SHIELD Intelligent 8 Loop FACP
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
• Listed to LPCB
• 8 x Loops (242) capacity (1936) addressable points
• 140 programmable LED zones
• Maximum 10 Loops Standalone, Modular constructed for future
expansion
• 40 x15 lines LCD Display.
• Up to 999 programmable zones and 140 zone indication
• Auto Programming Day and Night Mode
• Enable and Disable function
• PAS and Acknowledge Function
• Dirty Detector Reporting
• Duplicate Address Checking and Device Mismatch
• Walk Test Function with optional silent mode
SHIELD
SHIELD Intelligent 8 Loop FACP
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
• Start and Stop Function
• Can edit device detailed and programmed
• Day/Night delay time disable
• Programmable form PC or Panel
• History record- almost 2000 event capacity in
non-volatile memory
• Fully simulation of Cause and Effect
• Advanced user friendly programming software including
‘Fuzzy Logic’.
• Networked with all SHIELD Intelligent Fire panels up to 64 Nodes,
• Optional RS 485 mimic and repeater output up 64
• Optional RS 232-USB CRT interface for P-CGS graphic
• Built in Fire Alarm, FPE, Fault , Alarm Router output and
Feedback signal
• Panel Printer included
• Built in Battery charger.
continuation
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
XS1
XS8
XS2
XS3
XS4
XS5
XS11
XS10
XS9
XS6
XS7
XS14
XS13
XS12
COM BOARD
MAIN BOARD
LOOP BOARD
LOOP BOARD
LOOP BOARD
LOOP BOARD
LOOP BOARD
XS15
+5V
GND
TO
MAINBOARD
F7.820.1238V2
24V
GND 5V GND 24V
TX RX
LOOP
01
O+
O-
I+
I-
LOOP
02
O+
O-
I+
I-
LOOP
03
O+
O-
I+
I-
LOOP
04
O+
O-
I+
I-
LOOP
05
O+
O-
I+
I-
LOOP
06
O+
O-
I+
I-
LOOP
07
O+
O-
I+
I-
LOOP
08
O+
O-
I+
I-
LOOP
09
O+
O-
I+
I-
LOOP
10
O+
O-
I+
I-
OUTPUT
TO
SOUNDER
F2
F1
A
B
OUTPUT
TO
FPE
ALARM
ROUTING
FEED
BACK
REPEATER
FAULT
OUTPUT
NO
COM
NC
XT1
XT2
XT3
XT4
XT5
XT6
XT7
XT8
XT9
XT10
XT11
XT12
XT13
XT19
XT14
XT18
+
_
Fitted
470 ohms
+
_
+
_
FPE with
fitted diode
4.7Kohms
EOL
+
+
FPE FPE
Sounder with
built-in diode
Output Device with
fitted diode
+
+
O/P
Sounder with
built-in diode
Output Device with
fitted diode
+
+
O/P
A
B
Output to Repeater or
Mimic Panel
O+
O-
I+
I-
Loop Out
Loop In
LOOP
01
O+
O-
I+
I-
A1
LOOP
10
B1
B2
A2
Network Terminal - Class A
Out to next panel A2
Out to next panel B2
In from next panel B1
In from next panel A1
Out to first device
In from last device
XT1
XT10
O+
O-
I+
I-
A
LOOP
10
B
Network Terminal - Class B
Out to next panel A
Out to next panel B
XT10
No connection
4.7Kohms
EOL
4.7Kohms
EOL
4.7Kohms
EOL
Card Configuration
10 Loops + Repeater
10 Loops + Communication
8 Loops + Communication + Repeater
8 Loops + Communication+ Network
8 Loops + Network + Repeater
6 Loops + Communication + Network + Repeater
Note:
•Com Board (XS8-XS1) – Used only for Repeater/ Mimic Card RB-A8M or Communication Card DB-A8M (USB
and serial connection)
•Communication Card DB-A8M can be placed in any Loop Board using only serial port connection, USB is not
accessible
•Network card should be placed to Loop Board 5 (XS10-XS3) and wired in loop 10 terminal
SHIELD
Basic Card Addressing and
Designation
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Setting the card address
Numbering sequence, lower card is the
recommended lowest numerical setting.
Set dials on the additional board in
ascending order. Each card must be set
at least one higher digit than the lower
card.
CARD SUM: 03 LOOP SUM: 04 SUM:0012
********************************
LOOP 1: Loop Card, Devices Sum: 003
LOOP 2: Loop Card, Devices Sum: 003
LOOP 3: Loop Card, Devices Sum: 003
LOOP 4: Loop Card, Devices Sum: 003
LOOP 5: Net Card-01, Net Sum: 02
LOOP 6: CRT CARD -01
Press F1 to print LOOP DEVICES info
SHIELD
Panel And Card Addressing
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE SET-UP
2 ZONE SET-UP
3. COMMUNICATIONE SET UP
4. DAY/NIGTH TIME SETUP
5. MODIFY PASSWORD SETUP
6. C&E EQUATION SETUP
7. DEVICE TYPE SETUP
FAR: OK FPE: OK OTS: OK 13:01:07
*COMMUNICATION SETUP*
********************************
1. MONITOR INTERFACE
2. NETWORK INTERFACE
FAR: OK FPE: OK OTS: OK 13:01:08
1. Monitor interface (for DB-A8M card)
Please input loop number: (1:10)
Please input panel address: (1-32)
2 Network Interface (for NB-A8M card)
Please Input loop number: (1-10)
Please Input panel address (1-64)
Enter: Received Command : Enable/Disable
Send Command : Enable/Disable
Received Information : Enable/Disable
Send Information : Enable/Disable
Note: The address of the panel is saved in the card
SHIELD
Basic loop Terminal
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
O+
O-
I+
I-
Loop Out
Loop In
LOOP
01
O+
O-
I+
I-
A1
LOOP
10
B1
A2
B2
Network Terminal - Class A
out to next panel A2
out to next panel B2
in from next panel B1
in from next panel A1
Loop Wiring
out to first device
in from last device
XT1
XT10
•Loop Address: 242
•Output Voltage:21-27Vdc
•Output Current: 300mA
•Wiring Topology: Class A or B
•Recommended Cable length: 1200 meters
•Recommended Cable: GST Fire Cable
•Loop protection: Optional loop isolator (C-9503/4)
Connect the loop within the panel as follows: Loop
OUT + to Loop IN+/ Loop OUT- to Loop IN- .
SHIELD
Basic Output / Input Terminal
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Output Condition
Device
Number
Alarm
(Default)
Disable CE Mode
Delay Time
Program
Stop – via
Silence Button
Alarm
Routing
Routing A 00000083 Immediate Yes No Yes No
Output to
Sounder
Sounder A 00000082 Immediate Yes Yes Yes Yes
Output to
FPE
FPE A 00000081 Immediate Yes Yes No No
Note: For output dry contact use CI-500R (output capacity 5A/220VAC or 24VDC @26mA Alarm Current)
SHIELD
Basic Auto-Learn/Registration
Procedures
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Turn on the panel and perform an auto learn/registration as follows:
1. The control panel is set in COMMISIONING MODE by default, once it is powered ON, the system
immediately after the start-up will automatically initialize the REGISTRATION process.
2. If the system set to MONITORING MODE change the setting by: (System Setup→ 3 Working State Set-up→
select 1 Commissioning State)
3. For manual registration (System Setup→ 4 Commissioning → select 1 Device Learn)
X
FIRE CONTROL PANEL SHIELD
Wed 13 Jan 2012
Panel Healthy
FAR: OK FPE: OK OTS: OK 13:14:15
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*WORKING STATE SETUP*
********************************
1.COMISSION
2. MONITOR
FAR: OK FPE: OK OTS: OK 13:01:06
SHIELD
Basic Auto-Learn/Registration
Procedures
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
To check the registered devices
1. Press “User Setup”, (Default password) then press Enter
2. Press “Browse Devices”
3. Select the loop number using UP/Down arrow and then press Enter
*USER SET-UP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SET-UP
4. DELAY MODE SET-UP
5. ACKNOWLEDGE TIMER
6. TEST SET-UP
7. START SET-UP
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:14:15
CARD SUM: 03 LOOP SUM: 04 SUM:0012
********************************
LOOP 1: Loop Card, Devices Sum: 003
LOOP 2: Loop Card, Devices Sum: 003
LOOP 3: Loop Card, Devices Sum: 003
LOOP 4: Loop Card, Devices Sum: 003
LOOP 5: Net Card-01, Net Sum: 02
LOOP 6: CRT CARD -01
→F1 to print LOOP DEVICES info
→F2 –Found devices F3- Missed devices
FAR: OK FPE: OK OTS: OK 13:14:15
Loop01: Loop Card, Devices SUM:003
********************************
D001 Group 001 Loop 1 Lift
Mechanical Room
D002 Zone-001 Loop 1 Optical Smoke
Manager Room
D003 Zone-001 Loop 1 Optical Smoke
Secretary Room
D004 Zone-001 Loop 1 Heat Detector
Pantry
FAR: OK FPE: OK OTS: OK 13:14:15
SHIELD
Basic Software Configuration
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
1. Control Panel Detailed
2. Number of Loop
3. Zone Detailed ( LED and PAS)
4. Device Detailed per Loop (Naming of Repeater/Mimic)
5. Equation (Cause & Effect)
6. Saving Data
7. Download / Upload
SHIELD
1. Control Panel Detailed
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Adding Control Panel
1. Click the “FACP Net” icon
2. Right-click “FACP” and select “Add FACP”
•FACP Type: Select the panel part number
•FACP Address: Address of the panel
•FACP Name: File name reference
•Net: Click if the panels are network
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
3. Zone Configuration
Adding a zone
1.Click the “FACP Zone” icon
2.Right-click “Panel that will add zone” and select “Add Zone”
3.Or Click the “New” icon
Note: Max number of zone is 999
Zone ID : Zone number
Zone Mode:
0-Off: Panel display Fire immediately- No Pre-alarm feature
1-Type A: Enable Pre-alarm/ The system shall response to a second alarm from any device in the same zone as the system alarm (Type A)
2-Type B: Enable Pre-alarm/ The system shall response to a second alarm from any device in the same or other zone as the system alarm (Type B)
Zone Sounder Mode
0-Sound By Zone Fire: Alarm the sounder automatically if the fire is on the same zone
Ex: fire in zone 1, all the sounders in zone 1 will alarm
1-On E&C: Activation of Sounder through Equation
Zone Resound Mode
0-No Resound: Sounder will not alarm if new fire from the other zone after being silenced
1-Resound by New Fire: Sounder will alarm if new fire from other zone after being silenced
Zone LED: 1-140 LED
ForeColor: Font Color
BackColor: Text Highlight Color
Description: Zone name (note: 40 Max character)
Example: Zone example
4.To save click the “Save” icon
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
4. Device Detailed
Device Configuration per Loop
1.Click the “FACP Net” icon
2.Click “Panel to be programmed”
3.Click the “Loop 1”
Address: 1-242
Loop Number: Loop Number
Zone: Zone assignment
Device Type: Selection of device type.
Properties: For output- 0-on/off ; 1-continoues
Location: Device location information
Note: character 40 max
Registered: Once the data is uploaded from the
panel, it will indicate TRUE if the particular
device is being found or registered in the panel
otherwise it will indicate False.
4. Click Save icon to save
To configure the USER DEFINE
•Click the “Panel that will configure”
•Click the “Device Type -icons
•The Device Type window will pop-up
•Select the required condition and type new
Device Type name
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
5. Equation ( Cause and Effect )
Configuring the Equation
1. Click the “FACP Net” icon
2. Click “Panel to be programmed”
3. Click the “Equation”
4. To save the equation click “Save New”
5. To modify the equation click “Save
Modify”
6. To save the entire equation click “Save”
Condition: INPUT DEVICES- 8 digits
Effect: OUTPUT DEVICES – 10 digits
Logic: AND Logic (x), OR Logic (+)
Fuzzy Logic: Asterisk (* value 1-9)
Delay Time Ratio: 1:10 seconds
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
5. Equation ( Cause and Effect )
999 242 99 = 999 242 99 99
Zone Address Device Type Zone Address Device Type Delay Time
Condition
001 020 03 meaning Address 20 Optical smoke in Zone 1 (By Point)
001 *** 03 meaning At least 1(any address) Optical smoke in Zone 1 (By Zone)
*** *** 02 meaning At least 1(any address) Heat det. in the entire area (Global)
Effect:
XXX XXX 13 03 means sounder global alarm after 30 seconds (Global)
Sample:
001 *** 11 + 001 *** 03 + 001 *** 02 = 001*** 13 00, *** *** 13 06
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
6. Saving and Restoring Data
Click the “Database” icon
The Database Operation window will pop out
Click “Backup Database” to save the data.
Save the data to the required location
Click “Restore Database” to retrieve the data.
Locate the data save
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Basic Software Configuration
7. Upload and Download Data
Terminology:
Download: Data transferring from the PC
to the Control Panel
Upload : Data transferring from the Control
Panel to the PC
Warning!! The data must be downloaded/uploaded by
setting such as zone, loop, etc. Do not generally
download/upload the data.
3 important things to note:
1. Registration of RS232 download card (Hardware)
Identify the loop number of the DB-A8M card by pressing the “User Set-up”
Select or press number 1 Browse Devices
Press “System Setup” (No password) Press “Enter”
Press “1 Programming” and then “3 Communication Set-up”
Press “1 Monitor Interface”
Please input loop number: (1:10)
Please input panel address: (1-32)
2. Set Serial Port number (USB Connection-My computer-Properties-Hardware-Device Manger-Port)
3. Matched the address of the control panel “Local Address from the SHIELDDef software “FACP Address”.
To view the control panels address:
(Press “System Setup” 1 Programming3 Communication Set-up monitor or network interface)
Note:
•Com Board (XS8-XS1) – Used only for Repeater/ Mimic Card RB-A8M or Communication Card DB-A8M (USB and serial connection)
•Communication Card DB-A8M can be placed in any Loop Board using only serial port connection, USB is not accessible
SHIELD
Basic Keypad Configuration
1. Zone Setup
2. Device Type Setup
3. Point Setup
4. C&E Set-up
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
SHIELD
Zone Setup
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE SET-UP
2 ZONE SET-UP
3. COMMUNICATIONE SET UP
4. DAY/NIGTH TIME SETUP
5. MODIFY PASSWORD SETUP
6. C&E EQUATION SETUP
7. DEVICE TYPE SETUP
FAR: OK FPE: OK OTS: OK 13:01:07
*ZONE SETUP*
ZONE (1-999) : 001
********************************
DEPENDENCY TYPE (0-2) : 0-OFF
SOUNDER MODE (0-1) : 1-ON C&E
RESOUND MODE (0-1) : 1- Resound by New Fire
ZONE LED (1-140) : 001
TEXT (40 Byte) :
GROUND FLOOR
FAR: OK FPE: OK OTS: OK 13:01:08
Dependency Mode:
0-Off: Panel display Fire immediately- No Pre-alarm feature
1-Type A: Enable Pre-alarm/ The system shall response to a second alarm from any device in the same zone as the system alarm
2-Type B: Enable Pre-alarm/ The system shall response to a second alarm from any device in the same or other zone as the system alarm
Zone Sounder Mode
0-Sound By Zone Fire: Alarm the sounder automatically if the fire is on the same zone
Ex: fire in zone 1, all the sounders in zone 1 will alarm
1-On E&C: Activation of Sounder through Equation
Zone Resound Mode
0-No Resound: Sounder will not alarm if new fire from the other zone after being silenced
1-Resound by New Fire: Sounder will alarm if new fire from other zone after being silenced
Zone LED: 1-140 LED
TEXT: Up to 40 characters
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Device Type Setup
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE SET-UP
2 ZONE SET-UP
3. COMMUNICATIONE SET UP
4. DAY/NIGTH TIME SETUP
5. MODIFY PASSWORD SETUP
6. C&E EQUATION SETUP
7. DEVICE TYPE SETUP
FAR: OK FPE: OK OTS: OK 13:01:07
*DEVICE TYPE LIST*
00: Undefine 01: MultiSensor
02: Heat Detector 03: Optical Smoke
04: User Define 05: Gas Detector
06: Beam Detector 07: Flame detector
08: Conventional P 09: User Define
10: Flow Switch 11: MCP (BG)
12: Sounder Strobe 13: Sounder
14: Flasher 15: LIFT
!Press key [F2] to modify device type
FAR: OK FPE: OK OTS: OK 13:01:07
Device number Condition
1-11 FIRE
12-30 ACTION
31-40 FAULT
41-50 SUPERVISORY
51-65 ACTION
66-99 PANEL
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Device Setup
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE SET-UP
2 ZONE SET-UP
3. COMMUNICATIONE SET UP
4. DAY/NIGTH TIME SETUP
5. MODIFY PASSWORD SETUP
6. C&E EQUATION SETUP
7. DEVICE TYPE SETUP
FAR: OK FPE: OK OTS: OK 13:01:07
*DEVICE SETUP*
Loop: 01 Address(1-242) : 001
********************************
ZONE (I-999) : 001
DEVICE TYPE: 03- Optical Smoke
ATTRIBUTE (1-6) : 6
TEXT (40 Byte) :
MANAGER ROOM
FAR: OK FPE: OK OTS: OK 13:01:08
Zone: Zone assignment
Device Type: Selection of device type.
Attribute: Detector sensitivity/For output signal - 0-on/off ; 1-continoues
Location: Device location information , max 40 characters
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Equation Setup
*PROGRAMMING*
********************************
1.DEVICE SET-UP
2 ZONE SET-UP
3. COMMUNICATIONE SET UP
4. DAY/NIGTH TIME SETUP
5. MODIFY PASSWORD SETUP
6. C&E EQUATION SETUP
7. DEVICE TYPE SETUP
FAR: OK FPE: OK OTS: OK 13:01:07
CREATE C&E
********************************
C&E Quantity:001
N0.002
001***02+001***03= 001***1300 001***1200
FAR: OK FPE: OK OTS: OK 13:01:08
*C&E EQUATION SETUP*
********************************
1.CREATE
2 MODIFY
3. DELETE – (DELETE ONE BY ONE)
4. INITIALIZATION - (DELETE ALL )
FAR: OK FPE: OK OTS: OK 13:01:07
NOTE:
Condition: INPUT DEVICES- 8 digits
Effect: OUTPUT DEVICES – 10 digits
Delay Time Ratio: 1:10 seconds
Number Arrangement:
999 242 99 = 999 242 99 99
Zone Address Device Type Zone Address Device Type Delay Time
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Equation Setup
Types of logic
Condition:
001 020 03 meaning Address 20 Optical smoke in Zone 1 (By Point)
001 *** 03 meaning At least 1(any address) Optical smoke in Zone 1 (By Zone)
*** *** 02 meaning At least 1(any address) Heat det. in the entire area (Global)
Effect:
XXX XXX 13 03 means sounder global alarm after 30 seconds (Global)
Sample:
001 *** 11 + 001 *** 03 + 001 *** 02 = 001*** 13 00, *** *** 13 06
Note:
Logic: AND Logic (x), OR Logic (+)
Fuzzy Logic: Asterisk (* value 1-9)
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Device Learn
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
REGISTERING ACTIVE EQUIPMENT
PLEASE WAIT………
FAR: OK FPE: OK OTS: OK 13:01:07
Note:
The panel must be set to “Commissioning Mode”
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Duplicate Check
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
DUPLICATED ADDRESS CHECKING
Please wait……
Press [Cancel] to Exit!
FAR: OK FPE: OK OTS: OK 13:01:07
Note! to access into Duplicated Check:
1.The panel must be set to “Commissioning Mode”
2. The system must initialize to “Digital Mode”
To find out the duplicated address:
User Setup→1 Browse→4 Browse Duplicated Address
Enter the loop which have duplicated addresses to view
the addresses
DUPLICATED ADDRESS CHECKE OK
Duplicated Address Sum: 001
FAR: OK FPE: OK OTS: OK 13:01:07
CARD SUM: 03 LOOP SUM: 04 SUM:0012
********************************
LOOP 1: Loop Card, Dupli. Add. Sum : 000
LOOP 2: Loop Card, Dupli. Add. Sum : 001
LOOP 3: Loop Card, Dupli. Add. Sum : 000
LOOP 4: Loop Card, Dupli. Add. Sum : 000
LOOP 5: Net Card-01, Net Sum: 02
LOOP 6: CRT CARD -01
→F1 to print LOOP DEVICES info
→F2 –Found devices F3- Missed devices
FAR: OK FPE: OK OTS: OK 13:14:15
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Modify Address
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
Note:
The panel must be set to “Commissioning Mode”
To change the address.
1.Enter the loop number and address you wish to change.
2.Type the new address into “NEW CODE” then Enter.
*MODIFY ADDRESS*
Loop: 01 Address(1-242) : 001
********************************
USER CODE : 00100115
SERIAL NO.: 0000BB40
NEW CODE: 002
FAR: OK FPE: OK OTS: OK 13:01:08
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Modify Device Sensitivity
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
Note:
The panel must be set to “Commissioning Mode”
To change the detector sensitivity.
1.Enter the loop number and address you wish to change.
2.Type the sensitivity into “NEW SENSITIVITY” then Enter.
3 LEVELS OF SENSITIVITY
LEVEL 1: HIGHEST SENSITIVITY
LEVEL 2: STANDARD SENSITIVITY
LEVEL 3: LOWEST SENSITIVITY
LEVEL 4: FOR FUTURE USE
LEVEL 5: FOR FUTURE USE
LEVEL 6: FOR FUTURE USE
*MODIFY DEVICE SENSITIVITY*
Loop: 01 Address(1-242) : 001
********************************
USER CODE : 00100115
DEVICE TYPE: MULTISENSOR
SENSITIVITY: 1- SENSITIVITY 1
NEW SENSITIVITY: 0
FAR: OK FPE: OK OTS: OK 13:01:08
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Commission in Analog/Digital
Mode
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
Note:
The panel must be set to “Commissioning Mode”
Commission to Analog mode:
Normal Status: Range 450 to 650
Alarm Status: Range 900 to 1200
Fault Status: Range 1 to 120
Commission to Digital Mode: For future use
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
SHIELD
Commissioning
►
Keypad Configuration
►
Software Configuration
►
Operation ►
Initialization Mode
*SYSTEM SETUP*
********************************
1.PROGRAMMING
2. LOCAL OUTPUT SET-UP
3. WORKING STATE SET UP
4. COMMISSIONING
FAR: OK FPE: OK OTS: OK 13:01:06
*PROGRAMMING*
********************************
1.DEVICE LEARN
2 DUPLICATED ADDRESS CHECK
3. MODIFY ADDRESS
4. MODIFY DEVICE SENSITIVITY
5. COMMISSION IN ANALOG MODE
6. COMMISSION IN DIGITAL MODE
7. SYSTEM INITIALIZATION
FAR: OK FPE: OK OTS: OK 13:01:07
Note:
1.The panel must be set to “Commissioning Mode”
2. Required Initialization password:_______________
Detector: Indicate the current mode
Digital mode : to have access in the following
1. Duplicated Address Check
2. Modify Address
3. Modify Device Sensitivity
Analog mode: Default mode and must be used as the working mode
Initialize System: To reset the main control card – this will delete the configuration of Zone LED, Equation and
Device type list.
Warning!! Make sure you have the back up data base
Hide Sounder Plant Item – if you wish not to shown the active sounders
Detector: Analog Mode
Press [1] Initialize detector in digital mode
Press [2] Initialize detector in analog mode
Press [3] To Initialize the system
Press [4] To disable the battery resistance
Press [5] To hide sounder plant item
FAR: OK FPE: OK OTS: OK 13:01:07
SHIELD
Commissioning
►
Software Configuration
►
Basic System Operation
1. Browse
2. Delay Mode Setup
3. PAS – Positive Alarm Sequence
4. Test Setup
5. Start and Stop
6. Disable/Enable
Keypad Configuration
►
Operation ►
SHIELD
Commissioning
►
Software Configuration
►
Browse
*USER SETUP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
5. ACKNOWLEDGE TIMER
6. TEST SETUP
7. START/STOP DEVICE
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:01:06
*BROWSE*
********************************
1.BROWSE DEVICES
2 BROWSE ZONES
3.BROWSE GROUPS
4.BROWSE DUPLICATED ADDRESS
5.BROWSE PANEL STATUS
6.BROWSE C&E EQUATION
7. HISTORY LOG
FAR: OK FPE: OK OTS: OK 13:01:07
1 Browse Devices: View the number of devices per loop and detailed provided with each device
2 Browse Zones: View the total number of Input devices per zone
3 Browse Groups: View the total number of Output devices per group (Zone)
4 Browse Duplicated Address : View the repeated address in a loop
5 Browse Panel Status: View the panel configuration and version
6 Browse C&E Equation: View configured equation
7 History LOG:
1 Fire History
2 Common History
3 Initialization
Keypad Configuration
►
Operation ►
SHIELD
Commissioning
►
Software Configuration
►
Delayed Mode Setup
*USER SETUP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
5. ACKNOWLEDGE TIMER`
6. TEST SETUP
7. START/STOP DEVICE
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:01:06
*DELAY MODE SETUP*
********************************
1.ENABLE
2 DISABLE
FAR: OK FPE: OK OTS: OK 13:01:07
4 DELAY MODE SETUP Commission or Monitor Mode
1 Disable - No output delay
2 Enable - Enable the équations delay time
Note: The Delay Mode LED will turn ON
Setting required to enabling the delay outputs based on the configured C&E equation:
•Enable the delay command form DELAY MODE SETUP
•Configured the system “DAY TIME” form DAY/NIGTH SETUP
•Configured the zone mode parameter into 1- on C&E from the ZONE SETUP
Keypad Configuration
►
Operation ►
SHIELD
Commissioning
►
Software Configuration
►
PAS Setup
*USER SETUP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
5. ACKNOWLEDGE TIMER
6. TEST SETUP
7. START/STOP DEVICE
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:01:06
*ACKNOWLEDGE TIMER*
********************************
1.Please input the Pre-Alarm ACK time:
Phase 1 (Default 30S) : [00] M - [30] S
2.Please input the Pre-Alarm Verify time:
Phase 2 (Default 2M) : [02] M - [00] S
FAR: OK FPE: OK OTS: OK 13:01:07
Dependencies on more than one alarm signal – Type A & B (EN54 P2-7.12)
Day Mode
*Pre-alarm Window: programmable from 1 sec. to 30 min. A distinctive pre-alarm indication shall be displayed.
*Alarm Verification window: programmable from 1 sec. to 30 min.
The system shall response to a second alarm from any device in the same zone as the system alarm (Type A)
The system shall response to a second alarm from any device in the same or different zone as the system alarm (Type B)
Night Mode (Default setting)
*Pre-alarm Window: preprogrammed 30 min. Auto-reset the Alarm in the Panel after 30 min (Type A)
*Pre-alarm Window: preprogrammed 5 min. Auto-reset the Alarm in the Panel after 5 min (Type B)
The system shall response to a second alarm from any device in the same zone as the system alarm (Type A)
The system shall response to a second alarm from any device in the same or different zone as the system alarm (Type B)
Keypad Configuration
►
Operation ►
SHIELD
Commissioning
►
Software Configuration
►
Test Setup
*USER SETUP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
5. ACKNOWLEDGE TIMER
6. TEST SETUP
7. START/STOP DEVICE
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:01:06
*TEST SETUP*
********************************
1.LED BUZZER TEST
2 LOCAL OUTPUT TEST
3. SETUP TEST ZONE
4. CANCEL TEST ZONE
FAR: OK FPE: OK OTS: OK 13:01:07
TEST SETUP Commission or Monitor Mode
1 LED Buzzer Test – Test all the LED and Buzzer
2 Local Output Test – To test the 3 on board outputs
1 Output to Sounder Test (OTS)
2 Output to F.P.E. (FPE)
3 Alarm Routing Test (FAR)
3 Setup Test Zone
Input test zone : (1-999)
Input test mode : (0-1)
0-Without sounder
1-With sounder – Automatic Stop after 10 seconds
4 Cancel Test Zone
1 Cancel One Test Zone
2 Cancel All Test Zone
Keypad Configuration
►
Operation ►
SHIELD
Commissioning
►
Software Configuration
►
Start/Stop Setup
*USER SETUP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
5. ACKNOWLEDGE TIMER
6. TEST SETUP
7. START/STOP DEVICE
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:01:06
*START/STOP DEVICE*
********************************
1.START DEVICE
2 STOP DEVICE
FAR: OK FPE: OK OTS: OK 13:01:07
*START/STOP DEVICE*
********************************
1.START DEVICE
2 STOP DEVICE
START→
ZONE: 000 DEV: 000 TYPE: 00-Un-define
FAR: OK FPE: OK OTS: OK 13:01:07
Keypad Configuration
►
Operation ►
Note: Input the device code
Zone
Device Address
Device Type
SHIELD
Commissioning
►
Software Configuration
►
Disable/Enable
*USER SETUP*
********************************
1.BROWSE
2. CLOCK
3. PRINTER SETUP
4. DELAY MODE
5. ACKNOWLEDGE TIMER
6. TEST SETUP
7. START/STOP DEVICE
8. DISABLE/ENABLE
FAR: OK FPE: OK OTS: OK 13:01:06
*DISABLE/ENABLE*
********************************
1.DIS/ENABLE DEVICE-BY CODE
2 DIS/ENABLE DEVICE –BY ADDRESS
3. DIS/ENABLE ZONE
4. DIS/ENABLE SOUNDER
FAR: OK FPE: OK OTS: OK 13:01:07
DISABLE/ENABLE Commission or Monitor Mode
1 Dis/Enable Devices – By Code
1 Disable Device
2 Enable Device
2 Dis/Enable Device – By Address
1 Disable Device
2 Enable Device
3 Dis/Enable Zone
1 Disable Zone
2 Enable Zone
4 Disable/Enable Sounder
1 Disable Sounder
2 Enable Sounder
Keypad Configuration
►
Operation ►
SHIELD