SlideShare ist ein Scribd-Unternehmen logo
1 von 26
Downloaden Sie, um offline zu lesen
ASHRAE Standard 62.1-2010 DCV in Multiple-Zone Systems: Ventilation Reset Control

Agenda


Presenter: Dennis Stanke,          Trane Staff Applications Engineer, FASHRAE


Abstract:
ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality,” provides minimum outdoor airflow
requirements at design conditions. However, ASHRAE Standard 90.1 requires some systems to be operated so
that current ventilation capacity modulates to match current ventilation load (i.e., demand). Standard 62.1
allows optional “dynamic reset” controls to help match current capacity to load, but design details for such
controls are left to the designer. One design approached, described in this presentation, combines ventilation
reset control at the system level with various zone-level “demand controlled ventilation” strategies.



Learning objectives
After viewing this program Participants will be able to:

1. Apply ventilation system design calculations for three ventilation systems: single-zone,
   100% outdoor air, and multiple-zone systems (MZS)
2. Summarize how demand controlled ventilation (DCV) can be incorporated in all three ventilation systems
3. Apply dynamic reset to VAV systems using ventilation reset control, which responds to changes in
   system ventilation efficiency
4. Apply dynamic reset to VAV systems by combining zone-level DCV with system-level ventilation reset
   control, to respond to both changes in zone population and changes in system ventilation efficiency




Agenda

6.2.2 Zone calculations (zone OA)
6.2.3 Single-zone systems (OA intake)
6.2.4 100% OA systems (OA intake)
6.2.5 Multiple-zone recirc systems (OA intake)
6.2.7 Dynamic reset

Wrap-up/discussion
Standard 62.1-2010 DCV in Multiple-Zone Systems
                           Ventilation R
                           V til ti Reset Control
                                         tC t l
                            Dennis Stanke
                            September 2012




                                                                                           Ingersoll Rand




                                                  Standard 62.1-2010 DCV in Multiple-Zone Systems-Ventilation Reset Control: Course ID: 0090008756

                                                  Approved for 1.0 GBCI hours for LEED professionals

                                                                            1.5
                               2   © 2009 Trane




Multiple-Zone Ventilation                                                                                                                            1
© 2012 Trane a business of Ingersoll Rand. All rights reserved
“Trane” is a Registered Provider with The American
                                                         Institute of Architects Continuing Education Systems.
                                                         Credit earned on completion of this program will be
                                                         reported to CES Records for AIA members. Certificates
                                                         of C
                                                           f Completion for non-AIA members are available on
                                                                   l ti f        AIA      b          il bl
                                                         request.

                                                         This program is registered with the AIA/CES for
                                                         continuing professional education. As such, it does not
                                                         include content that may be deemed or construed to be
                                                         an approval or endorsement by the AIA of any material
                                                         of construction or any method or manner of handling,
                                                         using, distributing, or dealing in any material or
                                                         p
                                                         product.




                               3   © 2009 Trane




                                    Visit the Registered Continuing Education
                                    Programs (RCEP) Website to check state
                                    requirements for Professional
                                    Development Hours (PDH) for
                                    professional engineers.

                                                  www.RCEP.net




                               4   © 2009 Trane




Multiple-Zone Ventilation                                                                                          2
© 2012 Trane a business of Ingersoll Rand. All rights reserved
Copyrighted Materials

                             This presentation is protected by U.S. and
                             international copyright laws. Reproduction,
                             distribution, display, and use of the presentation
                             without written permission of Trane is prohibited.
                             © 2012 Trane a business of Ingersoll-Rand All rights reserved.
                                    Trane,              Ingersoll-Rand.           reserved




                               5   © 2009 Trane




                             Learning Objectives
                             After today’s program you will be able to:

                             • Apply ventilation system design calculations for three
                               ventilation systems: single-zone, 100% outdoor air, and
                                            y           g        ,                ,
                               multiple-zone systems (MZS)
                             • Summarize how demand controlled ventilation (DCV) can
                               be incorporated in all three ventilation systems
                             • Apply dynamic reset to VAV systems using ventilation
                               reset control, which responds to changes in system
                               ventilation efficiency
                             • Apply dynamic reset to VAV systems by combining zone-zone
                               level DCV with system-level ventilation reset control, to
                               respond to both changes in zone population and changes
                               in system ventilation efficiency



                               6   © 2009 Trane




Multiple-Zone Ventilation                                                                     3
© 2012 Trane a business of Ingersoll Rand. All rights reserved
Abstract and Venues
                                • Abstract
                                     – ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality,”
                                       p
                                       provides minimum outdoor airflow requirements at design conditions.
                                                                             q                   g
                                       However, ASHRAE Standard 90.1 requires some systems to be
                                       operated so that current ventilation capacity modulates to match
                                       current ventilation load (i.e., demand). Standard 62.1 allows optional
                                       “dynamic reset” controls to help match current capacity to load, but
                                       design details for such controls are left to the designer. One design
                                       approached, described in this presentation, combines ventilation reset
                                       control at the system level with various zone-level “demand controlled
                                       ventilation” strategies.
                                • Venues (1.5 hours)
                                     – 11SEP2012 Richland, WA
                                     – 15SEP2012 Portland, OR




                               7   © 2009 Trane




                             Standard 62.1 Ventilation
                             Why It’s Important …

                              • For comfort – reduce odors and irritation
                              • For health – reduce building related illness and
                                sick building syndrome
                              • For productivity – reduce absenteeism and
                                increase worker satisfaction
                              • For compliance …
                                    –    Section 6.2 (VRP) req’d by IMC and UMC
                                                      (    ) q     y
                                    –    Section 4 thru 8 req’d by Std 189.1 (one IgCC path)
                                    –    Section 4 thru 7 req’d as LEED prerequisite
                                    –    All of Std 62.1 required by ENERGY STAR® and bEQ


                               8   © 2009 Trane




Multiple-Zone Ventilation                                                                                       4
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.0 Procedures

                              • 6.1 General. Find OA intake using VRP or IAQP, or
                                find opening parameters using NVP
                                                         sing
                              • 6.2 Ventilation Rate Procedure
                                      – Prescribes minimum rates for “typical” zones and
                                        calculations for minimum outdoor air intake rate
                              • 6.3 IAQ Procedure
                                      – Specifies performance based on contaminant levels and
                                        subjective evaluation
                               • 6.4 Natural Ventilation Procedure
                                      – Prescribes opening areas and requires both MV and NV


                                 9   © 2009 Trane




                             6.2 Ventilation Rate Procedure

                             •       6.2.1 Outdoor air treatment
                             •       6.2.2 Zone calculations (zone OA)
                             •       6.2.3 Single-zone systems (OA intake)
                             •       6.2.4 100% OA systems (OA intake)
                             •       6.2.5 Multiple-zone recirc systems (OA intake)
                             •       6.2.6 Design for varying operating conditions
                             •       6.2.7
                                     6 2 7 Dynamic reset




                              10     © 2009 Trane




Multiple-Zone Ventilation                                                                       5
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2.2 Zone Calculations                                   design




                              1. Calculate breathing-zone outdoor airflow, using Table
                                 6-1
                                 6 1 rates (Rp cfm/per Ra cfm/ft2)
                                               cfm/per,
                                            Vbz = Rp × Pz + Ra × Az         (Eq 6-1)
                                                   where Pz = peak zone population
                              2. Find zone air distribution effectiveness
                                                     Look up Ez (typically 1.0)   (Tab 6-2)

                              3.
                              3 Calculate zone outdoor airflow
                                                     Voz = Vbz/Ez                 (Eq 6-2)




                              11   © 2009 Trane




                             6.2 Ventilation Rate Procedure

                             •     6.2.1 Outdoor air treatment
                             •     6.2.2 Zone calculations (zone OA)
                             •     6.2.3 Single-zone systems (OA intake)
                             •     6.2.4 100% OA systems (OA intake)
                             •     6.2.5 Multiple-zone recirc systems (OA intake)
                             •     6.2.6 Design for varying operating conditions
                             •     6.2.7
                                   6 2 7 Dynamic reset




                              12   © 2009 Trane




Multiple-Zone Ventilation                                                                       6
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2.3 Single-Zone Systems
                                                  One recirculating air handler
                                                        serves one zone


                                       EA                                  RA



                                     OA                             SA
                                    (Vot)                          (Vpz)
                                                                                zone




                              13   © 2009 Trane




                             6.2.3 Single-Zone Systems                                      design




                             For single-zone systems
                                   – Complete first three steps for zone
                                   – Then, find outdoor air intake flow
                                                     Vot = Voz                         (Eq 6-3)

                             Note:
                                   – No design credit for occupant diversity, i.e., must
                                            g                  p           y
                                     assume peak zone population
                                   – Zone ventilation efficiency (Evz = Voz-actual/Voz-
                                     design) is probably less than 1.0 during operation


                              14   © 2009 Trane




Multiple-Zone Ventilation                                                                            7
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2.3 Single-Zone Systems                                       operation




                             • That’s it for design, but does 62.1-2010 allow
                               intake i fl
                               i t k airflow to vary during operation?
                                             t       d i         ti ?
                             • Of course …
                                   – Section 6.2.7 allows optional dynamic reset of zone
                                     outdoor airflow using various approaches …
                                           Population estimate based on scheduling, occupancy
                                            sensing, people counting
                                           Bio effluent control using CO2-based reset
                                            Bio-effluent                   based
                                   – Read Journal articles for “how-to” ideas




                              15   © 2009 Trane




                                                                                             operation
                             Dynamic Reset Approaches
                             • Section 6.2.7 allows dynamic reset of OA intake
                                   based on operating conditions, including:
                                   – Variations in population – zone-level demand
                                     controlled ventilation (DCV)
                                   – Variations in system ventilation efficiency – system-
                                     level controls required
                             • Different systems use different approaches
                                   – For single-zone systems, use simple zone-level DCV
                                   – For 100% OA systems, use zone-level DCV, but only
                                                    y      ,                   ,        y
                                     in some VAV systems
                                   – For multiple-zone systems, use system-level controls,
                                     which can be combined with zone-level DCV
                             • Some examples …

                              16   © 2009 Trane




Multiple-Zone Ventilation                                                                                8
© 2012 Trane a business of Ingersoll Rand. All rights reserved
single-zone system                                                                operation
                                                   CO2-based Zone-DCV
                                                                Now CO2 varies,
                                                   4800         so DCV isn’t as easy                                          1200
                                                                                                             CO2 varies
                                                                                                             62.1 2007
                                                                                                             62.1-2007
                                                                                                           (Std 62.1-2007)
                          breathing zone OA, Vbz
                                               z




                                                                                                                                     differential CO2, ppm
                                                   4000                                                                       1000

                                                                                                             Vbz = 3900 cfm
                                                   3200                                                                       800

                                                                        CO2 = 700 ppm
                                                   2400                  (Std 62-2001)                                        600
                                                                                                             Vbz = 2190 cfm
                                                   1600                                                                       400
                          b




                                                    800                                                    lecture classroom 200
                                                                                                           Az = 4000 ft2
                                                                                                           design Pz = 260 p
                                                        0                                                                     0
                                                            0          40       80       120      160      200      240
                                                                                     zone population, Pz


                         © 2005 American Standard Inc.

                                                   17   © 2009 Trane




                                                   one way to implement zone-DCV …                                                   operation
                                                   62.1 User’s Manual
                                                   • Find breathing zone OA (Vbz) range
                                                        Vbz
                                                        Vb                  = (R  P + R  A )
                                                                              (Rp Pz Ra Az)
                                                        Vbz-des             = (7.5  260 + 0.06  4000)/1.0 = 2190 cfm
                                                        Vbz-min             = (7.5  0 + 0.06  4000)/1.0 = 240 cfm
                                                   • Find target indoor CO2 (Crz) range
                                                        Crz – Co                    = N/(Vbz/Pz)
                                                        Crz-des – Co            = 0.0105/(2190 cfm/260 p)  1250 ppm
                                                        Crz-min – Co            = 0.000350 – 0.000350  0 ppm
                                                   • The Controller: Match Vbz signal range to Crz range
                                                   • Adjust OA damper to deliver Vot = Vbz-des/Ez at max
                                                        signal, = Vbz-min/Ez at min signal



                                                   18   © 2009 Trane




Multiple-Zone Ventilation                                                                                                                                    9
© 2012 Trane a business of Ingersoll Rand. All rights reserved
zone DCV for single-zone systems                                                  operation
                                                             62.1 User’s Manual

                                                                                                 The Controller
                                                                  2190




                                                               Vbz
                                                              (cfm)



                                                                   240


                                                                           0                                                    1250
                                                                                                    Crz - Co (CO2, ppm)

                                                             19   © 2009 Trane




                                                             zone DCV for single-zone systems                                                  operation
                                                             62.1 User’s Manual
                                                                          Controller adjusts Vbz,
                               hing zone OA, Vbz (=Ez*Vot)




                                                             4800         based on sensed CO2                                          1200
                                                                                                                                               differential CO2, ppm




                                                             4000                                                                       1000

                                                                                                                  CO2
                                                             3200                                                                       800


                                                             2400                                                                       600


                                                             1600                     Vbz                                               400
                          breath




                                                              800                                                      lecture classroom 200
                                                                                                                       Az = 4000 ft2
                                                                                                                       design Pz = 260 p
                                                                  0                                                                     0
                                                                      0          40         80       120      160      220      240
                                                                                                 zone population, Pz


                         © 2005 American Standard Inc.

                                                             20   © 2009 Trane




Multiple-Zone Ventilation                                                                                                                                              10
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2 Ventilation Rate Procedure

                             •     6.2.1 Outdoor air treatment
                             •     6.2.2 Zone calculations (zone OA)
                             •     6.2.3 Single-zone systems (OA intake)
                             •     6.2.4 100% OA systems (OA intake)
                             •     6.2.5 Multiple-zone recirc systems (OA intake)
                             •     6.2.6 Design for varying operating conditions
                             •     6.2.7
                                   6 2 7 Dynamic reset




                              21   © 2009 Trane




                             6.2.4 100% OA Systems                                  design



                                          One non-recirculating air handler
                                                serves many zones


                              EA                                 Voz

                               OA                                      zone
                              (Vot)                                            SA
                                                                 CA
                                                                          RA

                                                                 Voz

                                                                       zone
                                                                               SA


                                                                          RA



                              22   © 2009 Trane




Multiple-Zone Ventilation                                                                    11
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2.4 100% OA Systems                                             design




                             For 100% OA systems
                                   – Complete first three steps for each zone
                                   – Then, find outdoor air intake flow
                                                     Vot = Voz                          (Eq 6-4)

                             Note:
                                   – No design credit for occupant diversity, i.e., must
                                            g                  p           y
                                     assume peak zone population in each zone
                                   – Zone ventilation efficiency (Evz = ΣVoz-actual/ΣVoz-
                                     design) is probably less than 1.0 during operation


                              23   © 2009 Trane




                             6.2.4 100% OA Systems                                            operation




                             • That’s it for design but does 62.1-2007 allow
                               intake i fl
                               i t k airflow to vary during operation?
                                             t       d i         ti ?
                             • Well, that depends …
                                   – Section 6.2.7 allows optional dynamic reset, but …
                                           For constant volume OA systems there’s no way to reset
                                            outdoor airflow
                                           For VAV OA systems, intake airflow can be reduced if
                                             – All zones i l d pressure-independent d
                                                          include       i d      d t dampers
                                             – DCV zones include DCV sensors and controls
                                             – The 100% OA unit includes VAV controls



                              24   © 2009 Trane




Multiple-Zone Ventilation                                                                                 12
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2 Ventilation Rate Procedure

                             •     6.2.1 Outdoor air treatment
                             •     6.2.2 Zone calculations (zone OA)
                             •     6.2.3 Single-zone systems (OA intake)
                             •     6.2.4 100% OA systems (OA intake)
                             •     6.2.5 Multiple-zone recirc systems (OA intake)
                             •     6.2.6 Design for varying operating conditions
                             •     6.2.7
                                   6 2 7 Dynamic reset




                              25   © 2009 Trane




                             6.2.5 Multiple-Zone Systems
                                                  One recirculating air handler
                                                       serves many zones
                                                                   RA

                              EA
                                                                   Vpz
                                                                          space

                                  OA
                                 (Vot)                             SA
                                                                  (Vps)


                                    Single-path system (dual-             space
                                    path is more complex)

                              26   © 2009 Trane




Multiple-Zone Ventilation                                                           13
© 2012 Trane a business of Ingersoll Rand. All rights reserved
design
                               6.2.5 Multiple-Zone Systems

                              For multiple-zone recirculating systems, complete first three
                                  steps for each zone then solve MZS equations:
                                                 zone,

                              4. Find primary outdoor air fraction, Zp
                                           Zp = Voz/Vpz-min                            (6-5)
                              5. Find uncorrected outdoor airflow, Vou
                                           Vou = D*(Rp×Pz) + (Ra×Az)               (6-6)
                              6. Find
                              6 Fi d system ventilation efficiency, E
                                         t        til ti   ffi i    Ev
                                           Calculate Ev per equations                  (App A)
                              7. Find outdoor air intake flow, Vot:
                                           Vot = Vou/Ev                                (6-8)

                              27   © 2009 Trane




                             6.2.5 Multiple-Zone Systems                                       design




                             4. Find primary outdoor air fraction for each zone or
                                   each critical zone
                                              Zp = Voz/Vpz                             (Eq 6-5)
                             Note:
                                   –  Vpz = Vpz-design = minimum primary airflow expected at
                                      “ventilation design” condition (usually higher than minimum
                                      box setting)
                                   – Picking Vpz-design - probably most confusing part for MZS
                                               Vpz design
                                      Many use minimum box setting – easy but conservative
                                      Some use 8760 simulation to find an accurate value
                                         (Maybe Std 62.1 should use 0.5*Vpz-design as default)
                                      NOTE: “ventilation design” ≠ “thermal design”

                              28   © 2009 Trane




Multiple-Zone Ventilation                                                                               14
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2.5 Multiple-Zone Systems                                        design




                             5. Find uncorrected outdoor airflow
                                   Vou = D*(R P ) + (R A )
                                   V        (Rp×Pz)    (Ra×Az)                    (Eq 6-6)
                                                                                  (E 6 6)
                             Note:
                                   –       Design credit for occupant diversity (D)
                                   –       D = expected population/sum-of-peak populations
                                             = 50 people/100 chairs = 0.5
                                   –       Occupant diversity reduces
                                           uncorrected outdoor airflow




                              29   © 2009 Trane




                             6.2.5 Multiple-Zone Systems                                        design




                             6. Find system ventilation efficiency
                                   – Fi t find average outdoor air f ti (Xs) using
                                     First, fi d          td     i fraction (X ) i
                                     system primary airflow (Vps) at ventilation design
                                              Xs = Vou/Vps                               (Eq A-1)
                                   – Then, find zone ventilation efficiency (Evz)
                                               Evz = 1 + Xs – Zpz                     (Eq A-2)
                                   – Finally, lowest Evz is system ventilation efficiency (Ev)
                                               Ev = min(Evz)                          (Eq A-8)
                             Note:
                                   –       Lowest Evz defines the “critical zone” for ventilation


                              30   © 2009 Trane




Multiple-Zone Ventilation                                                                                15
© 2012 Trane a business of Ingersoll Rand. All rights reserved
6.2.5 Multiple-Zone Systems                                    design




                             7. Find outdoor air intake flow
                                                     Vot Vou/Ev
                                                     V t = V /E                     (Eq 6-8)
                                                                                    (E 6 8)


                             Note:
                                   –       Compared to 2001, the 2010 rates and equations
                                           reduce intake airflow (Vot) for many systems




                              31   © 2009 Trane




                             6.2 Ventilation Rate Procedure

                             •     6.2.1 Outdoor air treatment
                             •     6.2.2 Zone calculations (zone OA)
                             •     6.2.3 Single-zone systems (OA intake)
                             •     6.2.4 100% OA systems (OA intake)
                             •     6.2.5 Multiple-zone recirc systems (OA intake)
                             •     6.2.6 Design for varying operating conditions
                             •     6.2.7
                                   6 2 7 Dynamic reset




                              32   © 2009 Trane




Multiple-Zone Ventilation                                                                            16
© 2012 Trane a business of Ingersoll Rand. All rights reserved
Multiple-Zone Systems                                                operation




                             • That’s it for MZS design but can intake flow vary
                               during
                               d i operation?
                                        ti ?
                             • Sure
                                   – Provided Section 5.3.1 (no less than required Vot
                                     under all “operating” conditions) is met …
                                   – Section 6.2.7 allows optional dynamic reset, regardless
                                     of system type
                             • But how do you do it in a VAV system?




                              33   © 2009 Trane




                             Dynamic Reset Approaches                                             operation




                             • Already reviewed for single zone and 100% OA
                             • For VAV MZS operation, you could …
                                   – Use “ventilation reset control” (VRC)
                                           Reset intake flow based only on changes in system
                                            ventilation efficiency (Ev) due to changes in zone airflow
                                   – Combine system-level VRC with zone-level DCV
                                           Reset intake flow based on changes in system ventilation
                                            efficiency due to changes in both zone airflow and
                                            population
                                   – Use system-level DCV of some sort
                                           Approaches not well-known, but hopefully Dr. Lau’s
                                            research addresses this

                              34   © 2009 Trane




Multiple-Zone Ventilation                                                                                     17
© 2012 Trane a business of Ingersoll Rand. All rights reserved
Ventilation Reset Control                                                            operation




                             • VRC resets system-level outdoor air intake flow
                                   (Vot) t
                                   (V t) at part l d conditions by:
                                               t load   diti    b
                                   – Assuming design population in all zones without
                                     accounting for reduced population in any zone
                                   – Accounting for changes in system ventilation efficiency
                                     (Ev) due to zone and system airflow changes
                                   – Solving the MZS equations in real time (quasi-steady
                                     state) to find current intake flow (Vot) set point required
                             • Here’s an example building using one possible
                                   VRC approach


                              35   © 2009 Trane




                           VRC w/o Zone-Level DCV                                                                   design


                                                                                                     Vot
                                                                                                    req’d
                                                                                                   @ design
                           Single Supply
                           Single-Supply VAV System: Ventilation Design
                           population       Pz       140     140     260     260     5    40        8, 810
                           prim airflow     Vpz    6,500   6,700   5,500   7,900   500 1,700
                           min expect       Vpzm   4,000   4,000   4,000   4,000   300 1,300
                           vent rate        Vbz    1,880   1,880   2,190   2,190    85   760
                           vent fract       Zpz    0.470   0.470   0.548   0.548 0.283 0.585
                             Ventilation design - For each zone use:         Then, find:
                                 Pz = peak zone population                      Vou = D*Rp*Pz + Ra*Az               (5)
                                 Vpz = peak primary airflow                                D = Ps/Pz = 550/845 = 0.65
                                 Vpzm = minimum expected Vpz @ design                  = 0.65*7,130 + 1,860 = 6,500
                             Then,
                             Then find:                                         Ev = min(Evz)                (6)
                                 Vbz = Rp*Pz + Ra*Az                 (1)               Vps = LDF*ΣVpz
                                 Ez = design zone air dist eff       (2)                       = 0.7*28,800 = 20,200
                                 Voz = Vbz/Ez                        (3)               Xs = Vou/Vps
                                 Zpz = Voz/Vpzm = Vbz/(Ez*Vpzm)      (4)                   = 6,500/20,200 = 0.322
                                                                                       Evz = 1+ Xs – Zpz
                             For the system use:                                               = 1 + 0.322 – 0.585 = 0.738
                                  Ps = highest system population = 550                 = min(Evz) = 0.738
                                  LDF= load diversity factor = 0.7              Vot = Vou/Ev = 6,500/0.738 = 8,810 (7)
                              36   © 2009 Trane




Multiple-Zone Ventilation                                                                                                     18
© 2012 Trane a business of Ingersoll Rand. All rights reserved
VRC w/o Zone-Level DCV                                                               operation


                                                                                                   Vot       Vot
                                                                                                  req’d     req’d
                                                                                                 @ design (current)
                           Single Supply
                           Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps)
                                                                                 Friday,
                           population Pz       140   140   260   260     5    40   8, 810  8, 390
                           prim airflow Vpz 4,960 5,000 4,000 4,000    500 1,700
                           vent rate     Vbz 1,880 1,880 2,190 2,190    85   760
                           vent fraction Zdz 0.379 0.376 0.548 0.548 0.170 0.447

                             Operation w/o DCV: For each zone use:          Now, controls calculate:
                                Pz = peak zone population (entry)              Vou = D*Rp*Pz + Ra*Az              (5)
                             Then, controls determine or calculate:                      D = Ps/Pz = 550/845 = 0.65
                                Vpz = current primary airflow (sensed)              = 0.65*7,130 + 1,860 = 6,500
                                Vbz = Rp*Pz + Ra*Az (calc or entry) (1)
                                       Rp Pz Ra Az                             Ev = min(Evz)               (6)
                                Ez = current value                    (2)           Vps = Vpz
                                Voz = Vbz/Ez                          (3)                     = 20,200
                                Zpz = Voz/Vpz                         (4)           Xs = Vou/Vps
                                                                                              = 6,500/20,200 = 0.322
                                                                                    Evz = 1+ Xs – Zpz
                             For the system use:                                             = 1 + 0.322 – 0.548 = 0.775
                                  Ps = highest system population = 550              = min(Evz) = 0.775
                                  LDF= load diversity factor = 0.7             Vot = Vou/Ev = 6,500/0.775 = 8,390 (7)
                              37   © 2009 Trane




                           VRC w/o Zone-Level DCV                                                               operation


                                                                                                   Vot       Vot
                                                                                                  req’d     req’d
                                                                                                 @ design (current)
                           Single Supply
                           Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps)
                                                                                 Friday,
                           population Pz       140   140   260   260     5    40   8, 810  8, 390
                           prim airflow Vpz 4,960 5,000 4,000 4,000    500 1,700
                           vent rate     Vbz 1,880 1,880 2,190 2,190    85   760
                           vent fraction Zdz 0.379 0.376 0.548 0.548 0.170 0.447
                                                                                                    Vot-actual is less
                             Operation w/o DCV: For each zone use:          Now, controls calculate: than Vot-design
                                 Pz = peak zone population (entry)             Vou = D*Rp*Pz + Ra*Az              (5)
                             Then, controls determine or calculate:                      D = Ps/Pz = 550/845 = 0.65
                                 Vpz = current primary airflow (sensed)             = 0.65*7,130 + 1,860 = 6,500
                                 Vbz = Rp*Pz + Ra*Az (calc or entry)w/o DCV Ev = min(Evz)
                                       Rp Pz Ra Az             VRC (1)         reduces                     (6)
                                 Ez = current value             required Vot, even at Vpz
                                                                       (2)          Vps =
                                 Voz = Vbz/Ez                          (3)                    = 20,200
                                 Zpz = Voz/Vpz                   100%(4)thermal load:= Vou/Vps
                                                                                    Xs
                                                               Ev-actual ≥ Ev-design = 6,500/20,200 = 0.322
                                                                                    Evz = 1+ Xs – Zpz
                             For the system use:                                             = 1 + 0.322 – 0.548 = 0.775
                                  Ps = highest system population = 550              = min(Evz) = 0.775
                                  LDF= load diversity factor = 0.7             Vot = Vou/Ev = 6,500/0.775 = 8,390 (7)
                              38   © 2009 Trane




Multiple-Zone Ventilation                                                                                                   19
© 2012 Trane a business of Ingersoll Rand. All rights reserved
VRC w/o Zone-Level DCV                                                 operation


                                                                                        Vot       Vot
                                                                                       req’d     req’d
                                                                                      @ design (current)
                           Single Supply
                           Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps)
                                                                                 Friday,
                           population Pz       140   140   260   260     5    40   8, 810  8, 390
                           prim airflow Vpz 4,960 5,000 4,000 4,000    500 1,700
                           vent rate     Vbz 1,880 1,880 2,190 2,190    85   760
                           vent fraction Zpz 0.379 0.376 0.548 0.548 0.170 0.447

                           Single-Supply VAV System: 90% Thermal Load (1:00 pm Monday, perhaps)
                           population Pz       140   140   260    260     5    40 8,810    7,780
                           prim airflow Vpz 4,000 3,700 4,200 4,300     300 1,700
                           vent rate     Vbz 1,880 1,880 2,190 2,190     85   760
                           vent fraction Zpz 0 470 0 508 0 521 0 509 0 283 0 447
                                             0.470 0.508 0.521 0.     0.283 0.447

                          Now, controls determine or calculate:                VRC w/o DCV reduces
                             Vou = D*Rp*Pz + Ra*Az = 6,500                  required Vot even more
                             Vpz = (sensed)
                             Vps = Vpz = 18,200                              at lower thermal loads:
                             Xs = Vou/Vps = 6,500/18,200 = 0.357              Ev-actual >> Ev-design
                             Ev = 1 + 0.357 – 0.521 = 0.836
                             Vot = Vou/Ev = 6,500/0.836 = 7,780
                              39   © 2009 Trane




                             Dynamic Reset Approaches                                             operation




                             • Already reviewed for single zone and 100% OA
                             • For VAV MZS operation, you could …
                                   – Use “ventilation reset control” (VRC)
                                           Reset intake flow based only on changes in system
                                            ventilation efficiency (Ev) due to changes in zone airflow
                                   – Combine system-level VRC with zone-level DCV
                                           Reset intake flow based on changes in system ventilation
                                            efficiency due to changes in both zone airflow and
                                            population
                                   – Use system-level DCV of some sort
                                           Approaches not well-known, but hopefully Dr. Lau’s
                                            research addresses this

                              40   © 2009 Trane




Multiple-Zone Ventilation                                                                                     20
© 2012 Trane a business of Ingersoll Rand. All rights reserved
VRC with Zone-Level DCV                                        operation




                             • VRC resets system-level outdoor air intake flow
                                   (Vot) t
                                   (V t) at part l d conditions by:
                                               t load   diti    b
                                   – Assuming design population in non-DCV zones while
                                     accounting for reduced population in DCV zones
                                   – Accounting for changes in system ventilation efficiency
                                     (Ev) due to zone and system airflow changes
                                   – Solving the MZS equations in real time (quasi-steady
                                     state) to find current intake flow (Vot) set point required
                             • Here’s the same example building using the same
                                   VRC approach, but with various “zone types”
                                   including both non-DCV and DCV zones

                              41   © 2009 Trane




                             VRC w/Zone-Level DCV                                           operation




                             • Defining zone types
                                   – Z
                                     Zones without DCV
                                            ith t
                                           Non-DCV zones (NON): Pz = peak zone population at all
                                            conditions, regardless of actual population
                                   – Population-estimating DCV zones (EST) include:
                                           “Time-of-day” zones (TOD): Pz = predicted population
                                           “Occupied/unoccupied” (OCC) zones: Pz = peak or zero
                                            population, depending on occupancy sensor
                                           “Count” zones (COU): Pz = sensed number of occupants
                                   – CO2-based DCV zones (CO2) (Pz = unknown)
                                           Breathing-zone OA flow depends on sensed difference
                                            between primary and zone CO2: Vbz = f (ΔCO2)

                              42   © 2009 Trane




Multiple-Zone Ventilation                                                                               21
© 2012 Trane a business of Ingersoll Rand. All rights reserved
VRC w/ Zone-Level DCV                                                                      design


                                                                                                      Vot
                                                    NON     NON     CO2      NON    NON     EST      req’d
                                                                                                    @ design
                           Single Supply
                           Single-Supply VAV System: Design Ventilation
                           population       Pz       140     140     260     260     5    40          8, 810
                           prim airflow     Vpz    6,500   6,700   5,500   7,900   500 1,700
                           min expect       Vpzm   4,000   4,000   4,000   4,000   300 1,300
                           vent rate        Vbz    1,880   1,880   2,190   2,190    85   760            DCV: No impact
                           vent fract       Zpz    0.470   0.470   0.548   0.548 0.283 0.585             on Vot-design
                             Design ventilation: For each zone use:           Then, find:
                                 Pz = peak zone population                       Vou = D*Rp*Pz + Ra*Az               (5)
                                 Vpz = peak primary airflow                                 D = Ps/Pz = 550/845 = 0.65
                                 Vpzm = minimum expected Vpz @ design                   = 0.65*7,130 + 1,860 = 6,500
                             Then,
                             Then find:                                          Ev = min(Evz)                (6)
                                 Vbz = Rp*Pz + Ra*Az                (1)                 Vps = LDF*ΣVpz
                                 Ez = design zone air dist eff      (2)                         = 0.7*28,800 = 20,200
                                 Voz = Vbz/Ez                       (3)                 Xs = Vou/Vps
                                 Zpz = Voz/Vpzm = Vbz/(Ez*Vpzm)     (4)                     = 6,500/20,200 = 0.322
                                                                                        Evz = 1+ Xs – Zpz
                             For the system use:                                                = 1 + 0.322 – 0.585 = 0.738
                                  Ps = highest system population = 550                  = min(Evz) = 0.738
                                  LDF= load diversity factor = 0.7               Vot = Vou/Ev = 6,500/0.738 = 8,810 (7)
                              43   © 2009 Trane




                           VRC w/ Zone-Level DCV                                                                    operation


                                                                                                      Vot       Vot
                                                    NON     NON     CO2      NON    NON     EST      req’d     req’d
                                                                                                    @ design (current)
                           Single Supply
                           Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps)
                                                                                 Friday,
                           population Pz       140   140   ???    260    5     0   8, 810  8, 390
                           prim airflow Vpz 4,960 5,400 4,000 4,000    500 1,300            8, 030
                           vent rate     Vbz 1,880 1,880 1,300 2,190    85   360
                           vent fraction Zpz 0.379 0.348 0.325 0.548 0.170 0.277

                             For each NON-DCV zone use:                       Now, for system:
                                 Pz = peak zone population         (entry)      Vou = D*NONRp*Pz + NONRa*Az             (5)
                                 Vbz = Rp*Pz + Ra*Az               (entry)             + ESTRp*Pz + ESTRa*Az + CO2Vbz
                             For each EST-DCV zone:                                  Ps = highest system population = 550
                                 Pz = estimated population      (sensed)             D = Ps/Pz-peak = 550/845 = 0.65
                                 Vbz Rp*Pz Ra*Az
                                 Vb = R *P + R *A                   (calc)
                                                                    ( l )            = 0.65*4,780 + 1,260 + 0 + 360 + 1,300
                                                                                            *
                             For each CO2-DCV zone use:                              = 6,030
                                 Vbz = f (ΔCO2)            (sense & calc)       Ev = min(Evz)                    (6)
                             For each zone, controls determine:                      Vps = Vpz = 20,200              (calc)
                                 Vpz = current zone primary     (sensed)             Xs = Vou/Vps = 6,030/20,200 = 0.299
                                 Vbz = current reqmt (entry or calc) (1)             Evz = 1 + Xs – Zpz
                                 Ez = current value                    (2)                 = 1 + 0.299 – 0.548 = 0.751
                                 Voz = Vbz/Ez                          (3)      Vot = small(Vou/Ev or Vot-des)           (7)
                                 Zpz = Voz/Vpz                         (4)           = 6,030/0.751 = 8,030
                              44   © 2009 Trane




Multiple-Zone Ventilation                                                                                                       22
© 2012 Trane a business of Ingersoll Rand. All rights reserved
VRC w/ Zone-Level DCV                                                                   operation


                                                                                                      Vot       Vot
                                                   NON      NON   CO2        NON   NON      EST      req’d     req’d
                                                                                                    @ design (current)
                           Single Supply
                           Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps)
                                                                                 Friday,
                           population Pz       140   140   ???    260    5     0   8, 810  8, 390
                           prim airflow Vpz 4,960 5,400 4,000 4,000    500 1,300            8, 030
                           vent rate     Vbz 1,880 1,880 1,300 2,190    85   360
                           vent fraction Zpz 0.379 0.348 0.325 0.548 0.170 0.277

                             For each NON-DCV zone use:                       Now, for system:         VRC w/DCV
                                 Pz = peak zone population         (entry)                        reduces Vot-actual
                                                                                Vou = D*NONRp*Pz + NONRa*Az             (5)
                                 Vbz = Rp*Pz + Ra*Az               (entry)             + ESTRp*Pz + ESTRa*Az + CO2Vbz
                             For each EST-DCV zone:                                  Ps = highest system population = 550
                                 Pz = estimated population      (sensed)             D = Ps/Pz-peak = 550/845 = 0.65
                                 Vbz Rp*Pz Ra*Az
                                 Vb = R *P + R *A                   (calc)
                                                                    ( l )            = 0.65*4,780 + 1,260 + 0 + 360 + 1,300
                                                                                            *
                             For each CO2-DCV zone use:                              = 6,030
                                 Vbz = f (ΔCO2)            (sense & calc)       Ev = min(Evz)                    (6)
                             For each zone, controls determine:                      Vps = Vpz = 20,200              (calc)
                                 Vpz = current zone primary     (sensed)             Xs = Vou/Vps = 6,030/20,200 = 0.299
                                 Vbz = current reqmt (entry or calc) (1)             Evz = 1 + Xs – Zpz
                                 Ez = current value                    (2)                 = 1 + 0.299 – 0.548 = 0.751
                                 Voz = Vbz/Ez                          (3)      Vot = small(Vou/Ev or Vot-des)           (7)
                                 Zpz = Voz/Vpz                         (4)           = 6,030/0.751 = 8,030
                              45   © 2009 Trane




                             VRC w/ Zone-Level DCV                                                                 operation




                                   – For design, note:
                                           D = P /ALLP
                                                 Ps/ Pz-peak, bk because occupant diversity
                                                                                    t di    it
                                            distributes total population among all zones in system
                                           D applies to all zones for design
                                   – For operation, note:
                                           D applies NON-DCV zones (occupant diversity credit)
                                           D = 1.0 for EST-DCV zones (estimated Pz is independent
                                            of occupant diversity)
                                                    p            y)
                                           D isn’t used for CO2-DCV zones (Vbz is determined by
                                            controller, without regard to occupant diversity
                                           Rule: To assure adequate heat/cool capacity, Vot during
                                            operation must never be greater than Vot at design


                              46   © 2009 Trane




Multiple-Zone Ventilation                                                                                                       23
© 2012 Trane a business of Ingersoll Rand. All rights reserved
VRC w/ Zone-Level DCV                                                        operation



                                                                                               Vot       Vot
                                                   NON      NON    CO2    NON   NON    EST    req’d     req’d
                                                                                             @ design (current)
                           Single Supply
                           Single-Supply VAV System: 100%Thermal Load (2:00 pm Friday perhaps)
                                                                                 Friday,
                           population Pz       140   140   ???   260     5     0   8, 810 8, 030
                           prim airflow Vpz 4,960 5,400 4,000 4,000    500 1,300
                           vent rate     Vbz 1,880 1,880 1,300 2,190    85   360
                           vent fraction Zpz 0.379 0.348 0.325 0.548 0.170 0.277

                           Single-Supply VAV System: 90% Thermal Load (1:00 pm Monday, perhaps)
                           population Pz       140   140    ???   260     5     0 8,810    7,780
                           prim airflow Vpz 4,000 3,700 4,200 4,300     300 1,700           7,440
                           vent rate     Vbz 1,880 1,880 1,300 2,190     85   360
                           vent fraction Zpz 0 470 0 508 0 521 0 509 0 283 0 447
                                             0.470 0.508 0.521 0.     0.283 0.447

                              Now:                                                    VRC with DCV reduces
                                 Vou     = 6,030
                                 Vps     = Vpz = 18,200                              Vot-actual more, saves
                                 Xs      = 6,030/18,200 = 0.331                            more energy
                                 Ev      = 1 + 0.331 – 0.521 = 0.810
                                 Vot     = Vou/Ev = 6,030/0.810 = 7,440

                              47   © 2009 Trane




                             Implementation

                             • For VRC alone or combined with zone-level DCV,
                                   design
                                   d i usually includes:
                                           ll i l d
                                   –    Communicating DDC-VAV boxes
                                   –    BAS with equation-solving capability
                                   –    Intake-airflow sensing and control at the AHU
                                   –    Building pressure control (which limits Vot reduction)
                             • Remember:
                                   – Std 62.1 allows DCV in any system
                                   – Std 90.1 requires DCV in 40 p/1000 ft2 zones
                                   – Std 189.1 requires DCV in 25 p/1000 ft2 zones


                              48   © 2009 Trane




Multiple-Zone Ventilation                                                                                           24
© 2012 Trane a business of Ingersoll Rand. All rights reserved
Quick Summary

                             Dynamic reset depends on ventilation system type
                                   – Single-zone systems (no design population diversity)
                                           Optional zone DCV allowed
                                   – 100% OA systems (no design population diversity)
                                           CV: Zone DCV & Vot reset not useful w/constant Vot
                                           VAV: Zone DCV & Vot reset allowed but not cheap
                                   – Multiple-zone sys (population diversity design credit):
                                           Optional system Vot reset allowed
                                             – Based only on system ventilation efficiency (VRC)
                                             – Based on zone DCV combined with system VRC
                                             – Based only on zone DCV (not covered)


                              49   © 2009 Trane




                             Thanks

                             Any questions?




                                                             Dennis Stanke
                                                           dstanke@trane.com


                              50   © 2009 Trane




Multiple-Zone Ventilation                                                                          25
© 2012 Trane a business of Ingersoll Rand. All rights reserved

Weitere ähnliche Inhalte

Was ist angesagt?

Secador Industrial (dryer)
Secador Industrial (dryer)Secador Industrial (dryer)
Secador Industrial (dryer)Ramón López
 
6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt
6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt
6046863-Psicrometria-y-Acondicionamiento-de-Aire.pptJuancho Solis
 
refrigeration and air conditioning
refrigeration and air conditioningrefrigeration and air conditioning
refrigeration and air conditioningGear Abohar
 
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANTROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANTGaurav Rai
 
Compressor and compressed_air_systems
Compressor and compressed_air_systemsCompressor and compressed_air_systems
Compressor and compressed_air_systemsGoa App
 
EVAPORATOR.pptx
EVAPORATOR.pptxEVAPORATOR.pptx
EVAPORATOR.pptxMrman210
 
2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...
2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...
2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...Komandur Sunder Raj, P.E.
 
ME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTES
ME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTESME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTES
ME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTESBIBIN CHIDAMBARANATHAN
 
Research proposal: Thermoelectric cooling in electric vehicles
Research proposal: Thermoelectric cooling in electric vehicles Research proposal: Thermoelectric cooling in electric vehicles
Research proposal: Thermoelectric cooling in electric vehicles KristopherKerames
 
Teknik refrigerasi
Teknik refrigerasiTeknik refrigerasi
Teknik refrigerasifaoeziku
 
Chapter (5) gas turbine power plants
Chapter (5) gas turbine power plantsChapter (5) gas turbine power plants
Chapter (5) gas turbine power plantsAzam Ali
 
Basic controls for boilers
Basic controls for boilersBasic controls for boilers
Basic controls for boilersAasheesh Tandon
 

Was ist angesagt? (20)

Joule thomson
Joule thomsonJoule thomson
Joule thomson
 
Secador Industrial (dryer)
Secador Industrial (dryer)Secador Industrial (dryer)
Secador Industrial (dryer)
 
6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt
6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt
6046863-Psicrometria-y-Acondicionamiento-de-Aire.ppt
 
refrigeration and air conditioning
refrigeration and air conditioningrefrigeration and air conditioning
refrigeration and air conditioning
 
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANTROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
ROLE OF CONTROL AND INSTRUMENTATION IN THERMAL POWER PLANT
 
Steam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvementSteam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvement
 
Fuel cell
Fuel cellFuel cell
Fuel cell
 
Compressor and compressed_air_systems
Compressor and compressed_air_systemsCompressor and compressed_air_systems
Compressor and compressed_air_systems
 
EVAPORATOR.pptx
EVAPORATOR.pptxEVAPORATOR.pptx
EVAPORATOR.pptx
 
steam generator
steam generatorsteam generator
steam generator
 
2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...
2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...
2007 ASME Power Conference Troubleshooting Condenser Vacuum Issues At North O...
 
Hrsg book
Hrsg bookHrsg book
Hrsg book
 
ME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTES
ME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTESME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTES
ME6301 ENGINEERING THERMODYNAMICS - LECTURE NOTES
 
Research proposal: Thermoelectric cooling in electric vehicles
Research proposal: Thermoelectric cooling in electric vehicles Research proposal: Thermoelectric cooling in electric vehicles
Research proposal: Thermoelectric cooling in electric vehicles
 
Torres de enfriamiento
Torres de enfriamientoTorres de enfriamiento
Torres de enfriamiento
 
Properties of steam (2)
Properties of steam (2)Properties of steam (2)
Properties of steam (2)
 
Teknik refrigerasi
Teknik refrigerasiTeknik refrigerasi
Teknik refrigerasi
 
Chapter (5) gas turbine power plants
Chapter (5) gas turbine power plantsChapter (5) gas turbine power plants
Chapter (5) gas turbine power plants
 
Pompa kompresor
Pompa kompresorPompa kompresor
Pompa kompresor
 
Basic controls for boilers
Basic controls for boilersBasic controls for boilers
Basic controls for boilers
 

Ähnlich wie Standard 62.1: A VAV Dynamic Reset Approach

High Performance Buidlings for Brazil
High Performance Buidlings for BrazilHigh Performance Buidlings for Brazil
High Performance Buidlings for Brazilsekkelww
 
Avoiding Soot Formation at Fuel Injector Tip
Avoiding Soot Formation at Fuel Injector TipAvoiding Soot Formation at Fuel Injector Tip
Avoiding Soot Formation at Fuel Injector TipMetis Partners
 
Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...
Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...
Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...McKenney's Inc
 
4th Annual Wind Operations and Maintenance Summit USA 2012
4th Annual Wind Operations and Maintenance Summit USA 20124th Annual Wind Operations and Maintenance Summit USA 2012
4th Annual Wind Operations and Maintenance Summit USA 2012Jon Harman, Wind Energy Update
 
Lennox -- Helping HVAC Professionals Take the "LEED"
Lennox -- Helping HVAC Professionals Take the "LEED"Lennox -- Helping HVAC Professionals Take the "LEED"
Lennox -- Helping HVAC Professionals Take the "LEED"STACY DAVIS
 
Ppt3 london - sophia ( operation intelligence ) what is the eu code of conduct
Ppt3   london - sophia ( operation intelligence ) what is the eu code of conductPpt3   london - sophia ( operation intelligence ) what is the eu code of conduct
Ppt3 london - sophia ( operation intelligence ) what is the eu code of conductJISC's Green ICT Programme
 
Deployment Strategy PowerPoint Presentation Slides
Deployment Strategy PowerPoint Presentation SlidesDeployment Strategy PowerPoint Presentation Slides
Deployment Strategy PowerPoint Presentation SlidesSlideTeam
 
Deployment Strategies Powerpoint Presentation Slides
Deployment Strategies Powerpoint Presentation SlidesDeployment Strategies Powerpoint Presentation Slides
Deployment Strategies Powerpoint Presentation SlidesSlideTeam
 
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...Pieter Jan Jordaens
 
Tcom Maint Operate
Tcom Maint OperateTcom Maint Operate
Tcom Maint Operateguest27036c7
 
Siemens Innovation Tools2010
Siemens Innovation Tools2010Siemens Innovation Tools2010
Siemens Innovation Tools2010Kirkdx
 
IRJET- Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...
IRJET-  	  Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...IRJET-  	  Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...
IRJET- Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...IRJET Journal
 

Ähnlich wie Standard 62.1: A VAV Dynamic Reset Approach (20)

High Performance Buidlings for Brazil
High Performance Buidlings for BrazilHigh Performance Buidlings for Brazil
High Performance Buidlings for Brazil
 
Avoiding Soot Formation at Fuel Injector Tip
Avoiding Soot Formation at Fuel Injector TipAvoiding Soot Formation at Fuel Injector Tip
Avoiding Soot Formation at Fuel Injector Tip
 
Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...
Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...
Warner Robins Air Logistics Center Strives for Energy Efficiency : Energy Ser...
 
Dcb 949
Dcb 949Dcb 949
Dcb 949
 
Tcom Energyfinal
Tcom EnergyfinalTcom Energyfinal
Tcom Energyfinal
 
Tcom Maint Operate
Tcom Maint OperateTcom Maint Operate
Tcom Maint Operate
 
4th Annual Wind Operations and Maintenance Summit USA 2012
4th Annual Wind Operations and Maintenance Summit USA 20124th Annual Wind Operations and Maintenance Summit USA 2012
4th Annual Wind Operations and Maintenance Summit USA 2012
 
ODAES brochure
ODAES brochureODAES brochure
ODAES brochure
 
Lennox -- Helping HVAC Professionals Take the "LEED"
Lennox -- Helping HVAC Professionals Take the "LEED"Lennox -- Helping HVAC Professionals Take the "LEED"
Lennox -- Helping HVAC Professionals Take the "LEED"
 
Ppt3 london - sophia ( operation intelligence ) what is the eu code of conduct
Ppt3   london - sophia ( operation intelligence ) what is the eu code of conductPpt3   london - sophia ( operation intelligence ) what is the eu code of conduct
Ppt3 london - sophia ( operation intelligence ) what is the eu code of conduct
 
Deployment Strategy PowerPoint Presentation Slides
Deployment Strategy PowerPoint Presentation SlidesDeployment Strategy PowerPoint Presentation Slides
Deployment Strategy PowerPoint Presentation Slides
 
Deployment Strategies Powerpoint Presentation Slides
Deployment Strategies Powerpoint Presentation SlidesDeployment Strategies Powerpoint Presentation Slides
Deployment Strategies Powerpoint Presentation Slides
 
About TBA - PT Toyosae Berkah Abadi
About TBA - PT Toyosae Berkah AbadiAbout TBA - PT Toyosae Berkah Abadi
About TBA - PT Toyosae Berkah Abadi
 
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
 
LCOE_2015_2_pager_US
LCOE_2015_2_pager_USLCOE_2015_2_pager_US
LCOE_2015_2_pager_US
 
Tcom Maint Operate
Tcom Maint OperateTcom Maint Operate
Tcom Maint Operate
 
Siemens Innovation Tools2010
Siemens Innovation Tools2010Siemens Innovation Tools2010
Siemens Innovation Tools2010
 
Proa presentation
Proa presentationProa presentation
Proa presentation
 
IRJET- Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...
IRJET-  	  Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...IRJET-  	  Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...
IRJET- Heat Transfer Enhancement in Heat Exchanger using Passive Enhancem...
 
Twe sales brochure
Twe sales brochureTwe sales brochure
Twe sales brochure
 

Kürzlich hochgeladen

How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxmanuelaromero2013
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxGaneshChakor2
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptxVS Mahajan Coaching Centre
 
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...RKavithamani
 
Arihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfArihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfchloefrazer622
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docxPoojaSen20
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppCeline George
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application ) Sakshi Ghasle
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Sapana Sha
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Krashi Coaching
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3JemimahLaneBuaron
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxRoyAbrique
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdfQucHHunhnh
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdfQucHHunhnh
 

Kürzlich hochgeladen (20)

How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptx
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptx
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
 
Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1
 
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
Privatization and Disinvestment - Meaning, Objectives, Advantages and Disadva...
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 
Arihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfArihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdf
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docx
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website App
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application )
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
 
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 

Standard 62.1: A VAV Dynamic Reset Approach

  • 1. ASHRAE Standard 62.1-2010 DCV in Multiple-Zone Systems: Ventilation Reset Control Agenda Presenter: Dennis Stanke, Trane Staff Applications Engineer, FASHRAE Abstract: ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality,” provides minimum outdoor airflow requirements at design conditions. However, ASHRAE Standard 90.1 requires some systems to be operated so that current ventilation capacity modulates to match current ventilation load (i.e., demand). Standard 62.1 allows optional “dynamic reset” controls to help match current capacity to load, but design details for such controls are left to the designer. One design approached, described in this presentation, combines ventilation reset control at the system level with various zone-level “demand controlled ventilation” strategies. Learning objectives After viewing this program Participants will be able to: 1. Apply ventilation system design calculations for three ventilation systems: single-zone, 100% outdoor air, and multiple-zone systems (MZS) 2. Summarize how demand controlled ventilation (DCV) can be incorporated in all three ventilation systems 3. Apply dynamic reset to VAV systems using ventilation reset control, which responds to changes in system ventilation efficiency 4. Apply dynamic reset to VAV systems by combining zone-level DCV with system-level ventilation reset control, to respond to both changes in zone population and changes in system ventilation efficiency Agenda 6.2.2 Zone calculations (zone OA) 6.2.3 Single-zone systems (OA intake) 6.2.4 100% OA systems (OA intake) 6.2.5 Multiple-zone recirc systems (OA intake) 6.2.7 Dynamic reset Wrap-up/discussion
  • 2. Standard 62.1-2010 DCV in Multiple-Zone Systems Ventilation R V til ti Reset Control tC t l Dennis Stanke September 2012 Ingersoll Rand Standard 62.1-2010 DCV in Multiple-Zone Systems-Ventilation Reset Control: Course ID: 0090008756 Approved for 1.0 GBCI hours for LEED professionals 1.5 2 © 2009 Trane Multiple-Zone Ventilation 1 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 3. “Trane” is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of C f Completion for non-AIA members are available on l ti f AIA b il bl request. This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or p product. 3 © 2009 Trane Visit the Registered Continuing Education Programs (RCEP) Website to check state requirements for Professional Development Hours (PDH) for professional engineers. www.RCEP.net 4 © 2009 Trane Multiple-Zone Ventilation 2 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 4. Copyrighted Materials This presentation is protected by U.S. and international copyright laws. Reproduction, distribution, display, and use of the presentation without written permission of Trane is prohibited. © 2012 Trane a business of Ingersoll-Rand All rights reserved. Trane, Ingersoll-Rand. reserved 5 © 2009 Trane Learning Objectives After today’s program you will be able to: • Apply ventilation system design calculations for three ventilation systems: single-zone, 100% outdoor air, and y g , , multiple-zone systems (MZS) • Summarize how demand controlled ventilation (DCV) can be incorporated in all three ventilation systems • Apply dynamic reset to VAV systems using ventilation reset control, which responds to changes in system ventilation efficiency • Apply dynamic reset to VAV systems by combining zone-zone level DCV with system-level ventilation reset control, to respond to both changes in zone population and changes in system ventilation efficiency 6 © 2009 Trane Multiple-Zone Ventilation 3 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 5. Abstract and Venues • Abstract – ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality,” p provides minimum outdoor airflow requirements at design conditions. q g However, ASHRAE Standard 90.1 requires some systems to be operated so that current ventilation capacity modulates to match current ventilation load (i.e., demand). Standard 62.1 allows optional “dynamic reset” controls to help match current capacity to load, but design details for such controls are left to the designer. One design approached, described in this presentation, combines ventilation reset control at the system level with various zone-level “demand controlled ventilation” strategies. • Venues (1.5 hours) – 11SEP2012 Richland, WA – 15SEP2012 Portland, OR 7 © 2009 Trane Standard 62.1 Ventilation Why It’s Important … • For comfort – reduce odors and irritation • For health – reduce building related illness and sick building syndrome • For productivity – reduce absenteeism and increase worker satisfaction • For compliance … – Section 6.2 (VRP) req’d by IMC and UMC ( ) q y – Section 4 thru 8 req’d by Std 189.1 (one IgCC path) – Section 4 thru 7 req’d as LEED prerequisite – All of Std 62.1 required by ENERGY STAR® and bEQ 8 © 2009 Trane Multiple-Zone Ventilation 4 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 6. 6.0 Procedures • 6.1 General. Find OA intake using VRP or IAQP, or find opening parameters using NVP sing • 6.2 Ventilation Rate Procedure – Prescribes minimum rates for “typical” zones and calculations for minimum outdoor air intake rate • 6.3 IAQ Procedure – Specifies performance based on contaminant levels and subjective evaluation • 6.4 Natural Ventilation Procedure – Prescribes opening areas and requires both MV and NV 9 © 2009 Trane 6.2 Ventilation Rate Procedure • 6.2.1 Outdoor air treatment • 6.2.2 Zone calculations (zone OA) • 6.2.3 Single-zone systems (OA intake) • 6.2.4 100% OA systems (OA intake) • 6.2.5 Multiple-zone recirc systems (OA intake) • 6.2.6 Design for varying operating conditions • 6.2.7 6 2 7 Dynamic reset 10 © 2009 Trane Multiple-Zone Ventilation 5 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 7. 6.2.2 Zone Calculations design 1. Calculate breathing-zone outdoor airflow, using Table 6-1 6 1 rates (Rp cfm/per Ra cfm/ft2) cfm/per, Vbz = Rp × Pz + Ra × Az (Eq 6-1) where Pz = peak zone population 2. Find zone air distribution effectiveness Look up Ez (typically 1.0) (Tab 6-2) 3. 3 Calculate zone outdoor airflow Voz = Vbz/Ez (Eq 6-2) 11 © 2009 Trane 6.2 Ventilation Rate Procedure • 6.2.1 Outdoor air treatment • 6.2.2 Zone calculations (zone OA) • 6.2.3 Single-zone systems (OA intake) • 6.2.4 100% OA systems (OA intake) • 6.2.5 Multiple-zone recirc systems (OA intake) • 6.2.6 Design for varying operating conditions • 6.2.7 6 2 7 Dynamic reset 12 © 2009 Trane Multiple-Zone Ventilation 6 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 8. 6.2.3 Single-Zone Systems One recirculating air handler serves one zone EA RA OA SA (Vot) (Vpz) zone 13 © 2009 Trane 6.2.3 Single-Zone Systems design For single-zone systems – Complete first three steps for zone – Then, find outdoor air intake flow Vot = Voz (Eq 6-3) Note: – No design credit for occupant diversity, i.e., must g p y assume peak zone population – Zone ventilation efficiency (Evz = Voz-actual/Voz- design) is probably less than 1.0 during operation 14 © 2009 Trane Multiple-Zone Ventilation 7 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 9. 6.2.3 Single-Zone Systems operation • That’s it for design, but does 62.1-2010 allow intake i fl i t k airflow to vary during operation? t d i ti ? • Of course … – Section 6.2.7 allows optional dynamic reset of zone outdoor airflow using various approaches …  Population estimate based on scheduling, occupancy sensing, people counting  Bio effluent control using CO2-based reset Bio-effluent based – Read Journal articles for “how-to” ideas 15 © 2009 Trane operation Dynamic Reset Approaches • Section 6.2.7 allows dynamic reset of OA intake based on operating conditions, including: – Variations in population – zone-level demand controlled ventilation (DCV) – Variations in system ventilation efficiency – system- level controls required • Different systems use different approaches – For single-zone systems, use simple zone-level DCV – For 100% OA systems, use zone-level DCV, but only y , , y in some VAV systems – For multiple-zone systems, use system-level controls, which can be combined with zone-level DCV • Some examples … 16 © 2009 Trane Multiple-Zone Ventilation 8 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 10. single-zone system operation CO2-based Zone-DCV Now CO2 varies, 4800 so DCV isn’t as easy 1200 CO2 varies 62.1 2007 62.1-2007 (Std 62.1-2007) breathing zone OA, Vbz z differential CO2, ppm 4000 1000 Vbz = 3900 cfm 3200 800 CO2 = 700 ppm 2400 (Std 62-2001) 600 Vbz = 2190 cfm 1600 400 b 800 lecture classroom 200 Az = 4000 ft2 design Pz = 260 p 0 0 0 40 80 120 160 200 240 zone population, Pz © 2005 American Standard Inc. 17 © 2009 Trane one way to implement zone-DCV … operation 62.1 User’s Manual • Find breathing zone OA (Vbz) range Vbz Vb = (R  P + R  A ) (Rp Pz Ra Az) Vbz-des = (7.5  260 + 0.06  4000)/1.0 = 2190 cfm Vbz-min = (7.5  0 + 0.06  4000)/1.0 = 240 cfm • Find target indoor CO2 (Crz) range Crz – Co = N/(Vbz/Pz) Crz-des – Co = 0.0105/(2190 cfm/260 p)  1250 ppm Crz-min – Co = 0.000350 – 0.000350  0 ppm • The Controller: Match Vbz signal range to Crz range • Adjust OA damper to deliver Vot = Vbz-des/Ez at max signal, = Vbz-min/Ez at min signal 18 © 2009 Trane Multiple-Zone Ventilation 9 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 11. zone DCV for single-zone systems operation 62.1 User’s Manual The Controller 2190 Vbz (cfm) 240 0 1250 Crz - Co (CO2, ppm) 19 © 2009 Trane zone DCV for single-zone systems operation 62.1 User’s Manual Controller adjusts Vbz, hing zone OA, Vbz (=Ez*Vot) 4800 based on sensed CO2 1200 differential CO2, ppm 4000 1000 CO2 3200 800 2400 600 1600 Vbz 400 breath 800 lecture classroom 200 Az = 4000 ft2 design Pz = 260 p 0 0 0 40 80 120 160 220 240 zone population, Pz © 2005 American Standard Inc. 20 © 2009 Trane Multiple-Zone Ventilation 10 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 12. 6.2 Ventilation Rate Procedure • 6.2.1 Outdoor air treatment • 6.2.2 Zone calculations (zone OA) • 6.2.3 Single-zone systems (OA intake) • 6.2.4 100% OA systems (OA intake) • 6.2.5 Multiple-zone recirc systems (OA intake) • 6.2.6 Design for varying operating conditions • 6.2.7 6 2 7 Dynamic reset 21 © 2009 Trane 6.2.4 100% OA Systems design One non-recirculating air handler serves many zones EA Voz OA zone (Vot) SA CA RA Voz zone SA RA 22 © 2009 Trane Multiple-Zone Ventilation 11 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 13. 6.2.4 100% OA Systems design For 100% OA systems – Complete first three steps for each zone – Then, find outdoor air intake flow Vot = Voz (Eq 6-4) Note: – No design credit for occupant diversity, i.e., must g p y assume peak zone population in each zone – Zone ventilation efficiency (Evz = ΣVoz-actual/ΣVoz- design) is probably less than 1.0 during operation 23 © 2009 Trane 6.2.4 100% OA Systems operation • That’s it for design but does 62.1-2007 allow intake i fl i t k airflow to vary during operation? t d i ti ? • Well, that depends … – Section 6.2.7 allows optional dynamic reset, but …  For constant volume OA systems there’s no way to reset outdoor airflow  For VAV OA systems, intake airflow can be reduced if – All zones i l d pressure-independent d include i d d t dampers – DCV zones include DCV sensors and controls – The 100% OA unit includes VAV controls 24 © 2009 Trane Multiple-Zone Ventilation 12 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 14. 6.2 Ventilation Rate Procedure • 6.2.1 Outdoor air treatment • 6.2.2 Zone calculations (zone OA) • 6.2.3 Single-zone systems (OA intake) • 6.2.4 100% OA systems (OA intake) • 6.2.5 Multiple-zone recirc systems (OA intake) • 6.2.6 Design for varying operating conditions • 6.2.7 6 2 7 Dynamic reset 25 © 2009 Trane 6.2.5 Multiple-Zone Systems One recirculating air handler serves many zones RA EA Vpz space OA (Vot) SA (Vps) Single-path system (dual- space path is more complex) 26 © 2009 Trane Multiple-Zone Ventilation 13 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 15. design 6.2.5 Multiple-Zone Systems For multiple-zone recirculating systems, complete first three steps for each zone then solve MZS equations: zone, 4. Find primary outdoor air fraction, Zp Zp = Voz/Vpz-min (6-5) 5. Find uncorrected outdoor airflow, Vou Vou = D*(Rp×Pz) + (Ra×Az) (6-6) 6. Find 6 Fi d system ventilation efficiency, E t til ti ffi i Ev Calculate Ev per equations (App A) 7. Find outdoor air intake flow, Vot: Vot = Vou/Ev (6-8) 27 © 2009 Trane 6.2.5 Multiple-Zone Systems design 4. Find primary outdoor air fraction for each zone or each critical zone Zp = Voz/Vpz (Eq 6-5) Note: – Vpz = Vpz-design = minimum primary airflow expected at “ventilation design” condition (usually higher than minimum box setting) – Picking Vpz-design - probably most confusing part for MZS Vpz design  Many use minimum box setting – easy but conservative  Some use 8760 simulation to find an accurate value (Maybe Std 62.1 should use 0.5*Vpz-design as default)  NOTE: “ventilation design” ≠ “thermal design” 28 © 2009 Trane Multiple-Zone Ventilation 14 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 16. 6.2.5 Multiple-Zone Systems design 5. Find uncorrected outdoor airflow Vou = D*(R P ) + (R A ) V (Rp×Pz) (Ra×Az) (Eq 6-6) (E 6 6) Note: – Design credit for occupant diversity (D) – D = expected population/sum-of-peak populations = 50 people/100 chairs = 0.5 – Occupant diversity reduces uncorrected outdoor airflow 29 © 2009 Trane 6.2.5 Multiple-Zone Systems design 6. Find system ventilation efficiency – Fi t find average outdoor air f ti (Xs) using First, fi d td i fraction (X ) i system primary airflow (Vps) at ventilation design Xs = Vou/Vps (Eq A-1) – Then, find zone ventilation efficiency (Evz) Evz = 1 + Xs – Zpz (Eq A-2) – Finally, lowest Evz is system ventilation efficiency (Ev) Ev = min(Evz) (Eq A-8) Note: – Lowest Evz defines the “critical zone” for ventilation 30 © 2009 Trane Multiple-Zone Ventilation 15 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 17. 6.2.5 Multiple-Zone Systems design 7. Find outdoor air intake flow Vot Vou/Ev V t = V /E (Eq 6-8) (E 6 8) Note: – Compared to 2001, the 2010 rates and equations reduce intake airflow (Vot) for many systems 31 © 2009 Trane 6.2 Ventilation Rate Procedure • 6.2.1 Outdoor air treatment • 6.2.2 Zone calculations (zone OA) • 6.2.3 Single-zone systems (OA intake) • 6.2.4 100% OA systems (OA intake) • 6.2.5 Multiple-zone recirc systems (OA intake) • 6.2.6 Design for varying operating conditions • 6.2.7 6 2 7 Dynamic reset 32 © 2009 Trane Multiple-Zone Ventilation 16 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 18. Multiple-Zone Systems operation • That’s it for MZS design but can intake flow vary during d i operation? ti ? • Sure – Provided Section 5.3.1 (no less than required Vot under all “operating” conditions) is met … – Section 6.2.7 allows optional dynamic reset, regardless of system type • But how do you do it in a VAV system? 33 © 2009 Trane Dynamic Reset Approaches operation • Already reviewed for single zone and 100% OA • For VAV MZS operation, you could … – Use “ventilation reset control” (VRC)  Reset intake flow based only on changes in system ventilation efficiency (Ev) due to changes in zone airflow – Combine system-level VRC with zone-level DCV  Reset intake flow based on changes in system ventilation efficiency due to changes in both zone airflow and population – Use system-level DCV of some sort  Approaches not well-known, but hopefully Dr. Lau’s research addresses this 34 © 2009 Trane Multiple-Zone Ventilation 17 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 19. Ventilation Reset Control operation • VRC resets system-level outdoor air intake flow (Vot) t (V t) at part l d conditions by: t load diti b – Assuming design population in all zones without accounting for reduced population in any zone – Accounting for changes in system ventilation efficiency (Ev) due to zone and system airflow changes – Solving the MZS equations in real time (quasi-steady state) to find current intake flow (Vot) set point required • Here’s an example building using one possible VRC approach 35 © 2009 Trane VRC w/o Zone-Level DCV design Vot req’d @ design Single Supply Single-Supply VAV System: Ventilation Design population Pz 140 140 260 260 5 40 8, 810 prim airflow Vpz 6,500 6,700 5,500 7,900 500 1,700 min expect Vpzm 4,000 4,000 4,000 4,000 300 1,300 vent rate Vbz 1,880 1,880 2,190 2,190 85 760 vent fract Zpz 0.470 0.470 0.548 0.548 0.283 0.585 Ventilation design - For each zone use: Then, find: Pz = peak zone population Vou = D*Rp*Pz + Ra*Az (5) Vpz = peak primary airflow D = Ps/Pz = 550/845 = 0.65 Vpzm = minimum expected Vpz @ design = 0.65*7,130 + 1,860 = 6,500 Then, Then find: Ev = min(Evz) (6) Vbz = Rp*Pz + Ra*Az (1) Vps = LDF*ΣVpz Ez = design zone air dist eff (2) = 0.7*28,800 = 20,200 Voz = Vbz/Ez (3) Xs = Vou/Vps Zpz = Voz/Vpzm = Vbz/(Ez*Vpzm) (4) = 6,500/20,200 = 0.322 Evz = 1+ Xs – Zpz For the system use: = 1 + 0.322 – 0.585 = 0.738 Ps = highest system population = 550 = min(Evz) = 0.738 LDF= load diversity factor = 0.7 Vot = Vou/Ev = 6,500/0.738 = 8,810 (7) 36 © 2009 Trane Multiple-Zone Ventilation 18 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 20. VRC w/o Zone-Level DCV operation Vot Vot req’d req’d @ design (current) Single Supply Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps) Friday, population Pz 140 140 260 260 5 40 8, 810 8, 390 prim airflow Vpz 4,960 5,000 4,000 4,000 500 1,700 vent rate Vbz 1,880 1,880 2,190 2,190 85 760 vent fraction Zdz 0.379 0.376 0.548 0.548 0.170 0.447 Operation w/o DCV: For each zone use: Now, controls calculate: Pz = peak zone population (entry) Vou = D*Rp*Pz + Ra*Az (5) Then, controls determine or calculate: D = Ps/Pz = 550/845 = 0.65 Vpz = current primary airflow (sensed) = 0.65*7,130 + 1,860 = 6,500 Vbz = Rp*Pz + Ra*Az (calc or entry) (1) Rp Pz Ra Az Ev = min(Evz) (6) Ez = current value (2) Vps = Vpz Voz = Vbz/Ez (3) = 20,200 Zpz = Voz/Vpz (4) Xs = Vou/Vps = 6,500/20,200 = 0.322 Evz = 1+ Xs – Zpz For the system use: = 1 + 0.322 – 0.548 = 0.775 Ps = highest system population = 550 = min(Evz) = 0.775 LDF= load diversity factor = 0.7 Vot = Vou/Ev = 6,500/0.775 = 8,390 (7) 37 © 2009 Trane VRC w/o Zone-Level DCV operation Vot Vot req’d req’d @ design (current) Single Supply Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps) Friday, population Pz 140 140 260 260 5 40 8, 810 8, 390 prim airflow Vpz 4,960 5,000 4,000 4,000 500 1,700 vent rate Vbz 1,880 1,880 2,190 2,190 85 760 vent fraction Zdz 0.379 0.376 0.548 0.548 0.170 0.447 Vot-actual is less Operation w/o DCV: For each zone use: Now, controls calculate: than Vot-design Pz = peak zone population (entry) Vou = D*Rp*Pz + Ra*Az (5) Then, controls determine or calculate: D = Ps/Pz = 550/845 = 0.65 Vpz = current primary airflow (sensed) = 0.65*7,130 + 1,860 = 6,500 Vbz = Rp*Pz + Ra*Az (calc or entry)w/o DCV Ev = min(Evz) Rp Pz Ra Az VRC (1) reduces (6) Ez = current value required Vot, even at Vpz (2) Vps = Voz = Vbz/Ez (3) = 20,200 Zpz = Voz/Vpz 100%(4)thermal load:= Vou/Vps Xs Ev-actual ≥ Ev-design = 6,500/20,200 = 0.322 Evz = 1+ Xs – Zpz For the system use: = 1 + 0.322 – 0.548 = 0.775 Ps = highest system population = 550 = min(Evz) = 0.775 LDF= load diversity factor = 0.7 Vot = Vou/Ev = 6,500/0.775 = 8,390 (7) 38 © 2009 Trane Multiple-Zone Ventilation 19 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 21. VRC w/o Zone-Level DCV operation Vot Vot req’d req’d @ design (current) Single Supply Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps) Friday, population Pz 140 140 260 260 5 40 8, 810 8, 390 prim airflow Vpz 4,960 5,000 4,000 4,000 500 1,700 vent rate Vbz 1,880 1,880 2,190 2,190 85 760 vent fraction Zpz 0.379 0.376 0.548 0.548 0.170 0.447 Single-Supply VAV System: 90% Thermal Load (1:00 pm Monday, perhaps) population Pz 140 140 260 260 5 40 8,810 7,780 prim airflow Vpz 4,000 3,700 4,200 4,300 300 1,700 vent rate Vbz 1,880 1,880 2,190 2,190 85 760 vent fraction Zpz 0 470 0 508 0 521 0 509 0 283 0 447 0.470 0.508 0.521 0. 0.283 0.447 Now, controls determine or calculate: VRC w/o DCV reduces Vou = D*Rp*Pz + Ra*Az = 6,500 required Vot even more Vpz = (sensed) Vps = Vpz = 18,200 at lower thermal loads: Xs = Vou/Vps = 6,500/18,200 = 0.357 Ev-actual >> Ev-design Ev = 1 + 0.357 – 0.521 = 0.836 Vot = Vou/Ev = 6,500/0.836 = 7,780 39 © 2009 Trane Dynamic Reset Approaches operation • Already reviewed for single zone and 100% OA • For VAV MZS operation, you could … – Use “ventilation reset control” (VRC)  Reset intake flow based only on changes in system ventilation efficiency (Ev) due to changes in zone airflow – Combine system-level VRC with zone-level DCV  Reset intake flow based on changes in system ventilation efficiency due to changes in both zone airflow and population – Use system-level DCV of some sort  Approaches not well-known, but hopefully Dr. Lau’s research addresses this 40 © 2009 Trane Multiple-Zone Ventilation 20 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 22. VRC with Zone-Level DCV operation • VRC resets system-level outdoor air intake flow (Vot) t (V t) at part l d conditions by: t load diti b – Assuming design population in non-DCV zones while accounting for reduced population in DCV zones – Accounting for changes in system ventilation efficiency (Ev) due to zone and system airflow changes – Solving the MZS equations in real time (quasi-steady state) to find current intake flow (Vot) set point required • Here’s the same example building using the same VRC approach, but with various “zone types” including both non-DCV and DCV zones 41 © 2009 Trane VRC w/Zone-Level DCV operation • Defining zone types – Z Zones without DCV ith t  Non-DCV zones (NON): Pz = peak zone population at all conditions, regardless of actual population – Population-estimating DCV zones (EST) include:  “Time-of-day” zones (TOD): Pz = predicted population  “Occupied/unoccupied” (OCC) zones: Pz = peak or zero population, depending on occupancy sensor  “Count” zones (COU): Pz = sensed number of occupants – CO2-based DCV zones (CO2) (Pz = unknown)  Breathing-zone OA flow depends on sensed difference between primary and zone CO2: Vbz = f (ΔCO2) 42 © 2009 Trane Multiple-Zone Ventilation 21 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 23. VRC w/ Zone-Level DCV design Vot NON NON CO2 NON NON EST req’d @ design Single Supply Single-Supply VAV System: Design Ventilation population Pz 140 140 260 260 5 40 8, 810 prim airflow Vpz 6,500 6,700 5,500 7,900 500 1,700 min expect Vpzm 4,000 4,000 4,000 4,000 300 1,300 vent rate Vbz 1,880 1,880 2,190 2,190 85 760 DCV: No impact vent fract Zpz 0.470 0.470 0.548 0.548 0.283 0.585 on Vot-design Design ventilation: For each zone use: Then, find: Pz = peak zone population Vou = D*Rp*Pz + Ra*Az (5) Vpz = peak primary airflow D = Ps/Pz = 550/845 = 0.65 Vpzm = minimum expected Vpz @ design = 0.65*7,130 + 1,860 = 6,500 Then, Then find: Ev = min(Evz) (6) Vbz = Rp*Pz + Ra*Az (1) Vps = LDF*ΣVpz Ez = design zone air dist eff (2) = 0.7*28,800 = 20,200 Voz = Vbz/Ez (3) Xs = Vou/Vps Zpz = Voz/Vpzm = Vbz/(Ez*Vpzm) (4) = 6,500/20,200 = 0.322 Evz = 1+ Xs – Zpz For the system use: = 1 + 0.322 – 0.585 = 0.738 Ps = highest system population = 550 = min(Evz) = 0.738 LDF= load diversity factor = 0.7 Vot = Vou/Ev = 6,500/0.738 = 8,810 (7) 43 © 2009 Trane VRC w/ Zone-Level DCV operation Vot Vot NON NON CO2 NON NON EST req’d req’d @ design (current) Single Supply Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps) Friday, population Pz 140 140 ??? 260 5 0 8, 810 8, 390 prim airflow Vpz 4,960 5,400 4,000 4,000 500 1,300 8, 030 vent rate Vbz 1,880 1,880 1,300 2,190 85 360 vent fraction Zpz 0.379 0.348 0.325 0.548 0.170 0.277 For each NON-DCV zone use: Now, for system: Pz = peak zone population (entry) Vou = D*NONRp*Pz + NONRa*Az (5) Vbz = Rp*Pz + Ra*Az (entry) + ESTRp*Pz + ESTRa*Az + CO2Vbz For each EST-DCV zone: Ps = highest system population = 550 Pz = estimated population (sensed) D = Ps/Pz-peak = 550/845 = 0.65 Vbz Rp*Pz Ra*Az Vb = R *P + R *A (calc) ( l ) = 0.65*4,780 + 1,260 + 0 + 360 + 1,300 * For each CO2-DCV zone use: = 6,030 Vbz = f (ΔCO2) (sense & calc) Ev = min(Evz) (6) For each zone, controls determine: Vps = Vpz = 20,200 (calc) Vpz = current zone primary (sensed) Xs = Vou/Vps = 6,030/20,200 = 0.299 Vbz = current reqmt (entry or calc) (1) Evz = 1 + Xs – Zpz Ez = current value (2) = 1 + 0.299 – 0.548 = 0.751 Voz = Vbz/Ez (3) Vot = small(Vou/Ev or Vot-des) (7) Zpz = Voz/Vpz (4) = 6,030/0.751 = 8,030 44 © 2009 Trane Multiple-Zone Ventilation 22 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 24. VRC w/ Zone-Level DCV operation Vot Vot NON NON CO2 NON NON EST req’d req’d @ design (current) Single Supply Single-Supply VAV System: 100% Thermal Load (2:00 pm Friday perhaps) Friday, population Pz 140 140 ??? 260 5 0 8, 810 8, 390 prim airflow Vpz 4,960 5,400 4,000 4,000 500 1,300 8, 030 vent rate Vbz 1,880 1,880 1,300 2,190 85 360 vent fraction Zpz 0.379 0.348 0.325 0.548 0.170 0.277 For each NON-DCV zone use: Now, for system: VRC w/DCV Pz = peak zone population (entry) reduces Vot-actual Vou = D*NONRp*Pz + NONRa*Az (5) Vbz = Rp*Pz + Ra*Az (entry) + ESTRp*Pz + ESTRa*Az + CO2Vbz For each EST-DCV zone: Ps = highest system population = 550 Pz = estimated population (sensed) D = Ps/Pz-peak = 550/845 = 0.65 Vbz Rp*Pz Ra*Az Vb = R *P + R *A (calc) ( l ) = 0.65*4,780 + 1,260 + 0 + 360 + 1,300 * For each CO2-DCV zone use: = 6,030 Vbz = f (ΔCO2) (sense & calc) Ev = min(Evz) (6) For each zone, controls determine: Vps = Vpz = 20,200 (calc) Vpz = current zone primary (sensed) Xs = Vou/Vps = 6,030/20,200 = 0.299 Vbz = current reqmt (entry or calc) (1) Evz = 1 + Xs – Zpz Ez = current value (2) = 1 + 0.299 – 0.548 = 0.751 Voz = Vbz/Ez (3) Vot = small(Vou/Ev or Vot-des) (7) Zpz = Voz/Vpz (4) = 6,030/0.751 = 8,030 45 © 2009 Trane VRC w/ Zone-Level DCV operation – For design, note:  D = P /ALLP Ps/ Pz-peak, bk because occupant diversity t di it distributes total population among all zones in system  D applies to all zones for design – For operation, note:  D applies NON-DCV zones (occupant diversity credit)  D = 1.0 for EST-DCV zones (estimated Pz is independent of occupant diversity) p y)  D isn’t used for CO2-DCV zones (Vbz is determined by controller, without regard to occupant diversity  Rule: To assure adequate heat/cool capacity, Vot during operation must never be greater than Vot at design 46 © 2009 Trane Multiple-Zone Ventilation 23 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 25. VRC w/ Zone-Level DCV operation Vot Vot NON NON CO2 NON NON EST req’d req’d @ design (current) Single Supply Single-Supply VAV System: 100%Thermal Load (2:00 pm Friday perhaps) Friday, population Pz 140 140 ??? 260 5 0 8, 810 8, 030 prim airflow Vpz 4,960 5,400 4,000 4,000 500 1,300 vent rate Vbz 1,880 1,880 1,300 2,190 85 360 vent fraction Zpz 0.379 0.348 0.325 0.548 0.170 0.277 Single-Supply VAV System: 90% Thermal Load (1:00 pm Monday, perhaps) population Pz 140 140 ??? 260 5 0 8,810 7,780 prim airflow Vpz 4,000 3,700 4,200 4,300 300 1,700 7,440 vent rate Vbz 1,880 1,880 1,300 2,190 85 360 vent fraction Zpz 0 470 0 508 0 521 0 509 0 283 0 447 0.470 0.508 0.521 0. 0.283 0.447 Now: VRC with DCV reduces Vou = 6,030 Vps = Vpz = 18,200 Vot-actual more, saves Xs = 6,030/18,200 = 0.331 more energy Ev = 1 + 0.331 – 0.521 = 0.810 Vot = Vou/Ev = 6,030/0.810 = 7,440 47 © 2009 Trane Implementation • For VRC alone or combined with zone-level DCV, design d i usually includes: ll i l d – Communicating DDC-VAV boxes – BAS with equation-solving capability – Intake-airflow sensing and control at the AHU – Building pressure control (which limits Vot reduction) • Remember: – Std 62.1 allows DCV in any system – Std 90.1 requires DCV in 40 p/1000 ft2 zones – Std 189.1 requires DCV in 25 p/1000 ft2 zones 48 © 2009 Trane Multiple-Zone Ventilation 24 © 2012 Trane a business of Ingersoll Rand. All rights reserved
  • 26. Quick Summary Dynamic reset depends on ventilation system type – Single-zone systems (no design population diversity)  Optional zone DCV allowed – 100% OA systems (no design population diversity)  CV: Zone DCV & Vot reset not useful w/constant Vot  VAV: Zone DCV & Vot reset allowed but not cheap – Multiple-zone sys (population diversity design credit):  Optional system Vot reset allowed – Based only on system ventilation efficiency (VRC) – Based on zone DCV combined with system VRC – Based only on zone DCV (not covered) 49 © 2009 Trane Thanks Any questions? Dennis Stanke dstanke@trane.com 50 © 2009 Trane Multiple-Zone Ventilation 25 © 2012 Trane a business of Ingersoll Rand. All rights reserved