7 Cálculo.pdf
- 1. Cliente
Dirección
Artefacto Tramo
Pot
(kW)
L Real
(m)
Q
(m3/h)
Codo
90°
Codo
45°
Tee a
180°
Tee a
90°
L Equiv.
(m)
L Total
(m)
Ø Nominal
Material
Ø Real
(mm)
Velocidad
(m/s)
∆p
(mbar)
Presión Final
(mbar)
CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214
T1-C1 8.79 5.80 0.80 0 0 0 1 1.20 7.00 2025 - PAP 20.000 0.53 0.027
1.241 APROBADO
CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214
T1-T2 87.58 17.95 7.93 0 0 1 0 0.40 18.35 2025 - PAP 20.000 5.30 4.684
T2-T3 70.00 1.05 6.34 0 0 1 0 0.40 1.45 2025 - PAP 20.000 4.22 0.246
T3-F1 35.00 5.15 3.17 0 0 0 1 1.20 6.35 2025 - PAP 20.000 2.11 0.305
6.448 APROBADO
CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214
T1-T2 87.58 17.95 7.93 0 0 1 0 0.40 18.35 2025 - PAP 20.000 5.30 4.684
T2-T3 70.00 1.05 6.34 0 0 1 0 0.40 1.45 2025 - PAP 20.000 4.22 0.246
T3-F2 35.00 5.75 3.17 0 0 1 0 0.40 6.15 2025 - PAP 20.000 2.11 0.295
6.438 APROBADO
CM-T1 96.37 4.00 8.72 0 0 0 0 0.00 4.00 2025 - PAP 20.000 5.82 1.214
T1-T2 87.58 17.95 7.93 0 0 1 0 0.40 18.35 2025 - PAP 20.000 5.30 4.684
T2-C2 17.58 5.80 1.59 0 0 0 1 1.20 7.00 2025 - PAP 20.000 1.06 0.096
5.993 APROBADO
N° Suministro 162397
CTG-GCO-F-VC-009
TABLA DE CÁLCULO DE INSTALACIONES INTERNAS - ALTA PRESIÓN
CHECHO'S DNI / RUC 21855208
CÁLCULOS DE LA INSTALACIÓN INTERNA - RENOUARD CUADRATICA - ALTA PRESIÓN
COCINA
1
337.26
Caída de Presión Acumulada
Caída de Presión Acumulada
FREIDORA1
332.06
Caída de Presión Acumulada
332.51
Caída de Presión Acumulada
FREIDORA2
COCINA
2
332.05