SIL Suitable Final Elements
FUNCTIONAL SAFETY OF
FIRE & GAS SYSTEMS
SA FIRE PROTECTION
FUNCTIONAL SAFETY
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 2SIL Suitable Final Elements
DEFINITION OF FUNCTIONAL SAFETY
 Safety is the absence of an
unacceptable risk of physical injury to
people or damage to the properties
 Functional Safety is part of the overall
safety which depends on the correct
functioning of a safety-related system
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 3SIL Suitable Final Elements
SAFETY INSTRUMENTED SYSTEM (SIS)
 A Safety Instrumented System (SIS) or
Safety-related System is an appropriate
system required to reduce the risk
(shown by a hazard analysis) of the
Equipment Under Control (EUC)
 A SIS performs one or more Safety
Functions to reduce the risk
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 4SIL Suitable Final Elements
REQUIREMENTS TO FUNCTIONAL SAFETY
Two types of requirements are necessary
to achieve Functional Safety:
 Safety Function Requirements: the
scope of the Safety Function, derived
from the hazard analysis
 Safety Integrity Requirements: the
probability that the Safety Function will
be performed satisfactorily, derived
from the risk assessment
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 5SIL Suitable Final Elements
THE STANDARD IEC 61508
IEC 61508 “Functional Safety of electrical
/electronic / programmable electronic
(E/E/PE) safety-related systems”:
 Covers all the safety lifecycle activities
 Contains requirements for preventing
failures and controlling failures,
ensuring safety even when faults are
present
 Specifies the techniques and measures
to achieve the required Safety Integrity
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 6SIL Suitable Final Elements
SAFETY INTEGRITY LEVEL (SIL)
 Safety Integrity is the probability that
the SIS will perform the required Safety
Functions satisfactorily
 IEC 61508 specifies 4 levels of safety
performance for a Safety Function,
called Safety Integrity Level (SIL)
 The Standard details the requirements
necessary to achieve each Safety
Integrity Level. SIL1 is the lowest level
and SIL4 is the highest
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 7SIL Suitable Final Elements
SAFETY INTEGRITY LEVEL (SIL)
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 8SIL Suitable Final Elements
Low demand mode of operation:
frequency of demands for the SIS not
greater than once per year, and not
greater than twice the proof-test
frequency
Safety Integrity Level (SIL)
Average Probability of Failure
on Demand (PFDavg)
4 ≥ 10-5 to < 10-4
3 ≥ 10-4 to < 10-3
2 ≥ 10-3 to < 10-2
1 ≥ 10-2 to < 10-1
FIRE & GAS SYSTEM
FUNCTIONAL SAFETY
F&G SYSTEM
• Objectives
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 9SIL Suitable Final Elements
TASKS OF F&G SYSTEM
The main tasks of a F&G system are:
 Detect any hazardous fire or gas
condition
 Alert the personnel in the monitored
area
 Activate the control and mitigation
systems
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 10SIL Suitable Final Elements
F&G SYSTEM EFFECTIVENESS
The F&G system Effectiveness is the
product of three factors:
 Detection Coverage: the fraction of the
monitored area in which an eventual
hazard would be detected
 Mitigation Effectiveness: the
probability that the activation of the
Final Elements would reduce the
consequence of a defined hazard
 F&G Safety Availability (SA): 1-PFDavg
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 11SIL Suitable Final Elements
A F&G system consists of:
 Detectors
 Logic Solver
 Final Elements
A chain is only as strong as its weakest
element
COMPONENTS OF F&G SYSTEM
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 12SIL Suitable Final Elements
LOGIC
SOLVER
FINAL
ELEMENTS
DETECTORS
The F&G Effectiveness is related to the
Safety Availability of all its components
SA has developed
SIL suitable Final Elements
for the main fire-fighting systems
FINAL ELEMENTS
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 13SIL Suitable Final Elements
LOGIC
SOLVER
FINAL
ELEMENTS
DETECTORS
NIAGARA
ELECTRIC
MONITORS
ELECTRIC
ACTUATORS
VDD
DELUGE
VALVES
ELECTRIC MONITOR
NIAGARA SERIES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 14SIL Suitable Final Elements
DESCRIPTION
 The fire-fighting monitors
Niagara series are electric
type remote controlled
water cannons, intended to
deliver large amount of water
towards remote targets.
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 15SIL Suitable Final Elements
 The monitor architecture comprises
of a Logic Controller and one or more
monitor assemblies
MAIN FEATURES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 16SIL Suitable Final Elements
 Automatic self-diagnostic
analysis
 Remote controlled
 Designed for sea water and
water foam solution
 Suitability for SIL2 systems
validated by Bureau Veritas
ADVANTAGES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 17SIL Suitable Final Elements
Automatic self-diagnostic analysis: at
regular intervals the self-diagnostic
system in the Logic Controller checks the
correct operation on given commands
 Constant monitoring of any possible
failure of monitor and nozzle
 Reduction of the probability that
faults, taking place between regular
maintenance, will pass undetected
 Increased reliability on demand
APPLICATION
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 18SIL Suitable Final Elements
Designed for petrochemical
jetty and marine harbor and
structure cooling
Recommended for those systems which
require:
 A low probability of failure on demand
 A fire protection system with a high
Safety Integrity Level
 A large amount of water towards
remote targets
DOUBLE COIL
ELECTRIC ACTUATOR
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 19SIL Suitable Final Elements
DESCRIPTION
 The double coil electric actuator has
been developed to sharply reducing
the probability of failure of a pilot
cylinder of a gaseous based fire
protection system (carbon dioxide,
inert gases, halocarbons) or a water
mist system
SIL Suitable Final Elements
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 20
MAIN FEATURES
 Redundancy: the actuator has two coils
which receive two independent signals
from the Logic Solver. If one coil should
fail, the other coil is able to open the
cylinder valve
 Suitability for SIL2
systems validated
by Bureau Veritas
SIL Suitable Final Elements
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 21
APPLICATION
Designed for the protection of gas
turbines and their generators, electronic
rooms and general installations on FPSO
Recommended for those systems which
require:
 A low probability of failure on demand
 A fire protection system with a high
Safety Integrity Level
SIL Suitable Final Elements
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 22
DOUBLE CHAMBER DELUGE VALVE
MODEL VDD
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 23SIL Suitable Final Elements
DESCRIPTION
 The VDD deluge valve combines all the
functions of a traditional deluge valve
with a fully redundant architecture,
designed to achieve a higher Safety
Availability
 The VDD deluge valve
has two priming
chambers, each one
provided with its own
diaphragm and trim
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 24SIL Suitable Final Elements
PRINCIPLE OF OPERATION
 In the set position (valve closed)
The pressure of the water trapped in
the priming chambers holds the
diaphragms on the valve seats, keeping
the valve closed
 In fire condition (valve open)
The pressure is released from the
priming chambers. The water supply
pressure forces the diaphragm off the
seats, opening the valve
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 25SIL Suitable Final Elements
MAIN FEATURES
 Fully redundant system
 Built-in emergency bypass line that
operates on both priming chambers in
“hot back-up”
 Continuous fire protection
 Designed to overcome a double failure
 Suitability for SIL3 systems validated by
Bureau Veritas
 Under UL testing for UL/cUL Listing
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 26SIL Suitable Final Elements
ADVANTAGES
Built-in emergency bypass line
 Each priming chamber provides the
nominal design waterway for the fire
protection system
 The system is fully redundant
 The time to respond to a failure is
reduced to zero
 No need of an external bypass line on
the skid: reduction of dimensions,
weight and cost of the skid
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 27SIL Suitable Final Elements
ADVANTAGES
Designed to overcome a double failure
 A hydraulic bridge between the trims
allows each trim to control both the
diaphragms
 In case of failure of one trim, the other
trim can open both the priming
chambers
 The VDD deluge valve can overcome a
double failure
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 28SIL Suitable Final Elements
ADVANTAGES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 29SIL Suitable Final Elements
Designed to overcome a double failure
 Fault Tree of the VDD deluge valve
ADVANTAGES
Fire protection system always in service
 Two built-in isolation
valves allow alternate
in-line maintenance
to be performed
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 30SIL Suitable Final Elements
 An interlock system prevents
the accidental or incorrect
rotation of the isolation valves
APPLICATION
 Made of Ni-Al-Bronze, a
highly resistant material
 Specifically designed for
harsh environments, such
as oil & gas onshore and
offshore and chemical and
nuclear plants installations
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 31SIL Suitable Final Elements
 Sea water, foam
concentrate and
water foam solution
APPLICATION
Recommended for those systems which
require:
 A low probability of failure on demand
 A fire protection system with a high
Safety Integrity Level
 Continuity of fire protection during
maintenance or repair
 Reduction of weight, dimension and
cost of the skid
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 32SIL Suitable Final Elements
REFERENCE CONTACT
SA Fire Protection
Viale Europa 121-123
Cascina ( PISA ) – Italy
Ph. +39.050.70.30.06
Fax. +39.050.70.35.80
export@sasrl.it

Weitere ähnliche Inhalte

Was ist angesagt?

Process Safety
Process SafetyProcess Safety
Process SafetyConsultivo
 
LOPA | Layer Of Protection Analysis | Gaurav Singh Rajput
LOPA | Layer Of Protection Analysis | Gaurav Singh RajputLOPA | Layer Of Protection Analysis | Gaurav Singh Rajput
LOPA | Layer Of Protection Analysis | Gaurav Singh RajputGaurav Singh Rajput
 
Process Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh RajputProcess Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh RajputGaurav Singh Rajput
 
Prestartup Safety Review (PSSR)
Prestartup Safety Review (PSSR)Prestartup Safety Review (PSSR)
Prestartup Safety Review (PSSR)TheSafetyGuru
 
Sil explained in valve actuators
Sil explained in valve actuatorsSil explained in valve actuators
Sil explained in valve actuatorsJohn Kingsley
 
Pre commissioning and Commissioning Safety.pdf
Pre commissioning and Commissioning Safety.pdfPre commissioning and Commissioning Safety.pdf
Pre commissioning and Commissioning Safety.pdfAssyaMohammed
 
Sil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluidsSil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluidsJohn Kingsley
 
IEC 62061 introduction
IEC 62061 introductionIEC 62061 introduction
IEC 62061 introductionKoenLeekens
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classificationdebuddit
 
IEC 61511 introduction
IEC 61511 introduction IEC 61511 introduction
IEC 61511 introduction KoenLeekens
 
Functional Safety (SIL) in the Subsea and Drilling Industry
Functional Safety (SIL) in the Subsea and Drilling IndustryFunctional Safety (SIL) in the Subsea and Drilling Industry
Functional Safety (SIL) in the Subsea and Drilling IndustryLloyd's Register Energy
 
Process Safety Management Fundamentals.pptx
Process Safety Management Fundamentals.pptxProcess Safety Management Fundamentals.pptx
Process Safety Management Fundamentals.pptxImtiazHussain312057
 
What Is Process Safety Engineering
What Is Process Safety EngineeringWhat Is Process Safety Engineering
What Is Process Safety Engineeringsmpr_iqbal
 
PSM Process Safety Management.pdf
PSM Process Safety Management.pdfPSM Process Safety Management.pdf
PSM Process Safety Management.pdfssuser2fc67e
 
Process Safety Management System
Process Safety Management SystemProcess Safety Management System
Process Safety Management SystemACM Facility Safety
 

Was ist angesagt? (20)

Process Safety
Process SafetyProcess Safety
Process Safety
 
LOPA | Layer Of Protection Analysis | Gaurav Singh Rajput
LOPA | Layer Of Protection Analysis | Gaurav Singh RajputLOPA | Layer Of Protection Analysis | Gaurav Singh Rajput
LOPA | Layer Of Protection Analysis | Gaurav Singh Rajput
 
Process Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh RajputProcess Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh Rajput
 
Prestartup Safety Review (PSSR)
Prestartup Safety Review (PSSR)Prestartup Safety Review (PSSR)
Prestartup Safety Review (PSSR)
 
Sil explained in valve actuators
Sil explained in valve actuatorsSil explained in valve actuators
Sil explained in valve actuators
 
management of change
management of changemanagement of change
management of change
 
Hazop analysis
Hazop analysisHazop analysis
Hazop analysis
 
Pre commissioning and Commissioning Safety.pdf
Pre commissioning and Commissioning Safety.pdfPre commissioning and Commissioning Safety.pdf
Pre commissioning and Commissioning Safety.pdf
 
Sil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluidsSil assessment Risk Graph and LOPA Training iFluids
Sil assessment Risk Graph and LOPA Training iFluids
 
IEC 62061 introduction
IEC 62061 introductionIEC 62061 introduction
IEC 62061 introduction
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 
IEC 61511 introduction
IEC 61511 introduction IEC 61511 introduction
IEC 61511 introduction
 
Process safety management system
Process safety management systemProcess safety management system
Process safety management system
 
Functional Safety (SIL) in the Subsea and Drilling Industry
Functional Safety (SIL) in the Subsea and Drilling IndustryFunctional Safety (SIL) in the Subsea and Drilling Industry
Functional Safety (SIL) in the Subsea and Drilling Industry
 
Process Safety Management Fundamentals.pptx
Process Safety Management Fundamentals.pptxProcess Safety Management Fundamentals.pptx
Process Safety Management Fundamentals.pptx
 
HSE PRESENTATION
HSE PRESENTATIONHSE PRESENTATION
HSE PRESENTATION
 
What Is Process Safety Engineering
What Is Process Safety EngineeringWhat Is Process Safety Engineering
What Is Process Safety Engineering
 
PSM Process Safety Management.pdf
PSM Process Safety Management.pdfPSM Process Safety Management.pdf
PSM Process Safety Management.pdf
 
Hazop ppt
Hazop pptHazop ppt
Hazop ppt
 
Process Safety Management System
Process Safety Management SystemProcess Safety Management System
Process Safety Management System
 

Andere mochten auch

35958867 safety-instrumented-systems
35958867 safety-instrumented-systems35958867 safety-instrumented-systems
35958867 safety-instrumented-systemsMowaten Masry
 
Best Practices in SIS Documentation
Best Practices in SIS DocumentationBest Practices in SIS Documentation
Best Practices in SIS DocumentationEmerson Exchange
 
Safety life cycle seminar IEC61511
Safety life cycle seminar IEC61511Safety life cycle seminar IEC61511
Safety life cycle seminar IEC61511Luis Atencio
 
IEC 61508-3 SW Engineering
IEC 61508-3 SW EngineeringIEC 61508-3 SW Engineering
IEC 61508-3 SW EngineeringHongseok Lee
 
When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?ISA Interchange
 
Integrating Proof and Testing in Verification Strategies for Safety Critical ...
Integrating Proof and Testing in Verification Strategies for Safety Critical ...Integrating Proof and Testing in Verification Strategies for Safety Critical ...
Integrating Proof and Testing in Verification Strategies for Safety Critical ...AdaCore
 
Ruud Dofferhoff - Siemens
Ruud Dofferhoff - SiemensRuud Dofferhoff - Siemens
Ruud Dofferhoff - SiemensThemadagen
 
Martin van der Have - RAB
Martin van der Have - RABMartin van der Have - RAB
Martin van der Have - RABThemadagen
 
Martijn Drost - Pilz
Martijn Drost - PilzMartijn Drost - Pilz
Martijn Drost - PilzThemadagen
 
TOPAAS Versie 2.0, een praktische inleiding
TOPAAS Versie 2.0, een praktische inleidingTOPAAS Versie 2.0, een praktische inleiding
TOPAAS Versie 2.0, een praktische inleidingJaap van Ekris
 
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Schneider Electric
 
SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...
SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...
SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...Emerson Exchange
 

Andere mochten auch (20)

35958867 safety-instrumented-systems
35958867 safety-instrumented-systems35958867 safety-instrumented-systems
35958867 safety-instrumented-systems
 
SIL in the practice: Safety by design
SIL in the practice: Safety by designSIL in the practice: Safety by design
SIL in the practice: Safety by design
 
Best Practices in SIS Documentation
Best Practices in SIS DocumentationBest Practices in SIS Documentation
Best Practices in SIS Documentation
 
LAYER OF PROTECTION ANALYSIS
LAYER OF PROTECTION ANALYSISLAYER OF PROTECTION ANALYSIS
LAYER OF PROTECTION ANALYSIS
 
What is a LOPA?
What is a LOPA?What is a LOPA?
What is a LOPA?
 
Safety life cycle seminar IEC61511
Safety life cycle seminar IEC61511Safety life cycle seminar IEC61511
Safety life cycle seminar IEC61511
 
Apex cnc catalogue
Apex cnc catalogueApex cnc catalogue
Apex cnc catalogue
 
IEC61508
IEC61508IEC61508
IEC61508
 
IEC 61508-3 SW Engineering
IEC 61508-3 SW EngineeringIEC 61508-3 SW Engineering
IEC 61508-3 SW Engineering
 
IEC 61508
IEC 61508IEC 61508
IEC 61508
 
When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?When is a SIL Rating of a Valve Required?
When is a SIL Rating of a Valve Required?
 
Integrating Proof and Testing in Verification Strategies for Safety Critical ...
Integrating Proof and Testing in Verification Strategies for Safety Critical ...Integrating Proof and Testing in Verification Strategies for Safety Critical ...
Integrating Proof and Testing in Verification Strategies for Safety Critical ...
 
Ruud Dofferhoff - Siemens
Ruud Dofferhoff - SiemensRuud Dofferhoff - Siemens
Ruud Dofferhoff - Siemens
 
Martin van der Have - RAB
Martin van der Have - RABMartin van der Have - RAB
Martin van der Have - RAB
 
Martijn Drost - Pilz
Martijn Drost - PilzMartijn Drost - Pilz
Martijn Drost - Pilz
 
TOPAAS Versie 2.0, een praktische inleiding
TOPAAS Versie 2.0, een praktische inleidingTOPAAS Versie 2.0, een praktische inleiding
TOPAAS Versie 2.0, een praktische inleiding
 
SPINDLE
SPINDLESPINDLE
SPINDLE
 
Presentation
PresentationPresentation
Presentation
 
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
 
SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...
SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...
SIS “Final Element” Diagnostics Including The SOV, Using A Digital Valve Cont...
 

Ähnlich wie Sil presentation

2015 Katalog Fluke - Siwali 021 45850618
2015 Katalog Fluke -  Siwali 021 458506182015 Katalog Fluke -  Siwali 021 45850618
2015 Katalog Fluke - Siwali 021 45850618PT. Siwali Swantika
 
katalog Fluke-test-tools-Siwali Swantika
katalog Fluke-test-tools-Siwali Swantikakatalog Fluke-test-tools-Siwali Swantika
katalog Fluke-test-tools-Siwali SwantikaPT. Siwali Swantika
 
4 david schepers certification process safety relay modules for machinery app...
4 david schepers certification process safety relay modules for machinery app...4 david schepers certification process safety relay modules for machinery app...
4 david schepers certification process safety relay modules for machinery app...Luiz Fernando Moraes
 
Sil for-valves-valve-automation-standards-implications-products- final (002)
Sil for-valves-valve-automation-standards-implications-products- final (002)Sil for-valves-valve-automation-standards-implications-products- final (002)
Sil for-valves-valve-automation-standards-implications-products- final (002)hazmat4
 
Rtk katalog gb
Rtk katalog gbRtk katalog gb
Rtk katalog gbLy Jolie
 
SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...
SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...
SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...Gaurav Singh Rajput
 
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building SolutionValve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building SolutionBassam Gomaa
 
Electric Control Valve Actuators for Industrial Process Applications
Electric Control Valve Actuators for Industrial Process ApplicationsElectric Control Valve Actuators for Industrial Process Applications
Electric Control Valve Actuators for Industrial Process ApplicationsCTi Controltech
 
Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205
Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205
Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205System Protection
 
Safety pp002 -en-e
Safety pp002 -en-eSafety pp002 -en-e
Safety pp002 -en-eVo Quoc Hieu
 
ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge Keren Meers
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...Keren Meers
 

Ähnlich wie Sil presentation (20)

2015 Katalog Fluke - Siwali 021 45850618
2015 Katalog Fluke -  Siwali 021 458506182015 Katalog Fluke -  Siwali 021 45850618
2015 Katalog Fluke - Siwali 021 45850618
 
Katalog produk-fluke-test-tools-tridinamika
Katalog produk-fluke-test-tools-tridinamikaKatalog produk-fluke-test-tools-tridinamika
Katalog produk-fluke-test-tools-tridinamika
 
katalog Fluke-test-tools-Siwali Swantika
katalog Fluke-test-tools-Siwali Swantikakatalog Fluke-test-tools-Siwali Swantika
katalog Fluke-test-tools-Siwali Swantika
 
4 david schepers certification process safety relay modules for machinery app...
4 david schepers certification process safety relay modules for machinery app...4 david schepers certification process safety relay modules for machinery app...
4 david schepers certification process safety relay modules for machinery app...
 
Manual tvoc 2
Manual tvoc 2Manual tvoc 2
Manual tvoc 2
 
Sil for-valves-valve-automation-standards-implications-products- final (002)
Sil for-valves-valve-automation-standards-implications-products- final (002)Sil for-valves-valve-automation-standards-implications-products- final (002)
Sil for-valves-valve-automation-standards-implications-products- final (002)
 
Rtk katalog gb
Rtk katalog gbRtk katalog gb
Rtk katalog gb
 
Why SIL3 (ENG)
Why SIL3 (ENG)Why SIL3 (ENG)
Why SIL3 (ENG)
 
SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...
SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...
SIL Awareness | Introduction to Safety Life-Cycle | IEC - 61508 & IEC- 61511 ...
 
Thông số kĩ thuật siemens miniature circuit breakers
Thông số kĩ thuật siemens miniature circuit breakersThông số kĩ thuật siemens miniature circuit breakers
Thông số kĩ thuật siemens miniature circuit breakers
 
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building SolutionValve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
 
Solitaire 710-ii
Solitaire 710-iiSolitaire 710-ii
Solitaire 710-ii
 
Electric Control Valve Actuators for Industrial Process Applications
Electric Control Valve Actuators for Industrial Process ApplicationsElectric Control Valve Actuators for Industrial Process Applications
Electric Control Valve Actuators for Industrial Process Applications
 
Relay testing procedure
Relay testing procedure Relay testing procedure
Relay testing procedure
 
Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205
Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205
Digital Portable Appliance Tester KEW 6205 | Kyoritsu KEW 6205
 
lenner.pptx
lenner.pptxlenner.pptx
lenner.pptx
 
CI_SCS_Intro
CI_SCS_IntroCI_SCS_Intro
CI_SCS_Intro
 
Safety pp002 -en-e
Safety pp002 -en-eSafety pp002 -en-e
Safety pp002 -en-e
 
ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...
 

Kürzlich hochgeladen

A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...drmkjayanthikannan
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwaitjaanualu31
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxSCMS School of Architecture
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersMairaAshraf6
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...Amil baba
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.Kamal Acharya
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Servicemeghakumariji156
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesRAJNEESHKUMAR341697
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxMuhammadAsimMuhammad6
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdfKamal Acharya
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiessarkmank1
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 

Kürzlich hochgeladen (20)

FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 

Sil presentation

  • 1. SIL Suitable Final Elements FUNCTIONAL SAFETY OF FIRE & GAS SYSTEMS SA FIRE PROTECTION
  • 2. FUNCTIONAL SAFETY FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 2SIL Suitable Final Elements
  • 3. DEFINITION OF FUNCTIONAL SAFETY  Safety is the absence of an unacceptable risk of physical injury to people or damage to the properties  Functional Safety is part of the overall safety which depends on the correct functioning of a safety-related system FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 3SIL Suitable Final Elements
  • 4. SAFETY INSTRUMENTED SYSTEM (SIS)  A Safety Instrumented System (SIS) or Safety-related System is an appropriate system required to reduce the risk (shown by a hazard analysis) of the Equipment Under Control (EUC)  A SIS performs one or more Safety Functions to reduce the risk FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 4SIL Suitable Final Elements
  • 5. REQUIREMENTS TO FUNCTIONAL SAFETY Two types of requirements are necessary to achieve Functional Safety:  Safety Function Requirements: the scope of the Safety Function, derived from the hazard analysis  Safety Integrity Requirements: the probability that the Safety Function will be performed satisfactorily, derived from the risk assessment FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 5SIL Suitable Final Elements
  • 6. THE STANDARD IEC 61508 IEC 61508 “Functional Safety of electrical /electronic / programmable electronic (E/E/PE) safety-related systems”:  Covers all the safety lifecycle activities  Contains requirements for preventing failures and controlling failures, ensuring safety even when faults are present  Specifies the techniques and measures to achieve the required Safety Integrity FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 6SIL Suitable Final Elements
  • 7. SAFETY INTEGRITY LEVEL (SIL)  Safety Integrity is the probability that the SIS will perform the required Safety Functions satisfactorily  IEC 61508 specifies 4 levels of safety performance for a Safety Function, called Safety Integrity Level (SIL)  The Standard details the requirements necessary to achieve each Safety Integrity Level. SIL1 is the lowest level and SIL4 is the highest FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 7SIL Suitable Final Elements
  • 8. SAFETY INTEGRITY LEVEL (SIL) FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 8SIL Suitable Final Elements Low demand mode of operation: frequency of demands for the SIS not greater than once per year, and not greater than twice the proof-test frequency Safety Integrity Level (SIL) Average Probability of Failure on Demand (PFDavg) 4 ≥ 10-5 to < 10-4 3 ≥ 10-4 to < 10-3 2 ≥ 10-3 to < 10-2 1 ≥ 10-2 to < 10-1
  • 9. FIRE & GAS SYSTEM FUNCTIONAL SAFETY F&G SYSTEM • Objectives • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 9SIL Suitable Final Elements
  • 10. TASKS OF F&G SYSTEM The main tasks of a F&G system are:  Detect any hazardous fire or gas condition  Alert the personnel in the monitored area  Activate the control and mitigation systems FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 10SIL Suitable Final Elements
  • 11. F&G SYSTEM EFFECTIVENESS The F&G system Effectiveness is the product of three factors:  Detection Coverage: the fraction of the monitored area in which an eventual hazard would be detected  Mitigation Effectiveness: the probability that the activation of the Final Elements would reduce the consequence of a defined hazard  F&G Safety Availability (SA): 1-PFDavg FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 11SIL Suitable Final Elements
  • 12. A F&G system consists of:  Detectors  Logic Solver  Final Elements A chain is only as strong as its weakest element COMPONENTS OF F&G SYSTEM FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 12SIL Suitable Final Elements LOGIC SOLVER FINAL ELEMENTS DETECTORS
  • 13. The F&G Effectiveness is related to the Safety Availability of all its components SA has developed SIL suitable Final Elements for the main fire-fighting systems FINAL ELEMENTS FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 13SIL Suitable Final Elements LOGIC SOLVER FINAL ELEMENTS DETECTORS NIAGARA ELECTRIC MONITORS ELECTRIC ACTUATORS VDD DELUGE VALVES
  • 14. ELECTRIC MONITOR NIAGARA SERIES FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 14SIL Suitable Final Elements
  • 15. DESCRIPTION  The fire-fighting monitors Niagara series are electric type remote controlled water cannons, intended to deliver large amount of water towards remote targets. FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 15SIL Suitable Final Elements  The monitor architecture comprises of a Logic Controller and one or more monitor assemblies
  • 16. MAIN FEATURES FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 16SIL Suitable Final Elements  Automatic self-diagnostic analysis  Remote controlled  Designed for sea water and water foam solution  Suitability for SIL2 systems validated by Bureau Veritas
  • 17. ADVANTAGES FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 17SIL Suitable Final Elements Automatic self-diagnostic analysis: at regular intervals the self-diagnostic system in the Logic Controller checks the correct operation on given commands  Constant monitoring of any possible failure of monitor and nozzle  Reduction of the probability that faults, taking place between regular maintenance, will pass undetected  Increased reliability on demand
  • 18. APPLICATION FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 18SIL Suitable Final Elements Designed for petrochemical jetty and marine harbor and structure cooling Recommended for those systems which require:  A low probability of failure on demand  A fire protection system with a high Safety Integrity Level  A large amount of water towards remote targets
  • 19. DOUBLE COIL ELECTRIC ACTUATOR FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 19SIL Suitable Final Elements
  • 20. DESCRIPTION  The double coil electric actuator has been developed to sharply reducing the probability of failure of a pilot cylinder of a gaseous based fire protection system (carbon dioxide, inert gases, halocarbons) or a water mist system SIL Suitable Final Elements FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 20
  • 21. MAIN FEATURES  Redundancy: the actuator has two coils which receive two independent signals from the Logic Solver. If one coil should fail, the other coil is able to open the cylinder valve  Suitability for SIL2 systems validated by Bureau Veritas SIL Suitable Final Elements FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 21
  • 22. APPLICATION Designed for the protection of gas turbines and their generators, electronic rooms and general installations on FPSO Recommended for those systems which require:  A low probability of failure on demand  A fire protection system with a high Safety Integrity Level SIL Suitable Final Elements FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 22
  • 23. DOUBLE CHAMBER DELUGE VALVE MODEL VDD FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 23SIL Suitable Final Elements
  • 24. DESCRIPTION  The VDD deluge valve combines all the functions of a traditional deluge valve with a fully redundant architecture, designed to achieve a higher Safety Availability  The VDD deluge valve has two priming chambers, each one provided with its own diaphragm and trim FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 24SIL Suitable Final Elements
  • 25. PRINCIPLE OF OPERATION  In the set position (valve closed) The pressure of the water trapped in the priming chambers holds the diaphragms on the valve seats, keeping the valve closed  In fire condition (valve open) The pressure is released from the priming chambers. The water supply pressure forces the diaphragm off the seats, opening the valve FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 25SIL Suitable Final Elements
  • 26. MAIN FEATURES  Fully redundant system  Built-in emergency bypass line that operates on both priming chambers in “hot back-up”  Continuous fire protection  Designed to overcome a double failure  Suitability for SIL3 systems validated by Bureau Veritas  Under UL testing for UL/cUL Listing FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 26SIL Suitable Final Elements
  • 27. ADVANTAGES Built-in emergency bypass line  Each priming chamber provides the nominal design waterway for the fire protection system  The system is fully redundant  The time to respond to a failure is reduced to zero  No need of an external bypass line on the skid: reduction of dimensions, weight and cost of the skid FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 27SIL Suitable Final Elements
  • 28. ADVANTAGES Designed to overcome a double failure  A hydraulic bridge between the trims allows each trim to control both the diaphragms  In case of failure of one trim, the other trim can open both the priming chambers  The VDD deluge valve can overcome a double failure FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 28SIL Suitable Final Elements
  • 29. ADVANTAGES FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 29SIL Suitable Final Elements Designed to overcome a double failure  Fault Tree of the VDD deluge valve
  • 30. ADVANTAGES Fire protection system always in service  Two built-in isolation valves allow alternate in-line maintenance to be performed FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 30SIL Suitable Final Elements  An interlock system prevents the accidental or incorrect rotation of the isolation valves
  • 31. APPLICATION  Made of Ni-Al-Bronze, a highly resistant material  Specifically designed for harsh environments, such as oil & gas onshore and offshore and chemical and nuclear plants installations FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 31SIL Suitable Final Elements  Sea water, foam concentrate and water foam solution
  • 32. APPLICATION Recommended for those systems which require:  A low probability of failure on demand  A fire protection system with a high Safety Integrity Level  Continuity of fire protection during maintenance or repair  Reduction of weight, dimension and cost of the skid FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 32SIL Suitable Final Elements