PROJECT THEME
I. Introduction
II. Background survey
III. Theoretical proof of ac-dc combine transmission
IV. Matlab simulation of ac-dc combine transmission
V. Response of ehv ac transmission
VI. Response of ac-dc combine transmission
VII. Case of study
VIII. Economical proof of ac-dc combine transmission
IX. Advantages & Limitation of ac-dc combine transmission
X. Conclusion
1. INTRODUCTION
1). EHV AC Transmission
2). HVDC Transmission
3). AC-DC Combine Transmission
a). AC-DC 3-phase Single Line Transmission
b). AC-DC 3-phase Double Line Transmission
CONDITION OF TRANSMISSION
[1] VMAX = √𝟐Vph = Vd + √𝟐Va
[2]VLL MAX = √𝟔Va
[3] Vd= Vph/√𝟐
[4] Va = Vph/ 2
2.
MATLAB SIMULATION
3.
CASE OF STUDY
AC Line: Twin Moose ACSR Bundled Conductor, 400kV, 50Hz, 320km
Line Parameters:
Resistance per unit length: 0.01273 Ω/km
Inductance per unit length: 0.9337 mH/km
Capacitance per unit length: 12.74 nF/km
PURE AC TRANSMISSION SYSTEM:
Sending End Voltage (VS) =400 kV
Receiving End Voltage (VR) = 392.6 kV
Sending End Power (PS) = 881 MW
Receiving End Power (PR) = 750 MW
Sending End Current (IS) = =952.5 A
Receiving End Current (IR) = 1004 A
X (Total Reactance per phase per circuit) =0.9337×10-3×320×314 = 93.82 Ω
𝛿 (power angle) =31.76
total power transmitted = 3×881 MW = 2643 MW
Total Power received = 3×750 MW = 2250 MW
Total Transmission Loss = 2643 MW – 2250 MW = 393 MW
SIMULTANEOUS AC-DC POWER TRANSMISSION SYSTEM:
Sending End AC Voltage (VS) = 400 kv
Receiving End AC Voltage (VR) = 392.6 kV
AC Current (Iac) = 2.341 kA
Sending End AC Power (PS) = 1600 MW
Receiving End AC Power (PR) = 1100 MW
Total Reactance per phase per circuit (X) = 93.82 Ω
Rectifier Voltage (Vdr) = 440 kV
Inverter Voltage (Vdi) = 300 kV
DC Link Current (Id) = 1.74 kA
Sending End DC Power = 765.6 MW
Receiving End DC Power = 522 MW
= 70°
Total Power Transmitted = 2×1600 + 765.6 = 3965.6 MW
Total Power Received = 2722 MW
Transmission Loss = 3965.6 MW – 2722 MW= 1243.6MW
Now, dc voltage across one winding = 440/2 = 220 kV.
Induced voltage across secondary winding of transformer = 200 kV
Vdo = 220 kV
So, power factor of the rectifier (cosθr) = 220/271 = 0.812
Similarly for inverter
Vdoi = 271 kV
Vdo = 150 kV
Power factor of the inverter (cosθi) = 150/271 = 0.5535
So, reactive power drawn by the rectifier = 765.6 tanθr = 550.3 MVAR
Reactive power drawn by the inverter = 522 tanθi = 785.45 MVAR
Power Up gradation =
Power transformer in composite AC – DC transmissions - power transmitted in pure transmission /
power transmitted in pure transmission
= [ 2722 – 2250 / 2250 ] Χ 100
= 21 %
4.
ECONOMY
ECONOMY OF THE SYSTEM
[1] ECONOMY OF SYSTEM BASED ON COMPARISON
[2] ECONOMY OF SYSTEM BASED ON STRUCTURE
FOR DOUBLE CIRCUIT EHV LINE
Base cost of 500 KV double circuit transmission line Rs. 1,78,020,000
Line Multiplier :
(1) Conductor
ACSR (1.0) √ ACSS (1.08) TLS (3.60)
(1) Tower Structure:
Lattice (1.0) √ Tabular Steel (1.50)
(1) Transmission Length:
Up to 4.82 Km (1.50) 4.82 Km to 16.093 Km (1.20) Above 16.093 Km (1.0) √
Total transmission line cost = [ (base transmission cost)*(conductor multiplier)*(structure multiplier) *(1.6093)*(no of kilometer) ]
Total transmission line cost Rs. 5.696641010
SUB-STATION CAPITAL COST
Base cost of Sub-Station (500 KV) Rs. 148,320,000
LINE & TRANSFORMER POSITION COST & MULTIPLIER (500 KV)
Cost multiplier : Breaker & half multiplier (1.50) Ring bus multiplier (1.0) √
Cost per line / transformer position Rs. 173,040,000
Transformer cost (Rs. per MVA)
230 / 500 KV Transformer – Rs. 660,000 115 / 500 KV Transformer – Rs. 600,000 √
Transformer cost (Rs. Per MVA) Rs. 600,000
REACTIVE COMPONENTS COST PER MVAR
Shunt reactor Rs. 1,200,000
Series reactor Rs. 600,000
SVC capital cost Rs. 5,100,000
Total substation cost = [ (sub-station base cost)+(line per transformer position base cost)*(no. of line per transformer position)*(CRB or BAAH
multiplier)+(transformer cost per MVA)*(transformer MVA rating)+(SVC cost per MVAR)*(require MVARs)+(series capacitor cost per
MVAR)*(require MVARs)+(shunt reactor cost per MVAR)*(require MVARs) ]
Total substation cost Rs. 839,052,000 x 2 = 1,678,104,000
TOTAL COST
HVDC TRANSMISSION LINE
500 KV HVDC bidirectional pole line (per Km) Rs. 89,040,000
TOTAL COST OF TRANSMISSION LINE
Total cost of transmission line Rs. 2.84928X1010
SUB-STATION CAPITAL COST
Converter terminal (include DC switching
station equipment)
Rs. 3,850,000,000
Reactive support (synchronous
condensers, SVCs, etc)
Rs. 2,100,000,000
AC switch yard Rs. 280,000,000
COST OF SUB-STATION
Cost of sub-station Rs. 6,230,000,000 x 2 = 1.246 x 1010
TOTAL COST
Total cost Rs. 3.47228 x 1010
COMBINE HVDC-HVAC
SUB-STATION COST
Sub-Station cost Rs. 6,230,000,000 x 2 = 1.246 x 1010
COST OF ZIG-ZAG TRANSFORMER (125)
Cost of zig-zag transformer per MVA (Rs. Per MVA) Rs. 78,000
Cost of 4 zig-zag transformer (Rs. Per MVA) Rs. 78,000 x 4 = 312,000
Total cost of four zig-zag transformer Rs. 390,000,000
TOTAL COST
Total cost Rs. 1.285 x 1010
5.
CONCLUSION
ADVANTAGES OF SYSTEM
(1) The feasibility to convert ac transmission line to a composite ac–dc line has been demonstrated.
(2) For the particular system studied, there is substantial increase (about 21.45%) in the load ability of the
line.
(3) The line is loaded to its thermal limit with the superimposed dc current.
(4) The dc power flow does not impose any stability problem.
(5) Dc current regulator may modulate ac power flow.
(6) There is no need for any modification in the size of conductors, insulator strings, and towers structure of
the original line.
(7) The optimum values of ac and dc voltage components of the converted composite line are ½ and 1/√2
times the ac voltage before conversion, respectively.
LIMITATION
(1) There Is Certain Limit Of Power Upgrading Of Transmission Line, So We Can Not Apply This Basic
Scheme Where New Unit Has More Power Capacity Then Limit Of Power Upgrading Of Transmission Line.
(2) The Combine HVDC-HVAC Transmission Line Is Very Complicated.
(3) There Is Necessity Of Double Circuit Long Extra High Voltage AC Transmission Line In Running Power
Generating Station.
(4) We Cannot Transfer The Power By This Basic Scheme Where Double Circuit EHV Line Not Going From
The Power Generating Station.
APPLICATION
(1) ADDITION OF GENERATION UNIT
(2) SOLAR GENERATION UNIT
CONCLUSION
For the particular system under study, the power up gradation of the line is observed to be twenty one
percent with the simultaneous ac-dc power flow. Maximum power up gradation is obtained at a
transmission angle of 60º. The line is loaded to its thermal limit with the superimposed dc current. The dc
power flows independent of the ac power in the transmission line.
REFERENCES
PAPERS:-
[1] “Upgradation Of Power Flow In EHV AC Transmission” International Journal Of Scientific Engineering And
Technology By K.K.Vasishta Kumar, K.Sathish Kumar.
[2] “Power Upgrading Of Transmission Line By Combining AC-DC Transmission”, Swarnandhra College Of Engineering
Technology Narsapur By Jarupula Somlal.
[3] “Power System Stability Enhancement By Simultaneous AC-DC Power Transmission” International Journal Of
Advanced Research In Electrical, Electronics And Instrumentation Engineering Vol. 2, Issue 5, May 2013 By Abhishek
Chaturvedi, V. K. Tripathi, T Vijay Muni, Neeraj Singh.
[4] “Power Tapping Of Upgrade Transmission Line By Using Composite Ac-dc Power Transmission Lines”
International Journal Of Engineering Research And Development By CH.Veeraiah, Y.Rambabu, V.K.R.Mohan Rao.
BOOKS:-
[1] D P Kothari And I J Nagrath “MODERN POWER SYSTEM ANALYSIS” FNAE Fnasc,
Fellow-ieee Director General, Raisoni Group Of Institutions, Nagpur.
[2] Tim Mason- Project Manager, Trevor Curry And Dan Wilson, “CAPITAL COSTS FOR
TRANSMISSION AND SUBSTATION” Western Electricity Coordinating Council.
[3] Roberto Rudervall, J.P. Charpentier And Raghuveer Sharma, “HIGH VOLTAGE DIRECT
CURRENT (HVDC)TRANSMISSION SYSTEMS” Technology Review Paper, Presented At Energy
Week 2000, Washington, D.C, USA, March 7-8, 2000.
THANK YOU

Weitere ähnliche Inhalte

Was ist angesagt?

ppt on the Super conducting power cable in dc electric railway systems
ppt on the Super conducting power cable in dc electric railway systemsppt on the Super conducting power cable in dc electric railway systems
ppt on the Super conducting power cable in dc electric railway systems
Yuvraj Singh
 
Load characteristics and Economic Aspects
Load characteristics and Economic AspectsLoad characteristics and Economic Aspects
Load characteristics and Economic Aspects
Abha Tripathi
 
Design of Synchronverter based Microgrid
Design of Synchronverter based MicrogridDesign of Synchronverter based Microgrid
Design of Synchronverter based Microgrid
Somsubhra Ghosh
 

Was ist angesagt? (20)

Lecture 15
Lecture 15Lecture 15
Lecture 15
 
(10) stability
(10) stability(10) stability
(10) stability
 
Indian journal 3
Indian journal 3Indian journal 3
Indian journal 3
 
Load Characteristics
Load CharacteristicsLoad Characteristics
Load Characteristics
 
ppt on the Super conducting power cable in dc electric railway systems
ppt on the Super conducting power cable in dc electric railway systemsppt on the Super conducting power cable in dc electric railway systems
ppt on the Super conducting power cable in dc electric railway systems
 
Power system Stability, Equal area criteria
Power system Stability, Equal area criteriaPower system Stability, Equal area criteria
Power system Stability, Equal area criteria
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
fasys
fasysfasys
fasys
 
Load characteristics and Economic Aspects
Load characteristics and Economic AspectsLoad characteristics and Economic Aspects
Load characteristics and Economic Aspects
 
Load flow study Part-I
Load flow study Part-ILoad flow study Part-I
Load flow study Part-I
 
Modelling of 25 kV Electric Railway System
Modelling of 25 kV Electric Railway SystemModelling of 25 kV Electric Railway System
Modelling of 25 kV Electric Railway System
 
Unit 3 FACTS Technology
Unit 3 FACTS TechnologyUnit 3 FACTS Technology
Unit 3 FACTS Technology
 
Impact of Renewables on Transmission System Protection
Impact of Renewables on Transmission System ProtectionImpact of Renewables on Transmission System Protection
Impact of Renewables on Transmission System Protection
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power system
 
Exp 5 (1)5. Newton Raphson load flow analysis Matlab Software
Exp 5 (1)5.	Newton Raphson load flow analysis Matlab SoftwareExp 5 (1)5.	Newton Raphson load flow analysis Matlab Software
Exp 5 (1)5. Newton Raphson load flow analysis Matlab Software
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power Management
 
Power station
Power stationPower station
Power station
 
Design of Synchronverter based Microgrid
Design of Synchronverter based MicrogridDesign of Synchronverter based Microgrid
Design of Synchronverter based Microgrid
 
Electromechanical energy conversion
Electromechanical energy conversionElectromechanical energy conversion
Electromechanical energy conversion
 
Newton raphson method
Newton raphson methodNewton raphson method
Newton raphson method
 

Ähnlich wie Power upgrading of transmission line by combining ac dc transmission

Power electronics and its applications.pptx
Power electronics and its applications.pptxPower electronics and its applications.pptx
Power electronics and its applications.pptx
SHIVANICHAUUHAN1
 
FACTs_Final_Presensation
FACTs_Final_PresensationFACTs_Final_Presensation
FACTs_Final_Presensation
MOHAN RAKIB
 

Ähnlich wie Power upgrading of transmission line by combining ac dc transmission (20)

Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...
 
Power electronics and its applications.pptx
Power electronics and its applications.pptxPower electronics and its applications.pptx
Power electronics and its applications.pptx
 
GENERATION OF HVDC 17.8.16 (2).ppt
GENERATION OF HVDC  17.8.16 (2).pptGENERATION OF HVDC  17.8.16 (2).ppt
GENERATION OF HVDC 17.8.16 (2).ppt
 
RGPV EX7102 unit I
RGPV EX7102 unit IRGPV EX7102 unit I
RGPV EX7102 unit I
 
seminar report on vsc-hvdc poornima college of engineering
seminar report on vsc-hvdc poornima college of engineeringseminar report on vsc-hvdc poornima college of engineering
seminar report on vsc-hvdc poornima college of engineering
 
High Voltage DC Transmission
High Voltage DC TransmissionHigh Voltage DC Transmission
High Voltage DC Transmission
 
Analysis of a Single Stage Three Level Converter for a Wind Driven Self Excit...
Analysis of a Single Stage Three Level Converter for a Wind Driven Self Excit...Analysis of a Single Stage Three Level Converter for a Wind Driven Self Excit...
Analysis of a Single Stage Three Level Converter for a Wind Driven Self Excit...
 
Comparative evaluation of hvdc
Comparative evaluation of hvdcComparative evaluation of hvdc
Comparative evaluation of hvdc
 
B044040916
B044040916B044040916
B044040916
 
THD ANALYSIS OF LFAC TRANSMISSION SYSTEM
THD ANALYSIS OF LFAC TRANSMISSION SYSTEMTHD ANALYSIS OF LFAC TRANSMISSION SYSTEM
THD ANALYSIS OF LFAC TRANSMISSION SYSTEM
 
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC ConvertersModeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
 
FACTs_Final_Presensation
FACTs_Final_PresensationFACTs_Final_Presensation
FACTs_Final_Presensation
 
Flexible ac transmission FACTs
Flexible ac transmission FACTsFlexible ac transmission FACTs
Flexible ac transmission FACTs
 
wire less charging in electric vehicles
wire less charging in electric vehicleswire less charging in electric vehicles
wire less charging in electric vehicles
 
Anura g jain_ppt
Anura g jain_pptAnura g jain_ppt
Anura g jain_ppt
 
transmission line
transmission line transmission line
transmission line
 
Ehv line design
Ehv line designEhv line design
Ehv line design
 
Study and Performance Analysis of FACTS-incorporated Transmission Line
Study and Performance Analysis of FACTS-incorporated Transmission LineStudy and Performance Analysis of FACTS-incorporated Transmission Line
Study and Performance Analysis of FACTS-incorporated Transmission Line
 
Vinay report
Vinay reportVinay report
Vinay report
 
C04721623
C04721623C04721623
C04721623
 

Kürzlich hochgeladen

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 

Kürzlich hochgeladen (20)

Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 

Power upgrading of transmission line by combining ac dc transmission

  • 1.
  • 2. PROJECT THEME I. Introduction II. Background survey III. Theoretical proof of ac-dc combine transmission IV. Matlab simulation of ac-dc combine transmission V. Response of ehv ac transmission VI. Response of ac-dc combine transmission VII. Case of study VIII. Economical proof of ac-dc combine transmission IX. Advantages & Limitation of ac-dc combine transmission X. Conclusion
  • 4. 1). EHV AC Transmission 2). HVDC Transmission 3). AC-DC Combine Transmission a). AC-DC 3-phase Single Line Transmission b). AC-DC 3-phase Double Line Transmission
  • 5.
  • 6. CONDITION OF TRANSMISSION [1] VMAX = √𝟐Vph = Vd + √𝟐Va [2]VLL MAX = √𝟔Va [3] Vd= Vph/√𝟐 [4] Va = Vph/ 2
  • 8.
  • 9.
  • 10.
  • 11.
  • 12.
  • 14. AC Line: Twin Moose ACSR Bundled Conductor, 400kV, 50Hz, 320km Line Parameters: Resistance per unit length: 0.01273 Ω/km Inductance per unit length: 0.9337 mH/km Capacitance per unit length: 12.74 nF/km PURE AC TRANSMISSION SYSTEM: Sending End Voltage (VS) =400 kV Receiving End Voltage (VR) = 392.6 kV Sending End Power (PS) = 881 MW Receiving End Power (PR) = 750 MW Sending End Current (IS) = =952.5 A Receiving End Current (IR) = 1004 A X (Total Reactance per phase per circuit) =0.9337×10-3×320×314 = 93.82 Ω 𝛿 (power angle) =31.76 total power transmitted = 3×881 MW = 2643 MW Total Power received = 3×750 MW = 2250 MW Total Transmission Loss = 2643 MW – 2250 MW = 393 MW
  • 15. SIMULTANEOUS AC-DC POWER TRANSMISSION SYSTEM: Sending End AC Voltage (VS) = 400 kv Receiving End AC Voltage (VR) = 392.6 kV AC Current (Iac) = 2.341 kA Sending End AC Power (PS) = 1600 MW Receiving End AC Power (PR) = 1100 MW Total Reactance per phase per circuit (X) = 93.82 Ω Rectifier Voltage (Vdr) = 440 kV Inverter Voltage (Vdi) = 300 kV DC Link Current (Id) = 1.74 kA Sending End DC Power = 765.6 MW Receiving End DC Power = 522 MW = 70° Total Power Transmitted = 2×1600 + 765.6 = 3965.6 MW Total Power Received = 2722 MW Transmission Loss = 3965.6 MW – 2722 MW= 1243.6MW Now, dc voltage across one winding = 440/2 = 220 kV. Induced voltage across secondary winding of transformer = 200 kV Vdo = 220 kV
  • 16. So, power factor of the rectifier (cosθr) = 220/271 = 0.812 Similarly for inverter Vdoi = 271 kV Vdo = 150 kV Power factor of the inverter (cosθi) = 150/271 = 0.5535 So, reactive power drawn by the rectifier = 765.6 tanθr = 550.3 MVAR Reactive power drawn by the inverter = 522 tanθi = 785.45 MVAR Power Up gradation = Power transformer in composite AC – DC transmissions - power transmitted in pure transmission / power transmitted in pure transmission = [ 2722 – 2250 / 2250 ] Χ 100 = 21 %
  • 18. ECONOMY OF THE SYSTEM [1] ECONOMY OF SYSTEM BASED ON COMPARISON [2] ECONOMY OF SYSTEM BASED ON STRUCTURE
  • 19. FOR DOUBLE CIRCUIT EHV LINE Base cost of 500 KV double circuit transmission line Rs. 1,78,020,000 Line Multiplier : (1) Conductor ACSR (1.0) √ ACSS (1.08) TLS (3.60) (1) Tower Structure: Lattice (1.0) √ Tabular Steel (1.50) (1) Transmission Length: Up to 4.82 Km (1.50) 4.82 Km to 16.093 Km (1.20) Above 16.093 Km (1.0) √ Total transmission line cost = [ (base transmission cost)*(conductor multiplier)*(structure multiplier) *(1.6093)*(no of kilometer) ] Total transmission line cost Rs. 5.696641010 SUB-STATION CAPITAL COST Base cost of Sub-Station (500 KV) Rs. 148,320,000 LINE & TRANSFORMER POSITION COST & MULTIPLIER (500 KV) Cost multiplier : Breaker & half multiplier (1.50) Ring bus multiplier (1.0) √ Cost per line / transformer position Rs. 173,040,000 Transformer cost (Rs. per MVA) 230 / 500 KV Transformer – Rs. 660,000 115 / 500 KV Transformer – Rs. 600,000 √ Transformer cost (Rs. Per MVA) Rs. 600,000 REACTIVE COMPONENTS COST PER MVAR Shunt reactor Rs. 1,200,000 Series reactor Rs. 600,000 SVC capital cost Rs. 5,100,000 Total substation cost = [ (sub-station base cost)+(line per transformer position base cost)*(no. of line per transformer position)*(CRB or BAAH multiplier)+(transformer cost per MVA)*(transformer MVA rating)+(SVC cost per MVAR)*(require MVARs)+(series capacitor cost per MVAR)*(require MVARs)+(shunt reactor cost per MVAR)*(require MVARs) ] Total substation cost Rs. 839,052,000 x 2 = 1,678,104,000 TOTAL COST
  • 20. HVDC TRANSMISSION LINE 500 KV HVDC bidirectional pole line (per Km) Rs. 89,040,000 TOTAL COST OF TRANSMISSION LINE Total cost of transmission line Rs. 2.84928X1010 SUB-STATION CAPITAL COST Converter terminal (include DC switching station equipment) Rs. 3,850,000,000 Reactive support (synchronous condensers, SVCs, etc) Rs. 2,100,000,000 AC switch yard Rs. 280,000,000 COST OF SUB-STATION Cost of sub-station Rs. 6,230,000,000 x 2 = 1.246 x 1010 TOTAL COST Total cost Rs. 3.47228 x 1010
  • 21. COMBINE HVDC-HVAC SUB-STATION COST Sub-Station cost Rs. 6,230,000,000 x 2 = 1.246 x 1010 COST OF ZIG-ZAG TRANSFORMER (125) Cost of zig-zag transformer per MVA (Rs. Per MVA) Rs. 78,000 Cost of 4 zig-zag transformer (Rs. Per MVA) Rs. 78,000 x 4 = 312,000 Total cost of four zig-zag transformer Rs. 390,000,000 TOTAL COST Total cost Rs. 1.285 x 1010
  • 23. ADVANTAGES OF SYSTEM (1) The feasibility to convert ac transmission line to a composite ac–dc line has been demonstrated. (2) For the particular system studied, there is substantial increase (about 21.45%) in the load ability of the line. (3) The line is loaded to its thermal limit with the superimposed dc current. (4) The dc power flow does not impose any stability problem. (5) Dc current regulator may modulate ac power flow. (6) There is no need for any modification in the size of conductors, insulator strings, and towers structure of the original line. (7) The optimum values of ac and dc voltage components of the converted composite line are ½ and 1/√2 times the ac voltage before conversion, respectively.
  • 24. LIMITATION (1) There Is Certain Limit Of Power Upgrading Of Transmission Line, So We Can Not Apply This Basic Scheme Where New Unit Has More Power Capacity Then Limit Of Power Upgrading Of Transmission Line. (2) The Combine HVDC-HVAC Transmission Line Is Very Complicated. (3) There Is Necessity Of Double Circuit Long Extra High Voltage AC Transmission Line In Running Power Generating Station. (4) We Cannot Transfer The Power By This Basic Scheme Where Double Circuit EHV Line Not Going From The Power Generating Station.
  • 25. APPLICATION (1) ADDITION OF GENERATION UNIT (2) SOLAR GENERATION UNIT
  • 26.
  • 27. CONCLUSION For the particular system under study, the power up gradation of the line is observed to be twenty one percent with the simultaneous ac-dc power flow. Maximum power up gradation is obtained at a transmission angle of 60º. The line is loaded to its thermal limit with the superimposed dc current. The dc power flows independent of the ac power in the transmission line.
  • 28. REFERENCES PAPERS:- [1] “Upgradation Of Power Flow In EHV AC Transmission” International Journal Of Scientific Engineering And Technology By K.K.Vasishta Kumar, K.Sathish Kumar. [2] “Power Upgrading Of Transmission Line By Combining AC-DC Transmission”, Swarnandhra College Of Engineering Technology Narsapur By Jarupula Somlal. [3] “Power System Stability Enhancement By Simultaneous AC-DC Power Transmission” International Journal Of Advanced Research In Electrical, Electronics And Instrumentation Engineering Vol. 2, Issue 5, May 2013 By Abhishek Chaturvedi, V. K. Tripathi, T Vijay Muni, Neeraj Singh. [4] “Power Tapping Of Upgrade Transmission Line By Using Composite Ac-dc Power Transmission Lines” International Journal Of Engineering Research And Development By CH.Veeraiah, Y.Rambabu, V.K.R.Mohan Rao.
  • 29. BOOKS:- [1] D P Kothari And I J Nagrath “MODERN POWER SYSTEM ANALYSIS” FNAE Fnasc, Fellow-ieee Director General, Raisoni Group Of Institutions, Nagpur. [2] Tim Mason- Project Manager, Trevor Curry And Dan Wilson, “CAPITAL COSTS FOR TRANSMISSION AND SUBSTATION” Western Electricity Coordinating Council. [3] Roberto Rudervall, J.P. Charpentier And Raghuveer Sharma, “HIGH VOLTAGE DIRECT CURRENT (HVDC)TRANSMISSION SYSTEMS” Technology Review Paper, Presented At Energy Week 2000, Washington, D.C, USA, March 7-8, 2000.