emergency lighting units. • Fire extinguishers (including types). • Emergency exits. • Fire doors with self closures. • Fire resistant constructions such as protected escape routes.
  • 19. nt – fra 59 Castillon Road Catford London 9) Photo Library: Sprinkler head with the kitchen area ceiling. Not the large build up of dust and other material on the head. The head is also not centred on the ceiling hole. There are some obvious electrical faults. Overloaded adaptors, multiple extension ganging. Obstructions to fire corridor. Neil Tilley 59 Castillon Road Catford London SE6 1QD 2 Tel: 020 8698 0181 Mob: 07748 336 902 tilley.neil@btinternet.com