D-1000
                                    GENERAL INFORMATION
                        EXPLODED VIEWS - PARTS LISTS

                                                         Webedition 08/2001




                                                                 ENGLISH
Attention! 3 minutes delay on all units with ‘Alfa-14’
controller. When starting or restarting the unit, it will take
3 minutes before the compressor and the fan will start
running.
Achtung! Wenn Sie das Gerät (wieder) in Betrieb setzen,
wird bei allen Geräten, die mit einem Zeitschaltuhr ‘Alfa-14’
ausgestattet sind, der Anlauf des Kompressors und der des
Ventilators um 3 Minuten verzögert.
Attention! Quand vous mettez ou remettez votre appareil
en fonctionnement, le compresseur et le ventilateur de tous les
appareils equipés d’une horloge électronique ‘Alfa-14’
commencent à fonctionner après 3 minutes.
Attentie! Wanneer u het apparaat wilt (her)starten en het
apparaat is uitgevoerd met een ‘Alfa-14’ tijdschakelaar, dan
duurt het 3 minuten voordat compressor en ventilator starten.
SAFETY
                                                     >10°
For safety reasons, read this information
carefully before operating.
Persons who are not familiar with this type of
product must not use it.
We strongly recommend keeping this
information in a safe place for future reference.

This appliance must be earthed.
The unit is designated for indoor
operation.

Refer to the rating plate for voltage and                       * Do not insert any object into an opening of the unit.
power input. The installation must be in                        * Disconnect from the mains before cleaning the unit or
accordance with regulations of the country                        any of its components.
where the installation is performed.                            * Never connect to an electrical outlet using an extension
The minimum distance between air inlet(s)                         cord. If an outlet is not available, one should be
and/or air outlet(s) and any object must be                       installed by a licenced electrician.
40 cm.                                                          * Any service other than regular cleaning or filter
                                                                  replacement should be performed by an authorized
* The unit is safe. It has been approved by many safety           service representative. Failure to do so could result in a
  institutions around the world. However, as with other           loss of warranty.
  electrical appliance, use it with care.                       * When the unit is placed in a (swimming) pool, connect
* Keep out of reach of children.                                  to the mains via a transformer or a breaking switch,
* Do not clean the unit by spraying it or immersing               conform the regulations regarding electrical
  it in water.                                                    installations.


                                             AMCOR DEHUMIDIFIERS

You can’t control humidity and haze outdoors.                   Water evaporating from a swimming pool, bathroom,
But in an indoor swimming pool and other                        archive, store or from wet objects and surfaces increases
humid interior spaces where hot stuffy air,                     the humidity of the air and creates the hazy and stuffy air
steamy windows and walls are frequent                           often found in the hall.
phenomena, you can.                                             At the same time water condenses on the cooler parts in
That’s why you need Amcor.                                      the hall: windows, walls, ceilings, etc.
                                                                Water condensation is not only an aesthetic defect, it can,
Amcor’s dehumidifiers clear the air in damp interior            in the long run, cause structural damage.
spaces.
Condensation is removed from windows, walls and                 There are two methods for drying the air in humid
ceilings.                                                       spaces:
Vaporous stuffy air is drawn off, clean air is pumped           - by ventilation,
back in.                                                        - by heat pumps.
You simply set the dial and the air humidity remains at         The Amcor dehumidifier is designed as a heat pump and
the required level.                                             has, through energy saving, a considerable advantage
And, the Amcor dehumidifier is an energy saver.                 over a ventilation system.



                                                            2
HOW THE “AMCOR” DEHUMIDIFIER WORKS

                                                                 The fan (1) sucks the humid air through the evaporator
                                                                 (2). There the air is cooled and the moisture in the air
             2 4             1
                                                                 condenses into water. This water is collected in the tray
                                                                 (3) and drained away through the sump and piping.
                                                                 The compessor (5) pumps the heat, which has been
                                                                 extracted from the air, into the condensor (6).
                                                                 There, this heat is once again released, and absorbed by
                                                                 the dry air. The ready wired control box monitors and
                                                                 controls the operation.
         3                   5             6




                                            ELECTRICAL WIRING


The unit can be supplied with a cord and an earthed plug. If it ever becomes necessary to replace this plug, be sure to
use an earthed plug suitable for the power supply in your area and conform your national safety standard.
The wires of the cable are coloured in accordance with the standard electrical code.

Blue             Neutral
Brown            Live
Green/Yellow     Earth

The blue (neutral) wire should be connected to the terminal in the plug marked N or coloured black.
The brown (live) wire should be connected to the terminal in the plug marked L or coloured red.
The green/yellow (earth) wire should be connected to the terminal in the plug marked E or coloured green or marked
with this symbol:

The unit must be connected to the power supply with the appropriate leads.
The cord should pass through holes with rubber grommets.
Properly fused disconnect switches must be installed between the unit and the power source.
The unit must be wired with an isolation (mains) switch accessible from outside the wet area in which the unit is
installed, to comply with IEE regulations.



                                                MAINTENANCE


The appliance is actually maintenance free, exept in cases
of soiling. In this case the filter has to be cleaned.




                                                             3
AMCOR MODEL D-1000

The Amcor D-1000 is a large capacity unit designed to
run highly efficiently in a domestic, commercial or
industrial environment.
The D-1000 keeps air dry and comfortable, prevents
condensation, and creates a better climate to prevent
damages caused by exessive humidity, such as: rusting of
equipment, dry rot of walls, mould growth in store
romms, etc.

It is ideal for places such as: restaurants, bars, printing
presses, indoor swimming pools, jacuzzis, garages,
animal enclosures, cellars, stores, boat sheds, weekend
cottages, archives, etc.
It can be positioned against the wall on legs.                       Model D-1000




                      INSTALL AND OPERATE YOUR AMCOR D-1000

1. Correct positioning                                            4. Humidity control
   It is possible to place the unit against the wall. The             The unit is controlled by a manually adjustable,
base of the unit at the air inlet must be clear of any            automatic humidistat, that switches the dehumidifier On
obstruction by at least 400 mm. The top of the unit must          and Off, to maintain the desired humidity level.
be clear of any obstruction by at least 400 mm.                   The humidistat should be 24V wall mounted type.
                                                                  It should be well ventilated and positioned at a height of
2. Electrical connections                                         about 1.50 m above the floor. The two leads of the
   The Amcor D-1000 must be connected to the power                humidistat should be connected to the appropriately
supply with appropriate leads.                                    marked terminals on the terminal strip in the electrical
The cord should pass through the hole with the rubber             control panel. Those two leads should then be fed to the
grommet on the top left side of the unit. Properly fused          vertical, white plastic conduit attached to the internal
disconnect switches must be installed between the unit            dividing panel. Set the humidistat to the level of relative
and the power source.                                             humidity required in the controlled space. For example,
                                                                  for normal comfort conditions the setting should be about
3. Condensate drainline                                           50% R.H.
   The end of the condensate drain pipe protrudes from
the base of the dehumidifier on the back extending the            5. Filter
pipe long enough to reach the nearest drain outlet and                 The filter should be regularly checked and if necessary,
insert its end.                                                   removed for cleaning or replacement. Slide the framed
                                                                  filter forwards and lift it out. Hold it under streaming
   Check that the condensate water tube does not at any           water and flush it clean. Let the trapped water drip off the
point slope upwards, which would cause a blockage.                filter fabric and replace the dried filter in reverse order.
A “U” trap, located in a place where the water will not
freeze, will prevent unpleasant odours from being drawn           6. De-icer control
into the conditioned space. Where it is necessary for                Your Amcor D-1000 is equipped with an automatic
condensate pipework or an electrical cable to pass                de-icer control that guards against ice forming on
through a wall, a lined or sleeved hole should be made.           refrigeration coils, in low temperature operation, by
Ensure that pipework and cables do not touch each other.          shutting off the compressor.
The hole should be sealed when installation is completed.         Note: The fan will keep running until all the ice has
                                                                  defrosted and then, the unit will start up again.




                                                              4
PROCEDURE ON START UP D-1000

PROCEDURE ON START UP
When the installation has been completed, carry out the
following procedure:
1. Make sure that the air filter has been fitted and that
   unfiltered air cannot be drawn in.
2. Check the condensate drain system for leaks.
3. Check whether the unit has been correctly wired
   according to the wiring diagram supplied.




                                          PRECAUTIONS D-1000

1. Switch off the power source at the mains, before                4. If the unit has been switched off, wait at least 3
   servicing the unit.                                                minutes before switching it on again. Safety cutouts
2. Do not operate the unit with the filter removed.                   and overload protective devices are fitted to protect the
3. The discharge air outlet grille and the return air filter          fan motor and the compressor.
   must not be covered at any time.                                5. Do not rapidly adjust the humidistat setting from one
   The minimum distance between inlet(s) and/or outlet(s)             extreme to the other and back again.
   and any object must be 40 cm.                                   6. For best results, close all windows to keep out
                                                                      additional moisture laden air.



                                     TROUBLESHOOTING D-1000

If the unit does not operate:                                      Leaking:
1. Make sure unit is connected properly.                           1. Make sure that condensate water tray outlet is not
2. Check fuse.                                                        blocked.
3. Ensure that the humidistat is in the required mode.             2. Make sure the plastic condensate water tube is
                                                                      securely attached and that it does not slope upwards
If the unit “short-cycles”:                                           at any point, causing a blockage.
1. Make sure that the filter is not blocked and that
   evaporator is not iced up.



                                      TECHNICAL DATA / D-1000

  MODEL                                   D-1000                                                 MOISTURE REMOVAL
  ELECTRICAL SUPPLY                       230 V
  FREQUENCY                               50 Hz
  MOISTURE REMOVAL AT 30°C                3.0 l/h                                                      "AMCOR" D - 1000

  40-100% R.H.                                                                        120                                       85
  POWER INPUT                             1260 W                                      100                                       80
                                                                        kg. / 24hr.




                                                                                       80
  CURRENT                                 5.7 A                                        60                                       75
                                                                                       40                                       70
  REFRIGERANT                             R407C (or R22)                               20                                       65
                                                                                        0
  REFRIGERANT CHARGE                      1260 g                                            15    20        25        30   35
                                                                                                                                60
                                                                                                                                55
  NET WEIGHT                              58 kg                                                        TEMP. deg. C
                                                                                                                                50
  LENGTH                                  1130 mm
  WIDTH                                   260 mm
  HEIGHT                                  680 mm

                                                               5
EXPLODED VIEW / D-1000




36
                                 1


35
                                 2



34
                                 3


                                 4




                                 5


54                               6
        33
                                 7
30
        31

                                 8
29
                                 9

32/56
                                 10

55                               11

28                               12

27



 6

26

25

24

23

22

                                 13


21


20
                                 14

19


18
             17        16   15




                  6
EXPLODED VIEW / D-1000


                                                                               37




53


52


51
                                                                               38
50


49
                                                                               39




                                                                               40




                                                                               41




                                              43
                                              44                               42

                                              45

                                              46

                                              47
     48




                     MOISTURE REMOVAL / D-1000

“AMCOR” D1000 - MOISTURE REMOVAL AT DIFFERENT ROOM TEMP. EN R.H.% (kg water/24h)
                               RELATIVE HUMIDITY %
          85       80       75         70         65   60        55       50
 ROOM
TEMP. °C
     15    40       36       33       30       27       24       23       17
     20    56       51       46       42       37       33       30       26
     25    75       68       62       56       50       44       39       35
     30    93       85       77       70       62       55       49       44
     35   101       92       83       76       68       60       53       48

                                       7
PARTSLIST / D-1000
DRAWING NO.       PART NO.        QTY.   PART NAME                 NO.
A2-1827-011       A414274         1      TOP COVER-RIGHT           1
A3-1827-015       O77001          1      PANEL-RIGHT               2
A1-1827-014       A382904         1      FRONT PANEL               3
A1-1827-046       A338666         1      LOUVERS                   4
A3-1827-032       A442545         1      HOLDER-LOUVERS R          5
A2-1827-064       A433345         1      WALL-RIGHT                6+8
A3-1827-006       A431004         1      DRIAN PAN                 7+21
                  429152/3        2+2    DIFFUSER                  9
                  271264          2      SCROLL-BLOWER             10
A3-1827-043       A438684         1      DROPS DEFLECTOR           11
A1-1827-040       A342565         1      WALL FRONT                12
A2-1827-023       A342554         1      COVER                     13+14
A2-1827-028       A501084         1      FOOT-RIGHT                15
A3-1827-031       A339094         1      HOLDER-FILTER             16
A3-1827-017       A436526         1      AIR FILTER                17
A2-1827-029       A501094         1      FOOT-LEFT                 18
                  410715          1      DRIAN PIPE                19
A1-1827-004       A326472         1      BASE                      20
A2-1827-035       A433355         1      WALL-LEFT                 22+6
                  386117          1      DEFROST CONTROL           23
A1-1827022        A330675         1      PANEL-BACK                24+55
                  425002          1      CAPACITOR-FAN MOTOR       25
DEPENDS OF COM                    1      CAPACITOR-COMPRESSOR      26
                  497103          2      GROMMET                   27
A3-1827-033       A442554         1      HOLDER-LOUVERS L          28
                  508027          2      CLIP                      29
                  346526          1      TERMINAL BLOCK            30
                  482301          1      TRANSFORMER               31
                  275016          1      TERMINAL & FUSE HOUSING   32
                  429182          1      CONTACTOR                 33
A3-1827-016       O77002          1      PANEL-LEFT                34
A2-1827-013       A414274         1      TOP COVER-LEFT            35
A3-1827-012       A372454         1      CROSS BAR                 36
A3-1827-042       A433374         1      CONNECTING PANEL-R        37
A3-1827-030       A434624         1      DIRECTIVE WALL            38
                  271264          2      BLOWER WHEEL              39/42
                  291016          1      FAN MOTOR                 40+41
DEPENDS OF COM                    3      SCREW                     43
ORDER WITH COM.                   3      SPRING WASHER             44
ORDER WITH COM.                   3      WASHER                    45
ORDER WITH COM.                   3      SLEEVE                    46
ORDER WITH COM.                   3      RUBBER GROMMET            47
                  274312          1      COMPRESSOR                48
                  292026          1      STRAINER-DISTRIBUTOR      49
                  442002          1      CAPILLARY TUBE            50
A1-1827-019       X1002080678     1      EVAPORATOR                51
A2-1827-042       A433384         1      CONNECTING PANEL-L        52
A1-1827-018       X1204100722     1      CONDENSER                 53
A2-1827-034       A422494         1      CONTROL BOARD             54
                  326101          1      FUSE                      56
WIRING DIAGRAM / D-1000




                                                                                     BLACK




                                                                                                      GREEN/YELLOW
                                                                                 3



                                                                                 1



                                                                         C                                                FAN
                                                                                                                         MOTOR
                                                                         COMP.

                                                              WHITE      R       S




                                                                                       RED
                                GREEN/YELLOW
                                               GREEN/YELLOW




                                                                                                                                BLACK
                                                                        CAPACITOR
                                                                                                                     WHITE    BROWN

                                                                                                                        CAPACITOR

                                                                      BLUE



                     GREEN/YELLOW                                     GREEN/YELLOW
LINE 230V/50HZ




                     BLUE                         BLUE
                 L
                                                  BLUE
                     BROWN                        BROWN
                 N
                                                                                                                                BLACK




                                                                                       P     F   M                    0 GND
                                                                                                      S




                                                                                       DEFROST TIMER
                                                                                         ALFA - 14/1
                                                                                        SNS1         SNS2              HYG



                                TO CONDENSATOR




                                    TO EVAPORATOR
TO HYGROSTAT




                                                       DEHUMIDIFIER D-1000                                                              274838




                                                                             9
Amcorex B.V.
    Anton Phillipsweg 9-11
1422 AL UITHOORN - Holland
  Tel. +31 (0)297 56 00 79
  Fax +31 (0)297 52 30 62
   Internet: www.amcorex.com
    e-mail: info@amcorex.com




  Amcor (Appliances) Ltd.
9 Ryan Drive, West Cross Centre
  Great West Road, Brentford
       Middlesex TW8 9ER
         United Kingdom
   Tel. +44 (0)20 8560 4141
   Fax +44 (0)20 8232 8814
  e-mail: amcor@amcorintl.co.uk

Weitere ähnliche Inhalte

Ähnlich wie D1000

caldeira elétrica montada na parede
caldeira elétrica montada na paredecaldeira elétrica montada na parede
caldeira elétrica montada na paredeDaxom/Navidens
 
manual da caldeira elétrica
manual da caldeira elétricamanual da caldeira elétrica
manual da caldeira elétricaDaxom/Navidens
 
Temperature and shade regulation in green house
Temperature and shade regulation in green houseTemperature and shade regulation in green house
Temperature and shade regulation in green houseiari
 
Img gas-water-heater-user-manuel-pdoc-975742227286282959
Img gas-water-heater-user-manuel-pdoc-975742227286282959Img gas-water-heater-user-manuel-pdoc-975742227286282959
Img gas-water-heater-user-manuel-pdoc-975742227286282959Daxom/Navidens
 
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...Graham Atherton
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Srinath Menon
 
Centralized AC System- S Menon & S Dayakar
Centralized AC System-  S Menon & S DayakarCentralized AC System-  S Menon & S Dayakar
Centralized AC System- S Menon & S DayakarSrinath Menon
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Srinath Menon
 
Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case studySona Rawat
 
Building services systems in sri lanka ac
Building services systems in sri lanka acBuilding services systems in sri lanka ac
Building services systems in sri lanka acArunali Dhelika
 

Ähnlich wie D1000 (20)

AIR CONDITIONING
AIR CONDITIONINGAIR CONDITIONING
AIR CONDITIONING
 
caldeira elétrica montada na parede
caldeira elétrica montada na paredecaldeira elétrica montada na parede
caldeira elétrica montada na parede
 
manual da caldeira elétrica
manual da caldeira elétricamanual da caldeira elétrica
manual da caldeira elétrica
 
caldeira elétrica
caldeira elétricacaldeira elétrica
caldeira elétrica
 
electric boiler
electric boiler electric boiler
electric boiler
 
Temperature and shade regulation in green house
Temperature and shade regulation in green houseTemperature and shade regulation in green house
Temperature and shade regulation in green house
 
Img gas-water-heater-user-manuel-pdoc-975742227286282959
Img gas-water-heater-user-manuel-pdoc-975742227286282959Img gas-water-heater-user-manuel-pdoc-975742227286282959
Img gas-water-heater-user-manuel-pdoc-975742227286282959
 
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
William Kidd CEO Institute of Specialist Surveyors and Engineers - plans for ...
 
HVAC
HVACHVAC
HVAC
 
Hvac & Refrigeration
Hvac & RefrigerationHvac & Refrigeration
Hvac & Refrigeration
 
electric boiler user boiler.pdf
electric boiler user boiler.pdfelectric boiler user boiler.pdf
electric boiler user boiler.pdf
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system
 
Centralized AC System- S Menon & S Dayakar
Centralized AC System-  S Menon & S DayakarCentralized AC System-  S Menon & S Dayakar
Centralized AC System- S Menon & S Dayakar
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system
 
Central ac system
Central ac system Central ac system
Central ac system
 
Air conditioning
Air conditioningAir conditioning
Air conditioning
 
Kazakistan references
Kazakistan referencesKazakistan references
Kazakistan references
 
Kazakistan references
Kazakistan references   Kazakistan references
Kazakistan references
 
Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case study
 
Building services systems in sri lanka ac
Building services systems in sri lanka acBuilding services systems in sri lanka ac
Building services systems in sri lanka ac
 

Mehr von erdinc klima

Tlc temperature-limit-controller
Tlc temperature-limit-controllerTlc temperature-limit-controller
Tlc temperature-limit-controllererdinc klima
 
T ex universal-controller
T ex universal-controllerT ex universal-controller
T ex universal-controllererdinc klima
 
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruTcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruerdinc klima
 
Tcx 12062-universal-controller
Tcx 12062-universal-controllerTcx 12062-universal-controller
Tcx 12062-universal-controllererdinc klima
 
Tcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllerTcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllererdinc klima
 
Tci universal-controller
Tci universal-controllerTci universal-controller
Tci universal-controllererdinc klima
 
M6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllerM6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllererdinc klima
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controllererdinc klima
 
Ec 300-energy-controller
Ec 300-energy-controllerEc 300-energy-controller
Ec 300-energy-controllererdinc klima
 
Tcy3 universa-controller
Tcy3 universa-controllerTcy3 universa-controller
Tcy3 universa-controllererdinc klima
 
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarKontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarerdinc klima
 
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisiKontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisierdinc klima
 
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisiKontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisiKontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisiKontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisierdinc klima
 
Duyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostatDuyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostaterdinc klima
 
Duyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorDuyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorerdinc klima
 
Duyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlerDuyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlererdinc klima
 

Mehr von erdinc klima (20)

Tlc temperature-limit-controller
Tlc temperature-limit-controllerTlc temperature-limit-controller
Tlc temperature-limit-controller
 
T ex universal-controller
T ex universal-controllerT ex universal-controller
T ex universal-controller
 
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruTcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
 
Tcx 12062-universal-controller
Tcx 12062-universal-controllerTcx 12062-universal-controller
Tcx 12062-universal-controller
 
Tcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllerTcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controller
 
Tci universal-controller
Tci universal-controllerTci universal-controller
Tci universal-controller
 
M6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllerM6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controller
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controller
 
Ec 300-energy-controller
Ec 300-energy-controllerEc 300-energy-controller
Ec 300-energy-controller
 
Tcy3 universa-controller
Tcy3 universa-controllerTcy3 universa-controller
Tcy3 universa-controller
 
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarKontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
 
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisiKontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
 
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisiKontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
 
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisiKontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
 
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisiKontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
 
Duyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostatDuyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostat
 
Duyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorDuyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensor
 
Duyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlerDuyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorler
 

D1000

  • 1. D-1000 GENERAL INFORMATION EXPLODED VIEWS - PARTS LISTS Webedition 08/2001 ENGLISH Attention! 3 minutes delay on all units with ‘Alfa-14’ controller. When starting or restarting the unit, it will take 3 minutes before the compressor and the fan will start running. Achtung! Wenn Sie das Gerät (wieder) in Betrieb setzen, wird bei allen Geräten, die mit einem Zeitschaltuhr ‘Alfa-14’ ausgestattet sind, der Anlauf des Kompressors und der des Ventilators um 3 Minuten verzögert. Attention! Quand vous mettez ou remettez votre appareil en fonctionnement, le compresseur et le ventilateur de tous les appareils equipés d’une horloge électronique ‘Alfa-14’ commencent à fonctionner après 3 minutes. Attentie! Wanneer u het apparaat wilt (her)starten en het apparaat is uitgevoerd met een ‘Alfa-14’ tijdschakelaar, dan duurt het 3 minuten voordat compressor en ventilator starten.
  • 2. SAFETY >10° For safety reasons, read this information carefully before operating. Persons who are not familiar with this type of product must not use it. We strongly recommend keeping this information in a safe place for future reference. This appliance must be earthed. The unit is designated for indoor operation. Refer to the rating plate for voltage and * Do not insert any object into an opening of the unit. power input. The installation must be in * Disconnect from the mains before cleaning the unit or accordance with regulations of the country any of its components. where the installation is performed. * Never connect to an electrical outlet using an extension The minimum distance between air inlet(s) cord. If an outlet is not available, one should be and/or air outlet(s) and any object must be installed by a licenced electrician. 40 cm. * Any service other than regular cleaning or filter replacement should be performed by an authorized * The unit is safe. It has been approved by many safety service representative. Failure to do so could result in a institutions around the world. However, as with other loss of warranty. electrical appliance, use it with care. * When the unit is placed in a (swimming) pool, connect * Keep out of reach of children. to the mains via a transformer or a breaking switch, * Do not clean the unit by spraying it or immersing conform the regulations regarding electrical it in water. installations. AMCOR DEHUMIDIFIERS You can’t control humidity and haze outdoors. Water evaporating from a swimming pool, bathroom, But in an indoor swimming pool and other archive, store or from wet objects and surfaces increases humid interior spaces where hot stuffy air, the humidity of the air and creates the hazy and stuffy air steamy windows and walls are frequent often found in the hall. phenomena, you can. At the same time water condenses on the cooler parts in That’s why you need Amcor. the hall: windows, walls, ceilings, etc. Water condensation is not only an aesthetic defect, it can, Amcor’s dehumidifiers clear the air in damp interior in the long run, cause structural damage. spaces. Condensation is removed from windows, walls and There are two methods for drying the air in humid ceilings. spaces: Vaporous stuffy air is drawn off, clean air is pumped - by ventilation, back in. - by heat pumps. You simply set the dial and the air humidity remains at The Amcor dehumidifier is designed as a heat pump and the required level. has, through energy saving, a considerable advantage And, the Amcor dehumidifier is an energy saver. over a ventilation system. 2
  • 3. HOW THE “AMCOR” DEHUMIDIFIER WORKS The fan (1) sucks the humid air through the evaporator (2). There the air is cooled and the moisture in the air 2 4 1 condenses into water. This water is collected in the tray (3) and drained away through the sump and piping. The compessor (5) pumps the heat, which has been extracted from the air, into the condensor (6). There, this heat is once again released, and absorbed by the dry air. The ready wired control box monitors and controls the operation. 3 5 6 ELECTRICAL WIRING The unit can be supplied with a cord and an earthed plug. If it ever becomes necessary to replace this plug, be sure to use an earthed plug suitable for the power supply in your area and conform your national safety standard. The wires of the cable are coloured in accordance with the standard electrical code. Blue Neutral Brown Live Green/Yellow Earth The blue (neutral) wire should be connected to the terminal in the plug marked N or coloured black. The brown (live) wire should be connected to the terminal in the plug marked L or coloured red. The green/yellow (earth) wire should be connected to the terminal in the plug marked E or coloured green or marked with this symbol: The unit must be connected to the power supply with the appropriate leads. The cord should pass through holes with rubber grommets. Properly fused disconnect switches must be installed between the unit and the power source. The unit must be wired with an isolation (mains) switch accessible from outside the wet area in which the unit is installed, to comply with IEE regulations. MAINTENANCE The appliance is actually maintenance free, exept in cases of soiling. In this case the filter has to be cleaned. 3
  • 4. AMCOR MODEL D-1000 The Amcor D-1000 is a large capacity unit designed to run highly efficiently in a domestic, commercial or industrial environment. The D-1000 keeps air dry and comfortable, prevents condensation, and creates a better climate to prevent damages caused by exessive humidity, such as: rusting of equipment, dry rot of walls, mould growth in store romms, etc. It is ideal for places such as: restaurants, bars, printing presses, indoor swimming pools, jacuzzis, garages, animal enclosures, cellars, stores, boat sheds, weekend cottages, archives, etc. It can be positioned against the wall on legs. Model D-1000 INSTALL AND OPERATE YOUR AMCOR D-1000 1. Correct positioning 4. Humidity control It is possible to place the unit against the wall. The The unit is controlled by a manually adjustable, base of the unit at the air inlet must be clear of any automatic humidistat, that switches the dehumidifier On obstruction by at least 400 mm. The top of the unit must and Off, to maintain the desired humidity level. be clear of any obstruction by at least 400 mm. The humidistat should be 24V wall mounted type. It should be well ventilated and positioned at a height of 2. Electrical connections about 1.50 m above the floor. The two leads of the The Amcor D-1000 must be connected to the power humidistat should be connected to the appropriately supply with appropriate leads. marked terminals on the terminal strip in the electrical The cord should pass through the hole with the rubber control panel. Those two leads should then be fed to the grommet on the top left side of the unit. Properly fused vertical, white plastic conduit attached to the internal disconnect switches must be installed between the unit dividing panel. Set the humidistat to the level of relative and the power source. humidity required in the controlled space. For example, for normal comfort conditions the setting should be about 3. Condensate drainline 50% R.H. The end of the condensate drain pipe protrudes from the base of the dehumidifier on the back extending the 5. Filter pipe long enough to reach the nearest drain outlet and The filter should be regularly checked and if necessary, insert its end. removed for cleaning or replacement. Slide the framed filter forwards and lift it out. Hold it under streaming Check that the condensate water tube does not at any water and flush it clean. Let the trapped water drip off the point slope upwards, which would cause a blockage. filter fabric and replace the dried filter in reverse order. A “U” trap, located in a place where the water will not freeze, will prevent unpleasant odours from being drawn 6. De-icer control into the conditioned space. Where it is necessary for Your Amcor D-1000 is equipped with an automatic condensate pipework or an electrical cable to pass de-icer control that guards against ice forming on through a wall, a lined or sleeved hole should be made. refrigeration coils, in low temperature operation, by Ensure that pipework and cables do not touch each other. shutting off the compressor. The hole should be sealed when installation is completed. Note: The fan will keep running until all the ice has defrosted and then, the unit will start up again. 4
  • 5. PROCEDURE ON START UP D-1000 PROCEDURE ON START UP When the installation has been completed, carry out the following procedure: 1. Make sure that the air filter has been fitted and that unfiltered air cannot be drawn in. 2. Check the condensate drain system for leaks. 3. Check whether the unit has been correctly wired according to the wiring diagram supplied. PRECAUTIONS D-1000 1. Switch off the power source at the mains, before 4. If the unit has been switched off, wait at least 3 servicing the unit. minutes before switching it on again. Safety cutouts 2. Do not operate the unit with the filter removed. and overload protective devices are fitted to protect the 3. The discharge air outlet grille and the return air filter fan motor and the compressor. must not be covered at any time. 5. Do not rapidly adjust the humidistat setting from one The minimum distance between inlet(s) and/or outlet(s) extreme to the other and back again. and any object must be 40 cm. 6. For best results, close all windows to keep out additional moisture laden air. TROUBLESHOOTING D-1000 If the unit does not operate: Leaking: 1. Make sure unit is connected properly. 1. Make sure that condensate water tray outlet is not 2. Check fuse. blocked. 3. Ensure that the humidistat is in the required mode. 2. Make sure the plastic condensate water tube is securely attached and that it does not slope upwards If the unit “short-cycles”: at any point, causing a blockage. 1. Make sure that the filter is not blocked and that evaporator is not iced up. TECHNICAL DATA / D-1000 MODEL D-1000 MOISTURE REMOVAL ELECTRICAL SUPPLY 230 V FREQUENCY 50 Hz MOISTURE REMOVAL AT 30°C 3.0 l/h "AMCOR" D - 1000 40-100% R.H. 120 85 POWER INPUT 1260 W 100 80 kg. / 24hr. 80 CURRENT 5.7 A 60 75 40 70 REFRIGERANT R407C (or R22) 20 65 0 REFRIGERANT CHARGE 1260 g 15 20 25 30 35 60 55 NET WEIGHT 58 kg TEMP. deg. C 50 LENGTH 1130 mm WIDTH 260 mm HEIGHT 680 mm 5
  • 6. EXPLODED VIEW / D-1000 36 1 35 2 34 3 4 5 54 6 33 7 30 31 8 29 9 32/56 10 55 11 28 12 27 6 26 25 24 23 22 13 21 20 14 19 18 17 16 15 6
  • 7. EXPLODED VIEW / D-1000 37 53 52 51 38 50 49 39 40 41 43 44 42 45 46 47 48 MOISTURE REMOVAL / D-1000 “AMCOR” D1000 - MOISTURE REMOVAL AT DIFFERENT ROOM TEMP. EN R.H.% (kg water/24h) RELATIVE HUMIDITY % 85 80 75 70 65 60 55 50 ROOM TEMP. °C 15 40 36 33 30 27 24 23 17 20 56 51 46 42 37 33 30 26 25 75 68 62 56 50 44 39 35 30 93 85 77 70 62 55 49 44 35 101 92 83 76 68 60 53 48 7
  • 8. PARTSLIST / D-1000 DRAWING NO. PART NO. QTY. PART NAME NO. A2-1827-011 A414274 1 TOP COVER-RIGHT 1 A3-1827-015 O77001 1 PANEL-RIGHT 2 A1-1827-014 A382904 1 FRONT PANEL 3 A1-1827-046 A338666 1 LOUVERS 4 A3-1827-032 A442545 1 HOLDER-LOUVERS R 5 A2-1827-064 A433345 1 WALL-RIGHT 6+8 A3-1827-006 A431004 1 DRIAN PAN 7+21 429152/3 2+2 DIFFUSER 9 271264 2 SCROLL-BLOWER 10 A3-1827-043 A438684 1 DROPS DEFLECTOR 11 A1-1827-040 A342565 1 WALL FRONT 12 A2-1827-023 A342554 1 COVER 13+14 A2-1827-028 A501084 1 FOOT-RIGHT 15 A3-1827-031 A339094 1 HOLDER-FILTER 16 A3-1827-017 A436526 1 AIR FILTER 17 A2-1827-029 A501094 1 FOOT-LEFT 18 410715 1 DRIAN PIPE 19 A1-1827-004 A326472 1 BASE 20 A2-1827-035 A433355 1 WALL-LEFT 22+6 386117 1 DEFROST CONTROL 23 A1-1827022 A330675 1 PANEL-BACK 24+55 425002 1 CAPACITOR-FAN MOTOR 25 DEPENDS OF COM 1 CAPACITOR-COMPRESSOR 26 497103 2 GROMMET 27 A3-1827-033 A442554 1 HOLDER-LOUVERS L 28 508027 2 CLIP 29 346526 1 TERMINAL BLOCK 30 482301 1 TRANSFORMER 31 275016 1 TERMINAL & FUSE HOUSING 32 429182 1 CONTACTOR 33 A3-1827-016 O77002 1 PANEL-LEFT 34 A2-1827-013 A414274 1 TOP COVER-LEFT 35 A3-1827-012 A372454 1 CROSS BAR 36 A3-1827-042 A433374 1 CONNECTING PANEL-R 37 A3-1827-030 A434624 1 DIRECTIVE WALL 38 271264 2 BLOWER WHEEL 39/42 291016 1 FAN MOTOR 40+41 DEPENDS OF COM 3 SCREW 43 ORDER WITH COM. 3 SPRING WASHER 44 ORDER WITH COM. 3 WASHER 45 ORDER WITH COM. 3 SLEEVE 46 ORDER WITH COM. 3 RUBBER GROMMET 47 274312 1 COMPRESSOR 48 292026 1 STRAINER-DISTRIBUTOR 49 442002 1 CAPILLARY TUBE 50 A1-1827-019 X1002080678 1 EVAPORATOR 51 A2-1827-042 A433384 1 CONNECTING PANEL-L 52 A1-1827-018 X1204100722 1 CONDENSER 53 A2-1827-034 A422494 1 CONTROL BOARD 54 326101 1 FUSE 56
  • 9. WIRING DIAGRAM / D-1000 BLACK GREEN/YELLOW 3 1 C FAN MOTOR COMP. WHITE R S RED GREEN/YELLOW GREEN/YELLOW BLACK CAPACITOR WHITE BROWN CAPACITOR BLUE GREEN/YELLOW GREEN/YELLOW LINE 230V/50HZ BLUE BLUE L BLUE BROWN BROWN N BLACK P F M 0 GND S DEFROST TIMER ALFA - 14/1 SNS1 SNS2 HYG TO CONDENSATOR TO EVAPORATOR TO HYGROSTAT DEHUMIDIFIER D-1000 274838 9
  • 10. Amcorex B.V. Anton Phillipsweg 9-11 1422 AL UITHOORN - Holland Tel. +31 (0)297 56 00 79 Fax +31 (0)297 52 30 62 Internet: www.amcorex.com e-mail: info@amcorex.com Amcor (Appliances) Ltd. 9 Ryan Drive, West Cross Centre Great West Road, Brentford Middlesex TW8 9ER United Kingdom Tel. +44 (0)20 8560 4141 Fax +44 (0)20 8232 8814 e-mail: amcor@amcorintl.co.uk