Presented by Gary H. Fox PE. Senior Specification Engineer
Tuesday, September 22, 2009
The Transition From TVSS to SPD
Surge Device Standards &
UL 1449, 3rd Edition Changes
What is Transient Valtage ? External Sources = 20% of all transients
High level surges - Immediate Catastrophic Damage
Examples:
• lightning
• Utility lood switching
• Fault Clearing
• Crossed Power lines
• Damaged transformers
..,....':.';,,;:
Va/tape splkesare high energy short
duratIon transient voltoge events that
damage or destroy senSItive electronic
equipment
Allequipmentwith printed circuit
boards and microprocessors ore
susceptible to transient surge damage.
Equipment Affected
Definition
Effects of Transient Voltage (Surge) Lightning Flash Density
Permanent Damage to Sensitive Electronic Equipment
Erratic Control of Electronic Loads
Control Failure
System Down I Operation Interrupted
Cost of operation down time
Lost of productivity
..'IIh ............. '~11c:....oto>Iogr """'.... , ...h ~...
COoI>aI""~"""""OI~,"""'lm-F."....,.Wll""'.""t""_
<1'''''''''''''''.:1_WSA 010 ,4I(l'..J-OOj _ll!l (1......-2!l'aJ .""........
.--_._.
• imagination at work
1/
GE /
Internal Saurces = 80% of all transients
low level repeated surges - Damage Over Time
E)(omples:
• Compressors
• Inductive loads
-li.e) motors & pumps
• HVAC Units
• Elevators
• Drives - control elevators!
• Laser copiers •
• Cleaning equipment
-Vacuums, Floor polishers
Standards
NEMA LS-1- 1992
Low Voltage Surge Protective Devices
NEMA LS-l standard was established in 1991lo serve as 0 uniform spKifict:lt!on
gu(d~ine for low voltage surge protective devices.
NEHA 1S·1 providn minimum parameters and definitions thot make up the
content of 0 proper SPO (TVSSI specification formal
Int."t of NEMA L5-11s to be generol in naturllt and !'lOt to introduce standards,
derive lesting methodology or elrtenslVi! vocobulol)l.
Key palllmetfn addressed in the NEMA LS-1 Sf)« fannat llfe:
MCDV (MaKimum Continuous Dperatil'lg Voltagel
Protected Modes Definition (L-N, L-G, L-!.. N-Gl
Single Impulse Surge Rating
Clamping Voltages per C62.41
Sofety Ageney Approvols by NRTL lUI.., CSA etc..)
Natoli NEMA l5-1 parameters are rrquirftl forcompkte spKificotion ofollSPD
dlfVlcu.
IEEE Standards
IEEE C62.41.1- 2002 Guide on the Surge Environment in LowVoltage
AC Circuits
IEEE C62.4L2 - 2002 Recommended Practlc. on the Characterilatlon
of Surges in Low-Valtagf AC power Circuits
IEEE (62.45 - 2002 Recommended Plllctke on Surge Testing for
Equ!pment Connected to LV AC Power CirCl;U
IEEE C62.62-2000 Standard Test Specifications for Surge-
Protective Devices for Law-Voltag, AC Power
Circuits
IEEE C62.72 - 2007
IEEE1100-200S
Guide forth, Application of Surge Protective
Devices
Recommende-d Practice for Pow,ring and
Grounding Electromr'llc Equipment
(Emerald Book!
TVSS Overview
TVSS Standards
Standards? Recommended Practices? Guides?
What's the Difference?
IEEE Standards - Categorized
ANSI/IEEE
UL 1449
UL 1283
NEC
NEMA
C62.41, C62.45, C62.62,
C62.72,1100
TVSS Safety Standard
Noise Filtering
Article 280, 285
LS-11992
Standard:
Reed Practice:
Guide:
Mandatory requirements. Uses the
word -Sholl"
Procedures and positions preferred
by IEEE: -Should"
Alternative approaches listed. No
clear cut recommendation
• imagination at work
2/
GE /
IEEE C62.41.1 - 2002
Guide on the Surge Environment in Low Voltage AC Circuits
IEEE C62.41.1 provides information on surge voltages. currents and lOV
thot Off propagated In low-voltage oc power circuits and charocterizes
the surge environment
Provides pll;lcticol bosis for the selection of voltage and curnn! tests for
surgewithuond of elKtronic/eTectricol equipment
Key orlClS oddrused:
Provide bask information on surges
Origin of Surges
Propa~on, dispersion and mitigation of surges
Rate of Occurrence and Voltoge Lenis in UnprotKted Circuits
Octobase of observ~ sUfge behavior
Reference document for C62.41.2
IEEE C62.41.2 - 2002
Re<:ommended Proctice on the Characterization of Surges in low-Voltage
AC power Circuits
IHE C62.41.2 choroctrrins the su'gl environment at locations on ac
power circuits dncrilad In IEEE Sid C62.1I1.1-20C12 by means of
standardized waveforms ond other stren paramettfl.
HOT A PERFORMAHCE STANDARD
Key arlal addr'llId:
Waveshapes of Representati~tSurge Voltages, Entrgy and
SOutCt ImptdafICt
Location Categories relative to position ftom Service Entrance
Rtpreuntati~tSurgt Wavtforms for eoch cattgory
IEEE C62.41.2 - 2002
Recommended Practice on tne Ctloracterization of
Surges in Low-Voltoge AC power Circuits
Surge Exposure Locations
Cottgory C " Service EntraflCe
High - Medium Exposure lVSS
Cottgory 8 • Service/Distribution I
Short Run Branch Pontls
Medium - Low Exposure TVSS
Category A • Long 9ronch Ponelll
Point of Use Locotions more thonlUm
from CoL Bor 20m from Cot. C
Low Exposure TVSS
• imagination at work
IEEE C62.45 - 2002
Recommended Practice on Surge Testing for Equipment
Connected to LVAC Power Circuits
'EEE C62.4S provides 0 recommend proctiCt for tht ptnormance of surge
ttsling on tltctricol ond tll:cttonic system cormected to low voltogt oc powtr
circuiU.
Provides guidofICt for specifying and opplying sU'llt ttsting equ!pmtnt to
electrical devices subject to transitnt voltages.
KlY areas oddrlssed:
Provides general surge test plan recommendations
Test methods to aid in dtsign. quality control, acceptonce and
troubleshooting.
C62.4S Is II guid.lln. only. Sptclficatian or Ptrlonnonce tnU lor any
particular type of l:Quipment rtmains the prerogative of tltt
monufacturu, user, and standards group involvl:'<l.
IEEE C62.62 - 2000
Standard Test Specificotions far Surge Protective Devices
IEEE C62.621s a successor document to rEEE 62.41 standards.
thell provldts usus. indtptndtnt laboratoriu and manufactur.rs with test
sp.cificatlons and tuting mtthodologies for Surge PTotl:ctlvt Dtvicu.
KIY OriOI addrlllld:
Ottai!s testing sptclficatlons for
Moldmum Continuous Optratln.g Valtoge
Ma><imum Single Withstand Surge
Minimum Surgt Lile Withstand
Surge Ruponst Voltoge (clamping voltagtl
IEEE C62.72 - 2007
Guide for tlte Application of Surge Protective Devices
IEEE C62.72 providts speclfil:r$ and users of SPO's with on understonling of
numerous application considtfOtions to be eva!uatl:'<l befOfe SPD's ore installed
In low voltoge AC power circuiU.
Key arias oddrlssed:
Defines considerations fOf the SPD stlectlon procen
Dtscribes Surgt Origins, Eflecu, and Mognitudes
Location Categories and Power Distribution
SYlttmsandCanfigurot/ons
Grounding and Sonding
Protected Modes
SPD Sptcifications
SPD Failure Modes
{~ SPD Systtm Coordination and Methodolog;es
~"'''''''I'''~'''"'''·.'''
3/
GE /
UL 1449 2nd Edition
IEEE 1100 - 2005
Recommended Practice for Powering and Grounding Electronic
Equipment (Emerald Bookl
JEfE 1100 presents recommended design,lnstaliation and molntenance
proctlces for electrical power ond grounding and protection of electronil; foods
such 05 industrial controllen, computers, ond other ITE used In commen:iol and
induitriol applIcation$.
Key SPO r.lat.d Topics;
SPD purpose end method of operation.
SPDT~hnologje5
Selection and Installation Considerations
I
IEEE 1100 - 2005 (Emerald Book)
Powering cnd Grounding Electronic Equipment
Section 8.6.1:
'lorg' transienls on th.pow.r IYS/lm originolinlllNfSidr of/heusrr's
focility. OUr>cKlt~ with lighlnlng or mojor POIWf system IWlnls, 0,. best
~;~~;;>;g:':;;:::5f~~~~:~~:':J:~~c~o£:£~~7cjCaf:d~'6~nt~Fllrr7:t~~1
$ourc,o'I'" trclluirnrs or C/O$.IO th. fl/ec/ronic lood equipment if this is not
possible. 8est ,,5ults ortobtoined ifboth locotlons artproteeted."
S,ctlon 11.6.3:
"Focililits hOU5i~ el.ctronk load I'quipmenl ofony type should hOlle
~i~~~~~f:;c:,~~ t~8t:~5 spW:,/:fj':J';~I~n~~ttproteel/on in the form of
IEEE 1100 - 2005 (Emerald Book)
Powering end Grounding Electronic Equipment
S,ctlon 11.6.1:
'Pont/boords Ort cwoiloble thot contain inlef1rolly mounted SPOs that
~~~~:.~~;~~~~~h;;~r~oo~i~IIErh~~~~:":v1{e~~~~~~i~'f~~:r:~of
inside switchboords orpan.lboards. thffe is 0 conetm thot fai/urt ofth. SPO
~~~~~~;:i;i~~Ot~;~~~~/~t;g~ ;~5tt~t,:::·:~hsbuob~:r,~~~r~i~~dt:1?~~~1:~.~
From IEEE C62.72:
'h.MOV inilialfS 0 condllctiv. condition idenlified as th.rmol
runaway lhot inevitably rtsUlts In tIM dtstruction ofthe MOV. Th. r.sulti"f1
dtstruclion ofthe MOIlmight txpel hot metol ~ogm.ntst condlletive ioniztd
gas.s. and d.nu conductive smoke and sooL~ond the mtroduction ofsuch
mal.rials inlo the inlfriorof.ltetrical distribution I'qulpment con domog. or
compromiu on Insulotion syst.m and rtsult in 0 caseadinf1 efftet ond 5ffious
.qulpm.nt domaf1e.·
IEEE 1100 - 2005 (Emerald Book)
Powering ond Grounding Electranlc Equipment
IEEE C62.72 tontlnues by stating:
'Th.rmal runoway conditions a" fXIJ".m.1y d.struetivt ond SPO
:::~~~~~~~o~~~~~s ~~E~~':::;~~~I;g~~r;;%t1~7fh~~~~1ty of
runoway condillons 0":
l<ldot;u.-.DiSPO w/fAIn" w/t,,!HHtClolur.
Inctu"","'Dit"'HOII_w/fItltl_lIngcon>~Of"_.
Inf"9'"QIOf".itUfn<I/~fpr«_1on
"""9"'lfJ.nr!<lICUfDlf"-b.
Utnitlng_Di"""'-IW _ _
IEEEonly d.scrlb#s pot.ntlalfalfun conditions as a cautIonary
rtat.m.nt to th. sp«lfi.r or us.rs ofSPOs. Olff.r.nt SPO dfilgns will
folf In dfff.nnt mannlN'S.
UL 1449
Standard for Safety for Transient Voltage Surge Suppressors
First Introduced in 1985. Ul1449 continues (0 serve os the Industry
Approved Safety Stondord for Tronslent Voltoge Surge Suppressors
used on AC low Voltoge Systems.
listing requires product submittal to on OSHA occredited
Notlonolly Recognized Test loborotory. (NRTU
Any accredited NRTl can evoluote a TVSS for compliance to
Ull449. IUL ElL MET Labs. etc_I
Underwriters lobs is the Qt:l.LY. OSHA accredited lab that is not-for·
profi( ond the only lob thO! can gille Ull449 compliance
authorizotion to ploce the "Ul listed" sofety product mark.
(02107 Effective)
Standard For Sofety for Transient Voltoge Surge Suppressors
The most current revision of Ull449 is 2"" Edition, dated February 9. 2005.
Mandotory complionce to this revision become effective on Februory 9,
2007.
All TVSS devices ore currently reqUired to meet the provisions of the most
recent effective revision of Ul14491n order to continue to ploce the Ul
mark.
The most notable updates to the F,b, 2005 s(andotd were the Indusion of
odditionolsofety tests which farces a product to foil in a sofe ond non·
deslnJctive manner when subjected to abnormal elevated phose voltages
with intermediote fault current potentials of 10. 100. 500 ond 1000
omperes.
• imagination at work
."'''.0:.=:
4/
GE /
UL 1449 2nd
Edition '02107"''''''••'Standard For Safety for Transient Vohoge Surge Suppressors
Fun Phose Voltagl Short Orcult lut and limited Current Ovlrvoltogl
T,st Fallur. Unocceptable Results lOuring and Following Tlsts);
01 Emission oflome, molten metal. glowing or naming particles through
ony openings (preexisting or created as 0 result of the test) in the product.
bl Charring. glowing. or flaming of the supporting surface, tissue paper, Of
cheesecloth.
cllgnition of the enclosure.
dl Creation of any openings In the enclosure thot result in occessibility of
live potU. when f'Ioluote<l in accordonce with the occl!ssibiJity of live ports
tnt in S5A.2.
ellen ofstructural integrity to (I degree thot the equipment collapses or
eKPeriences such displacement of ports thot there is (I risk of short-
circuiting or grounding of current-carrying ports.
Terminology
Type 1 _ Permanently conneaed SPOS Intended for InstoUotion betwHn the
SKOndery of the service troMfOfTMf ond the line $Ide of the serviu equipment
OItfCWTent device. os -U lfli the load side, including wott-kour mtItf sodtet
enclosures and intended to be instolll'Cl without on Vdemol oYIrCWTem prctK1ive
diMe•.
T)'lMl Z_ PI!f1TlCfmt!yCOMKted SPOS intended for Installation on the load side of
the servic:. equipment overanltflt devic., inducing SPOt locoted at the tKondI
......
T)'lMl J _ Point-Qf·utililotion SPOt, instoUl'Clat 0 minimum cww:Iuetot length of JO ft
from the e1ectricol service ponti to the point of utililOtion. ~Il~ cord connKted. dirKt
plug.... rKeptode type ond SPOt iMUlDed at the U'tilil'O'tion equipment being
protected. The distanc. CO ftI is .xdusiw of condl.lClors provided with or used to
attochSPOS..
Type" - Component SPOs and componltflt ossemblies.
.._.-:.=:
Types of Metal Oxide Varistors (MOVs)
"'1'" linn mod.11 or••qlllpp.dWltll EnhGnctd
ThormGIIy PrGlnt.d M.IGI O-'Cid.IIGriIlGr
fTPHOV)TKhnCllogy
TPHOV Ftot""t1
• SGf.ty ftmOYts HOV "om circuit prior to ....ptuf. whtn
'!<9oud to Glmormol Of su,t<lin.d pho.. owrvollog.
tv.nll
........... GE TVSS to pall 011 Ull'19foll!:CUfftnt TUII
'ndU<lmg feb. z007 rtvlsionll....tIlout til. n.td fOf
oddltlonal up.trt<lm .......<u,..nl Pl'llltCtlotl
..,...-:.....::
UL 1449 3rd Edition: What is changing?
Nominal Discharge Current - In
- Value is selected by the manufacturer
Type 1 SPO con be either lOkA or ZOkA
• Type 2 SPD can be 3kA, 5kA, lOkA or 20kA
'- Nominal dischorge current level is morked on the label of 5PD
- Test subjects SPD to a total of 15 impulses
-In order to successfully pass test:
SPO connot create a shock or fire hazard during the lest
Nothing in the surge poth can open at any time during or after the lest
llncJudes olllnternoJ and lilt.mol d.vlces, such as fusn andlor circuit
breokersl
.._.-:..=
Measured Limiting Voltage Test
2nd Edition
L Tton1itnIVCIltog. Surge SllJIptt110t
"',,,,
t. Fordtvict1oncif<urts6DD/OtI.n
" su!V. Voltog. I(e*'9 !MtI
., CuI)I'C.,.:!.Tt1tIIIQ IiW/SOCI,t"
S. lnstolctlon ""Icod tid. onIr
3fd Edition
L Sllt9.Prolt<_OtvI<.ISPOI
-olIO includ.IIKondOf)' SUfg. onulOts
l. Fotcltvict1 on w<..u 1.OOOYorl.1t
J. 110li<l;. P'OIt<!ion I(Cli~IIIPIt.I
'" Nomilal D1Kharg. CWTtrrt Iiwn A ll.
S. Type 1 c1_t1 cen btlfl1toltdon ... 1>cI.
otlooclsicl.
6, Typell,l,_dtvict1
7, ._011 NotlOMI Slondo,c1lANSlI
• Results in Voltage Protection Rating (VPR)
• Uses a 6kV/3 kA combination wove surge
{current is 6X greater than SVR test using
6kv/SOO A combinotian wove!
• Higher current levels will produce higher VPR
ratings, when compared to 2" edition SVR
ratings for an identical device
UL Sfandord is now more similar to the lEe Standard
_. And complies with changes in Z008 edition ofNEe
f»!'~'""-'
• imagination at work
5/
GE I
Lightning Protection Systems
• UL96A - Installation Requirements for
Lightning Protection Systems
• Requires a Type 1 or Type 2 SPD rated 20kA
nominal discharge current 11,1
• NFPA 780-2008 is in line with UL96A
requirements
• Nate: all GE SPD devices will be certified for
UL96A usage
SPD Component Technologies
• Metal Oxide Varistors (MOVs)
• Selenium
• Gas Tubes
• Hybrid
••••
.._.-:..=:
Frequently Asked Questions: Types of Metal Oxide Varistors (MOVs)
Q.
~
Q.
~
Q.
Q.
~
When don thl UL 1/149, 3"' edition go Into .".ell
September 29, ZOO9 INo,lnlt/olly the date lhot the 3'" edition wcs to toke effect,
but UL stm hos (I lorg. backlog. Mlgrs con b. gronted a limited Intoslon.
Whet Is th,lmpo(t on my u:lsting TVSS Installations?
Nothing. Th. chong" In th. stondord onll offm produtU mOllllfocfuffdon or
ofttr th. 'fftctivi dati. Any ......sting inlto lotions witlstill be In UL compliance.
What Impact don thIs hall' on my existing stocklln~ntory?
Nothing. The chong•• In thl standard only affect product that II monufocluffd
on or oft,r Septtmb,r 29. 2009. Any .lei,tlng stack monufoctur.d Mfore this
datI will still be in ULcomplloncl.
Don this rnt(Inthctpf'OdlKt$ c:ertifi"ll to UL 11149. 2"" edition or. nolOI me or
Itffectlwl
Som, monufoctur«l may be maki~ change. to their products In Mdel'" to
com~ with 3"' editlon. GE'llinlt of curnnt TVSS productl olr~ colTllllv with
3..ltdltion ItOndarcli. Thltfltfore. _ orlt ~t chonglng OUf dnlgnIn ortJ~ to
obtoln 3" edition Cltrt/fk;atlon.
II GE dlo"llin9 ~r SPD productl1 Will thittlt bit nM ccrtolog nurnbitn1
GE II nllt ~ng thItIr pl"oductl in order to compfy with 3" edition. Onelt Wit
obtoin~ Itdition cltftiflCatlon _ ....ilI ~n IobItling all product 01 3'" ItditiOtl
compllonL
.,.._.~
High En"gy Metal Oxide
Varistor Components
Many ManufactureNi U..
Small", Electronic Grode
MOV Arrays
.,.._.-=:
General SPD Information
• imagination at work
SPD Terms
Modes of Protection
L-N L-G
A
B
C
N
G
..,....~
6/
GE /
SPDTerms
"Mode" vs "Phose" Rating
L-N L-G
SPD Maximum Surge Current Rating
Surge Severity Ratings Per Made
25 - 50kA
65 -100kA
100-300kAHigh Exposure
Low Exposure
Medium ExposureN-G
L-L
A
B
C
N
G
@ + @ 1=2001
~ __•__. Mode x 2 = Phase Rating
SPD Application
Cascading System Wide Protection
ANSI/IEEE 1100 Emerald Book Guide to SPD APPcUcotlon
Outlinu coscading SPD approach for all calflgorics and flxposurll/'HI,
HIgh tivil voltage spikes con get post leIVlce entronCII
Vollog. spikes from high kA trolls/,nls con stilldomal1l1 downJfrrom IIqu,pmllnl SPD Installation
Internally glneratld transients - 80% of all transients
ServiclI IIntrance SPDconnOI provide prolfction from In!troo! ,urges
Un'Kplcted IIlt.rnol transllnts In distribution - 1.11. Rooftop AC
lightning strikes On building or nrorby bring highkA tronsiems Inro diSlribulion
Redundant layered prot,ctlon at multiple levels
Addiliono/'aym protllct sensitive e!t<:lronln Ifupstrtom devicn fail
SPD Application
Integral Switchboard" Panelboord
New construction
New panels or §witchboords on eKistlng facility
80M Extenllon
Add to eldsting facility elKuicol distribution
When bronch ponel disconnect is required
Wall Mounted
l7''''1i"'i1 New Construction
U I~ Add 10 eldsllng focility eleet:ricol distribtltion
n IImuJ When branch ponel disconneet: Is required
SPD - Installation Options
Paint af U..
Category'"
ANSI/IEEE C62.41
"Cascading Approach"
Dlrtrlbutlon
""""" B
Holn
service Entra~
CategoryC
• imagination at work
7/
GE /
Integral Advantages -
Better p.rforma~owr Wall Hountitd units
~=-~...c~
......""'""-
Shorter ~PO leads .. Britt( surgor rtduetion
IWall SPOt;e SavIng.
ltoves mort spoce for odditlonolpon,l, and gear
plOCfmrnt in tight "'elricol rooms
Factory Installed and Warranted
Avoid Instollotlon errors, splicing or locollon probillms III
labor_lngs
1.5 hours on overog' conlroclor lobor savings per SPD instolled
flush mounting behind panel door
Mounts bl/hind door in bronch ponl/ls and flush wilh switchboards and
powerpone/s
UL 61,891 Llsted
Enf;TII Ponti &Swifchboard ourmbli.s wilh SPD hovlI bun UL lrstrei
t1t~_.
"'''w-:.;;;,;;:.:
SPD Installation
SPD Connection - Wire Length Effects Study
In ZOO4, GE controet.,j A&' Laboretori'lln Conlhallock.n p~ to p.rlorm .urge
luting on a .Imulotld .Iectrical dl.tribution ,v"l.m with SPo Inilolilld.
Th' purp01f oflh tell WO, to d.t.rmln. th• • ",~t, of(obl.l.ngth on SPO
p,rformonct.
Both inttgroUy mounttd ond woll mounted SPO dnign, w.I.lndud.d In th. tnt
Woll Mount SPO. w.r. fYoluottd wh.n (onnect.d ot I,ngth, 01 J' ond 10'.
Integrol SPO, w.r, (onnect,d to th. dl'trlbution ,q"pm,nt bUI.
IEEE recommend.d ,urg. wawform' w'r. InJect.d ot th. moln lug, of th.
,1,ctricolpon,l.
L.t thru voItognw.r, coptured and r.cord.d down.tnomfrom the SPD ponol on
both til, primory ond ,"candory lido 010 ,tIp-down uonllormtr.
"Codl J-IndllMgrh o(SPD tHmllN1tlon ""'f. ""'" O«Ot1nl fof IncfftJlttJIUrg. volt.
Itt Ihru fIvth. ,.". dfCfftJlf In domplng performona will ""I)' from 01 Ifttl. 01 11
voItl, or01 much 01 ZS IIOhs perIndl-
imagination at work
"'''.~,';l
SPD Application
Installatian
1. Minimize lead lengths
2. Twist wires to reduce impedance
3. Use fully rated surge class disconnect
devices at service entrance.
4. Some models may require the use of a
breaker. Refer to manufacturer
..".•-:.=
• imagination at work
8/
GE /
CATASTROPHIC PROTECTION SYSTEM
IT'S ABOUT TIME!
Damaging voltage surges and noise have become an all too common occurrence, including events like power swells
(measured in seconds!. TOV Itemporary over voltages measured in milliseconds) and transient surges (measured in micro
and nanosecondsl. Power quality experts'" indicate that these power quality events will continue to get worse as the loading
on the North America power grid continues to grow, pushing the limits of the already dated and strained national power grid.
POWER QUALITY DISTURBANCES
While power quality disturbances come from many sources, their destructive ability is generally measured in power
which has a function of time. A power quality disturbance from avery small over voltage event can be considerably more
destructive than even a local lightning strike - given its application to the unprotected load for thousands of times longer
li.e. milliseconds verses microsecondsI. While lightning will always be the most obvious source of failed equipment because
of its effects on our environment, temporary over voltages and swells will be the most destructive power quality events seen
over the next ten years'"
The IEEE std 1100-20051Emerald Bookl indicates when singular or "burst" surges exceed the nominal peak line voltage,
they will damage many types of electronic/electrical equipment. Even very small voltage surges applied at sensitive frequen-
cies have been documented to cause damage and, at the very least, disrupt the data and its integrity"·I0"""'" Demonstrated
through many industry tests, electronic and electrical components have been destroyed when exposed to higher voltage and
energy events over normal line voltage.13 Gan",eal';;l Puto/l.4,Va1 Keurenl
The industry typically identifies the following power quality events as:
Over Voltage
Swell
,, ; I '
> 1min
8 ms -1 min
I • I '
1.1-1.2
1.1 - 18
Temporary Over Voltage (lOV)
Transient Surge
100 ~sec - 8 ms
1~sec - 100 ~sec
Table 1
1.8 - 2.0
>1.2
While there are infinite numbers of sources that contribute to damaging voltage and energy surges, the majority can be
broken into two major categories - environmental power quality disturbances and electrical switching surges.
WWW.CUFlFlENTTECHNOLOGY.COM
(CUnentThchnoJogy.
ENVIRONMENTAL POWER QUAlITY DISTURBANCES
Lightning proves to be the most destructive environmental generator of power quality disturbances. Other environmental
induced surges include non-arcing electrostatic discharges IESOI with varying charge build up between cloud and earth.
While the wives' tale states, "Lightning doesn't strike twice", in reality as many as 40 return strikes have been
recorded"'''''''' with current surges of more than 500kA being seen, but typical surges reaching 20 kA to 40 kA. A typical
lightning strike can last between 50~s to 100 ~s with most of the damaging energy below 1MHz 1<1.0 ~s rise times).
When developing astrategy for power quality protection, it is critical to remember the high-frequency current element of
a lightning surge, and that ESO protection requires special wiring and grounding techniques. Wiring and grounding practices
for normal construction only consider the electrical safety element followed by NFPA 70 National Safety Code, leaving a
building and all contents at serious risk to damage. A power quality strategy includes low-impedance wiring and grounding
with the inclusion of a Catastrophic Protection System (CaPSI.
Significant levels of current can be found in the area of the grounding electrode during a lightning surge event.
The lightning discharge in the earth can actually become ionized by an event, becoming aground potential rise source IGPR)
for damaging surge into a facility through the grounding system.
Power quality events caused by coupling to conductive objects Imetal) is also very common Through inductive, capacitive
and magnetic coupling, transients and noise are fixed onto objects. These transients are typically caused by cloud to cloud
discharges"'-' coupled onto both buried and overhead conductors. For every charged cloud there is a reflective opposite
charge seen by the earth, called acharge center. When there is cloud to cloud discharge, asimilar reflective event on earth
follows the cloud activity. This rapid change in charges from the charge centers cause voltage and current surges in overhead
and buried conductors."""'''' This rush for equilibrium in electrical charges can cause arcing and flashes inside a building as
different paths and potentials are sought by the charged particles. Based on abuilding's internal system impedance and
protection system installed, this type of power quality event results in simultaneous affects involving power, signal, communi-
cations, data, and grounding at varying power levels. Even if lightning is discharged miles away and not seen or heard, often
times, this coupling event damages equipment.
ElECTRICAL SWITCHING SURGES
Another example of a source of destructive power quality events come from rapid changes in current flow rates in an
electrical system. These surges are typically oscillatory, meaning the ability to couple onto other conductive equipment in the
area. A switching surge will also have multiple elements of both high and low frequency, with the highest frequency element
found near the source and quickly losing energy as it travels further away from the source, and a low frequency element with
aslower rise and fall time allowing propagation throughout a building.
Typical causes of switching surges include:
a) Energizing or de-energizing the reactive element ofapower source wiring system
b) Arcing associated with contactors, relays or even loose connections and ground faults
c) Unsynchronized power factor capacitor switching
The dampening effect of the building impedance directly relates to the first-transition time of the surge. While transient
surges (typically found in the microsecond to nanosecond range) can be quickly reduced by a factor of two, very little tran-
sient attenuation can be expected for longer first-transition timed surges."''''''''''' This longer transient wave will have the
appearance of a ring wave in the system and potentially is more damaging then asingle surge event. A building protection
system should have the ability to protect and survive both fast and more destructive slow power quality events.
WWW.CURRENTTECHNOLOGY.COM (¢anent 7tN:hnoJogy:
ICT Is/olivo!. J I'»u. 'lEI
WHAT IS A CATASTROPHIC PROTECTION SYSTEM (CaPS)?
Current Technology repeatedly demonstrates itself as a leader in protection performance in both the labs and with
its tens of thousands of protection systems installed in the field. From this wealth of information, Current Technology has
developed a Catastrophic Protection System, or CaPS, using selenium hybrid protection as an effective strategy against
power quality events caused by transient surges, temporary over voltage, power swells and noise entering into a building
through its service entrance.
While other Metal Oxide Varistor (MOV) based protection manufacturers claim to protect against power quality surge
events for durations into the microseconds, only Current Technology's CaPS strategy allows protection from power quality
events lasting up to the seconds (millions of times longer then any MOV based protectors). This difference in time will feel
like an eternity to equipment loads being stressed by poor quality power. Therefore, while other manufacturer's protection
elements are forced into failure or have yet to be turned on because of their design, Current Technology's CaPS strategy
will continue to protect against surges throughout the transient surge, TOVor power swell event."·''''"'''''''''_'SdU''''
The following chart (Figure 11 demonstrates both the industry equipment ITI CEBEMA curve (20001 with the protection
levels from MOV only verses selenium hybrid technology.
Over Voltage (Vrms)
700
600
500
400
300
200
100
o
MOV destroyed- no protection
 fRISK Area
 f -- Equipment
 f CaPS continues to protect -MOV
 f Selenium
~
Limited Risk
160115 1ms 3ms 20ms 100ms 500ms 15 105
Duration
Figure I
As Figure 1demonstrates, any voltage / time event that exceeds the equipment manufacturer specification is seen as
an equipment risk area. While the CEBEMA curve provides equipment manufacturers a guideline for robustness required
by electronic equipment, it is only providing aminimum design requirement. Not only are power quality events on the rise,
but equipment failures are steadily increasing, as well. While MOV only technology provides adequate protection against
transient surge events that happen in the nano and microseconds, the MOV's will literally destroy themselves when power
quality over voltage events last into the milliseconds.
Using a selenium hybrid based protection solution protects against transient surges, and is also actively diverting
dangerous currents to ground caused by both TOV and voltage swell events.
WWW.CURRENTTECHNOLOGY.COM
Icr ls/o7lvol. 'I',,"' '19
HOW SHOULD CURRENT TECHNOlOGY CaPS BE USED?
CaPS is all about better power quality protection for your sensitive equipment. IEEE C62.41 states that the best approach
for total protection is using acascaded approach with the installation at multiple locations of the electrical system of the
facility. By using Current Technology's CaPS strategy, surge protection starts BEFORE the surge actually enters the building.
The Select 2 CaPS Protector is the only protector in the industry rated as both aSurge Arrestor and Surge Protection Device.
When multiple protector units are deployed with SLc at the main and SLc secondary panels in acascaded strategy, a facility
has the most versatile power quality protection system against transient surges and noises, and also has the ability to protect
and survive against TOV and power swell events caused by abnormal voltages."O-U'","'''''
As Figure 2demonstrates, acascaded concept can also include protection down stream in your building power distribu-
tion system. This means that your load risk building evaluation should include power quality protection inside and outside
of your building.
Areas of concern should always include any power and telephone/data access points corning into a building structure.
Figure 2
REFERENCES
IEEE Std 1100-2005 was used as a core reference throughout whitepaper
1. Power Quality &Reliability Show - Panel Review Oct 2006
2. FIPS Pub 94-1983. Guideline on Electrical Power for AD? Installations
3. Gallace. Land Pujol. H., "The evaluation 01 CMOS Static-Charge Protection Networks and Failure Mechanisms Associated With Overstress Conditions as Related 10
Device Life.: Reliability Physics Symposium Proceedings, April/9ll
4. Van Keuren. E., "Effects of EM? Induced Transients on Integrated Circuits, .. IEEE Symposium on Electromagnetic Compatibility, pp. 1-5, 1975
5. McCann. G.D" "The Measurement of Lighting Currents in Direct Strokes." AlEE Transactions, vol 63.pp. 1157·64,1944
6. Boyce. C. F. Ch 25 "Protection of Telecommunications Systems" Vol 2, "lightning" in LightIJing Protection. R.H. Goldeledllondon: Academic Press, 1977
7. Sunde, E.D" Earth Conduction Effects on Transmission Systems. Van Nostrand Company, 1949 and Dover Publications 1968
8. Martzlofl. ED. and leedy, T.F., "Electrical Fast Transient Tests: Applications and limitations," IEEE Transaction on Industry Applications, vol fA-2B, no 1, pp 151-159,
Jan/Feb 1990
9. Thomas &Betts Power Solutions Engineering Paper EP082006- .. Protection Effects of Selenium with Abnormal Voltage Applied", Aug 2006
10. Ul1449 2Edition Ver2.5 Abnormal Voltage Test
WWW.CURRENTTECHNOLOGY.COM
~tTechnology.
Page I of2
PRIMEDIABusilless Magazines & Media
Selenium Suppressors Outperform MOV Cousins
By Rajendranath K. Maharaj, eKE, Lucernemines, Pa.
PCIM Power Electronic Systems, May 1, 2001
Used as a semiconductor in rectifiers and suppressors for many years, selenium occurs naturally on the
earth. Its popularity as a rectifier is fading in favor of its silicon equivalent. However, demand for
selenium suppressors continues.
Depositing the elements on a metal substrate's surface produces selenium cells. This provides the cells
with good thermal mass and energy dissipation as well as "self-healing" characteristics, allowing the
device to survive energy discharges in excess of the rated value. Selenium's crystalline structure gives it
the ability to continue functioning after a burst of energy in excess of its short pulse width rating. Its
suppressor operation is comparable to a pressure relief valve - when the pressure rises, the relief valve
opens, releases the pressure, and then resets itself.
Because of its unique properties, the selenium suppressor remains viable in many applications. Special
clamping capabilities enable the selenium suppressor to find its own niche as a transient voltage
suppressor. Because of its ability to continuously dissipate power and handle long surges, it's better
than MOVs or silicon suppressors for some applications.
The selenium suppressor can absorb energy levels in excess of its rated capability while maintaining its
clamping characteristics on the next cycle. The layering of the suppressor onto the aluminum plate
allows the suppressor's energy capabilities to follow that of a heat sink curve. This heat sinking
capability allows steady-state power dissipation up to 40 times that of an MOV. For a 130V suppressor,
the selenium product allows steady-state dissipation of2.5W to 80W, compared with an MOV that
allows only 0.1 W to 2.5W. Fig. I shows several selenium cells.
Manufacturers produce selenium suppressor cell plates in sizes varying from I in. x I in. to 12 in. x16 in.
that can function at a temperature ofO°C to 55°C ambient without any derating. The voltage ofa
selenium suppressor cell starts at 26Vnns or 22.5Vdc per cell plate. Users must keep the suppressor to a
75V maximum due to the dielectric ceiling of the cell. The capacitive nature of the plate allows
placement in series to attain higher voltage levels.
Other suppressors can handle high current, short pulse widths in the microsecond range, but the
selenium suppressor can handle millisecond pulse width currents, making it a more robust suppressor
than silicon devices. It has a typical response time of less than I ms and is capable of handling pulses
with long decay times as seen in large dc motors or any inductive loads with L/R ratios in the 100 ms
range.
Power conditioning systems, generators, and ac controllers are typical selenium suppressor
applications. Suppressor applications are specifically used on the dc side ofa rectified generator output,
across SCRs on large controllers, across dc motors, and on transformers for line-to-line transient
suppressIOn.
7/26/2001
Page 2 of2
Typical applications for selenium suppressors include:
" On the dc side of a rectified generator output.
.., Across the SCRs on large controllers.
" Across dc motors.
" On transformers (for line-to-line suppression).
.., Power conditioning (i.e. from power strips to service entrance).
For some devices, an MOV or a TVSS is better suited, and for others, a combination of suppressors is
best. However, to the surprise of many electrical engineers, the capabilities unique to the selenium
suppressor have enabled it to retain a firm place in today's market.
7/26/200 I
All Current Technology products are listed to the new requirements of UL
1449 2nd Edition 2005 Revision (effective 2/9/2007).
What is UL1449?
UL 1449 is a safety standard developed by UL and adopted by OSHA as the standard
for evaluating the safe operation of TVSS (transient voltage surge suppressors) or SPD
(Surge Protection Devices). Compliance to UL standards is required by the NEC (Nation-
al Electric Code) and must be certified by a NRTL (Nationally Recognized Test Lab).
What or Who is UL?
Underwriters Laboratories Inc. (UL) is an independent, not-for-profit product safety cer-
tification organization that has been writing Standards for Safety for over a century. Up
until recently, UL was the only NRTL that could test products and verify compliance to
the standards. This compliance has previously been referred to as having a product "UL
Listed".
UL is not a government agency, they are a private organization responsible for the gen-
eration and publication of safety standards. A separate division of UL is also an OSHA
approved NRTL (Nationally Recognized Test Lab), which means they are authorized by
OSHA to test, evaluate, and list products to safety standards.
What is an NRTL, and what is the significance of OSHA recognition?
The U.S. Department of Labor; Occupation Safety and Health Administration's (OSHA).
is the legal authority for evaluating and approving NRTLs (Nationally Recognized Test
Labs). The following definition of an NRTL can be found on OSHA's website. http://www.
osha.gov/dts/otpca/nrtljindex. html.
An NRTL is an organization that OSHA has "recognized" as meeting the legal require-
ments in 29 CFR 1910.7. In brief, these requirements are the capability, control pro-
grams, complete independence, and reporting and complaint handling procedures to test
and certify specific types of products for workplace safety. This means, in part, that an
organization must have the necessary capability both as a product safety testing labora-
tory and as a product certification body to receive OSHA recognition as an NRTL.
OSHA's recognition is not a government license or position, or a delegation or grant of
government authority. Instead, the recognition is an acknowledgment that an organiza-
tion has necessary qualifications to perform safety testing and certification of the specific
products covered within its scope of recognition. As a result, OSHA can accept products
"properly certified" by the NRTL. "Properly certified" generally means: 1) the product is
labeled or marked with the registered certification mark of the NRTL, 2) the NRTL is-
sues the certification for a product covered within the scope of a test standard for which
OSHA has recognized it, and 3) the NRTL issues the certification from one of its sites
(i.e., locations) that OSHA has recognized.
There are a total of 17 labs that OSHA recognizes as approved NRTLs. Links are pro-
vided to each NRTL from OSHA's website allowing you to view the list of standards, sites,
and programs that OSHA has recognized that NRTL to evaluate products too. The fol-
lowing 5 labs are qualified to test and list products to UL1449; CSA, ETL, MET, UL, and
Wyle Lab. TVSS products do not have to bear UL's mark for OSHA to deem them safe
for the workplace or for compliance with the NEe.
Current Technology products were tested and evaluated in our world class laboratory
that is certified by UL and ETL as part of their client data test programs. All Current
Technology products are listed by ETL to UL 1449 2nd Edition 2005 Revision (effective
2/9/2007). Since ETL was the NRTL selected, all Current Technology products bear the
ETL mark.
Bottom Line.
A product no longer has to be listed by UL, the NRTL, to be deemed safe for use in the
workplace, or to adhere to the NEC requirements. Attached you will find a document
from ETL that more clearly states their position as an OSHA approved NRTL.
Best Regards,
Chris Martin
TVSS Product Manager
CATASTROPHIC PROTECTION SYSTEM
IT'S ABOUT TIME!
•FACT: Lightning has proven to be the most destructive
•FACT: A usual lightning strike can last between
environmental generator of power quality disturbances. 50 ms to 100 ms with most of the damaging energy
•FACT: A switching surge has multiple elements of both
occurring below 1MHz (< 1.0 ms rise timesl.
high and low frequency. The highest frequency element
•FACT: Manufacturers of metal oxide varistor IMOV) only
is found near the source and quickly loses energy as it based surge protection devices claim to protect against
moves farther away. surge events found in the micro and nano seconds;
•FACT: According to power quality experts, while lightning
however, their products are at risk during common
is the most obvious source of failed equipment, temoorary power quality events like temporary over voltages and
over voltages and swells will be the most destructive voltage swells that range up to the seconds.
power Quality events seen within the next 10 years.
•FACT: Unlike MOV only based technology with its
•FACT: Although the old wives' tale states, sensitivity to longer over voltage events, selenium hybrid
"Lightning doesn't strike twice," in reality, as many as
technology is proven to ride-through voltage swells
40 return strikes have been recorded (McCann) with
unharmed, continuously protecting critical loads.
visible current surges of more than 500kA, but typical
•FACT: Only Current Technology offers a selenium
surges reaching 20-40kA. enhanced Catastrophic Protection System {CaPSI solution.
To Learn More About CaPS, Visit www.CurrentTechnology.com
WWW.CURRENTTECHNOLOGY.CQM
Selenium Test
The next test keeps the voltage at
250V but brings a Selenium cell in
parallel with the MDV. The typical
response is that the MOV conducts
0.5 amps while the Selenium cell is
now providing the majority of the
protection, clamping current from
17-25 amps. The voltage is then
raised to 275V with similar results.
The MDV is still functional having
only conducted 1-3 amps while the
Selenium cell conducted 18-30 amps.
With the flip of a switch the Selenium
cell is removed from the circuit and
the unprotected MOV fails instantly
when 275V is applied to it.
THE TEST
PROCEDURE
Standard Test
During the standard
test (2) 20mm MOVs
are randomly selected
from abox of MOVs.
Each MOVs clamping
voltages are meas-
ured by avoltage
breakdown tester.
The Variac on the demo unit is adjusted to
200V and the MOV is subjected to 30 cycles
at 200V. Typical responses range from
no response at all, because the MDV did
not conduct, to the MOV conducting up to
5amps of current. The Variac is then
adjusted to 225V RMS. The response to
this voltage could range from afailure of the
MDV to a clamping current up to 19 amps.
If the MOV sUlVived 225V the voltage is
then raised to 250V At 250V the MOV will
catastrophically fail and potentially trip the
breaker to the outlet connected to the CaPS
demo unit. This is asimulated test environ-
ment limited by the available fault current
of the local breaker connected to the
CaPS tester. With unlimited fault current
available, MOV only technology will fail
quicker at lower voltages.
INTRODUCTION
The CaPS portable test platform
demonstrates and validates the
Current Technology advantage!
The test performed wiII prove how
Selenium/MOV hybrid technology
provides better-quality protection
against transients, TOV and swell
conditions - far superior to MOV only
based technology.
DEMONSTRATION
COMPONENTS
The portable test unit is capable of
providing a 30 cycle voltage swell
ranging from 0-300V RMS. With the
flip of a switch, the test platform can
supply this voltage to an MOV or an
MOV in parallel with a Selenium cell.
An oscilloscope displays the conducted
current of each device during the test.
A monitor is attached to the output of
the oscilloscope for ease of viewing.
Current transformers are connected to
the output of both the MDV and Selenium
cell so that conducted current readings
can be displayed on the monitor.
THE CURRENT TECHNOLOGY
ADVANTAGEI
CAPS - CATASTROPHIC
PROTECTION SYSTEM
DEMONSTRATION
KEY TAKE AWAY
V" A Catastrophic Protection System must protect against transients, TOVs and swells.
V" The CaPS demonstration shows key protection value of Selenium hybrid technology.
V" MDV only based technology is at risk to common power quality events.
V" Current Technology Select2~ meets CaPS requirements.
Come tour Current Technology's surge laboratory in Richmond, Virginia - the largest in the United States.
For more information, visit our web site at wwwcurrenttechnology.com or call us at 1-800-238-5000.
WWW.CURRENTTECHNOLOGY.COM
(CuntmtTec/moJogy.
FACILITY WIDE CATASTROPHIC PROTECTION SYSTEM
Part 1-General
1.1 Description/Scope
A. The Catastrophic Protection System covered under this section includes all surge protection installed at the
service entrance and all distribution panels electrically downstream from the same service entrance.
B. A Catastrophic Protection System is a broad power quality protector capable of protecting against both
transient surges under 100~Sec and temporary over voltages (TOV) and swells from 1OO~Sec to 2
minutes.
C. Contractor shall provide all labor, materials, equipment and incidentals as shown, specified and required to
finish and install surge protection devises.
1.2 Quality Assurance
A. Reference Standard: Comply with the latest edition of the applicable provisions and recommendations of
the following, except as otherwise stated in this document:
1. UL 1449 Second Edition 2005 Revision (effective 2/9/2007).
2. UL 1283.
3. ANSI/IEEE C62.41, Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits.
4. ANSIIIEEE C62A5, Guide for Surge Testing for equipment connected to Low-Voltage AC Power
Circuits.
5. ANSI/IEEE C62.34, Secondary Surge Arrestor.
6. IEEE 1100 Emerald Book.
7. NEMA LS-1, 1992-(R2000) Low Voltage Surge Protection Devises.
8. National Fire Protection Association (NFPA 70: National Electrical Code).
1.3 Submittals/Quality Assurance - Submit the following:
A. The Catastrophic Protection System must include shop drawings complete with all technical information,
unit dimensions, detailed installation instructions, maintenance manual, recommended replacement parts
list and wiring configuration.
B. Copies of Manufacturer's catalog data, technical information and specifications on equipment proposed for
use.
C. Copies of documentation stating that the Surge Protection Device is listed from a Nationally Recognized
Testing Laboratory (NRTL) (UL, ETL, etc) and are tested and multi-listed to UL 1449 and UL 1283.
D. Copies of actual let through voltage data in the form of oscillograph results for both ANSIIIEEE C62A1
Category C3 (combination wave) and B3 (Ring wave) tested in accordance with ANSI/IEEE C6245.
E. Copies of Noise Rejection testing as outlined in NEMA LS1-1992 (R2000) Section 3.11. Noise rejection is
to be measured between 50kHZ and 100MHz verifying the devices noise attenuation. Must show multiple
attenuation levels over a range of frequencies.
F. Copies of Surge Fuse Testing. Each unit shall be surge tested with fusing in series to verify that a transient
of maximum surge current capacity/magnitude is fully suppressed without fuse failure, operation or
degradation per NEMA LS1-1992 (R2000) Section 3.9.
G. Copies of test reports from a recognized independent testing laboratory, capable of producing 200kA surge
current waveforms, verifying the suppressor components can survive published surge current rating on
both a per mode and per phase basis using the ANSI/IEEE C62A1 impulse waveform C3 (8 x 20
microsecond, 20kV/1 OkA). Test data on an individual module is not acceptable.
H. Copy of warranty statement clearly establishing the terms and conditions to the building/facility
owner/operator.
Part 2-Products
2.1 Approved Manufacturer: Service Entrance
A. Current Technology - Select2 or SL2 Series (voltage and surge current depending on specific application &
location).
B. Approved equivalent.
2.2 Approved Manufacturer: Branch Panels, Distribution Systems, or Point of Use downstream of main service
entrance.
A. Current Technology - Select2, SL2, Select Compact or SLc
B. Approved equivalent.
2.3 Manufactured Units/ Electrical Requirements
A. Refer to draWing for operating voltage, configuration and surge current capacity per mode for each location,
or you may list locations and information here.
Facility Wide Catastrophic Proteclion System -1- 9.20.07
B. Maximum Continuous Operating Voltage shall be greater than 115 percent of the nominal system operating
voltage and in compiiance with test and evaluation procedures outlined in NEMA LS-1-1992 (R2000)
paragraphs 2.2.6 and 3.6.
C. Unit shall have not more than 10% deterioration or degradation of the UL1449, Second Edition surge
suppression rating due to repeated surges. Unit shall have a monitoring option available to be able to test
and determine the percentage of protection available at all times.
D. Protection Modes and NEMA LS1 1992 (R2000)/UL1449 SVR for grounded WYE/delta and High Leg Delta
circuits with voltages of (480Y/277), (208Y/120), (600Y/347). 3-Phase, 4 wire circuits, (120/240) split
phase shall be as follows:
System Mode B3 Rmgwave B3/C1 Comb. C3 Comb. Wave UL 1449
Voltage Wave Second Edition
120/240 L-N 300/350 400/450 625/725 400/400
120/208 L-G 375/425 400/475 625/750 500/500
N-G 325/325 450/450 725/725 500/500
L-L 375/475 750/825 975/1225 700/700
277/480 L-N 525/575 850/900 1125/1200 9001900
L-G 8251850 850/875 1050/1200 1000/1000
N-G 6751700 900/900 1200/1200 9001900
L-L 6501725 1675/1700 1925/2175 150011500
E. Electrical Noise Filter- each unit shall include a high performance EMIIRFI noise rejection filter. Noise
attenuation for electric noise shall be as follows using the MIL-STD-220A insertion loss test method.
1. 100 kHz at 44 db.
2. All other frequencies should be 32 db or better.
F. The Catastrophic Protection System shall provide temporary over voltage and voltage swell protection to
the following:
1. TOV - should be capable of surviving and continue to protect critical loads against multiple TOV events
(described as 200% nominal voltage by 8 mS.
2. Swell- should be capable of protection against swells up to 180% nominal for 0.7 ohms load >18,000
events.
G. Each fuse shall be individually sealed in a manner that eliminates cross arcing.
H. Integral Disconnect Switch.
1. The device shall have an optional NEMA compliant safety interlocked integral disconnect switch with an
externally mounted metal manual operator.
2. The switch shall disconnect all ungrounded circuit conductors from the distribution system to enable
testing and maintenance without interruption to the facility's distribution system.
3. The switch shall be rated for 600Vac.
4. The SPD device shall be tested to UL1449 Second Edition listed with the integral disconnect switch
and the UL1449 Second Edition Suppression Voltage Ratings shall be provided.
5. The integral disconnect switch shall be capable of withstanding, without failure, the published maximum
surge current magnitude without failure or damage to the switch.
I. Each unit shall provide the following features:
1. Phase Indicator lights, Form C dry contacts, counter and audible alarm.
2. Field testable while installed.
3. Measuring capability to indicate the percent protection available in SPD.
Part 3-Executionllnstallation
3.1 Each unit shall be installed per Manufacturer's recommended installation and wiring practices, as show on the
drawing supplied.
3.2 The UL 1449 Suppression Voltage Rating (SVR) shall be permanently affixed to the SPD unit.
3.3 The SPD manufacturer's technician shall perform a system checkout and start-up in the field to assure proper
installation, operation and to initiate the warranty of the system. The technician will be required to do the
following:
A. Verify clamp levels.
B. Verify N-G connection.
C. Record information to product signature card for each product installed.
Part 4-Product Warranty
4.1 Warranty on defective material and workmanship shall be for 15 years.
4.2 Copy of Warranty to be sent with submittal.
Facility Wide Catastrophic Protection System -2- 9.20.07
GE Digital Energy
Power Quality
Integral SPD's:
ASafe Solution with
Better Performance
•
1 Introduction
The increasing number af cammercially available
Surge Pratective Devices ISPD's) has pravided electrical
system designers with a wide range af options to choose
fram. SPO's are currently defined by the 2008 National
Electrical Code as Type 1iSurge Arrester) or Type 2 (TVSS!.
For the purpose of this paper, we will focus on SPO types
commonly referred to as Transient Voltage Surge Sup-
pressors ITVSSI that are intended for use at locations
on the laad side of the primary overcurrent disconnect
or main breaker of the electrical distribution system.
Of the many model types, ratings and suppression
technologies available, there are essentially two
distinctive instollation methods that are frequently
specified for commercial and industrial opplications.
These are SPO's that are intended for either external
mounting or integral installation.
Externally mounted (also commonly referred to as
"Wall-Mount" SPO'sl are availoble fram almost all major
manufocturers of SPO's. These devices are typically
housed in a dedicated enclosure and are intended to be
connected to the power distribution system vio electrical
conductors. These SPO's are terminated at a dedicated
breaker, or in some instances directly to the phase
bus of the electrical panel. Externally mounted SPO's
ore designed to be installed by qualified electricol
contractors at the job site.
Integrally installed SPD's are offered by many electrical
distribution equipment manufacturers. Integral SPO's
are normolly mounted within the electrical gear and
shipped to the job site as a complete package. Integral
SPO's are factory installed and pre-wired to the electrical
panel bus, so in many cases there is no need for further
installatian.
In recent years, a number of marketing publications
have been released by monufacturers and proponents
of externally maunted SPO's about the potential hazards
associated with placing these devices inside af elec-
trical distribution equipment. The focus of these pub-
lications are to create concerns about the possibility
of ancillary equipment damage that might occur in
the event of SPO failure. lit should be noted that SPD
foilure is most often the result of praduct misapplication
or sustained abnarmal phase voltage potentials!. Many
of these papers attempt to discourage the use of integrally
installed SPO's while citing IEEE or other industry recognized
standards as the authoritative basis for their position.
These documents, are carefully conceived, but typicolly fall
well shart of legitimacy due to the omission or misin-
terpretation of key information from the referenced
2
standards. In many instances, the case against integral
SPO application is being made based on historical data
rather than taking into account the present status of
the industry and the regulations that are currently in
place to prevent the potentially destructive failure of
SPO's for all applications. The focus of this paper sholl
be to take a closer look at these standards, how they
relate to SPD's, and what has been done to remedy
the potentially damaging effects of a failing SPD.
Both externally mounted and integrally installed SPO's offer
a variety of options and features. There are advantages
and disadvantages for both design types. While exter-
nally mounted SPO's offer a good solution for users that
would like to add surge pratection to an existing elec-
trical system, their installatian and performance can
be affected dramatically by enviranmental variables
such as limited panel access, limited wall space, orthe
level of experience that an installer has with such devices.
A knowledge of the characteristics of high-frequency
transient currents and the wiring techniques that must
be used to successfully convey these currents is neces-
sary for the praper installation of any SPO. In contrast.
integral SPO's are not restricted by panel access or
variations in installation. Since the SPO can be installed
very close to the conductor being pratected in an integral
mounting arrangement, the connecting lead length is
often much shorter than when connecting an externally
mounted SPD to the same conductor. This reduction in
lead length contributes to impraved SPO voltage clamping
performance over that of the externally mounted instal-
lation and results in better surge protection (see "The
Influence of Cable Connections on TVSS Performance"
for more details)'- Equipment manufacturers who have
earned good reputations can usually be relied on to
employ persons who are trained and competent in the
praper wiring pracedures for installing SPOs within
their equipment. making the quality of the installation
less of a factor with integrally installed SPOs. Some integral
devices are offered without a dedicated disconnect
feature which would require the panel to be powered
down in the rare instance that the SPO needs to be
serviced or replaced. However, de-energizing the
equipment may be preferred, even with SPO's equipped
with disconnects, when the SPO assembly is located
adjacent to bare live parts.
2 Standards
IEEE 1100-2005 is an industry-recognized standard
that addresses recommended practices for the powering
and graunding of electronic equipment. While this
standard is nat exclusive to 5PD's, there are relevant
sections with considerations for the application of such
devices within the electrical distribution system. Section
8.4.2.5 states that SPD's "may be installed externally
or internally to the switchboard or panelboard." And that
"panelboards are available that contain integrally mounted
SPD's that minimize the length of the SPD conductors,
thus optimizing the effectiveness of the device."
Additionally, IEEE 1100-2005 also cites IEEE preliminary
draft standard PC62.72 by stating, "there is concern
that failure of the SPD can cause collateral damage to
the switchboard or panelboards." However, readers of
IEEE 1100 might nat be aware that this statement was
not a direct quotation fram PC62.72. Instead it was an
interpretive comment made on section 14.1 of PC62.72
that describes the failure mechanisms of Metal Oxide
Varistor (MOV) components that are commonly found
within most SPD assemblies.
PC62.72 has since been formally released as IEEE
C62.72-2007, and is the IEEE guide standard for the
application of Surge Pratective Devices. The approved
standard does nat, nor has ever contained any specific
language which would prohibit or warn against the
use of integral SPD assemblies.
Instead, IEEE C62.72-2007, Section 14.1 cautions that
MOV's might expel hot metal fragments, conductive
ionized gases, or canductive smoke/soot upon reaching
a destructive thermal runaway condition. Of greater
importance, C62.72 also advises that manufacturers will
anticipate possible MOV failure and lessen or eliminate
these potentially damaging effects using a variety of
methods. These methods can include, but are not limited
to, containment of the failing camponents by a fortified
encasement, the addition of current limiting fusing, em-
ploying thermal cutoffs, using non-flammable or flame
quenching material/media, or any cambination thereof.
3 MOV Design Considerations
Because of the many ways to prevent or contain the
potentially damaging effects of MOV's, it is unlikely that
any two SPD manufacturers will employ identical design
approaches. Thus, it is important to realize that the
severity of failure is dependant upon the SPD design and
destructive failure prevention techniques and not the
location of the SPD installation. An effectively designed
SPD should nat fail in a manner that compramises the
integrity of surraunding electrical equipment. regardless
of integral or external design types. All major manu-
facturers within the surge protection industry should be
aware of the potential for catastrophic failure of MOV's
and should design for each application accordingly.
MOV's will eventually reach an end-of-Iife condition
should the power system voltage elevate beyond the
Maximum Continuous Operating Voltage (MCOVI rating
of the SPD. MOV degradation can also lead to a permanent
failure condition by gradually reducing the voltage
clamping characteristic of the MOV until the clamping
level eventually coincides with the normal system voltage.
While degradation due to excessive surge energy remains
a possibility within lower surge energy rated designs,
it is nat considered a normal occurrence in the majority
of today's high-energy SPD praducts.
Regardless of the cause of MOV failure, the end result
will be the same. When an extended avervoltage is
present, or if the MOV degrades below the nominal
operating voltage of the electrical power system, the
MOV will attempt to "clamp" the system phase voltage.
The MOV begins to cycle with the power frequency,
initially "clipping" the voltage peaks of AC sinewave.
The MOV attempts to dissipate the residual current,
resulting in a rapid heating of the MOV body. This initial
cycling/clipping condition of an MOV, attempting to
absorb the overvoltage energy, begins the end-of-life
stage of the MOV. This pracess is known as "thermal
runaway". When the MOV can no longer dissipate this
energy, it will typically fail at a random location an the
MOV body. This location is sometimes referred to as
the "punch-thraugh" site where the low impedance
breakdown and subsequent shorting of the failing
MOV develops. Once the MOV reaches a law resistive
state, it can rapidly become a fragmentation and/or fire
hazard if not immediately removed fram the electrical
system fault current path. The level of available system
fault current will then drive the subsequent destructive
energy release fram the MOV.
As stated in IEEE C62.72, section 14.1, SPD manufacturers
employ various techniques in an attempt to limit the
damage caused by a failing MOV. For example, designs
that include a combination of current limiting fuses and
thermal cutoffs rely on the current limiting fuses to in-
terrupt high fault currents and the thermal cutoffs to
interrupt low fault currents by opening as a result of
radiant heat emitted fram the body of the failing MOV.
However, coordination of fault interruption at intermediate
fault current levels can present a significant problem
for SPD design engineers. Thermal cutoffs are only good
for limited levels of available current and can only react
if the MOV can radiate enough heat directly at the cutoff
during the thermal runaway cycle. The higher the
available fault current. the more rapidly the failing MOV
3
will be driven into a low resistive state. In most cases,
this happens much too fast for even the closest proximity
thermal cutoffs to react. And once the MOV has shorted,
the initial energy release from the MOV will be concentroted
at the location on the MOV surface where the short has
originated. After this sequence occurs, the thermal cut-
offs become ineffective. And if the fault current potential
is not significant enough to open the primary current
limiting fuse, the SPD could remain in a low resistive state
with on unstable MOV that continues to emit intense
energy in the form of fiome, molten material, smoke, etc.
If only limited or intermediate system fault conditions
are present, or if the SPD is not designed to effectively
deal with fault currents at less than the maximum short
circuit rating of the SPD, it is easy see how certain SPD
designs could couse damage to the surrounding electricol
equipment once the SPD housing has been breached
by a foiling MOV.
4 Safety Testing
UL1449 is the industry-recognized safety standard for
Surge Protective Devices. During reviews of the UL 1449
standard in 2005, the UL Standards Technical Panel
agreed that certain "blind spots" still existed within the
abnormal avervoltoge/foult current testing program
that is defined within the standard.
As a result, UL 1449 was revised to incorporote additional
requirements for abnormal overvoltoge testing to be
applied with available intermediate fault currents of
10, 100, sao and 1000 amperes. These new testing
levels were mode in addition to the maximum short
circuit current and limited current testing levels that
were introduced in the initial release of UL 1449 2'd
edition in 1996. The addition of these new testing levels
are intended to address conditions that SPD's are likely
to be exposed to under a more extensive ronge of fault
current potentials that exist within typical power systems.
Many times, SPD's are installed on secondary power
systems with power transformers or other power
generation sources that cannot produce the maximum
fault current potentials the SPD is rated for. As on example,
on SPD that has been rated for use on power systems
with a short circuit fault current potential of 200kA will
be connected to a power system that is only capable
of delivering a few thousand short circuit amperes.
Prior to the addition of the new testing requirements,
UL did not evaluate the SPD for safe current interruption
at these lower, fault potentials. The new intermediate
~W imagination at work
fault testing levels would reveal the vulnerability of many
SPD designs that did not have full current limiting coordi-
nation across ranges that are much lower than the
tested maximum short circuit interrupt levels.
During the UL test sequence for each specified fault
current, the SPD is purposely driven into a failure condition
by applying twice the nominal phose voltage that the
SPD is designed for. In order to obtain a passing grode,
the SPD cannot foil with any form of cotastrophic results
that would include emission of flame, molten metal,
glowing or flaming particles through any openings,
charring, glowing, or flaming of the supporting surface,
tissue paper, or cheesecloth, ignition of the enclosure,
creation of any openings in the enclosure that result
in accessibility of live parts or loss of structural integrity.
The mandatory dote for UL certification using the inter-
mediate level fault current testing revisions of UL 1449
was February 9, 2007. SPD's that are manufactured
after this dote will not have authorization to apply the
UL mark unless UL witness testing has been performed
on each of the manufacturer's representative SPD models
and voltage types and are found to be in compliance.
These recent and significant testing updates to the UL
1449 standard should help to assure those who specify
and purchase UL 1449 certified SPD's that the SPD's will
not become a fire or fragmentation hazard, nor couse
damage to surrounding gear, when the MOV's or other
suppression components foil.
5 Conclusion
Integral SPD's provide on excellent choice for new
construction applications by eliminating installation
variables, saving wall space and reducing the perform-
ance degroding effects of SPD connecting lead length.
Many proponents and manufactures of wall mount only
type SPD's will argue that integrally mounted designs
are unsafe, or will couse substantial collateral damage
upon foiling while often citing incomplete or misinter-
preted passages from various standards and historical
documents as the basis. However, due to very recent
changes in safety testing standards, SPD devices that
are certified by UL to the latest revisions of UL 1449
will provide a safe and reliable solution for applications
where the SPD is factory installed within electrical distri-
bution equipment.
1 The Innuence of Coble Connections on TVSS Performance Marshall, E.; Honder:
Valdes, M.; Britton, J.: Jones. 1: Whitehead. J.; Mcintyre, B. Industrial and Commercial
Power Systems Technical Conference. 200S IEEE Volume, Issue. 8-12 May 200S
Pagels): 212-217
GE Digital Energy - Power Quality
701 E22nd Street, lombord,lL 60148 USA
8006371738 www.gedigitolenergy.com/tvss
www.getvss.com
Information subject 10 change without notice. Please verify 011 details with GE.
OET-661 1121081 lO 2008 General Electric Company All Rights Reserved
'-

Weitere ähnliche Inhalte

Was ist angesagt?

ATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation ConsiderationsATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation Considerationsmichaeljmack
 
Lv genset protection
Lv genset protectionLv genset protection
Lv genset protectionrkdheepan
 
Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016
Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016
Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016Alan Courtay
 
Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settingsH. Kheir
 
Emergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching ControlEmergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching Controlmichaeljmack
 
Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysismichaeljmack
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsJames S Nasby
 
Fat procedure for lv switchboards
Fat procedure for lv switchboardsFat procedure for lv switchboards
Fat procedure for lv switchboardskhongai
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relaydavid roy
 
Selectivity and Coodination
Selectivity and CoodinationSelectivity and Coodination
Selectivity and Coodinationmichaeljmack
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)Gensol Engineering Limited
 
Serial 3 Channel AC 230V SSR and Dimmer
Serial 3 Channel AC 230V SSR and DimmerSerial 3 Channel AC 230V SSR and Dimmer
Serial 3 Channel AC 230V SSR and DimmerRaghav Shetty
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 

Was ist angesagt? (20)

ATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation ConsiderationsATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation Considerations
 
Lv genset protection
Lv genset protectionLv genset protection
Lv genset protection
 
Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016
Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016
Quasi-resonant Flyback Converter Simulations with Saber - APEC 2016
 
Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settings
 
Emergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching ControlEmergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching Control
 
Emii
EmiiEmii
Emii
 
Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysis
 
Smh presentación jmsc depc
Smh presentación  jmsc depcSmh presentación  jmsc depc
Smh presentación jmsc depc
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC Considerations
 
Fat procedure for lv switchboards
Fat procedure for lv switchboardsFat procedure for lv switchboards
Fat procedure for lv switchboards
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
 
Aspix validation
Aspix validationAspix validation
Aspix validation
 
Out of step
Out of stepOut of step
Out of step
 
Selectivity and Coodination
Selectivity and CoodinationSelectivity and Coodination
Selectivity and Coodination
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
 
Serial 3 Channel AC 230V SSR and Dimmer
Serial 3 Channel AC 230V SSR and DimmerSerial 3 Channel AC 230V SSR and Dimmer
Serial 3 Channel AC 230V SSR and Dimmer
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 

Andere mochten auch

Etc pictorial surface standards 1
Etc pictorial surface standards  1Etc pictorial surface standards  1
Etc pictorial surface standards 1Fakhruddin Gandhi
 
Matching Customer's expectations for Innovative Future
Matching Customer's expectations for Innovative FutureMatching Customer's expectations for Innovative Future
Matching Customer's expectations for Innovative FutureRuby Med Plus
 
الخصائص المجالية للحي وتاثيرها على العنف لدى الشباب
الخصائص المجالية للحي وتاثيرها على العنف لدى الشبابالخصائص المجالية للحي وتاثيرها على العنف لدى الشباب
الخصائص المجالية للحي وتاثيرها على العنف لدى الشبابTizi Zakaria
 
Conflict notes for nb pg 19 pwr pt 2016
Conflict notes for nb pg  19 pwr  pt 2016Conflict notes for nb pg  19 pwr  pt 2016
Conflict notes for nb pg 19 pwr pt 2016Missy Colhour
 
37 турнир имени ломоносова
37 турнир имени ломоносова37 турнир имени ломоносова
37 турнир имени ломоносоваMasha Bo
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
Vedi tour group. Черепанова О.
Vedi tour group. Черепанова О.Vedi tour group. Черепанова О.
Vedi tour group. Черепанова О.URFU
 
Plan wallon des déchets
Plan wallon des déchetsPlan wallon des déchets
Plan wallon des déchetsEcoloMons
 
VirtuOz - Chatbots - 2007
VirtuOz - Chatbots - 2007VirtuOz - Chatbots - 2007
VirtuOz - Chatbots - 20072pasc
 
2.2
2.22.2
2.2URFU
 
Return on Training Investment.
Return on Training Investment.Return on Training Investment.
Return on Training Investment.Sufi Nouman Riaz
 
Return on Investment for Training and Development
Return on Investment for Training and DevelopmentReturn on Investment for Training and Development
Return on Investment for Training and DevelopmentGloria Bentley
 

Andere mochten auch (17)

Etc pictorial surface standards 1
Etc pictorial surface standards  1Etc pictorial surface standards  1
Etc pictorial surface standards 1
 
Jadecliff Ltd
Jadecliff LtdJadecliff Ltd
Jadecliff Ltd
 
Matching Customer's expectations for Innovative Future
Matching Customer's expectations for Innovative FutureMatching Customer's expectations for Innovative Future
Matching Customer's expectations for Innovative Future
 
الخصائص المجالية للحي وتاثيرها على العنف لدى الشباب
الخصائص المجالية للحي وتاثيرها على العنف لدى الشبابالخصائص المجالية للحي وتاثيرها على العنف لدى الشباب
الخصائص المجالية للحي وتاثيرها على العنف لدى الشباب
 
Conflict notes for nb pg 19 pwr pt 2016
Conflict notes for nb pg  19 pwr  pt 2016Conflict notes for nb pg  19 pwr  pt 2016
Conflict notes for nb pg 19 pwr pt 2016
 
37 турнир имени ломоносова
37 турнир имени ломоносова37 турнир имени ломоносова
37 турнир имени ломоносова
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
Trabajo 1
Trabajo 1Trabajo 1
Trabajo 1
 
Vedi tour group. Черепанова О.
Vedi tour group. Черепанова О.Vedi tour group. Черепанова О.
Vedi tour group. Черепанова О.
 
Plan wallon des déchets
Plan wallon des déchetsPlan wallon des déchets
Plan wallon des déchets
 
Mangas e animês
Mangas e animêsMangas e animês
Mangas e animês
 
VirtuOz - Chatbots - 2007
VirtuOz - Chatbots - 2007VirtuOz - Chatbots - 2007
VirtuOz - Chatbots - 2007
 
2.2
2.22.2
2.2
 
MBA Digital Marketing & E-Commerce
MBA Digital Marketing & E-CommerceMBA Digital Marketing & E-Commerce
MBA Digital Marketing & E-Commerce
 
Qawaid Fiqhiyyah
Qawaid FiqhiyyahQawaid Fiqhiyyah
Qawaid Fiqhiyyah
 
Return on Training Investment.
Return on Training Investment.Return on Training Investment.
Return on Training Investment.
 
Return on Investment for Training and Development
Return on Investment for Training and DevelopmentReturn on Investment for Training and Development
Return on Investment for Training and Development
 

Ähnlich wie Transistion from TVSS to SPD

Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueThorne & Derrick International
 
244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdfBarlomax
 
IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...
IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...
IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...IRJET Journal
 
Dc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsDc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsLangir Electric
 
2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)Sofics
 
H2PToday1201_design_IR
H2PToday1201_design_IRH2PToday1201_design_IR
H2PToday1201_design_IRParviz Parto
 
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vnLs catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vnDien Ha The
 
On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...
On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...
On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...Sofics
 
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-CouplingGate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-CouplingNusrat Mary
 
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorIRJET Journal
 
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATORUNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATORijiert bestjournal
 
Calculation of short_circuit_currents
Calculation of short_circuit_currentsCalculation of short_circuit_currents
Calculation of short_circuit_currentsRaymund Cortez
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoIRJET Journal
 
Industrial electronics 1 marks- polytechnic
Industrial electronics  1 marks- polytechnicIndustrial electronics  1 marks- polytechnic
Industrial electronics 1 marks- polytechnicSukesh R
 

Ähnlich wie Transistion from TVSS to SPD (20)

Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
 
244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...
IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...
IRJET- Design of Single Phase High Frequency Inverter for Wireless Charging A...
 
L.v tech presentation 2
L.v tech presentation 2L.v tech presentation 2
L.v tech presentation 2
 
HVM NFPA 70E White Paper
HVM NFPA 70E White PaperHVM NFPA 70E White Paper
HVM NFPA 70E White Paper
 
Dc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsDc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installations
 
2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)
 
H2PToday1201_design_IR
H2PToday1201_design_IRH2PToday1201_design_IR
H2PToday1201_design_IR
 
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vnLs catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
 
On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...
On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...
On-Chip ESD Protection with Improved High Holding Current SCR (HHISCR) Achiev...
 
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-CouplingGate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
Gate Pulse Triggering of Single Phase Thyristor Circuit through Opto-Coupling
 
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
 
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATORUNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
 
Dc mini-breaker
Dc mini-breakerDc mini-breaker
Dc mini-breaker
 
Calculation of short_circuit_currents
Calculation of short_circuit_currentsCalculation of short_circuit_currents
Calculation of short_circuit_currents
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using Arduino
 
Industrial electronics 1 marks- polytechnic
Industrial electronics  1 marks- polytechnicIndustrial electronics  1 marks- polytechnic
Industrial electronics 1 marks- polytechnic
 

Mehr von michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 
Short Circuit and Coordination Anaylsis
Short Circuit and Coordination AnaylsisShort Circuit and Coordination Anaylsis
Short Circuit and Coordination Anaylsismichaeljmack
 

Mehr von michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 
Short Circuit and Coordination Anaylsis
Short Circuit and Coordination AnaylsisShort Circuit and Coordination Anaylsis
Short Circuit and Coordination Anaylsis
 

Kürzlich hochgeladen

Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Kürzlich hochgeladen (20)

Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 

Transistion from TVSS to SPD

  • 1. Compulers Electronic Ballasts Cosh Registers ATMs Building Automation HVAC Systems Manurocturing Equipment Medical Equipment Drives PlCs Electronically CantraUed Motors Security Systems Audio & Video Equipment Telephones Sensitive Electronics - Presented by Gary H. Fox PE. Senior Specification Engineer Tuesday, September 22, 2009 The Transition From TVSS to SPD Surge Device Standards & UL 1449, 3rd Edition Changes What is Transient Valtage ? External Sources = 20% of all transients High level surges - Immediate Catastrophic Damage Examples: • lightning • Utility lood switching • Fault Clearing • Crossed Power lines • Damaged transformers ..,....':.';,,;: Va/tape splkesare high energy short duratIon transient voltoge events that damage or destroy senSItive electronic equipment Allequipmentwith printed circuit boards and microprocessors ore susceptible to transient surge damage. Equipment Affected Definition Effects of Transient Voltage (Surge) Lightning Flash Density Permanent Damage to Sensitive Electronic Equipment Erratic Control of Electronic Loads Control Failure System Down I Operation Interrupted Cost of operation down time Lost of productivity ..'IIh ............. '~11c:....oto>Iogr """'.... , ...h ~... COoI>aI""~"""""OI~,"""'lm-F."....,.Wll""'.""t""_ <1'''''''''''''''.:1_WSA 010 ,4I(l'..J-OOj _ll!l (1......-2!l'aJ .""........ .--_._. • imagination at work 1/ GE /
  • 2. Internal Saurces = 80% of all transients low level repeated surges - Damage Over Time E)(omples: • Compressors • Inductive loads -li.e) motors & pumps • HVAC Units • Elevators • Drives - control elevators! • Laser copiers • • Cleaning equipment -Vacuums, Floor polishers Standards NEMA LS-1- 1992 Low Voltage Surge Protective Devices NEMA LS-l standard was established in 1991lo serve as 0 uniform spKifict:lt!on gu(d~ine for low voltage surge protective devices. NEHA 1S·1 providn minimum parameters and definitions thot make up the content of 0 proper SPO (TVSSI specification formal Int."t of NEMA L5-11s to be generol in naturllt and !'lOt to introduce standards, derive lesting methodology or elrtenslVi! vocobulol)l. Key palllmetfn addressed in the NEMA LS-1 Sf)« fannat llfe: MCDV (MaKimum Continuous Dperatil'lg Voltagel Protected Modes Definition (L-N, L-G, L-!.. N-Gl Single Impulse Surge Rating Clamping Voltages per C62.41 Sofety Ageney Approvols by NRTL lUI.., CSA etc..) Natoli NEMA l5-1 parameters are rrquirftl forcompkte spKificotion ofollSPD dlfVlcu. IEEE Standards IEEE C62.41.1- 2002 Guide on the Surge Environment in LowVoltage AC Circuits IEEE C62.4L2 - 2002 Recommended Practlc. on the Characterilatlon of Surges in Low-Valtagf AC power Circuits IEEE (62.45 - 2002 Recommended Plllctke on Surge Testing for Equ!pment Connected to LV AC Power CirCl;U IEEE C62.62-2000 Standard Test Specifications for Surge- Protective Devices for Law-Voltag, AC Power Circuits IEEE C62.72 - 2007 IEEE1100-200S Guide forth, Application of Surge Protective Devices Recommende-d Practice for Pow,ring and Grounding Electromr'llc Equipment (Emerald Book! TVSS Overview TVSS Standards Standards? Recommended Practices? Guides? What's the Difference? IEEE Standards - Categorized ANSI/IEEE UL 1449 UL 1283 NEC NEMA C62.41, C62.45, C62.62, C62.72,1100 TVSS Safety Standard Noise Filtering Article 280, 285 LS-11992 Standard: Reed Practice: Guide: Mandatory requirements. Uses the word -Sholl" Procedures and positions preferred by IEEE: -Should" Alternative approaches listed. No clear cut recommendation • imagination at work 2/ GE /
  • 3. IEEE C62.41.1 - 2002 Guide on the Surge Environment in Low Voltage AC Circuits IEEE C62.41.1 provides information on surge voltages. currents and lOV thot Off propagated In low-voltage oc power circuits and charocterizes the surge environment Provides pll;lcticol bosis for the selection of voltage and curnn! tests for surgewithuond of elKtronic/eTectricol equipment Key orlClS oddrused: Provide bask information on surges Origin of Surges Propa~on, dispersion and mitigation of surges Rate of Occurrence and Voltoge Lenis in UnprotKted Circuits Octobase of observ~ sUfge behavior Reference document for C62.41.2 IEEE C62.41.2 - 2002 Re<:ommended Proctice on the Characterization of Surges in low-Voltage AC power Circuits IHE C62.41.2 choroctrrins the su'gl environment at locations on ac power circuits dncrilad In IEEE Sid C62.1I1.1-20C12 by means of standardized waveforms ond other stren paramettfl. HOT A PERFORMAHCE STANDARD Key arlal addr'llId: Waveshapes of Representati~tSurge Voltages, Entrgy and SOutCt ImptdafICt Location Categories relative to position ftom Service Entrance Rtpreuntati~tSurgt Wavtforms for eoch cattgory IEEE C62.41.2 - 2002 Recommended Practice on tne Ctloracterization of Surges in Low-Voltoge AC power Circuits Surge Exposure Locations Cottgory C " Service EntraflCe High - Medium Exposure lVSS Cottgory 8 • Service/Distribution I Short Run Branch Pontls Medium - Low Exposure TVSS Category A • Long 9ronch Ponelll Point of Use Locotions more thonlUm from CoL Bor 20m from Cot. C Low Exposure TVSS • imagination at work IEEE C62.45 - 2002 Recommended Practice on Surge Testing for Equipment Connected to LVAC Power Circuits 'EEE C62.4S provides 0 recommend proctiCt for tht ptnormance of surge ttsling on tltctricol ond tll:cttonic system cormected to low voltogt oc powtr circuiU. Provides guidofICt for specifying and opplying sU'llt ttsting equ!pmtnt to electrical devices subject to transitnt voltages. KlY areas oddrlssed: Provides general surge test plan recommendations Test methods to aid in dtsign. quality control, acceptonce and troubleshooting. C62.4S Is II guid.lln. only. Sptclficatian or Ptrlonnonce tnU lor any particular type of l:Quipment rtmains the prerogative of tltt monufacturu, user, and standards group involvl:'<l. IEEE C62.62 - 2000 Standard Test Specificotions far Surge Protective Devices IEEE C62.621s a successor document to rEEE 62.41 standards. thell provldts usus. indtptndtnt laboratoriu and manufactur.rs with test sp.cificatlons and tuting mtthodologies for Surge PTotl:ctlvt Dtvicu. KIY OriOI addrlllld: Ottai!s testing sptclficatlons for Moldmum Continuous Optratln.g Valtoge Ma><imum Single Withstand Surge Minimum Surgt Lile Withstand Surge Ruponst Voltoge (clamping voltagtl IEEE C62.72 - 2007 Guide for tlte Application of Surge Protective Devices IEEE C62.72 providts speclfil:r$ and users of SPO's with on understonling of numerous application considtfOtions to be eva!uatl:'<l befOfe SPD's ore installed In low voltoge AC power circuiU. Key arias oddrlssed: Defines considerations fOf the SPD stlectlon procen Dtscribes Surgt Origins, Eflecu, and Mognitudes Location Categories and Power Distribution SYlttmsandCanfigurot/ons Grounding and Sonding Protected Modes SPD Sptcifications SPD Failure Modes {~ SPD Systtm Coordination and Methodolog;es ~"'''''''I'''~'''"'''·.''' 3/ GE /
  • 4. UL 1449 2nd Edition IEEE 1100 - 2005 Recommended Practice for Powering and Grounding Electronic Equipment (Emerald Bookl JEfE 1100 presents recommended design,lnstaliation and molntenance proctlces for electrical power ond grounding and protection of electronil; foods such 05 industrial controllen, computers, ond other ITE used In commen:iol and induitriol applIcation$. Key SPO r.lat.d Topics; SPD purpose end method of operation. SPDT~hnologje5 Selection and Installation Considerations I IEEE 1100 - 2005 (Emerald Book) Powering cnd Grounding Electronic Equipment Section 8.6.1: 'lorg' transienls on th.pow.r IYS/lm originolinlllNfSidr of/heusrr's focility. OUr>cKlt~ with lighlnlng or mojor POIWf system IWlnls, 0,. best ~;~~;;>;g:':;;:::5f~~~~:~~:':J:~~c~o£:£~~7cjCaf:d~'6~nt~Fllrr7:t~~1 $ourc,o'I'" trclluirnrs or C/O$.IO th. fl/ec/ronic lood equipment if this is not possible. 8est ,,5ults ortobtoined ifboth locotlons artproteeted." S,ctlon 11.6.3: "Focililits hOU5i~ el.ctronk load I'quipmenl ofony type should hOlle ~i~~~~~f:;c:,~~ t~8t:~5 spW:,/:fj':J';~I~n~~ttproteel/on in the form of IEEE 1100 - 2005 (Emerald Book) Powering end Grounding Electronic Equipment S,ctlon 11.6.1: 'Pont/boords Ort cwoiloble thot contain inlef1rolly mounted SPOs that ~~~~:.~~;~~~~~h;;~r~oo~i~IIErh~~~~:":v1{e~~~~~~i~'f~~:r:~of inside switchboords orpan.lboards. thffe is 0 conetm thot fai/urt ofth. SPO ~~~~~~;:i;i~~Ot~;~~~~/~t;g~ ;~5tt~t,:::·:~hsbuob~:r,~~~r~i~~dt:1?~~~1:~.~ From IEEE C62.72: 'h.MOV inilialfS 0 condllctiv. condition idenlified as th.rmol runaway lhot inevitably rtsUlts In tIM dtstruction ofthe MOV. Th. r.sulti"f1 dtstruclion ofthe MOIlmight txpel hot metol ~ogm.ntst condlletive ioniztd gas.s. and d.nu conductive smoke and sooL~ond the mtroduction ofsuch mal.rials inlo the inlfriorof.ltetrical distribution I'qulpment con domog. or compromiu on Insulotion syst.m and rtsult in 0 caseadinf1 efftet ond 5ffious .qulpm.nt domaf1e.· IEEE 1100 - 2005 (Emerald Book) Powering ond Grounding Electranlc Equipment IEEE C62.72 tontlnues by stating: 'Th.rmal runoway conditions a" fXIJ".m.1y d.struetivt ond SPO :::~~~~~~~o~~~~~s ~~E~~':::;~~~I;g~~r;;%t1~7fh~~~~1ty of runoway condillons 0": l<ldot;u.-.DiSPO w/fAIn" w/t,,!HHtClolur. Inctu"","'Dit"'HOII_w/fItltl_lIngcon>~Of"_. Inf"9'"QIOf".itUfn<I/~fpr«_1on """9"'lfJ.nr!<lICUfDlf"-b. Utnitlng_Di"""'-IW _ _ IEEEonly d.scrlb#s pot.ntlalfalfun conditions as a cautIonary rtat.m.nt to th. sp«lfi.r or us.rs ofSPOs. Olff.r.nt SPO dfilgns will folf In dfff.nnt mannlN'S. UL 1449 Standard for Safety for Transient Voltage Surge Suppressors First Introduced in 1985. Ul1449 continues (0 serve os the Industry Approved Safety Stondord for Tronslent Voltoge Surge Suppressors used on AC low Voltoge Systems. listing requires product submittal to on OSHA occredited Notlonolly Recognized Test loborotory. (NRTU Any accredited NRTl can evoluote a TVSS for compliance to Ull449. IUL ElL MET Labs. etc_I Underwriters lobs is the Qt:l.LY. OSHA accredited lab that is not-for· profi( ond the only lob thO! can gille Ull449 compliance authorizotion to ploce the "Ul listed" sofety product mark. (02107 Effective) Standard For Sofety for Transient Voltoge Surge Suppressors The most current revision of Ull449 is 2"" Edition, dated February 9. 2005. Mandotory complionce to this revision become effective on Februory 9, 2007. All TVSS devices ore currently reqUired to meet the provisions of the most recent effective revision of Ul14491n order to continue to ploce the Ul mark. The most notable updates to the F,b, 2005 s(andotd were the Indusion of odditionolsofety tests which farces a product to foil in a sofe ond non· deslnJctive manner when subjected to abnormal elevated phose voltages with intermediote fault current potentials of 10. 100. 500 ond 1000 omperes. • imagination at work ."'''.0:.=: 4/ GE /
  • 5. UL 1449 2nd Edition '02107"''''''••'Standard For Safety for Transient Vohoge Surge Suppressors Fun Phose Voltagl Short Orcult lut and limited Current Ovlrvoltogl T,st Fallur. Unocceptable Results lOuring and Following Tlsts); 01 Emission oflome, molten metal. glowing or naming particles through ony openings (preexisting or created as 0 result of the test) in the product. bl Charring. glowing. or flaming of the supporting surface, tissue paper, Of cheesecloth. cllgnition of the enclosure. dl Creation of any openings In the enclosure thot result in occessibility of live potU. when f'Ioluote<l in accordonce with the occl!ssibiJity of live ports tnt in S5A.2. ellen ofstructural integrity to (I degree thot the equipment collapses or eKPeriences such displacement of ports thot there is (I risk of short- circuiting or grounding of current-carrying ports. Terminology Type 1 _ Permanently conneaed SPOS Intended for InstoUotion betwHn the SKOndery of the service troMfOfTMf ond the line $Ide of the serviu equipment OItfCWTent device. os -U lfli the load side, including wott-kour mtItf sodtet enclosures and intended to be instolll'Cl without on Vdemol oYIrCWTem prctK1ive diMe•. T)'lMl Z_ PI!f1TlCfmt!yCOMKted SPOS intended for Installation on the load side of the servic:. equipment overanltflt devic., inducing SPOt locoted at the tKondI ...... T)'lMl J _ Point-Qf·utililotion SPOt, instoUl'Clat 0 minimum cww:Iuetot length of JO ft from the e1ectricol service ponti to the point of utililOtion. ~Il~ cord connKted. dirKt plug.... rKeptode type ond SPOt iMUlDed at the U'tilil'O'tion equipment being protected. The distanc. CO ftI is .xdusiw of condl.lClors provided with or used to attochSPOS.. Type" - Component SPOs and componltflt ossemblies. .._.-:.=: Types of Metal Oxide Varistors (MOVs) "'1'" linn mod.11 or••qlllpp.dWltll EnhGnctd ThormGIIy PrGlnt.d M.IGI O-'Cid.IIGriIlGr fTPHOV)TKhnCllogy TPHOV Ftot""t1 • SGf.ty ftmOYts HOV "om circuit prior to ....ptuf. whtn '!<9oud to Glmormol Of su,t<lin.d pho.. owrvollog. tv.nll ........... GE TVSS to pall 011 Ull'19foll!:CUfftnt TUII 'ndU<lmg feb. z007 rtvlsionll....tIlout til. n.td fOf oddltlonal up.trt<lm .......<u,..nl Pl'llltCtlotl ..,...-:.....:: UL 1449 3rd Edition: What is changing? Nominal Discharge Current - In - Value is selected by the manufacturer Type 1 SPO con be either lOkA or ZOkA • Type 2 SPD can be 3kA, 5kA, lOkA or 20kA '- Nominal dischorge current level is morked on the label of 5PD - Test subjects SPD to a total of 15 impulses -In order to successfully pass test: SPO connot create a shock or fire hazard during the lest Nothing in the surge poth can open at any time during or after the lest llncJudes olllnternoJ and lilt.mol d.vlces, such as fusn andlor circuit breokersl .._.-:..= Measured Limiting Voltage Test 2nd Edition L Tton1itnIVCIltog. Surge SllJIptt110t "',,,, t. Fordtvict1oncif<urts6DD/OtI.n " su!V. Voltog. I(e*'9 !MtI ., CuI)I'C.,.:!.Tt1tIIIQ IiW/SOCI,t" S. lnstolctlon ""Icod tid. onIr 3fd Edition L Sllt9.Prolt<_OtvI<.ISPOI -olIO includ.IIKondOf)' SUfg. onulOts l. Fotcltvict1 on w<..u 1.OOOYorl.1t J. 110li<l;. P'OIt<!ion I(Cli~IIIPIt.I '" Nomilal D1Kharg. CWTtrrt Iiwn A ll. S. Type 1 c1_t1 cen btlfl1toltdon ... 1>cI. otlooclsicl. 6, Typell,l,_dtvict1 7, ._011 NotlOMI Slondo,c1lANSlI • Results in Voltage Protection Rating (VPR) • Uses a 6kV/3 kA combination wove surge {current is 6X greater than SVR test using 6kv/SOO A combinotian wove! • Higher current levels will produce higher VPR ratings, when compared to 2" edition SVR ratings for an identical device UL Sfandord is now more similar to the lEe Standard _. And complies with changes in Z008 edition ofNEe f»!'~'""-' • imagination at work 5/ GE I
  • 6. Lightning Protection Systems • UL96A - Installation Requirements for Lightning Protection Systems • Requires a Type 1 or Type 2 SPD rated 20kA nominal discharge current 11,1 • NFPA 780-2008 is in line with UL96A requirements • Nate: all GE SPD devices will be certified for UL96A usage SPD Component Technologies • Metal Oxide Varistors (MOVs) • Selenium • Gas Tubes • Hybrid •••• .._.-:..=: Frequently Asked Questions: Types of Metal Oxide Varistors (MOVs) Q. ~ Q. ~ Q. Q. ~ When don thl UL 1/149, 3"' edition go Into .".ell September 29, ZOO9 INo,lnlt/olly the date lhot the 3'" edition wcs to toke effect, but UL stm hos (I lorg. backlog. Mlgrs con b. gronted a limited Intoslon. Whet Is th,lmpo(t on my u:lsting TVSS Installations? Nothing. Th. chong" In th. stondord onll offm produtU mOllllfocfuffdon or ofttr th. 'fftctivi dati. Any ......sting inlto lotions witlstill be In UL compliance. What Impact don thIs hall' on my existing stocklln~ntory? Nothing. The chong•• In thl standard only affect product that II monufocluffd on or oft,r Septtmb,r 29. 2009. Any .lei,tlng stack monufoctur.d Mfore this datI will still be in ULcomplloncl. Don this rnt(Inthctpf'OdlKt$ c:ertifi"ll to UL 11149. 2"" edition or. nolOI me or Itffectlwl Som, monufoctur«l may be maki~ change. to their products In Mdel'" to com~ with 3"' editlon. GE'llinlt of curnnt TVSS productl olr~ colTllllv with 3..ltdltion ItOndarcli. Thltfltfore. _ orlt ~t chonglng OUf dnlgnIn ortJ~ to obtoln 3" edition Cltrt/fk;atlon. II GE dlo"llin9 ~r SPD productl1 Will thittlt bit nM ccrtolog nurnbitn1 GE II nllt ~ng thItIr pl"oductl in order to compfy with 3" edition. Onelt Wit obtoin~ Itdition cltftiflCatlon _ ....ilI ~n IobItling all product 01 3'" ItditiOtl compllonL .,.._.~ High En"gy Metal Oxide Varistor Components Many ManufactureNi U.. Small", Electronic Grode MOV Arrays .,.._.-=: General SPD Information • imagination at work SPD Terms Modes of Protection L-N L-G A B C N G ..,....~ 6/ GE /
  • 7. SPDTerms "Mode" vs "Phose" Rating L-N L-G SPD Maximum Surge Current Rating Surge Severity Ratings Per Made 25 - 50kA 65 -100kA 100-300kAHigh Exposure Low Exposure Medium ExposureN-G L-L A B C N G @ + @ 1=2001 ~ __•__. Mode x 2 = Phase Rating SPD Application Cascading System Wide Protection ANSI/IEEE 1100 Emerald Book Guide to SPD APPcUcotlon Outlinu coscading SPD approach for all calflgorics and flxposurll/'HI, HIgh tivil voltage spikes con get post leIVlce entronCII Vollog. spikes from high kA trolls/,nls con stilldomal1l1 downJfrrom IIqu,pmllnl SPD Installation Internally glneratld transients - 80% of all transients ServiclI IIntrance SPDconnOI provide prolfction from In!troo! ,urges Un'Kplcted IIlt.rnol transllnts In distribution - 1.11. Rooftop AC lightning strikes On building or nrorby bring highkA tronsiems Inro diSlribulion Redundant layered prot,ctlon at multiple levels Addiliono/'aym protllct sensitive e!t<:lronln Ifupstrtom devicn fail SPD Application Integral Switchboard" Panelboord New construction New panels or §witchboords on eKistlng facility 80M Extenllon Add to eldsting facility elKuicol distribution When bronch ponel disconnect is required Wall Mounted l7''''1i"'i1 New Construction U I~ Add 10 eldsllng focility eleet:ricol distribtltion n IImuJ When branch ponel disconneet: Is required SPD - Installation Options Paint af U.. Category'" ANSI/IEEE C62.41 "Cascading Approach" Dlrtrlbutlon """"" B Holn service Entra~ CategoryC • imagination at work 7/ GE /
  • 8. Integral Advantages - Better p.rforma~owr Wall Hountitd units ~=-~...c~ ......""'""- Shorter ~PO leads .. Britt( surgor rtduetion IWall SPOt;e SavIng. ltoves mort spoce for odditlonolpon,l, and gear plOCfmrnt in tight "'elricol rooms Factory Installed and Warranted Avoid Instollotlon errors, splicing or locollon probillms III labor_lngs 1.5 hours on overog' conlroclor lobor savings per SPD instolled flush mounting behind panel door Mounts bl/hind door in bronch ponl/ls and flush wilh switchboards and powerpone/s UL 61,891 Llsted Enf;TII Ponti &Swifchboard ourmbli.s wilh SPD hovlI bun UL lrstrei t1t~_. "'''w-:.;;;,;;:.: SPD Installation SPD Connection - Wire Length Effects Study In ZOO4, GE controet.,j A&' Laboretori'lln Conlhallock.n p~ to p.rlorm .urge luting on a .Imulotld .Iectrical dl.tribution ,v"l.m with SPo Inilolilld. Th' purp01f oflh tell WO, to d.t.rmln. th• • ",~t, of(obl.l.ngth on SPO p,rformonct. Both inttgroUy mounttd ond woll mounted SPO dnign, w.I.lndud.d In th. tnt Woll Mount SPO. w.r. fYoluottd wh.n (onnect.d ot I,ngth, 01 J' ond 10'. Integrol SPO, w.r, (onnect,d to th. dl'trlbution ,q"pm,nt bUI. IEEE recommend.d ,urg. wawform' w'r. InJect.d ot th. moln lug, of th. ,1,ctricolpon,l. L.t thru voItognw.r, coptured and r.cord.d down.tnomfrom the SPD ponol on both til, primory ond ,"candory lido 010 ,tIp-down uonllormtr. "Codl J-IndllMgrh o(SPD tHmllN1tlon ""'f. ""'" O«Ot1nl fof IncfftJlttJIUrg. volt. Itt Ihru fIvth. ,.". dfCfftJlf In domplng performona will ""I)' from 01 Ifttl. 01 11 voItl, or01 much 01 ZS IIOhs perIndl- imagination at work "'''.~,';l SPD Application Installatian 1. Minimize lead lengths 2. Twist wires to reduce impedance 3. Use fully rated surge class disconnect devices at service entrance. 4. Some models may require the use of a breaker. Refer to manufacturer ..".•-:.= • imagination at work 8/ GE /
  • 9. CATASTROPHIC PROTECTION SYSTEM IT'S ABOUT TIME! Damaging voltage surges and noise have become an all too common occurrence, including events like power swells (measured in seconds!. TOV Itemporary over voltages measured in milliseconds) and transient surges (measured in micro and nanosecondsl. Power quality experts'" indicate that these power quality events will continue to get worse as the loading on the North America power grid continues to grow, pushing the limits of the already dated and strained national power grid. POWER QUALITY DISTURBANCES While power quality disturbances come from many sources, their destructive ability is generally measured in power which has a function of time. A power quality disturbance from avery small over voltage event can be considerably more destructive than even a local lightning strike - given its application to the unprotected load for thousands of times longer li.e. milliseconds verses microsecondsI. While lightning will always be the most obvious source of failed equipment because of its effects on our environment, temporary over voltages and swells will be the most destructive power quality events seen over the next ten years'" The IEEE std 1100-20051Emerald Bookl indicates when singular or "burst" surges exceed the nominal peak line voltage, they will damage many types of electronic/electrical equipment. Even very small voltage surges applied at sensitive frequen- cies have been documented to cause damage and, at the very least, disrupt the data and its integrity"·I0"""'" Demonstrated through many industry tests, electronic and electrical components have been destroyed when exposed to higher voltage and energy events over normal line voltage.13 Gan",eal';;l Puto/l.4,Va1 Keurenl The industry typically identifies the following power quality events as: Over Voltage Swell ,, ; I ' > 1min 8 ms -1 min I • I ' 1.1-1.2 1.1 - 18 Temporary Over Voltage (lOV) Transient Surge 100 ~sec - 8 ms 1~sec - 100 ~sec Table 1 1.8 - 2.0 >1.2 While there are infinite numbers of sources that contribute to damaging voltage and energy surges, the majority can be broken into two major categories - environmental power quality disturbances and electrical switching surges. WWW.CUFlFlENTTECHNOLOGY.COM (CUnentThchnoJogy.
  • 10. ENVIRONMENTAL POWER QUAlITY DISTURBANCES Lightning proves to be the most destructive environmental generator of power quality disturbances. Other environmental induced surges include non-arcing electrostatic discharges IESOI with varying charge build up between cloud and earth. While the wives' tale states, "Lightning doesn't strike twice", in reality as many as 40 return strikes have been recorded"'''''''' with current surges of more than 500kA being seen, but typical surges reaching 20 kA to 40 kA. A typical lightning strike can last between 50~s to 100 ~s with most of the damaging energy below 1MHz 1<1.0 ~s rise times). When developing astrategy for power quality protection, it is critical to remember the high-frequency current element of a lightning surge, and that ESO protection requires special wiring and grounding techniques. Wiring and grounding practices for normal construction only consider the electrical safety element followed by NFPA 70 National Safety Code, leaving a building and all contents at serious risk to damage. A power quality strategy includes low-impedance wiring and grounding with the inclusion of a Catastrophic Protection System (CaPSI. Significant levels of current can be found in the area of the grounding electrode during a lightning surge event. The lightning discharge in the earth can actually become ionized by an event, becoming aground potential rise source IGPR) for damaging surge into a facility through the grounding system. Power quality events caused by coupling to conductive objects Imetal) is also very common Through inductive, capacitive and magnetic coupling, transients and noise are fixed onto objects. These transients are typically caused by cloud to cloud discharges"'-' coupled onto both buried and overhead conductors. For every charged cloud there is a reflective opposite charge seen by the earth, called acharge center. When there is cloud to cloud discharge, asimilar reflective event on earth follows the cloud activity. This rapid change in charges from the charge centers cause voltage and current surges in overhead and buried conductors."""'''' This rush for equilibrium in electrical charges can cause arcing and flashes inside a building as different paths and potentials are sought by the charged particles. Based on abuilding's internal system impedance and protection system installed, this type of power quality event results in simultaneous affects involving power, signal, communi- cations, data, and grounding at varying power levels. Even if lightning is discharged miles away and not seen or heard, often times, this coupling event damages equipment. ElECTRICAL SWITCHING SURGES Another example of a source of destructive power quality events come from rapid changes in current flow rates in an electrical system. These surges are typically oscillatory, meaning the ability to couple onto other conductive equipment in the area. A switching surge will also have multiple elements of both high and low frequency, with the highest frequency element found near the source and quickly losing energy as it travels further away from the source, and a low frequency element with aslower rise and fall time allowing propagation throughout a building. Typical causes of switching surges include: a) Energizing or de-energizing the reactive element ofapower source wiring system b) Arcing associated with contactors, relays or even loose connections and ground faults c) Unsynchronized power factor capacitor switching The dampening effect of the building impedance directly relates to the first-transition time of the surge. While transient surges (typically found in the microsecond to nanosecond range) can be quickly reduced by a factor of two, very little tran- sient attenuation can be expected for longer first-transition timed surges."''''''''''' This longer transient wave will have the appearance of a ring wave in the system and potentially is more damaging then asingle surge event. A building protection system should have the ability to protect and survive both fast and more destructive slow power quality events. WWW.CURRENTTECHNOLOGY.COM (¢anent 7tN:hnoJogy:
  • 11. ICT Is/olivo!. J I'»u. 'lEI WHAT IS A CATASTROPHIC PROTECTION SYSTEM (CaPS)? Current Technology repeatedly demonstrates itself as a leader in protection performance in both the labs and with its tens of thousands of protection systems installed in the field. From this wealth of information, Current Technology has developed a Catastrophic Protection System, or CaPS, using selenium hybrid protection as an effective strategy against power quality events caused by transient surges, temporary over voltage, power swells and noise entering into a building through its service entrance. While other Metal Oxide Varistor (MOV) based protection manufacturers claim to protect against power quality surge events for durations into the microseconds, only Current Technology's CaPS strategy allows protection from power quality events lasting up to the seconds (millions of times longer then any MOV based protectors). This difference in time will feel like an eternity to equipment loads being stressed by poor quality power. Therefore, while other manufacturer's protection elements are forced into failure or have yet to be turned on because of their design, Current Technology's CaPS strategy will continue to protect against surges throughout the transient surge, TOVor power swell event."·''''"'''''''''_'SdU'''' The following chart (Figure 11 demonstrates both the industry equipment ITI CEBEMA curve (20001 with the protection levels from MOV only verses selenium hybrid technology. Over Voltage (Vrms) 700 600 500 400 300 200 100 o MOV destroyed- no protection fRISK Area f -- Equipment f CaPS continues to protect -MOV f Selenium ~ Limited Risk 160115 1ms 3ms 20ms 100ms 500ms 15 105 Duration Figure I As Figure 1demonstrates, any voltage / time event that exceeds the equipment manufacturer specification is seen as an equipment risk area. While the CEBEMA curve provides equipment manufacturers a guideline for robustness required by electronic equipment, it is only providing aminimum design requirement. Not only are power quality events on the rise, but equipment failures are steadily increasing, as well. While MOV only technology provides adequate protection against transient surge events that happen in the nano and microseconds, the MOV's will literally destroy themselves when power quality over voltage events last into the milliseconds. Using a selenium hybrid based protection solution protects against transient surges, and is also actively diverting dangerous currents to ground caused by both TOV and voltage swell events. WWW.CURRENTTECHNOLOGY.COM
  • 12. Icr ls/o7lvol. 'I',,"' '19 HOW SHOULD CURRENT TECHNOlOGY CaPS BE USED? CaPS is all about better power quality protection for your sensitive equipment. IEEE C62.41 states that the best approach for total protection is using acascaded approach with the installation at multiple locations of the electrical system of the facility. By using Current Technology's CaPS strategy, surge protection starts BEFORE the surge actually enters the building. The Select 2 CaPS Protector is the only protector in the industry rated as both aSurge Arrestor and Surge Protection Device. When multiple protector units are deployed with SLc at the main and SLc secondary panels in acascaded strategy, a facility has the most versatile power quality protection system against transient surges and noises, and also has the ability to protect and survive against TOV and power swell events caused by abnormal voltages."O-U'","''''' As Figure 2demonstrates, acascaded concept can also include protection down stream in your building power distribu- tion system. This means that your load risk building evaluation should include power quality protection inside and outside of your building. Areas of concern should always include any power and telephone/data access points corning into a building structure. Figure 2 REFERENCES IEEE Std 1100-2005 was used as a core reference throughout whitepaper 1. Power Quality &Reliability Show - Panel Review Oct 2006 2. FIPS Pub 94-1983. Guideline on Electrical Power for AD? Installations 3. Gallace. Land Pujol. H., "The evaluation 01 CMOS Static-Charge Protection Networks and Failure Mechanisms Associated With Overstress Conditions as Related 10 Device Life.: Reliability Physics Symposium Proceedings, April/9ll 4. Van Keuren. E., "Effects of EM? Induced Transients on Integrated Circuits, .. IEEE Symposium on Electromagnetic Compatibility, pp. 1-5, 1975 5. McCann. G.D" "The Measurement of Lighting Currents in Direct Strokes." AlEE Transactions, vol 63.pp. 1157·64,1944 6. Boyce. C. F. Ch 25 "Protection of Telecommunications Systems" Vol 2, "lightning" in LightIJing Protection. R.H. Goldeledllondon: Academic Press, 1977 7. Sunde, E.D" Earth Conduction Effects on Transmission Systems. Van Nostrand Company, 1949 and Dover Publications 1968 8. Martzlofl. ED. and leedy, T.F., "Electrical Fast Transient Tests: Applications and limitations," IEEE Transaction on Industry Applications, vol fA-2B, no 1, pp 151-159, Jan/Feb 1990 9. Thomas &Betts Power Solutions Engineering Paper EP082006- .. Protection Effects of Selenium with Abnormal Voltage Applied", Aug 2006 10. Ul1449 2Edition Ver2.5 Abnormal Voltage Test WWW.CURRENTTECHNOLOGY.COM ~tTechnology.
  • 13. Page I of2 PRIMEDIABusilless Magazines & Media Selenium Suppressors Outperform MOV Cousins By Rajendranath K. Maharaj, eKE, Lucernemines, Pa. PCIM Power Electronic Systems, May 1, 2001 Used as a semiconductor in rectifiers and suppressors for many years, selenium occurs naturally on the earth. Its popularity as a rectifier is fading in favor of its silicon equivalent. However, demand for selenium suppressors continues. Depositing the elements on a metal substrate's surface produces selenium cells. This provides the cells with good thermal mass and energy dissipation as well as "self-healing" characteristics, allowing the device to survive energy discharges in excess of the rated value. Selenium's crystalline structure gives it the ability to continue functioning after a burst of energy in excess of its short pulse width rating. Its suppressor operation is comparable to a pressure relief valve - when the pressure rises, the relief valve opens, releases the pressure, and then resets itself. Because of its unique properties, the selenium suppressor remains viable in many applications. Special clamping capabilities enable the selenium suppressor to find its own niche as a transient voltage suppressor. Because of its ability to continuously dissipate power and handle long surges, it's better than MOVs or silicon suppressors for some applications. The selenium suppressor can absorb energy levels in excess of its rated capability while maintaining its clamping characteristics on the next cycle. The layering of the suppressor onto the aluminum plate allows the suppressor's energy capabilities to follow that of a heat sink curve. This heat sinking capability allows steady-state power dissipation up to 40 times that of an MOV. For a 130V suppressor, the selenium product allows steady-state dissipation of2.5W to 80W, compared with an MOV that allows only 0.1 W to 2.5W. Fig. I shows several selenium cells. Manufacturers produce selenium suppressor cell plates in sizes varying from I in. x I in. to 12 in. x16 in. that can function at a temperature ofO°C to 55°C ambient without any derating. The voltage ofa selenium suppressor cell starts at 26Vnns or 22.5Vdc per cell plate. Users must keep the suppressor to a 75V maximum due to the dielectric ceiling of the cell. The capacitive nature of the plate allows placement in series to attain higher voltage levels. Other suppressors can handle high current, short pulse widths in the microsecond range, but the selenium suppressor can handle millisecond pulse width currents, making it a more robust suppressor than silicon devices. It has a typical response time of less than I ms and is capable of handling pulses with long decay times as seen in large dc motors or any inductive loads with L/R ratios in the 100 ms range. Power conditioning systems, generators, and ac controllers are typical selenium suppressor applications. Suppressor applications are specifically used on the dc side ofa rectified generator output, across SCRs on large controllers, across dc motors, and on transformers for line-to-line transient suppressIOn. 7/26/2001
  • 14. Page 2 of2 Typical applications for selenium suppressors include: " On the dc side of a rectified generator output. .., Across the SCRs on large controllers. " Across dc motors. " On transformers (for line-to-line suppression). .., Power conditioning (i.e. from power strips to service entrance). For some devices, an MOV or a TVSS is better suited, and for others, a combination of suppressors is best. However, to the surprise of many electrical engineers, the capabilities unique to the selenium suppressor have enabled it to retain a firm place in today's market. 7/26/200 I
  • 15. All Current Technology products are listed to the new requirements of UL 1449 2nd Edition 2005 Revision (effective 2/9/2007). What is UL1449? UL 1449 is a safety standard developed by UL and adopted by OSHA as the standard for evaluating the safe operation of TVSS (transient voltage surge suppressors) or SPD (Surge Protection Devices). Compliance to UL standards is required by the NEC (Nation- al Electric Code) and must be certified by a NRTL (Nationally Recognized Test Lab). What or Who is UL? Underwriters Laboratories Inc. (UL) is an independent, not-for-profit product safety cer- tification organization that has been writing Standards for Safety for over a century. Up until recently, UL was the only NRTL that could test products and verify compliance to the standards. This compliance has previously been referred to as having a product "UL Listed". UL is not a government agency, they are a private organization responsible for the gen- eration and publication of safety standards. A separate division of UL is also an OSHA approved NRTL (Nationally Recognized Test Lab), which means they are authorized by OSHA to test, evaluate, and list products to safety standards. What is an NRTL, and what is the significance of OSHA recognition? The U.S. Department of Labor; Occupation Safety and Health Administration's (OSHA). is the legal authority for evaluating and approving NRTLs (Nationally Recognized Test Labs). The following definition of an NRTL can be found on OSHA's website. http://www. osha.gov/dts/otpca/nrtljindex. html. An NRTL is an organization that OSHA has "recognized" as meeting the legal require- ments in 29 CFR 1910.7. In brief, these requirements are the capability, control pro- grams, complete independence, and reporting and complaint handling procedures to test and certify specific types of products for workplace safety. This means, in part, that an organization must have the necessary capability both as a product safety testing labora- tory and as a product certification body to receive OSHA recognition as an NRTL. OSHA's recognition is not a government license or position, or a delegation or grant of government authority. Instead, the recognition is an acknowledgment that an organiza- tion has necessary qualifications to perform safety testing and certification of the specific products covered within its scope of recognition. As a result, OSHA can accept products "properly certified" by the NRTL. "Properly certified" generally means: 1) the product is labeled or marked with the registered certification mark of the NRTL, 2) the NRTL is- sues the certification for a product covered within the scope of a test standard for which OSHA has recognized it, and 3) the NRTL issues the certification from one of its sites (i.e., locations) that OSHA has recognized.
  • 16. There are a total of 17 labs that OSHA recognizes as approved NRTLs. Links are pro- vided to each NRTL from OSHA's website allowing you to view the list of standards, sites, and programs that OSHA has recognized that NRTL to evaluate products too. The fol- lowing 5 labs are qualified to test and list products to UL1449; CSA, ETL, MET, UL, and Wyle Lab. TVSS products do not have to bear UL's mark for OSHA to deem them safe for the workplace or for compliance with the NEe. Current Technology products were tested and evaluated in our world class laboratory that is certified by UL and ETL as part of their client data test programs. All Current Technology products are listed by ETL to UL 1449 2nd Edition 2005 Revision (effective 2/9/2007). Since ETL was the NRTL selected, all Current Technology products bear the ETL mark. Bottom Line. A product no longer has to be listed by UL, the NRTL, to be deemed safe for use in the workplace, or to adhere to the NEC requirements. Attached you will find a document from ETL that more clearly states their position as an OSHA approved NRTL. Best Regards, Chris Martin TVSS Product Manager
  • 17. CATASTROPHIC PROTECTION SYSTEM IT'S ABOUT TIME! •FACT: Lightning has proven to be the most destructive •FACT: A usual lightning strike can last between environmental generator of power quality disturbances. 50 ms to 100 ms with most of the damaging energy •FACT: A switching surge has multiple elements of both occurring below 1MHz (< 1.0 ms rise timesl. high and low frequency. The highest frequency element •FACT: Manufacturers of metal oxide varistor IMOV) only is found near the source and quickly loses energy as it based surge protection devices claim to protect against moves farther away. surge events found in the micro and nano seconds; •FACT: According to power quality experts, while lightning however, their products are at risk during common is the most obvious source of failed equipment, temoorary power quality events like temporary over voltages and over voltages and swells will be the most destructive voltage swells that range up to the seconds. power Quality events seen within the next 10 years. •FACT: Unlike MOV only based technology with its •FACT: Although the old wives' tale states, sensitivity to longer over voltage events, selenium hybrid "Lightning doesn't strike twice," in reality, as many as technology is proven to ride-through voltage swells 40 return strikes have been recorded (McCann) with unharmed, continuously protecting critical loads. visible current surges of more than 500kA, but typical •FACT: Only Current Technology offers a selenium surges reaching 20-40kA. enhanced Catastrophic Protection System {CaPSI solution. To Learn More About CaPS, Visit www.CurrentTechnology.com WWW.CURRENTTECHNOLOGY.CQM
  • 18. Selenium Test The next test keeps the voltage at 250V but brings a Selenium cell in parallel with the MDV. The typical response is that the MOV conducts 0.5 amps while the Selenium cell is now providing the majority of the protection, clamping current from 17-25 amps. The voltage is then raised to 275V with similar results. The MDV is still functional having only conducted 1-3 amps while the Selenium cell conducted 18-30 amps. With the flip of a switch the Selenium cell is removed from the circuit and the unprotected MOV fails instantly when 275V is applied to it. THE TEST PROCEDURE Standard Test During the standard test (2) 20mm MOVs are randomly selected from abox of MOVs. Each MOVs clamping voltages are meas- ured by avoltage breakdown tester. The Variac on the demo unit is adjusted to 200V and the MOV is subjected to 30 cycles at 200V. Typical responses range from no response at all, because the MDV did not conduct, to the MOV conducting up to 5amps of current. The Variac is then adjusted to 225V RMS. The response to this voltage could range from afailure of the MDV to a clamping current up to 19 amps. If the MOV sUlVived 225V the voltage is then raised to 250V At 250V the MOV will catastrophically fail and potentially trip the breaker to the outlet connected to the CaPS demo unit. This is asimulated test environ- ment limited by the available fault current of the local breaker connected to the CaPS tester. With unlimited fault current available, MOV only technology will fail quicker at lower voltages. INTRODUCTION The CaPS portable test platform demonstrates and validates the Current Technology advantage! The test performed wiII prove how Selenium/MOV hybrid technology provides better-quality protection against transients, TOV and swell conditions - far superior to MOV only based technology. DEMONSTRATION COMPONENTS The portable test unit is capable of providing a 30 cycle voltage swell ranging from 0-300V RMS. With the flip of a switch, the test platform can supply this voltage to an MOV or an MOV in parallel with a Selenium cell. An oscilloscope displays the conducted current of each device during the test. A monitor is attached to the output of the oscilloscope for ease of viewing. Current transformers are connected to the output of both the MDV and Selenium cell so that conducted current readings can be displayed on the monitor. THE CURRENT TECHNOLOGY ADVANTAGEI CAPS - CATASTROPHIC PROTECTION SYSTEM DEMONSTRATION KEY TAKE AWAY V" A Catastrophic Protection System must protect against transients, TOVs and swells. V" The CaPS demonstration shows key protection value of Selenium hybrid technology. V" MDV only based technology is at risk to common power quality events. V" Current Technology Select2~ meets CaPS requirements. Come tour Current Technology's surge laboratory in Richmond, Virginia - the largest in the United States. For more information, visit our web site at wwwcurrenttechnology.com or call us at 1-800-238-5000. WWW.CURRENTTECHNOLOGY.COM (CuntmtTec/moJogy.
  • 19. FACILITY WIDE CATASTROPHIC PROTECTION SYSTEM Part 1-General 1.1 Description/Scope A. The Catastrophic Protection System covered under this section includes all surge protection installed at the service entrance and all distribution panels electrically downstream from the same service entrance. B. A Catastrophic Protection System is a broad power quality protector capable of protecting against both transient surges under 100~Sec and temporary over voltages (TOV) and swells from 1OO~Sec to 2 minutes. C. Contractor shall provide all labor, materials, equipment and incidentals as shown, specified and required to finish and install surge protection devises. 1.2 Quality Assurance A. Reference Standard: Comply with the latest edition of the applicable provisions and recommendations of the following, except as otherwise stated in this document: 1. UL 1449 Second Edition 2005 Revision (effective 2/9/2007). 2. UL 1283. 3. ANSI/IEEE C62.41, Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits. 4. ANSIIIEEE C62A5, Guide for Surge Testing for equipment connected to Low-Voltage AC Power Circuits. 5. ANSI/IEEE C62.34, Secondary Surge Arrestor. 6. IEEE 1100 Emerald Book. 7. NEMA LS-1, 1992-(R2000) Low Voltage Surge Protection Devises. 8. National Fire Protection Association (NFPA 70: National Electrical Code). 1.3 Submittals/Quality Assurance - Submit the following: A. The Catastrophic Protection System must include shop drawings complete with all technical information, unit dimensions, detailed installation instructions, maintenance manual, recommended replacement parts list and wiring configuration. B. Copies of Manufacturer's catalog data, technical information and specifications on equipment proposed for use. C. Copies of documentation stating that the Surge Protection Device is listed from a Nationally Recognized Testing Laboratory (NRTL) (UL, ETL, etc) and are tested and multi-listed to UL 1449 and UL 1283. D. Copies of actual let through voltage data in the form of oscillograph results for both ANSIIIEEE C62A1 Category C3 (combination wave) and B3 (Ring wave) tested in accordance with ANSI/IEEE C6245. E. Copies of Noise Rejection testing as outlined in NEMA LS1-1992 (R2000) Section 3.11. Noise rejection is to be measured between 50kHZ and 100MHz verifying the devices noise attenuation. Must show multiple attenuation levels over a range of frequencies. F. Copies of Surge Fuse Testing. Each unit shall be surge tested with fusing in series to verify that a transient of maximum surge current capacity/magnitude is fully suppressed without fuse failure, operation or degradation per NEMA LS1-1992 (R2000) Section 3.9. G. Copies of test reports from a recognized independent testing laboratory, capable of producing 200kA surge current waveforms, verifying the suppressor components can survive published surge current rating on both a per mode and per phase basis using the ANSI/IEEE C62A1 impulse waveform C3 (8 x 20 microsecond, 20kV/1 OkA). Test data on an individual module is not acceptable. H. Copy of warranty statement clearly establishing the terms and conditions to the building/facility owner/operator. Part 2-Products 2.1 Approved Manufacturer: Service Entrance A. Current Technology - Select2 or SL2 Series (voltage and surge current depending on specific application & location). B. Approved equivalent. 2.2 Approved Manufacturer: Branch Panels, Distribution Systems, or Point of Use downstream of main service entrance. A. Current Technology - Select2, SL2, Select Compact or SLc B. Approved equivalent. 2.3 Manufactured Units/ Electrical Requirements A. Refer to draWing for operating voltage, configuration and surge current capacity per mode for each location, or you may list locations and information here. Facility Wide Catastrophic Proteclion System -1- 9.20.07
  • 20. B. Maximum Continuous Operating Voltage shall be greater than 115 percent of the nominal system operating voltage and in compiiance with test and evaluation procedures outlined in NEMA LS-1-1992 (R2000) paragraphs 2.2.6 and 3.6. C. Unit shall have not more than 10% deterioration or degradation of the UL1449, Second Edition surge suppression rating due to repeated surges. Unit shall have a monitoring option available to be able to test and determine the percentage of protection available at all times. D. Protection Modes and NEMA LS1 1992 (R2000)/UL1449 SVR for grounded WYE/delta and High Leg Delta circuits with voltages of (480Y/277), (208Y/120), (600Y/347). 3-Phase, 4 wire circuits, (120/240) split phase shall be as follows: System Mode B3 Rmgwave B3/C1 Comb. C3 Comb. Wave UL 1449 Voltage Wave Second Edition 120/240 L-N 300/350 400/450 625/725 400/400 120/208 L-G 375/425 400/475 625/750 500/500 N-G 325/325 450/450 725/725 500/500 L-L 375/475 750/825 975/1225 700/700 277/480 L-N 525/575 850/900 1125/1200 9001900 L-G 8251850 850/875 1050/1200 1000/1000 N-G 6751700 900/900 1200/1200 9001900 L-L 6501725 1675/1700 1925/2175 150011500 E. Electrical Noise Filter- each unit shall include a high performance EMIIRFI noise rejection filter. Noise attenuation for electric noise shall be as follows using the MIL-STD-220A insertion loss test method. 1. 100 kHz at 44 db. 2. All other frequencies should be 32 db or better. F. The Catastrophic Protection System shall provide temporary over voltage and voltage swell protection to the following: 1. TOV - should be capable of surviving and continue to protect critical loads against multiple TOV events (described as 200% nominal voltage by 8 mS. 2. Swell- should be capable of protection against swells up to 180% nominal for 0.7 ohms load >18,000 events. G. Each fuse shall be individually sealed in a manner that eliminates cross arcing. H. Integral Disconnect Switch. 1. The device shall have an optional NEMA compliant safety interlocked integral disconnect switch with an externally mounted metal manual operator. 2. The switch shall disconnect all ungrounded circuit conductors from the distribution system to enable testing and maintenance without interruption to the facility's distribution system. 3. The switch shall be rated for 600Vac. 4. The SPD device shall be tested to UL1449 Second Edition listed with the integral disconnect switch and the UL1449 Second Edition Suppression Voltage Ratings shall be provided. 5. The integral disconnect switch shall be capable of withstanding, without failure, the published maximum surge current magnitude without failure or damage to the switch. I. Each unit shall provide the following features: 1. Phase Indicator lights, Form C dry contacts, counter and audible alarm. 2. Field testable while installed. 3. Measuring capability to indicate the percent protection available in SPD. Part 3-Executionllnstallation 3.1 Each unit shall be installed per Manufacturer's recommended installation and wiring practices, as show on the drawing supplied. 3.2 The UL 1449 Suppression Voltage Rating (SVR) shall be permanently affixed to the SPD unit. 3.3 The SPD manufacturer's technician shall perform a system checkout and start-up in the field to assure proper installation, operation and to initiate the warranty of the system. The technician will be required to do the following: A. Verify clamp levels. B. Verify N-G connection. C. Record information to product signature card for each product installed. Part 4-Product Warranty 4.1 Warranty on defective material and workmanship shall be for 15 years. 4.2 Copy of Warranty to be sent with submittal. Facility Wide Catastrophic Protection System -2- 9.20.07
  • 21. GE Digital Energy Power Quality Integral SPD's: ASafe Solution with Better Performance •
  • 22. 1 Introduction The increasing number af cammercially available Surge Pratective Devices ISPD's) has pravided electrical system designers with a wide range af options to choose fram. SPO's are currently defined by the 2008 National Electrical Code as Type 1iSurge Arrester) or Type 2 (TVSS!. For the purpose of this paper, we will focus on SPO types commonly referred to as Transient Voltage Surge Sup- pressors ITVSSI that are intended for use at locations on the laad side of the primary overcurrent disconnect or main breaker of the electrical distribution system. Of the many model types, ratings and suppression technologies available, there are essentially two distinctive instollation methods that are frequently specified for commercial and industrial opplications. These are SPO's that are intended for either external mounting or integral installation. Externally mounted (also commonly referred to as "Wall-Mount" SPO'sl are availoble fram almost all major manufocturers of SPO's. These devices are typically housed in a dedicated enclosure and are intended to be connected to the power distribution system vio electrical conductors. These SPO's are terminated at a dedicated breaker, or in some instances directly to the phase bus of the electrical panel. Externally mounted SPO's ore designed to be installed by qualified electricol contractors at the job site. Integrally installed SPD's are offered by many electrical distribution equipment manufacturers. Integral SPO's are normolly mounted within the electrical gear and shipped to the job site as a complete package. Integral SPO's are factory installed and pre-wired to the electrical panel bus, so in many cases there is no need for further installatian. In recent years, a number of marketing publications have been released by monufacturers and proponents of externally maunted SPO's about the potential hazards associated with placing these devices inside af elec- trical distribution equipment. The focus of these pub- lications are to create concerns about the possibility of ancillary equipment damage that might occur in the event of SPO failure. lit should be noted that SPD foilure is most often the result of praduct misapplication or sustained abnarmal phase voltage potentials!. Many of these papers attempt to discourage the use of integrally installed SPO's while citing IEEE or other industry recognized standards as the authoritative basis for their position. These documents, are carefully conceived, but typicolly fall well shart of legitimacy due to the omission or misin- terpretation of key information from the referenced 2 standards. In many instances, the case against integral SPO application is being made based on historical data rather than taking into account the present status of the industry and the regulations that are currently in place to prevent the potentially destructive failure of SPO's for all applications. The focus of this paper sholl be to take a closer look at these standards, how they relate to SPD's, and what has been done to remedy the potentially damaging effects of a failing SPD. Both externally mounted and integrally installed SPO's offer a variety of options and features. There are advantages and disadvantages for both design types. While exter- nally mounted SPO's offer a good solution for users that would like to add surge pratection to an existing elec- trical system, their installatian and performance can be affected dramatically by enviranmental variables such as limited panel access, limited wall space, orthe level of experience that an installer has with such devices. A knowledge of the characteristics of high-frequency transient currents and the wiring techniques that must be used to successfully convey these currents is neces- sary for the praper installation of any SPO. In contrast. integral SPO's are not restricted by panel access or variations in installation. Since the SPO can be installed very close to the conductor being pratected in an integral mounting arrangement, the connecting lead length is often much shorter than when connecting an externally mounted SPD to the same conductor. This reduction in lead length contributes to impraved SPO voltage clamping performance over that of the externally mounted instal- lation and results in better surge protection (see "The Influence of Cable Connections on TVSS Performance" for more details)'- Equipment manufacturers who have earned good reputations can usually be relied on to employ persons who are trained and competent in the praper wiring pracedures for installing SPOs within their equipment. making the quality of the installation less of a factor with integrally installed SPOs. Some integral devices are offered without a dedicated disconnect feature which would require the panel to be powered down in the rare instance that the SPO needs to be serviced or replaced. However, de-energizing the equipment may be preferred, even with SPO's equipped with disconnects, when the SPO assembly is located adjacent to bare live parts.
  • 23. 2 Standards IEEE 1100-2005 is an industry-recognized standard that addresses recommended practices for the powering and graunding of electronic equipment. While this standard is nat exclusive to 5PD's, there are relevant sections with considerations for the application of such devices within the electrical distribution system. Section 8.4.2.5 states that SPD's "may be installed externally or internally to the switchboard or panelboard." And that "panelboards are available that contain integrally mounted SPD's that minimize the length of the SPD conductors, thus optimizing the effectiveness of the device." Additionally, IEEE 1100-2005 also cites IEEE preliminary draft standard PC62.72 by stating, "there is concern that failure of the SPD can cause collateral damage to the switchboard or panelboards." However, readers of IEEE 1100 might nat be aware that this statement was not a direct quotation fram PC62.72. Instead it was an interpretive comment made on section 14.1 of PC62.72 that describes the failure mechanisms of Metal Oxide Varistor (MOV) components that are commonly found within most SPD assemblies. PC62.72 has since been formally released as IEEE C62.72-2007, and is the IEEE guide standard for the application of Surge Pratective Devices. The approved standard does nat, nor has ever contained any specific language which would prohibit or warn against the use of integral SPD assemblies. Instead, IEEE C62.72-2007, Section 14.1 cautions that MOV's might expel hot metal fragments, conductive ionized gases, or canductive smoke/soot upon reaching a destructive thermal runaway condition. Of greater importance, C62.72 also advises that manufacturers will anticipate possible MOV failure and lessen or eliminate these potentially damaging effects using a variety of methods. These methods can include, but are not limited to, containment of the failing camponents by a fortified encasement, the addition of current limiting fusing, em- ploying thermal cutoffs, using non-flammable or flame quenching material/media, or any cambination thereof. 3 MOV Design Considerations Because of the many ways to prevent or contain the potentially damaging effects of MOV's, it is unlikely that any two SPD manufacturers will employ identical design approaches. Thus, it is important to realize that the severity of failure is dependant upon the SPD design and destructive failure prevention techniques and not the location of the SPD installation. An effectively designed SPD should nat fail in a manner that compramises the integrity of surraunding electrical equipment. regardless of integral or external design types. All major manu- facturers within the surge protection industry should be aware of the potential for catastrophic failure of MOV's and should design for each application accordingly. MOV's will eventually reach an end-of-Iife condition should the power system voltage elevate beyond the Maximum Continuous Operating Voltage (MCOVI rating of the SPD. MOV degradation can also lead to a permanent failure condition by gradually reducing the voltage clamping characteristic of the MOV until the clamping level eventually coincides with the normal system voltage. While degradation due to excessive surge energy remains a possibility within lower surge energy rated designs, it is nat considered a normal occurrence in the majority of today's high-energy SPD praducts. Regardless of the cause of MOV failure, the end result will be the same. When an extended avervoltage is present, or if the MOV degrades below the nominal operating voltage of the electrical power system, the MOV will attempt to "clamp" the system phase voltage. The MOV begins to cycle with the power frequency, initially "clipping" the voltage peaks of AC sinewave. The MOV attempts to dissipate the residual current, resulting in a rapid heating of the MOV body. This initial cycling/clipping condition of an MOV, attempting to absorb the overvoltage energy, begins the end-of-life stage of the MOV. This pracess is known as "thermal runaway". When the MOV can no longer dissipate this energy, it will typically fail at a random location an the MOV body. This location is sometimes referred to as the "punch-thraugh" site where the low impedance breakdown and subsequent shorting of the failing MOV develops. Once the MOV reaches a law resistive state, it can rapidly become a fragmentation and/or fire hazard if not immediately removed fram the electrical system fault current path. The level of available system fault current will then drive the subsequent destructive energy release fram the MOV. As stated in IEEE C62.72, section 14.1, SPD manufacturers employ various techniques in an attempt to limit the damage caused by a failing MOV. For example, designs that include a combination of current limiting fuses and thermal cutoffs rely on the current limiting fuses to in- terrupt high fault currents and the thermal cutoffs to interrupt low fault currents by opening as a result of radiant heat emitted fram the body of the failing MOV. However, coordination of fault interruption at intermediate fault current levels can present a significant problem for SPD design engineers. Thermal cutoffs are only good for limited levels of available current and can only react if the MOV can radiate enough heat directly at the cutoff during the thermal runaway cycle. The higher the available fault current. the more rapidly the failing MOV 3
  • 24. will be driven into a low resistive state. In most cases, this happens much too fast for even the closest proximity thermal cutoffs to react. And once the MOV has shorted, the initial energy release from the MOV will be concentroted at the location on the MOV surface where the short has originated. After this sequence occurs, the thermal cut- offs become ineffective. And if the fault current potential is not significant enough to open the primary current limiting fuse, the SPD could remain in a low resistive state with on unstable MOV that continues to emit intense energy in the form of fiome, molten material, smoke, etc. If only limited or intermediate system fault conditions are present, or if the SPD is not designed to effectively deal with fault currents at less than the maximum short circuit rating of the SPD, it is easy see how certain SPD designs could couse damage to the surrounding electricol equipment once the SPD housing has been breached by a foiling MOV. 4 Safety Testing UL1449 is the industry-recognized safety standard for Surge Protective Devices. During reviews of the UL 1449 standard in 2005, the UL Standards Technical Panel agreed that certain "blind spots" still existed within the abnormal avervoltoge/foult current testing program that is defined within the standard. As a result, UL 1449 was revised to incorporote additional requirements for abnormal overvoltoge testing to be applied with available intermediate fault currents of 10, 100, sao and 1000 amperes. These new testing levels were mode in addition to the maximum short circuit current and limited current testing levels that were introduced in the initial release of UL 1449 2'd edition in 1996. The addition of these new testing levels are intended to address conditions that SPD's are likely to be exposed to under a more extensive ronge of fault current potentials that exist within typical power systems. Many times, SPD's are installed on secondary power systems with power transformers or other power generation sources that cannot produce the maximum fault current potentials the SPD is rated for. As on example, on SPD that has been rated for use on power systems with a short circuit fault current potential of 200kA will be connected to a power system that is only capable of delivering a few thousand short circuit amperes. Prior to the addition of the new testing requirements, UL did not evaluate the SPD for safe current interruption at these lower, fault potentials. The new intermediate ~W imagination at work fault testing levels would reveal the vulnerability of many SPD designs that did not have full current limiting coordi- nation across ranges that are much lower than the tested maximum short circuit interrupt levels. During the UL test sequence for each specified fault current, the SPD is purposely driven into a failure condition by applying twice the nominal phose voltage that the SPD is designed for. In order to obtain a passing grode, the SPD cannot foil with any form of cotastrophic results that would include emission of flame, molten metal, glowing or flaming particles through any openings, charring, glowing, or flaming of the supporting surface, tissue paper, or cheesecloth, ignition of the enclosure, creation of any openings in the enclosure that result in accessibility of live parts or loss of structural integrity. The mandatory dote for UL certification using the inter- mediate level fault current testing revisions of UL 1449 was February 9, 2007. SPD's that are manufactured after this dote will not have authorization to apply the UL mark unless UL witness testing has been performed on each of the manufacturer's representative SPD models and voltage types and are found to be in compliance. These recent and significant testing updates to the UL 1449 standard should help to assure those who specify and purchase UL 1449 certified SPD's that the SPD's will not become a fire or fragmentation hazard, nor couse damage to surrounding gear, when the MOV's or other suppression components foil. 5 Conclusion Integral SPD's provide on excellent choice for new construction applications by eliminating installation variables, saving wall space and reducing the perform- ance degroding effects of SPD connecting lead length. Many proponents and manufactures of wall mount only type SPD's will argue that integrally mounted designs are unsafe, or will couse substantial collateral damage upon foiling while often citing incomplete or misinter- preted passages from various standards and historical documents as the basis. However, due to very recent changes in safety testing standards, SPD devices that are certified by UL to the latest revisions of UL 1449 will provide a safe and reliable solution for applications where the SPD is factory installed within electrical distri- bution equipment. 1 The Innuence of Coble Connections on TVSS Performance Marshall, E.; Honder: Valdes, M.; Britton, J.: Jones. 1: Whitehead. J.; Mcintyre, B. Industrial and Commercial Power Systems Technical Conference. 200S IEEE Volume, Issue. 8-12 May 200S Pagels): 212-217 GE Digital Energy - Power Quality 701 E22nd Street, lombord,lL 60148 USA 8006371738 www.gedigitolenergy.com/tvss www.getvss.com Information subject 10 change without notice. Please verify 011 details with GE. OET-661 1121081 lO 2008 General Electric Company All Rights Reserved '-