Types of P refabricat ed Modular 
Data Centers 
White Paper 165 
Revision 0 
by Wendy Torell 
Executive summary 
Data center systems or subsystems that are pre-assembled 
in a factory are often described with terms 
like prefabricated, containerized, modular, skid-based, 
pod-based, mobile, portable, self-contained, all-in-one, 
and more. There are, however, important distinc-tions 
between the various types of factory-built 
building blocks on the market. This paper proposes 
standard terminology for categorizing the types of 
prefabricated modular data centers, defines and 
compares their key attributes, and provides a frame-work 
for choosing the best approach(es) based on 
business requirements. 
by Schneider Electric White Papers are now part of the Schneider Electric 
white paper library produced by Schneider Electric’s Data Center Science Center 
DCSC@Schneider-Electric.com
Types of Prefabricated Modular Data Centers 
Many terms, with varying definitions and scopes, have been used to describe data center 
systems or subsystems that are pre-assembled in a factory. A partial list includes: 
• Containerized 
• Self-contained 
• Modular 
• Prefabricated 
• Portable 
• Mobile 
• Pod (based) 
• Skid (based) 
These terms create confusion and lead to dysfunctional discussions because they overlap 
and are ambiguous in meaning. 
A prefabricated modular data center is defined here in this paper as a data center that is: 
1. made up of at least one pre-engineered, factory-integrated, and pre-tested assembly 
of subsystems that have traditionally been installed separately onsite 
2. mounted on a skid or in an enclosure 
While the benefits of this type of approach to data centers is well-documented (such as in 
White Paper 163, Prefabricated Power and Cooling Modules for Data Centers), the lack of a 
common language and classification system has resulted in confusion over the differences in 
attributes and applications between them. 
This white paper presents a framework for classifying the different types of prefabricated 
modular data centers, based on three attributes, so that ambiguity is eliminated. Definitions 
and categories are presented, along with guidance for choosing the right approach(es) for 
given business requirements. Figure 1 illustrates the three attributes that, together, define 
the majority of prefabricated modular data centers. 
• Power 
• Cooling 
• IT 
Functional block 
• ISO container 
• Enclosure (non-ISO) 
• Skid-mounted 
Form factor 
• Fully prefabricated data center 
• Semi-prefabricated data center 
• All-in-one data center 
Configuration 
Schneider Electric – Data Center Science Center Rev 0 2 
Introduction 
Figure 1 
Framework for types of 
prefabricated data centers
Types of Prefabricated Modular Data Centers 
Pre-engineered vs. 
Prefabricated data centers 
The terms pre-engineered and prefabricat-ed 
are sometimes used interchangeably, 
however there are important distinctions 
between the two. 
A data center that is pre-engineered is 
designed to meet pre-determined perfor-mance 
specifications, and consists of, at 
minimum, a documented list of materials, 
system level specifications, and drawings of 
the integrated system. 
A prefabricated data center is a data 
center that is pre-engineered and has its 
systems (hardware & software) pre-assembled, 
integrated, and tested in a 
factory environment to shorten deployment 
timeframe and improve predictability of 
performance. 
A reference design is an example of a 
system that is pre-engineered but not 
necessarily prefabricated. A power or 
cooling facility module is an example of a 
prefabricated system. 
One reason modular data centers are segmented by functional block is because 
data centers may only require a specific resource (just power, just cooling) due to 
stranded capacity in their existing facility. Another is because different personnel 
with different skill sets are needed to operate and maintain each (i.e. facilities 
staff vs. IT staff, mechanical operators vs. electrical operators). And yet another 
has to do with the physical constraint of the module’s foot print. Form factor is the 
second key attribute that distinguishes prefabricated solutions. A form factor may 
be chosen based on the application (i.e. a data center may be required to be 
permanently mobile – on wheels – to meet a business need); or it may be 
constrained by its capacity (i.e. a power system in an ISO enclosure is generally 
limited to around 500 kW, but a skid-mounted design can support greater 
capacities). 
The prefabricated functional blocks are deployed in various configurations. Some 
prefabricated data centers include a mix of prefabricated modules and traditional 
or “stick built” systems (such as modular power and cooling with traditional IT 
space). Others are fully prefabricated, meaning all three functional blocks – 
power, cooling, and IT – are prefabricated. Lastly, a specific configuration of a 
fully prefabricated data center is an “all-in-one”, where the power, cooling, and IT 
co-exist in a single enclosure. 
The three attributes – functional block, form factor, and configuration – are further 
defined and explained in the following sections. 
The functions of a data center can be broken down into three major categories – the power 
plant, the cooling plant, and the IT space. Prefabricated data center modules sometimes 
provide multiple functions (referred to as all-in-one configurations), but often they provide one 
function of the data center, for the following reasons: 
• A prefabricated module may be needed only for a specific resource (just power, just 
cooling, or just IT space) because of stranded capacity in their existing facility 
• A greater IT capacity is needed than what an all-in-one module can support, and a 
single IT space is required (physical space constraint of modules) 
• There is a requirement to separate personnel (IT, mechanical, electrical) from a 
maintenance and operations perspective to reduce human error risks 
• An optimized footprint is needed, and function-specific modules can utilize larger ca-pacity 
components and share clearances to provide a greater kW per square foot or 
square meter 
Power 
A prefabricated power module (see Figure 2) is designed to provide bulk power to the data 
center. It may power a modular IT space or a traditional IT space within a building. The 
typical subsystems within a power facility module are switchgear / switchboards, ATS, UPSs 
with batteries, transformers, and panelboards. In addition, support systems such as lighting, 
security, cooling may exist in the module for enclosed form factors. Standby generators are 
generally a separate module that can be integrated with the power module. 
Schneider Electric – Data Center Science Center Rev 0 3 
Functional block
Types of Prefabricated Modular Data Centers 
Cooling 
Today’s data centers use a range of cooling architectures to support the IT space, based on 
requirements for cost, efficiency, reliability, etc. The physical location (climate) of the data 
center is also a big driver when determining the optimal approach. Schneider Electric’s 
TradeOff Tool, Cooling Economizer mode PUE Calculator, helps illustrate the energy 
tradeoffs of the various architectures, and white paper 59, The Different Technologies for 
Cooling Data Centers, provides further details on the different cooling approaches. At a high 
level, the typical subsystems within prefabricated cooling modules are shown in Table 1. 
Chiller plant 
module 
DX plant 
module 
Indirect air 
module 
Direct air 
module 
• Air cooled chiller 
• Pumps / drives 
• Storage tank 
• Dry cooler / 
evaporative cooler 
• Air cooled 
condenser or dry 
cooler 
• Pump package 
• Air-to-air heat 
exchanger 
• Evaporative 
cooling 
• DX backup 
• Fans 
• Ducts 
• Air filters 
• Evaporative 
cooling 
• DX backup 
• Fans 
• Ducts 
Figure 3 illustrates a hydronics module consisting of pumps, VFDs, management, and 
connections for an air cooled chiller modular design. 
IT Space 
A prefabricated IT space is one that houses the IT equipment. It also houses the support 
infrastructure to distribute power and air to those systems, as well as provides a suitable work 
environment for the IT staff that must operate the space. Typically, such a module incorpo-rates 
the following subsystems: 
• IT racks to hold the IT equipment 
• Power distribution units (PDUs) 
• Rack PDUs 
• Air distribution system (CRAHs, CRACs, air ducts, depending on architecture) 
• Humidification / dehumidification system 
Schneider Electric – Data Center Science Center Rev 0 4 
Figure 2 
Example of a “Power” 
functional block 
Table 1 
Typical subsystems within 
prefabricated cooling 
modules 
Figure 3 
Example of a “Cooling” 
functional block
Types of Prefabricated Modular Data Centers 
• Cabling infrastructure / cable management 
• Fire detection / protection 
• Lights 
• Security systems 
In addition to having the systems pre-engineered and integrated, having the IT equipment in 
a module provides the added benefit of being a form of containment, to separate the hot and 
cold air streams, which is critical to effective and efficient air distribution. Figure 4 is an 
example of an IT space module consisting of 10 IT racks and the supporting systems, but 
other form factors exist that increase the rack capacity. 
The following is a general rule of thumb when it comes to the cost effectiveness of IT space 
modules: 
The greater the IT density per rack, the more sensible IT space modules are, due to the 
increase in capacity of each module 
Prefabricated data centers can take on different form factors – meaning the type of structure, 
the size, and shape. The form of a particular solution impacts the transportability of it, the 
placement of it, and its location (inside vs. outside on the ground vs. on a rooftop). The three 
general forms of prefabricated data center modules are: 
• ISO container 
• Enclosure 
• Skid-mounted 
Which form factor or combination of form factors is suitable for a given data center project is 
based on requirements such as transportability, capacity, scalability, etc. Table 2 summariz-es 
how each compares in terms of location, placement, and transportation. In addition, the 
form of the module impacts the capacity of the module, since the specific dimensions of the 
module constrain the equipment that fits within it. There may also be permitting and tax 
implications in certain geographies. 
These and other attributes are further described in the following sections along with examples 
to illustrate the form factors. 
Schneider Electric – Data Center Science Center Rev 0 5 
Figure 4 
Example of an “IT Space” 
functional block 
Form factor
Types of Prefabricated Modular Data Centers 
Location Placement Transportation 
ISO 
container 
Generally, 
outdoors 
Mount on concrete 
pad or other founda-tion 
Standard dimensions; from 
ship to rail to truck 
Enclosure 
May be placed 
indoors or 
outdoors, de-pending 
on 
weather rating & 
application 
May ship in parts that 
require assembly 
onsite; Mount on 
concrete pad or other 
foundation 
Shipping preparations may 
be required if in parts; 
Delivery may require 
permits, escorts depending 
on width 
Skid-mounted 
Generally, indoors Often placed directly 
on room floor 
Shipping preparations 
required; Delivery may 
require permits, escorts 
depending on width 
ISO container 
ISO containers are standardized re-usable steel shipping enclosures, designed for safe, 
efficient, and secure storage and movement of materials from one from of transportation to 
another (i.e. ship to rail to truck). There are a number of ISO standards that regulate many 
aspects of freight containers from the classification, dimensions, to corner fitting specifica-tions, 
to hooks for lifting the containers, to the markings/identification on the container.1 
These standards make transportation and handling simpler and standardized. 
Standard footprints of these containers for use as data center modules are: 20 ft x 8 ft (6.10 
m x 2.44 m) and 40 ft x 8 ft (12.2 m x 2.44 m). The 20 ft (6.10 m) containers come in a 
standard height of 8 ft 6 in (2.591 m), and the 40 ft (12.2 m) containers come in either the 
standard height of 8 ft 6 in (2.591 m) or the “high bay” height of 9 ft 6 in (2.896 m). Generally, 
the high bay containers are used, as they provide greater flexibility for equipment placement 
within the module. 
Often times, when containers are used as the shell for data center modules, they are 
modified in the following ways: 
• Cut-outs for doors and other mounted equipment 
• Equipment installed that hangs off the side or top of container 
With these types of modifications, the container may no longer be ISO certified, for example, 
limiting its ability to be stacked with other containers. However, having the standard footprint 
of an ISO container makes it simpler to transport, lift, and place than non-standard footprints 
which tends to reduce installation costs. It is also generally lower in cost to modify a 
standard shell than to construct one from the ground up. 
ISO container modules generally have a practical limit on capacity of around 500 kW for 
power or cooling plants, and around 200 - 250 kW for an IT space. The IT module capacity 
constraint is based on the number of IT racks that can fit within the footprint, and there are 
space tradeoffs with different rack arrangements. For example, if the racks are placed along 
the back wall to provide a wide cold aisle, the hot aisle may only be accessible through 
panels or doors from the outside. If the IT racks are placed as a long row in the center, the 
1 http://www.container-transportation.com/iso-container-standards.html (accessed 9/18/2013) 
Schneider Electric – Data Center Science Center Rev 0 6 
Table 2 
Typical form factors 
“Mobile” modules 
Mobility is a benefit of all 
prefabricated module form 
factors, with ISO containers 
providing the best transportabil-ity; 
however sometimes a 
module is designed to be 
permanently mobile, meaning it 
is designed in a structure that 
includes wheels and axles. 
These permanently mobile 
modules are often built as all-in-one 
modules that are used for 
temporary data center needs 
such as military applications or 
sporting events. The figure 
below illustrates two examples:
Types of Prefabricated Modular Data Centers 
hot and cold aisle must be narrower. Lastly, if multiple short aisles are used perpendicular to 
the length of the container, a narrow aisle will be likely to move from row to row. In general, 
the capacity constraint of the IT modules make them more suitable for smaller data centers. 
Larger capacity needs would generally steer towards more traditional IT spaces. 
Often times, this form factor requires lighting and security, since they are accessed by 
personnel for operation and maintenance. 
Placement of ISO containers usually involves laying slab on grade (concrete pad) outdoors. 
A crane would be used to lift the container off the truck and onto the pad. When used to 
supplement capacity in a constrained existing brick and mortar facility, the container(s) are 
generally placed in close proximity to the perimeter of the building, near the data center they 
are supporting. Sometimes, a power or IT container is placed indoors in a warehouse 
environment – in order to protect the personnel from inclement weather during operation & 
maintenance activities, and to provide added security for their critical systems. 
Figure 5 illustrates a power module and a cooling module, both designed with ISO containers 
and modified to meet the system requirements. 
Enclosure 
Another form factor, in this paper referred to as “enclosure”, is less standard in terms of its 
dimensions, and therefore does not necessarily meet specific shipping standards like the ISO 
containers. Enclosures are also commonly referred to as shells, metal houses, and pods. 
Relative to ISO containers, transporting and handling costs may be greater; and onsite work 
may be greater if the structure isn’t fully assembled in the factory. For example, a wide 
enclosure may come in two sections, as Figure 6 illustrates. Some enclosures, often 
referred to as modular rooms, are actually constructed in a factory, integrated with the data 
center equipment, tested and commissioned, and then disassembled and put back together 
at the customer site, much like a Lego building block kit. 
The benefit of this form factor is that it offers more flexibility in terms of the IT capacity it can 
support as well as the layout of the equipment within the enclosure. 
The majority of enclosures are rated for outdoor use and can be exposed to varying weather 
conditions, but there are some that are not, and should be installed indoors (i.e. inside a 
warehouse). Even ones that are rated for outdoor conditions may at times be installed 
indoors for reasons like security, personnel access, or shelter from inclement weather as 
personnel carry equipment (e.g. servers) to an enclosure. Some enclosures are rooms 
Schneider Electric – Data Center Science Center Rev 0 7 
Figure 5 
Examples of ISO container 
form factor 
Figure 6 
Examples of an IT space 
enclosure that ships in 2 
parts
Types of Prefabricated Modular Data Centers 
where personnel can walk into them2, for maintenance and operation, while others would be 
better described as enclosed “systems”, where the primary access for personnel is through 
access panels on the outside of the enclosure (non-walk-in type). Table 3 summarizes this 
further categorization of enclosures and provides examples of each. 
Personnel accessibility 
Indoor / outdoor rating 
Indoor, enclosed “system” 
• Non-weather proof 
• Personnel access only through 
access panels on outside of 
enclosure 
Indoor, walk-in enclosure 
• Non-weather proof 
• Personnel have full access within 
enclosure 
Outdoor, enclosed “system” 
• Weather proof for outdoors 
• Personnel access only through 
access panels on outside of 
enclosure 
Outdoor, walk-in enclosure 
• Weather proof for outdoors 
• Personnel have full access within 
enclosure 
A key driver for choosing an enclosed form factor is the need for the data center subsystems 
to go outside, or be protected from other elements such as in a hazardous, rugged, or 
adverse indoor environment. Enclosures that are placed outdoors should have an appropri-ate 
level of security to prevent undesirable access (i.e. vandalizing). 
Skid-mounted 
“A skid mount is a method of distributing and storing machinery where the machinery at point 
of manufacture is permanently mounted in a frame or onto rails or a metal pallet. The 
equipment can then be easily and securely transported as and used as a unit.”3 Figure 7 
illustrates examples of skid-mounted data center modules. 
Skid-mounted modules are generally not designed for outdoor use, as components are 
unprotected from the outdoor elements. Power modules are often in this form factor, as items 
like switchgear, UPS, transformers, and panelboards don’t have a requirement to be outdoors 
2 An enclosure designed for personnel occupancy, such as the one in Figure 6 must have lighting, fire 
protection, security, and a means of egress. 
3 http://en.wikipedia.org/wiki/Skid_mount 
Schneider Electric – Data Center Science Center Rev 0 8 
Table 3 
Categories of enclosures 
and examples 
Figure 7 
Examples of skid-mounted 
form factors for modular 
data centers 
X (No practical examples)
Types of Prefabricated Modular Data Centers 
like many cooling modules do. There are also fewer capacity constraints due to footprint 
limitations with skid-mounted power modules (vs. enclosures or ISO containers), enabling 
them to support greater capacity data centers. So, as the power requirement increases, the 
skid-mounted approach becomes more sensible. In general, the cost of a prefabricated skid-mounted 
module is less than the equivalent enclosure design, often by up to 40% less. 
Note – skid-mounted systems for IT spaces are not logical because it leaves the equipment 
open to the space rather than separating hot and cold air from the IT equipment. 
There are several ways the functional blocks can be implemented in a data center. These 
approaches fall under three main categories: 
• Semi-prefabricated – A data center comprised of a combination of prefabricated 
functional blocks and traditional “stick built” systems 
• Fully prefabricated – A data center comprised completely of prefabricated IT, power, 
and cooling modules 
• All-in-one – A data center that is self-contained in a single enclosure, with IT, power, 
and cooling systems 
In this section, each configuration is explained, illustrated examples shown, and typical 
scenarios when each would be deployed are described. Common across all of the configura-tions 
is the need to deploy the data center in weeks rather than months or years, the ability to 
scale the data center if or when needed, and the desire for improved predictability of perfor-mance. 
There are also specific requirements (i.e. around space or cash flow or speed) that 
also influence the decision. 
Semi-prefabricated data centers 
A common deployment of prefabricated data centers consists of a mix of prefabricated 
modules and traditional “stick built” systems. This approach is referred to as “semi-prefabricated”. 
Figure 8 illustrates an example, where power and cooling modules support a 
traditional IT space within a building. Other combinations are possible as well, such as a 
traditional power and cooling plants with IT space modules outside. The specific combination 
of prefabricated and traditional systems deployed depends on the application and need of the 
data center. A retrofit project, where a particular resource is capacity constrained, is a 
common situation where this configuration would be deployed. 
Schneider Electric – Data Center Science Center Rev 0 9 
Configuration 
Figure 8 
Example of semi-prefabricated 
data center 
with prefabricated power 
and cooling modules and 
traditional IT space
Types of Prefabricated Modular Data Centers 
Semi-prefabricated data centers are generally implemented when: 
• An existing data center is out of bulk power capacity and is space constrained in the 
electrical room, but IT space is available for growth 
• An existing data center is out of bulk cooling (heat rejection) capacity, but IT space is 
available for growth 
• An existing data center is out of IT space due to a deployed density that was lower than 
the design density, and there’s plenty of bulk power and cooling capacity 
• A new enterprise-class data center has a mixed IT environment, which limits the appli-cation 
of IT modules, but power and cooling modules can be deployed 
• A short-term plan is desired to address a gap in capacity and/or reliability until a long-term 
plan is implemented (at which time the modules would be re-purposed) 
Fully prefabricated data centers 
In a fully prefabricated data center, modules are implemented for all three functional blocks – 
providing the bulk power to the data center, providing heat rejection for the data center, and 
housing the critical IT equipment. Figure 9 illustrates two examples of fully prefabricated 
data centers and how the modules may be laid out on the grounds. Deployments vary in 
form factor, power capacity, technology, and placement (inside or outside), based on the 
business requirements. 
Fully prefabricated data centers are generally implemented when: 
• Scalability of the entire data center is a key business driver 
• A multi-tenant data center wants to partition IT spaces by tenant, and requires scalabil-ity 
of power and cooling resources 
• A large scale homogenous IT data center wants to deploy equipment in a step and 
repeat manner 
• A high density, high performance computing data center deploys thousands of servers 
repetitively and wants to scale capacity as the servers scale 
• A large disaster recovery data center is needed 
Schneider Electric – Data Center Science Center Rev 0 10 
Figure 9 
Example layouts of fully 
prefabricated data 
centers, based on Schnei-der 
Electric reference 
designs
Types of Prefabricated Modular Data Centers 
All-in-one data centers 
An all-in-one data center is really a specific type of fully prefabricated data center, but is 
being highlighted as a separate configuration because of its unique characteristic of having 
the components co-located in a single structure. Figure 10 is an example of an all-in-one 
design. 
When multiple functions are combined into a single module, the capacity is generally more 
limited. A typical limit to an all-in-one (power, cooling, and IT) is approximately 150 kW in a 
single module such as an ISO container footprint. This limit is higher for modules that arrive 
in sections and snap together in the field. Beyond 2 or 3 all-in-one modules on a site 
(approximately 500 kW), all-in-ones are cost prohibitive. 
Although these configurations are referred to as “all-in-one”, there is often some additional 
support infrastructure outside of the module, such as the generator or chiller. And yet 
another variation may exist where only the IT and cooling is combined in a single enclosure, 
and the UPS is located in a separate module. This is common for fresh air cooling designs, 
where the IT space is adapted to allow either the fresh air directly in, or with air-to-air heat 
exchangers to indirectly cool the space. 
All-in-one prefabricated data centers are generally implemented when: 
• A temporary need exists such as for military use, sporting or other temporary event 
• Mobility of the data center is important 
• A remote branch site requires a small data center, less than 150 kW 
• A small data center is in a mixed-use facility and desires ownership and control of all 
functions 
• A data center will be located in a harsh environment like an industrial application, an oil 
rig, etc. 
• A small disaster recovery data center is needed 
Schneider Electric – Data Center Science Center Rev 0 11 
Figure 10 
Example of all-in-one 
prefabricated data center
Types of Prefabricated Modular Data Centers 
There are many approaches to implementing prefabricated modular data centers; however, a 
lack of standard terminology for describing them has made selecting the appropriate type 
difficult. The optimal configuration, including the right functional blocks and form factors 
depends on the application and specific business requirements. In some cases, a fully 
prefabricated data center is the best approach, and for others, a semi-prefabricated approach 
with a mix of prefabricated modules and traditional systems is best. Understanding the 
limitations and benefits of each form factor helps ensure the optimal approach is selected. 
Ultimately, business needs around speed of deployment, scalability, space constraints, 
capacity, and cash flow drive the decision. 
About the author 
Schneider Electric – Data Center Science Center Rev 0 12 
Conclusion 
Wendy Torell is a Senior Research Analyst at Schneider Electric’s Data Center Science 
Center. In this role, she researches best practices in data center design and operation, 
publishes white papers & articles, and develops TradeOff Tools to help clients optimize the 
availability, efficiency, and cost of their data center environments. She also consults with 
clients on availability science approaches and design practices to help them meet their data 
center performance objectives. She received her Bachelors of Mechanical Engineering 
degree from Union College in Schenectady, NY and her MBA from University of Rhode 
Island. Wendy is an ASQ Certified Reliability Engineer.
Types of Prefabricated Modular Data Centers 
Prefabricated Power and Cooling Modules for Data Centers 
White Paper 163 
TCO Analysis of a Traditional Data Center vs. 
a Scalable, Prefabricated Data Center 
White Paper 164 
Specification of Modular Data Center Architecture 
White Paper 160 
Practical Considerations for Implementing Prefabricated Data Centers 
White Paper 166 
Prefabricated vs. Traditional Data Center Cost Calculator 
TradeOff Tool 17 
Browse all 
TradeOff Tools™ 
Contact us 
Schneider Electric – Data Center Science Center Rev 0 13 
Resources 
Browse all 
white papers 
whitepapers.apc.com 
tools.apc.com 
© 2014 Schneider Electric. All rights reserved. 
For feedback and comments about the content of this white paper: 
Data Center Science Center 
dcsc@schneider-electric.com 
If you are a customer and have questions specific to your data center project: 
Contact your Schneider Electric representative at 
www.apc.com/support/contact/index.cfm

Weitere ähnliche Inhalte

Was ist angesagt?

Datacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildDatacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildChristopher Kelley
 
Advantages of a modern DCS in coal handling
Advantages of a modern DCS in coal handlingAdvantages of a modern DCS in coal handling
Advantages of a modern DCS in coal handlingSchneider Electric
 
How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...
How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...
How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...Schneider Electric
 
The Mine Central Control Room: From Concept to Reality
The Mine Central Control Room: From Concept to Reality The Mine Central Control Room: From Concept to Reality
The Mine Central Control Room: From Concept to Reality Schneider Electric
 
Essential Elements of Data Center Facility Operations
Essential Elements of Data Center Facility OperationsEssential Elements of Data Center Facility Operations
Essential Elements of Data Center Facility OperationsSchneider Electric
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operationsSchneider Electric
 
Effect on Substation Engineering Costs of IEC61850 & System Configuration Tools
Effect on Substation Engineering Costs of IEC61850 & System Configuration ToolsEffect on Substation Engineering Costs of IEC61850 & System Configuration Tools
Effect on Substation Engineering Costs of IEC61850 & System Configuration ToolsSchneider Electric
 
[Industry report] U.S. Grid Automation Report
[Industry report] U.S. Grid Automation Report[Industry report] U.S. Grid Automation Report
[Industry report] U.S. Grid Automation ReportSchneider Electric
 
[Webinar Presentation] Best Practices for IT/OT Convergence
[Webinar Presentation] Best Practices for IT/OT Convergence[Webinar Presentation] Best Practices for IT/OT Convergence
[Webinar Presentation] Best Practices for IT/OT ConvergenceSchneider Electric
 
POWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTERPOWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTERvivekprajapatiankur
 
Industrial sawmill solution Wood Mizer
Industrial sawmill solution Wood MizerIndustrial sawmill solution Wood Mizer
Industrial sawmill solution Wood MizerSchneider Electric
 
Datacenter101
Datacenter101Datacenter101
Datacenter101tarundua
 
Simplifying Data Center Design/ Build
Simplifying Data Center Design/ BuildSimplifying Data Center Design/ Build
Simplifying Data Center Design/ BuildSchneider Electric
 
The Intelligent and Connected Data Center
The Intelligent and Connected Data CenterThe Intelligent and Connected Data Center
The Intelligent and Connected Data CenterSchneider Electric
 
Integrated Control and Safety - Assessing the Benefits; Weighing the Risks
Integrated Control and Safety - Assessing the Benefits; Weighing the RisksIntegrated Control and Safety - Assessing the Benefits; Weighing the Risks
Integrated Control and Safety - Assessing the Benefits; Weighing the RisksSchneider Electric
 
The Data Center Evolution and Pre-Fab Data Centers
The Data Center Evolution and Pre-Fab Data CentersThe Data Center Evolution and Pre-Fab Data Centers
The Data Center Evolution and Pre-Fab Data CentersSchneider Electric
 
A framework for converting hotel guestroom energy management into ROI
A framework for converting hotel guestroom energy management into ROIA framework for converting hotel guestroom energy management into ROI
A framework for converting hotel guestroom energy management into ROISchneider Electric
 
Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Schneider Electric
 

Was ist angesagt? (20)

Datacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildDatacenter Strategy, Design, and Build
Datacenter Strategy, Design, and Build
 
Advantages of a modern DCS in coal handling
Advantages of a modern DCS in coal handlingAdvantages of a modern DCS in coal handling
Advantages of a modern DCS in coal handling
 
How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...
How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...
How Test Labs Reduce Cyber Security Threats to Industrial Control Systemse cy...
 
The Mine Central Control Room: From Concept to Reality
The Mine Central Control Room: From Concept to Reality The Mine Central Control Room: From Concept to Reality
The Mine Central Control Room: From Concept to Reality
 
Essential Elements of Data Center Facility Operations
Essential Elements of Data Center Facility OperationsEssential Elements of Data Center Facility Operations
Essential Elements of Data Center Facility Operations
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operations
 
Effect on Substation Engineering Costs of IEC61850 & System Configuration Tools
Effect on Substation Engineering Costs of IEC61850 & System Configuration ToolsEffect on Substation Engineering Costs of IEC61850 & System Configuration Tools
Effect on Substation Engineering Costs of IEC61850 & System Configuration Tools
 
Ensuring your plant is secure
Ensuring your plant is secureEnsuring your plant is secure
Ensuring your plant is secure
 
[Industry report] U.S. Grid Automation Report
[Industry report] U.S. Grid Automation Report[Industry report] U.S. Grid Automation Report
[Industry report] U.S. Grid Automation Report
 
[Webinar Presentation] Best Practices for IT/OT Convergence
[Webinar Presentation] Best Practices for IT/OT Convergence[Webinar Presentation] Best Practices for IT/OT Convergence
[Webinar Presentation] Best Practices for IT/OT Convergence
 
POWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTERPOWER POINT PRESENTATION ON DATA CENTER
POWER POINT PRESENTATION ON DATA CENTER
 
Industrial sawmill solution Wood Mizer
Industrial sawmill solution Wood MizerIndustrial sawmill solution Wood Mizer
Industrial sawmill solution Wood Mizer
 
Datacenter101
Datacenter101Datacenter101
Datacenter101
 
Simplifying Data Center Design/ Build
Simplifying Data Center Design/ BuildSimplifying Data Center Design/ Build
Simplifying Data Center Design/ Build
 
The Intelligent and Connected Data Center
The Intelligent and Connected Data CenterThe Intelligent and Connected Data Center
The Intelligent and Connected Data Center
 
Integrated Control and Safety - Assessing the Benefits; Weighing the Risks
Integrated Control and Safety - Assessing the Benefits; Weighing the RisksIntegrated Control and Safety - Assessing the Benefits; Weighing the Risks
Integrated Control and Safety - Assessing the Benefits; Weighing the Risks
 
The Data Center Evolution and Pre-Fab Data Centers
The Data Center Evolution and Pre-Fab Data CentersThe Data Center Evolution and Pre-Fab Data Centers
The Data Center Evolution and Pre-Fab Data Centers
 
project report on DATACENTER
project report on DATACENTERproject report on DATACENTER
project report on DATACENTER
 
A framework for converting hotel guestroom energy management into ROI
A framework for converting hotel guestroom energy management into ROIA framework for converting hotel guestroom energy management into ROI
A framework for converting hotel guestroom energy management into ROI
 
Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?
 

Andere mochten auch

panel built metal building
panel built metal buildingpanel built metal building
panel built metal buildingathome here
 
prefabricated houses india
prefabricated houses indiaprefabricated houses india
prefabricated houses indiaJoyousRay
 
Bc open pre fabricated construction system
Bc open pre fabricated construction systemBc open pre fabricated construction system
Bc open pre fabricated construction systemAnuj Singhal
 
Introduction of Prefabricated structures
Introduction  of Prefabricated structuresIntroduction  of Prefabricated structures
Introduction of Prefabricated structuresYogi Yogesh
 
Spaceframe and prefabrication
Spaceframe and prefabricationSpaceframe and prefabrication
Spaceframe and prefabricationkaiwan1996
 
Prefabrication for improving Sustainability and Economics of Civil Engineerin...
Prefabrication for improving Sustainability and Economics of Civil Engineerin...Prefabrication for improving Sustainability and Economics of Civil Engineerin...
Prefabrication for improving Sustainability and Economics of Civil Engineerin...Ankit Singhai
 
Prefabrication
PrefabricationPrefabrication
Prefabricationaaronetan
 
Prefabrication types and Applications explained
Prefabrication types and Applications explainedPrefabrication types and Applications explained
Prefabrication types and Applications explainedEyad Reda
 
PREFABRICATED STRUCTURES
PREFABRICATED STRUCTURESPREFABRICATED STRUCTURES
PREFABRICATED STRUCTURESRajendran s.
 
Prefabricated structures
Prefabricated structuresPrefabricated structures
Prefabricated structuresFAIZAL MUHAMMED
 

Andere mochten auch (14)

panel built metal building
panel built metal buildingpanel built metal building
panel built metal building
 
prefabricated houses india
prefabricated houses indiaprefabricated houses india
prefabricated houses india
 
Bamboo Prefabricated Housing
Bamboo Prefabricated HousingBamboo Prefabricated Housing
Bamboo Prefabricated Housing
 
Bc open pre fabricated construction system
Bc open pre fabricated construction systemBc open pre fabricated construction system
Bc open pre fabricated construction system
 
Prefabricated structures
Prefabricated structuresPrefabricated structures
Prefabricated structures
 
Introduction of Prefabricated structures
Introduction  of Prefabricated structuresIntroduction  of Prefabricated structures
Introduction of Prefabricated structures
 
Spaceframe and prefabrication
Spaceframe and prefabricationSpaceframe and prefabrication
Spaceframe and prefabrication
 
Prefabrication for improving Sustainability and Economics of Civil Engineerin...
Prefabrication for improving Sustainability and Economics of Civil Engineerin...Prefabrication for improving Sustainability and Economics of Civil Engineerin...
Prefabrication for improving Sustainability and Economics of Civil Engineerin...
 
Prefabrication
PrefabricationPrefabrication
Prefabrication
 
Prefabrication types and Applications explained
Prefabrication types and Applications explainedPrefabrication types and Applications explained
Prefabrication types and Applications explained
 
PREFABRICATED STRUCTURES
PREFABRICATED STRUCTURESPREFABRICATED STRUCTURES
PREFABRICATED STRUCTURES
 
Prefabricated structure
Prefabricated structurePrefabricated structure
Prefabricated structure
 
Prefabrication
PrefabricationPrefabrication
Prefabrication
 
Prefabricated structures
Prefabricated structuresPrefabricated structures
Prefabricated structures
 

Ähnlich wie Types of Prefabricated Modular Data Centers

vivektraining-131212145311-phpapp01.pdf
vivektraining-131212145311-phpapp01.pdfvivektraining-131212145311-phpapp01.pdf
vivektraining-131212145311-phpapp01.pdfssuser4f7e3f
 
vivektraining-131212145311-phpapp01.pptx
vivektraining-131212145311-phpapp01.pptxvivektraining-131212145311-phpapp01.pptx
vivektraining-131212145311-phpapp01.pptxJosephDanquah6
 
Research Paper  Find a peer reviewed article in the following d.docx
Research Paper  Find a peer reviewed article in the following d.docxResearch Paper  Find a peer reviewed article in the following d.docx
Research Paper  Find a peer reviewed article in the following d.docxeleanorg1
 
Research Paper  Find a peer reviewed article in the following dat.docx
Research Paper  Find a peer reviewed article in the following dat.docxResearch Paper  Find a peer reviewed article in the following dat.docx
Research Paper  Find a peer reviewed article in the following dat.docxaudeleypearl
 
Datacenter 2014: Schneider Electric A/S - Jørgen Bjerg
Datacenter 2014: Schneider Electric A/S - Jørgen BjergDatacenter 2014: Schneider Electric A/S - Jørgen Bjerg
Datacenter 2014: Schneider Electric A/S - Jørgen BjergMediehuset Ingeniøren Live
 
Competitive Strategies Benchmarking in Datacenter Infra Industry
Competitive Strategies Benchmarking in Datacenter Infra IndustryCompetitive Strategies Benchmarking in Datacenter Infra Industry
Competitive Strategies Benchmarking in Datacenter Infra IndustryAmit Singh
 
01 infra ti o que e um data center
01 infra ti o que e um data center01 infra ti o que e um data center
01 infra ti o que e um data centerClaudiney Silva
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
Data Centric Networking SRMIST unit 1 ppt
Data Centric Networking SRMIST unit 1 pptData Centric Networking SRMIST unit 1 ppt
Data Centric Networking SRMIST unit 1 pptak5806
 
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESglenioleonel
 
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESglenioleonel
 
Primer for what is and why modularity in Internet Data Center
Primer for what is and why modularity in Internet Data CenterPrimer for what is and why modularity in Internet Data Center
Primer for what is and why modularity in Internet Data CenterMehmet Cetin
 
DATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEY
DATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEYDATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEY
DATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEYIJCSEA Journal
 

Ähnlich wie Types of Prefabricated Modular Data Centers (20)

vivektraining-131212145311-phpapp01.pdf
vivektraining-131212145311-phpapp01.pdfvivektraining-131212145311-phpapp01.pdf
vivektraining-131212145311-phpapp01.pdf
 
vivektraining-131212145311-phpapp01.pptx
vivektraining-131212145311-phpapp01.pptxvivektraining-131212145311-phpapp01.pptx
vivektraining-131212145311-phpapp01.pptx
 
Data center
Data centerData center
Data center
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
Research Paper  Find a peer reviewed article in the following d.docx
Research Paper  Find a peer reviewed article in the following d.docxResearch Paper  Find a peer reviewed article in the following d.docx
Research Paper  Find a peer reviewed article in the following d.docx
 
Research Paper  Find a peer reviewed article in the following dat.docx
Research Paper  Find a peer reviewed article in the following dat.docxResearch Paper  Find a peer reviewed article in the following dat.docx
Research Paper  Find a peer reviewed article in the following dat.docx
 
Datacenter 2014: Schneider Electric A/S - Jørgen Bjerg
Datacenter 2014: Schneider Electric A/S - Jørgen BjergDatacenter 2014: Schneider Electric A/S - Jørgen Bjerg
Datacenter 2014: Schneider Electric A/S - Jørgen Bjerg
 
The New Approach to Retrofitting
The New Approach to RetrofittingThe New Approach to Retrofitting
The New Approach to Retrofitting
 
Competitive Strategies Benchmarking in Datacenter Infra Industry
Competitive Strategies Benchmarking in Datacenter Infra IndustryCompetitive Strategies Benchmarking in Datacenter Infra Industry
Competitive Strategies Benchmarking in Datacenter Infra Industry
 
01 infra ti o que e um data center
01 infra ti o que e um data center01 infra ti o que e um data center
01 infra ti o que e um data center
 
Data center m&e
Data center  m&eData center  m&e
Data center m&e
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Build Energy Saving into Your Datacenter
Build Energy Saving into Your DatacenterBuild Energy Saving into Your Datacenter
Build Energy Saving into Your Datacenter
 
Data Center
Data CenterData Center
Data Center
 
Data Centric Networking SRMIST unit 1 ppt
Data Centric Networking SRMIST unit 1 pptData Centric Networking SRMIST unit 1 ppt
Data Centric Networking SRMIST unit 1 ppt
 
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
 
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
 
Cloud & Data Center Networking
Cloud & Data Center NetworkingCloud & Data Center Networking
Cloud & Data Center Networking
 
Primer for what is and why modularity in Internet Data Center
Primer for what is and why modularity in Internet Data CenterPrimer for what is and why modularity in Internet Data Center
Primer for what is and why modularity in Internet Data Center
 
DATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEY
DATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEYDATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEY
DATACENTRE TOTAL COST OF OWNERSHIP (TCO) MODELS: A SURVEY
 

Mehr von Schneider Electric

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design ConsiderationsSchneider Electric
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsSchneider Electric
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing Schneider Electric
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsSchneider Electric
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service ProvidersSchneider Electric
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingSchneider Electric
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSchneider Electric
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingSchneider Electric
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingSchneider Electric
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Schneider Electric
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesSchneider Electric
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Schneider Electric
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.Schneider Electric
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...Schneider Electric
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTSchneider Electric
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingSchneider Electric
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingSchneider Electric
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingSchneider Electric
 

Mehr von Schneider Electric (20)

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service Providers
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
 

Kürzlich hochgeladen

Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationRadu Cotescu
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Paola De la Torre
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024The Digital Insurer
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure servicePooja Nehwal
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonAnna Loughnan Colquhoun
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024The Digital Insurer
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...Martijn de Jong
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024The Digital Insurer
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processorsdebabhi2
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Scriptwesley chun
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking MenDelhi Call girls
 
Developing An App To Navigate The Roads of Brazil
Developing An App To Navigate The Roads of BrazilDeveloping An App To Navigate The Roads of Brazil
Developing An App To Navigate The Roads of BrazilV3cube
 

Kürzlich hochgeladen (20)

Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Script
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 
Developing An App To Navigate The Roads of Brazil
Developing An App To Navigate The Roads of BrazilDeveloping An App To Navigate The Roads of Brazil
Developing An App To Navigate The Roads of Brazil
 

Types of Prefabricated Modular Data Centers

  • 1. Types of P refabricat ed Modular Data Centers White Paper 165 Revision 0 by Wendy Torell Executive summary Data center systems or subsystems that are pre-assembled in a factory are often described with terms like prefabricated, containerized, modular, skid-based, pod-based, mobile, portable, self-contained, all-in-one, and more. There are, however, important distinc-tions between the various types of factory-built building blocks on the market. This paper proposes standard terminology for categorizing the types of prefabricated modular data centers, defines and compares their key attributes, and provides a frame-work for choosing the best approach(es) based on business requirements. by Schneider Electric White Papers are now part of the Schneider Electric white paper library produced by Schneider Electric’s Data Center Science Center DCSC@Schneider-Electric.com
  • 2. Types of Prefabricated Modular Data Centers Many terms, with varying definitions and scopes, have been used to describe data center systems or subsystems that are pre-assembled in a factory. A partial list includes: • Containerized • Self-contained • Modular • Prefabricated • Portable • Mobile • Pod (based) • Skid (based) These terms create confusion and lead to dysfunctional discussions because they overlap and are ambiguous in meaning. A prefabricated modular data center is defined here in this paper as a data center that is: 1. made up of at least one pre-engineered, factory-integrated, and pre-tested assembly of subsystems that have traditionally been installed separately onsite 2. mounted on a skid or in an enclosure While the benefits of this type of approach to data centers is well-documented (such as in White Paper 163, Prefabricated Power and Cooling Modules for Data Centers), the lack of a common language and classification system has resulted in confusion over the differences in attributes and applications between them. This white paper presents a framework for classifying the different types of prefabricated modular data centers, based on three attributes, so that ambiguity is eliminated. Definitions and categories are presented, along with guidance for choosing the right approach(es) for given business requirements. Figure 1 illustrates the three attributes that, together, define the majority of prefabricated modular data centers. • Power • Cooling • IT Functional block • ISO container • Enclosure (non-ISO) • Skid-mounted Form factor • Fully prefabricated data center • Semi-prefabricated data center • All-in-one data center Configuration Schneider Electric – Data Center Science Center Rev 0 2 Introduction Figure 1 Framework for types of prefabricated data centers
  • 3. Types of Prefabricated Modular Data Centers Pre-engineered vs. Prefabricated data centers The terms pre-engineered and prefabricat-ed are sometimes used interchangeably, however there are important distinctions between the two. A data center that is pre-engineered is designed to meet pre-determined perfor-mance specifications, and consists of, at minimum, a documented list of materials, system level specifications, and drawings of the integrated system. A prefabricated data center is a data center that is pre-engineered and has its systems (hardware & software) pre-assembled, integrated, and tested in a factory environment to shorten deployment timeframe and improve predictability of performance. A reference design is an example of a system that is pre-engineered but not necessarily prefabricated. A power or cooling facility module is an example of a prefabricated system. One reason modular data centers are segmented by functional block is because data centers may only require a specific resource (just power, just cooling) due to stranded capacity in their existing facility. Another is because different personnel with different skill sets are needed to operate and maintain each (i.e. facilities staff vs. IT staff, mechanical operators vs. electrical operators). And yet another has to do with the physical constraint of the module’s foot print. Form factor is the second key attribute that distinguishes prefabricated solutions. A form factor may be chosen based on the application (i.e. a data center may be required to be permanently mobile – on wheels – to meet a business need); or it may be constrained by its capacity (i.e. a power system in an ISO enclosure is generally limited to around 500 kW, but a skid-mounted design can support greater capacities). The prefabricated functional blocks are deployed in various configurations. Some prefabricated data centers include a mix of prefabricated modules and traditional or “stick built” systems (such as modular power and cooling with traditional IT space). Others are fully prefabricated, meaning all three functional blocks – power, cooling, and IT – are prefabricated. Lastly, a specific configuration of a fully prefabricated data center is an “all-in-one”, where the power, cooling, and IT co-exist in a single enclosure. The three attributes – functional block, form factor, and configuration – are further defined and explained in the following sections. The functions of a data center can be broken down into three major categories – the power plant, the cooling plant, and the IT space. Prefabricated data center modules sometimes provide multiple functions (referred to as all-in-one configurations), but often they provide one function of the data center, for the following reasons: • A prefabricated module may be needed only for a specific resource (just power, just cooling, or just IT space) because of stranded capacity in their existing facility • A greater IT capacity is needed than what an all-in-one module can support, and a single IT space is required (physical space constraint of modules) • There is a requirement to separate personnel (IT, mechanical, electrical) from a maintenance and operations perspective to reduce human error risks • An optimized footprint is needed, and function-specific modules can utilize larger ca-pacity components and share clearances to provide a greater kW per square foot or square meter Power A prefabricated power module (see Figure 2) is designed to provide bulk power to the data center. It may power a modular IT space or a traditional IT space within a building. The typical subsystems within a power facility module are switchgear / switchboards, ATS, UPSs with batteries, transformers, and panelboards. In addition, support systems such as lighting, security, cooling may exist in the module for enclosed form factors. Standby generators are generally a separate module that can be integrated with the power module. Schneider Electric – Data Center Science Center Rev 0 3 Functional block
  • 4. Types of Prefabricated Modular Data Centers Cooling Today’s data centers use a range of cooling architectures to support the IT space, based on requirements for cost, efficiency, reliability, etc. The physical location (climate) of the data center is also a big driver when determining the optimal approach. Schneider Electric’s TradeOff Tool, Cooling Economizer mode PUE Calculator, helps illustrate the energy tradeoffs of the various architectures, and white paper 59, The Different Technologies for Cooling Data Centers, provides further details on the different cooling approaches. At a high level, the typical subsystems within prefabricated cooling modules are shown in Table 1. Chiller plant module DX plant module Indirect air module Direct air module • Air cooled chiller • Pumps / drives • Storage tank • Dry cooler / evaporative cooler • Air cooled condenser or dry cooler • Pump package • Air-to-air heat exchanger • Evaporative cooling • DX backup • Fans • Ducts • Air filters • Evaporative cooling • DX backup • Fans • Ducts Figure 3 illustrates a hydronics module consisting of pumps, VFDs, management, and connections for an air cooled chiller modular design. IT Space A prefabricated IT space is one that houses the IT equipment. It also houses the support infrastructure to distribute power and air to those systems, as well as provides a suitable work environment for the IT staff that must operate the space. Typically, such a module incorpo-rates the following subsystems: • IT racks to hold the IT equipment • Power distribution units (PDUs) • Rack PDUs • Air distribution system (CRAHs, CRACs, air ducts, depending on architecture) • Humidification / dehumidification system Schneider Electric – Data Center Science Center Rev 0 4 Figure 2 Example of a “Power” functional block Table 1 Typical subsystems within prefabricated cooling modules Figure 3 Example of a “Cooling” functional block
  • 5. Types of Prefabricated Modular Data Centers • Cabling infrastructure / cable management • Fire detection / protection • Lights • Security systems In addition to having the systems pre-engineered and integrated, having the IT equipment in a module provides the added benefit of being a form of containment, to separate the hot and cold air streams, which is critical to effective and efficient air distribution. Figure 4 is an example of an IT space module consisting of 10 IT racks and the supporting systems, but other form factors exist that increase the rack capacity. The following is a general rule of thumb when it comes to the cost effectiveness of IT space modules: The greater the IT density per rack, the more sensible IT space modules are, due to the increase in capacity of each module Prefabricated data centers can take on different form factors – meaning the type of structure, the size, and shape. The form of a particular solution impacts the transportability of it, the placement of it, and its location (inside vs. outside on the ground vs. on a rooftop). The three general forms of prefabricated data center modules are: • ISO container • Enclosure • Skid-mounted Which form factor or combination of form factors is suitable for a given data center project is based on requirements such as transportability, capacity, scalability, etc. Table 2 summariz-es how each compares in terms of location, placement, and transportation. In addition, the form of the module impacts the capacity of the module, since the specific dimensions of the module constrain the equipment that fits within it. There may also be permitting and tax implications in certain geographies. These and other attributes are further described in the following sections along with examples to illustrate the form factors. Schneider Electric – Data Center Science Center Rev 0 5 Figure 4 Example of an “IT Space” functional block Form factor
  • 6. Types of Prefabricated Modular Data Centers Location Placement Transportation ISO container Generally, outdoors Mount on concrete pad or other founda-tion Standard dimensions; from ship to rail to truck Enclosure May be placed indoors or outdoors, de-pending on weather rating & application May ship in parts that require assembly onsite; Mount on concrete pad or other foundation Shipping preparations may be required if in parts; Delivery may require permits, escorts depending on width Skid-mounted Generally, indoors Often placed directly on room floor Shipping preparations required; Delivery may require permits, escorts depending on width ISO container ISO containers are standardized re-usable steel shipping enclosures, designed for safe, efficient, and secure storage and movement of materials from one from of transportation to another (i.e. ship to rail to truck). There are a number of ISO standards that regulate many aspects of freight containers from the classification, dimensions, to corner fitting specifica-tions, to hooks for lifting the containers, to the markings/identification on the container.1 These standards make transportation and handling simpler and standardized. Standard footprints of these containers for use as data center modules are: 20 ft x 8 ft (6.10 m x 2.44 m) and 40 ft x 8 ft (12.2 m x 2.44 m). The 20 ft (6.10 m) containers come in a standard height of 8 ft 6 in (2.591 m), and the 40 ft (12.2 m) containers come in either the standard height of 8 ft 6 in (2.591 m) or the “high bay” height of 9 ft 6 in (2.896 m). Generally, the high bay containers are used, as they provide greater flexibility for equipment placement within the module. Often times, when containers are used as the shell for data center modules, they are modified in the following ways: • Cut-outs for doors and other mounted equipment • Equipment installed that hangs off the side or top of container With these types of modifications, the container may no longer be ISO certified, for example, limiting its ability to be stacked with other containers. However, having the standard footprint of an ISO container makes it simpler to transport, lift, and place than non-standard footprints which tends to reduce installation costs. It is also generally lower in cost to modify a standard shell than to construct one from the ground up. ISO container modules generally have a practical limit on capacity of around 500 kW for power or cooling plants, and around 200 - 250 kW for an IT space. The IT module capacity constraint is based on the number of IT racks that can fit within the footprint, and there are space tradeoffs with different rack arrangements. For example, if the racks are placed along the back wall to provide a wide cold aisle, the hot aisle may only be accessible through panels or doors from the outside. If the IT racks are placed as a long row in the center, the 1 http://www.container-transportation.com/iso-container-standards.html (accessed 9/18/2013) Schneider Electric – Data Center Science Center Rev 0 6 Table 2 Typical form factors “Mobile” modules Mobility is a benefit of all prefabricated module form factors, with ISO containers providing the best transportabil-ity; however sometimes a module is designed to be permanently mobile, meaning it is designed in a structure that includes wheels and axles. These permanently mobile modules are often built as all-in-one modules that are used for temporary data center needs such as military applications or sporting events. The figure below illustrates two examples:
  • 7. Types of Prefabricated Modular Data Centers hot and cold aisle must be narrower. Lastly, if multiple short aisles are used perpendicular to the length of the container, a narrow aisle will be likely to move from row to row. In general, the capacity constraint of the IT modules make them more suitable for smaller data centers. Larger capacity needs would generally steer towards more traditional IT spaces. Often times, this form factor requires lighting and security, since they are accessed by personnel for operation and maintenance. Placement of ISO containers usually involves laying slab on grade (concrete pad) outdoors. A crane would be used to lift the container off the truck and onto the pad. When used to supplement capacity in a constrained existing brick and mortar facility, the container(s) are generally placed in close proximity to the perimeter of the building, near the data center they are supporting. Sometimes, a power or IT container is placed indoors in a warehouse environment – in order to protect the personnel from inclement weather during operation & maintenance activities, and to provide added security for their critical systems. Figure 5 illustrates a power module and a cooling module, both designed with ISO containers and modified to meet the system requirements. Enclosure Another form factor, in this paper referred to as “enclosure”, is less standard in terms of its dimensions, and therefore does not necessarily meet specific shipping standards like the ISO containers. Enclosures are also commonly referred to as shells, metal houses, and pods. Relative to ISO containers, transporting and handling costs may be greater; and onsite work may be greater if the structure isn’t fully assembled in the factory. For example, a wide enclosure may come in two sections, as Figure 6 illustrates. Some enclosures, often referred to as modular rooms, are actually constructed in a factory, integrated with the data center equipment, tested and commissioned, and then disassembled and put back together at the customer site, much like a Lego building block kit. The benefit of this form factor is that it offers more flexibility in terms of the IT capacity it can support as well as the layout of the equipment within the enclosure. The majority of enclosures are rated for outdoor use and can be exposed to varying weather conditions, but there are some that are not, and should be installed indoors (i.e. inside a warehouse). Even ones that are rated for outdoor conditions may at times be installed indoors for reasons like security, personnel access, or shelter from inclement weather as personnel carry equipment (e.g. servers) to an enclosure. Some enclosures are rooms Schneider Electric – Data Center Science Center Rev 0 7 Figure 5 Examples of ISO container form factor Figure 6 Examples of an IT space enclosure that ships in 2 parts
  • 8. Types of Prefabricated Modular Data Centers where personnel can walk into them2, for maintenance and operation, while others would be better described as enclosed “systems”, where the primary access for personnel is through access panels on the outside of the enclosure (non-walk-in type). Table 3 summarizes this further categorization of enclosures and provides examples of each. Personnel accessibility Indoor / outdoor rating Indoor, enclosed “system” • Non-weather proof • Personnel access only through access panels on outside of enclosure Indoor, walk-in enclosure • Non-weather proof • Personnel have full access within enclosure Outdoor, enclosed “system” • Weather proof for outdoors • Personnel access only through access panels on outside of enclosure Outdoor, walk-in enclosure • Weather proof for outdoors • Personnel have full access within enclosure A key driver for choosing an enclosed form factor is the need for the data center subsystems to go outside, or be protected from other elements such as in a hazardous, rugged, or adverse indoor environment. Enclosures that are placed outdoors should have an appropri-ate level of security to prevent undesirable access (i.e. vandalizing). Skid-mounted “A skid mount is a method of distributing and storing machinery where the machinery at point of manufacture is permanently mounted in a frame or onto rails or a metal pallet. The equipment can then be easily and securely transported as and used as a unit.”3 Figure 7 illustrates examples of skid-mounted data center modules. Skid-mounted modules are generally not designed for outdoor use, as components are unprotected from the outdoor elements. Power modules are often in this form factor, as items like switchgear, UPS, transformers, and panelboards don’t have a requirement to be outdoors 2 An enclosure designed for personnel occupancy, such as the one in Figure 6 must have lighting, fire protection, security, and a means of egress. 3 http://en.wikipedia.org/wiki/Skid_mount Schneider Electric – Data Center Science Center Rev 0 8 Table 3 Categories of enclosures and examples Figure 7 Examples of skid-mounted form factors for modular data centers X (No practical examples)
  • 9. Types of Prefabricated Modular Data Centers like many cooling modules do. There are also fewer capacity constraints due to footprint limitations with skid-mounted power modules (vs. enclosures or ISO containers), enabling them to support greater capacity data centers. So, as the power requirement increases, the skid-mounted approach becomes more sensible. In general, the cost of a prefabricated skid-mounted module is less than the equivalent enclosure design, often by up to 40% less. Note – skid-mounted systems for IT spaces are not logical because it leaves the equipment open to the space rather than separating hot and cold air from the IT equipment. There are several ways the functional blocks can be implemented in a data center. These approaches fall under three main categories: • Semi-prefabricated – A data center comprised of a combination of prefabricated functional blocks and traditional “stick built” systems • Fully prefabricated – A data center comprised completely of prefabricated IT, power, and cooling modules • All-in-one – A data center that is self-contained in a single enclosure, with IT, power, and cooling systems In this section, each configuration is explained, illustrated examples shown, and typical scenarios when each would be deployed are described. Common across all of the configura-tions is the need to deploy the data center in weeks rather than months or years, the ability to scale the data center if or when needed, and the desire for improved predictability of perfor-mance. There are also specific requirements (i.e. around space or cash flow or speed) that also influence the decision. Semi-prefabricated data centers A common deployment of prefabricated data centers consists of a mix of prefabricated modules and traditional “stick built” systems. This approach is referred to as “semi-prefabricated”. Figure 8 illustrates an example, where power and cooling modules support a traditional IT space within a building. Other combinations are possible as well, such as a traditional power and cooling plants with IT space modules outside. The specific combination of prefabricated and traditional systems deployed depends on the application and need of the data center. A retrofit project, where a particular resource is capacity constrained, is a common situation where this configuration would be deployed. Schneider Electric – Data Center Science Center Rev 0 9 Configuration Figure 8 Example of semi-prefabricated data center with prefabricated power and cooling modules and traditional IT space
  • 10. Types of Prefabricated Modular Data Centers Semi-prefabricated data centers are generally implemented when: • An existing data center is out of bulk power capacity and is space constrained in the electrical room, but IT space is available for growth • An existing data center is out of bulk cooling (heat rejection) capacity, but IT space is available for growth • An existing data center is out of IT space due to a deployed density that was lower than the design density, and there’s plenty of bulk power and cooling capacity • A new enterprise-class data center has a mixed IT environment, which limits the appli-cation of IT modules, but power and cooling modules can be deployed • A short-term plan is desired to address a gap in capacity and/or reliability until a long-term plan is implemented (at which time the modules would be re-purposed) Fully prefabricated data centers In a fully prefabricated data center, modules are implemented for all three functional blocks – providing the bulk power to the data center, providing heat rejection for the data center, and housing the critical IT equipment. Figure 9 illustrates two examples of fully prefabricated data centers and how the modules may be laid out on the grounds. Deployments vary in form factor, power capacity, technology, and placement (inside or outside), based on the business requirements. Fully prefabricated data centers are generally implemented when: • Scalability of the entire data center is a key business driver • A multi-tenant data center wants to partition IT spaces by tenant, and requires scalabil-ity of power and cooling resources • A large scale homogenous IT data center wants to deploy equipment in a step and repeat manner • A high density, high performance computing data center deploys thousands of servers repetitively and wants to scale capacity as the servers scale • A large disaster recovery data center is needed Schneider Electric – Data Center Science Center Rev 0 10 Figure 9 Example layouts of fully prefabricated data centers, based on Schnei-der Electric reference designs
  • 11. Types of Prefabricated Modular Data Centers All-in-one data centers An all-in-one data center is really a specific type of fully prefabricated data center, but is being highlighted as a separate configuration because of its unique characteristic of having the components co-located in a single structure. Figure 10 is an example of an all-in-one design. When multiple functions are combined into a single module, the capacity is generally more limited. A typical limit to an all-in-one (power, cooling, and IT) is approximately 150 kW in a single module such as an ISO container footprint. This limit is higher for modules that arrive in sections and snap together in the field. Beyond 2 or 3 all-in-one modules on a site (approximately 500 kW), all-in-ones are cost prohibitive. Although these configurations are referred to as “all-in-one”, there is often some additional support infrastructure outside of the module, such as the generator or chiller. And yet another variation may exist where only the IT and cooling is combined in a single enclosure, and the UPS is located in a separate module. This is common for fresh air cooling designs, where the IT space is adapted to allow either the fresh air directly in, or with air-to-air heat exchangers to indirectly cool the space. All-in-one prefabricated data centers are generally implemented when: • A temporary need exists such as for military use, sporting or other temporary event • Mobility of the data center is important • A remote branch site requires a small data center, less than 150 kW • A small data center is in a mixed-use facility and desires ownership and control of all functions • A data center will be located in a harsh environment like an industrial application, an oil rig, etc. • A small disaster recovery data center is needed Schneider Electric – Data Center Science Center Rev 0 11 Figure 10 Example of all-in-one prefabricated data center
  • 12. Types of Prefabricated Modular Data Centers There are many approaches to implementing prefabricated modular data centers; however, a lack of standard terminology for describing them has made selecting the appropriate type difficult. The optimal configuration, including the right functional blocks and form factors depends on the application and specific business requirements. In some cases, a fully prefabricated data center is the best approach, and for others, a semi-prefabricated approach with a mix of prefabricated modules and traditional systems is best. Understanding the limitations and benefits of each form factor helps ensure the optimal approach is selected. Ultimately, business needs around speed of deployment, scalability, space constraints, capacity, and cash flow drive the decision. About the author Schneider Electric – Data Center Science Center Rev 0 12 Conclusion Wendy Torell is a Senior Research Analyst at Schneider Electric’s Data Center Science Center. In this role, she researches best practices in data center design and operation, publishes white papers & articles, and develops TradeOff Tools to help clients optimize the availability, efficiency, and cost of their data center environments. She also consults with clients on availability science approaches and design practices to help them meet their data center performance objectives. She received her Bachelors of Mechanical Engineering degree from Union College in Schenectady, NY and her MBA from University of Rhode Island. Wendy is an ASQ Certified Reliability Engineer.
  • 13. Types of Prefabricated Modular Data Centers Prefabricated Power and Cooling Modules for Data Centers White Paper 163 TCO Analysis of a Traditional Data Center vs. a Scalable, Prefabricated Data Center White Paper 164 Specification of Modular Data Center Architecture White Paper 160 Practical Considerations for Implementing Prefabricated Data Centers White Paper 166 Prefabricated vs. Traditional Data Center Cost Calculator TradeOff Tool 17 Browse all TradeOff Tools™ Contact us Schneider Electric – Data Center Science Center Rev 0 13 Resources Browse all white papers whitepapers.apc.com tools.apc.com © 2014 Schneider Electric. All rights reserved. For feedback and comments about the content of this white paper: Data Center Science Center dcsc@schneider-electric.com If you are a customer and have questions specific to your data center project: Contact your Schneider Electric representative at www.apc.com/support/contact/index.cfm