International Journal of Engineering Research and Development
e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com
Volume 2, Issue 11 (August 2012), PP. 66-70


 Performance Improvement of an Air Conditioning System Using
                  Matrix Heat Exchanger
                     N K Mohammed Sajid1, K Sankar Ram2, K A Shafi3
                          1,2,3
                                  Dept.of Mechanical Engineering, TKM College of Engineering, India



Abstract––The objective of this work is to study the performance of a split air conditioning system with and without a
Matrix Heat Exchanger (MHE) .The experiment was done using HFC134a as the refrigerant and Polyol-ester oil (POE)
as the conventional lubricant in the air conditioning system. The performance of the split air conditioning system with
HFC134a/POE oil system was compared with HFC134a/POE oil/MHE for different load conditions. The result indicates
that the system performance has improved when HFC134a/POE oil/MHE system was used instead of HFC134a/POE oil
system and there was also a reduction in power consumption at all load conditions. The HFC134a/POE oil/MHE works
normally and safely in the air conditioning system. HFC134a/POE mineral oil/MHE system reduced the energy
consumption by 33.84% when compared with the HFC134a/POE oil system. There was also an enhancement in
coefficient of performance (COP) when MHE was introduced in the normal system.

Keywords––Split air conditioner, HFC134a, POE oil, Matrix Heat Exchanger, COP, Vapour Compression System

                                                 I.       INTRODUCTION
           Most of the refrigeration system uses conventional Vapour Compression Refrigeration (VCR) cycle which has a
low Co-efficient of Performance (COP).But installing a heat exchanger to the VCR makes it more efficient. The refrigerating
effect of a refrigeration cycle mainly depends on the temperature of refrigerant that is entering the expansion valve. When it
is compared with standard vapour compression cycle, the system using the heat exchanger will have increasing refrigerating
effect as refrigerating temperature entering the expansion valve is low due to the presence of heat exchanger. Hence both the
capacity and coefficient of performance will be increased. This study aims to investigate experimentally the effect of Matrix
Heat Exchanger (MHE) in a split air conditioner system and compare the results.
           Shengshan Bi et.al [1] conducted a performance study of a domestic refrigerator using R134a/mineral oil/nano-
Ti02 as working fluid. A reduction in 21.2% energy consumption for a mass proportion of 0.06% of nano particle was
obtained with R134a/POE oil system.
           R saidur et.al [2] conducted an experiment in a domestic refrigerator with R134a/mineral oil with TiO2
nanoparticle to determine the thermal physical properties of these particles suspended in the refrigerant and lubricating oil
refrigerating systems. The energy consumption was saved by 26.1% with 0.1% mass fraction Ti02 nanoparticle compared to
the R134a and POE oil system
           Shengshan Bi et.al [3] conducted a performance study of a domestic refrigerator using R600a/mineral oil/nano-
Ti02 as working fluid. They got a reduction of 9.6% energy consumption for 0.5g/L of Tio2-R600a nanoparticle. This
system rejected less heat to the environment so it is safer in environmental aspects.

                                           II.        EXPERIMENTAL SETUP
A. Experimental System
           The experimental setup is a modification of conventional vapour compression refrigeration cycle. The basic
components are all same as that of VCR namely compressor, condenser, expansion valve and evaporator. Fig.1 shows the
photograph of experimental set up. The fabricated compact heat exchanger is installed between the condenser and the
expansion valve. The flow here is counter flow type as the effectiveness is more when compared with the parallel flow type
heat exchangers. The hot fluid flows through the inner tube of the compact heat exchanger and the cold stream passes
through the outer tube. The hot fluid from condenser is given as input and the cold fluid coming out of the heat exchanger is
passed to the expansion valve. The cold fluid from the evaporator is given as cold in and the cold out is passed to the
compressor to repeat the cycle. Copper tubes are used to connect the components and observations are made under different
loading conditions. A split air conditioner was used as an experimental setup and the system was modified by adding a
matrix heat exchanger by making a bypass line. The matrix heat exchanger is a tube in tube heat exchanger. The temperature
at various points was noted using thermocouples. The power consumption of the split air conditioner was measured using a
digital energy meter.




                                                               66
Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger




                         Fig. 1 Photograph of experimental set up of an air conditioner with MHE

B. Experimental Procedure
          After the integration of the components the heat exchanger is isolated so that the system is working normally
without the heat exchanger. The tests were conducted at 1000W, 1500W and 2000W using R134a/POE oil. At each load
conditions temperature and pressure at salient points were noted down at regular intervals. The experiment was done until
steady state condition was attained. After taking the readings, the heat exchanger valves are opened and the system starts
working with heat exchanger. The loading procedures are repeated until steady state conditions achieved.

                                   III.      RESULTS AND DISCUSSIONS
         Figure 2 shows comparison of the work done by the compressor with HFC134a/POE oil and HFC134a/MHE
mineral oil system. The work done by the compressor was greater for the HFC134a/POE oil system than the
HFC134a/POE/MHE mineral oil system. This was because the condenser-evaporator pressure difference was high for the
system when operating with HFC134a/POE oil than the HFC134a/POE/MHE mineral oil system. As the work done by the
compressor increases the power consumption also increases




                                                                                                      .
                                       Fig.2 variation of work done vs cooling load

           Figure 3 shows the COP variation of HFC134a/POE oil and HFC134a / POE/MHE mineral oil system. The COP
was greater for the HFC134a/POE/MHE mineral oil system. This may be due to reduction in compressor work done at
different load conditions.




                                                           67
Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger




                                         Fig.3 variation of cop vs cooling load

          Figure 4 shows the comparison of power consumption of the air conditioning system. As the work done increases
the power consumed by the system also increases. Power consumed by the compressor is less when the system is operating
with MHE. The power consumption of HFC134a/POE/MHE mineral oil system is lower than the HFC134a/POE oil. These
results show that the performance of the air conditioner with HFC134a/POE/MHE mineral oil system is better than that of
the HFC134a/POE oil system and there was an improvement in the operation when the air conditioner works with MHE.




                                      Fig.4 variation of power consumption vs load

          Figure 5 shows the variation of cooling capacity of the air conditioner with load. The increase in the cooling
capacity of R134a/POE/MHE oil system may be due to much lower temperature attained compared to the conventional
system.




                                                          68
Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger




                                      Fig.5 variation of cooling capacity vs cooling load

         Table 1 gives a performance comparison of the conventional system and the modified one. Various parameters
such as COP, work done, refrigerating effect, and power consumption are analysed.

       Table 1: PERFORMANCE COMPARISON of an AIR CONDITIONER with R134A/POE OIL SYSTEM and
                                   R134A/POE/MHE OIL SYSTEM
                     parameters R134a/POE Oil system   R134a/POE      Oil/MHE
                                                       system

                                         Various Loading conditions      Various Loading conditions
                                         1000W 1500W 2000W               1000W 1500W 2000W
                        Work done
                        W (KJ/kg))       42.04        39.65    38.76     29.65     27.5     26.45
                        Power
                        P (kW)           0.675        0.68     0.695     0.6       0.625    0.65
                        Refrigerating
                        Effect           156.65       162.4    168.47    180.56    187.86   190.44
                        (KJ/kg)




                        COP              4            4.3      4.3       6.3       6.5      6.8

                        Evaporative
                        Outlet           15.7         16.2     16.5      17        18.5     20
                        temperature
                        (T0c)

                                                IV.          CONCLUSIONS
The matrix heat exchanger worked normally and efficiently with the air conditioner. The power consumption of the
HFC134a/POE/MHE mineral oil system was reduced by 33.84% when compared with the conventional one. The results
show that the COP of HFC134a/POE/MHE mineral oil system was higher than that of the conventional system. Most of the
refrigeration system uses conventional vapour compression refrigeration cycle which has a low co-efficient of performance,
but installing a matrix heat exchanger to the VCR makes it more efficient. The refrigerating effect of a refrigeration cycle
mainly depends on the temperature of the refrigerant entering the expansion valve. The refrigerating temperature entering the
expansion valve was low due to the presence of heat exchanger So when it was compared with conventional vapour
compression cycle, the system using the heat exchanger had more refrigerating effect.. So both capacity and coefficient of
performance increased.


                                                               69
Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger

                                          ACKNOWLEDGEMENT
        This study was supported by the PG section (Industrial Refrigeration and Cryogenic Engineering) of Department
of Mechanical Engineering T.K.M. College of Engineering Kollam, Kerala, India

                                                 REFERENCE
  [1].   S Shengshan BI,Lin Shi,Lili Zhang,performance study of a domestic refrigerator using R134a/Mineral oil/nano-
         Ti02 as working fluid, International Congress Of refrigeration,2007,Beijing.
  [2].   R.Saidur, S.N.Kazi, M.S.Hossain, M.M Rahman, A review on the performance of nanoparticles suspended with
         refrigerants and lubricating oils in refrigeration systems, renewable and sustainable energy reviews 2010.
  [3].   Shengshan Bi , Kai Guo, Zhigang Liu, Jiangtao Wu, Performance of a domestic refrigerator using TiO2-R600a
         nano-refrigerant as working fluid, Energy Conversion and Management 52 (2011) 733–737.




                                                         70

Weitere ähnliche Inhalte

Was ist angesagt?

gas reheat and intercooling
gas reheat and intercoolinggas reheat and intercooling
gas reheat and intercooling
Cik Minn
 
Paper cid-furnace-feed-maxmization
Paper cid-furnace-feed-maxmizationPaper cid-furnace-feed-maxmization
Paper cid-furnace-feed-maxmization
CANDHARE
 
Using coolant modulation and pre cooling to avoid turbine blade
Using coolant modulation and pre cooling to avoid turbine bladeUsing coolant modulation and pre cooling to avoid turbine blade
Using coolant modulation and pre cooling to avoid turbine blade
Rakesh Rauth
 
Gas turbine efficiency - 7th January 2010
Gas turbine efficiency - 7th January 2010Gas turbine efficiency - 7th January 2010
Gas turbine efficiency - 7th January 2010
CangTo Cheah
 

Was ist angesagt? (20)

Gas turbines
Gas turbinesGas turbines
Gas turbines
 
HCCI Engines Fueled with Ethanol
HCCI Engines Fueled with EthanolHCCI Engines Fueled with Ethanol
HCCI Engines Fueled with Ethanol
 
Study and Implementation of Advanced Control and Optimization for Ethylene Fu...
Study and Implementation of Advanced Control and Optimization for Ethylene Fu...Study and Implementation of Advanced Control and Optimization for Ethylene Fu...
Study and Implementation of Advanced Control and Optimization for Ethylene Fu...
 
Conserve energy
Conserve energyConserve energy
Conserve energy
 
Learningpowerplantbasics
LearningpowerplantbasicsLearningpowerplantbasics
Learningpowerplantbasics
 
Furnace Draft.docx
Furnace Draft.docxFurnace Draft.docx
Furnace Draft.docx
 
Sibi
SibiSibi
Sibi
 
gas reheat and intercooling
gas reheat and intercoolinggas reheat and intercooling
gas reheat and intercooling
 
Beer combustion
Beer combustionBeer combustion
Beer combustion
 
Paper cid-furnace-feed-maxmization
Paper cid-furnace-feed-maxmizationPaper cid-furnace-feed-maxmization
Paper cid-furnace-feed-maxmization
 
Combustion control
Combustion controlCombustion control
Combustion control
 
Using coolant modulation and pre cooling to avoid turbine blade
Using coolant modulation and pre cooling to avoid turbine bladeUsing coolant modulation and pre cooling to avoid turbine blade
Using coolant modulation and pre cooling to avoid turbine blade
 
50 watt sterling engine
50 watt sterling engine50 watt sterling engine
50 watt sterling engine
 
High Ethane Fuel Gas_ Combustors
High Ethane Fuel Gas_ CombustorsHigh Ethane Fuel Gas_ Combustors
High Ethane Fuel Gas_ Combustors
 
Heat rate of coal fired power plant
Heat rate of coal fired power plantHeat rate of coal fired power plant
Heat rate of coal fired power plant
 
Improve plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlImprove plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater control
 
Gas turbine efficiency - 7th January 2010
Gas turbine efficiency - 7th January 2010Gas turbine efficiency - 7th January 2010
Gas turbine efficiency - 7th January 2010
 
210 MW BHEL Turbine Cycle Heat Balance
210 MW BHEL Turbine Cycle Heat Balance210 MW BHEL Turbine Cycle Heat Balance
210 MW BHEL Turbine Cycle Heat Balance
 
Fired Heater and Combustion Optimization From Yokogawa
Fired Heater and Combustion Optimization From YokogawaFired Heater and Combustion Optimization From Yokogawa
Fired Heater and Combustion Optimization From Yokogawa
 
Heatreflex
HeatreflexHeatreflex
Heatreflex
 

Andere mochten auch

IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 

Andere mochten auch (7)

IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...
Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...
Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
International Journal of Engineering Research and Development (IJERD)
 International Journal of Engineering Research and Development (IJERD) International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Power System Damping Oscillations in Smib with Pss-Fuzzy Upfc Controller
Power System Damping Oscillations in Smib with Pss-Fuzzy Upfc ControllerPower System Damping Oscillations in Smib with Pss-Fuzzy Upfc Controller
Power System Damping Oscillations in Smib with Pss-Fuzzy Upfc Controller
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...
Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...
Reduced Order Observer (DGO) based State Variable Design of Two Loop Lateral ...
 

Ähnlich wie IJERD (www.ijerd.com) International Journal of Engineering Research and Development

Escape 24 biomass power plant with integrated drying-effective utilization of...
Escape 24 biomass power plant with integrated drying-effective utilization of...Escape 24 biomass power plant with integrated drying-effective utilization of...
Escape 24 biomass power plant with integrated drying-effective utilization of...
Tesfaldet Gebregerges
 
Thermodynamic Analysis of Absorption Heat Transformer
Thermodynamic Analysis of Absorption Heat TransformerThermodynamic Analysis of Absorption Heat Transformer
Thermodynamic Analysis of Absorption Heat Transformer
Navneet Rohilla
 
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
inventy
 

Ähnlich wie IJERD (www.ijerd.com) International Journal of Engineering Research and Development (20)

Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
 
Escape 24 biomass power plant with integrated drying-effective utilization of...
Escape 24 biomass power plant with integrated drying-effective utilization of...Escape 24 biomass power plant with integrated drying-effective utilization of...
Escape 24 biomass power plant with integrated drying-effective utilization of...
 
P01314101108
P01314101108P01314101108
P01314101108
 
Recupretor
RecupretorRecupretor
Recupretor
 
B0362004014
B0362004014B0362004014
B0362004014
 
Pptx
PptxPptx
Pptx
 
Comparison of two different cooling methods for extrusion
Comparison of two different cooling methods for extrusionComparison of two different cooling methods for extrusion
Comparison of two different cooling methods for extrusion
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...
 
C012441216
C012441216C012441216
C012441216
 
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
 
E012262226
E012262226E012262226
E012262226
 
Thermodynamic Analysis of Absorption Heat Transformer
Thermodynamic Analysis of Absorption Heat TransformerThermodynamic Analysis of Absorption Heat Transformer
Thermodynamic Analysis of Absorption Heat Transformer
 
CASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptx
CASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptxCASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptx
CASE-STUDY-OF-LIQUID-SUCTION-HEAT-EXCHANGER-IN.pptx
 
Heat pump water heaters
Heat pump water heatersHeat pump water heaters
Heat pump water heaters
 
Industrial Heat Pumps
Industrial Heat PumpsIndustrial Heat Pumps
Industrial Heat Pumps
 
Effect of Combustion Air Pre-Heating In Carbon Monoxide Emission in Diesel Fi...
Effect of Combustion Air Pre-Heating In Carbon Monoxide Emission in Diesel Fi...Effect of Combustion Air Pre-Heating In Carbon Monoxide Emission in Diesel Fi...
Effect of Combustion Air Pre-Heating In Carbon Monoxide Emission in Diesel Fi...
 
Gas turbines working ppt
Gas turbines working pptGas turbines working ppt
Gas turbines working ppt
 
Improving and Comparing the Coefficient of Performance of Domestic Refgirator...
Improving and Comparing the Coefficient of Performance of Domestic Refgirator...Improving and Comparing the Coefficient of Performance of Domestic Refgirator...
Improving and Comparing the Coefficient of Performance of Domestic Refgirator...
 
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
Experimental Investigation of a Household Refrigerator Using Evaporative-Cool...
 
Gard analytics DOE energy modeling
Gard analytics DOE energy modelingGard analytics DOE energy modeling
Gard analytics DOE energy modeling
 

Mehr von IJERD Editor

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
IJERD Editor
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’
IJERD Editor
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
IJERD Editor
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
IJERD Editor
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
IJERD Editor
 

Mehr von IJERD Editor (20)

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACE
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding Design
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and Verification
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive Manufacturing
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string value
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF Dxing
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart Grid
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powder
 

Kürzlich hochgeladen

Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
amitlee9823
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
lizamodels9
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
dlhescort
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 

Kürzlich hochgeladen (20)

Famous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st CenturyFamous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st Century
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors Data
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 

IJERD (www.ijerd.com) International Journal of Engineering Research and Development

  • 1. International Journal of Engineering Research and Development e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com Volume 2, Issue 11 (August 2012), PP. 66-70 Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger N K Mohammed Sajid1, K Sankar Ram2, K A Shafi3 1,2,3 Dept.of Mechanical Engineering, TKM College of Engineering, India Abstract––The objective of this work is to study the performance of a split air conditioning system with and without a Matrix Heat Exchanger (MHE) .The experiment was done using HFC134a as the refrigerant and Polyol-ester oil (POE) as the conventional lubricant in the air conditioning system. The performance of the split air conditioning system with HFC134a/POE oil system was compared with HFC134a/POE oil/MHE for different load conditions. The result indicates that the system performance has improved when HFC134a/POE oil/MHE system was used instead of HFC134a/POE oil system and there was also a reduction in power consumption at all load conditions. The HFC134a/POE oil/MHE works normally and safely in the air conditioning system. HFC134a/POE mineral oil/MHE system reduced the energy consumption by 33.84% when compared with the HFC134a/POE oil system. There was also an enhancement in coefficient of performance (COP) when MHE was introduced in the normal system. Keywords––Split air conditioner, HFC134a, POE oil, Matrix Heat Exchanger, COP, Vapour Compression System I. INTRODUCTION Most of the refrigeration system uses conventional Vapour Compression Refrigeration (VCR) cycle which has a low Co-efficient of Performance (COP).But installing a heat exchanger to the VCR makes it more efficient. The refrigerating effect of a refrigeration cycle mainly depends on the temperature of refrigerant that is entering the expansion valve. When it is compared with standard vapour compression cycle, the system using the heat exchanger will have increasing refrigerating effect as refrigerating temperature entering the expansion valve is low due to the presence of heat exchanger. Hence both the capacity and coefficient of performance will be increased. This study aims to investigate experimentally the effect of Matrix Heat Exchanger (MHE) in a split air conditioner system and compare the results. Shengshan Bi et.al [1] conducted a performance study of a domestic refrigerator using R134a/mineral oil/nano- Ti02 as working fluid. A reduction in 21.2% energy consumption for a mass proportion of 0.06% of nano particle was obtained with R134a/POE oil system. R saidur et.al [2] conducted an experiment in a domestic refrigerator with R134a/mineral oil with TiO2 nanoparticle to determine the thermal physical properties of these particles suspended in the refrigerant and lubricating oil refrigerating systems. The energy consumption was saved by 26.1% with 0.1% mass fraction Ti02 nanoparticle compared to the R134a and POE oil system Shengshan Bi et.al [3] conducted a performance study of a domestic refrigerator using R600a/mineral oil/nano- Ti02 as working fluid. They got a reduction of 9.6% energy consumption for 0.5g/L of Tio2-R600a nanoparticle. This system rejected less heat to the environment so it is safer in environmental aspects. II. EXPERIMENTAL SETUP A. Experimental System The experimental setup is a modification of conventional vapour compression refrigeration cycle. The basic components are all same as that of VCR namely compressor, condenser, expansion valve and evaporator. Fig.1 shows the photograph of experimental set up. The fabricated compact heat exchanger is installed between the condenser and the expansion valve. The flow here is counter flow type as the effectiveness is more when compared with the parallel flow type heat exchangers. The hot fluid flows through the inner tube of the compact heat exchanger and the cold stream passes through the outer tube. The hot fluid from condenser is given as input and the cold fluid coming out of the heat exchanger is passed to the expansion valve. The cold fluid from the evaporator is given as cold in and the cold out is passed to the compressor to repeat the cycle. Copper tubes are used to connect the components and observations are made under different loading conditions. A split air conditioner was used as an experimental setup and the system was modified by adding a matrix heat exchanger by making a bypass line. The matrix heat exchanger is a tube in tube heat exchanger. The temperature at various points was noted using thermocouples. The power consumption of the split air conditioner was measured using a digital energy meter. 66
  • 2. Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger Fig. 1 Photograph of experimental set up of an air conditioner with MHE B. Experimental Procedure After the integration of the components the heat exchanger is isolated so that the system is working normally without the heat exchanger. The tests were conducted at 1000W, 1500W and 2000W using R134a/POE oil. At each load conditions temperature and pressure at salient points were noted down at regular intervals. The experiment was done until steady state condition was attained. After taking the readings, the heat exchanger valves are opened and the system starts working with heat exchanger. The loading procedures are repeated until steady state conditions achieved. III. RESULTS AND DISCUSSIONS Figure 2 shows comparison of the work done by the compressor with HFC134a/POE oil and HFC134a/MHE mineral oil system. The work done by the compressor was greater for the HFC134a/POE oil system than the HFC134a/POE/MHE mineral oil system. This was because the condenser-evaporator pressure difference was high for the system when operating with HFC134a/POE oil than the HFC134a/POE/MHE mineral oil system. As the work done by the compressor increases the power consumption also increases . Fig.2 variation of work done vs cooling load Figure 3 shows the COP variation of HFC134a/POE oil and HFC134a / POE/MHE mineral oil system. The COP was greater for the HFC134a/POE/MHE mineral oil system. This may be due to reduction in compressor work done at different load conditions. 67
  • 3. Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger Fig.3 variation of cop vs cooling load Figure 4 shows the comparison of power consumption of the air conditioning system. As the work done increases the power consumed by the system also increases. Power consumed by the compressor is less when the system is operating with MHE. The power consumption of HFC134a/POE/MHE mineral oil system is lower than the HFC134a/POE oil. These results show that the performance of the air conditioner with HFC134a/POE/MHE mineral oil system is better than that of the HFC134a/POE oil system and there was an improvement in the operation when the air conditioner works with MHE. Fig.4 variation of power consumption vs load Figure 5 shows the variation of cooling capacity of the air conditioner with load. The increase in the cooling capacity of R134a/POE/MHE oil system may be due to much lower temperature attained compared to the conventional system. 68
  • 4. Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger Fig.5 variation of cooling capacity vs cooling load Table 1 gives a performance comparison of the conventional system and the modified one. Various parameters such as COP, work done, refrigerating effect, and power consumption are analysed. Table 1: PERFORMANCE COMPARISON of an AIR CONDITIONER with R134A/POE OIL SYSTEM and R134A/POE/MHE OIL SYSTEM parameters R134a/POE Oil system R134a/POE Oil/MHE system Various Loading conditions Various Loading conditions 1000W 1500W 2000W 1000W 1500W 2000W Work done W (KJ/kg)) 42.04 39.65 38.76 29.65 27.5 26.45 Power P (kW) 0.675 0.68 0.695 0.6 0.625 0.65 Refrigerating Effect 156.65 162.4 168.47 180.56 187.86 190.44 (KJ/kg) COP 4 4.3 4.3 6.3 6.5 6.8 Evaporative Outlet 15.7 16.2 16.5 17 18.5 20 temperature (T0c) IV. CONCLUSIONS The matrix heat exchanger worked normally and efficiently with the air conditioner. The power consumption of the HFC134a/POE/MHE mineral oil system was reduced by 33.84% when compared with the conventional one. The results show that the COP of HFC134a/POE/MHE mineral oil system was higher than that of the conventional system. Most of the refrigeration system uses conventional vapour compression refrigeration cycle which has a low co-efficient of performance, but installing a matrix heat exchanger to the VCR makes it more efficient. The refrigerating effect of a refrigeration cycle mainly depends on the temperature of the refrigerant entering the expansion valve. The refrigerating temperature entering the expansion valve was low due to the presence of heat exchanger So when it was compared with conventional vapour compression cycle, the system using the heat exchanger had more refrigerating effect.. So both capacity and coefficient of performance increased. 69
  • 5. Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger ACKNOWLEDGEMENT This study was supported by the PG section (Industrial Refrigeration and Cryogenic Engineering) of Department of Mechanical Engineering T.K.M. College of Engineering Kollam, Kerala, India REFERENCE [1]. S Shengshan BI,Lin Shi,Lili Zhang,performance study of a domestic refrigerator using R134a/Mineral oil/nano- Ti02 as working fluid, International Congress Of refrigeration,2007,Beijing. [2]. R.Saidur, S.N.Kazi, M.S.Hossain, M.M Rahman, A review on the performance of nanoparticles suspended with refrigerants and lubricating oils in refrigeration systems, renewable and sustainable energy reviews 2010. [3]. Shengshan Bi , Kai Guo, Zhigang Liu, Jiangtao Wu, Performance of a domestic refrigerator using TiO2-R600a nano-refrigerant as working fluid, Energy Conversion and Management 52 (2011) 733–737. 70