This document discusses definitions and requirements related to fire pumps according to NFPA 20. It defines key terms like "authority having jurisdiction" and "approved" and discusses requirements for water supply sources, pump types, installation, and testing. Specific topics covered include acceptable suction lift for centrifugal pumps, necessary water supply flow and pressure, requirements for packaged and field-erected pump houses, and guidelines for piping, valves, and other pump components.
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
NFPA 20 Fire Pump Water Supply Requirements
1. NFPA 20 1-8 (3.2) NFPA Official DefinitionsNFPA 20 1-8 (3.2) NFPA Official Definitions
Authority Having JurisdictionAuthority Having Jurisdiction.*.* The organization,
office, or individual responsible for approving
equipment, materials, an installation, or a procedure.
A-1-8 (3.2.2) Authority Having Jurisdiction.A-1-8 (3.2.2) Authority Having Jurisdiction.
The phrase “authority having jurisdiction” is used in NFPA documents in a
broad manner, since jurisdictions and approval agencies vary, as do their
responsibilities. Where public safety is primary, the authority having
jurisdiction may be a federal, state, local, or other regional department or
individual such as a fire chief; fire marshal; chief of a fire prevention bureau,
labor department, or health department; building official; electrical
inspector; or others having statutory authority. For insurance purposes, an
insurance inspection department, rating bureau, or other insurance
company representative may be the authority having jurisdiction. In many
circumstances, the property owner or his or her designated agent assumes
the role of the authority having jurisdiction; at government installations,
the commanding officer or departmental official may be the authority
having jurisdiction.
2. NFPA 20 (3.2.1)NFPA 20 (3.2.1)
Approved.*Approved.* Acceptable to theAcceptable to the
authority having jurisdiction.authority having jurisdiction.
A-1-8 (A.3.2.1) Approved.A-1-8 (A.3.2.1) Approved.
The National Fire Protection Association does not approve,
inspect, or certify any installations, procedures, equipment,
or materials; nor does it approve or evaluate testing
laboratories. In determining the acceptability of
installations, procedures, equipment, or materials, the
authority having jurisdiction may base acceptance on
compliance with NFPA or other appropriate standards. In
the absence of such standards, said authority may require
evidence of proper installation, procedure, or use. The
authority having jurisdiction may also refer to the listings
or labeling practices of an organization ( UL or <FM> )( UL or <FM> )
that is concerned with product evaluations and is thus in a
position to determine compliance with appropriate
standards for the current production of listed items.
3. WATER SUPPLYWATER SUPPLY NFPA 20 (5.6)NFPA 20 (5.6)
The most common sources of fireThe most common sources of fire
protection water are: city water, aboveprotection water are: city water, above
ground tank, below ground tank, well, orground tank, below ground tank, well, or
an open body of water ( pond, river,an open body of water ( pond, river,
lake, etc. )lake, etc. )
NFPA 20 (6.1.2)NFPA 20 (6.1.2) Centrifugal pumps shallCentrifugal pumps shall
not be used where a static suction lift isnot be used where a static suction lift is
required.required.
Find out how many GPM are required and how much PSI
is needed to make the sprinkler and/or stand pipe system
work… Will the “proposed” water supplywater supply and firefire
pumppump meet the system demand ?
4. Will the water supply be adequate at 150% of theWill the water supply be adequate at 150% of the
fire pump rated flow???fire pump rated flow??? NFPA 20NFPA 20 (5.6.2)(5.6.2)
(5.6.5.1)(5.6.5.1)
NFPA 20 (5.6.2.2)NFPA 20 (5.6.2.2) Where the water supplyWhere the water supply
from a public service main is not adequate infrom a public service main is not adequate in
quality, quantity, or pressure,quality, quantity, or pressure, an alternativean alternative
water source “SHALL” be provided.water source “SHALL” be provided.
NFPA 20NFPA 20 (5.6.5) Head. The head (suction
pressure) available from a water supply shall be
figured on the basis of a flow of 150 percent of
the rated capacity of the fire pump. This head
should be determined by a flow test of the water
supply priorprior to ordering the pump.
5. --SAMPLE----SAMPLE--
This water supply has a 6” line and an 8” that will feed a 1000 GPM pump.This water supply has a 6” line and an 8” that will feed a 1000 GPM pump.
The top curve has both lines open, the lower curve has only the 6” open.The top curve has both lines open, the lower curve has only the 6” open.
In the worst condition (6” only) the line will provide 1000 GPM @ 45 PSI.In the worst condition (6” only) the line will provide 1000 GPM @ 45 PSI.
NOTE: Water supply flow test - MUSTNOTE: Water supply flow test - MUST
BE CONDUCTED BEFORE A PUMP ISBE CONDUCTED BEFORE A PUMP IS
SPECIFIED AND ORDERED! (5.6.5)SPECIFIED AND ORDERED! (5.6.5)
6. STATE of OHIO FIRE SCHOOL - BGSU 6
Theoretical ConditionsTheoretical Conditions
.323 ‘323 ‘
NFPA 20 TheoreticalNFPA 20 Theoretical
Maximum ChurnMaximum Churn
HEADHEAD “Must not“Must not
exceed” 140 % ofexceed” 140 % of
RatedRated HEADHEAD
231 ‘231 ‘
NFPA 20 100%NFPA 20 100%
“Rated” Condition“Rated” Condition
500 GPM @ 231 ‘500 GPM @ 231 ‘
HEADHEAD
500 GPM500 GPM
750 GPM750 GPM
NFPA 20 TheoreticalNFPA 20 Theoretical
Minimum Head ATMinimum Head AT
150%of RATED FLOW150%of RATED FLOW
- Head Must Be- Head Must Be
“Above“Above ““ 65%of65%of
RatedRated HeadHead
PP
UU
MM
PP
HH
EE
AA
PUMP FLOW in GPMPUMP FLOW in GPM
7. Total Head (H), Horizontal Pumps.*Total Head (H), Horizontal Pumps.* TheThe
measure of themeasure of the “work increase”“work increase” per poundper pound
(kilogram) of liquid, imparted to the liquid by the(kilogram) of liquid, imparted to the liquid by the
pump, and therefore the algebraic differencepump, and therefore the algebraic difference
between the total discharge head and the totalbetween the total discharge head and the total
suction head.suction head.
Where “positive” suction head exists,Where “positive” suction head exists,
thethe total headtotal head (( work increasework increase )) = the= the
totaltotal dischargedischarge head ‘head ‘minus’ ( - )minus’ ( - )
the totalthe total suctionsuction head.head.
Total Head (H), Vertical Turbine Pumps.*Total Head (H), Vertical Turbine Pumps.* TheThe
distance from the pumping water level to the center of thedistance from the pumping water level to the center of the
discharge gaugedischarge gauge ‘plus’ ( + )‘plus’ ( + ) the total discharge head.the total discharge head.
8. STATE of OHIO FIRE SCHOOL - BGSU 8PSI /PSI / HEAD (ft)HEAD (ft)
CALIBRATED ??CALIBRATED ?? CALIBRATED ??CALIBRATED ??
9. To determineTo determine
FEET of HEADFEET of HEAD
multiply “multiply “ HH ““
(net PSI) X 2.31(net PSI) X 2.31
To determine “To determine “
HH ” (net PSI)” (net PSI)
subtractsubtract
SuctionSuction PSIPSI
fromfrom
DischargeDischarge PSIPSI
150 PSI150 PSI
50 PSI50 PSI
100 PSI100 PSI
231’ (ft)231’ (ft)
HORIZONTALHORIZONTAL
PUMPSPUMPS
The suction pressure mustThe suction pressure must
be (0 psi) or higher whenbe (0 psi) or higher when
pump is operating at 150 %.pump is operating at 150 %.
When suction is from a tankWhen suction is from a tank
the pressure is permitted tothe pressure is permitted to
drop to (-3 psi). NFPA 20drop to (-3 psi). NFPA 20
(5.14.3)(5.14.3)
10. STATE of OHIO FIRE SCHOOL - BGSU 10
.
.
.
“RATED 100% FLOW “
..
AA
CC
BB
..
..
..
“ 150 %
FLOW “
““CHURN”CHURN”
PressurePressure ““RATED”RATED”
100 %100 %
FLOWFLOW
ACTUAL CITY WATERACTUAL CITY WATER
FROM PUMP TESTFROM PUMP TEST
FLOW IN GPMFLOW IN GPM
HH
EE
AA
DD
11. STATE of OHIO FIRE SCHOOL - BGSU 11
PUMP FLOWPUMP FLOW
DETERMINATIONDETERMINATION
WITH FLOWWITH FLOW
METERMETER
12. STATE of OHIO FIRE SCHOOL - BGSU 12
NOZZLENOZZLE (PLAY PIPE)(PLAY PIPE)
AND PITOT TUBEAND PITOT TUBE
PUMP FLOWPUMP FLOW
DETERMINATIONDETERMINATION
26. WaterWater
SealSeal
PipingPiping
NOTE: Water sealNOTE: Water seal
piping is not providedpiping is not provided
on UL Fire Pumpson UL Fire Pumps
with suction pressurewith suction pressure
of 30 psi or more !of 30 psi or more !
#1#1
YOU MUSTYOU MUST
ACCURATELYACCURATELY
DETERMINE THEDETERMINE THE
SUCTION PRESSURESUCTION PRESSURE
““BEFORE”BEFORE” THE PUMPTHE PUMP
IS ORDERED !!IS ORDERED !!
NFPA 20 (5.2.2)NFPA 20 (5.2.2)
(5.6.2.3)(5.6.2.3)
27. ““ACTUAL” Suction pressure MUST beACTUAL” Suction pressure MUST be
determined BEFORE you order the pump !determined BEFORE you order the pump !
NFPA 20 (5.2.2) (5.6.2.3)NFPA 20 (5.2.2) (5.6.2.3)
ActualActual
suctionsuction
pressurepressure
MUST NOTMUST NOT
exceedexceed
this !this !
28. STATE of OHIO FIRE SCHOOL - BGSU 28
NO RODS !!!
SAFE ??
Look at the pipe
fittings !!
This pump installation
develops 213 PSI at
churn.
A 125 lb flanged fitting
is rated at 175 PSI
maximum working
pressure !! NFPA 20
(5.7.4.1)
NFPA 13 15.1.6.1.1NFPA 13 15.1.6.1.1
29. STATE of OHIO FIRE SCHOOL - BGSU 29
NFPA 20NFPA 20
(5.7.4.1)(5.7.4.1)
(5.7.4.2)(5.7.4.2)
VariableVariable
Speed PLCSpeed PLC
(5.18.1.3)(5.18.1.3)(5.18.7)(5.18.7)
30. STATE of OHIO FIRE SCHOOL - BGSU 30
Circulation Relief ValveCirculation Relief Valve
¾”¾” is theis the MINIMUMMINIMUM size for upsize for up
to 2500 GPM Rated Pump*.to 2500 GPM Rated Pump*.
1”1” MIN.MIN. for larger pumps ???for larger pumps ???
NFPA 20 (5.11)NFPA 20 (5.11) **
31. Circulation “Case”Circulation “Case”
Relief ValveRelief Valve
NFPA 20 2-6 (5.11)NFPA 20 2-6 (5.11)
NOTE : Not required on dieselNOTE : Not required on diesel
engine-driven HSC fire pumps unlessengine-driven HSC fire pumps unless
the engine is radiator-cooled !the engine is radiator-cooled ! **
55 L55 L
918918 19 - 2019 - 20 1069110691 FWCFWC
32. STATE of OHIO FIRE SCHOOL - BGSU 32
NOTE: Above
(optional) Back-
pressure orifice
assembly installed
in ¾” case relief
valve discharge to
create back
pressure and
reduce cavitation.
NOTE: (Optional) Y strainer can
be used when foreign material
(sand or other debris) is present
in the water.
ORIFICE
FLOWFLOW
Typical CIRCULATION (CASE)Typical CIRCULATION (CASE)
RELIEF VALVE Assembly – TheRELIEF VALVE Assembly – The
valve must be installedvalve must be installed
(VERTICALLY)(VERTICALLY) on the pumpon the pump
discharge before the dischargedischarge before the discharge
check valve NFPA 20 (5.11.1.2)check valve NFPA 20 (5.11.1.2)
34. STATE of OHIO FIRE SCHOOL - BGSU 34
NFPANFPA
2020
NOTE :NOTE :
AutomaticAutomatic
air releaseair release
valvevalve
installedinstalled
35. STATE of OHIO FIRE SCHOOL - BGSU 35
!!
(5.14)(5.14)
Elbows and tees with a centerlineElbows and tees with a centerline
plane parallel to a horizontal split-caseplane parallel to a horizontal split-case
pump shaft shall be avoided. Seepump shaft shall be avoided. See
Figure A-2-9.6. (5.14.6.3.1)Figure A-2-9.6. (5.14.6.3.1)
If there is a parallel elbow : YOUIf there is a parallel elbow : YOU
MUST HAVE 10 PIPE DIAMETERSMUST HAVE 10 PIPE DIAMETERS
of STRAIGHT PIPE BETWEEN THEof STRAIGHT PIPE BETWEEN THE
ELBOW AND PUMP SUCTIONELBOW AND PUMP SUCTION
FLANGE (5.14.6.3.2)FLANGE (5.14.6.3.2)
PIPE SIZE ?PIPE SIZE ?
NFPA 20NFPA 20
(5.14.3.4)(5.14.3.4)
36. STATE of OHIO FIRE SCHOOL - BGSU 36
NFPA 20NFPA 20
2-9.6.42-9.6.4
(5.14.6.4)(5.14.6.4)
38. STATE of OHIO FIRE SCHOOL - BGSU 38
NFPA 20 2-9.6.3NFPA 20 2-9.6.3 Elbows and teesElbows and tees
with a centerlinewith a centerline
plane parallel toplane parallel to
a horizontala horizontal
split-case pumpsplit-case pump
shaft shall beshaft shall be
avoided. Seeavoided. See
Figure A-2-9.6.Figure A-2-9.6.
SUCTIONSUCTION
(5.14.6.3.1)(5.14.6.3.1)
39. STATE of OHIO FIRE SCHOOL - BGSU 39
CORRECTED !!!CORRECTED !!!
NOTE: No ELBOWSNOTE: No ELBOWS
40.
41. STATE of OHIO FIRE SCHOOL - BGSU 41
OSYOSY
SuctionSuction
ValveValve
NOTE: Backflow Preventer!
NOTE: The long straight run of
suction pipe after a
HORIZONTAL 90 DEGREE
ELBOW !
More than 10 pipe diameters ?
(5.14.6.3.2)
43. STATE of OHIO FIRE SCHOOL - BGSU 43
SUCTIONSUCTION
DISCHARGEDISCHARGE
Is this HSC verticalIs this HSC vertical
installationinstallation
“REALLY” a space“REALLY” a space
saver ??saver ??
IS IT CORRECT ??IS IT CORRECT ??
OK ?OK ?
NFPA 20NFPA 20
(5.14.6.3.1)(5.14.6.3.1)
44. STATE of OHIO FIRE SCHOOL - BGSU 44
NOTE: BackflowNOTE: Backflow
Preventer on DISCHARGEPreventer on DISCHARGE
side of Pump !! (5.26)side of Pump !! (5.26)
(5.14.9)(5.14.9)
PUMPPUMP
SuctionSuction
City By-Pass
City By-Pass
NOTE : Left HandNOTE : Left Hand
Rotation ! *Rotation ! *
Counter Clockwise !Counter Clockwise !
CONFIRMCONFIRM
BEFOREBEFORE you orderyou order
the PUMP !!the PUMP !!
NFPA 20 (5.22)NFPA 20 (5.22)
Study andStudy and
understand theunderstand the
piping !piping !
Ask questionsAsk questions
if you are notif you are not
sure !sure !
#2#2
46. NOTE: Test Header Piping isNOTE: Test Header Piping is
Connected Between theConnected Between the
Pump Discharge Check ValvePump Discharge Check Valve
and the Discharge (System)and the Discharge (System)
Shut - Off Valve.Shut - Off Valve.
NFPA 20 (A.5.19.3.1)NFPA 20 (A.5.19.3.1)
Test HeaderTest Header
Control ValveControl Valve
and Pipingand Piping
City Water By-Pass
City Water By-Pass
What is the SUPPLY Voltage ?What is the SUPPLY Voltage ?
Is a Transfer Switch required ?Is a Transfer Switch required ?
DOUBLE CHECK andDOUBLE CHECK and CONFIRMCONFIRM
BEFOREBEFORE you order the pumpyou order the pump
#3#3
47. Test Header
Control
Valve and
Piping
NOTE : No drain valve onNOTE : No drain valve on
bottom of test head pipe !bottom of test head pipe !
NFPA 20 (5.19.3.3.1)NFPA 20 (5.19.3.3.1)
FLOWFLOW
48. FIRE PUMP TESTFIRE PUMP TEST
CONNECTIONCONNECTION
(5.19.3)(5.19.3)
What hose threads areWhat hose threads are
required on the hose valvesrequired on the hose valves
in your jurisdiction ?in your jurisdiction ?
CHECK and CONFIRMCHECK and CONFIRM
beforebefore you order theyou order the
pump ! NFPA 20pump ! NFPA 20
(5.19.3.2)(5.19.3.2)
#4#4
49. Fire Pump TestFire Pump Test
HeadHead
Must be located where the
motor and controller will
not be damaged by
spraying or splashing
water.
Preferably outside ofPreferably outside of
the pump house or thethe pump house or the
pump room !pump room !
NFPA 20 (A.5.19.3.1)NFPA 20 (A.5.19.3.1)
FIREFIRE
PUMPPUMP
TESTTEST
HEADHEAD
50. STATE of OHIO FIRE SCHOOL - BGSU 50
NFPA 20 A-2-14.3.1NFPA 20 A-2-14.3.1
(A.5.19.3.1)(A.5.19.3.1)
TESTHEAD??TESTHEAD??
HOSE/TESTVALVESHOSE/TESTVALVES
51. STATE of OHIO FIRE SCHOOL - BGSU 51FALK Steel Flex – APPROVED ??FALK Steel Flex – APPROVED ??
What coupling will beWhat coupling will be
accepted by LAHJ ?accepted by LAHJ ? FINDFIND
OUTOUT ! ASK ! “UL”! ASK ! “UL”
Listed ?? NFPA 20 (6.5)Listed ?? NFPA 20 (6.5)
#5#5
52. STATE of OHIO FIRE SCHOOL - BGSU 52
Drive Shaft – APPROVED ?Drive Shaft – APPROVED ?
56. LOOSE SET-SCREWS ????LOOSE SET-SCREWS ????
DO NOT USE Elastomer
Couplings ON UL/FM
FIRE PUMPS !
< FM> 9-2006< FM> 9-2006
IRI Bulletin 91-9IRI Bulletin 91-9
57. STATE of OHIO FIRE SCHOOL - BGSU 57
TB WoodsTB Woods
ElastomerElastomer
CouplingCoupling
58. Diesel DrivenDiesel Driven
HSC Fire PumpsHSC Fire Pumps
Engine HP De-rateEngine HP De-rate (11.2.2)(11.2.2) **
3% for every 1000’3% for every 1000’ ALT.ALT. above 300’above 300’
1% for every 10 degrees (F) above 771% for every 10 degrees (F) above 77
#6#6
60. NOTE : With a PLDNOTE : With a PLD
All pump dischargeAll pump discharge
fittings,fittings, TOTO andand
including theincluding the
system shut offsystem shut off
valve, must bevalve, must be
rated for therated for the
MAXIMUMMAXIMUM
discharge (CHURN)discharge (CHURN)
100 PSI100 PSI
170 PSI170 PSI
240 PSI240 PSI
FOR TESTINGFOR TESTING
(14.2.7.3.7.3)(14.2.7.3.7.3)
62. System Relief Valve is
Required when a Variable
Speed – OR --
Pressure Limiting Driver
is used (5.18.1.3 ) *
-------also---------
Required when
diesel fire pump churn
pressure X 1.21 (plus
maximum static suction)
exceeds the maximum
working pressure of the
system components
NFPA 20 (5.18.1.1) *
##77 REQUIRED ?REQUIRED ?
63. STATE of OHIO FIRE SCHOOL - BGSU 63
(5.18.1.1)(5.18.1.1)
NOTE:NOTE: ThisThis
Pump did notPump did not
require a mainrequire a main
relief valve sincerelief valve since
the sum of thethe sum of the
churn pressurechurn pressure
times 121%times 121%
plus the max.plus the max.
suction pressuresuction pressure
is only 142 PSI.is only 142 PSI.
No ReliefNo Relief
Valve ?Valve ?
64. NOTE: FlexibleNOTE: Flexible
Dresser PipeDresser Pipe
Couplings to allow forCouplings to allow for
tank settling!tank settling!
( A.5.17 )( A.5.17 )
WaterWater
supply issupply is
from afrom a
groundground
storagestorage
tanktank
Combustion Air LouverCombustion Air Louver
NOTE: ReliefNOTE: Relief
valve is piped tovalve is piped to
waste outsidewaste outside
of buildingof building
(5.18.6)(5.18.6)
(A.5.18.5)(A.5.18.5)
Relief valve discharge isRelief valve discharge is
permitted to be pipedpermitted to be piped
back to the above groundback to the above ground
storage tank (5.18.6.3)storage tank (5.18.6.3)
Note: Packing drainNote: Packing drain
lines run to a floorlines run to a floor
drain.(5.12.6.2)drain.(5.12.6.2)
65. STATE of OHIO FIRE SCHOOL - BGSU 65
When PumpWhen Pump
MaximumMaximum
DischargeDischarge
Pressure isPressure is
evaluatedevaluated
with the 121with the 121
% rule% rule
NFPA 20NFPA 20
(A.5.18.1)(A.5.18.1)
66. STATE of OHIO FIRE SCHOOL - BGSU 66
Relief Valve Waste
Relief Valve Waste
(5.18.6)
(5.18.6)
Engine CoolingEngine Cooling
Water PipingWater Piping ––
NFPA 20 (11.2.6.3)NFPA 20 (11.2.6.3)
NOTE: System (Main) Relief Valve (if
used) is connected to the pump
discharge BEFORE the Discharge
Check Valve !! (5.18.3)
(5.18.5)(5.18.5)
67. STATE of OHIO FIRE SCHOOL - BGSU 67
Where the cooling water contains
foreign material such as leaves, grass,
wood chips, etc – duplex filter type
strainers should be provided.
NFPA 20 (A.11.2.6.4)
68.
69. ENGINE coolingENGINE cooling
waste waterwaste water
MUST be piped soMUST be piped so
the flow can bethe flow can be
VISUALLYVISUALLY
observed andobserved and
confirmed.confirmed.
The dischargeThe discharge
pipe MUST be atpipe MUST be at
least one sizeleast one size
larger than thelarger than the
inlet.inlet.
NFPA 20NFPA 20
(11.2.6.6)(11.2.6.6)
71. EMERGENCY MANUAL STARTINGEMERGENCY MANUAL STARTING
PROCEDURE - NFPA 20 (11.6.6)PROCEDURE - NFPA 20 (11.6.6)
CC = Cooling Water= Cooling Water
FF = Fuel= Fuel
CC = Crank= Crank
72. #1#1
CCOOLINGOOLING
WATERWATER
#2#2
FFUELUEL
# 3# 3
CCRANKRANK
NOTE !NOTE !
SET at 120 % of
Rated RPM *****
EMERGENCYEMERGENCY
MANUALMANUAL
STARTINGSTARTING
PROCEDUREPROCEDURE
(11.6.6)(11.6.6)
BE SURE THAT YOU
KNOW WHERE
THE OVERSPEED
RESET IS ON
EVERY TYPE OF
ENGINE THAT YOU
SELL or INSTALL !!
INSTRUCT THE
OWNER’S
REPRESENTATIVE
OR OPERATOR.
CUMMINS
73. ## 11 For EMERGENCYFor EMERGENCY
OPERATION of “ANY ENGINE”OPERATION of “ANY ENGINE”
the by-passthe by-pass ANDAND normalnormal
COOLING WATER VALVES mustCOOLING WATER VALVES must
ALL be - OPEN !ALL be - OPEN !
74. STATE of OHIO FIRE SCHOOL - BGSU 74
##33 CRANKCRANK
BATTERY 1 or 2BATTERY 1 or 2
#2#2
With Newer Engines, the toggle switch, when inWith Newer Engines, the toggle switch, when in MANUALMANUAL
will turn on bothwill turn on both FUELFUEL andand COOLING WATERCOOLING WATER
75. NFPA 20 (11.5.3)NFPA 20 (11.5.3)
Exhaust pipesExhaust pipes
shall be installedshall be installed
with clearances ofwith clearances of
at least 9” toat least 9” to
combustiblecombustible
material.material.
Insulate or guard exhaustInsulate or guard exhaust
pipe???pipe???
78. Exhaust FanExhaust Fan andand Air Intake LouverAir Intake Louver
NFPA 20NFPA 20
(11.3.2.4)(11.3.2.4)
NFPA 20NFPA 20
(11.3.2.3)(11.3.2.3)
MAX 120MAX 120
degrees Fdegrees F
79. NOTE : UL Listed tanks mustNOTE : UL Listed tanks must
have a metal “ UL ”have a metal “ UL ”
nameplate attached to thenameplate attached to the
tank !tank !
LOOK FOR IT !LOOK FOR IT !
(12.4.1.3 - 11) Tank must(12.4.1.3 - 11) Tank must
be kept 2/3 full !be kept 2/3 full !
FuelFuel
ReturnReturn
81. FUEL Tank DrainsFUEL Tank Drains
NFPA 20NFPA 20
A-8-4.6 (A.11.4.6)A-8-4.6 (A.11.4.6)
Top 5%Top 5% andand bottom 5% ofbottom 5% of
tank volume is not used intank volume is not used in
determining capacity of tank.determining capacity of tank.
NFPA 20 8-4.3 (11.4) *NFPA 20 8-4.3 (11.4) *
Bottom 5%Bottom 5%
82. Fuel Supply ValveFuel Supply Valve
locked in OPENlocked in OPEN
position …NFPA 20position …NFPA 20
A-8-4.6 (A.11.4.6)A-8-4.6 (A.11.4.6)
NEW: 2003NEW: 2003
NFPA 20NFPA 20
(11.4.6.2)(11.4.6.2)
Fuel linesFuel lines
no copperno copper
oror
galvanizedgalvanized
The fuel supplyThe fuel supply
opening to the engineopening to the engine
shall be no lowershall be no lower
than the engine fuelthan the engine fuel
pump centerline.pump centerline.
NFPA 20 (11.4.5.4)NFPA 20 (11.4.5.4)
83. STATE of OHIO FIRE SCHOOL - BGSU 83
Fuel tank capacity NFPA 20 (11.4.3) *
Tank location inside NFPA 20 (11.4.5.6)
Fill and vent piping NFPA 20 (11.4.5.8)
Fuel LevelFuel Level
(11.4.5.7)(11.4.5.7)
Low FuelLow Fuel
Switch *Switch *
SET AT 2/3SET AT 2/3
(12.4.1.3)(12.4.1.3)
FuelFuel
ReturnReturn
84. 10 ‘
The flash arresterThe flash arrester
should be a minimumshould be a minimum
11’- 0” above the top11’- 0” above the top
of the fuel tank NFPAof the fuel tank NFPA
20 (A.11.4.6)20 (A.11.4.6)
86. Tank Fill SHOULD BE PipedTank Fill SHOULD BE Piped
to the outsideto the outside
(A.11.4.5)(A.11.4.5)
87. Some “LAHJ” REQUIRE a containment dike,Some “LAHJ” REQUIRE a containment dike,
even when a double wall tank is provided !even when a double wall tank is provided !
CHECK and LEARNCHECK and LEARN
THE LOCAL CODES !THE LOCAL CODES !
5 PSI Hydro-test at the JOB ??5 PSI Hydro-test at the JOB ??
ToTo
EngineEngine
#8#8
89. STATE of OHIO FIRE SCHOOL - BGSU 89
ALL Pump Rooms are
Required to have a FLOOR
DRAIN!!! (5.12.6.2)
Circulation “CASE” Relief
Valve Piped To A Floor
Drain. (5.11)*
Packing Drain
Lines Run to a
Floor Drain. Do
not combine
with case relief
valve piping! !!
(5.11.1.5)
90. STATE of OHIO FIRE SCHOOL - BGSU 90
NOTE STRAINER!NOTE STRAINER!
10 pipe
10 pipedia. ??
dia. ??
NFPA 20 (6.3.4)NFPA 20 (6.3.4)
NOTE: Strainer requirementNOTE: Strainer requirement
was removed after 2007 !was removed after 2007 !
#9#9
91. STATE of OHIO FIRE SCHOOL - BGSU 91
(6.3.4) A Hand Hole is “NOT” a(6.3.4) A Hand Hole is “NOT” a
Strainer!!Strainer!! Could You Get RocksCould You Get Rocks
and Boards out of this small “and Boards out of this small “
PIPE PLUG “ opening ??PIPE PLUG “ opening ??
NO SUCTION STRAINER ?? WHY NOT ?NO SUCTION STRAINER ?? WHY NOT ?
92. Could YOU get this stuff out of a “PIPE PLUGCould YOU get this stuff out of a “PIPE PLUG
OPENING” in the bottom of an Inline Fire Pump ?OPENING” in the bottom of an Inline Fire Pump ?
Could this be why a strainer Is “REQUIRED” ?Could this be why a strainer Is “REQUIRED” ?
94. NOTE: Automatic air releaseNOTE: Automatic air release
NFPA 20 (7.3.5.2.3)NFPA 20 (7.3.5.2.3) “SHALL BE”“SHALL BE”
Located between the fire pump andLocated between the fire pump and
the discharge check valve. *the discharge check valve. *
Motor HP andMotor HP and
THRUST limitsTHRUST limits mustmust
meet or exceedmeet or exceed
those of the Firethose of the Fire
Pump.Pump. CHECK !CHECK !
(7.5.1.1) (9.5.2)(7.5.1.1) (9.5.2)
#10#10
95. STATE of OHIO FIRE SCHOOL - BGSU 95
NOTE:NOTE: Automatic air release “SHALL BE” LocatedAutomatic air release “SHALL BE” Located
in the highest point in the discharge line, betweenin the highest point in the discharge line, between
the fire pump and the discharge check valve.the fire pump and the discharge check valve. NFPANFPA
20 (7.3.5.2.3)20 (7.3.5.2.3) **
96. STATE of OHIO FIRE SCHOOL - BGSU 96
NFPA 20 (7.6.2.3)NFPA 20 (7.6.2.3)
ACCESS FOR REMOVAL ?ACCESS FOR REMOVAL ?
97. NFPA 20 ( 7.4.3.7 )NFPA 20 ( 7.4.3.7 )
I– beams must be parallelI– beams must be parallel
to the driver !to the driver !
98.
99. STATE of OHIO FIRE SCHOOL - BGSU 99
One degree of off-set is the preferredOne degree of off-set is the preferred
angle, per drive shaft manufacturers!!angle, per drive shaft manufacturers!!
NFPA 20 (6.5) (7.5.1.7.2)NFPA 20 (6.5) (7.5.1.7.2)
100. CHECK the pump HP and THRUST requirements.CHECK the pump HP and THRUST requirements.
CHECK the gear HP and THRUST limits.CHECK the gear HP and THRUST limits.
CHECK the engine HP rating.CHECK the engine HP rating.
THIS MUST BE DONE BEFORE THE PUMP ISTHIS MUST BE DONE BEFORE THE PUMP IS
ORDERED !!ORDERED !! ( 7.5.1.6.4 )( 7.5.1.6.4 )
#11#11
101. STATE of OHIO FIRE SCHOOL - BGSU 101
Top Shaft Nut isTop Shaft Nut is
used to raiseused to raise
shaft andshaft and
impellersimpellers
approximatelyapproximately
1/81/8 “ inch. (see“ inch. (see
instructioninstruction
book)book)
NFPA 20 (7.6.1.3)
102. Water Vel,
2’/sec Max
Water Vel.Water Vel.
1’/sec Max1’/sec Max
Screen openings equal to 1Screen openings equal to 1
sq. in. for every GPMsq. in. for every GPM
(pump capacity at 150%)(pump capacity at 150%)
(at LOWEST Water LEVEL)(at LOWEST Water LEVEL)
NFPA 20 (5.14.8)NFPA 20 (5.14.8)
Confirm properConfirm proper
submergencesubmergence
(Pump Length) *(Pump Length) *
(7.2.2.2)(7.2.2.2)
NFPA 20 (A.7.2.2.2) (5.14.8)NFPA 20 (A.7.2.2.2) (5.14.8)
#12#12
**
106. STATE of OHIO FIRE SCHOOL - BGSU 106
NFPA 20 2003NFPA 20 2003
Zebra Mussel InfestationZebra Mussel Infestation
(5.14.8.12)(5.14.8.12)
With a vertical turbine fireWith a vertical turbine fire
pump a plugged screen willpump a plugged screen will
affect the water level in theaffect the water level in the
sump and a plugged basketsump and a plugged basket
strainer on the bottom of thestrainer on the bottom of the
pump will reduce the totalpump will reduce the total
pump performance.pump performance.
107. VTFP INTAKE PROBLEMS………..VTFP INTAKE PROBLEMS………..
Removable screens NFPA 20 A4-2.2.2 (5.14.8.3)(5.14.8.3)
Intake size ???Intake size ??? NFPA 20 A4-2.2NFPA 20 A4-2.2 (5.14.8.4)(5.14.8.4)
2 ft/sec and2 ft/sec and
1 Sq. Inch per1 Sq. Inch per
GPM atGPM at
150% Flow ?150% Flow ?
110. PART 2PART 2
FIRE PUMPFIRE PUMP
Acceptance TestingAcceptance Testing
In The State ofIn The State of
OHIOOHIO
111. FIRE PUMPFIRE PUMP ACCEPTANCE TESTACCEPTANCE TEST
1. Check for company and individual LICENSING.1. Check for company and individual LICENSING.
2. Check for HYDRO and FLUSHING CERTIFICATES.2. Check for HYDRO and FLUSHING CERTIFICATES.
3. Check for CERTIFIED shop test curve vs. SYSTEM DEMAND.3. Check for CERTIFIED shop test curve vs. SYSTEM DEMAND.
4. Has the pump been properly ALIGNED and PRE-TESTED???4. Has the pump been properly ALIGNED and PRE-TESTED???
5. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)5. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)
6. Look system over…sensing lines, reducers, piping , water supply….6. Look system over…sensing lines, reducers, piping , water supply….
7. Check for CERTIFICATE of CALIBRATION for test equip. (SAFE??)7. Check for CERTIFICATE of CALIBRATION for test equip. (SAFE??)
8. Decide in advance just what is to take place during the test8. Decide in advance just what is to take place during the test
9. Operate the pump at churn (no flow)….temp., brgs., packing, etc.9. Operate the pump at churn (no flow)….temp., brgs., packing, etc.
10. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).10. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).
11. Operate the pump at additional flow points 50%, 100%, 150%,.11. Operate the pump at additional flow points 50%, 100%, 150%,.
12. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).12. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).
13. 6 AUTO Starts and 6 MANUAL Starts. (One Full Load Start)13. 6 AUTO Starts and 6 MANUAL Starts. (One Full Load Start)
14. Controller and Driver alarms connected / tested (electric and diesel)14. Controller and Driver alarms connected / tested (electric and diesel)
15. Start and Stop PSI for Main Fire Pump and Jockey Pump.15. Start and Stop PSI for Main Fire Pump and Jockey Pump.
16. Low Suction Control Set Point AND Alarm Connected???16. Low Suction Control Set Point AND Alarm Connected???
17. Operators trained in maintenance and weekly testing???17. Operators trained in maintenance and weekly testing???
18. Review test results - ASK QUESTIONS!!!!!! Do it again ???18. Review test results - ASK QUESTIONS!!!!!! Do it again ???
19. STOP!!!! Don’t accept it if the data is not CORRECT!!!!19. STOP!!!! Don’t accept it if the data is not CORRECT!!!!
112. 1. Check for company and1. Check for company and
individual LICENSING asindividual LICENSING as
REQUIRED by STATE orREQUIRED by STATE or LAHJLAHJ..
CHECK EVERYONE who touches the
equipment…pump guy, fitters, controller
guy, and engine guy!!! They all must have
a license to service, test, repair, or install
any fire protection equipment in the State
of Ohio.
Compare with driver’s license…..
Check every year…..
RECORD the information…….
113. RECORD NAMES OF ALL FIELDRECORD NAMES OF ALL FIELD
ACCEPTANCE TEST PERSONNELACCEPTANCE TEST PERSONNEL
(LAHJ)(LAHJ) FIRE DEPT OFFICIALFIRE DEPT OFFICIAL
OWNER’S REPRESENTATIVEOWNER’S REPRESENTATIVE
MAINTENANCE PERSONNELMAINTENANCE PERSONNEL
INSTALLING CONTRACTORINSTALLING CONTRACTOR
AUTHORIZED FIRE PUMP REPAUTHORIZED FIRE PUMP REP
AUTHORIZED CONTROLLER REPAUTHORIZED CONTROLLER REP
AUTHORIZED ENGINE REPAUTHORIZED ENGINE REP
INSURANCE REPRESENTATIVEINSURANCE REPRESENTATIVE
115. 1.1. Check for HYDRO andCheck for HYDRO and
FLUSHING CERTIFICATES.FLUSHING CERTIFICATES.
NFPA 20 11-1.1 (14.1)
Was the UUnderground and AAboveground piping
installed, flushed, and hydro-tested by a “Licensed”
contractor ?
Did “YOU”“YOU” witness flushing and hydro-test??
Did installing contractor “OFFER” to have you witness
the above and provide you with the mandatory test
certificates …… NFPA 20 11-1.3 (14.1.3)
Someone had to sign and witness (WHO ??)(WHO ??)
NO TEST CERTIFICATES???? WHY NOT???
NFPA 20 (14.1.3)
What happens when the pump plugs with rocks or a
pipe fitting blows apart?????
116.
117. Table (14.1.1.1[a])Table (14.1.1.1[a]) Minimum Flush RatesMinimum Flush Rates..
Contractor may have a calculated systemContractor may have a calculated system
demand which, if greater, will require higherdemand which, if greater, will require higher
flush rates than those listed below.flush rates than those listed below.
Pipe SizePipe Size Flow RateFlow Rate
in.in. mmmm gpmgpm L/minL/min
44 102102 590590 2,2332,233
66 152152 1,3601,360 5,1485,148
88 203203 2,3502,350 8,8958,895
1010 254254 3,6703,670 13,89113,891
1212 305305 5,2905,290 20,02320,023
NFPA 20 (14.1.1.1) FLUSHINGNFPA 20 (14.1.1.1) FLUSHING
119. System was flushed for 2 hours with 3 hoses !System was flushed for 2 hours with 3 hoses !
Problem : Hoses were ¾” garden hoses !!!Problem : Hoses were ¾” garden hoses !!!
120.
121. 3. Check for PUMP CERTIFIED
SHOP TEST CURVE. Compare
it to the SYSTEM DEMAND.
NFPA 20 2-162-16 and 11-2.3 (14.2.4)
Find out how many GPM are required and
how much PSI is needed to make the
sprinkler system work… Will the fire
pump and water supply do it ?
Fire Pumps are selected for “SYSTEM
DESIGNS” which can utilize any pump
flow up to 150% of rated capacity.
NFPA 20 2-3 and A-2-3 (5.8)
123. 4. Has the Pump and Driver4. Has the Pump and Driver
been ALIGNED, LUBRICATED,been ALIGNED, LUBRICATED,
and PRE-TESTED???and PRE-TESTED???
Pump and driver MUSTMUST be field-aligned
NFPA 20 3-5 (6.5.2) and pre-tested PRIORPRIOR to
the field acceptance test - includes electricalincludes electrical
NFPA 20 (14.2.3)NFPA 20 (14.2.3) so that inspector’s time is
not wasted standing around…….. MANY
jurisdictions charge an additional fee if re-
testing is required due to problems with a
system which has not been pre-tested prior
to the acceptance test!!!!
126. STATE of OHIO FIRE SCHOOL - BGSU 126
GAP MUST BEGAP MUST BE
EQUAL - TOP TOEQUAL - TOP TO
BOTTOM ANDBOTTOM AND
SIDE TO SIDE.SIDE TO SIDE.
Within .005”Within .005”
USE OF DIALUSE OF DIAL
INDICATORS ORINDICATORS OR
LASERS ISLASERS IS
PREFERRED.PREFERRED.
AngularAngular
AlignmentAlignment
127. STATE of OHIO FIRE SCHOOL - BGSU 127
Parallel alignment should be less than .005Parallel alignment should be less than .005
“VERTICAL and HORIZONTAL”“VERTICAL and HORIZONTAL”
NOTE : TheNOTE : The
coupling halvescoupling halves
should remainshould remain
disconnecteddisconnected
until rotationuntil rotation
has beenhas been
checked!checked!
128. STATE of OHIO FIRE SCHOOL - BGSU 128
AFTERAFTER alignment andalignment and
rotation have beenrotation have been
checked the couplingchecked the coupling
should be lubricatedshould be lubricated
and re-assembled.and re-assembled.
Be sure to check theBe sure to check the
set screws forset screws for
tightnesstightness
FALKFALK
SteelflexSteelflex
CouplingCoupling
129. After checking the alignment, leave the pump and
driver uncoupled until after rotation check !
Pump rotation should be checked with the
coupling notnot connected……..**
Pump was 6 % Low.
4 Year Old4 Year Old
PumpPump
131. STATE of OHIO FIRE SCHOOL - BGSU 131
NOTE: The quarter on aNOTE: The quarter on a
properly installed, grouted,properly installed, grouted,
aligned, and lubricatedaligned, and lubricated
fire pump!!!fire pump!!!
125 HP, 1760 RPM Motor -125 HP, 1760 RPM Motor -
in operationin operation,,
NO VIBRATION !NO VIBRATION !
NFPA 20 ( 14.2.6 )NFPA 20 ( 14.2.6 )
132. Add GreaseAdd Grease
slowly !slowly !
Check ForCheck For
Excess GreaseExcess Grease
After greasing beAfter greasing be
sure to checksure to check
torque of ALLtorque of ALL boltsbolts
andand set screws !set screws !
133. NOTE:NOTE: InsertInsert
clean greaseclean grease
slowly until oldslowly until old
grease is forcedgrease is forced
out of the drainout of the drain
hole withhole with PLUGPLUG
REMOVED !!REMOVED !!
NOTE : Operate theNOTE : Operate the
pump for 15 – 30 min.pump for 15 – 30 min.
before replacing thebefore replacing the
plug !plug !
134. Motor oil full ?Motor oil full ?
Check it !Check it !
Gear oil full ?Gear oil full ?
Check it !Check it !
What oil did they use ??What oil did they use ??
ASK !!ASK !!
135. Coolant level full ?Coolant level full ?
Engine LubeEngine Lube
Oil andOil and
CoolantCoolant
Checked ?Checked ?
Engine Guy ?Engine Guy ?
136. STATE of OHIO FIRE SCHOOL - BGSU 136
HAS THE PUMPHAS THE PUMP
BEEN PRE-TESTED ??BEEN PRE-TESTED ??
Is it required ?Is it required ?
137. 5.5. RECORDRECORD all equipment data:all equipment data:
pump, driver, and controller. (HP,pump, driver, and controller. (HP,
RPM, VOLTAGE, SN, etc.)RPM, VOLTAGE, SN, etc.)
Are the fire pump, driver, and controller
ALL “ULUL” listed or “FMFM” approved????
CHECK THE NAME PLATES !!!CHECK THE NAME PLATES !!!
Motor and controller voltage and HP must
be the same!!! 200 volt is “not” the same
as 230 volt!!! The required pump HP must
not exceed the driver rated HP X 1.15 SF!!!
140. STATE of OHIO FIRE SCHOOL - BGSU 140
Incoming Power SupplyIncoming Power Supply (voltage) MUST(voltage) MUST
Be the “SAME” as the Main Fire PumpBe the “SAME” as the Main Fire Pump
Controller “AND” the UL Listed Fire PumpController “AND” the UL Listed Fire Pump
MotorMotor !! NFPA 20 (9.1.3)NFPA 20 (9.1.3)
NFPA 70 Article 695NFPA 70 Article 695 CHECK IT !!*CHECK IT !!*
141. THE AVAILABLE POWER MUSTTHE AVAILABLE POWER MUST
MATCH THE FIRE PUMP MOTORMATCH THE FIRE PUMP MOTOR
NAMEPLATE AND CONTROLLERNAMEPLATE AND CONTROLLER
NAMEPLATE VOLTAGES - LOOK FORNAMEPLATE VOLTAGES - LOOK FOR
CHANGED OR ALTEREDCHANGED OR ALTERED
NAMEPLATES THAT ATTEMPT TONAMEPLATES THAT ATTEMPT TO
COVER UP A MISTAKE !!!!COVER UP A MISTAKE !!!!
**
142. **
NFPA 20 (10.3.4.4)NFPA 20 (10.3.4.4)
Means shall be provided onMeans shall be provided on
the exterior of thethe exterior of the
controller for measuring allcontroller for measuring all
line amps and volts.line amps and volts.
143. Is it “Is it “SAFESAFE”? Is it “CORRECT”?”? Is it “CORRECT”?
Power, sensing lines, reducers,Power, sensing lines, reducers,
UL/FM piping , water supplyUL/FM piping , water supply.
Jockey and main fire pump must each have a separate ½ “
sensing line with 2 ea. 3/32 “ orifices located at least 5’ – 0”
apart . `NFPA 20 7-5.2.1 and appendix!! (10.5.2.1.6)NFPA 20 7-5.2.1 and appendix!! (10.5.2.1.6)
Case relief valve (electric fire pumps) piped to a REQUIREDREQUIRED
floor drain inin the pump room??? NFPA 20 2-6.1 and 2-7.6
(5.12.6.2)
Do not pipe Case Relief Valve discharge and Packing Drain lines
together into a common drain line (5.11.1.5)
Pump coupling and guard secured???
144. IS THIS A CONFINED SPACE????IS THIS A CONFINED SPACE????
Is the “TEST SET UP” (test hoses, rack,Is the “TEST SET UP” (test hoses, rack,
and play pipes) pump location “and play pipes) pump location “SAFE”SAFE”??
145. WouldWould
““YOUYOU” go” go
down heredown here
to test thisto test this
pump????pump????
OSHA APPROVED ???OSHA APPROVED ???
NFPA 25 4.7.1NFPA 25 4.7.1
and A.4.8and A.4.8
( A.5.12) DRAINAGE and VENTILATION( A.5.12) DRAINAGE and VENTILATION
))
146. STATE of OHIO FIRE SCHOOL - BGSU 146
Note : Rods onNote : Rods on
transition piece!!transition piece!!
NOTE : This fire pump
develops 165 psi at churn !
The class 125 fittings are
good for a maximum
working pressure of 175 psi.
(5.7.4.1)
147. STATE of OHIO FIRE SCHOOL - BGSU 147
NO RODS !!!
SAFE ??
Look at the pipe
fittings !!
This pump installation
develops 213 PSI at
churn.
A 125 lb flanged fitting
is rated at 175 PSI
maximum working
pressure !! NFPA 20
(5.7.4.1)
NFPA 13 15.1.6.1.1NFPA 13 15.1.6.1.1
148. STATE of OHIO FIRE SCHOOL - BGSU 148
TEST HEAD ??TEST HEAD ??
Test Header outsideTest Header outside
of the pump house orof the pump house or
“IN” the pump room“IN” the pump room
??
NFPA 20 (A.5.19.3.1)NFPA 20 (A.5.19.3.1)
149. STATE of OHIO FIRE SCHOOL - BGSU 149
Has the Voltage Been Checked ??Has the Voltage Been Checked ??
Check NFPA 70E and NFPA 25 A.4.8Check NFPA 70E and NFPA 25 A.4.8
WHERE DOES THE POWER COME FROM ?WHERE DOES THE POWER COME FROM ?
IS THERE ANOTHER DISCONNECT ORIS THERE ANOTHER DISCONNECT OR
FUSES ???FUSES ???
PRESSUREPRESSURE
RECORDERRECORDER
150. Each “Fire Pump” Controller MUST have IT’SEach “Fire Pump” Controller MUST have IT’S
OWN Pressure Sensing Line and PressureOWN Pressure Sensing Line and Pressure
RecorderRecorder
NFPA 20 (10.5.2.1.6) and (12.5.2.1.6) *NFPA 20 (10.5.2.1.6) and (12.5.2.1.6) *
151. NOTE: Main fire pumpNOTE: Main fire pump
controller sensing line iscontroller sensing line is
connected between theconnected between the
pump discharge checkpump discharge check
valve and the system shutvalve and the system shut
- off valve. (10.5.2.1.6)- off valve. (10.5.2.1.6)
152. NFPA 20 10.5.2.1*NFPA 20 10.5.2.1*
One sensing lineOne sensing line
Two (2) CONTROLLERS ??Two (2) CONTROLLERS ??
NFPA 20NFPA 20
(10.5.2.1.6)(10.5.2.1.6)
PressurePressure
RecorderRecorder
MISSING!MISSING!
153. One sensing line for 3 controllers ??One sensing line for 3 controllers ??
154. Pressure RecorderPressure RecorderEach fire pump controller must have it’s own recorder !!Each fire pump controller must have it’s own recorder !! (10.5.2.1.6)(10.5.2.1.6)
155. *On the pump suction, a listed OSY valve is
required: no valve, other than a listed OSY valve
is allowed within 50 feet of the pump suction
flange NFPA 20 (5.14.5.2)*
*When located in the suction pipe of a fire pump,
back flow prevention devices, check valves, and
pipeline strainers (for in-line pumps) shall be noshall be no
closer than 10 pipe diameters from the pumpcloser than 10 pipe diameters from the pump
suction flangesuction flange. NFPA 20 (5.14.6.3.1) (5.26.3)*
156. STATE of OHIO FIRE SCHOOL - BGSU 156
NOTE ROTATION ?NOTE ROTATION ?
Counter-ClockwiseCounter-Clockwise
LEFT Hand *LEFT Hand *
Impeller TurnsImpeller Turns
Toward The Suction !Toward The Suction !
Have The WireHave The Wire
Connections BeenConnections Been
Checked By theChecked By the
Electrician and/orElectrician and/or
Controller Guy ?Controller Guy ?
SUCTION
OSYOSY
ValveValve
157. STATE of OHIO FIRE SCHOOL - BGSU 157
!!
(5.14.6.4)(5.14.6.4)
Elbows and tees with a centerlineElbows and tees with a centerline
plane parallel to a horizontal split-caseplane parallel to a horizontal split-case
pump shaft shall be avoided. Seepump shaft shall be avoided. See
Figure A-2-9.6. (5.14.6.3.1)Figure A-2-9.6. (5.14.6.3.1)
If there is a parallel elbow : YOUIf there is a parallel elbow : YOU
MUST HAVE 10 PIPE DIAMETERSMUST HAVE 10 PIPE DIAMETERS
of STRAIGHT PIPE BETWEEN THEof STRAIGHT PIPE BETWEEN THE
ELBOW AND PUMP SUCTIONELBOW AND PUMP SUCTION
FLANGE (5.14.6.3.2)FLANGE (5.14.6.3.2)
158. STATE of OHIO FIRE SCHOOL - BGSU 158
OSYOSY
SuctionSuction
ValveValve
NOTE: Backflow Preventer!
NOTE: The long straight run of
suction pipe after a
HORIZONTAL 90 DEGREE
ELBOW !
More than 10 pipe diameters ?
(5.14.6.3.2)
160. Batteries Properly Connected andBatteries Properly Connected and
Electrolyte Topped Off ?? USE CAUTIONElectrolyte Topped Off ?? USE CAUTION
WHEN FILLING AND CONNECTINGWHEN FILLING AND CONNECTING
LEAD ACID BATTERIES !!!LEAD ACID BATTERIES !!!
DualDual
BatteriesBatteries
Have The Wire Connections been
Checked at “BOTH”“BOTH” The Engine and
Controller ???
Wires Correct and Terminals “TIGHT”Wires Correct and Terminals “TIGHT”
161. DO NOT USE FORKEDDO NOT USE FORKED
CONNECTORS FM F27-92CONNECTORS FM F27-92
162. 7. Check for CERTIFICATE of7. Check for CERTIFICATE of
CALIBRATION for test equip.CALIBRATION for test equip.
““TEST GAUGES”TEST GAUGES” and “CLAMP-ON VOLT/AMMETERS” should be re-
calibrated and certified every 12 months (by an approved testing and
calibration facility)….Most never get calibrated and certified ! NFPA 20NFPA 20
(A.14.2.7.1)(A.14.2.7.1)
““TEST GAUGES”TEST GAUGES” will have an accuracy of;will have an accuracy of;
0.25%0.25% (ASME Grade 3A)(ASME Grade 3A)
or sometimes-
0.5%0.5% (ASME Grade 2A) pocket(ASME Grade 2A) pocket “TEST GAUGES”“TEST GAUGES” or inspectorsor inspectors
“TEST GAUGES”.“TEST GAUGES”.
DEMAND a “Certificate of Calibration” from an approved testing and
calibration facility –then- Check and Verify the Serial Numbers! If you
suspect a problem, write down the phone number of the calibration
facility and phone them!!
Look forLook for “TEST GAUGE”“TEST GAUGE” on the dial.on the dial.
163.
164. Calibrated “TEST GAUGES”Calibrated “TEST GAUGES”
plus CALIBRATIONplus CALIBRATION
DOCUMENTATION as perDOCUMENTATION as per
NFPA 20 A-11-2.6.1NFPA 20 A-11-2.6.1
(A.14.2.7.1)(A.14.2.7.1)
165.
166.
167. 8. Decide in advance just what is8. Decide in advance just what is
to take place during the testing….to take place during the testing….
WHO WILL TAKE CHARGE ?WHO WILL TAKE CHARGE ?
What test equipment will be used ?
What flow points (PITOTS) will be targeted ?
Who will do what ????
TAKE THE PITOT READINGS ?
ADJUST and HOLD THE TEST VALVES ?
TAKE PRESSURE AND RPM READINGS ?
RECORD and PLOT THE TEST RESULTS ?
TAKE THE ELECTRICAL READINGS ?
PRE RUN EQUIPMENT CHECK LIST ??PRE RUN EQUIPMENT CHECK LIST ??
168. SOMEONE HASSOMEONE HAS
TO TAKE CHARGETO TAKE CHARGE
OF THE PUMPOF THE PUMP
TEST ?TEST ?
Will It Be The SprinklerWill It Be The Sprinkler
Guy, The Local FireGuy, The Local Fire
Official, The Pump Guy,Official, The Pump Guy,
The Insurance Guy, orThe Insurance Guy, or
The Owners Rep ?The Owners Rep ?
SOMEONE HAS TOSOMEONE HAS TO
STEP UP TO THESTEP UP TO THE
PLATE !!PLATE !!
170. STATE of OHIO FIRE SCHOOL - BGSU 170
FLOW METERFLOW METER
When a flow meter isWhen a flow meter is
used, you must have anused, you must have an
air vent valve or auto airair vent valve or auto air
release valve to eliminaterelease valve to eliminate
ALLALL air from the flowair from the flow
meter piping !meter piping !
10 X D10 X D
4 X D4 X D
171. <FM> Short Play Pipe
Underwriters Play Pipe
1 ¾ ” Nozzle
1 1/8 ” Nozzle
Pitot
Tube
172. STATE of OHIO FIRE SCHOOL - BGSU 172
FREE FLOW WITH HOSES AND PLAYPIPESFREE FLOW WITH HOSES AND PLAYPIPES
173. STATE of OHIO FIRE SCHOOL - BGSU 173
Each additional pitotEach additional pitot
tube, used during thetube, used during the
test, will increase thetest, will increase the
chance for error!chance for error!
Use 1 pitot tube and 1Use 1 pitot tube and 1
gauge which hasgauge which has
been checked prior tobeen checked prior to
the start of the test!the start of the test!
175. STATE of OHIO FIRE SCHOOL - BGSU 175
In Areas where water shortages exist,In Areas where water shortages exist,
the test water can be discharged backthe test water can be discharged back
to the stored supply !to the stored supply !
176. STATE of OHIO FIRE SCHOOL - BGSU 176
THERBOLIZER 6THERBOLIZER 6
177. STATE of OHIO FIRE SCHOOL - BGSU 177
Test HeaderTest Header
arranged to SAFELYarranged to SAFELY
discharge directly todischarge directly to
the Pondthe Pond
179. STATE of OHIO FIRE SCHOOL - BGSU 179
AA
BB
CC
. .
.
““CHURN”CHURN”
PressurePressure
“RATED 100% FLOW “ 1
Hose, Pitot of 32 PSI
“ 150 % FLOW “
2 Hoses, Pitots
of 18 PSI
What Flow Points Will Be Targeted?What Flow Points Will Be Targeted?
181. To determineTo determine
FEET of HEADFEET of HEAD
multiplymultiply (H)(H)
(net PSI) X 2.31*(net PSI) X 2.31*
To determine (H)To determine (H)
(net PSI)(net PSI) subtractsubtract
Suction PSISuction PSI fromfrom
Discharge PSIDischarge PSI
150 PSI150 PSI
50 PSI50 PSI
100 PSI100 PSI
231’ (ft)231’ (ft)
Who will observeWho will observe
and record theand record the
test results ??test results ??
182. STATE of OHIO FIRE SCHOOL - BGSU 182
WHO Will Take The
Pitot Readings ??
Does that person know
the CORRECT Procedure ?
183. To Obtain aTo Obtain a
CorrectCorrect
PressurePressure
Reading With AReading With A
Pitot Tube, ItPitot Tube, It
“MUST” Be“MUST” Be
Held In TheHeld In The
Center of TheCenter of The
Flow StreamFlow Stream
And It “MUST”And It “MUST”
Be KeptBe Kept
PerpendicularPerpendicular
To the FlowTo the Flow
StreamStream
184. STATE of OHIO FIRE SCHOOL - BGSU 184
Hold The HOSE TEST VALVES After theHold The HOSE TEST VALVES After the
Pitot Readings have been obtained.Pitot Readings have been obtained.
Will These Hose Valves Vibrate or Chatter Open ?Will These Hose Valves Vibrate or Chatter Open ?
185. NFPA 70E andNFPA 70E and
OSHAOSHA 1910.3331910.333
OnlyOnly “QUALIFIED”“QUALIFIED”
persons arepersons are
permitted to work onpermitted to work on
or near “LIVE”or near “LIVE”
exposed parts ofexposed parts of
electrical equipment.electrical equipment.
3.3. Distinguish live parts.Distinguish live parts.
(WHAT’S HOT, WHAT’S NOT ?)(WHAT’S HOT, WHAT’S NOT ?)
4.4. Determine nominal voltage andDetermine nominal voltage and
protection required.protection required.
5.5. Determine the minimumDetermine the minimum
required safe clearance or saferequired safe clearance or safe
working distances.working distances.
(4 feet / 12 inches ) *(4 feet / 12 inches ) *
ARC-FLASHARC-FLASH
12 Inches12 Inches
MINIMUMMINIMUM
NEC Digest - Feb. 2006NEC Digest - Feb. 2006
186. OSHA may cite non-compliance withOSHA may cite non-compliance with
29CFR 1910.335(a)(1)(i)29CFR 1910.335(a)(1)(i) which requireswhich requires
the use of protective equipment when workingthe use of protective equipment when working
where a potential electrical hazard doeswhere a potential electrical hazard does
exist.**exist.**
-OR--OR-
29CFR 1910.132(d)(1),29CFR 1910.132(d)(1), which requireswhich requires
employer assessment of workplace hazardsemployer assessment of workplace hazards
and the use of personal protective equipment.and the use of personal protective equipment.
These regulations are supported by NFPA 70E.These regulations are supported by NFPA 70E.
NFPA 70E, isNFPA 70E, is NOT LAWNOT LAW, however, it helps, however, it helps
employers by providing education, guidance,employers by providing education, guidance,
andand “how-to”“how-to” for compliance.for compliance.
187. CONFIRM THAT PUMP BASE IS PROPERLY GROUTEDCONFIRM THAT PUMP BASE IS PROPERLY GROUTED
CONFIRM THAT ALL EQUIPMENT IS ALIGNED AND LUBRICATEDCONFIRM THAT ALL EQUIPMENT IS ALIGNED AND LUBRICATED
CONFIRM THAT COUPLING GUARDS ARE INSTALLEDCONFIRM THAT COUPLING GUARDS ARE INSTALLED
CONFIRM CASE RELIEF, AIR RELEASE, COOLING WATER ALL CORRECTCONFIRM CASE RELIEF, AIR RELEASE, COOLING WATER ALL CORRECT
CONFIRM THAT POWER IS CORRECT and “ON”CONFIRM THAT POWER IS CORRECT and “ON”
CONFIRM THAT WATER IS AVAILABLE and “ON” (PUMP PRIMED)CONFIRM THAT WATER IS AVAILABLE and “ON” (PUMP PRIMED)
CONFIRM THAT PUMP HAS PROPER ROTATIONCONFIRM THAT PUMP HAS PROPER ROTATION
CONFIRM THAT VALVES ARE IN CORRECT POSITION FOR TESTINGCONFIRM THAT VALVES ARE IN CORRECT POSITION FOR TESTING
CONFIRM SAFE TEST SET UP (HOSES, PLAYPIPES, WATER DISPOSAL)CONFIRM SAFE TEST SET UP (HOSES, PLAYPIPES, WATER DISPOSAL)
CONFIRM THAT SYSTEM PRESSURE IS AT OR ABOVE EXPECTED FIRECONFIRM THAT SYSTEM PRESSURE IS AT OR ABOVE EXPECTED FIRE
PUMP CHURN PRESSURE (USE THE JOCKEY PUMP) -OR-PUMP CHURN PRESSURE (USE THE JOCKEY PUMP) -OR-
IT IS PREFERABLE TO ISOLATE THE SYSTEMIT IS PREFERABLE TO ISOLATE THE SYSTEM
““CLOSE THE DISCHARGECLOSE THE DISCHARGE
(SYSTEM) VALVE”(SYSTEM) VALVE”
KEEP IT CLOSED DURING FLOW TESTINGKEEP IT CLOSED DURING FLOW TESTING
! **! **
FIRE PUMP “PRE-RUN” CHECK LISTFIRE PUMP “PRE-RUN” CHECK LIST
LAST CHANCELAST CHANCE - PRIOR TO TEST- PRIOR TO TEST
190. Motor Oil Full ?Motor Oil Full ?
Check It !Check It !
LAST CHANCE !!!LAST CHANCE !!!
Gear Oil Full ?Gear Oil Full ?
Double CheckDouble Check
It !It !
What Oil Did TheyWhat Oil Did They
Use ??Use ?? ASK !!ASK !!
191. Is The Engine Oil andIs The Engine Oil and
Coolant Correct ?Coolant Correct ?
Checked By Engine GuyChecked By Engine Guy ????
BlockBlock
HeaterHeater
Working ??Working ??
120 Degrees F120 Degrees F
(11.6.5.2)(11.6.5.2)
192. NOTE : Guard Is In Place !NOTE : Guard Is In Place !
NFPA 20 (5.12.7) **NFPA 20 (5.12.7) **
NOTE : CoolingNOTE : Cooling
Water For GearWater For Gear
Connected !Connected !
Flow Visible ??Flow Visible ??
(7.5.1.6.5)(7.5.1.6.5)
195. IS THE POWER ONIS THE POWER ON ????
Has the Voltage Been CONFIRMED andHas the Voltage Been CONFIRMED and
controller digital readoutcontroller digital readout (amps/volts)(amps/volts)
compared to readings taken with acompared to readings taken with a
“CALIBRATED” hand held amp / volt“CALIBRATED” hand held amp / volt
multimeter ??multimeter ??
196. Supply “OSY” Valve OPEN, WaterSupply “OSY” Valve OPEN, Water
Available, and pump primed ??Available, and pump primed ??
NOTE ROTATION ?NOTE ROTATION ?
Clockwise / Right HandClockwise / Right Hand
Impeller Turns TowardImpeller Turns Toward
The Suction ! **The Suction ! ** SUCTION
This PumpThis Pump
Base HasBase Has
Been ProperlyBeen Properly
Grouted !Grouted !
(6.4.1)(6.4.1)
197. FIRE PUMPFIRE PUMP
TEST HEADTEST HEAD
OUTSIDE ! !OUTSIDE ! !
Hose valvesHose valves
closed andclosed and
hoseshoses
connected ?connected ?
198. Playpipes secured so water can be SAFELYPlaypipes secured so water can be SAFELY
disposed of during flow testing ??disposed of during flow testing ??
199. OPEN TestOPEN Test
Header ValveHeader ValveSystem Pressure at orSystem Pressure at or
above “EXPECTED”above “EXPECTED”
Fire Pump ChurnFire Pump Churn
Pressure -or-Pressure -or-
Discharge (System)Discharge (System)
ValveValve CLOSED DuringCLOSED During
the Flow Testthe Flow Test ??**??** 1/2” Test1/2” Test
Head DrainHead Drain
ValveValve
Closed ??Closed ??
(Bottom of(Bottom of
Test HeadTest Head
Pipe ! )Pipe ! )
Outside HoseOutside Hose
Valves Closed ??Valves Closed ??
200. TEST HEADTEST HEAD
CONTROLCONTROL
VALVE OPENVALVE OPEN
FOR TEST ???FOR TEST ???
½” TEST HEAD½” TEST HEAD
DRAIN VALVEDRAIN VALVE
CLOSED FORCLOSED FOR
TEST !TEST !
201. 9.9. Operate the pump atOperate the pump at CHURNCHURN PSIPSI
(POINT A on CURVE)(POINT A on CURVE)
Momentarily Operate the PumpMomentarily Operate the Pump - Check for- Check for
rotation, vibration, pressures, leaks, unusual sounds.rotation, vibration, pressures, leaks, unusual sounds.
Start The Pump Again:Start The Pump Again:
Check the pump for vibration, temperature,Check the pump for vibration, temperature,
case relief valve operation (Electric) or cooling watercase relief valve operation (Electric) or cooling water
flow (Diesel), bearing temp, packing leakage, pumpflow (Diesel), bearing temp, packing leakage, pump
pressures, RPM, Electrical (Controller Guy), etc.pressures, RPM, Electrical (Controller Guy), etc.
““DO NOT”DO NOT” stand in front of electrical panels or motor
junction boxes and keep the controller doors closed
during the initial starts (THINK SAFETY - 4 Foot Rule).
Note theNote the test start timetest start time… Pump must be operated for
AT LEAST ONE HOURAT LEAST ONE HOUR for “ENTIRE” acceptance test !
NFPA 20 11-2.11 ( 14.2.12 )
202. PACKING LEAKAGE: 1 – 2PACKING LEAKAGE: 1 – 2
Drops per second +/-Drops per second +/-
Adjust as Needed ¼ Turn !Adjust as Needed ¼ Turn !
Packing and bearingsPacking and bearings
SHOULD stay cool orSHOULD stay cool or
warm to the touch!!warm to the touch!!
(14.2.5)(14.2.5)
203. Case Relief ValveCase Relief Valve
“FULL” Stream“FULL” Stream
Discharge To anDischarge To an
Open Floor Drain ?Open Floor Drain ?
Packing DrainPacking Drain
Lines Piped to aLines Piped to a
Floor Drain !!Floor Drain !!
Does the pump andDoes the pump and
motor stay COOL ?motor stay COOL ?
(14.2.5)(14.2.5)
204. 10. Record10. Record ChurnChurn PSI Readings,PSI Readings,
RPM, AMPS, VOLTS,RPM, AMPS, VOLTS,
Look at the factory shop test curve and plot the
Churn Pressure in feet of headfeet of head, (no-flow POINT AA).
How close is it ???? NFPA 20 11-2.3 ( 14.2.4.2 )NFPA 20 11-2.3 ( 14.2.4.2 )
NOTE: Some pumps will require a correction for
(RPM) speed !!! NFPA 20 A-11-2.6.3 ( A.14.2.7.3.f )NFPA 20 A-11-2.6.3 ( A.14.2.7.3.f )
REMEMBER THISREMEMBER THIS - TO GET FEET OF HEAD !!- TO GET FEET OF HEAD !!
1 PSI = 2.31 FEET OF HEAD -or-1 PSI = 2.31 FEET OF HEAD -or-
.433 PSI = 1 FOOT OF HEAD.433 PSI = 1 FOOT OF HEAD
206. 11. Operate the pump at additional “TARGETED”11. Operate the pump at additional “TARGETED”
flow points : 50%, 100%,flow points : 50%, 100%,
150%, Etc.150%, Etc.
With the hose valves closed, SLOWLY open test head valve
to pressurize test head (If it is not already open and
pressurized). (DISCHARGE (SYSTEM) VALVE and TEST(DISCHARGE (SYSTEM) VALVE and TEST
HEAD DRAIN VALVE SHOULD ALREADY BE CLOSED)HEAD DRAIN VALVE SHOULD ALREADY BE CLOSED)
OpenOpen and adjustadjust appropriate number of hose valves to
obtain each targeted flow point (PITOT). You should
already know how many hose streams and what Pitot
Readings will be required to obtain “EACH” Targeted
Flow point!!
Double check pitot readings, do not allow hose valves to
vibrate open after obtaining the targeted pitot readings, and
make sure that there are “NO” kinks in the hoses !!!
NOTE: On High Pressure Systems (above 150 PSI) it may beNOTE: On High Pressure Systems (above 150 PSI) it may be
desirable todesirable to OpenOpen the proper number of hose valves and regulate thethe proper number of hose valves and regulate the
pitot pressures with thepitot pressures with the Test Header Control ValveTest Header Control Valve..
AVERAGEAVERAGE the pitot readings (NO MATTER HOW CAREFUL YOUthe pitot readings (NO MATTER HOW CAREFUL YOU
ARE, ALL OF THE PITOT READINGS WILL NOT BE THE SAME) !!ARE, ALL OF THE PITOT READINGS WILL NOT BE THE SAME) !!
207. 12. Record PSI, RPM, AMPS,12. Record PSI, RPM, AMPS,
VOLTS, (compare and plotVOLTS, (compare and plot
results on the factory curve).results on the factory curve).
Do the field test results duplicate the factory shop test curve
for EACHEACH flow point ??? NFPA 20NFPA 20 11-2.3 ( 14.2.4.2)11-2.3 ( 14.2.4.2)
If any results are “OFF” Double Check PITOT Readings?
Correct for RPM ? ( On Small Pumps check the Case Relief( On Small Pumps check the Case Relief
Valve flow. The case relief discharge flow could be as muchValve flow. The case relief discharge flow could be as much
as 5% to 10% of the rated flow of smaller pumps !! )as 5% to 10% of the rated flow of smaller pumps !! )
If Total Head (Total Head (Net PSINet PSI) is STILLSTILL low, do we need to correct
for velocity head? Triple Check PITOT Readings, hose
valves vibrating open, gauge piping plugged, RPM low???
AS A LAST RESORT : before you pull the cover to checkAS A LAST RESORT : before you pull the cover to check
for rocks - retest using a backup set of calibrated “TESTfor rocks - retest using a backup set of calibrated “TEST
GAUGES” and backup pitot tube with gauge!GAUGES” and backup pitot tube with gauge!
208. STATE of OHIO FIRE SCHOOL - BGSU 208
BB
CC
. .
.
“RATED 100% FLOW
“1 Hose, Pitot of 32 PSI
“ 150 % FLOW “
2 Hoses, Pitots
of 18 PSI
209. LOW TEST RESULTS ? WHY ?LOW TEST RESULTS ? WHY ?
Are there any kinksAre there any kinks
in the hoses??in the hoses??
Hose ValvesHose Valves
Vibrating Open ?Vibrating Open ?
Is this guy doing his job ?Is this guy doing his job ?
210. STATE of OHIO FIRE SCHOOL - BGSU 210
DidDid SomeoneSomeone Stay Outside to Adjust andStay Outside to Adjust and HoldHold
The HOSE VALVES (especially ANGLE Valves) toThe HOSE VALVES (especially ANGLE Valves) to
Keep Them From Vibrating OpenKeep Them From Vibrating Open ??
211. STATE of OHIO FIRE SCHOOL - BGSU 211
DOUBLE or TRIPLE CheckDOUBLE or TRIPLE Check
Pitot Readings !!Pitot Readings !!
CONFIRMCONFIRM Pitot GaugePitot Gauge
accuracy prior to testing !accuracy prior to testing !
212. ??
Check pitot tube andCheck pitot tube and
gauge for fouling , whichgauge for fouling , which
might occur during test?might occur during test?
213. Each additional pitotEach additional pitot
tube, used during thetube, used during the
test, will increase thetest, will increase the
chance for error!chance for error!
Use 1 pitot tube and 1Use 1 pitot tube and 1
gauge which has beengauge which has been
checked prior to thechecked prior to the
start of the test!start of the test!
Half of all fieldHalf of all field
test problemstest problems
involve theinvolve the
“USE” of, or the“USE” of, or the
“MIS-USE” of,“MIS-USE” of,
Hose MonstersHose Monsters
214. STATE of OHIO FIRE SCHOOL - BGSU 214
Calibrated Test Gauges (Calibrated Test Gauges (
liquid filled gauges areliquid filled gauges are NOTNOT Test gauges )*Test gauges )*
215. STATE of OHIO FIRE SCHOOL - BGSU 215
Gauge connectionGauge connection
piping must have a fullpiping must have a full
flow when flushedflow when flushed
(checked) PRIOR to(checked) PRIOR to
flow testing of theflow testing of the
fire pump.fire pump.
Check for anCheck for an
obstruction duringobstruction during
testing, if test resultstesting, if test results
are not correct !are not correct !
216. STATE of OHIO FIRE SCHOOL - BGSU 216
DO NOTDO NOT
connect testconnect test
gauges togauges to
case reliefcase relief
valve piping !valve piping !
217. STATE of OHIO FIRE SCHOOL - BGSU 217
On small fire pumps theOn small fire pumps the
case relief valvecase relief valve
discharge may be asdischarge may be as
much as 10% of themuch as 10% of the
rated flow - if it has notrated flow - if it has not
shut off during the test.shut off during the test.
218. STATE of OHIO FIRE SCHOOL - BGSU 218
Main system reliefMain system relief
valve must be closedvalve must be closed
for testing !**for testing !**
Failure to do so willFailure to do so will
result in low (POOR)result in low (POOR)
test results !test results !
219. STATE of OHIO FIRE SCHOOL - BGSU 219
!!
(5.14)(5.14)
Elbows and tees with a centerlineElbows and tees with a centerline
plane parallel to a horizontal split-caseplane parallel to a horizontal split-case
pump shaft shall be avoided. Seepump shaft shall be avoided. See
Figure A-2-9.6. (5.14.6.3.1)Figure A-2-9.6. (5.14.6.3.1)
If there is a parallel elbow : YOUIf there is a parallel elbow : YOU
MUST HAVE 10 PIPE DIAMETERSMUST HAVE 10 PIPE DIAMETERS
of STRAIGHT PIPE BETWEEN THEof STRAIGHT PIPE BETWEEN THE
ELBOW AND PUMP SUCTIONELBOW AND PUMP SUCTION
FLANGE (5.14.6.3.2)**FLANGE (5.14.6.3.2)**
PIPE SIZE ?PIPE SIZE ?
NFPA 20NFPA 20
(5.14.3.4)(5.14.3.4)
220.
221.
222. Curve will continueCurve will continue
to drop off as theto drop off as the
flow increasesflow increases
225. STATE of OHIO FIRE SCHOOL - BGSU 225
Top Shaft Nut isTop Shaft Nut is
used to raise shaftused to raise shaft
and impellersand impellers
approximatelyapproximately
1/81/8 “ inch. (see“ inch. (see
instruction book)instruction book)
VTFP Best Lateral Setting
LOWLOW
PERFORMANCEPERFORMANCE
MAY RESULT IFMAY RESULT IF
LATERAL IS NOTLATERAL IS NOT
CORRECT !CORRECT !
226. STATE of OHIO FIRE SCHOOL - BGSU 226
Check SubmergenceCheck Submergence
(MEASURE) how far(MEASURE) how far
downdown (feet)(feet) thethe
water level is fromwater level is from
the gauge centerthe gauge center
line,line, at each flowat each flow
point !point !
REMEMBER : ThisREMEMBER : This
must bemust be addedadded toto
the reading ( TH )the reading ( TH )
on the dischargeon the discharge
TEST GAUGE !TEST GAUGE !
WL ??WL ??
ADD +ADD +
227.
228. VTFP INTAKE PROBLEMS………..VTFP INTAKE PROBLEMS………..
Removable screens NFPA 20 A4-2.2.2 (5.14.8.3)(5.14.8.3)
Intake size ???Intake size ??? NFPA 20 A4-2.2NFPA 20 A4-2.2 (5.14.8.4)(5.14.8.4)
2 ft/sec and2 ft/sec and
1 Sq. Inch per1 Sq. Inch per
GPM atGPM at
150% Flow ?150% Flow ?
229. STATE of OHIO FIRE SCHOOL - BGSU 229
Removable screens? CheckRemovable screens? Check
for fouling (build-up) !for fouling (build-up) !
230. STATE of OHIO FIRE SCHOOL - BGSU 230
With a verticalWith a vertical
turbine fire pumpturbine fire pump
a plugged screena plugged screen
will affectwill affect
(lower)(lower) the waterthe water
level in the sump!level in the sump!
CheckCheck (measure)(measure)
the water level inthe water level in
the sump duringthe sump during
each and everyeach and every
flow point !flow point !
231. A plugged basket strainer onA plugged basket strainer on
the bottom of the pump willthe bottom of the pump will
reduce the total pumpreduce the total pump
performance.performance.
232. STATE of OHIO FIRE SCHOOL - BGSU 232
Underwater Inspection of Basket StrainerUnderwater Inspection of Basket Strainer
233.
234.
235. 13. * “6” AUTO starts
and “6” MANUAL starts *
(one “FULL LOAD” start)
When an electric fire pump is provided with an automatic
transfer switch, at least half of the starts should be performed
while the fire pump is connected to the emergency power
source (with one start under peak load). **
NFPA 20 (14.2.8) (14.2.7.4) **NFPA 20 (14.2.8) (14.2.7.4) **
NOTE: Pumps should be operated for 5 Min. for eachNOTE: Pumps should be operated for 5 Min. for each
start (This will allow the Motor and Controller time tostart (This will allow the Motor and Controller time to
Cool Down)Cool Down)
When a diesel driven fire pump is provided, the starts shall beWhen a diesel driven fire pump is provided, the starts shall be
divided between both sets of batteries.divided between both sets of batteries.
NFPA 20 (14.2.8.7)NFPA 20 (14.2.8.7)
236. 1.1. Controller and Driver alarmsController and Driver alarms
connected, tested, andconnected, tested, and
demonstrated + low suction…demonstrated + low suction…
A. Electric requires Power Available, Phase Reversal, Pump
Running, and Controller Connected to Alt. Source …..…
NFPA 20 (10.4.7.2)
(These are “TROUBLETROUBLE” or “SUPERVISORYSUPERVISORY”” alarmsalarms)
B. Diesel engine is much more involved…..* Engine Trouble -
High temp, low oil pressure, over crank - fail to start,
charger fail, battery fail, over speed, low fuel, Switch Not
in Auto, and Engine Run…….NFPA 20 (12.6.7.3)…….NFPA 20 (12.6.7.3)
(These are “TROUBLETROUBLE” or “SUPERVISORYSUPERVISORY”” alarmsalarms)
Pressure Recorder Installed / Operational ???Pressure Recorder Installed / Operational ???
EACHEACH Fire Pump Controller is required to be furnished
with a pressure recorder. (ELECTRONIC or CHART TYPE)(ELECTRONIC or CHART TYPE)
NFPA 20NFPA 20 (10.5.2.1.6 and 12.6.9.1)(10.5.2.1.6 and 12.6.9.1)
237.
238. Main Fire Pump and Jockey Pump.Main Fire Pump and Jockey Pump.
Use a “TEST GAUGE” toUse a “TEST GAUGE” to
confirm set points.confirm set points. NFPANFPA
20 A-11-2.6 (A.14.2.7)20 A-11-2.6 (A.14.2.7)
Jockey “STOP”Jockey “STOP” = Fire Pump churn pressure plus (+)
lowest static suction pressure !
Jockey “START”Jockey “START” = Jockey Stop PSI less (-) 10 PSI
Fire Pump “START”Fire Pump “START” = Jockey Start less (-) 5 –10 PSI
““MANUAL” Fire Pump “STOP”MANUAL” Fire Pump “STOP” = ( Must be used when Fire
Pump is a sole supply pump) !
- or - (if permitted by L.A.H.J.)
““AUTOMATIC” Fire Pump “STOP”AUTOMATIC” Fire Pump “STOP” = (Fire Pump churn +
lowest static suction)
239. STATE of OHIO FIRE SCHOOL - BGSU 239
Jockey
Jockey Pump
Pump
240. STATE of OHIO FIRE SCHOOL - BGSU 240
Jockey Pump Control
Jockey Pump Control
Set Jockey Pump to STOP At /OR Near The Maximum
(CHURN) Discharge Pressure of the Main Fire Pump !!
Set Jockey Pump To START at 10 - 20 PSI Less
241.
242.
243. 16. Low Suction Shut Down16. Low Suction Shut Down
Panel/Device Listed, TestedPanel/Device Listed, Tested
AND “Alarm” Connected ?AND “Alarm” Connected ?
Required by some states to protect the public water supply, when it is
used as the main water source.
Set to lock out the fire pump at 20 PSI,20 PSI, after a 30 second30 second delay -delay - withwith
manual re-set only (OHIO) and ALARM must be monitored (5.23)manual re-set only (OHIO) and ALARM must be monitored (5.23).
Must be FM or UL listed for Fire Protection Equipment –Must be FM or UL listed for Fire Protection Equipment –
not UL Industrial !!not UL Industrial !! NFPA 13 15.1.8.3
Is the “EQUIPMENT” or “DEVICE” listed in the UL or FMIs the “EQUIPMENT” or “DEVICE” listed in the UL or FM
Directory for Fire Protection EquipmentDirectory for Fire Protection Equipment ?
CHECK THE BOOK !CHECK THE BOOK !
244. -
See if you
can find this
low suction
control
listed in the
UL or FM
Directory
for Fire
Protection
Equipment
??????
245. See if you canSee if you can
find this lowfind this low
suctionsuction
“DEVICE”“DEVICE” listedlisted
in the UL or FMin the UL or FM
Directory forDirectory for FireFire
ProtectionProtection
EquipmentEquipment ????
246. Ohio EPA and Ohio Department of HealthOhio EPA and Ohio Department of Health
CHECK WITH “ YOUR” LAHJ ?CHECK WITH “ YOUR” LAHJ ?
247. Suction Control ValveSuction Control Valve
Should be locatedShould be located
between the pumpbetween the pump
discharge and thedischarge and the
discharge check valve !discharge check valve !
Sensing line for suction control valveSensing line for suction control valve
and/or low suction shut down paneland/or low suction shut down panel
should be at leastshould be at least ½”½” (Copper, 300(Copper, 300
Stainless, or Brass) and include provisionStainless, or Brass) and include provision
248. UL/FM SuctionUL/FM Suction
Control ValveControl Valve
½”½”
SuctionSuction
PressurePressure
sensingsensing
line !line !
In the State of Ohio
a UL or FM Listed
low suction shut
down control is
required to protect
a public water
supply – this is in
addition to any
suction control
valve (which may
“ALSO”“ALSO” be required
by others) .
249. 15.1.8* Connection from Waterworks System.
15.1.8.1 Where connections are made from public waterworks systems, it
might be necessary to guard against possible contamination of the public
supply.
15.1.8.2 The requirements of the public health authority having jurisdiction
shall be determined and followed.
FIND OUT WHAT “ YOUR ” STATE or CITY REQUIRES !!FIND OUT WHAT “ YOUR ” STATE or CITY REQUIRES !!
NFPA 13 15.1.8.3NFPA 13 15.1.8.3 Where equipment is installed to guard
against possible contamination of the public water system, such
“EQUIPMENT”EQUIPMENT” and “DEVICES”“DEVICES” SHALLSHALL be listed forbe listed for
““FIRE PROTECTION SERVICE”FIRE PROTECTION SERVICE”.
NFPA 13 - Chapter 15NFPA 13 - Chapter 15
250. 17. Operators trained in required17. Operators trained in required
maintenance, weekly operation,maintenance, weekly operation,
testing, and record keeping ???testing, and record keeping ???
Did the pump rep provide a weekly check
list and go over the required weekly
testing, maintenance, and inspections of
the pump, driver, and controller ???
NFPA 20 (14.3 ) NFPA 25 4.1 - 4.3NFPA 20 (14.3 ) NFPA 25 4.1 - 4.3
If not, he is not doing his job!!!
Weekly Check list should include those
items required by NFPA 25 Chapter 8NFPA 25 Chapter 8.
251. Develop a check listDevelop a check list
of your own forof your own for
both “electric” andboth “electric” and
“diesel” Fire“diesel” Fire
Pumps.Pumps.
-OR--OR-
Make a copy ofMake a copy of
NFPA 25, Chapter 8NFPA 25, Chapter 8
for the owner or hisfor the owner or his
representative torepresentative to
use as a guide foruse as a guide for
weekly checks.weekly checks.
““TRAIN THEM !!TRAIN THEM !!
252.
253. NOTE: Clean GreaseNOTE: Clean Grease
Forced out of theForced out of the
Drain hole withDrain hole with
PLUG REMOVED !!PLUG REMOVED !!
Check ForCheck For
ExcessExcess
GreaseGrease
Review ALL RequiredReview ALL Required WeeklyWeekly//AnnualAnnual MaintenanceMaintenance
254. STATE of OHIO FIRE SCHOOL - BGSU 254
AFTERAFTER alignment hasalignment has
been re-checkedbeen re-checked
(ANNUALLY) the(ANNUALLY) the
coupling should becoupling should be
lubricated and re-lubricated and re-
assembled. Be sureassembled. Be sure
to check the setto check the set
screws for tightnessscrews for tightness
AnnualAnnual
AlignmentAlignment
CheckCheck
256. STATE of OHIO FIRE SCHOOL - BGSU 256
??????
This is the ONLY “WM” case relief valve –This is the ONLY “WM” case relief valve –
on record, that had a tight shut off withon record, that had a tight shut off with
“NO” nuisance leakage - until they had to“NO” nuisance leakage - until they had to
buy a new pump !!buy a new pump !!
257. STATE of OHIO FIRE SCHOOL - BGSU 257
#1#1
CCOOLINGOOLING
WATERWATER
#2#2
FFUELUEL
# 3# 3
CCRANKRANK
NOTE !NOTE !
SET at 120 % of
Rated RPM **
EMERGENCYEMERGENCY
MANUALMANUAL
STARTINGSTARTING
PROCEDUREPROCEDURE
(11.6.6)(11.6.6)
BE SURE THAT YOU
KNOW WHERE THE
OVERSPEED RESET
IS ON EVERY TYPE
OF ENGINE THAT
YOU SELL !!
INSTRUCT (TRAIN)
THE OWNER’S
REPRESENTATIVE
OR OPERATOR.
CUMMINS
258. 18. Review test results …18. Review test results …
ASK QUESTIONS ! Do itASK QUESTIONS ! Do it
again if the results do notagain if the results do not
look correct ???look correct ???
Did the pump rep try to rush the testing????Did the pump rep try to rush the testing????
Did the pump rep get nervous or defensiveDid the pump rep get nervous or defensive
when you questioned any of the results or testwhen you questioned any of the results or test
procedures???procedures???
Were the PUMP test results at or above theWere the PUMP test results at or above the
factory shop test curve and within ½ % (factory shop test curve and within ½ % (
the minimum accuracy of a CALIBRATEDthe minimum accuracy of a CALIBRATED
TEST GAUGE ) ??? NFPA 20 (14.2.4.2)TEST GAUGE ) ??? NFPA 20 (14.2.4.2)
Did the pump run forDid the pump run for one hourone hour (all testing)???(all testing)???
NFPA 20 (14.2.12)NFPA 20 (14.2.12)
259.
260. 19.19. STOP !STOP ! Don’t accept it ifDon’t accept it if
the pump test results do notthe pump test results do not
duplicate the shop test curve orduplicate the shop test curve or
the system is not CORRECT !the system is not CORRECT !
L.A.H.J. ( INSPECTOR )L.A.H.J. ( INSPECTOR ) : YOUR NAMEYOUR NAME andand
REPUTATIONREPUTATION goes on the bottom line:
Approved and Accepted By:
NAMENAME : ………………………………………….………………………………………….
261. FIRE PUMP ““Annual”Annual” FLOW TEST
1.1. CheckCheck for company and individual LICENSING.for company and individual LICENSING.
2.2. CheckCheck for HYDRO and FLUSH CERTIFICATES (if work has been done).for HYDRO and FLUSH CERTIFICATES (if work has been done).
3. Look system over…housekeeping, sensing lines, leaks, piping , etc.3. Look system over…housekeeping, sensing lines, leaks, piping , etc.
4. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)4. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)
5. Has the pump been properly Maintained and ALIGNED ANNUALY???5. Has the pump been properly Maintained and ALIGNED ANNUALY??? (CHECK)(CHECK)
6. Review Records of weekly testing and maintenance that was performed.6. Review Records of weekly testing and maintenance that was performed.
7.7. CheckCheck for CERTIFICATE of CALIBRATION forfor CERTIFICATE of CALIBRATION for ALLALL flow test equip. (SAFE??)flow test equip. (SAFE??)
8. Decide in advance just what is to take place during the flow test.8. Decide in advance just what is to take place during the flow test.
9. Operate the pump at Churn (no flow)….temp., brgs., packing, relief, etc.9. Operate the pump at Churn (no flow)….temp., brgs., packing, relief, etc.
10. Record Churn Test Results (compare with test results from previous year).10. Record Churn Test Results (compare with test results from previous year).
11. Operate the pump at additional flow points 100%, 150%,.11. Operate the pump at additional flow points 100%, 150%,.
12. Record Test Results , compare with previous year ( within 5 % nameplate?).12. Record Test Results , compare with previous year ( within 5 % nameplate?).
13. 1 AUTO Start and 2 MANUAL Starts (One Full Load Start)13. 1 AUTO Start and 2 MANUAL Starts (One Full Load Start)
14. Controller and Driver alarms14. Controller and Driver alarms TESTEDTESTED (electric and diesel)(electric and diesel) (CHECK)(CHECK)
15.15. ConfirmConfirm Start and Stop PSI for Main Fire Pump and Jockey Pump.Start and Stop PSI for Main Fire Pump and Jockey Pump.
16. Low Suction Control Operation, Set Point, Time Delay,16. Low Suction Control Operation, Set Point, Time Delay, ANDAND AlarmAlarm TESTEDTESTED ??
17. Review17. Review ALLALL results - ASK QUESTIONS!! - ANY CONCERNS?? - Do it again ?results - ASK QUESTIONS!! - ANY CONCERNS?? - Do it again ?
18. STOP ! INVESTIGATE ! If the PUMP is more than 5 % below nameplate !18. STOP ! INVESTIGATE ! If the PUMP is more than 5 % below nameplate !